Air-Conditioners For Building Application
INDOOR UNIT
PKFY-P·NHMU-E2
For use with the R410A & R22
A utiliser avec le R410A et le R22
Para utilizar con el R410A y el R22
INSTALLATION MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing
the air-conditioner unit.
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil
extérieur pour une utilisation sûre et correct.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad exterior
antes de instalar la unidad de aire acondicionado.
3. Installing the indoor unit ....................................................................................3
4. Installing the refrigerant piping ..........................................................................6
Note:
The phrase “Wired remote controller” in this installation manual refers to the PAR-21MAA.
If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are included in these
box.
5. Drainage piping work .........................................................................................7
6. Electrical work ...................................................................................................8
7. Test run (Fig. 7-1) ............................................................................................10
1. Safety precautions
X Before installing the unit, make sure you read all the “Safety
precautions”.
X Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
• Install the unit at a place that can withstand its weight.
• Use the specified cables for wiring.
• Use only accessories authorized by Mitsubishi Electric and ask the dealer
or an authorized technician to install them.
• Do not touch the heat exchanger fins.
• Install the air conditioner according to this Installation Manual.
• Have all electric work done by a licensed electrician according to local
regulations.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main power switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
: At servicing, please shut down the power supply for both the Indoor and
ELV
Outdoor Unit.
Warning:
Carefully read the labels affixed to the main unit.
• The cut face punched parts may cause injury by cut, etc. The installers are
requested to wear protective equipement such as gloves, etc.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it
with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal
high pressure in the refrigerant line, and may result in an explosion and
other hazards.
The use of any refrigerant other than that specified for the system will
cause mechanical failure or system malfunction or unit breakdown. In the
worst case, this could lead to a serious impediment to securing product
safety.
Caution:
• Do not use the existing refrigerant piping, when use R410A refrigerant.
• Use ester oil, either oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections, when use R410A refrigerant.
• Do not use the air conditioner where food, pets, plants, precision
instruments, or artwork are kept.
• Do not use the air conditioner in special environments.
• Ground the unit.
• Install an leak molded case circuit braker, as required.
• Use power line cables of sufficient current carrying capacity and rating.
• Use only a molded case circuit braker and fuse of the specified capacity.
• Do not touch the switches with wet fingers.
• Do not touch the refrigerant pipes during and immediately after operation.
• Do not operate the air conditioner with the panels and guards removed.
• Do not turn off the power immediately after stopping operation.
2
2. Installation location
G
PKFY-P·NHMU-E2
L
M
B
F
898
35-23/64
Fig. 2-1
3. Installing the indoor unit
1
45
23
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
A
249
9-51/64
E
*
(mm)
(inch)
C
K
295
11-39/64
D
J
H
I
Select a proper position allowing the following clearances for installation and
maintenance.
PKFY-P·NHMU-E2
(mm, inch)
ABCDE
Min. 150Min. 50Min. 50Min. 250Min. 220
Min. 5-29/32Min. 1-31/32Min. 1-31/32Min. 9-27/32Min. 8-21/32
F
Air outlet: Do not place an obstacle within 1500 mm, 59-1/16 inch of the air outlet.
G Floor surface
H Furnishing
I When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
2-23/64 inch extra distance should be taken because the fan air current may create a short
cycle.
J 1800 mm, 70-7/8 inch or greater from the floor surface (for high location mounting)
K 55 mm, 2-11/64 inch or greater with left or rear left piping and optional drain pump
installation
L 550 mm, 21-21/32 inch or greater with optional drain pump installation
M Minimum 7 mm, 9/32 inch: 250 mm, 9-27/32 inch or greater with optional drain pump
installation
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART
NUMBER
1
2
3
4
5
ACCESSORY
Mount board1
Tapping screw 4 × 35
Felt tape3
Band3
Block of cushion1
QUANTITY
P08, P12, P15, P18
12
LOCATION OF
SETTING
Fix at the back of
the unit
Fig. 3-1
PKFY-P·NHMU-E2
G
2-9/32
H
14-21/32
14-1/32
12-57/64
11-15/32
10-7/16
8-55/64
7-7/8
4-59/64
2-3/4
19/32
5/8
25/32
1-1/8
1-39/64
2-7/64
2-19/32
3-3/32
3-37/64
4-5/64
4-9/16
5-1/16
6-3/64
6-17/32
7-1/32
9-5/32
9-31/64
9-63/64
9-3/8
8-25/64
6-27/32
3-15/16
J
10-61/64
A
I
CEB
A
K
Fig. 3-2
19/32
C
5/64
2-3/4
4-17/32
4-59/64
7-7/8
8-55/64
7-5/8
7-3/32
5-33/64
6-37/64
D
Fig. 3-3
9-3/8
10-7/16
11-15/32
E
(inch)
12-57/64
14-1/32
14-21/32
9-7/64
D
B
3.2. Installing the wall mounting fixture (Fig. 3-2)
3.2.1. Setting the wall mounting fixture and piping positions
X Using the wall mounting fixture, determine the unit’s installation position
and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
F
PKFY-P·NHMU-E2
A Mount board 1
B
Indoor unit
C Bottom left rear pipe hole (ø65 mm, 2-9/16 inch)
D Bottom right rear pipe hole (ø65 mm, 2-9/16 inch)
E Knockout hole for left rear hole (70 mm, 2-3/4 inch × 310 mm, 12-13/14 inch)
F Bolt hole (4-ø9 mm, 23/64 inch hole)
G Center measurement hole (ø2.5 mm, 3/32 inch hole)
H Tapping hole (77-ø5.1 mm, 13/64 inch hole)
I Hole centre
J Align the scale with the line.
