Mitsubishi MELSEC iQ-R, RD75-U-OU-E User Manual

Page 1
NetSure™ 710NPBA +24 VDC Power System
User Manual
Specification Number: 581127000 Model Number: 710
NPBA
Page 2
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/
for additional assistance.
Vertiv™ NetSure™ 710
Page 3
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
iii
TABLE OF CONTENTS
Admonishments Used in this Document ............................................................................................................................. iv
Important Safety Instructions .................................................................................................................................................. v
Static Warning ........................................................................................................................................................................... viii
1 Customer Documentation Package ..................................................................................................................................1
2 System Description ............................................................................................................................................................... 2
3 Operating Procedures .......................................................................................................................................................... 3
3.1 Controller, Rectifiers, and Optional Converters................................................................................................................................................................................. 3
3.2 ESTOP Function............................................................................................................................................................................................................................................................. 3
3.3 Controller Battery Charge Current Limit Feature ...........................................................................................................................................................................4
3.4 Local Controls and Indicators ...........................................................................................................................................................................................................................4
4 Maintenance ........................................................................................................................................................................... 10
4.1 System Maintenance Procedures ............................................................................................................................................................................................................... 10
4.2 Adding a Rectifier or DC-DC Converter Module to an Existing Module Mounting Assembly .......................................................... 10
4.3 Installing a Field Expansion Module Mounting Assembly..................................................................................................................................................... 12
4.4 Reconfiguring a Dual Voltage Distribution Panel (List DA, DB, DC, DD) ................................................................................................................15
4.5 Reconfiguring a Dual Voltage Distribution Panel (List DE, DF, DG, DH, DJ, DK) .......................................................................................... 24
4.6 Changing the Controller’s LVD Control Level for a Contactor ........................................................................................................................................ 33
5 Troubleshooting and Repair ........................................................................................................................................... 33
5.1 Contact Information ................................................................................................................................................................................................................................................. 33
5.2 Controller, Rectifiers, and Optional Converters.............................................................................................................................................................................. 33
5.3 Controller Configuration ...................................................................................................................................................................................................................................... 33
5.4 System Troubleshooting Information ..................................................................................................................................................................................................... 33
5.5 Replacement Information .................................................................................................................................................................................................................................. 34
5.6 Replacement Procedures ................................................................................................................................................................................................................................... 35
5.6.1 Replacing a Rectifier or Converter Module ................................................................................................................................................................. 35
5.6.2 Replacing the Controller ............................................................................................................................................................................................................... 35
5.6.3 Replacing a Distribution Device............................................................................................................................................................................................. 35
5.6.4 Replacing a Distribution Panel (List AA, AB, AC, AD, AE, AF, AG, AH, AJ, AK, DA, DB, DC, DD, BA, BB,
BC, BD, BE, BF, BG, BH, AM, and AP) ................................................................................................................................................................................ 45
5.6.5 Replacing a Distribution Panel (List AL, AN, DE, DF, DG, DH, DJ, and DK) ................................................................................. 48
5.6.6 Replacing a Distribution Panel List AA, AB, AC, AD, AE, AF, AG, AH, AJ, AK, DA, DB, DC, DD, BA, BB,
BC, BD, BE, BF, BG, or BH with a List AL, AN, DE, DF, DG, DH, DJ, or DK .........................................................................................51
5.6.7 Circuit Card Replacement Procedures ........................................................................................................................................................................... 56
5.6.8 Replacing a Battery or Load Disconnect Contactor .......................................................................................................................................... 69
Page 4
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
iv
DANGER
in death or serious injury if not avoided. (ANSI, OSHA)
WARNING
result in death or serious injury if not avoided. This admonition is not used for situations that pose a risk only to equipment, software, data, or service. (ANSI)
CAUTION
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition is not used for situations that pose a risk only to equipment, data, or service, even if such use appears to be permitted in some of the applicable standards. (OSHA)
ALERT
equipment, software, data, or service. (ISO)
ALERT
equipment damage, software corruption, data lo
FIRE SAFETY
or policies, or of the locations of fire
SAFETY
policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)

Admonishments Used in this Document

! Warns of a hazard the reader
! Warns of a potential hazard the reader
! Warns of a potential hazard the reader
! Alerts the reader to an action that
will
be exposed to that will
may
be exposed to that
may
be exposed to that
must be avoided
likely
result
could
could
in order to protect
! Alerts the reader to an action that
! Informs the reader of fire safety information, reminders, precautions,
! Informs the reader of general safety information, reminders, precautions, or
-fighting and fire-safety equipment. (ISO)
must be performed
ss, or service interruption. (ISO)
in order to prevent
Page 5
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
v

Important Safety Instructions

Safety Admonishments Definitions

Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv.

General Safety

DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should be performed by qualified
technicians familiar with the hazards associated with this type of equipment. These hazards may include shock, energy,
and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other metal objects.
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the expected
voltage is present. Check for voltage with both AC and DC voltmeters prior to making contact.
d) Wear eye protection.
e) Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the work to be
performed.

Voltages

AC Input Voltages

DANGER! This system operates from AC input voltage capable of producing fatal electrical shock. AC input power must be
completely disconnected from the branch circuits wiring used to provide power to the system before any AC electrical
connections are made. Follow local lockout/tagout procedures to ensure upstream branch circuit breakers remain de-
energized during installation. DO NOT apply AC input power to the system until all electrical connections have been
completed and checked.

DC Output and Battery Voltages

DANGER! This system produces DC power and may have a battery source connected to it. Although the DC voltage is not
hazardously high, the rectifiers and/or battery can deliver large amounts of current. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact an output terminal or battery terminal or exposed wire
connected to an output terminal or battery terminal. NEVER allow a metal object, such as a tool, to contact more than one
termination or battery terminal at a time, or to simultaneously contact a termination or battery terminal and a grounded
object. Even a momentary short circuit can cause sparking, explosion, and injury.
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection devices remain de-energized
during installation at loads, as required.
Page 6
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
vi

Battery

Refer to the battery manufacturer documentation for specific battery safety instructions. The following are general guidelines.
WARNING! Correct polarity must be observed when connecting battery leads.
WARNING! Special safety precautions are required for procedures involving handling, installing, and servicing batteries.
Observe all battery safety precautions in this manual and in the battery instruction manual. These precautions should be
followed implicitly at all times.
WARNING! A battery can present a risk of electrical shock and high short circuit current. Servicing of batteries should be
performed or supervised only by properly trained and qualified personnel knowledgeable about batteries and the required
precautions.
The following precautions should be observed when working on batteries:
Follow the recommended PPE requirements per the SDS for the battery to be used.
Batteries are an energy source that can produce high amounts of electrical current.
Remove watches, rings, and other metal objects.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the work to be
performed. Ensure that wrenches with more than one working end have only one end exposed.
Do not lay tools or metal parts on top of batteries.
Verify that no current will flow when the battery is connected or disconnected by opening battery disconnects (if
available) or adjusting the system to match battery voltage.
Risk of explosion if battery is replaced with an incorrect type or if polarity is reversed. Recommended to replace
batteries with the same manufacturer and type, or equivalent.
Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a fire.
They may explode.
Batteries may generate explosive gases during normal operation. Systems containing batteries should never be installed
in an airtight room or space. Only install in a ventilated environment.
Batteries may contain sulfuric acid. If battery acid enters your eye, immediately flush your eye with running cold water
for at least 15 minutes. Get medical attention immediately. If battery acid contacts skin or clothing, wash immediately with soap and water.
Do not open or mutilate batteries.
ALWAYS FOLLOW THE BATTERY MANUFACTURER’S RECOMMENDATIONS AND SAFETY INSTRUCTIONS.
ALERT! Performing maintenance and/or troubleshooting procedures may interrupt power to the loads, if battery reserve is
not sufficient.
Page 7
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
vii

Personal Protective Equipment (PPE)

DANGER! ARC FLASH AND SHOCK HAZARD.
Appropriate PPE and tools required when working on this equipment. An appropriate flash protection boundary analysis
should be done to determine the “hazard/risk” category, and to select proper PPE.
Only authorized and properly trained personnel should be allowed to install, inspect, operate, or maintain the equipment.
Do not work on LIVE parts. If required to work or operate live parts, obtain appropriate Energized Work Permits as required
by the local authority, per NFPA 70E “Standard for Electrical Safety in the Workplace”.

Hazardous Voltage

DANGER! HAZARD OF ELECTRICAL SHOCK.
More than one disconnect may be required to de-energize the system before servicing.

Handling Equipment Containing Static Sensitive Components

ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before
handling any equipment containing static sensitive components, read and follow the instructions contained on the Static
Warning Page.

Maintenance and Replacement Procedures

CAUTION! When performing any step in procedures that requires removal or installation of hardware, use caution to ensure
no hardware is dropped and left inside the unit; otherwise service interruption or equipment damage may occur.
NOTE!
When performing any step in procedures that requires removal of existing hardware, retain all hardware for use in
subsequent steps, unless otherwise directed.
Page 8
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
viii

Static Warning

This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to
these components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any equipment containing static sensitive components, discharge all static electricity from yourself by
wearing a wrist strap grounded through a one megohm resistor. Some wrist straps have a built-in one megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s instructions outlining use of a specific wrist strap.
3. Do not touch traces or components on equipment containing static sensitive components. Handle equipment
containing static sensitive components only by the edges that do not have connector pads.
4. After removing equipment containing static sensitive components, place the equipment only on static dissipative
surfaces such as conductive foam or ESD bag. Do not use ordinary Styrofoam or ordinary plastic.
5. Store and ship equipment containing static sensitive components only in static shielding containers.
6. If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap,
work on a conductive surface, use a grounded soldering iron, and use grounded test equipment.
Page 9
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
1

1 Customer Documentation Package

This document (UM581127000) provides User Instructions for NetSure +24 VDC Power System Model 710NPBA, Spec. No. 581127000.
The complete Customer Documentation Package consists of…

NetSure +24 VDC Power System Installation Manual

Power System Installation Instructions: IM581127000

NetSure ACU+ Controller User Manual

ACU+ Controller User Instructions: UM1M820BNA

NetSure NCU Controller User Manual

NCU Controller User Instructions: UM1M830BNA

USB Drive with All Customer Documentation

Power System Quick Start Guide: QS581127000
Power System Installation Instructions: IM581127000
Power System User Instructions: UM581127000
ACU+ Controller User Instructions: UM1M820BNA
NCU Controller User Instructions: UM1M830BNA
Power System “System Application Guide”: SAG581127000
Module Mounting Shelf Power Data Sheet: PD588705200 (PD588705201, PD588705202, PD588705203, PD588705204)
Rectifier Instructions: UM1R243000
Converter Instructions: UM1C24481500
NCU Controller 2nd Ethernet Port Add-On Kit Instructions: IM559252
NCU Controller 2nd Ethernet Port Retrofit Kit Instructions: IM559251
Engineering Drawings
Also provided on the USB drive is a controller configuration drawing and the controller configuration files loaded into the
controller as shipped.
Page 10
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
2

2 System Description

+24 VDC @ up to 2000 Amperes Power System
The NetSure 710NPBA DC Power System is an integrated power system containing rectifiers, optional converters, intelligent control, metering, monitoring, and distribution.
This power system is designed to power a load while charging a negative grounded battery. This power system is capable of operating in a batteryless installation or off battery for maintenance purposes. The power system is designed for operation with the negative output grounded.
This system consists of the following components.

Distribution Cabinet

The system always includes a minimum of one distribution cabinet, which provides DC distribution through fuses and/or circuit breakers. The distribution cabinet is factory mounted in the relay rack or shipping brackets specified when ordered.
Four different sizes of distribution cabinets are available to accept from one (1) to four (4) distribution panels. A variety of distribution panels are available that provide load distribution, battery distribution, and dual voltage load distribution for use with -48V converters. These distribution panels are configured to accept either bullet nose type circuit breakers and TPS/TLS fuseholders, TPH fuses, TPL­B fuses, or GJ/218 circuit breakers. A bulk output panel is also available.
The distribution cabinet may be equipped with low voltage load disconnect (LVLD), low voltage battery disconnect (LVBD), and manual battery disconnect.

