Mitsubishi PUG18AYB, PUG24AYB, PUG30AYB, PUG36AYB, PUG42AYB Technical Manual

SPLIT-TYPE, AIR CONDITIONERS
TECHNICAL MANUAL
PUG OUTDOOR UNIT
MODELS PUG18AYB PUG24AYB PUG30AYB PUG36AYB PUG42AYB
036-21534-001 Rev. B (0703)
Table 1:
APPLIES TO:
VOLTAGE PHASE SUFFIX
208/230 VAC 1 PH AYB
036-21534-001 Rev. B (0703)
1
DESCRIPTION AND FEATURES
DESCRIPTION AND FEATURES . . . . . . . . . . . . . . . . . . 2
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
STANDARD OPERATING DATA . . . . . . . . . . . . . . . . 4-6
PERFORMANCE DATA - OPERATING PRESSURES 7-19
DIMENSIONS AND CLEARANCES . . . . . . . . . . . . . . . 20
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
OPERATING PRESSURES / SUPERHEAT . . . . . . 21-22
OPERATING RANGE . . . . . . . . . . . . . . . . . . . . . . . . . . 23
The PUG condensing units are cooling only models that are designed specifically for use with Mitsubishi Electronics PK, PC, and PL MR. SLIM indoor units of matching nominal capacities. Models from 1.5 through 3.5 tons are available.
QUALITY CONDENSER COILS - The coil is con­structed of enhanced copper tube and aluminum fins.
COIL PROTECTION - Coils are protected from dam­age by a polymer mesh applied between the coil face and the PVC coated steel coil guard.
PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temper­ature. This is accomplished by the simultaneous oper­ation of high and low pressure switches and a temperature sensor that protects the compressor if undesirable operating conditions occur. A liquid line fil­ter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre­painted steel. The pre-treated flat galvanized steel pro­vides a better paint to steel bond, which resists corro­sion and rust creep. Special primer formulas and matted desert sand finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knock­outs are provided, if required. The unit contains enough refrigerant for matching indoor units and 25 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
REFRIGERANT CHARGE (R-22 0z.) ADJUSTMENT FOR
OPTIMUM PERFORMANCE . . . . . . . . . . . . . . . . . . . . 24
CAPACITY CORRECTION FACTORS FOR VARIOUS PIPE
LENGTHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
MICROPROCESSOR CONTROL . . . . . . . . . . . . . . .26-27
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
REFRIGERANT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . 29
PARTS BREAKDOWN . . . . . . . . . . . . . . . . . . . . . . .30-32
NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
ADVANCED CONTROL BOARD - Each unit is equipped with an advanced electronic control board. This board controls the function of the outdoor unit and improves the operation and protection of the unit. The control board also provides operational and diagnostic information to the service technician through multiple LED’s.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubri- cated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed re fri g era n t connections, a single panel covering the electrical con­trols and a plug in the control box connecting the con­denser fan, make for easy servicing of the unit.
SECURED SERVICE V ALVES - Secured reusabl e ser- vice valves are provided on both the liquid and vapor connections for ease of evacuating and charging.
ETL LISTED - Approved for outdoor application.
• Certified in accordance with the Unitary Small Equip­ment certification program, which is based on ARI Standard 210/240.
2 Mitsubishi Electronics 2003
2
SPECIFICATIONS
PK SERIES - AIR CONDITIONING SYSTEMS
SYSTEM INDOOR OUTDOOR BTU/H* S.E.E.R. E.E.R.*
PKG18FK3 PK18FK3 PUG18AYB 19400 11.60 10.65 PKG24FK3 PK24FK3 PUG24AYB 23400 11.00 9.80 PKG30FK3 PK30FK3 PUG30AYB 29200 11.60 10.20 PKG36FK3 PK36FK3 PUG36AYB 34200 11.40 10.25
* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor)
Based on ARI operating conditions. Specifications subject to change without notice.
PC SERIES - AIR CONDITIONING SYSTEMS
SYSTEM INDOOR OUTDOOR BTU/H* S.E.E.R. E.E.R.*
PCG24GK PC24GK PUG24AYB 24400 10.50 9.35 PCG30GK PC30GK PUG30AYB 29800 11.00 9.65 PCG36GK PC36GK PUG36AYB 36000 11.20 10.05 PCG42GK PC42GK PUG42AYB 41500 10.00 9.50
* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor)
Based on ARI operating conditions. Specifications subject to change without notice.