K Insert scale.
3.2.2. Drilling the piping hole (Fig. 3-3)
X Use a core drill to make a hole of 65-80 mm, 2-9/16-3-5/32 inch diameter in
the wall in the piping direction, at the position shown in the diagram to the
left.
X The hole should incline so that the outside opening is lower than the
inside opening.
X Insert a sleeve (with 65-80 mm, 2-9/16-3-5/32 inch diameter and purchased
locally) through the hole.
A
Sleeve
B Hole
C (Indoors)
D Wall
E (Outdoors)
Note:
The purpose of the hole’s inclination is to promote drain flow.
3
3. Installing the indoor unit
E
D
B
PKFY-P·NHMU-E2
F
A
D
C
E
I
H
Fig. 3-4
B
Fig. 3-5
C
D
Fig. 3-6
)
1
3.2.3. Installing the wall mounting fixture
X Since the indoor unit weighs near 13 kg, 29lbs, selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
X The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold
arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
• The unit body must be mounted horizontally.
• Fasten at the holes marked with S as shown by the arrows.
C
B
G
PKFY-P·NHMU-E2 (Fig. 3-4)
A Min. 90 mm, 3-35/64 inch (617.6 mm, 24-5/16 inch or greater with optional drain pump
installation)
B Min. 200 mm, 7-7/8 inch
C Min. 72 mm, 2-53/64 inch (142.5 mm, 5-39/64 inch or greater with left, rear left, or lower
left piping, and optional drain pump installation)
D Fixing screws (4 × 35 mm, 1-3/8 inch) 2
E
Level
F Fasten a thread to the hole.
G
Place the level against the horizontal reference line of the mount board and mount so that it is
level. Hang a weight from the thread and align with
H Weight
I Mount board 1
V
EPK of the mount board to permit leveling.
3.3. When embedding pipes into the wall (Fig. 3-5)
A
• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external connection lines etc are to
be embedded into the wall in advance, the extruding pipes etc, may have to be
bent and have their length modified to suit the unit.
• Use marking on the mount board as a reference when adjusting the length of the
embedded cooling pipe.
• During construction, give the length of the extruding pipes etc some leeway.
A
Mount board 1
Reference marking for flare connection
B
C Through hole
D On-site piping
3.4. Preparing the indoor unit
* Check beforehand because the preparatory work will differ depending on the
exiting direction of the piping.
* When bending the piping, bend gradually while maintaining the base of the
piping exiting portion. (Abrupt bending will cause misshaping of the piping.)
Extraction and processing of the piping and wiring (Fig. 3-6)
B
A
)
2
1. Connection of indoor/outdoor wiring See page. 8.
2. Wrap the felt tape 3 in the range of the refrigerant piping and drain hose which
will be housed within the piping space of the indoor unit.
• Wrap the felt tape 3 securely from the base for each of the refrigerant piping
and the drain hose.
• Overlap the felt tape 3 at one-half of the tape width.
• Fasten the end portion of the wrapping with vinyl tape.
A
Liquid pipe
B Gas pipe
C Indoor/outdoor connection cable
D Drain hose
E Felt tape 3
3. Be careful that the drain hose is not raised, and that contact is not made with the
indoor unit box body.
Do not pull the drain hose forcefully because it might come out.
A
Fig. 3-7
4
Rear, right and lower piping (Fig. 3-7)
1) Be careful that the drain hose is not raised, and that contact is not made with
the indoor unit box body.
