Pushing button starts
operation. Pushing again
stops operation.
MODE SELECT button
This button is used to change
between auto, cooling,
Attention :
● Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch remote controller.
heating and drying operation
modes. (SLZ)
SET TEMPERATURE
button
SET TEMPERATURE
button sets and any
desired room temperature.
TIMER SELECT button
Used for selecting timed
starting or stopping.
FAN SPEED button
This button is used to set
fan speed to low, medium
or high.
VANE CONTROL button
Used to change the airflow
direction.
2
Page 3
Wired remote controller
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
door.
Start/Stop button
Fan Speed button
Filter button
(<return sign> button)
Test Run button
Service button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To preceding operation
number.
Ventilation button
(
Operation button)
To next operation number.
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
SLZ-KA25VA.TH
SLZ-KA35VA.TH
SLZ-KA50VA.TH
● Operation buttons [ PAR-21MAA ]
3
Page 4
● Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
Caution
● Only the Power display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (Centrally controlled) display appears to go off momentarily but this is not a
malfunction.
● “NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
4
Page 5
2
SLZ-KA25VAL.TH
SLZ-KA25VA.TH
SLZ-KA35VAL.TH
SLZ-KA35VA.TH
Indoor model
Function
Power supply
Single phase
230V, 50Hz
600/540/480
10
0.35
75
0.014
0.19
PK6V15-LD
4
37/31/28
650/530/480
3
10
10
10
Cooling
90
Heating
93
Single phase
230V, 50Hz
660/540/480
10
0.40
85
0.014
0.26
PK6V20-LL
4
38/33/29
690/570/510
3
10
10
10
Cooling
94
Heating
94
Air flow
(High/Medium/Low)
Power outlet
Running current ✽1
Power input Rated frequency
Dew prevention heater
Power factor ✽1
Fan motor current ✽1
Model
Winding
resistance (at20:)
Width
Height
Depth
Weight
Air direction
Sound level(High/Medium/Low)
Fan speed(High/Medium/Low)
Fan speed regulator
Thermistor TH1(at25:)
Thermistor TH2(at25:)
Thermistor TH5(at25:)
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA35VAL.TH
SLZ-KA35VA.TH
High
Medium
38
SPL(dB)33LINE
<50Hz>
NOTCH
Low
29
90
80
70
60
50
40
30
20
10
631252505001000 20004000 8000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA25VAL.TH
SLZ-KA25VA.TH
High
Medium
37
SPL(dB)31LINE
<50Hz>
NOTCH
Low
28
NOISE CRITERION CURVES
UNIT
1.5m
MICROPHONE
CEILING
90
80
70
60
50
40
30
20
10
631252505001000 20004000 8000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA50VAL.TH
SLZ-KA50VA.TH
High
Medium
39
SPL(dB)34LINE
<50Hz>
NOTCH
Low
30
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
6
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
Page 7
3
SLZ-KA50VA(L)
SLZ-KA35VA(L)
SLZ-KA25VA(L)
Brand label
(Case of Wired remote controller)
Terminal block
Terminal block
87
Suspension bolt
M10 or 3/8
(procure locally)
1/4F
flared connection
{ 6.35mm
1/4F
flared connection
{ 6.35mm
{ 9.52mm
flared connection
3/8F
1/2F
flared connection
Refrigerent pipe (liquid)
Refrigerent pipe (gas)
Models
{ 6.35mm
flared connection
1/4F
Refrigerent pipe
(liquid)
Refrigerent pipe
(gas)
{ 12.7mm
{ 9.52mm
flared connection
3/8F
15~3715~37
576~620
570
530
Grille
Fresh air
intake
Drain pipe
VP-25 connection
(O.D. { 32)
Vane motor
Drain hole
V/M
Air intake grille
55 35
35 55
Auto vane
Grille
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
301
301
Emergency operation switch(cooling)
Emergency operation switch(heating)
Operation lamp
DEFROST/STAND BY lamp
(WIRELESS PANEL)
Receiver
Detail drawing of fresh air intake
Ceiling surface
Cut out hole
{ 73.4
Burring hole
3- { 2.8 hole
{ 100
118
25
120°
120°
377
377
650
650
Suspension bolt
lower edge
230
18248
Wiring entry
Ceiling surface
235
208
27
+5
0
193
20
93
38~58
66121
17202
56
57
31
Ceiling hole
Suspension bolt pitch
15~3715~37576~620
420
570
335
199
352
335
Suspension bolt
pitch
Ceiling hole
V/M
V/M
V/M
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
• Area in which the remote controller is not exposed direct sunshine.
• Area in which there is no nearby heating source.
• Area in which the remote controller is not exposed to cold (or hot) winds.
