This installation manual describes the installation methods and precautions related to the remote control. Use this
manual together with the user’s manuals for the indoor unit, outdoor unit and other option equipment. Please read
this manual carefully before starting the installation work to install the unit properly.
Safety precautions
●
Please read this manual carefully before starting installation work to install the unit properly.
Every one of the followings is important information to be observed strictly.
WARNING
CAUTION
It could have serious consequences depending on the circumstances.
●
The following pictograms are used in the text.
Never do.Always follow the instructions given.
●
Keep this manual at a safe place where you can consult with whenever necessary. Show this manual to installers
when moving or repairing the unit. When the ownership of the unit is transferred, the “Installation Manual”
should be given to a new owner.
Failure to follow these instructions properly may result in serious consequences such as
death, severe injury, etc..
Failure to follow these instructions properly may cause injury or property damage.
WARNING
Ask a professional contractor to carry out installation work according to the installation manual.
Improper installation work may result in electric shocks, fire or break-down.
Shut OFF the main power source before starting electrical work.
Otherwise, it could result in electric shocks, break-down or malfunction.
Do not install the unit in appropriate environment or where inflammable gas could generate, flow
in, accumulate or leak.
If the unit is used at places where air contains dense oil mist, steam, organic solvent vapor, corrosive
gas (ammonium, sulfuric compound, acid, etc) or where acidic or alkaline solution, special spray, etc.
are used, it could cause electric shocks, break-down, smoke or fire as a result of significant
deterioration of its performance or corrosion.
Do not install the unit where water vapor is generated excessively or condensation occurs.
It could cause electric shocks, fire or break-down.
Use the specified cables for wiring, and connect them securely with care to protect electronic
parts from external forces.
Improper connections or fixing could cause heat generation, fire, etc.
Seal the inlet hole for remote control cable with putty.
If dew, water, insect, etc. enters through the hole, it could cause electric shocks, fire or break-down.
-
-
76
Page 3
'15 • PAC-T-236
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress
electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power
generator, high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could
disrupt medical activities, video broadcasting or cause noise interference.
CAUTION
Do not install the remote control at following places.
It could cause break-down or deformation of remote control.
(1)Where it is exposed to direct sunlight
(2)Near the equipment to generate heat
(3)Where the surface is not flat
Do not leave the remote control with its upper case removed.
When the upper case is removed, put it in a packing box or packing bag to protect internal PCBs or
other parts from dust, moisture, etc.
-
77
-
Page 4
2 . Accessories & prepare on site
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
'15 • PAC-T-236
Accessories
Parts procured at site
Switch box
For 1 piece or 2 pieces (JIS C 8340 or
equivalent)
(JIS C 8305 or equivalent)
Lock nut, bushing (JIS C 8330 or equivalent)
Lacing (JIS C 8425 or equivalent)
PuttySuitably For sealing gaps
Molly anchor
R/C cable (0.3 mm2 x 2 pcs)
R/C main unit, wood screw (ø3.5 x 16) 2 pcs
User’s Manual, Installation Manual
Item nameQ’tyRemark
1
These are not required when installing
As required
As required
As required
As required
As required
directly on a wall.Thin wall steel pipe for electric appliance
Necessary to run R/C cable on the wall.
See right table when longer than 100 m
When the cable length is longer than
100 m, the max size for wires used
in the R/C case is 0.5 mm
them to wires of larger size near
the outside of R/C. When wires are
connected, take measures to prevent
water, etc. from entering inside.
< 200 m0.5 mm2 x 2-core
< 300 m0.75 mm
< 400 m1.25 mm
< 600 m2.0 mm
3. Remote control installation procedure
Determine where to install the remote control
2
. Connect
2
x 2-core
2
x 2-core
2
x 2-core
Installation“Using a switch box”
“Installed directly on a wall”
Wiring direction“Backward”
“Upper center”, “Upper left”
Cautions for selecting installation place
(1) Installation surface must be flat and sufficiently strong.
R/C case must not be deformed.
(2) Where the R/C can detect room temperatures accurately.
This is a must when detecting room temperatures with
the temperature sensor of R/C.
· Install the R/C where it can detect the average temperature in the room.