Controller

The controller controls the operation of the rectifier and converter modules. The controller also provides power system control, metering, monitoring, and alarm functions.
NCU (NetSure Control Unit): The controller provides power system control (including optional low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a charge control function), converter control, metering functions, monitoring functions, and local/remote alarm functions. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe(s). Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains a color LCD display and keypad for local access. The controller provides an Ethernet port and comes with comprehensive webpages for remote access. The controller has SNMP v3 capability for remote system management. The controller supports software upgrade via its USB port. Refer to the NCU Controller Instructions (UM1M830BNA) for more information.
ACU+ (Advanced Control Unit Plus): The controller provides power system control (including optional low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a charge control function), converter control, metering functions, monitoring functions, and local/remote alarm functions. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe(s). Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains an LCD display and keypad for local access. The controller provides an Ethernet port and comes with comprehensive webpages for remote access. The controller has SNMP capability for remote system management. The controller supports software upgrade via its USB port. Refer to the ACU+ Controller Instructions (UM1M820BNA) for more information.

Module Mounting Assembly

The system contains one module mounting assembly which houses rectifier modules and optional DC-DC converter modules. A module mounting assembly consists of one (1) to four (4) 8-position module mounting shelves. Refer to Power Data Sheet PD588705200 (PD588705201, PD588705202, PD588705203, PD588705204) for more information.
Page 11
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
3

Rectifier Modules

The system contains rectifier modules, which provide load power, battery float current, and battery recharge current during normal operating conditions. Refer to the Rectifier User Instructions (UM1R243000) for more information.

Converter Modules

Where –48VDC load power is also required, DC-DC converter modules are available. Refer to the Converter User Instructions (UM1C24481500) for more information.

3 Operating Procedures

3.1 Controller, Rectifiers, and Optional Converters

For operation instructions on these units, refer to the following documents.
ACU+ Controller Instructions (UM1M820BNA)
NCU Controller Instructions (UM1M830BNA)
Rectifier User Instructions (UM1R243000)
Converter User Instructions (UM1C24481500)

3.2 ESTOP Function

If an ESTOP switch is wired to the IB2-1 Controller Interface Board, customer-furnished system ground applied to terminal DI8­activates the ESTOP function. The ESTOP function shuts down and locks out the rectifiers, shuts down and locks out the optional +24 VDC to -48 VDC converters, and opens the optional low voltage disconnect (LVD) contactors (battery and load type). If the system has battery connected and does not contain a battery LVD or the controller power option is set to Battery Pwr (jumper J8 on the system interface board is set to Battery Pwr), the controller will remain operational. If the system does not contain battery or load LVD(s) and has battery connected, the loads will be sustained by the battery voltage.
For Systems NOT Containing a Battery LVD: When the ESTOP signal is removed, LVD contactors (battery and load type) will close after the “LVD Reconnect Delay” has elapse (customer configurable via the controller) if battery voltage is present on the bus. Rectifiers and +24 VDC to -48 VDC converters will remain off. The rectifiers will restart when the input power is removed and restored after 30 seconds or more (until the LEDs on the modules extinguish). To restart the +24 VDC to -48 VDC converters: remove the converter, wait 30 seconds or more (until the LEDs on the converter extinguish), then re-insert the converter.
For Systems Containing a Battery LVD: When the ESTOP signal is removed, LVD contactors (battery and load type) will remain open. Rectifiers and +24 VDC to -48 VDC converters will remain off. The rectifiers will restart when the input power is removed and restored after 30 seconds or more (until the LEDs on the modules extinguish). When the rectifiers restart, LVD contactors (battery and load type) will close after the “LVD Reconnect Delay” has elapse (customer configurable via the controller) and the +24 VDC to ­48 VDC converters will restart.
NOTE!
If a customer-furnished method to disconnect the input power to the system is not provided, the rectifiers will stay
locked OFF until the input power is recycled. If the ESTOP signal is removed without recycling the input power, the rectifiers
will remain off and have a local alarm visible on the module. The ESTOP alarm from the controller will extinguish. The
controller will not issue an alarm for this condition.
Page 12
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
4

3.3 Controller Battery Charge Current Limit Feature

Functionality: After a commercial AC failure or when some battery cells are permanently damaged, the current to the batteries can be quite extensive. To avoid overheating or further damages to the battery, the controller can be programmed to limit the battery current to a preset level by limiting the charging voltage of the rectifiers. Should the battery current still exceed a higher preset value, an alarm is issued.
The controller limits the current going to the batteries based on the “Battery Current Limit” set point which is a percentage of the battery capacity in C10. For example, 0.1C10 would mean 10% of the battery capacity.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) to program this feature. Battery charge current is limited to the value set in the controller, as long as battery voltage is above 23.5V DC.

3.4 Local Controls and Indicators

Refer to the Controller, Rectifier, and Converter Instructions for descriptions of the local controls and indicators located on these units.
Refer to this section for descriptions of the local controls and indicators located on the circuit cards installed in the distribution cabinet.

Circuit Card Locations

Refer to Figure 3.1.
Page 13
5
Figure 3.1 Circuit Card Locations
IB2
(Interface Board)
(located on inside side panel)
Optional EIB
(Extended Interface Board)
(located on inside side panel)
Optional SM-DU+ and Shunt Interface Board
4-Row Cabinet Shown,
Others Similar
(Front Door Removed in
Illustration for Clarity)
Controller
Mounting Position
System Interface
Circuit Card
OR
Optional LVD
Driver Circuit Card
Optional LVD Driver
Lite Circuit Card
Optional Manual Battery Disconnect Circuit Card
Optional LVD Inhibit Switch
(factory installed
if option specified)
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 14
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
6
Monitoring

System Interface Circuit Card

The system interface circuit card contains test points to externally monitor bay voltage and bay load. Refer to Figure 3.2.
Figure 3.2 System Interface Circuit Card
J7
System Load Shunt Scale
List 21, 1-Row Cabinet 800A / 25mV 32A per mV
List 22, 2-Row Cabinet 2000A / 25mV 80A per mV
List 23, 3-Row Cabinet 2500A / 25mV 100A per mV
List 24, 4-Row Cabinet 2500A / 25mV 100A per mV
J8
TB2
J10
J1
J2
J3
J4
1
1
1
1
TB1
TP1 TP2 TP3
TP1 (+) and TP2 (-)
System Voltage
J5
TP4
TP3 (+) and TP4 (-) System Load Shunt Monitoring
Page 15
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
7
LVD Inhibit Switch
Momentary UP
/ Middle / Down Momentary UP Position: Closes all LVD Contactors (inhibit mode). Middle Position: OFF (Controller DOES NOT control LVD’s) (inhibit mode). DOWN Position: ON (Controller controls LVD’s).
LVD Inhibit
Active Indicator
Illuminates when the
low voltage disconnect
circuit has been disabled
through the use of the
LVD Inhibit switch.
J6 J5 J4
J3 J2 J1
J9
J7
S1
Note: The U P position will not close the LVBD contactor if the battery is manually disconnected using the Manual Battery Disconnect Switch.

Optional LVD Driver Circuit Card

The optional LVD driver circuit card contains an LVD inhibit switch and indicator. Refer to Figure 3.3. LVD driver circuit cards are required for 2-, 3-, or 4-row distribution cabinets that contain three or more LVD contactors (LVBD and/or LVLD); or if the distribution cabinet is equipped with an LVBD contactor rated 1200A or higher.
CAUTION! If the switch is returned to the ON (normal) position when low voltage disconnect alarms are active, a low voltage
disconnection will occur.
WARNING! While the LVD inhibit switch is in the OFF (inhibit) position, a low voltage disconnection will not occur if battery
or load voltage decreases below the low voltage disconnect setpoint. For maximum battery protection, this switch should
NOT be left in the OFF (inhibit) position.
ALERT! Do not hold the LVD inhibit switch in the up position for more than 3 seconds to avoid damaging the contactor.
Figure 3.3 Optional LVD Driver Circuit Card
Page 16
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
8
LVD Inhibit Switch
LVD Inhibit
Active Indicator
Momentary UP / Middle / Down Momentary UP Position: Closes all LVD Contactors (inhibit mode). Middle Position: OFF (Controller DOES NOT control LVD’s) (inhibit mode). DOWN Position: ON (Controller controls LVD’s).
Illuminates when the
low voltage disconnect
circuit has been disabled
through the use of the
LVD Inhibit switch.
J1J3
J2
S1
Note: The UP position will not close the LVBD contactor if the battery is manually disconnected using the Manual Battery Disconnect Switch.

Optional LVD Driver Lite Circuit Card

The optional LVD driver lite circuit card contains an LVD inhibit switch and indicator. Refer to Figure 3.4. LVD driver lite circuit cards are required for distribution cabinets that contain two LVLD contactors or one LVLD contactor and one LVBD contactor. LVBD contactor must be rated at 600A or lower.
CAUTION! If the switch is returned to the ON (normal) position when low voltage disconnect alarms are active, a low voltage
disconnection will occur.
WARNING! While the LVD inhibit switch is in the OFF (inhibit) position, a low voltage disconnection will not occur if battery
or load voltage decreases below the low voltage disconnect setpoint. For maximum battery protection, this switch should
NOT be left in the OFF (inhibit) position.
ALERT! Do not hold the LVD inhibit switch in the up position for more than 3 seconds to avoid damaging the contactor.
Figure 3.4 Optional LVD Driver Lite Circuit Card
Page 17
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
9
Momentary UP / Middle / Momentary Down
Manual Battery Disconnect Active Indicator
Manual Battery
Disconnect Switch
Illuminates if the Battery Disconnect Contactor has been manually disconnected (placed in open position).
J1
J2
S1
Momentary UP Position: Closes (latches in close position) the Battery Disconnect Contactor.
Middle Position: Normal Operation.
Momentary DOWN Position: Opens (latches in open position) the Battery Disconnect Contactor. Momentarily place switch in the UP position to close the contactor.

Optional Manual Battery Disconnect Circuit Card

The optional manual battery disconnect circuit card contains a manual battery disconnect switch and indicator. Refer to Figure 3.5.
NOTE!
If this option is to be used as a Maintenance Battery Disconnect only, at least one rectifier requires to be active and
providing voltage to the system for proper operation.
ALERT! Do not hold the MBD switch (S1) in the up position for more than 3 seconds to avoid damaging the contactor.
ALERT! When using switch, after either pushing up or down let switch return to the center position for 3 seconds before
pushing switch in the opposite direction to avoid damaging the contactor.
Figure 3.5 Optional Manual Battery Disconnect Circuit Card
Page 18
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
10

4 Maintenance

4.1 System Maintenance Procedures

It is recommended to perform the maintenance procedures listed in Table 4.1 every 6-months to ensure continual system operation.
Table 4.1 Maintenance Procedures to be Performed at 6-Month Intervals
PROCEDURE REFERENCED IN
Check ventilation openings for obstructions such as dust, papers, manuals, etc.
Inspect and tighten all installer's connections.
IM581127000, “Making Electrical Connections” section.
--
4.2 Adding a Rectifier or DC-DC Converter Module
to an Existing Module Mounting Assembly
To increase system current capacity, a rectifier module can easily be added to an existing module mounting assembly that contains an empty rectifier module mounting position. Likewise, in systems that accept DC-DC converter modules, to increase subsystem capacity a DC-DC converter module can be added to a module mounting assembly that contains an empty converter module mounting position.
The module location diagram on the front of each module mounting assembly shows which type of module can be operated in that shelf. (See Figure 4.1.) Rectifier modules will operate in any mounting position in any shelf. If a shelf accepts DC-DC converter modules, they must be installed in any or all of the four middle mounting positions (B, C, F, G) of each 8-position module mounting shelf.
It is recommended that the current limit point be checked whenever a rectifier or converter is added to or removed from the power system. Refer to “Checking the Controller’s Current Limit Point after Adding or Removing a Rectifier Module” on page 34.
The rectifier or converter module being added is assigned by the controller the lowest available identification number. If desired, you can change the identification number. Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure.