036-21534-001 Rev. B (0703)
PL SERIES - AIR CONDITIONING SYSTEMS
SYSTEM INDOOR OUTDOOR BTU/H* SEER. EER.*
PLG18AK PL18AK PUG18AYB 20000 11.40 10.50 PLG24AK PL24AK PUG24AYB 24000 10.00 9.00 PLG30AK PL30AK PUG30AYB 28400 10.30 9.30 PLG36AK PL36AK PUG36AYB 35600 11.00 9.90 PLG42AK PL42AK PUG42AYB 41000 10.00 9.25
* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor)
Based on ARI operating conditions. Specifications subject to change without notice.
ELECTRICAL SPECIFICATIONS - AIR CONDITIONING CONDENSING UNITS
MODEL PUG18AYB PUG24AYB PUG30AYB PUG36AYB PUG42AYB
Compressor Outdoor Fan Full Load Amps 0.5 0.5 0.5 1.4 1.4
Unit Total Full Load Amps 10.1 12.6 15.2 17.4 21.4 Max. Fuse Size (Amps) 20 25 30 35 45 Min. Circuit Ampacity 12.5 15.5 18.9 21.4 26.4 Max. Tubing Length 75 75 75 75 75 Max. Vertical Separation 50 50 50 50 50
Locked Rotor Amps 54 57 73 82 129 Full Load Amps 9.6 12.1 14.7 16.0 20.0
Mitsubishi Electronics 2003 3
036-21534-001 Rev. B (0703)
3
STANDARD OPERATING DATA
PK-FK INDOOR UNITS WITH PUG OUTDOOR UNITS
MODELS PK18FK PK24FK PK30FK PK36FK
Item Unit Cooling Cooling Cooling Cooling
Voltage V 208/230 208/230 208/230 208/230 Frequency Hz 60 60 60 60 Total Input kW 1.82 2.38 2.85 3.34 Indoor Fan Current A 0.8 0.8 0.9 1.0 Booster Heater Current A -- -- -- -­Outdoor Fan Current (FLA) A 0.5 0.5 0.5 1.4
Electrical Circuit
Compressor Current (230v) A 7.3 9.6 12.6 14.0 Condensing Pressure PSIG 260 271 287 278 Suction Pressure PSIG 85 86 84 77 Discharge Temperature °F 182 191 196 191 Condensing Temperature °F 107 112 109 112 Suction Temperature °F 62 58 61 59 Refrigerant Pipe Length FT. 25 25 25 25
Refrigerant Circuit
Refrigerant Charge - 3 lbs 8 oz 3 lbs 6 oz 4 lbs 3 oz 3 lbs 15 oz Intake Air Temperature
Discharge Air Temperature
Indoor Side
Fan Speed RPM. 1490 1490 1490 1490 Airflow (High) CFM 710 710 990 990
Intake Air Temperature Fan Speed RPM. 1050 1050 1050 1100
Airflow (High) CFM 1690 1785 1600 2340
Outdoor Side
Capacity BTU/H 19400 23400 29200 34200 SHF --0.770.710.690.65
DB °F 80 80 80 80 WB °F 67 67 67 67 DB °F 60 58 58 58 WB °F 59 57 56 56
DB °F 95 95 95 95 WB °F -- -- -- --
4 Mitsubishi Electronics 2003
036-21534-001 Rev. B (0703)
3
STANDARD OPERATING DATA
PL-AK INDOOR UNITS WITH PUG OUTDOOR UNITS
MODELS PL18AK PL24AK PL30AK PL36AK PL42AK
Item Unit Cooling Cooling Cooling Cooling Cooling
Voltage V 208/230 208/230 208/230 208/230 208/230 Frequency Hz 60 60 60 60 60 Total Input kW 1.82 2.38 2.85 3.34 4.35 Indoor Fan Current A 0.8 0.8 0.9 1.0 1.4 Booster Heater Current A -- -- -- -- -­Outdoor Fan Current (FLA) A 0.5 0.5 0.5 1.4 1.4
Electrical Circuit
Compressor Current (230v) A 7.3 9.6 12.6 14.0 16.4 Condensing Pressure PSIG 223 270 283 280 267 Suction Pressure PSIG 84 85 80 82 71 Discharge Temperature °F 165 191 197 190 192 Condensing Temperature °F 91 112 108 111 104 Suction Temperature °F 60 58 59 62 50 Refrigerant Pipe Length FT 25 25 25 25 25
Refrigerant Circuit
Refrigerant Charge -- 3 lbs 14 oz 4 lbs 3 oz 4 lbs 2 oz 4 lbs 10 oz 5 lbs 3 oz Intake Air Temperature
Discharge Air Temperature
Indoor Side
Fan Speed RPM. 1490 1490 1490 1490 1490 Airflow (High) CFM 710 990 1060 1060 710
Intake Air Temperature Fan Speed RPM. 1050 1050 1050 1100 1100