Arrange the drain hose at the underside of the piping and wrap it with felt
tape 3.
2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
one-half of the tape width.)
A
Cut off for right piping.
B Cut off for lower piping.
3. Installing the indoor unit
B
)
1
)
2
Fig. 3-8
Left and left rear piping (Fig. 3-8)
4. Drain hose replacement See 7. Drainage piping work
Be sure to replace the drain hose and the drain cap for the left and rear left
piping. Dripping may occur if you forget to install or fail to replace these parts.
C
Drain cap
1) Be careful that the drain hose is not raised, and that contact is not made with
C
the indoor unit box body.
2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
one-half of the tape width.)
3) Fasten the end portion of the felt tape 3 with vinyl tape.
D
Cut off for left piping.
D
)
3
B
PKFY-P·NHMU-E2
A
Fig. 3-9
D
Fig. 3-10
A
C
C
A
3.5. Mounting the indoor unit
1. Affix the mount board 1 to the wall.
2. Hang the indoor unit on the hook positioned on the upper part of the mount
board.
Rear, right and lower piping (Fig. 3-9)
3. While inserting the refrigerant piping and drain hose into the wall penetration
hole (penetration sleeve), hang the top of the indoor unit to the mount board 1.
4. Move the indoor unit to the left and right, and verify that the indoor unit is hung
securely.
5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1.
(Fig. 3-10)
* Check that the knobs on the bottom of the indoor unit are securely hooked into
the mount board 1.
6. After installation, be sure to check that the indoor unit is installed level.
A
Mount board 1
Indoor unit
B
C Hook
D square hole
Left and left rear piping (Fig. 3-11)
3. While inserting the drain hose into the wall penetration hole (penetration sleeve),
hang the top of the indoor unit to the mount board 1.
Giving consideration to the piping storage, move the unit all the way to the left
side, then cut part of the packaging carton and wrap into a cylindrical form as
illustrated in the diagram. Hook this to the rear surface rib as a spacer, and raise
the indoor unit.
4. Connect the refrigerant piping with the site-side refrigerant piping.
5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1.
* Check that the knobs on the bottom of the indoor unit are securely hooked into
the mount board 1.
6. After installation, be sure to check that the indoor unit is installed level.
* Connect the joint with the following pipes: Liquid and gas pipes of P18.
E Apply refrigerating machine oil over the entire flare seat surface.
PKFY-P·NHMU-E2 (inch)
ODø6.35
1/4”
ODø9.52
3/8”
Flare dimensions
øA dimensions (mm, inch)
R22R410A
Tightening
torque.
(N·m, ft·lbs)
14 - 18
10 - 13
14 - 18*
10 - 13
Pipe size O.D.
(mm, inch)
ODø12.7
1/2”
ODø15.88
5/8”
Tightening
torque.
(N·m, ft·lbs)
49 - 61
35 - 44
49 - 61*
35 - 44
4.1. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F
or more, thickness of 12 mm, 1/2 inch or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or
D
more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before
tightening flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
B Refrigerant pipe sizes & Flare nut tightening torque
C Do not apply refrigerating machine oil to the screw portions.
(This will make the flare nuts more apt to loosen.)
D Be certain to use the flare nuts that are attached to the main unit.
(Use of commercially-available products may result in cracking.)
Pipe size O.D.
(mm, inch)
ODø6.35
1/4”
ODø6.35
1/4”
Tightening
torque.
(N·m, ft·lbs)
14 - 18
10 - 13
14 - 18
10 - 13
Pipe size O.D.
(mm, inch)
ODø12.7
1/2”
ODø12.7
1/2”
Tightening
torque.
(N·m, ft·lbs)
49 - 61
35 - 44
49 - 61
35 - 44
35-23/64
Flare nut O.D.
Liquid pipe
(mm, inch)
17
43/64
17
43/64
Gas pipe
(mm, inch)
26
1-1/16
26
1-1/16
2-23/32
15/64
1-11/16
2-13/64
G
1-27/32
E
2-13/64
15/64
25/32
11-39/64
D
1-11/16
2-13/64
(B)
21-7/32
17-63/64
24-1/64
(A)
(C)
1-27/32
FF
2-23/64
6-7/32
6-21/32
7-7/32
5-5/16
1-11/16
1-11/16
2-21/64
Fig. 4-2
4.2. Positioning refrigerant and drain piping (Fig. 4-2)
PKFY-P·NHMU-E2
A Gas pipe * Indicates the condition with accessories mounted.