Procedure

1. Unpack the module.
2. Note the model number located on the handle of the module. Model numbers starting with the letter “R” (R24-2500 or R24-
3000) are rectifier modules. Model numbers starting with the letter “C” (C24/48-1500) are DC-DC converter modules.
3. Check the module location diagram on the front of the module mounting assembly to determine which type of module
(rectifier or DC-DC converter) can be installed in each mounting position. See Figure 4.1.
4. If present, remove the blank cover panel from the mounting position into which a rectifier or DC-DC converter module is to be
installed.
5. Install the rectifier or converter module into the shelf. Refer to the rectifier or converter User Instructions for a procedure.
Page 19
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
11
Rectifier Modules Only
DC-DC Converter Modules
Figure 4.1 Module Location Diagrams (located on the front of each module mounting assembly)
MODULE
LOCATION
DIAGRAM
RECTIFIERS
(PCUs)
A B C D
E F G H
THIS SHELF
ACCEPTS
RECTIFIERS
(PCUs)
ONLY
This Shelf Accepts
MODULE
LOC
A
TION
DIAGRAM
RECTIFIERS
(PCUs)
A B C D
E F G H
CONVE
RTERS
THIS SHELF
ACCEPTS
RECTIFIERS
(PCUs) IN
AL
SLOTS
AND
L
8 SLOTS
CONVERTER S
IN 4 MIDDLE
This Shelf Accepts
Rectifier Modules and
Page 20
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
12

4.3 Installing a Field Expansion Module Mounting Assembly

A field expansion module mounting assembly can be added to a system that has 24 or fewer module mounting positions.

Procedure

DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
NOTE!
1. Slide the expansion module mounting assembly into position directly beneath the bottom-most shelf of the module mounting
NOTE!
2. Remove the rear cover from the bottom-most shelf of the module mounting assembly installed in the system and the
NOTE!
3. Secure the existing shelf’s busbars to the expansion shelf’s mating busbars with the supplied interconnect busbars and
4. Install the supplied side brackets (both sides) to tie the existing shelf to the expansion module mounting assembly.
5. If the Expansion Shelf Accepts DC-DC Converters: Refer to the Power System Installation Instructions (IM581127000) and
6. Remove the termination cable from the bottom controller bus interconnection connector on the bottom-most existing shelf
Refer to Figure 4.2 as this procedure is performed.
assembly installed in the system (no space between shelves). Secure the expansion module mounting assembly to the relay rack with the provided 12-24 x 1/2" mounting screws and grounding washers.
Install the ground washers so the teeth make contact with the metal on the mounting angles. Torque all screws to 65
in-lbs.
expansion module mounting assembly.
Apply electrical anti-oxidizing compound to busbar mating surfaces before performing the next step.
hardware. Hardware build-up is: shelf’s busbar, interconnect busbar, 1/4" hardened flat washer, 1/4" Belleville lock washer, 1/4­20 nut. Install the Belleville lock washer so the concave side is towards the busbar. Torque all connections to 60 in-lbs.
install the converter output jumpers.
and plug it into the bottom controller bus interconnection connector on the expansion shelf. See Figure 4.2.
7. Plug the controller bus connector on the cable exiting the top of the expansion shelf into the mating connector exiting the
bottom of the shelf above it. See Figure 4.3.
8. Replace the rear covers removed in step 2) above.
9. Refer to the Power System Installation Instructions (IM581127000) and connect AC input power to the expansion shelf.
10. Refer to the rectifier and converter User Instructions and install modules into the expansion shelf as required.
Page 21
13
Figure 4.2 Installing a Field Expansion Module Mounting Assembly
Interconnect Busbars
588705200
(8-Position Expansion Shelf)
588705203
(Existing 24-Position Shelf Assembly)
(588705201 and 588705202 similar)
1/4" Hardened Flat Washer 1/4" Belleville Lock Washer 1/4-20 Nut (16 places) Torque to 60 in-lbs.
Apply electrical anti-oxidizing compound to busbar mating surfaces before installing Expansion Module Mounting Shelf.
Rear View
Bracket to secure shelves together.
12-24 x 1/2" Thread Forming Hex Head Screw (2 per side) No. 10/12 Ground Washer (2 per side) (Torque to 65 in-lbs)
1. Slide the Expansion Module Mounting Shelf into the relay rack.
2. Secure the Expansion Module Mounting S helf to the relay rack.
3. Remove rear cover from existing shelf and the Expansion Module Mounting Shelf.
4. Secure the existing shelf’s busbars to the expansion shelf’s busbars with the supplied interconnect busbars.
5. Tie the existing shelf to the Expansion Module Mounting Shelf with the supplied brackets (both sides).
5. Remove the connector from the bottom controller communications connector in the existing shelf and plug it into the bottom controller communications connector in the expansion shelf. Plug the loose end of the bottom controller communications connector in the existing shelf into the loose end of the top controller communications connector in the expansion shelf.
6. Reinstall rear covers.
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 22
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
14
Existing Communications Cable Connections
Distribution Cabinet
Module Mounting Shelf
Brown and
Brown/W hite
Wires
New Communications Cable Connections
Brown and
Brown/W hite
Wires
Slate and
Slate/White
Wires
Slate and
Slate/White
Wires
Distribution Cabinet
Module Mounting Shelf
Expansion Module Mounting Shelf
Figure 4.3 Communications Cables
Page 23
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
15

4.4 Reconfiguring a Dual Voltage Distribution Panel (List DA, DB, DC, DD)

Perform the following procedure to reconfigure a dual voltage distribution panel (List DA, DB, DC, DD) to move distribution positions from one voltage to the other.
DANGER! Performing this procedure exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
NOTE!
Save all removed hardware. Hardware will be re-used.

Removing the Distribution Panel

Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
3. Remove the plastic shield covering the circuit breakers and/or fuseholders on the distribution panel to be removed by
loosening the screws holding the shield and sliding the shield upwards.
4. Record circuit breaker and/or fuse positions and sizes.
5. Remove circuit breakers and/or fuseholders.
6. Label the load leads.
7. Disconnect all load leads from the circuit breaker and/or fuse positions.
8. Disconnect all load return leads from the ground busbar.
9. Refer to Figure 4.4 and remove the hardware securing the -48V jumper leads. Insulate and tie back these leads.
10. Refer to Figure 4.4 and locate the in-line FA/CBA connector located near the back of the distribution panel. Separate the
connector halves.
11. Refer to Figure 4.4 and remove the hardware securing the distribution panel’s ground busbar to the distribution cabinet’s
busbar.
12. Refer to Figure 4.4 and remove the hardware securing the distribution panel’s system load distribution busbar to the
distribution cabinet’s busbar.
13. Refer to Figure 4.4 and remove the hardware securing the distribution panel to the distribution cabinet. Remove the
distribution panel from the distribution cabinet.
Page 24
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
16
List DB Dual Voltage Distribution Panel (List DA, DC, DD similiar)
Components removed in illustration for clarity only.
Front
List DB Dual Voltage Distribution Panel (List DA, DC, DD similiar)
Ground Busbar Hardware
In-Line FA/CBA Connector
-48V Jumpers
Distribution Panel Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
Figure 4.4 Removing/Installing the Distribution Panel
Page 25
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
17
List DB Dual
Voltage Distribution Panel (List DA, DC, DD similar)
Move -48V Input Power
Busbar 4-Positions
Left or Right in Increment
of Four Positions
Move -48V Input Lead Busbars
4-Positions Left or Right in
Increments of Four Positions
Distribution Device Lead Busbars
Distribution Device
Lead Busbars
Move -48V Input Power Busbar
4-Positions Left or Right in
Increments of Four Positions
Front
Rear
Move -48V
Distribution Device
Busbar Right
Move +24V Distribution Device Busbar Left
OR

Reworking the Distribution Panel Introduction

You can reconfigure the distribution panel to swap +24V distribution positions for -48V distribution positions, and vice versa, in groups of four. The resulting assembly can have (5) +24V and (16) -48V, (9) +24V and (12) -48V, (13) +24V and (8) -48V, or (17) +24V and (4) -48V positions.
You do this by removing the subsystem input power busbar and associated input lead busbars, then moving the appropriate distribution device busbar and associated distribution device lead busbars left or right in increments of four (4) positions, then re-installing the subsystem input power busbar and associated input lead busbars. The distribution devices alarm spring most also be appropriately moved. Refer to the following procedures to reconfigure the distribution panel.
Figure 4.5 Reworking the Distribution Panel Introduction
Page 26
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
18
List DB Dual Voltage Distribution Panel (List DA, DC, DD similar)
-48V Input
Power Busbar
-48V Input
Power Busbar
-48V Input Lead Busbars
-48V Input Lead Busbars
Front
Rear
Press in Tabs to Release
Input Lead Busbars

Removing the -48V Input Power Busbar and Input Lead Busbars

Procedure
1. From the front of the distribution panel, remove the three bolts and hardware from the -48V input power busbar.
2. From the rear of the distribution panel, remove the two bolts and hardware from the -48V input power busbar.
3. Remove the -48V input power busbar from the distribution panel. Set aside for later re-installation.
4. Remove the three -48V input lead busbars from the distribution panel. Refer to Figure 4.6 and press in the tab to release a
-48V input lead busbar. Slide the -48V input lead busbar up and out of the distribution panel. Repeat for all three busbars.
Set aside for later re-installation.
Figure 4.6 Removing the -48V Input Power Busbar and Input Lead Busbars
Page 27
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
19

Moving the Distribution Device Busbar and Distribution Lead Busbars Left or Right

Procedure
1. Determine how you are reconfiguring the distribution panel (adding -48V or +24V distribution positions). Locate the
distribution device busbars and distribution device lead busbars to be moved.
2. From the front of the distribution panel, remove the two screws and hardware securing the appropriate distribution device
busbar(s). The busbar(s) are located to the left or to the right of the open space created when the -48V input power busbar
was removed in the previous procedure.
3. From the rear of the distribution panel, remove the two bolts and hardware securing the distribution device link busbar(s)
between the distribution device busbar(s) to be moved and the one adjacent to it.
4. Slide the distribution device busbar(s) three (3) positions to the left or to the right.
5. From the front of the distribution panel, re-install the two screws and hardware to secure the distribution device busbar(s)
just moved. Torque as indicated in Figure 4.7.
6. From the rear of the distribution panel, re-install the distribution device link busbar(s) between the distribution device
busbar(s) just moved and the one adjacent to it with the two bolts and hardware previously removed. Apply anti-oxidizing
compound to busbar mating surfaces. Torque as indicated in Figure 4.7.
7. Remove the four distribution device lead busbars located above the position(s) of each of the distribution device busbar(s)
were moved from. Refer to Figure 4.7 and press in the tab to release a distribution device lead busbar. Slide the distribution
device lead busbar up and out of the distribution panel. Repeat for all distribution device lead busbars.
8. Remove the polarity labels from these positions. Turn over the polarity labels so the other polarity shows. Re-install the
polarity labels to the left or right of the original position (into the positions the distribution device lead busbars will be moved
to in the next step).
9. Re-install the distribution device lead busbars three (3) positions to the left or to the right of the original positions. Slide a
distribution device lead busbar down and into the distribution panel. Repeat for all distribution device lead busbars.
Page 28
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
20
List DB Dual Voltage Distribution Panel (List DA, DC, DD similar)
Front
Move -48V Distribution
Device Busbar(s)
3 Positions Right
Move +24V Distribution Device Busbar(s) 3 Positions Left
OR
OR
Remove polarity label. Turn over polarity label so other polarity shows. Replace polarity label in relocated distribution positions.
Distribution Device Lead Busbars
Press in
T
abs to Release
Distribution Device Lead Busbars
Rear
Move -48V Distribution Device Busbar(s) 3 Positions Right
Move +24V Distribution
Device Busbar(s)
3 Positions Left
OR
6-32 x 3/4 Screw #6 Lock Washer #6 Flat Washer Torque to 11 in-lbs.
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars.
Figure 4.7 Moving the Distribution Device Busbar and Distribution Lead Busbars Left or Right
Page 29
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
21
List DB Dual Voltage Distribution Panel (List DA, DC, DD similar)
Typical Before View
Exploded View
Typical After View
Rear
Rear
Rear
Move Alarm Spring(s)
3 Positions Right
Place Alarm Spring
Link on Opposite Side
Place Alarm Spring Link on Opposite Side
Move Alarm Spring(s) 3 Positions Left
OR
6-19 x 1/2 Screw
Torque to 9.6 in-lbs.
6-19 x 5/16 Screw
Torque to 9.6 in-lbs.

