Mitsubishi Electric RC-EX1A Installation Manual

Installation of wired remote control (Option)
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1.9.3
(1) Model RC-EX1A
'15 • PAC-T-236
PJZ012D077
B
RC-EX1A
INSTALLATION MANUAL
-
75
-
'15 • PAC-T-236
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1 . Safety precautions
This installation manual describes the installation methods and precautions related to the remote control. Use this manual together with the user’s manuals for the indoor unit, outdoor unit and other option equipment. Please read this manual carefully before starting the installation work to install the unit properly.
Safety precautions
Please read this manual carefully before starting installation work to install the unit properly.
Every one of the followings is important information to be observed strictly.
WARNING
CAUTION
It could have serious consequences depending on the circumstances.
The following pictograms are used in the text.
Never do. Always follow the instructions given.
Keep this manual at a safe place where you can consult with whenever necessary. Show this manual to installers
when moving or repairing the unit. When the ownership of the unit is transferred, the “Installation Manual” should be given to a new owner.
Failure to follow these instructions properly may result in serious consequences such as death, severe injury, etc..
Failure to follow these instructions properly may cause injury or property damage.
WARNING
Ask a professional contractor to carry out installation work according to the installation manual.
Improper installation work may result in electric shocks, fire or break-down.
Shut OFF the main power source before starting electrical work.
Otherwise, it could result in electric shocks, break-down or malfunction.
Do not install the unit in appropriate environment or where inflammable gas could generate, flow in, accumulate or leak.
If the unit is used at places where air contains dense oil mist, steam, organic solvent vapor, corrosive gas (ammonium, sulfuric compound, acid, etc) or where acidic or alkaline solution, special spray, etc. are used, it could cause electric shocks, break-down, smoke or fire as a result of significant deterioration of its performance or corrosion.
Do not install the unit where water vapor is generated excessively or condensation occurs.
It could cause electric shocks, fire or break-down.
Use the specified cables for wiring, and connect them securely with care to protect electronic parts from external forces.
Improper connections or fixing could cause heat generation, fire, etc.
Seal the inlet hole for remote control cable with putty.
If dew, water, insect, etc. enters through the hole, it could cause electric shocks, fire or break-down.
-
-
76
'15 • PAC-T-236
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power generator, high frequency medical equipment, radio communication equipment, etc. The influences transmitted from the remote control to medical or communication equipment could disrupt medical activities, video broadcasting or cause noise interference.
CAUTION
Do not install the remote control at following places.
It could cause break-down or deformation of remote control. (1) Where it is exposed to direct sunlight (2) Near the equipment to generate heat (3) Where the surface is not flat
Do not leave the remote control with its upper case removed.
When the upper case is removed, put it in a packing box or packing bag to protect internal PCBs or other parts from dust, moisture, etc.
-
77
-
2 . Accessories & prepare on site
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
'15 • PAC-T-236
Accessories
Parts procured at site
Switch box For 1 piece or 2 pieces (JIS C 8340 or equivalent)
(JIS C 8305 or equivalent)
Lock nut, bushing (JIS C 8330 or equivalent)
Lacing (JIS C 8425 or equivalent)
Putty Suitably For sealing gaps
Molly anchor
R/C cable (0.3 mm2 x 2 pcs)
R/C main unit, wood screw (ø3.5 x 16) 2 pcs User’s Manual, Installation Manual
Item name Q’ty Remark
1
These are not required when installing
As required
As required
As required
As required
As required
directly on a wall.Thin wall steel pipe for electric appliance
Necessary to run R/C cable on the wall.
See right table when longer than 100 m
When the cable length is longer than 100 m, the max size for wires used in the R/C case is 0.5 mm them to wires of larger size near the outside of R/C. When wires are connected, take measures to prevent water, etc. from entering inside.
< 200 m 0.5 mm2 x 2-core
< 300 m 0.75 mm
< 400 m 1.25 mm
< 600 m 2.0 mm
3. Remote control installation procedure
Determine where to install the remote control
2
. Connect
2
x 2-core
2
x 2-core
2
x 2-core
Installation “Using a switch box”
“Installed directly on a wall”
Wiring direction “Backward”
“Upper center”, “Upper left”
Cautions for selecting installation place
(1) Installation surface must be flat and sufficiently strong.
R/C case must not be deformed.
(2) Where the R/C can detect room temperatures accurately.
This is a must when detecting room temperatures with the temperature sensor of R/C.
· Install the R/C where it can detect the average tempera­ture in the room.
· Install the R/C separated from a heat source sufficiently.
· Install the R/C where it will not be influenced by the turbulence of air when the door is opened or closed.
Select a place where the R/C is not exposed to direct sunlight or blown by winds from the air- conditioner or temperatures on the wall surface will not deviate largely from actual room temperature.
Installation space
30mm
Wiring
120mm
30mm
30mm
R/C temperature sensor
Secure minimum spaces for disassembling the case. Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped screwdriver, 50mm or more is available.
-
78
-
'15 • PAC-T-236
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Request
Be sure not to install R/C at a place where temperatures around the installation surface of R/C may differ largely from actual room temperature. Difference between detected temperature and actual room temperature could cause troubles. The correction for detected temperature by the R/C cannot offset such temperature difference because it corrects the detected temperatures itself.
Request
Do not install the R/C at a place where it is exposed to direct sunlight or where surrounding air temperature exceeds 40°C or drops below 0°C. It could cause discoloration, deformation, malfunction or breakdown.
Installation procedure
Dimensions (Viewed from front)
18.383.5
Fixing holes
37 23 23
120
To remove the upper case from the bottom cases of R/C
120
· Insert the tip of flat head screwdriver or the like in the recess at the lower part of R/C and twist it lightly to remove.
Take care to protect the removed upper case from moisture or dust.
19
PCB side (Viewed from rear)
Sensor
USB port
Terminal Block
②
Connect wires from X and Y terminals of R/C to X and Y terminals of indoor unit. R/C wires (X, Y) have no polarity.
In case of embedding wiring
③ 
Embed the switch box and the R/C wires beforehand.
(When the wiring is retrieved “Backward”)
Seal the inlet hole for the R/C wiring with putty.
If dust or insect enters, it could cause electric shocks,
●
fire or breakdown.
-
79
Wall
Bushing
50
8
200
-
Conduit
Locknut
Switch box
Seal with putty
R/C cable