· Install the R/C separated from a heat source sufficiently.
· Install the R/C where it will not be influenced by the
turbulence of air when the door is opened or closed.
Select a place where the R/C is not exposed to direct
sunlight or blown by winds from the air- conditioner or
temperatures on the wall surface will not deviate largely
from actual room temperature.
Installation space
30mm
Wiring
120mm
30mm
30mm
R/C temperature sensor
Secure minimum spaces for
disassembling the case.
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped
screwdriver, 50mm or
more is available.
-
78
-
Page 5
'15 • PAC-T-236
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Request
Be sure not to install R/C at a place where temperatures around the installation surface of R/C may differ largely from
actual room temperature.
Difference between detected temperature and actual room temperature could cause troubles.
The correction for detected temperature by the R/C cannot offset such temperature difference because it corrects the
detected temperatures itself.
Request
Do not install the R/C at a place where it is exposed to direct sunlight or where surrounding air temperature exceeds 40°C
or drops below 0°C.
It could cause discoloration, deformation, malfunction or breakdown.
Installation procedure
Dimensions (Viewed from front)
18.383.5
Fixing holes
372323
120
①
To remove the upper case from the bottom cases of R/C
120
· Insert the tip of flat head screwdriver or the like in the
recess at the lower part of R/C and twist it lightly to
remove.
Take care to protect the removed upper case
from moisture or dust.
19
PCB side (Viewed from rear)
Sensor
USB port
Terminal Block
②
Connect wires from X and Y terminals of R/C to X and Y
terminals of indoor unit.
R/C wires (X, Y) have no polarity.
In case of embedding wiring
③
Embed the switch box and the R/C wires beforehand.
(When the wiring is retrieved “Backward”)
Seal the inlet hole for the R/C wiring with putty.
If dust or insect enters, it could cause electric shocks,
●
fire or breakdown.
-
79
Wall
Bushing
50
8
200
-
Conduit
Locknut
Switch box
Seal with putty
R/C cable
Page 6
④
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When wires are passed through the bottom case, fix the bottom case at 2 places on the switch box.
Upper side
Bottom case
Switch box
for 1 pc
Upper side
Switch box
for 2 pcs
Bottom case
'15 • PAC-T-236
Cut out the thin
wall part at the
screw mounting
section with a
knife or the like
before tightening
the screw.
Downside
Wire outlet
⑤
When fixing the bottom case diagonally at 2 places, cut out the
thin wall section on the case.
⑥
Fix wires such that the wires will run around the terminal screws
on the top case of R/C.
Cautions for wire connection
Use wires of no larger than 0.5 mm2 for
wiring running through the remote
control case, Take care not to pinch
the sheath.
Tighten by hand (0.7 N·m or less)
the wire connection. If the wire is
connected using an electric driver, it
may cause failure or deformation.
⑦
Install the upper case with care not to pinch wires of R/C.
In case of exposing wiring
③
Cut out the thin wall sections on the cases for the size of wire.
Upper center
(When the wiring is taken out from the “upper center” or “upper left” of R/C)
Downside
Wire outlet
Wiring hole on bottom case
When taking the wiring out from the upper center,
open a hole before separating the upper and
bottom cases. This will reduce risk of damaging
the PCB and facilitate subsequent work.
Upper case
Upper left
-
80
When taking the wiring out from the upper left,
take care not to damage the PCB and not to
leave any chips of cut thin wall inside.
Bottom case
-
Page 7
If the hole is cut too large, moisture, dust or insects may enter.
○○
○○
○−
○−
○−
○−
○−
○−
○−
○○
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Seal gaps with putty or the like.
④
Fix the bottom R/C case on a
flat surface with wood screws.
⑤
In case of the upper center,
pass the wiring behind
the bottom case. (Hatched
section)
⑥
Fix wires such that the wires
120mm
(for retrieving
wire from
upper left)
will run around the terminal
screw of the top case of R/C.
⑦
Install the top case with care
not to pinch wires of R/C.
'15 • PAC-T-236
190mm
(for retrieving wire
from upper center)
8
Main/Sub setting when more than one remote control are used
Main-Sub setting for use of two or more R/C
Up to two units of R/C can be used at the maximum for 1 indoor unit or 1 group.