Moving the Alarm Spring(s) Left or Right

Procedure
1. Located the alarm spring(s) and alarm spring link(s) to be moved.
2. From the rear of the distribution panel, remove the appropriate alarm spring link(s).
3. From the rear of the distribution panel, remove the screw(s) from the alarm spring(s) to be moved. Slide the alarm spring(s)
three (3) positions to the left or to the right. Secure with the screw(s) just removed. Torque as indicated in Figure 4.8.
4. Re-install the alarm spring link(s) to the opposite side of the alarm spring(s) just moved and to the alarm spring adjacent to it.
Torque as indicated in Figure 4.8.
Figure 4.8 Moving the Alarm Spring(s) Left or Right
Page 30
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
22
List DB Dual Voltage Distribution Panel (List DA, DC, DD similar)
-48V Input
Power Busbar
-48V Input
Power Busbar
-48V Input Lead Busbars
-48V Input Lead Busbars
Front
Rear
Press in Tabs to Release
Input Lead Busbars
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
Enlarged View
Enlarged View
1/4-20 x 3/4 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars.

Re-Installing the -48V Input Power Busbar and Input Lead Busbars

Procedure
1. Re-install the -48V input lead busbars. Slide the -48V input lead busbars down and into the distribution panel in the
mounting locations created when the distribution device lead busbars were moved in the previous procedure.
2. Re-install the -48V input power busbar into the distribution panel in the position created when the distribution device busbar
in the previous procedure was moved.
3. From the front of the distribution panel, re-install the three bolts and hardware to secure the -48V input power busbar to the
-48V input lead busbars. Torque as indicated in Figure 4.9.
4. From the rear of the distribution panel, re-install the two bolts and hardware to secure the -48V input power busbar. Torque
as indicated in Figure 4.9.
Figure 4.9 Re-Installing the -48V Input Power Busbar and Input Lead Busbars
Page 31
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
23
Move this Label Left
or Right as Required

Moving the 24V/48V Label on the Distribution Device Cover to the New Position

Procedure
1. Move the polarity label on the distribution device cover right or left to align with the distribution positions moved in the
previous procedures.
Figure 4.10 Moving the 24V/48V Label on the Distribution Device Cover to the New Position

Replacing the Distribution Panel

NOTE!
Procedure
1. Orient the distribution panel into the distribution cabinet, checking to ensure no wires are pinched. Replace the hardware
2. Reconnect the -48V jumper leads. Refer to Figure 4.4 for hardware build-up. Torque as indicated in Figure 4.4.
3. Replace the hardware securing the distribution panel’s system load distribution busbar to the distribution cabinet’s busbar.
4. Replace the hardware securing the distribution panel’s ground busbar to the distribution cabinet’s busbar. Torque as
5. Plug the in-line FA/CBA connector located near the back of the distribution panel into the mating connector half in the
WARNING! In the next step, observe correct polarity; otherwise equipment damage will result.
6. Reconnect the load return leads to the ground busbar.
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
securing the distribution panel to the distribution cabinet. Refer to Figure 4.4 for hardware build-up. Torque as indicated in
Figure 4.4.
Refer to Figure 4.4 for hardware build-up. Torque as indicated in Figure 4.4.
indicated in Figure 4.4.
distribution cabinet. Refer to Figure 4.4.
7. Reconnect the load leads to the circuit breaker and/or fuse positions.
8. Replace the circuit breakers and/or fuseholders.
9. Replace the plastic shield covering the circuit breakers and/or fuseholders on the distribution panel.
10. Verify no circuit breaker/fuse alarms are active.
11. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
12. Ensure that there are no local or remote alarms active on the system.
Page 32
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
24
4.5 Reconfiguring a Dual Voltage Distribution Panel (List DE, DF, DG, DH, DJ,
DK)
Perform the following procedure to reconfigure a dual voltage distribution panel (List DE, DF, DG, DH, DJ, DK) to move distribution positions from one voltage to the other.
DANGER! Performing this procedure exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
NOTE!
Save all removed hardware. Hardware will be re-used.

Removing the Distribution Panel

Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system
while the procedure is being performed.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
3. Remove the plastic shield covering the circuit breakers and/or fuseholders on the distribution panel to be removed by
loosening the screws holding the shield and sliding the shield upwards.
4. Record circuit breaker and/or fuse positions and sizes.
5. Remove circuit breakers and/or fuseholders.
6. Label the load leads.
7. Disconnect and insulate all load leads from the circuit breaker and/or fuse positions.
8. Disconnect and insulate all load return leads from the ground busbar.
9. Refer to Figure 4.11 and remove the hardware securing the -48V jumper leads. Insulate and tie back these leads.
10. Refer to Figure 4.11 and locate the in-line FA/CBA connector located near the back of the distribution panel. Separate the
connector halves.
11. Refer to Figure 4.11 and remove the hardware securing the distribution panel’s ground busbar to the distribution cabinet’s
busbar.
12. Refer to Figure 4.11 and remove the hardware securing the distribution panel’s system load distribution busbar to the
distribution cabinet’s busbar.
13. Refer to Figure 4.11 and remove the hardware securing the distribution panel to the distribution cabinet. Remove the
distribution panel from the distribution cabinet.
Page 33
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
25

Reworking the Distribution Panel

You can reconfigure the distribution panel to swap +24V distribution positions for -48V distribution positions, and vice versa, in groups of four. The resulting assembly can have (0) +24V and (26) -48V, (6) +24V and (20) -48V, (10) +24V and (16) -48V, (14) +24V and (12) -48V, (18) +24V and (8) -48V, (22) +24V and (4) -48V, or (26) +24V and (0) -48V positions.
You do this by moving the shorting bus and CBA/FA alarm strap. Refer to Figure 4.12 to reconfigure the distribution panel.
Note that for a List DE distribution panel, you must also move the subsystem input power busbar as shown in Figure 4.12.
Note that if you reconfigure a distribution panel for all subsystem voltage (List DK) or all system voltage, you must also move the extra CBA/FA alarm strap stored on the far left (as viewed from the rear) to the far right position (as shown in Figure 4.12).
Note that if you reconfigure a distribution panel for all subsystem voltage (List DK), you must disconnect and insulate the system CBA/FA lead (as shown in Figure 4.12).
Note that if you reconfigure a distribution panel for all system voltage, you must disconnect and insulate the subsystem CBA/FA lead (as shown in Figure 4.12).
Note that if the panel is re-configured for all subsystem positions (List DK), the distribution cabinet's load side busbar must be removed since it is not to be connected to the distribution panel and will cause interference. Note that the busbar that is removed should be retained in the event that the panel is re-configured at a later date to revert back to a panel with some subsystem positions.
Page 34
26
Components removed in illustration for clarity only.
In-Line FA/CBA Connector
List DG (Lists DE , DF, DH, DJ, and DK similar.)
Rear
Connect “-48V” jumpers to an available landing here. Assembly order is: lug, 1/4" flat washer, 1/4" lock washer, 1/4-20 x 3/4” bolt. Torque to 84 in-lbs.
Ground Busbar Hardware
Distribution Panel Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
Front
Front
Lugs can be landed back-to-back.
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Figure 4.11 Removing/Installing the Distribution Panel
Page 35
27
List DE Dual Voltage Distribution Panel
List DF Dual Voltage Distribution Panel
List DG Dual Voltage Distribution Panel
List DH Dual Voltage Distribution Panel
List DJ Dual Voltage Distribution Panel
List DK Dual Voltage Distribution Panel
Reconfigured for all System Positions
Extra Shorting Block Stored Here
Extra Shorting Block Stored Here
Extra Shorting Block Stored Here
Extra Shorting Block Stored Here
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Figure 4.12 Reworking the Distribution Panel (cont’d on next page)
Page 36
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
28
From the front, remove the polarity labels for the positions reassigned and turn the label over so the other polarity shows. See Detail A.
From the front, remove the voltage barrier shield from the right-most
EXISTING sub-system distribution position and place it in the right-most NEW sub-system distribution position.
See Detail B.
List DE Only: Move the -48V Input Power Busbar one (1) position to the left.
Before
After
List DE Only: Move the Shorting Bus at the desired point of the voltage division to the storage position shown in a previous illustration.
List DE Only: Move the CBA/FA alarm strap at the desired point of the voltage division to the location above the relocated
-48V Input Power Busbar.
Move CBA/FA
Alarm Strap Here
6-19 x 1/2 Screw
Torque to 9.6 in-lbs.
Move Shorting Bus Here
Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars.
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
Move
-48V Input Power Bus Here
List DE Dual Voltage Distribution Panel
Figure 4.12 Reworking the Distribution Panel (cont’d from previous page, cont’d on next page)
Page 37
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
29
Before
After
List DF, DG, DH, DJ Dual Voltage Distribution Panel (DF Shown, Others Similar)
Move the Shorting Bus at the desired point of of the voltage division to the new location as shown in a previous illustration.
Move Extra Shorting Bus
Extra Shorting Bus
Move the CBA/FA alarm strap at the desired point of the voltage division to the new location.
Move CBA/FA
Alarm Strap
Here
Move CBA/FA Alarm Strap Here
6-19 x 1/2 Screw Torque to 9.6 in-lbs.
Move Shorting
Bus Here
Move Shorting Bus Here
Input Power Busbar Not Shown
Input Power Busbar Not Shown
Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars.
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
From the front, remove the polarity labels for the positions reassigned and turn the label over so the other polarity shows. See Detail A.
From the front, remove the voltage barrier shield from the right-most
EXISTING sub-system distribution position and place it in the right-most NEW sub-system distribution position.
See Detail B.
Figure 4.12 Reworking the Distribution Panel (cont’d from previous page, cont’d on next page)
Page 38
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
30
From the front, remove the polarity labels for the positions reassigned and turn the label over so the other polarity shows. See Detail A.
From the front, remove the voltage barrier shield. See Detail B.
Distribution Panel Reconfigured for All Subsysytem (List DK) or All System Positions
Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars.
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs.
Move CBA/FA Alarm
Strap FROM Here
Modified Panel View
Before Modification View: An Alarm Strap is Stored Here
After Modification View:
The Alarm Strap is Moved Here
Move CBA/FA Alarm
Strap TO Here
6-19 x 1/2 Screw
Torque to 9.6 in-lbs.
Ensure the Subsystem
Busbar is Installed in
this Position
All Except List DE: Move the Extra Shorting Bus Stored as shown in a Previous Illustration to the Open Position
Note that if you reconfigure a distribution panel for all system voltage, you must disconnect and insulate the subsystem CBA/FA lead attached here.
Note that if you reconfigure a distribution panel for all subsystem voltage (List DK), you must disconnect and insulate the system CBA/FA lead attached here.
Figure 4.12 Reworking the Distribution Panel (cont’d from previous page, cont’d on next page)
Page 39
31
For reassigned distribution positions...
1. Remove polarity label plug buttons.
2. Remove polarity label.
3. Turn over polarity label so other polarity shows.
4. Replace polarity label.
5. Replace polarity label plug buttons.
For right-most reassigned sub-system distribution position...
1. Remove the load lug from the right-most EXISTING sub-system distribution position.
2. Replace the load lug from the right-most EXISTING sub-system distribution position WITHOUT the voltage barrier shield.
3. Remove the load lug from the right-most NEW sub-system distribution position.
4. Replace the load lug from the right-most NEW sub-system distribution position WITH the voltage barrier shield.
Front
Load Lug
Load Lug
New Location Voltage Barrier Shield
System Voltage
Sub-System
Voltage
Old Location Voltage Barrier Shield
Detail A
Front
Detail B
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Figure 4.12 Reworking the Distribution Panel (cont’d from previous page)
Page 40
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
32