Airflow (High) CFM 1785 1785 1835 2340 3320
Outdoor Side
Capacity BTU/H 20000 24000 28400 35600 41000 SHF --0.750.810.750.690.67
DB °F 80 80 80 80 80
WB °F 67 67 67 67 67
DB °F 59 58 59 59 59
WB °F 58 57 57 57 57
DB °F 95 95 95 95 95
WB °F -- -- -- -- --
Mitsubishi Electronics 2003 5
036-21534-001 Rev. B (0703)
3
STANDARD OPERATING DATA
PC-GK INDOOR UNITS WITH PUG OUTDOOR UNITS
MODELS PC24GK PC30GK PC36GK PC42GK
Item Unit Cooling Cooling Cooling Cooling
Voltage V 208/230 208/230 208/230 208/230 Frequency Hz 60 60 60 60 Total Input kW 2.38 2.85 3.34 4.35 Indoor Fan Current A 0.8 0.9 1.0 1.4 Booster Heater Current A -- -- -- -­Outdoor Fan Current (FLA) A 0.5 0.5 1.4 1.4
Electrical Circuit
Compressor Current (230v) A 9.6 12.6 14.0 16.7 Condensing Pressure PSIG 273 286 282 268 Suction Pressure PSIG 89 83 84 74 Discharge Temperature °F 191 196 190 191 Condensing Temperature °F 113 109 113 105 Suction Temperature °F 59 61 63 51 Refrigerant Pipe Length FT 25 25 25 25
Refrigerant Circuit
Refrigerant Charge -- 4 lbs 9 oz 4 lbs 9 oz 5 lbs 0 oz 5 lbs 10 oz Intake Air Temperature
Discharge Air Temperature
Indoor Side
Fan Speed RPM 1490 1490 1490 1490 Airflow (High) CFM 880 1240 1240 1240
Intake Air Temperature Fan Speed RPM 1050 1050 1100 1100
Airflow (High) CFM 1785 1835 2340 3320
Outdoor Side
Capacity BTU/H 24400 29800 36000 41500 SHF --0.750.780.720.71
DB °F 80 80 80 80 WB °F 67 67 67 67 DB °F 58 58 58 57 WB °F 56 57 57 56
DB °F 95 95 95 95 WB °F -- -- -- --
6 Mitsubishi Electronics 2003
4
PERFORMANCE DATA - OPERATING PRESSURES
PK18+PUG18 (Indoor Air = 710 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 19,283 12.38 1,558 11,535 14,927 18,319 21,711 25,103 72 198 65 20,058 12.76 1,572 10,084 13,476 16,868 20,260 23,652 74 202 67 20,833 13.14 1,585 8,632 12,024 15,416 18,808 22,200 76 206 69 21,530 13.54 1,591 6,925 10,317 13,709 17,101 20,493 82 208 71 22,226 13.93 1,596 5,218 8,610 12,002 15,394 18,786 87 210
Indoor Wet
Bulb (°F)
63 18,401 11.02 1,670 11,047 14,439 17,831 21,223 24,615 76 231 65 19,259 11.42 1,687 9,720 13,112 16,504 19,896 23,288 78 234 67 20,117 11.81 1,704 8,393 11,785 15,177 18,569 21,961 81 238 69 20,812 12.15 1,712 6,612 10,004 13,396 16,788 20,180 85 239 71 21,508 12.50 1,721 4,830 8,222 11,614 15,006 18,398 89 241
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
85 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
036-21534-001 Rev. B (0703)
Pressures
(psig)
Pressures
(psig)
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 17,518 9.83 1,782 10,559 13,951 17,343 20,735 24,127 80 263 65 18,459 10.24 1,802 9,356 12,748 16,140 19,532 22,924 83 266 67 19,400 10.65 1,822 8,154 11,546 14,938 18,330 21,722 85 269 69 20,095 10.96 1,834 6,298 9,690 13,082 16,474 19,866 88 271 71 20,789 11.26 1,846 4,442 7,834 11,226 14,618 18,010 90 272
Indoor Wet
Bulb (°F)
63 16,284 8.55 1,905 9,261 12,653 16,045 19,437 22,829 85 301 65 17,000 8.86 1,919 8,420 11,812 15,204 18,596 21,988 87 303 67 17,716 9.16 1,933 7,579 10,971 14,363 17,755 21,147 89 306 69 18,567 9.50 1,955 5,730 9,122 12,514 15,906 19,298 91 308 71 19,417 9.83 1,976 3,882 7,274 10,666 14,058 17,450 94 311
Indoor Wet
Bulb (°F)
