NAPCO GEM-, MA3000, Signature 5500, SS-P, GEM-EZM4 Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS
GEM-EZM4, GEM-EZM8GEM-EZM4, GEM-EZM8
ZONE EXPANSION MODULESZONE EXPANSION MODULES
NAPCO SECURITY SYSTEMS, INC.
333 BAYVIEW AVENUE
AMITYVILLE, NEW YORK 11701
SALES, REPAIRS & TECHNICAL SERVICE
TOLL FREE: (800) 645-9445
TECHNICAL SERVICE DIRECT LINE
TOLL FREE: (800) 645-9440
© Napco 1997 WI583C 2/97
DESCRIPTIONDESCRIPTION
The capacity of the MA3000, GEM-Series and Signature 5500 and SS-P Series control panels may be expanded through the use of GEM-EZM zone expansion modules. GEM-EZM4 modules provide up to four additional zones; GEM-EZM8 modules, up to 8 additional zones. Four-zone and 8-zone modules may be combined as necessary to supply the required number of zones. Refer to the installa­tion instructions for the control panel in use for wiring requirements for UL-listed applications.
WIRINGWIRING
Wire the expansion zones to the module and the module to the control panel in accordance with the wiring diagrams using wire no thinner than #22AWG. Install end-of-line resistors on all zones even if one or more zones are not used.
Note:Note: The addition of Zone Expansion Modules will re­duce the amount of current available at the control panel’s Auxiliary Power Output terminals.
MODULE ASSIGNMENTMODULE ASSIGNMENT
Regardless of how the modules are arranged, the expan­sion zones are divided into consecutively-numbered groups of four. Each 4-zone module comprises one group of zones; each 8-zone module comprises two groups.
Every module must be assigned a unique ‘‘base address’’. In the case of a 4-zone module, the base address number is the same as its group number. For the 8-zone module, the base address number will be the lower of its two group numbers. Note that (a) groups must be numbered con­secutively (that is, missing numbers are not permitted); and (b) no two modules may be numbered alike.
Example. Two GEM-EZM8s and one GEM-EZM4 are used to provide 20 expansion zones:
Groups 1 & 2 Group 3 Groups 4 & 5 GEM-EZM8GEM-EZM8 GEM-EZM4GEM-EZM4 GEM-EZM8GEM-EZM8
Base Addr ‘‘1’’ Base Addr ‘‘3’’ Base Addr ‘‘4’’
The base address is assigned to the module by proper selection of Address Jumpers JP1-JP5 (to the right of the LED) in accordance with Table 1. Also refer to the Zone Wiring Diagram.
for MA3000, GEM-Series,for MA3000, GEM-Series,
Signature S5500 & SS-P SeriesSignature S5500 & SS-P Series
Control PanelsControl Panels
BaseBase
AddressAddress
1 ON ON ON ON OFF 2 ON ON ON OFF ON 3 ON ON ON OFF OFF 4 ON ON OFF ON ON 5 ON ON OFF ON OFF 6 ON ON OFF OFF ON 7 ON ON OFF OFF OFF 8 ON OFF ON ON ON
9 ON OFF ON ON OFF 10 ON OFF ON OFF ON 11 ON OFF ON OFF OFF 12 ON OFF OFF ON ON 13 ON OFF OFF ON OFF 14 ON OFF OFF OFF ON 15 ON OFF OFF OFF OFF 16 OFF ON ON ON ON 17 OFF ON ON ON OFF 18 OFF ON ON OFF ON 19 OFF ON ON OFF OFF 20 OFF ON OFF ON ON 21 OFF ON OFF ON OFF 22 OFF ON OFF OFF ON
Table 1. Jumper emplacement as a function of Base Address.Table 1. Jumper emplacement as a function of Base Address.
Shaded area is not applicable to GEM-P3200 or SS-P3200.Shaded area is not applicable to GEM-P3200 or SS-P3200.
JP5JP5 JP4JP4 JP3JP3 JP2JP2 JP1JP1
PROGRAMMINGPROGRAMMING
The control panel must be programmed with regard to the modules (4-zone or 8-zone) in use. Referring to the respective Programming Workbook, program EZM TYPE to enable the module. Starting in the first location and pro­ceeding in succession, program a ‘‘1’’ for each 4-zone group of expansion zones in the system. For example, if one GEM-EZM8 is used for Zones 9 through 16 (two groups of 4), program a ‘‘1’’ in the first and second locations (right ‘‘nibble’’). Similarly, if an GEM-EZM4 is used for Zones 17 through 20 (1 group), program a ‘‘1’’ in the third location (right ‘‘nibble’’). Thus, each GEM-EZM4 will require a ‘‘1’’ in only one location whereas each GEM-EZM8 will require a
Address JumpersAddress Jumpers
‘‘1’’ in two consecutive locations.