Replacing the Distribution Panel

NOTE!
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
Procedure
NOTE!
If the panel is re-configured for all subsystem positions (List DK), the distribution cabinet's load side busbar must be
removed since it is not to be connected to the distribution panel and will cause interference. Note that the busbar that is
removed should be retained in the event that the panel is re-configured at a later date to revert back to a panel with some
subsystem positions.
1. If the panel is re-configured for all subsystem positions, remove the distribution cabinet's load side busbar. Save this busbar
and hardware for future use.
2. Orient the distribution panel into the distribution cabinet, checking to ensure no wires are pinched. Replace the hardware
securing the distribution panel to the distribution cabinet. Refer to Figure 4.11 for hardware build-up. Torque as indicated in
Figure 4.11.
3. Reconnect the -48V jumper leads. Refer to Figure 4.11 for hardware build-up. Torque as indicated in Figure 4.11
. For a panel re-configured to all +24V positions, the -48V jumper leads MUST not be used. They should be retained at the site for future use if necessary.
4. In all except panels re-configured for all subsystem positions (List DK), replace the hardware securing the distribution panel’s
system load distribution busbar to the distribution cabinet’s busbar. Refer to Figure 4.11 for hardware build-up. Torque as indicated in Figure 4.11.
5. Replace the hardware securing the distribution panel’s ground busbar to the distribution cabinet’s busbar. Torque as
indicated in Figure 4.11.
6. Plug the in-line FA/CBA connector located near the back of the distribution panel into the mating connector half in the
distribution cabinet. Refer to Figure 4.11.
WARNING! In the next step, observe correct polarity; otherwise equipment damage will result.
7. Reconnect the load return leads to the ground busbar.
8. Reconnect the load leads to the circuit breaker and/or fuse positions.
9. Replace the circuit breakers and/or fuseholders.
10. Replace the plastic shield covering the circuit breakers and/or fuseholders on the distribution panel.
11. Verify no circuit breaker/fuse alarms are active.
12. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
13. Ensure that there are no local or remote alarms active on the system.
Page 41
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
33

4.6 Changing the Controller’s LVD Control Level for a Contactor

The controller has two available LVD control levels (LVD1 and LVD2). The level used to control a contactor is determined by which connector on the LVD circuit card its control leads are plugged into. To change the LVD control level for a contactor, simply switch which LVD connector it is plugged into (if an open connector is available) on the LVD circuit card. Refer to Figure 5.16 and Figure 5.17 for connector location and function.
NOTE!
DO NOT change a Low Voltage Load Disconnect contactor to LVD Control Level 2 (LVD2) if the system is furnished
with a Low Voltage Battery Disconnect contactor.

5 Troubleshooting and Repair

5.1 Contact Information

Refer to Section 4154 (provided with your customer documentation) for support contact information.

5.2 Controller, Rectifiers, and Optional Converters

For troubleshooting and repair instructions on these units, refer to the following documents.
ACU+ Controller Instructions (UM1M820BNA)
NCU Controller Instructions (UM1M830BNA)
Rectifier User Instructions (UM1R243000)
Converter User Instructions (UM1C24481500)

5.3 Controller Configuration

If any controller configuration settings were changed, refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) and save a copy of the configuration file. This file can be used to restore the controller settings, if required, at a later date.
Note that provided on a USB drive furnished with the system is a controller configuration drawing (C-drawing) and the
controller configuration files loaded into the controller as shipped.

5.4 System Troubleshooting Information

This system is designed for ease in troubleshooting and repair. The various indicators as described in “Local Controls and Indicators” on page 4 and in the Controller and Rectifier Instructions are designed to isolate failure to a specific element. Once the faulty element has been identified, refer to “Replacement Information” on page 34 and “Replacement Procedures” on page 35.

Troubleshooting Alarm Conditions on the Controller

The controller displays alarm conditions as listed in the “Available Alarms” or “Resolving Alarms” section of the controller’s User Manual. Programmable external alarm relays are also available. Refer to the System Installation Instructions (IM581127000) and the configuration drawing (C-drawing) supplied with your power system documentation for your alarm relay configurations.
The controller’s (UM1M820BNA) or NCU Instructions (UM1M830BNA) to access these menus.
Active Alarm
and
Alarm History
submenus allow the User to view alarm details. Refer to the ACU+ Instructions
Page 42
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
34

Checking the Controller’s Current Limit Point after Adding or Removing a Rectifier Module

If a rectifier module is added to the power system, the system current limit point will automatically increase by the percentage each existing rectifier was set to provide prior to the addition.
If a rectifier module is removed from the system (and the Rect Comm Fail alarm is reset), the current limit point will remain unchanged unless the capacity of the remaining rectifiers is not sufficient to maintain the present current limit point. If that happens, the current limit point will automatically increase to the maximum (121% of the remaining rectifiers).
It is recommended that the current limit point be checked whenever a rectifier module is added to or removed from the power system.
When setting total rectifier current limit, the set point to each unit is the total set point divided by the number of units. For example, if the system contains five rectifiers and the current limit is set to 150 amps then each rectifier has a current limit set point of 30 amps. If one or more rectifiers are removed or fail it will take several seconds for the individual set points to the remaining rectifiers to be reset. In the example given, if one rectifier is removed the current limit set point will drop to 120 amps (30 amps times four remaining rectifiers) until the controller can send updated set points to the remaining rectifiers. This takes a couple communication cycles (several seconds) after which each rectifier would have a new set point of 37.5 amps for a total of 150 amps. The total current limit of the rectifiers should not be set such that the loss of the redundant rectifiers will cause this temporary set point to drop below the actual maximum expected load. If batteries are used on the rectifier output, the batteries should support the load until the current limit set points can be re-established due to loss of a rectifier.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure.

Clearing a Rectifier Communications Fail Alarm after Removing a Rectifier

If a rectifier module is removed from the system, a rectifier communications failure alarm is generated. If the rectifier module will not be replaced, the alarm should be cleared.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure.

Clearing a Converter Communications Fail Alarm after Removing a Converter

If a converter module is removed from the system, a converter communications failure alarm is generated. If the converter module will not be replaced, the alarm should be cleared.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure.

Clearing a Rectifier Lost Alarm

If the controller resets while a rectifier communications fail alarm is active, the rectifier communications fail alarm is replaced with a rectifier lost alarm.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure to clear the alarm.

Clearing a Converter Lost Alarm

If the controller resets while a converter communications fail alarm is active, the converter communications fail alarm is replaced with a converter lost alarm.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure to clear the alarm.

5.5 Replacement Information

Replacement Assemblies

When a trouble symptom is localized to a faulty rectifier module, converter module, controller, or system circuit card; that particular device or circuit card should be replaced in its entirety. No attempt should be made to troubleshoot or repair individual components on any rectifier module, converter module, controller, or circuit card.
Refer to SAG581127000 (System Application Guide) for replacement part numbers.
Page 43
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
35
Safety Cover
P/N 248898700
(GMT-X)
Safety Cover
P/N 102774
(GMT-Y)

5.6 Replacement Procedures

DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.

5.6.1 Replacing a Rectifier or Converter Module

Refer to the Rectifier User Instructions (UM1R243000) or Converter User Instructions (UM1C24481500) for a rectifier and converter module replacement procedure. Refer also to “System Troubleshooting Information” on page 33.
The rectifier or converter module being replaced is assigned by the controller the lowest available identification number. If desired, you can change the identification number. Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a procedure.

5.6.2 Replacing the Controller

Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for a controller replacement procedure.

