Mustek PowerMust 6048 Online LCD X, PowerMust 6048 Online LCD XL, PowerMust 10800 Online LCD X User Manual

PowerMust 6048 Online LCD X
PowerMust 10800 Online LCD X
Uninterruptible Power Supply System
EN
1
Please comply with all warnings and operating
instructions in this manual strictly. Save this
manual properly and read carefully the following
instructions before installing the unit. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.
2
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS .......................................................................................... 3
1-1. TRANSPORTATION AND STORAGE ................................................................................................................... 3
1-2. PREPARATION ............................................................................................................................................ 3
1-3. INSTALLATION ........................................................................................................................................... 3
1-4. OPERATION............................................................................................................................................... 4
1-5. STANDARDS .............................................................................................................................................. 4
2. INSTALLATION AND OPERATION............................................................................................ 5
2-1. UNPACKING AND INSPECTION ....................................................................................................................... 5
2-2. REAR PANEL VIEW ..................................................................................................................................... 5
2-3. SINGLE UPS INSTALLATION .......................................................................................................................... 6
2-4. SOFTWARE INSTA LLATION ............................................................................................................................ 8
3. OPERATIONS ......................................................................................................................... 9
3-1. BUTTON OPERATION ................................................................................................................................... 9
3-2. LED INDICATORS AND LCD PANEL ................................................................................................................ 9
3-3. AUDIBLE ALARM....................................................................................................................................... 11
3-4. SINGLE UPS OPERATION ........................................................................................................................... 11
3-5. ABBREVIATION MEANING IN LCD DISPLAY .................................................................................................... 14
3-6. LCD SETTING ......................................................................................................................................... 15
3-7. OPERATING MODE/STATUS DESCRIPTION ..................................................................................................... 20
3-8. FAULT CODE ........................................................................................................................................... 21
3-9. WARNING INDICATOR ............................................................................................................................... 21
4. TROUBLE SHOOTING ........................................................................................................... 22
5. STORAGE AND MAINTENANCE .............................................................................................. 23
5-1. STORAGE................................................................................................................................................ 23
5-2. MAINTENANCE ......................................................................................................................................... 23
6. SPECIFICATIONS ................................................................................................................. 24
3
1. Safety and EMC instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and
impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
4
1-4. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-5. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2 Category C3
Radiated Emission..................................:IEC/EN 62040-2 Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4 Level 4
SURGE................................................... :IEC/EN 61000-4-5 Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8 Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.
5
2. Installation and Operation
There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
Model Type Model Type
PowerMust
6048 Online
LCD X
Standard
model
PowerMust
6048 Online
LCD XL
Long-run
model PowerMust
10800 Online
LCD X
PowerMust
10800 Online
LCD XL
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
● One UPS
● One user manual
● One monitoring software CD
● One RS-232 cable (option)
● One USB cable
● One battery cable (option)
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use.
2-2. Rear Panel View
Diagram1: 6K/10K Rear Panel
6
Diagram 2: 6KL/10KL Rear Panel Diagram 3: 6K(L)/10K(L) Input/Output Terminal
1. External battery connector
2. RS-232 communication port
3. Intelligent slot
4. USB communication
5. Emergency power off function connector (EPO connector)
6. Cooling fan
7. Input circuit breaker
8. Input/Output terminal (Refer to Diagram 3 and 5 for the details)
9. Maintenance bypass switch
10. Output terminal
11. Grounding terminal
12. Utility input terminal
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
7
Model
Wiring spec (AWG)
Input Output Battery Ground
PowerMust 6048
Online LCD X
10 10 10
PowerMust 6048
Online LCD XL
10 10 10 10
PowerMust 10800
Online LCD X
8 8 8
PowerMust 10800
Online LCD XL
8 8 8 8
NOTE 1: The cable for 6K/6KL should be able to withstand over 50A current. It is recommended to use 10AWG or thicker wire for safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use 8AWG or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
Terminal Block wiring diagram for 6K(L)/10K(L)
NOTE 1: Make sure that the wires are connected tightly with the terminals.
NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6) Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery. The battery type and voltage and numbers may be different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
Input Neutral
Input Line
Ground
Output Line
Output Neutral
Loading...
+ 17 hidden pages