NAPCO FW-4, FW4-H, FW-2, FW2-H Installation Instruction

INSTALLATION INSTRUCTIONS
FW4-H and FW2-H
These installation instructions are for the FW-4, FW4-H, FW-2 and the FW2-H FIREWOLF Smoke Detectors.
CAUTION!!!
Install this and all life safety devices in accordance with applicable NFPA standards, local codes, and the au­thorities having jurisdiction. Failure to follow these in­structions may result in failure of the detector to initiate an alarm condition. Napco Security Systems, Inc. and the original equipment manufacturer, are not respon si­ble for detectors that have been improperly installed, tested, or maintained.
For testing and cleaning information, refer to these in­structions and/or call the NAPCO fax request line at (631) 842-3291. Also refer to NFPA-72 Chapter 5 for Automatic Fire Detectors for installation guidelines and Chapter 7 for testing and maintenance requirements.
Use “3M” Weatherban # 606 non-flammable sealing compound to seal field wiring conduit openings in the mounting back box. Compliance with this request may reduce the occurrence of the “STACK EFFECT”.
Box Mounting
Trim Ring 3” OCT 4” Oct
SPECIFICATIONS SMOKE DETECTOR DATA
Detector
Type of Detector
Working Voltage
Voltage
Waveform
Max. Alarm
Current
Max. Surge
FW-2 FW2-H FW-4 FW4-H
Photoelectric
(2 wire baseless)
8.0 - 35.0 VDC 8.0 - 35.0 VDC 8.0 - 35.0 VDC 8.0 - 35.0 VDC Filtered DC
15% ripple max.
Limit current to 150mA @ 35.0
VDC
200µA 200µA 200µA 200µA
Photoelectric
(2 wire baseless)
Filtered DC
15% ripple max.
Limit current to 150mA @ 35.0
VDC
Photoelectric
(4 wire baseless)
Filtered DC
15% ripple max.
55mA @ 35.0
VDC
Current
Average
Standby Current
Compatibility
38µA @ 12 VDC 55µA @ 24 VDC 70µA @ 35 VDC
HD-6 HD-6 N/A N/A
38µA @ 12 VDC 55µA @ 24 VDC 70µA @ 35 VDC
38µA @ 12 VDC 55µA @ 24 VDC 70µA @ 35 VDC
Identifier
Sensitivity Test
Feature NAPCO
Control Panel
Built-In Test
Feature
See Wiring
Diagram Below
Built-In Test
Feature
See Wiring
Diagram Below
Built-In Test
Feature
N/A N/A
Compatibility
Heat Element
N/A 135° F N/A 135° F
Rating
When mounting detector on a wall, it must be between 4” and 12” from the ceiling.
Note:
Photoelectric
(4 wire baseless)
Filtered DC
15% ripple max.
55 mA @ 35.0
VDC
38µA @ 12 VDC 55µA @ 24 VDC 70µA @ 35 VDC
Built-In Test
Feature
Wiring
: Connect wiring to the bases as shown in the wiring diagrams tha t follow. Detectors may be mixed on the same init iating
loop as long as the number of two-wire powered detectors does not exceed the specifications of the control panel. See Specification Table above.
CAUTION: Connect wiring to terminals as shown. Do not loop wire under terminals. Break wire run to provide supervision.
FW-4 Wiring Diagram
FW-2 Wiring Diagram
U.L. List ed
Control
Panel
U.L. List ed
Power
Supply
*24VDC
U.L. List ed
Power
Supply
*12VDC
* = Use 12 or 24VDC - CANNOT BE USED SIMULTANEOUSLY
U.L. LISTED
COMPATIBLE
CONTROL PANEL
LISTED
END-OF-LINE
DEVICE
LISTED
END-OF-LINE
RELAY
12 OR 24VDC
LISTED
END-OF-LINE
DEVICE
Compatible Control Panels:
FW-C2Z, FW-C4Z, FW-C4EZ GEM-P3200 GEM-P9600 GEM-P800, G EM-P801 GEM-P816, GEM-P1632 NAPCO Express XP600 MA3000
For cross listings with additional manufacturers and models pending,
Note:
contact the NAPCO Technical Support Department for the latest listings at (800) 645-9440. Also available online at www.napcosecurity.com (go to the Firewolf folder and download FW2_WI1009_ADDM).
Limiting to no more than 150mA
CAUTION
The FW-2 requires current
@ 35.0 VDC
Magnum Alert® is a Registered trademark of NAPCO. Gemini,™ Signature™ and NAPCO Express™ are Trademarks of NAPCO.
Napco Security Systems, Inc.