5.6.3 Replacing a Distribution Device

General
Replace distribution devices with the same type and rating. Refer to System Application Guide SAG581127000 for part numbers.
Distribution Fuse “Alarm Fuse” Replacement
If a distribution fuse opens, the associated alarm fuse opens. Replace the distribution fuse before replacing the alarm fuse.
Procedure
1. An alarm fuse is removed by pulling it straight out of the fuseholder. If the alarm fuse is located in a modular fuse carrier, hold
the fuse carrier in place with your thumb while pulling on the alarm fuse to prevent the entire carrier from inadvertently being pulled out.
2. Safety fuse covers are provided for all Bussmann GMT type fuses installed in the system. These covers snap onto the fuses
and provide protection from exposed electrical terminations when a fuse opens. Insure that the safety fuse cover is installed after replacing a fuse. Refer to Figure 5.1 for installation details.
Figure 5.1 Installation of Safety Fuse Covers
Page 44
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
36
Replacing a TPS/TLS Fuse
Procedure
NOTE!
Refer to Figure 5.2 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the fuse carrier from the mounted fuseholder body by pulling it straight out.
3. Remove the open fuse from the fuse carrier and replace it with the same type and rating.
4. Replace the alarm fuse located in the front of the fuse carrier with the same type and rating. Ensure that a plastic safety
cover is installed on the alarm fuse.
5. Push the fuse carrier securely back into the mounted fuseholder body. Note that a polarizing key on the bottom of the
carrier prevents the carrier from being inserted upside down.
6. Verify no Fuse Alarms are active.
7. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Replacing a Bullet Nose Fuseholder
Procedure
NOTE!
Refer to Figure 5.2 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the fuse carrier from the mounted fuseholder body by pulling it straight out. Hold the fuseholder body while you pull
the fuse carrier from the body.
3. Gently rock the defective fuseholder up and down while pulling firmly outward until the fuseholder is free from the
distribution panel.
4. Orient the fuseholder as shown in Figure 5.2. Insert the terminals on the rear of the fuseholder into their corresponding
sockets on the distribution panel. Ensure the alarm contact on the back of the fuseholder makes contact with the alarm terminal on the spring strip. Push fuseholder in firmly until fully seated in the distribution panel.
5. Push the fuse carrier securely back into the mounted fuseholder body. Note that a polarizing key on the bottom of the
carrier prevents the carrier from being inserted upside down.
6. Verify no Fuse Alarms are active.
7. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Page 45
37
Figure 5.2 Replacing a TPS/TLS Fuseholder and/or Fuse
Fuseholder Asse
mbly
Longer Side to the Bottom
Shorter Side to the Top
Fuse Carrier
Fuseholder Body
TPS/TLS Fuse
Polarizing Keyway Matches Key on Bottom of Fuse Carrie r
Fuseholder Assembly Exploded View
Fuseholder Assembly (P/N 117201) includes body & carrier, alarm fuse, and alarm fuse safety cover.
Insert these terminals into corresponding sockets on distribution panel .
GMT-X
Safety Fuse Cover
(Replacement
P/N 248898700)
GMT-18/100A Alarm Fuse (Replacement P/N 248610301)
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 46
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
38
Insert these terminals into corresponding sockets on distribution panel.
Longer Side to the Bottom
Shorter Side to the Top
Lettering on handle must be right side up.
Turn off before installing.
Replacing a Bullet Nose Circuit Breaker
Procedure
NOTE!
Refer to Figure 5.3 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Operate the defective circuit breaker to the OFF position.
3. Gently rock the defective circuit breaker up and down while pulling firmly outward until the breaker is free from the
distribution panel.
4. Ensure that the circuit breaker is in the OFF position, and is of the correct rating.
5. Orient the circuit breaker as shown in Figure 5.3. Insert the terminals on the rear of the circuit breaker into their
corresponding sockets on the distribution panel. Ensure the alarm contact on the back of the circuit breaker makes contact with the alarm terminal on the spring strip. Push distribution device in firmly until fully seated in the distribution panel.
6. Operate the replacement circuit breaker to the ON position.
7. Verify no Circuit Breaker Alarms are active.
8. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Figure 5.3 Replacing a Bullet Nose Circuit Breaker
Page 47
39
Replacing a TPH Fuse
Fuse
Fuse Carrier
Fuseholder Body
Procedure
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
NOTE!
Refer to Figure 5.4 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the fuse carrier from the mounted fuseholder body by grasping its handle and pulling straight out.
3. Remove the open fuse from the fuse carrier and replace it with the same type and rating.
4. Push the fuse carrier securely back into the mounted fuseholder body.
5. On the distribution panel, locate the open alarm fuse associated with the TPH fuse being replaced. Replace the alarm fuse
with the same type and rating. Ensure that a plastic safety cover is installed on the alarm fuse.
6. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Figure 5.4 Replacing a TPH Fuse
Page 48
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
40
Fuse Case
Open Fuse Case View
TPL Fuse
Fuse Installed in Open Fuse Case (rear view)
Fuse Installed in Closed Fuse Case (rear view)
Fuseblock (P/N 516241)
GMT-18/100A Alarm Fuse
(P/N 248610301) and
GMT-X Safety Fuse Cover
(P/N 248898700)
(Both are provided
w/ fuseblock)
Replacing a TPL-B Fuse
Procedure
NOTE!
Refer to Figure 5.5 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the fuse case from the mounted fuse block by grasping its handle and pulling it straight out.
3. Open the fuse case.
4. Remove the open fuse from the fuse case and replace it with the same type and rating.
5. Close the fuse case.
6. Push the fuse case securely back into the mounted fuse block.
7. Replace the alarm fuse located in the front of the TPL-B fuse block. Replace only with a fuse of the same type and rating.
Ensure that a plastic safety cover is installed on the alarm fuse.
8. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Figure 5.5 Replacing a TPL-B Fuse
Page 49
41
Replacing a GJ/218 Circuit Breaker
Procedure
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
NOTE!
Refer to Figure 5.6 as this procedure is performed.
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Operate the defective circuit breaker to the OFF position.
DANGER! The bolts being removed in the following step may be at system potential. Use insulated tools.
3. Remove the hardware securing the circuit breaker to the distribution panel and partially remove the circuit breaker.
4. Record each alarm wire located on the back of the circuit breaker (color and location on circuit breaker). Wiring diagrams are
provided in Figure 5.6. Carefully disconnect the alarm wiring from the back of the circuit breaker, ensuring the exposed end does not contact any energized circuit.
5. Shunted Breakers Only: Record each shunt wire located on the back of the circuit breaker (color and location on circuit
breaker). Wiring diagrams are provided in
Figure 5.6. Carefully disconnect the shunt wiring from the back of the circuit
breaker, ensuring the exposed end does not contact any energized circuit.
6. Ensure that the replacement circuit breaker is in the OFF position, and is of the correct rating and type (electrical
trip/mechanical trip or electrical trip only). Orient the circuit breaker over its mounting location. Re-attach the alarm wiring and shunt wiring (if applicable) to the back of the circuit breaker as recorded above. Wiring diagrams are provided in Figure
5.6.
DANGER! The bolts being installed in the following step may be at system potential. Use insulated tools.
7. Install the replacement circuit breaker into its mounting position and secure with the hardware previously removed. Torque
to 60 in-lbs.
8. Transfer the circuit breaker guard from the old circuit breaker to the new circuit breaker.
9. Operate the replacement circuit breaker to the ON position.
10. Verify no Circuit Breaker Alarms are active.
11. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Page 50
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
42
1/4" Hardened Flat Washer 1/4" Belleville Lock Washer 1/4-20 x 3/4” Bolt (2 places) Torque to 60 in-lbs.
OFF
ON
Apply anti-oxidizing compound to busbar mating surfaces before mounting circuit breakers.
INSTALLING CIRCUIT BREAKER
Alarm jumper connector.
Holes to route shunt jumper through (if applicable).
ALARM WIRING (BREAKERS W/OUT SHUNTS)
ALARM WIRING (BREAKERS WITH SHUNTS)
Standard and
Electrical
Trip Breaker
Shunted Breaker Jumper: Red
Alarm Jumper: Brown
Alarm Jumper: Brown
Alarm Jumper: Red
Alarm Jumper: Red
Shunted Breaker Jumper: Black
INSTALLING CIRCUIT BREAKER GUARD
ON
OFF
LONGER SIDE OF GUARD
10-32 X 7/16 PH
10-32 LW
CIRCUIT BREAKER GUARD LABEL
CIRCUIT BREAKER GUARD
TYPICAL DIST ASSY SHOWN FOR EXAMPLE
Figure 5.6 Replacing a GJ/218 Circuit Breaker (1-Pole) (Lists AC, AD, BC, BD) (cont’d on next page)
Page 51
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
43
ALARM WIRING (BREAKERS W/OUT SHUNTS)
ALARM WIRING (BREAKERS WITH SHUNTS)
Standard and
Electrical
Trip Breaker
Shunted Breaker Jumper: Red
Alarm Jumper: Brown
Alarm Jumper: Brown
Alarm Jumper: Red
Alarm Jumper: Red
Shunted Breaker Jumper: Black
INSTALLING CIRCUIT BREAKER GUARD
ON
OFF
LONGER SIDE OF GUARD
10-32 X 7/16 PH
10-32 LW
CIRCUIT BREAKER GUARD LABEL
CIRCUIT BREAKER GUARD
TYPICAL DIST ASSY SHOWN FOR EXAMPLE
1/4" Hardened Flat Washer 1/4" Belleville Lock Washer 1/4-20 x 3/4” Bolt (4 places / 2-pole brk, 6 places / 3-pole brk, 8 places / 4-pole brk) Torque to 60 in-lbs.
Apply anti-oxidizing compound to busbar mating surfaces before mounting circuit breakers.
OFF
ON
INSTALLING CIRCUIT BREAKER
Alarm jumper connectors.
Holes to route shunt jumper through (if applicable).
Busbar
2-pole breaker shown. 3-pole and 4-pole breakers similar.
Figure 5.6 Replacing a GJ/218 Circuit Breaker (2-Pole, 3-Pole, 4-Pole) (Lists AC, AD, BC, BD) (cont’d from previous page, cont’d
on next page)
Page 52
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
44
ALARM WIRING (BREAKERS W/OUT SHUNTS)
ALARM WIRING (BREAKERS WITH SHUNTS)
Standard and
Electrical
Trip Breaker
Shunted Breaker Jumper: Red
Alarm Jumper: Brown
Alarm Jumper: Brown
Alarm Jumper: Red
Alarm Jumper: Red
Shunted Breaker Jumper: Black
INSTALLING CIRCUIT BREAKER GUARD
ON
OFF
LONGER SIDE OF GUARD
10-32 X 7/16 PH
10-32 LW
CIRCUIT BREAKER GUARD LABEL
CIRCUIT BREAKER GUARD
TYPICAL DIST ASSY SHOWN FOR EXAMPLE
INSTALLING CIRCUIT BREAKER
Apply anti-oxidizing compound to busbar mating surfaces before mounting circuit breakers.
1/4" Hardened Flat Washer 1/4" Belleville Lock Washer 1/4-20 x 3/4” Bolt (2 places) Torque to 60 in-lbs.
OFF
ON
OFF
ON
Alarm jumper connector.
1/4" Hardened Flat Washer 1/4" Belleville Lock Washer 1/4-20 x 3/4” Bolt (4 places / 2-pole breaker, 6 places / 3-pole breaker, 8 places / 4-pole breaker) Torque to 60 in-lbs.
Shorting Busbar
For a 3-pole and 4-pole breaker, install shorting busbars top and bottom. (4-pole shorting busbars shown, 3-pole similar)
2-pole breaker shown. 3-pole and 4-pole breakers similar.
Return Busbar (not included with List AP)
Figure 5.6 Replacing a GJ/218 Circuit Breaker (1-Pole, 2-Pole, 3-Pole, 4-Pole) (List AM and List AP) (cont’d from previous page)
Page 53
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
45
5.6.4 Replacing a Distribution Panel (List AA, AB, AC, AD, AE, AF, AG, AH, AJ, AK, DA,
DB, DC, DD, BA, BB, BC, BD, BE, BF, BG, BH, AM, and AP)
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
Procedure
NOTE!
NOTE!
Removing the Distribution Panel
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the plastic shield covering the circuit breakers or fuseholders on the panel to be removed by loosening the screws
3. Disconnect all load or battery wiring from the circuit breaker or fuse positions.
4. On panels equipped with a ground busbar, remove all load return or battery return wiring from the ground busbar.
5. On panels equipped with shunts, label the shunt leads then remove them from the panel.
6. Locate the in-line FA/CBA connector located near the back of the panel, and separate the connector halves.
7. Refer to Figure 5.7 and remove the hardware securing the panel’s Ground Busbar (if equipped) to the distribution cabinet’s
8. For load distribution panels, refer to Figure 5.7 and remove the hardware securing the panel’s System Load Distribution
List AC shown in illustration, other Lists similar.
Refer to Figure 5.7 as this procedure is performed.
holding the shield and sliding the shield upwards.
busbar.
busbar to the distribution cabinet’s busbar.
9. For battery distribution panels, refer to Figure 5.7 and remove the hardware securing the panel’s Battery Busbar to the
distribution cabinet’s busbar.
10. For dual voltage load distribution panels, refer to Figure 5.7 and remove the hardware securing the -48V jumper leads.
11. Refer to Figure 5.7 and remove the hardware securing the distribution panel to the distribution cabinet. Remove the panel
from the distribution cabinet.
Installing the Distribution Panel
NOTE!
1. Orient the replacement distribution panel into distribution cabinet, checking to ensure no wires are pinched. Replace the
2. For dual voltage load distribution panels, replace the hardware securing the -48V jumper leads (1/4-20 bolt, 1/4” lock
3. For battery distribution panels, replace the hardware securing the panel’s Battery Busbar to the distribution cabinet’s
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
hardware securing the distribution panel to the distribution cabinet (10-32 x 5/8” bolt, #10 flat washer, 4-places).
washer, 1/4” flat washer. Torque to 84 in-lbs).
busbar (3/8-16 x 1-1/4” bolt, 3/8” Belleville lock washer, 3/8” hardened flat washer, 2-places. Torque to 180 in-lbs.)
Page 54
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
46
4. For load distribution panels, replace the hardware securing the panel’s System Load Distribution busbar to the distribution
cabinet’s busbar (1/4-20 x 1” bolt, 1/4” Belleville lock washer, 1/4” Belleville lock washer (concave side of Belleville lock washers face each other), 1/4” hardened flat washer, 2-places. Torque to 60 in-lbs).
5. Replace the hardware securing the panel’s Ground Busbar (if equipped) to the distribution cabinet’s busbar (1/4-20 x 1” bolt,
1/4” Belleville lock washer, 1/4” Belleville lock washer (concave side of Belleville lock washers face each other), 1/4” hardened flat washer, 2-places. Torque to 60 in-lbs).
6. Locate the in-line FA/CBA connector located near the back of the panel, and plug it into the mating connector half in the
distribution cabinet.
7. On panels equipped with shunts, reconnect the shunt leads.
WARNING! In the next step, observe correct polarity; otherwise equipment damage will result.
8. On panels equipped with a ground busbar, reconnect the load return or battery return wiring to the ground busbar.
9. Reconnect the load or battery wiring to the circuit breaker or fuse positions.
10. Transfer the plug-in circuit breakers or fuses from the old panel to the replacement panel.
11. Replace the plastic shield covering the circuit breakers or fuseholders on the replacement panel.
12. Verify no Circuit Breaker/Fuse Alarms are active.
13. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Page 55
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
47
Front Front
Battery
Distribution
Panel
Load
Distribution
Panel
Ground Busbar
Hardware
Ground Busbar
Hardware
Battery Busbar Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
Distribution Panel
Hardware
Shorting Block if 4th shelf
has Converter O ption.
If more than three shelves with the
Converter Option, /–48/ jumpers.
Assembly order is: lug, 1/4" flat washer, 1/4" lock washer,
1/4-20 nut. Torque to 84 in-lbs. Note that a shorting block
will be factory installed in this distribution device position.
/–48/ jumpers. Assembly order is: lug, 1/4" flat washer, 1/4" lock washer, 1/4-20 bolt. Torque to 84 in-lbs.
List DA Dual Voltage
Distribution Panel
(Lists DB, DC, and DD similar.)
Components removed in illustrations for clarity only.
List AC Shown, Other Lists Similar
Figure 5.7 Replacing a Distribution Panel (List AA, AB, AC, AD, AE, AF, AG, AH, AJ, AK, DA, DB, DC, DD, BA, BB, BC, BD, BE, BF,
BG, BH, AM, and AP)
Page 56
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
48