One is main R/C and the other is sub R/C.
Operating range is different depending on the main or sub R/C.
R/C functionMainSub
Indoor unit
X Y
R/C cable (No polarity)
X Y
R/C
“Main”
Set the “Main” and “Sub” as described at Section 7
of installtion manual attached to the remote control.
X Y
R/C
“Sub”
Run/Stop, setting temperature, fan speed and flap
direction operations
High power and energy-saving operations
Energy-saving setting
R/C sensor
Test run menu operation
Room temperature range setting
Indoor unit settings
Individual flap control
Operation data display
Error history display
-
81
-
Page 8
Note: Connection to personal computer
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
It can be set from a personal computer via the USB port (mini-B).
Connect after removing the cover for USB port of upper case.
Replace the cover after use.
If dust, insect, etc. enters, it could cause electric
shocks or breakdown.
Special software is necessary for the connection.
For details, view the web site or refer to the engineering data.
Do not connect to a personal computer
without using the special software.
Do not connect the personal computer to the USB
simultaneously with other USB devices.
It could cause malfunction or breakdown of R/C or
personal computer.
'15 • PAC-T-236
USB port
Cover
Note: Initializing of password
Administrator password (for daily setting items) and service password (for installation, test
run and maintenance) are used.
The administrator password at factory default is “0000”. This setting can be changed
(Refer to User's Manual). When the administrator password is forgotten, it can be
initialized, if the [High power] and the [Energy-saving] buttons are pushed simultaneously
for 5 seconds on the administrator password input screen.
Service password is “9999”, which cannot be changed.
When the administrator password is input, the service password is also accepted.
-
82
-
Page 9
'15 • PAC-T-236
Installation manual for wired remote controller
Installation and wiring of remote control
Wiring of remote control should use 0.3mm
2
s 2 core wires or cables. (on-site configuration)
Maximum prolongation of remote control wiring is 600 m.
100 - 200m
.........................
0.5mm
2
s 2 cores
Under 300m
.......................
0.75mm
2
s 2 cores
Under 400m
.......................
1.25mm
2
s 2 cores
Under 600m
.......................
2.0mm
2
s 2 cores
Master/ slave setting when more than one remote controls are used
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
Remote control cord (no polarity)
Remote control
SW1 "Master"
SwitchSettingContents
MMaster remote control
SW1
SSlave remote control
The indication when power source is supplied
When power source is turned on, the following is displayed on the remote control until the communication between the remote control and indoor unit settled.
Master remote control : " "
Slave remote control : " "
At the same time, a mark or a number will be displayed for two seconds first.
This is the software's administration number of the remote control, not an error cord.
When remote control cannot communicate with the indoor unit for half an hour, the below indication willappear.Check wiring of the indoor unit and the outdoor unit etc.
Connect the remote control cord to the terminal block.Connect the terminal of remote control (X,Y) with the terminal of indoor unit (X,Y).(X and Y are no polarity)Wiring route is as shown in the right diagram depending on the pulling out direction.
The wiring inside the remote control case should be within 0.3mmThe sheath should be peeled off inside the remote control case.
The peeling-off length of each wire is as below.
Pulling out from upper left
Pulling out from upper center
X wiring : 215mmY wiring : 195mm
X wiring : 170mmY wiring : 190mm
Install the upper case as before so as not to catch up the remote control cord, and tighten with the screws.In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.
In case of pulling out from
upper left
WiringWiring
UpperUpper
Board
Lower
If the prolongation is over 100m, change to the size below.But, wiring in the remote control case should be under 0.5mm
2
. Change the wire size outside of the case according to wire connecting. Waterproof treatment is necessary at the wire connecting section. Be careful about contact failure.
Remote control
SW1 "Slave"
Master
Slave
The left mark is only an example. Other marks may appear.
Indoor units
Set SW1 to "Slave" for the slave remote control. It was factory set to "Master" for shipment.
Note: The setting "Remote control thermistor enabled" is only selectable with the master remote control in
the position where you want to check room temperature.The air-conditioner operation follows the last operation of the remote control regardless of the master/ slave setting of it.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
(2) Model RC-E5
PJA012D730
Read together with indoor unit's installation manual.