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children.
Installation method
1 Attach the remote controller holder to the desired location using two tapping screws.
2 Place the lower end of the controller into the holder.
A Wireless remote controller (Accessory)
B Wall
C Remote controller holder (Accessory)
D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there is interference of light of fluorescent
lights or strong sunlight.
A
C
B
D
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
h
5717.5
140
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
Unit : mm
8
Page 9
WIRED REMOTE CONTROLLER
130
120
19
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
Unit : mm
9
Page 10
4
SWE
GRILLE
OFF
ON
SW3
OFF
54321
ON
SW2
OFF
54321
ON
WHT
RED
RED
CNDK
(POWER
BOARD)
ZNR
X1
RED
ORN
YLW
YLW
BLU
BLU
BLU
BLU
LED3
CN2L
CN32 CN51 CN41
(REMOCON)
BLU
TO OUTDOOR UNIT
S3
ORN
MF
MV
MV
MV
MV
5
5
5
5
H2
5
31
P.B
3
TB4
S1
S2
TB15
1
2
TO MA-REMOTE
CONTROLLER
DC8.7-13V
}
REMOTE
CONTROLLER
W.R
9
5
CN6V
(VANE)
GRN
BLU
WHT
ORN
RED
YLW
YLW
X5
X5 X4
X4X7X6
X6X7
97531
C1
BLK
WHT
BLU
YLW
BRN
RED
I.B
CNB
BZ
LED2
LED1
SW1
SW2
RU
W.B
9
CN22
1
(2 PHASE)
CN29
BLK
WHT
RED
(INTAKE)
(LIQUID)
CN31
3
CN20
CN21
11 2
21 2
2
1 2
DS
TH5
TH1
TH2
X1
YLW
BLU
(D·U·M)
CNP
RED
(D·HEATER)
CNC
313131
CND
(POWER)
ORN
FUSE
(CONTROL)
CN3C
BLU
3131
LED1
1 2
1 2
TRANS
DC13.1V
CN2S(WHT)
AC220-240V
CNSK(RED)
WHT
BLK
2
1
(POWER
BOARD)
CN2D
WHT
LED2
* Case of wireress model
* Case of wired model
See fig:w1
MODELS
KA25
KA35
KA50
<fig:w1>
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
SW2
YLW
YLW
RED
ORN
YLW
WHT
BLU
17 4 5 10 8 92 3 6
DP
GRY
VLT
BLU
YLW
ORN
RED
BRN
SKYBLU
PINK
WHT
(WIRELESS)
CN90
987654321
654321
(FAN)
FAN
WHT
BRN
RED
ORN
YLW
BLU
VLT
GRY
PINK
SKY BLU
1 2 3 4 5 6 7 8 9
(DRAIN)
WHT
w For details on how to operate self-diagnosis
refer to the technical manuals etc.
:Connector, :Terminal (block).
1.Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make
wiring matching terminal numbers(S1,S2,S3).
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set refrigerant address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
˚C
˚C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
B
C
A
E D
A CHECK button
B Refrigerant address
C TEMP. button
D IC:Indoor unit
OC:Outdoor unit
E Check code
RESET
TOO
TOO
COOL
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
ON/OFF
TOO
WARM
TOO
COOL
h
1 Turn ON the power.
2 During pressing both the MODE SELECT button and TOO COOL button on the
remote controller at the same time, press the RESET button.
3 At first, release the RESET button.
4 And release the other two buttons since all LCD in operation display section of the
remote controller is displayed after 3 seconds.
5 Transmit the signal of remote controller, pressing OPERATE/STOP (ON/OFF)
button on the remote controller.
(The above procedure allows OPERATION INDICATOR lamp to indicate the failure-mode.)
6 Transmit the signal of remote controller, pressing OPERATE/STOP (ON/OFF)
button to stop the self-check.
The following indication
applies regardless of shape
of the indicator
.
OPERATION INDICATOR lamp
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
TROUBLESHOOTING
6-1. Cautions on troubleshooting
(1) Before troubleshooting, check the followings:
1Check the power supply voltage.
2Check the indoor/outdoor connecting wire for mis-wiring.
(2) Take care the followings during servicing.
1 Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then turn
off the breaker.
2 When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the
components.
3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
6-2. Self-check
6-2-1. Wired remote controller
6-2-2. Wireless remote controller
12
Page 13
• Refer to the following tables for details on the check codes.