5.6.5 Replacing a Distribution Panel (List AL, AN, DE, DF, DG, DH, DJ, and DK)

DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
Procedure
NOTE!
Removing the Distribution Panel
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the plastic shield covering the circuit breakers or fuseholders on the panel to be removed by loosening the screws
3. Disconnect all load wiring from the circuit breaker or fuse positions.
4. Remove all load return wiring from the ground busbar (if present).
5. Locate the in-line FA/CBA connector located near the back of the panel, and separate the connector halves.
6. Refer to Figure 5.8 and remove the hardware securing the panel’s ground busbar (if present) to the distribution cabinet’s
7. Refer to Figure 5.8 and remove the hardware securing the panel’s system load distribution busbar to the distribution cabinet’s
8. For dual voltage load distribution panels, refer to Figure 5.8 and remove the hardware securing the -48V jumper leads.
9. Refer to Figure 5.8 and remove the hardware securing the distribution panel to the distribution cabinet. Remove the panel
Refer to Figure 5.8 as this procedure is performed.
holding the shield and sliding the shield upwards.
busbar.
busbar.
from the distribution cabinet.
Installing the Distribution Panel
NOTE!
1. Orient the replacement distribution panel into distribution cabinet, checking to ensure no wires are pinched. Replace the
2. For dual voltage load distribution panels, replace the hardware securing the -48V jumper leads. Torque per Figure 5.8.
3. Replace the hardware securing the panel’s system load distribution busbar to the distribution cabinet’s busbar. Torque per
4. Replace the hardware securing the panel’s ground busbar (if present) to the distribution cabinet’s busbar. Torque per Figure
5. Locate the in-line FA/CBA connector located near the back of the panel, and plug it into the mating connector half in the
6. On panels equipped with shunts, reconnect the shunt leads.
WARNING! In the next step, observe correct polarity; otherwise equipment damage will result.
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
hardware securing the distribution panel to the distribution cabinet. Torque per Figure 5.8.
Figure 5.8.
5.8.
distribution cabinet.
Page 57
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
49
7. Reconnect the load return wiring to the ground busbar (if present).
8. Reconnect the load wiring to the circuit breaker or fuse positions.
9. Transfer the plug-in circuit breakers or fuses from the old panel to the replacement panel.
10. Replace the plastic shield covering the circuit breakers or fuseholders on the replacement panel.
11. Verify no circuit breaker/fuse alarms are active.
12. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Page 58
50
Components removed in illustration for clarity only.
In-Line FA/CBA Connector
Ground Busbar Hardware
Distribution Panel Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
Front
Front
List DG (Lists DE , DF, DH, DJ, and DK similar.)
Rear
Connect “-48V” jumpers to an available landing here. Assembly order is: lug, 1/4" flat washer, 1/4" lock washer, 1/4-20 x 3/4” bolt. Torque to 84 in-lbs.
Lugs can be landed back-to-back.
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Figure 5.8 Replacing a Distribution Panel (List AL, AN, DE, DF, DG, DH, DJ, and DK)
Page 59
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
51
5.6.6 Replacing a Distribution Panel List AA, AB, AC, AD, AE, AF, AG, AH, AJ, AK, DA, DB,
DC, DD, BA, BB, BC, BD, BE, BF, BG, or BH with a List AL, AN, DE, DF, DG, DH, DJ, or DK
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
Procedure
Removing the Existing Distribution Panel
NOTE!
1. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2. Remove the plastic shield covering the circuit breakers or fuseholders on the panel to be removed by loosening the screws
3. Disconnect all load or battery wiring from the circuit breaker or fuse positions.
4. On panels equipped with a ground busbar, remove all load return or battery return wiring from the ground busbar.
5. On panels equipped with shunts, label the shunt leads then remove them from the panel.
6. Locate the in-line FA/CBA connector located near the back of the panel, and separate the connector halves.
7. Refer to Figure 5.9 and remove the hardware securing the panel’s Ground Busbar (if equipped) to the distribution cabinet’s
8. For load distribution panels, refer to Figure 5.9 and remove the hardware securing the panel’s System Load Distribution
9. For battery distribution panels, refer to Figure 5.9 and remove the hardware securing the panel’s Battery Busbar to the
10. For dual voltage load distribution panels, refer to Figure 5.9 and remove the hardware securing the -48V jumper leads.
Refer to Figure 5.9.
holding the shield and sliding the shield upwards.
busbar.
busbar to the distribution cabinet’s busbar.
distribution cabinet’s busbar.
11. Refer to Figure 5.9 and remove the hardware securing the distribution panel to the distribution cabinet. Remove the panel
from the distribution cabinet.
Replacing the Busbar
NOTE!
NOTE!
1. Perform the procedure in Figure 5.10.
Refer to Figure 5.10.
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
Page 60
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
52
Installing the New Distribution Panel
NOTE!
Refer to Figure 5.11.
NOTE!
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
1. Remove the plastic shield covering the circuit breakers or fuseholders on the replacement panel by loosening the screws
holding the shield and sliding the shield upwards.
2. For dual voltage load distribution panels, orient the replacement distribution panel into distribution cabinet. Secure the -
48V jumper leads to the rear of the panel as shown in
Figure 5.11. Torque per Figure 5.11.
3. Secure the replacement distribution panel to the distribution cabinet, ensuring no wires are pinched. Torque per Figure 5.11.
4. Replace the hardware securing the panel’s System Load Distribution busbar to the distribution cabinet’s busbar. Torque per
Figure 5.11.
5. Replace the hardware securing the panel’s Ground Busbar to the distribution cabinet’s busbar. Torque per Figure 5.11.
6. Locate the in-line FA/CBA connector located near the back of the panel, and plug it into the mating connector half in the
distribution cabinet.
WARNING! In the next step, observe correct polarity; otherwise equipment damage will result.
7. Refer to IM581127000 and connect load leads to the replacement panel.
8. Ensure appropriately sized circuit breakers or fuses are installed in the replacement panel.
9. Replace the plastic shield covering the circuit breakers or fuseholders on the replacement panel.
10. Verify no Circuit Breaker/Fuse Alarms are active.
11. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
Page 61
53
Figure 5.9 Removing the Existing Distribution Panel
Components removed in illustration for clarity only.
Front
List DB Dual Voltage Distribution Panel (other distribution panels similiar)
Ground Busbar Hardware
In-Line FA/CBA Connector
Distribution Panel Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
Front
Front
List DB Dual Voltage Distribution Panel (other distribution panels similiar)
-48V Jumpers
Battery Busbar Hardware (Battery Distribution Panel)
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 62
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
54
Apply electrical anti-oxidizing compound to busbar mating surfaces.
4-row distribution cabinet shown.
1, 2, or 3-row cabinet similar.
1. Remove this busbar.
Existing busbar.
New busbar.
2. Replace with new busbar. See SAG581127000 for part number.
3. New busbar installed view.
3/8-16 x 1-1/4” Bolt 3/8" Belleville Lock Washer 3/8" Belleville Lock Washer (concave side of Belleville Lock Washers face each other) 3/8" Hardened Flat Washer (2 places) Torque to 180 in-lbs.
Figure 5.10 Replacing the Busbar
Page 63
55
Components removed in illustration for clarity only.
In-Line FA/CBA Connector
Ground Busbar Hardware
Distribution Panel Hardware
Distribution Panel Hardware
System Load Distribution Busbar Hardware
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
1/4-20 x 1” Bolt 1/4” Belleville Lock Washer 1/4” Flat Washer Torque to 60 in-lbs.
10-32 x 5/8” Screw #10 Flat Washer Torque to 31 in-lbs.
Front
Front
List DG (Lists DE , DF, DH, DJ, and DK similar.)
Rear
Connect “-48V” jumpers to an available landing here. Assembly order is: lug, 1/4" flat washer, 1/4" lock washer, 1/4-20 x 3/4” bolt. Torque to 84 in-lbs.
Lugs can be landed back-to-back.
Figure 5.11 Installing the New Distribution Panel
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 64
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
56