WARNING
Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the
terminal.
Loose connection or hold will cause abnormal heat generation or fire.
Make sure the power source is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
CAUTION
DO NOT install the remote control at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight
(2) Places near heat devices
(3) High humidity places
DO NOT leave the remote control without the upper case.
In case the upper cace needs to be detached, protect the remote control with a packaging box or bag in
order to keep it away from water and dust.
(4) Hot surface or cold surface enough to generate condensation
Prepare on siteRemote control cord (2 cores) the insulation thickness in 1mm or more.
[In case of embedding cord] Erectrical box, M4 screw (2 pieces)
[In case of exposing cord] Cord clamp (if needed)
Installation procedure
Open the cover of remote control, and remove the screw under the
buttons without fail.
Remove the upper case of remote control.
Insert a flat-blade screwdriver into the dented part of the upper part
of the remote control, and wrench slightly.
Screw
[In case of embedding cord]
Embed the erectrical box and remote control cord beforehand.
Control cord
Prepare two M4 screws (recommended length is 12-16mm) on site, and install the lower case to erectrical box.
Choose either of the following two positions in fixing it with screws.
Upper part
Lower caseLower case
Upper part
Tighten the screws after
cutting off the thin part of
screw mounting part.
Wiring oulet
Lower part
Wiring oulet
Lower part
Connect the remote control cord to the terminal block.
Connect the terminal of remote control (X,Y) with the terminal of
indoor unit (X,Y). (X and Y are no polarity)
Install the upper case as before so as not to catch up the remote control cord,
and tighten with the screws.
[In case of exposing cord]
You can pull out the remote control cord from left upper part or center upper part.
Cut off the upper thin part of remote control lower case with a nipper or knife,
and grind burrs with a file etc.
Install the lower case to the flat wall with attached two wooden screws.
-
-
83
M4 screw 2 (Prepare on site)
The thin part
Lower case
Lower
Upper
Lower case
Lower
Erectrical box
(Prepare on site)
Upper
Page 10
'15 • PAC-T-236
The range of temperature setting
When shipped, the range of set temperature differs depending on the operation mode as below.
Upper limit and lower limit of set temperature can be changed with remote control.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30˚C (68
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26°C (6279°F).When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote control function of function setting mode is "INDN CHANGE" (factory setting),
During heating, you cannot set the value exceeding the upper limit.
During operation mode except heating, you cannot set the value below the lower limit.
2. When TEMP RANGE SET, remote control function of function setting mode is "NO INDN CHANGE"
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.But, the indication is the same as the temperature set.
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.But, the indication is the same as the temperature set.
How to set upper and lower limit value
1. Stop the air-conditioner, and press (SET) and (MODE) button at the same time for over three seconds.
The indication changes to "FUNCTION SET ".
2. Press button once, and change to the "TEMP RANGE " indication.
3. Press (SET) button, and enter the temperature range setting mode.
4. Select "UPPER LIMIT " or "LOWER LIMIT " by using button.
5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Press (SET) button to fix. Indication example: "UPPER 26˚C" (Displayed for two seconds)After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Indication: " SET UP" "LOWER 18˚C "
8. Press ON/OFF button to finish.
If upper limit value is set
If upper limit value is set
If lower limit value is set
If lower limit value is set
Indication: " SET UP" "UPPER 30˚C "
Select the upper limit value with temperature setting button . Indication example: "UPPER 26˚C "(blinking)
Select the lower limit value with temperature setting button . Indication example: "LOWER 24˚C " (blinking)
Press (SET) button to fix. Indication for example: "LOWER 24˚C" (Displayed for two seconds)
After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT ".
It is possible to finish by pressing ON/OFF button on the way, but unfinished change of setting is unavailable.
During setting, if you press(RESET) button, you return to the previous screen.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Board
Sheath
Upper case
Connect the remote control cord to the
terminal block.
Connect the terminal of remote control (X,Y)
with the terminal of indoor unit (X,Y).
UpperUpper
Board
Sheath
Upper case
(X and Y are no polarity)
Wiring route is as shown in the right diagram
depending on the pulling out direction.
The wiring inside the remote control case should be within 0.3mm
The sheath should be peeled off inside the remote control case.