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
n
On
0.5 sec.
th
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
BeepBeep Beep BeepBeepBeep Beep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
4P4Drain sensor error
5P5Drain pump error
6P6Freeing/Overheating safeguard operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Number of flashes/beeps in pattern indicates
the check code in the following table
rd
n
··· Repeated
th
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
1st2
nd
··· Repeated
SymptomRemark
[Output pattern B]
Wireless remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes1 Check code
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan safeguard stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
two beeps to confirm the self-check start signal was received and
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
13
SymptomRemark
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
service manual
OC322.
To be continued on the next page.
Page 14
•
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Symptom
Cause
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes following power-on
After about 2
minutes has
expired following power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
Only LED 1 is lighted. →
LED 1, 2 blink.
Only LED 1 is lighted.
→
LED 1 blinks twice,
LED 2 blinks once.
•For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not con-nected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, L3)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
lighted.
(Correct operation)
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
14
Page 15
6-3. Test point diagram
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
CN2D
Connector to the indoor
power board (CN2S)
(12.5~13.7V DC)
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
Non polarity
CND
Power
supply input
(220~240V AC)
FUSE
(6.3A 250V)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
CNC
Dew prevention
heater (H2)
(220~240V AC)
CNP
Drain-pump output
(DP)
(220~240V AC)
LED1
Power supply
(I.B)
LED2
Power supply
(R.B)
LED3
Transmission
(Indoor/outdoor)
}
–
+
CN22
Remote controller
connecting wire
+
}
(10.4~14.6V DC)
–
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid
(TH2)
CN29
Condenser/evaporator
temperature thermistor
(TH5)
CN31
Drain sensor (DS)
CN90
Connect to the
wireless remote
controller board
(CNB)
CN41
Connector
(HA terminal-A)
CN6V
Vane motor output
(MV)
CN51
Centrally control
FAN
Fan motor output
SW3
Mode selection
SWE
Emergency operation
16
CN2L
Connector
(LOSSNAY)
Jumper connector
J11~J15
Unit setting
SW2
Capacity setting
Page 17
6-4. Trouble criterion of main parts
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
(Refer to the thermistor)
Abnormal
Open or short
Normal
0.6k"~6.0k"
BLKREDORNYLW
BLU
BRN
WHT
P
Room temperature
thermistor
(TH1)
Condenser/evaporator
temperature thermistor
(TH5)
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Measure the resistance between the terminals with a tester.
(Coil wiring temperature 10°C ~ 30°C)
Pipe temperature
thermistor/liquid
(TH2)
Indoor fan motor
(MF)
Check method and criterion
Part name
Normal
KA25VA(L)
Normal
WHT-BLK
BLK-BLU
BLU-YLW
BRN-RED
386~428"
81~91"
28~32"
157~174"
KA35VA(L)
373~413"
155~172"
44~49"
302~335"
KA50VA(L)
308~341"
135~151"
44~49"
293~324"
4.3kΩ~9.6k"
Abnormal
Abnormal
Opened or
short-circuited
Opened or short-circuited
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor (MV)
Drain pump (DP)
Drain sensor (DS)
1
2
Yellow
Yellow
1
2
3
NormalConnectorAbnormal
300"Open or short
NormalAbnormal
290"Open or short
Orange
Red
White
P : Thermal fuse 145 ± 2˚C
Red — Yellow
Red — Blue
Red — Orange
Red — White
Blue
Yellow
35
1
2
4
M
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
How to read curves
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust system for air flow amount Q <Pa>
E…Static pressure of indoor unit with air
flow amount Q
Qa…Estimated amount of fresh air
intake with out D<m3/min>
<m
3
/min>
<Pa>
<Pa>
<Pa>
<Pa>
7-3. Interlocking operation method with duct fan (Booster fan)
●Whenever the indoor unit is operating,
the duct fun
operates.
(1)Connect the optional multiple remote
controller adapter(PAC-SA88HAE)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow
and Orange connector lines.
Use a relay under 1W.
MB: Electromagnetic switch power
relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
19
Page 20
7-4. Fixing of horizontal vane
Standard of
horizontal position
Dimension A (mm)
21252830
Level 30°
(Min.)
Downward 45°Downward 55°
Downward 70°
(Max.)
w Dimension between 21 mm and 30 mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
Erroneous setting could cause dew drips, smudge on ceiling or malfunction of unit.
<Set range>
.
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
Horizontal vane of each air outlet can be fixed according to the environment, which is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure
below.
Electricity insulate the disconnected connector with the vinyl tape.
Vane motor
Vane motor
Connector
Unlocking button
Horizontal vane
3) Set a vertical vane of the air outlet, which tries to fixed by the hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
20
Page 21
8DISASSEMBLY PROCEDURE
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
SLZ-KA25VAL.TH SLZ-KA35VAL.TH SLZ-KA50VAL.TH
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the hook for secure belt on air inlet grille from the
panel.