63 15,049 7.42 2,028 7,964 11,356 14,748 18,140 21,532 90 339 65 15,541 7.63 2,037 7,484 10,876 14,268 17,660 21,052 91 341 67 16,032 7.84 2,045 7,004 10,396 13,788 17,180 20,572 92 342 69 17,039 8.21 2,075 5,162 8,554 11,946 15,338 18,730 95 346 71 18,045 8.57 2,106 3,321 6,713 10,105 13,497 16,889 98 350
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
105 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
115 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
Pressures
Pressures
(psig)
(psig)
(psig)
Mitsubishi Electronics 2003 7
036-21534-001 Rev. B (0703)
4
PERFORMANCE DATA - OPERATING PRESSURES
PK24+PUG24 (Indoor Air = 640 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 23,389 11.43 2,046 14,266 17,658 21,050 24,442 27,834 69 218 65 24,447 11.83 2,066 12,412 15,804 19,196 22,588 25,980 71 221 67 25,504 12.23 2,085 10,559 13,951 17,343 20,735 24,127 73 224 69 26,268 12.55 2,093 8,645 12,037 15,429 18,821 22,213 75 225 71 27,031 12.87 2,100 6,732 10,124 13,516 16,908 20,300 76 225
Indoor Wet
Bulb (°F)
63 21,933 10.13 2,166 13,570 16,962 20,354 23,746 27,138 73 250 65 23,193 10.54 2,201 11,882 15,274 18,608 22,058 25,450 76 254 67 24,452 10.93 2,237 10,194 13,586 16,978 20,370 23,762 80 257 69 25,272 11.24 2,247 8,291 11,683 15,017 18,467 21,859 80 258 71 26,092 11.55 2,258 6,388 9,780 13,172 16,564 19,956 81 259
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
85 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
(psig)
Pressures
(psig)
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 20,477 8.96 2,285 12,874 16,266 19,658 23,050 26,442 76 282 65 21,939 9.38 2,337 11,352 14,744 18,019 21,528 24,920 81 286 67 23,400 9.80 2,388 9,830 13,222 16,614 20,006 23,398 86 290 69 24,277 10.11 2,402 7,937 11,329 14,604 18,113 21,505 86 292 71 25,153 10.41 2,416 6,044 9,436 12,828 16,220 19,612 86 293
Indoor Wet
Bulb (°F)
63 18,736 7.72 2,426 11,542 14,934 18,326 21,718 25,110 80 321 65 20,005 8.11 2,467 10,266 13,658 16,992 20,442 23,834 84 322 67 21,274 8.49 2,507 8,990 12,382 15,774 19,166 22,558 87 323 69 22,428 8.85 2,533 7,226 10,618 13,952 17,402 20,794 89 326 71 23,582 9.22 2,558 5,463 8,855 12,247 15,639 19,031 90 329
Indoor Wet
Bulb (°F)
63 16,995 6.62 2,567 10,211 13,603 16,995 20,387 23,779 84 359 65 18,071 6.96 2,597 9,181 12,573 15,965 19,357 22,749 86 358 67 19,147 7.29 2,626 8,151 11,543 14,935 18,327 21,719 88 356 69 20,579 7.72 2,664 6,516 9,908 13,300 16,692 20,084 91 361 71 22,010 8.15 2,701 4,881 8,273 11,665 15,057 18,449 94 365
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
105 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
115 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
(psig)
Pressures
(psig)
Pressures
(psig)
8 Mitsubishi Electronics 2003
4
PERFORMANCE DATA - OPERATING PRESSURES
PK30+PUG30 (Indoor Air = 990 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 29,702 12.28 2,419 18,029 21,421 26,138 30,855 34,247 72 224 65 30,517 12.57 2,428 15,612 19,004 23,721 28,438 31,830 73 225 67 31,331 12.85 2,438 13,196 16,588 21,305 26,022 29,414 74 225 69 32,153 13.08 2,458 10,787 14,179 18,896 23,613 27,005 76 228 71 32,974 13.31 2,477 8,378 11,770 16,487 21,204 24,596 78 230
Indoor Wet
Bulb (°F)