The peeling-off length of each wire is as below.
Pulling out from upper left
X wiring : 215mm
Y wiring : 195mm
Pulling out from upper center
X wiring : 170mm
Y wiring : 190mm
Install the upper case as before so as not to catch up the remote control cord, and tighten with
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.
Lower
In case of pulling out from
upper left
WiringWiring
2
(recommended) to 0.5mm2.
Installation and wiring of remote control
2
Wiring of remote control should use 0.3mm
s 2 core wires or cables. (on-site configuration)
Maximum prolongation of remote control wiring is 600 m.
If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm
2
. Change the wire size outside of
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
100 - 200m
Under 300m
Under 400m
Under 600m
.........................
.......................
.......................
.......................
Master/ slave setting when more than one remote controls are used
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
0.5mm
0.75mm
1.25mm
2.0mm
2
s 2 cores
2
s 2 cores
2
s 2 cores
2
s 2 cores
SwitchSettingContents
Indoor units
Remote control
SW1 "Master"
SW1
Remote control cord (no polarity)
Remote control
SW1 "Slave"
MMaster remote control
SSlave remote control
Master
Slave
Set SW1 to "Slave" for the slave remote control. It was factory set to "Master" for shipment.
Note: The setting "Remote control thermistor enabled" is only selectable with the master remote control in
the position where you want to check room temperature.
The air-conditioner operation follows the last operation of the remote control regardless of the
master/ slave setting of it.
Lower
In case of pulling out from
upper center
The peeling-off length
of sheath
Upper
Board
Lower
The indication when power source is supplied
When power source is turned on, the following is displayed on the remote control until the
communication between the remote control and indoor unit settled.
Master remote control : " "
Slave remote control : " "
At the same time, a mark or a number will be displayed for two seconds first.
This is the software's administration number of the remote control, not an error cord.
When remote control cannot communicate with the indoor unit for half an hour, the below indication will
appear.
Check wiring of the indoor unit and the outdoor unit etc.
The left mark is only an
example. Other marks may
appear.
-
-
84
Page 11
The range of temperature setting
PJA012D730
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When shipped, the range of set temperature differs depending on the operation mode as below.
Upper limit and lower limit of set temperature can be changed with remote control.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30˚C (68
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26°C (62
79°F).
When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote control function of function setting mode is "INDN CHANGE" (factory setting),
If upper limit value is set
During heating, you cannot set the value exceeding the upper limit.
If lower limit value is set
During operation mode except heating, you cannot set the value below the lower limit.
2. When TEMP RANGE SET, remote control function of function setting mode is "NO INDN CHANGE"
If upper limit value is set
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
If lower limit value is set
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
How to set upper and lower limit value
1. Stop the air-conditioner, and press (SET) and (MODE) button at the same time for over three
seconds.
The indication changes to "FUNCTION SET ".
2. Press button once, and change to the "TEMP RANGE " indication.
3. Press (SET) button, and enter the temperature range setting mode.
4. Select "UPPER LIMIT " or "LOWER LIMIT " by using button.
5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Indication: " SET UP" "UPPER 30˚C "
Select the upper limit value with temperature setting button . Indication example: "UPPER 26˚C "
(blinking)
Press (SET) button to fix. Indication example: "UPPER 26˚C" (Displayed for two seconds)
After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Indication: " SET UP" "LOWER 18˚C "
Select the lower limit value with temperature setting button . Indication example: "LOWER 24˚C "
(blinking)
Press (SET) button to fix. Indication for example: "LOWER 24˚C" (Displayed for two seconds)
After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT ".
8. Press ON/OFF button to finish.
to
86˚F).
'15 • PAC-T-236
to
It is possible to finish by pressing
ON/OFF button on the way, but
unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the
previous screen.
-
85
Previous button
-
Page 12
To next page
To next page
The functional setting
The initial function setting for typical using is performed automatically by the indoor unit connected, when remote
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
control and indoor unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “ ”, set your desired setting as for the selected item.
The procedure of functional setting is shown as the following diagram.
[Flow of function setting]
Start : Stop air-conditioner and press “” (SET) and
Finalize : Press “” (SET) button.