(3) Slide the shaft in the hinge to the direction of the arrow 2
and remove the air intake grille.
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
Figure 1
Air intake grille
Air intake grille knob
Photo 1
Fan guard
Be careful on removing heavy parts.
Grille
Screws
Air intake grille
3. Removing the panel
(1) Remove the air intake grille. (Refer to 1)
Corner panel (See figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow 3, and
remove the corner panel.
Panel (See photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a large diameter of the
oval hole, which has two different diameters.)
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Terminal block (TB4)
• Indoor power board (P.B)
Figure 2
Corner
panel
Photo 2
Connectors
Screws
Photo 3
Indoor power board
(P.B)
Screw
Corner
panel
Panel
Screws
Panel
21
Indoor controller board
(I.B)
Terminal block
(TB4)
Page 22
OPERATING PROCEDURE
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
PHOTOS&ILLUSTRATIONS
5. Remove the room temperature thermistor (TH1)
(1) Remove the panel. (Refer to 3)
(2) Pull out the room temperature thermistor from the drain
pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature thermistor.
6. Remove the drain pan
(1) Remove the panel. (Refer to 3)
(2) Remove the room temperature thermistor and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to 2)
7. Removing the pipe temperature thermistor/liquid (TH2)
and condenser/evaporator temperature thermistor (TH5)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Disconnect the indoor coil thermistor from the holder.
(4) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Photo 4
Screw
Room
temperature
thermistor
(TH1)
Screw
Photo 5
Control box
Fan guard
Control box
Connectors
Drain plug
Screw
Drain pan
Screw
Pipe temperature thermistor/liquid (TH2)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature thermistor/liquid.
Condenser/evaporator temperature thermistor (TH5)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the condenser/evaporator temperature
thermistor.
8. Remove the fan motor (MF)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (fan 1) and the (fan 2)
from the indoor controller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove the 3 nuts of the fan motor.
Pipe temperature
thermistor/liquid
(TH2)
Photo 6
Screws
Lead
wires
Screw
Flat plate
Condenser/evaporator
temperature thermistor
(TH5)
Screw
Nut
Nut
Fan motor
(MF)
Nut
Screws
22
Page 23
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
9. Removing the drain pump (DP) and drain sensor (DS)
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connectors of the (CNP) and the (CN31)
from the indoor controller board.
(5) Remove the 1 screw fixed to the cover, and remove the
cover.
(6) Disconnect the lead wires to the direction of the drain
pump.(See photo 7)
(7) Remove the 3 screws of the drain pump.
(8) Cut the drain hose band, pull out the drain hose from the
drain pump.
(9) Pull out the drain pump.
(10) Remove the drain sensor and the holder.
10. Removing the heat exchanger
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connector of the (fan) from the indoor con-
troller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the pipe temperature thermistor/liquid and
condenser/evaporator temperature thermistor. (Refer to 7)
(8) Disconnect the lead wires to the direction of the fan motor.
(9) Remove the 1 coil support screw, the 2 inside coil screws
(See photo 10), and the 4 outside coil screws (See photo 9)
from the heat exchanger, and remove the heat exchanger.
AIR OUTLET GRILLE
AIR OUTLET GRILLE
WIRELSS REMOTE CONTROL BOARD
AUTO VANE
CORNER PANEL
AIR FILTER
INTAKE GRILLE
VANE MOTOR
VANE BUSH
GEAR (V)
GEAR (M)
Parts name
SLP-2AL SLP-2AA
Q'ty/set
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
www.ilmalämpöpumput.com
1
E07 104 290
2
E07 104 124
3
E07 104 808
4
E07 105 124
E07 140 620
5
E07 141 620
E07 142 620
6
E07 104 105
E07 162 300
7
E07 164 300
E07 166 300
8
E07 104 816
9
E07 104 502
10
E07 104 097
11
E07 104 700
12
E07 154 308
13
E07 104 520
14
E07 104 524
15
E07 104 648
16
E07 154 309
17
E07 154 307
18
E07 104 702
19
E07 104 266
20
E07 104 241
21
E07 104 355
22
E07 104 809
23
E07 154 006
24
E07 140 426
25
E02 527 083
26
E07 159 426
27
E07 018 089
Parts nameParts No.
BASE
DRUM-1
LEG-1
DRUM-2
I
NDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
MOTOR MOUNT
INDOOR FAN MOTOR
INDOOR FAN MOTOR
INDOOR FAN MOTOR
FLAT PLATE
TURBO FAN
SPL WASHER
DRAIN PAN
ROOM TEMPERATURE THERMISTOR
FAN GUARD
DRAIN PLUG
COIL SUPPORT