63 27,689 10.81 2,561 17,027 20,419 25,136 29,853 33,245 75 256 65 28,977 11.12 2,606 14,822 18,214 22,931 27,648 31,040 77 260 67 30,266 11.42 2,650 12,618 16,010 20,727 25,444 28,836 79 264 69 31,255 11.73 2,665 10,394 13,786 18,503 23,220 26,612 81 265 71 32,245 12.03 2,680 8,171 11,563 16,280 20,997 24,389 83 267
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
85 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
036-21534-001 Rev. B (0703)
Pressures
(psig)
Pressures
(psig)
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 25,675 9.50 2,703 16,026 19,418 24,135 28,852 32,244 77 287 65 27,438 9.85 2,783 14,032 17,424 22,141 26,858 30,250 81 295 67 29,200 10.20 2,863 12,039 15,431 20,148 24,865 28,257 84 302 69 30,358 10.57 2,873 10,001 13,393 18,110 22,827 26,219 86 303 71 31,515 10.93 2,883 7,964 11,356 16,073 20,790 24,182 88.5 303
Indoor Wet
Bulb (°F)
63 23,599 8.95 2,635 14,612 18,004 22,721 27,438 30,830 81 326 65 25,183 8.95 2,813 12,912 16,304 21,021 25,738 29,130 83 331 67 26,768 8.95 2,991 11,212 14,604 19,321 24,038 27,430 86 337 69 28,268 9.31 3,035 9,213 12,605 17,322 22,039 25,431 89 339 71 29,769 9.67 3,078 7,213 10,605 15,322 20,039 23,431 92 342
Indoor Wet
Bulb (°F)
63 21,522 8.38 2,568 13,198 16,590 21,307 26,024 29,416 84 364 65 22,929 8.09 2,844 11,792 15,184 19,901 24,618 28,010 86 368 67 24,335 7.80 3,120 10,386 13,778 18,495 23,212 26,604 88 372 69 26,179 8.18 3,197 8,424 11,816 16,533 21,250 24,642 92 376 71 28,022 8.56 3,274 6,462 9,854 14,571 19,288 22,680 96 380
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
105 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
115 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
Pressures
Pressures
(psig)
(psig)
(psig)
Mitsubishi Electronics 2003 9
036-21534-001 Rev. B (0703)
4
PERFORMANCE DATA - OPERATING PRESSURES
PK36+PUG36 (Indoor Air = 990 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 35,104 12.32 2,849 20,676 24,068 28,785 33,502 36,894 67 222 65 36,163 12.56 2,879 18,194 21,586 26,303 31,020 34,412 69 219 67 37,221 12.80 2,908 15,712 19,104 23,821 28,538 31,930 70 215 69 38,491 13.19 2,918 13,543 16,935 21,652 26,369 29,761 71 216 71 39,760 13.58 2,928 11,373 14,765 19,482 24,199 27,591 72 217
Indoor Wet
Bulb (°F)
63 32,861 10.90 3,014 19,756 23,148 27,865 32,582 35,974 70 249 65 34,286 11.17 3,068 17,336 20,728 25,445 30,162 33,554 72 249 67 35,711 11.44 3,122 14,917 18,309 23,026 27,743 31,135 74 250 69 36,865 11.74 3,140 12,719 16,111 20,828 25,545 28,937 75 251 71 38,020 12.04 3,158 10,521 13,913 18,630 23,347 26,739 77 252
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
85 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
(psig)
Pressures
(psig)
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 30,618 9.63 3,179 18,835 22,227 26,944 31,661 35,053 72 275 65 32,409 9.94 3,258 16,478 19,870 24,587 29,304 32,696 75 280 67 34,200 10.25 3,337 14,121 17,513 22,230 26,947 30,339 77 285 69 35,240 10.48 3,362 11,895 15,287 20,004 24,721 28,113 79 286 71 36,280 10.71 3,387 9,668 13,060 17,777 22,494 25,886 81 287
Indoor Wet
Bulb (°F)