333 Bayview Avenue * Amityville, NY 11701 Phone: (800) 645-9445 (631) 842-9400 Fax: (631) 789-3383
®
R
To mount the FW- 4 and the FW-2 Basel es s Det ec tor Head to the Trim Rin g, d o th e foll o win g:
1. Place the Baseless Detector Head over the Trim Ring with its back towards the Trim Ring.
2. Place the detector with the Alignment Mark at Alignment Position 1 (see diagram).
3. Bring the detector together with the Trim Ring.
4. Turn the detector clockwise and when the Alignment Mark is at Alignment Position 2 the detector will have snapped into place (see diagram).
5. Refer to the diagram for visual reference to the alignment marks.
TESTING THE FW- 4 and the FW-2 INSTALLATION
For go/no-go testing, a magnet will be required.
1. Hold the magnet j ust UNDER the word “TEST” as shown on Diagram 2A.
2. The detector should alarm within 10 seconds (If control panel is programmed for
HOLD
MAGNET
HERE
Fire Alarm Verification, it may take up to 30 seconds).
3. The detector’s LEDs should be on Red continuously and any control panel indi­cating appliances should activate.
4. Silence the system and activate the control panel reset to reset smoke detector.
5. The smoke detector LEDs should flash Green.
DIAGRAM 2A
FIREWOLF SENSITIVITY TEST FEATURE and INSTALLATION VERIFICATION
Note: The FW- 4 and the FW-2 have a built-in automatic sensitivity test feature that will automatically indicate a change in sensitivity.
1. In normal condition bo th LEDs flash Green.
2. When the sensitivity drifts outside of its sensitivity limits, both LEDs flash Red (e.g., when the unit needs cleaning).
3. In the alarm state bo t h L EDs are on Red cont inuously.
4. When the condition exists as stated in 2 above, the device needs to be cleaned or returned to the factory for servicing. Refer to the follow­ing instructio ns for cleaning info rmation:
MANUAL CLEANING PROCEDURE
Tools you will need:
2 small screwdrivers (1/8” wide)
A small soft-bristled artist’s pai nt brush
Denatured alcohol
Clean dry compressed air.
Use only lint-free materials when cleaning the chambers of the photoelectric smoke detector. Use of fibrous materials may result in
NOTE:
DIAGRAM 2B
false alarms.
Remove and Disassemble the Detect or
Follow the steps in this section to prepare the detector for cleaning:
1. Remove the detector from the trim ring.
2. Disassemble det ector by placing o ne screwdriver under the tab as shown in Diagram 2B (above).
3. Then place the se cond screwdriver under the next adjacent TAB pushing it the direction show n in Diagram 2B.
4. Push the screwdri ver outward from the center of the detect or and lift the Enclosure upward.
5. Do the same with the second screwdriver, but do not remove it--keep it in place.
6. Ta ke the first screwdriver and place it under the third TAB adjacent to the second TAB. Push the TAB outward and lift the Enclosure upward.
7. With three tabs freed, the Enclosure will finally remove easily with the application of the screwdriver.
Clean the Detector
CAUTION: Do not attempt to remove the insect screen.
1. Remove the Outer Cover of the detector as specified and set aside.
2. Place the detector in the palm of your left hand and grasp the Chamber Cover with your right hand. Twist t he Chamber Cover counter-clockwise until the Cover Tabs clear the Tab Catches. Lift and separate the Cham ber Cover and Outer Cover from the Optical Unit.
3. Swab the Optical unit with denatured alcohol using a small soft-bristled brush.
4. Use dry clean compressed air to dry the optical unit and to remove any re­maining particles.
5. Clean the Chamber Cover and Outer Cover in the same manner.
Reassemble the Detector
1. Locate the Alignment Arrows on both the Chamber Cover and the Optical Unit.
2. Set the Chamber cover onto the Optical Unit while making sure that Alignment Arrow 1 and Ali gnment Arrow 2 are aligned with each another.
3. Holding the detector in your left hand and grasping the Chamber Cover with your right hand, rotate the Chamber Cover clockwise until the Cover Tabs snap into the Tab Catches.
4. Place the Outer Co ver of the detector nose down on a flat s urface.
5. Align the Outer Cover Nub with the Alignment Arrow on the enclosure (two Orien­tations are pos sible, only one will fit properly).
6. With the Outer Cover Nub aligned with the Alignment Arrow, press down firmly on the back of the detector. The dete ctor will s nap into the Outer C over. Th e de tec­tor is now ready to be returned to the Trim Ring from which it was removed.
7. The detector should be re-tested by performing the test procedure described in this document.
If after testing, the detector is not working within the prescribed limits, then
Note:
return it to the manufacturer for servicing.
© NAPCO 2004
WI 972C 10/04
Loading...