ING for other indications.
TAMPERTAMPER
If the cover is removed, the keypad sounder will pulse and the display will indicate a zone-module tamper condition along with the module number. Press [RESET] to silence the sounder.
LOOP RESPONSELOOP RESPONSE
Loop response times for Zones 1 through 8 are pro­grammed in the control panel. Normal loop response for all expansion zones is 750mS. To reduce the response time of an expansion zone to 50mS, cut the respective resistor at the upper-left corner of the board. Refer to the Wiring Diagram.
STATUS LEDSTATUS LED
The Status LED displays the condition of the zone mod­ule. The LED will blink every few seconds to indicate that each 4-zone group is operating normally. The LED in the 4-zone module will blink once; the LED in the 8-zone module will blink once for the first group, then double-blink shortly thereafter for the second. See TROUBLESHOOT-
WIRING DIAGRAMSWIRING DIAGRAMS
PGM TERMINALPGM TERMINAL
The PGM terminal (Terminal 6) will go low when the area is armed. This terminal may be used to light an LED or trip auxiliary equipment. Note:Note: This terminal is programmed in the control panel; it may be selected to trip when any one area is armed (not necessarily its own). Refer to the instal­lation instructions for the control panel for programmable options.
4Z/8Z ZONE JUMPER4Z/8Z ZONE JUMPER
To convert an 8-zone module for use with only 4-zones, remove the jumper just below the large microprocessor IC on the circuit board.
TROUBLESHOOTINGTROUBLESHOOTING
A steady Status LED is most likely caused by loss of
data reception from the control panel at the module’s Terminal 3.
No illumination is most likely due to a loss of power at
Terminals 1 and/or 2.
22
Zone Wiring Diagram.Zone Wiring Diagram.
System Wiring Diagram.System Wiring Diagram.
NOTESNOTES
33
NAPCO LIMITED WARRANTYNAPCO LIMITED WARRANTY
NAPCO SECURITY SYSTEMS, INC. (NAPCO) warrants its prod­ucts to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufac­ture. NAPCO will, within said period, at its option, repair or replace any product failing to operate correctly without charge to the original purchaser or user.
This warranty shall not apply to any equipment, or any part thereof, which has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to acts of God, or on which any serial numbers have been altered, defaced or removed. Seller will not be responsible for any dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. THERE IS NO EXPRESS OR IMPLIED WARRANTY OF MERCHANT­ABILITY OR A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. ADDITIONALLY, THIS WARRANTY IS IN LIEU OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF NAPCO.
Any action for breach of warranty, including but not limited to any implied warranty of merchantability, must be brought within the six months following the end of the warranty period.
IN NO CASE SHALL NAPCO BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional who installed and maintains your security system. In order to exercise the warranty, the product must be returned by the security professional, shipping costs prepaid and insured to NAPCO. After repair or replacement, NAPCO assumes the cost of returning products under warranty. NAPCO shall have no obligation under this warranty, or otherwise, if the product has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to accident, nuisance, flood, fire or acts of God, or on which any serial numbers have been altered, defaced or removed. NAPCO will not be responsible for any dismantling, reassembly or reinstal­lation charges.
This warranty contains the entire warranty. It is the sole warranty and any prior agreements or representations, whether oral or written, are either merged herein or are expressly cancelled. NAPCO neither assumes, nor authorizes any other person purport-
ing to act on its behalf to modify, to change, or to assume for it, any other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in excess of NAPCO’s original selling price of the product, for any loss or damage, whether direct, indirect, incidental, consequential, or otherwise arising out of any failure of the product. Seller’s warranty, as hereinabove set forth, shall not be enlarged, diminished or affected by and no obligation or liability shall arise or grow out of Seller’s rendering of technical advice or service in connection with Buyer’s order of the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM BE COM­PLETELY TESTED WEEKLY.
Warning: Despite frequent testing, and due to, but not limited to, any or all of the following; criminal tampering, electrical or commu­nications disruption, it is possible for the system to fail to perform as expected. NAPCO does not represent that the product/system may not be compromised or circumvented; or that the product or system will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; nor that the product or system will in all cases provide adequate warning or protection. A properly installed and maintained alarm may only reduce risk of burglary, robbery, fire or otherwise but it is not insurance or a guarantee that these events will not occur. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. Therefore, the installer should in turn advise the con­sumer to take any and all precautions for his or her safety including, but not limited to, fleeing the premises and calling police or fire department, in order to mitigate the possibilities of harm and/or damage.
NAPCO is not an insurer of either the property or safety of the user’s family or employees, and limits its liability for any loss or damage including incidental or consequential damages to NAPCO’s original selling price of the product regardless of the cause of such loss or damage.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, or differentiate in their treatment of limitations of liability for ordinary or gross negligence, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Loading...