5.6.7 Circuit Card Replacement Procedures

WARNING! Circuit cards used in this power system contain static-sensitive devices. Read the Static Warning at the front of
this document before performing any of the following procedures.
General
The following circuit card replacement procedures can be performed with the system operating.
Refer to Figure 3.1 for circuit card locations.
CAUTION! When performing any step in these procedures that requires removal or installation of hardware, use caution to
ensure no hardware is dropped and left inside the cabinet; otherwise service interruption or equipment damage may occur.
NOTE!
When performing any step in these procedures that requires removal of existing hardware, retain all hardware for use
in subsequent steps.
System Interface Circuit Card Replacement
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4. Remove the top and front panels to access the circuit cards at the bottom of the distribution cabinet.
5. Carefully label any wires connected to the customer connection terminal block on the circuit card. These wires must be
connected to the same terminals on the replacement circuit card. Refer to Figure 5.12.
6. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.12.
DANGER! In the next step, external wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
7. Remove the external wiring from the customer connection terminal block. DO NOT allow the bare wire end to contact any
grounded or energized object. Isolate the wire end with electrical tape. Repeat for each wire to be removed.
8. Unplug all connectors plugged into the circuit card.
9. Remove the screws securing the circuit card and remove the circuit card from the distribution cabinet.
10. In this step, ensure you do not intermix the old and replacement circuit cards. Set the shorting jumpers on the replacement
circuit card to match the locations on the old circuit card. Jumper settings are documented in the “Setting Jumpers and Switch Options” section of the Power System Installation Instructions (IM581127000).
Page 65
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
57
11. Slide the replacement circuit card into the mounting position inside the distribution cabinet, and secure with the screws
removed from the old circuit card.
12. Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
13. Reconnect the external wiring to the correct terminals on the customer connection terminal block. First remove the electrical
tape that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or energized object. After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be reconnected.
14. Remove the grounding wrist strap.
15. Reinstall the top and front panels that cover the circuit cards at the bottom of the distribution cabinet.
16. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
17. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
18. Ensure that there are no local or remote alarms active on the system.
Page 66
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
58
J1, J2, J3, J4 Distribution Panels FA Inputs
J8 Selects to power Controller from “Battery Power” or not.
Shorting Jumper
No
Battery
Pwr
Battery Pwr
External Internal
J8
J10
1 2 3
7 8 9
3 2 1
J10 Battery Monitoring External / Internal (see TB1-4 and TB1-5 for external monitoring points)
J5 CAN
TP3 (+) and TP4 (-) System Load Shunt Monitoring
TP1 (+) and TP2 (-) System Voltage Monitoring
TB1-1: Battery Tray FA
TB1-2: External Battery FA
TB1-3: External System FA
TB1-4: External Battery Monitoring (-)
TB1-5: External Battery Monitoring (+)
1
1A 2A 3A
1B 2B 3B
5
RS485 Connection TB2 1A: RS485+ TB2 2A: RS485-
RS232 Connection TB2 1B: CGND TB2 2B: TXD232 TB2 3B:RXD232
Shorting Jumper
J1
J2
J3
J4
J8
TB2
TB1
TP1 TP2 TP3 TP4
J10
J5
TB1 Wire Size Capacity: 22-12 AWG. Recommended Torque: 3.0 in-lbs. FA Signals: Battery applied to the terminal turns in an alarm.
Figure 5.12 System Interface Circuit Card Connector Locations
Page 67
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
59
IB2 (Controller Interface Board) and Optional EIB (Controller Extended Interface Board) Replacement
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4. Carefully label the wires connected to the customer connection terminal blocks on the circuit card. These wires must be
connected to the same terminals on the replacement circuit card. Refer to Figure 5.13 or Figure 5.14.
5. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.13 or Figure 5.14.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
6. Remove the external wiring from the customer connection terminal blocks. DO NOT allow the bare wire end to contact any
grounded or energized object. Isolate the wire end with electrical tape. Repeat for each wire to be removed.
7. Unplug all connectors plugged into the circuit card.
8. Remove the circuit card by removing the bracket the circuit card is mounted to. Remove the circuit card from the bracket.
9. In this step, ensure you do not intermix the old and replacement circuit cards. Set the switch on the replacement circuit card
to the same setting as the old circuit card. Switch settings are documented in the “Setting Jumpers and Switch Options” section of the Power System Installation Instructions (IM581127000).
10. Secure the replacement circuit card to the bracket, and re-install the circuit card and bracket into the distribution cabinet.
11. Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
12. Reconnect the external wiring to the correct terminals on the customer connection terminal block. First remove the electrical
tape that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or energized object. After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be reconnected.
13. Remove the grounding wrist strap.
14. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
15. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
16. Ensure that there are no local or remote alarms active on the system.
Page 68
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
60
J3-J9: Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
-
J12
*
RELAY
J1
SW1
7
J2
J11
J10
5 3
1
Relay Output Terminal Blocks
Digital Input Terminal Blocks
J9 J8 J7
J6
J5 J4
J3
8
6 4
2
8 7 6 5 4 3
2 1
+
IB2 Board (Top View)
NO
C
NC
NO C NC
NO
C
NC
NO C NC
NO
C
NC
NO C NC
NO
C
NC
NO C NC
5 3 1
46 2
5 3 1
46 2
5
3
1
46 2
5
3
1
46 2
5
3
1
46 2
5 3 1
46 2
5
3
1
46 2
Connector
to Controller
EX TEMP
PROBRE 1
EX TEMP
PROBE 2
IB2 Board Assembly
Figure 5.13 IB2 (Controller Interface Board) Connector Locations
Page 69
61
Figure 5.14 EIB (Controller Extended Interface Board) Connector Locations
Optional EIB Interface Board
(
T
op V
iew)
Optional EIB
Interface Board Assembly
SW1
J3 J4J2
J9J8J7J6J5
J5-J9 Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 70
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
62
SM-DU+ and Shunt Interface Assembly Replacement
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4. Carefully label the wires connected to the shunt input terminal blocks on circuit card. These wires must be connected to the
same terminals on the replacement circuit card. Refer to Figure 5.15.
5. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.15.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
6. Remove the external wiring from the shunt input terminal blocks. DO NOT allow the bare wire end to contact any grounded
or energized object. Isolate the wire end with electrical tape. Repeat for each wire to be removed.
7. Unplug all connectors plugged into the circuit card.
8. Remove the screw securing the SM-DU+ and Shunt Interface Assembly to the bottom of the distribution cabinet, and remove
the assembly.
9. SM-DU+: In this step, ensure you do not intermix the old and replacement circuit cards. Set the switches on the
replacement circuit card to the same settings as the old circuit card. Switch settings are documented in the “Setting Jumpers and Switch Options” section of the Power System Installation Instructions (IM581127000).
10. Slide the replacement SM-DU+ and Shunt Interface Assembly into the mounting position inside the distribution cabinet, and
secure with the screw removed from the old assembly.
11. Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
12. Reconnect the external wiring to the correct terminals on the shunt input terminal blocks. First remove the electrical tape
that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or energized object. After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be reconnected.
13. Remove the grounding wrist strap.
14. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
15. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
Page 71
63
Figure 5.15 SM-DU+ and Shunt Interface Assembly Connector Locations
TB1 - TB2 Wire Size Capacity: 16-26 AWG. Recommended Torque: 2.2 in-lbs.
SM-DU+ and
Shunt Interface Board
pow er can
RS48 5
RS48 5
SHUNT SHUNT FUSE
RS 232
SW1 SW2
J1
J7 J8 J6
J3 J4 J4A
J5
ON
OFF
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Red Indicator
Yellow Indicator
Green Indicator
Shunt Interface BoardSM-DU+
1A
1B
TB
1 TB2
J2J1
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
16. Ensure that there are no local or remote alarms active on the system.
Page 72
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
64
Optional LVD Driver and LVD Driver Lite Circuit Card Replacement
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4. If any of the low voltage disconnect contactors is open and it is desired to be closed, push the LVD Inhibit Switch located on
the circuit card to the UP position momentarily and then leave the switch in the middle (OFF) position.
5. Remove the top and front panels to access the circuit cards at the bottom of the distribution cabinet.
6. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.16 or Figure 5.17.
7. Unplug all connectors plugged into the circuit card.
8. Remove the screws securing the circuit card and remove the circuit card from the distribution cabinet.
9. Slide the replacement circuit card into the mounting position inside the distribution cabinet, and secure with the screws
removed from the old circuit card.
10. Ensure that the LVD Inhibit Switch is in the middle (OFF) position.
11. Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
12. Push the LVD Inhibit Switch to the down (ON) position.
13. Remove the grounding wrist strap.
14. Reinstall the top and front panels that cover the circuit cards at the bottom of the distribution cabinet.
15. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
16. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
17. Ensure that there are no local or remote alarms active on the system.
Page 73
65
Figure 5.16 Optional LVD Driver Circuit Card Connector Locations
J1, J2, J3 To LVLD contactor, uses Controller LVD1 control setting (Level 1).
J4, J5, J6 To LVLD contactor, uses Controller LVD2 control setting (Level 2).
J7 To LVBD contactor, uses Controller LVD2 control setting (Level 2).
Notes:
1. Connects up to (4) LVLD and (1) LVBD contactors.
J6
J5
J4
J3 J2 J1
J7
S1
DO NOT change a Low Voltage Load Disconnect contactor to LVD Control Level 2 (LVD2) if the system is furnished with a Low Voltage Battery Disconnect contactor.
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Page 74
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
66
Figure 5.17 Optional LVD Driver Lite Circuit Card Connector Locations
DO NO
T
change a Low Voltage Load Disconnect contactor to LVD Control Level 2 (LVD2) if the system is furnished with a Low V
oltage Battery Disconnect
contactor.
J1 To LVLD contactor
, uses Controller
LVD1 control setting (Level 1).
J3 To LVLD contactor, uses Controller LVD2 control setting (Level 2).
J2 To LVBD contactor
, uses Controller LVD2 control setting (Level 2). Can only be used if it is contained in a List 21 (1-row) cabinet.
Notes:
1. Connects up to (2) LVD contactors rated at 600 A or less.
2. Only one (1) contactor per level can be accommodated. J2 and J3 are on Level 2, only one (1) of these connectors can be used at a time.
J2
J3
J1
S1
Page 75
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
67
Optional Manual Battery Disconnect Circuit Card Replacement
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
WARNING! Damage to the circuit card may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4. Remove the top and front panels to access the circuit cards at the bottom of the distribution cabinet.
5. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on
the replacement circuit card. Refer to Figure 5.18.
6. Unplug all connectors plugged into the circuit card.
7. Remove the screws securing the circuit card and remove the circuit card from the distribution cabinet.
8. Place the replacement circuit card into the mounting position inside the distribution cabinet, and secure with the screws
removed from the old circuit card.
9. Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.
10. Remove the grounding wrist strap.
11. Reinstall the top and front panels that cover the circuit cards at the bottom of the distribution cabinet.
12. Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.
13. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
14. Ensure that there are no local or remote alarms active on the system.
Page 76
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
68
J1
J2
S1
Figure 5.18 Optional Manual Battery Disconnect Circuit Card Connector Locations
Page 77
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
69

5.6.8 Replacing a Battery or Load Disconnect Contactor

DANGER! All sources of AC and DC power must be completely disconnected from this power system before performing this
procedure. Use a voltmeter to verify no DC voltage is present on the system busbars before proceeding.
NOTE!
In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-
oxidizing compound to the mating surfaces of the busbars.
Procedure
NOTE!
Refer to Figure 5.19, Figure 5.20, Figure 5.21, or Figure 5.22 as this procedure is performed.
Removing the Contactor
1. Verify all AC and DC power sources are disconnected from the power system.
2. For the 1-row distribution cabinet, the contactor can be accessed from the top of the distribution cabinet. For the 2, 3, or 4-
row distribution cabinet, the contactor can be accessed from the rear (and top) of the distribution cabinet.
3. For the 2, 3, or 4-row distribution cabinet, remove the distribution cabinet’s rear access panel(s).
4. Disconnect the wiring to the contactor by unplugging the quick disconnects.
5. Note the orientation of the contactor to ensure the replacement is installed the same way. Unbolt the contactor (4-places)
and remove. Save all hardware.
Installing the Replacement Contactor
6. Position the replacement contactor oriented the same way as the old.
7. Secure the contactor with the hardware removed above. Refer to Figure 5.19, Figure 5.20, Figure 5.21, or Figure 5.22 for
hardware build-up and recommended torque.
8. Replace the wiring to the contactor by plugging-in the quick disconnects. Refer to Figure 5.19, Figure 5.20, Figure 5.21, or
Figure 5.22.
9. For the 2, 3, or 4-row distribution cabinet, replace the distribution cabinet’s rear access panel(s).
Restarting the Power System
10. Reconnect the AC and DC power sources to the power system.
11. Start the power system. Refer to the separate Installation Instructions (IM581127000) for a startup procedure.
12. Verify no alarms are active.
Page 78
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
70
Battery Disconnect Contactor
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Components removed in illustration for clarity only.
Contactor styles vary between manufacturer’s.
Front
5/16-18 x 1” Bolt 5/16" Belleville Lock Washer 5/16" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
5/16" Hardened Flat Washer
(4 places)
Torque to 100 in-lbs.
White/Black Wire
Brown Wire
Brow n/W hite Wire
Red/White Wire
Brown Wire
Brow n/W hite Wire
White/Black Wire
Red/White Wire
Figure 5.19 Replacing a Battery Disconnect Contactor in a 1-Row Distribution Cabinet
Page 79
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
71
Battery Disconnect Contactor
Apply electrical anti-oxidizing compound to busbar mating surfaces.
Components removed in illustration for clarity only.
Front
2-row Distribution Cabinet shown, 3 or 4-row cabinet similar.
Shown being removed from front for clarity only. Removal is from rear.
1/2-13 x 1-1/4” Bolt 1/2" Belleville Lock Washer 1/2" Belleville Lock Washer (concave side of Belleville Lock Washers face each other) 1/2" Hardened Flat Washer (4 places) Torque to 500 in-lbs.
White/Black Wire
Brown Wire
Brow n/W hite Wire
Red/White
Wire
Figure 5.20 Replacing a Battery Disconnect Contactor in a 2, 3, or 4-Row Distribution Cabinet
Page 80
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
72
Load Disconnect Contactor
Components removed in illustration for clarity only.
Front
5/16-18 x 1” Bolt 5/16" Belleville Lock Washer 5/16" Belleville Lock Washer (concave side of Belleville Lock Washers face each other) 5/16" Hardened Flat Washer (4 places) Torque to 100 in-lbs.
Apply electrical anti-oxidizing compound to busbar mating surfaces.
Contactor styles vary between manufacturer’s.
Black Wire
Violet/White Wire
Violet W ire
Red Wire
Violet/White Wire
Violet W ire
Black Wire
Red Wire
Figure 5.21 Replacing a Load Disconnect Contactor in a 1-Row Distribution Cabinet
Page 81
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
73
Load Disconnect
Contactor
2-row Distribution Cabinet shown, 3 or 4-row cabinet similar.
Apply electrical anti-oxidizing
compound to busbar
mating surfaces.
5/16-18 Nut 5/16" Belleville Lock Washer 5/16" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
5/16" Hardened Flat Washer
(4 places)
Torque to 100 in-lbs.
Components removed in illustration for clarity only.
Front
Contactor styles vary between manufacturer’s.
Black Wire
Violet/White Wire
Violet W ire
Red Wire
Violet/White Wire
Violet W ire
Black Wire
Red Wire
Figure 5.22 Replacing a Load Disconnect Contactor in a 2, 3, or 4-Row Distribution Cabinet
Page 82
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
74
This page intentionally left blank
Page 83
Vertiv™ NetSure™ 710NPBA +24 VDC Power System User Manual
Connect with Vertiv on Social Media
https://www.facebook.com/vertivI
https://www.instagram.com/vertiv/
https://www.linkedin.com/company/vertiv/
https://www.twitter.com/vertiv/
Page 84
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.
UM581127000 _REVP
Loading...