Reset : Press “” (RESET) button.
Select : Press button.
End: Press ON/OFF button.
It is possible to finish above setting on the way,
and unfinished change of setting is unavailable.
“ ” : Initial settings
“ ” : Automatic criterion
“” (MODE) buttons at the same time for over three seconds.
Stop air-conditioner and press
(SET) + (MODE) buttons
at the same time for over three seconds.
(Remote control function)
01
02
04
05
06
07
08
09
10
Function
setting
Validate setting of ESP:External Static Pressure
Invalidate setting of ESP
Automatical operation is impossible
Temperature setting button is not working
Mode button is not working
On/Off button is not working
Fan speed button is not working
Louver button is not working
Timer button is not working
Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for producing +3.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing +2.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing +1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0˚C increase in temperature.
'15 • PAC-T-236
Record and keep the
setting
Consult the technical data etc. for each control details
11
In case of Single split series, by connecting ventilation device to CNT of the
indoor printed circuit board (in case of VRF series, by connecting it to CND of the
indoor printed circuit board), the operation of ventilation device is linked with the
operation of indoor unit.
In case of Single split series, by connecting ventilation device to CNT of the indoor printed
circuit board (in case of VRF series, by connecting it to CND of the indoor printed circuit
12
13
14
15
16
17
18
19
board), you can operate /stop the ventilation device independently by (VENT) button.
If you change the range of set temperature, the indication of set temperature
will vary following the control.
If you change the range of set temperature, the indication of set temperature
will not vary following the control, and keep the set temperature.
Airflow of fan becomes of - - or the four speed of - - - .
Airflow of fan becomes of - .
Airflow of fan becomes of - .
Airflow of fan is fixed at one speed.
If you change the remote control function "14 ",
you must change the indoor function "04 " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.
If you input signal into CNT of the indoor printed circuit board from external, the
indoor unit will be operated independently according to the input from external.
If you input into CNT of the indoor printed circuit board from external, all units which
connect to the same remote control are operated according to the input from external.
In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote control can be indicated.)
Heating preparation indication should not be indicated.
Temperature indication is by degree C
Temperature indication is by degree F
ON/OFF button
(finished)
-
86
-
Page 13
'15 • PAC-T-236
tent operation for five minutes
tent operation for five minutes
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
From previous page
(Indoor unit function)
Indoor unit No. are indicated only when
plural indoor units are connected.
To set other indoor unit, press
AIRCON
NO. button, which
allows you to go back to the indoor
unit selection screen
(for example: I/U 000 ).
Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table.
Function No.
Remote control
function02
Remote control
function06
Remote control
function07
Remote control
function13
Remote control
function15
Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit.
But only master indoor unit is received the setting change of indoor unit function “05 EXTERNAL INPUT” and “06 PERMISSION /
PROHIBISHION”.
Function
02
03
04
05
Item
setting
DefaultModel
The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then the indoor unit will be stopped by
compulsion after 24 hours.
If you change the indoor function "04 ",
you must change the remote control function "14 " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.
"Auto-RUN" mode selectable indoor unit.
Indoor unit without "Auto-RUN" mode
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting
Indoor unit with only one of air flow setting
Heat pump unit
Exclusive cooling unit
Note2: Fan setting of "HIGH SPEED"
Fan tap
UH - Hi - Me - Lo
STANDARD
FAN
SPEED
HIGH
SET
SPEED1, 2
Initial function setting of some indoor unit is "HIGH SPEED".
4 speed is not able to be set with wireless remote control.
UH - UH - Hi - Me
Indoor unit air flow setting
Hi - Me - Lo
Hi - LoHi - Me
UH - Hi UH - MeUH - Hi - Me
06
07
Permission/prohibition control of operation will be valid.
With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately.
-------
From previous page
To be reset for producing +3.0˚C increase in temperature during heating.
To be reset for producing +2.0˚C increase in temperature during heating.
08
09
10
11
12
13
14
15
16
17
To be reset for producing +1.0˚C increase in temperature during heating.
To be reset producing +2.0˚C increase in return air temperature of indoor unit.
To be reset producing +1.5˚C increase in return air temperature of indoor unit.
