MSD 8970 Installation

3-Stage Retard
PN 8970
IMPORTANT: Read the instructions before attempting the installation.
Parts Included:
1 - 3-Stage Retard Control 4 - Mounting Screws 4 - Mounting Grommets 6 - Retard Modules, 2°, 3°, 4°, 3-Zero°
WARNING: During installation disconnect the battery cables. When disconnecting the battery,
always remove the negative cable first and connect it last.
Note: When the Three Stage Retard Control is installed the ignition timing will retard approximately
4° from its original setting. After installation, the timing should be checked and adjusted
as necessary.
OPERATION
The 3-Stage Retard Control can retard the timing three different times and each with an individual amount. The three amounts are cumulative and the maximum amount of retard is 25°. Each retard stage is activated when its corresponding activation wire is removed from ground and the retard will remain activated until the wire is grounded again. There is also a Start Retard circuit that will retard the timing 10° or 25° during cranking to ease starting on engines with locked-out timing or crank triggers.
CYLINDER SELECT
T h e 3 - S t a ge Ret a r d C o n t r ol is programmed at the factory for 8-cylinder engines. It can easily be modified for use on 4 and 6-cylinder engines. The number of cylinders is selected by cutting the Cylinder Select Loops as shown in Figure 1.
CYLINDERS CUT LOOPS 8 NONE 6 RED 4 RED AND BLUE
Figure 1 Selecting the Number of Cylinders.
MOUNTING
The 3-Stage Retard Control can be mounted under the hood but should be away from direct engine heat sources. Make sure that the wiring reaches their connections. Before mounting the control, install the supplied rubber grommets into the end panels. Then install the sleeve with the beveled edge facing down (Figure 2).
Use the Control as a template and mark the mounting holes. Use an 1/8” bit to drill the mounting holes.
M S D I G N I T I O N • w w w . ms di g ni ti on. co m • ( 9 15 ) 8 5 7 -52 00 • F A X ( 91 5) 8 5 7-3 3 4 4
Figure 2 Installing the
Vibration Mounts.
2 INSTALLATION INSTRUCTIONS
WIRING
RED
BLACK
YELLOW
This is the On/Off wire. Connects to switched 12 volts.
Connects to Ground.
Trigger output. Connects to the MSD Ignition's White Wire.
TRIGGER INPUTS
There are two input trigger circuits. The wires will never be connected at the same time.
WHITE
GREEN/VIOLET
2-Pin Connector
Connects to points or the amplifier trigger wire.
Connects to the magnetic pickup of the distributor or crank trigger. Green is negative, Violet is positive.
RETARD CONTROL WIRES
BROWN
ORANGE
GRAY
Retard 1, Activated when removed from ground.
Retard 2, Activated when removed from ground.
Retard 3, Activated when removed from ground.
START RETARD WIRES
VIOLET
This wire activates the start retard. When 12 volts are supplied, the timing is retarded during cranking.
VIOLET LOOP
This programs the start retard for either 10° or 25° of retard. The unit is set for 10° at the factory and this loop must be cut to obtain 25°.
The Retard Control wires activate the corresponding retard stage. The retard amount is activated when its wire is removed from ground. If you do not plan on using each stage, the corresponding wire must be grounded or a Zero degree module must be installed. When more than one are activated, the retard is the sum of the modules (6°+4°+8°=18°). The maximum retard is 25°.
Figure 3 Wiring an MSD 6 Series Ignition with Points/Amplifier.
M S D I G N I T I O N • w w w . ms di g ni ti on. co m • ( 9 15 ) 8 5 7 -52 00 • F A X ( 91 5) 8 5 7-3 3 4 4
INSTALLATION INSTRUCTIONS 3
Figure 4 Wiring an MSD 6 Series Ignition with a Mag Pickup.
Figure 5 Wiring an MSD 7 Series Ignition with Points/Amplifier.
M S D I G N I T I O N • w w w . ms di g ni ti on. co m • ( 9 15 ) 8 5 7 -52 00 • F A X ( 91 5) 8 5 7-3 3 4 4
Loading...
+ 5 hidden pages