63 27,936 8.32 3,358 17,359 20,751 25,468 30,185 33,577 76 314 65 29,667 8.63 3,438 15,258 18,650 23,367 28,084 31,476 79 318 67 31,398 8.93 3,518 13,158 16,550 21,267 25,984 29,376 83 323 69 32,844 9.21 3,565 11,006 14,398 19,115 23,832 27,224 84 324 71 34,290 9.49 3,612 8,855 12,247 16,964 21,681 25,073 86 326
Indoor Wet
Bulb (°F)
63 25,254 7.14 3,537 15,882 19,274 23,991 28,708 32,100 79 353 65 26,925 7.44 3,618 14,038 17,430 22,147 26,864 30,256 84 357 67 28,596 7.73 3,699 12,194 15,586 20,303 25,020 28,412 88 360 69 30,448 8.08 3,768 10,118 13,510 18,227 22,944 26,336 89 363 71 32,300 8.42 3,836 8,041 11,433 16,150 20,867 24,259 90 365
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
105 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
115 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
(psig)
Pressures
(psig)
Pressures
(psig)
10 Mitsubishi Electronics 2003
4
PERFORMANCE DATA - OPERATING PRESSURES
PL18+PUG18 (Indoor Air = 600 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 19,879 12.21 1,629 11,583 14,989 18,395 21,801 25,207 71 200 65 20,894 12.72 1,643 10,125 13,532 16,938 20,344 23,750 73 204 67 21,477 12.95 1,658 8,668 12,074 15,480 18,886 22,293 75 208 69 22,451 13.50 1,663 6,954 10,360 13,766 17,172 20,578 81 210 71 22,913 13.73 1,668 5,240 8,646 12,052 15,458 18,864 86 212
Indoor Wet
Bulb (°F)
63 18,970 10.86 1,746 11,093 14,499 17,905 21,311 24,717 75 233 65 19,823 11.24 1,764 9,760 13,166 16,573 19,979 23,385 77 236 67 20,739 11.64 1,781 8,428 11,834 15,240 18,646 22,052 80 240 69 21,600 12.06 1,790 6,639 10,045 13,451 16,857 20,263 84 241 71 22,173 12.32 1,799 4,850 8,256 11,662 15,068 18,474 88 243
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Disch.
85 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
036-21534-001 Rev. B (0703)
Pressures
(psig)
Pressures
(psig)
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
63 18,060 9.69 1,863 10,603 14,009 17,415 20,821 24,227 79 265 65 18,751 9.95 1,884 9,395 12,801 16,207 19,613 23,020 82 268 67 20,000 10.50 1,905 8,188 11,594 15,000 18,406 21,812 84 271 69 20,749 10.82 1,918 6,324 9,730 13,136 16,542 19,948 87 273 71 21,432 11.10 1,931 4,460 7,867 11,273 14,679 18,085 89 274
Indoor Wet
Bulb (°F)
63 16,787 8.43 1,992 9,300 12,706 16,112 19,518 22,924 84 303 65 17,098 8.52 2,007 8,455 11,861 15,267 18,673 22,079 86 305 67 18,264 9.03 2,022 7,610 11,016 14,422 17,828 21,235 88 308 69 19,169 9.38 2,044 5,754 9,160 12,566 15,972 19,378 90 310 71 20,018 9.69 2,066 3,898 7,304 10,710 14,116 17,522 93 313
Indoor Wet
Bulb (°F)
63 15,514 7.32 2,121 7,997 11,403 14,809 18,215 21,621 89 341 65 15,445 7.25 2,130 7,515 10,921 14,327 17,733 21,139 90 343 67 16,528 7.73 2,138 7,033 10,439 13,845 17,251 20,657 91 344 69 17,588 8.11 2,170 5,184 8,590 11,996 15,402 18,808 94 348 71 18,603 8.45 2,202 3,335 6,741 10,147 13,553 16,959 97 352
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
Cooling
Capacity
(Btu/hr)
EER
EER
EER
Total
Power
(Watts)
Total
Power
(Watts)
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
105 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
115 °F Outdoor Air Temperature
Net Sensible Cooling Capacity (Btu/hr)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
Pressures
Pressures
Pressures
(psig)
(psig)
(psig)
Mitsubishi Electronics 2003 11
Loading...
+ 24 hidden pages