To be reset producing +1.0˚C increase in return air temperature of indoor unit.
To be reset producing -1.0˚C increase in return air temperature of indoor unit.
To be reset producing -1.5˚C increase in return air temperature of indoor unit.
To be reset producing -2.0˚C increase in return air temperature of indoor unit.
When heating thermostat is OFF, fan speed is low speed.
When heating thermostat is OFF, fan speed is set speed.
When heating thermostat is OFF, fan speed is operated intermittently.
When heating thermostat is OFF, the fan is stopped.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set "FAN OFF" when the indoor unit's thermistor is working.
Change of indoor heat exchanger temperature to start frost prevention control.
Working only with the Single split series.
To control frost prevention, the indoor fan tap is raised.
Drain pump is run during cooling and dry.
Drain pump is run during cooling, dry and heating.
Drain pump is run during cooling, dry, heating and fan.
Drain pump is run during cooling, dry and fan.
After cooling is stopped, the fan does not perform extra operation.
After cooling is stopped, the fan perform extra operation for half an hour.
After cooling is stopped, the fan perform extra operation for an hour.
After cooling is stopped, the fan perform extra operation for six hours.
After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for six hours.
During heating is stopped or heating thermostat is OFF, the fan perform intermit
with low fan speed after twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermit
with low fan speed after five minutes' OFF.
Connected “OA Processing” type indoor unit, and is automatically defined.
-
87
-
Page 14
'15 • PAC-T-236
PJA012D730
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
How to set function
Stop air-conditioner and press (SET) (MODE)
1.
buttons at the same time for over three seconds, and the
"FUNCTION SET " will be displayed.
Press (SET) button.
2.
3.
Make sure which do you want to set, " FUNCTION "
(remote control function) or "I/U FUNCTION " (indoor unit
function).
4.
Press or button.
Selecct " FUNCTION " (remote control function) or "I/U
FUNCTION " (indoor unit function).
5.
Press (SET) button.
6.
On the occasion of remote control function selection
"DATA LOADING" (Indication with blinking)
Display is changed to "01 ".
Press or button.
"No. and function"are indicated by turns on the remote control
function table, then you can select from them.
(For example)
Function No.
Function
Press (SET) button.
The current setting of selected function is indicated.
(for example) "AUTO RUN ON" If "02 AUTO RUN SET" is
selected
Setting
Press or button.
Select the setting.
Press (SET)
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, Set as the
same procedure if you want to set continuously ,and if to
finish, go to 7.
Press ON/OFF button.
7.
Setting is finished.
Operation message
Function description: ,
setting description:
1
6
On the occasion of indoor unit function selection
"DATA LOADING" (Blinking for 2 to 23 seconds to read the data)
Indication is changed to "02 FAN SPEED SET".
Go to .
[Note]
(1)
If plural indoor units are connected to a remote control,
the indication is "I/U 000" (blinking) The lowest number of
the indoor unit connected is indicated.
Press or button.
(2)
Select the number of the indoor unit you are to set
If you select "ALL UNIT ", you can set the same setting with
all unites.
(3)
Press (SET) button.
Press or button.
"No. and function" are indicated by turns on the indoor unit function
table, then you can select from them.
(For example)
Press (SET) button.
The current setting of selected function is indicated.
(For example) "STANDARD" If "02 FAN SPEED SET" is
selected.
Press or button.
Select the setting.
Press (SET) button.
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, set as the same
procedure if you want to set continuously , and if to finish, go to 7.
Function No.
Previous screen buttonIndoor unit selection button
Function No.
Function
Setting
Fixing button
Finishing button
7
Starting button
2
It is possible to finish by pressing ON/OFF button on the way, but unfinished change of setting is
unavailable.
During setting, if you press (RESET) button, you return to the previous screen.
Setting is memorized in the control and it is saved independently of power failure.
How to check the current setting
When you select from "No. and funcion" and press set button by the previous operation, the "Setting" displayed first is the current
setting.
(But, if you select "ALL UNIT ", the setting of the lowest number indoor unit is displayed.)
-
88
When plural indoor units are connected to a remote control, press
the AIRCON NO. button, which allows you to go back to the
indoor unit selection screen. (example "I/U 000 ")
-