B Liquid pipe
C Drain hose
D Left-side piping knockout hole
E Right-side piping knockout hole
F Lower piping knockout hole
A
G Mount board 1
4.3. Refrigerant piping (Fig. 4-3)
Indoor unit
1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
B
Fig. 4-3
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. The portion where the insulation material is joined is sealed by taping.
A
Site-side refrigerant piping
B Unit side refrigerant piping
6
4. Installing the refrigerant piping
E
PKFY-P·NHMU-E2
C
Fig. 4-4
5. Drainage piping work
A
C
G
C
H
Fig. 5-1
1
3
A
I
B
2
4
4.3.1. Storing in the piping space of the unit (Fig. 4-4)
1. Wrap the supplied felt tape in the range of the refrigerant piping which will be
housed within the piping space of the unit to prevent dripping.
2. Overlap the felt tape at one-half of the tape width.
A
B
D
3. Fasten the end portion of the wrapping with vinyl tape, etc.
A
Gas pipe
B Liquid pipe
C Indoor/outdoor connection cable
D Felt tape 3
5.1. Drainage piping work (Fig. 5-1)
• Drain pipes should have an inclination of 1/100 or more.
• For extension of the drain pipe, use a soft hose (inner dia. 15 mm, 19/32 inch)
available on the market or hard vinyl chloride pipe (VP-16/O.D. ø22 mm,
ø55/64 inch PVC TUBE). Make sure that there is no water leakage from the
connections.
• Do not put the drain piping directly in a drainage ditch where sulphuric gas may
be generated.
• When piping has been completed, check that water flows from the end of the
drain pipe.
Caution:
The drain pipe should be installed according to this Installation Manual to
ensure correct drainage. Thermal insulation of the drain pipes is necessary
to prevent condensation. If the drain pipes are not properly installed and
insulated, condensation may drip on the ceiling, floor or other possessions.
A
Inclined downwards
B Must be lower than outlet point
C Water leakage
D Trapped drainage
E Air
F Wavy
G The end of drain pipe is under water.
H Drainage ditch
I 5 cm, 1-31/32 inch or less between the end of drain pipe and the ground.
J Drain hose
K Soft PVC hose (Inside diameter 15 mm, 19/32 inch)
or
Hard PVC pipe (VP-16)
* Bond with PVC type adhesive
B
D
E
C
F
J
K
a
b
A
Preparing left and left rear piping (Fig. 5-2)
1 Remove the drain cap.
A
Fig. 5-2
D
C
A
B
Fig. 5-3
• Remove the drain cap by holding the bit that sticks out at the end of the pipe and
pulling.
Drain cap
A
2 Remove the drain hose.
• Remove the drain hose by holding on to the base of the hose a (shown by
arrow) and pulling towards yourself b.
3 Insert the drain cap.
• Insert a screwdriver etc into the hole at the end of the pipe and be sure to push
to the base of the drain cap.
4 Insert the drain hose.
• Push the drain hose until it is at the base of the drain box connection outlet.
• Please make sure the drain hose hook is fastened properly over the extruding
drain box connection outlet.
B
Hooks
¡ Storing in the piping space of the indoor unit (Fig. 5-3)
* When the drain hose will be routed indoors, be sure to wrap it with commercially
available insulation.
* Gather the drain hose and the refrigerant piping together and wrap them with the
supplied felt tape 3.
* Overlap the felt tape 3 at one-half of the tape width.
* Fasten the end portion of the wrapping with vinyl tape, etc.
A
Gas pipe
B Liquid pipe
C Drain hose
D Indoor/outdoor connection wiring
E Felt tape 3
¡ Check of drainage (Fig. 5-4)
1. Open the front grille and remove the filter.
2. Facing the fins of the heat exchanger, slowly fill with water.
3. After the drainage check, attach the filter and close the grille.
Fig. 5-4
7
6. Electrical work
M
PKFY-P·NHMU-E2
L
J
6.1. Electric wiring
PKFY-P·NHMU-E2 (Fig. 6-1)
F
E
D
K
G
JKL
15/32 inch
2-11/64 inch
C
A
B
L1
L2
GR
C
RQNO P
L
I
Connection can be made without removing the front panel.
1. Open the front grille, remove the screw (1 piece), and remove the electrical
parts cover.
* Electrical work can be conducted more effectively with the panel removed.
When attaching the panel, check that the hooks M at five locations on the air
outlet side are connected securely.
2. Securely connect each wire to the terminal board.
* In consideration of servicing, provide extra length for each of the wires.
* Take care when using strand wires, because beards may cause the wiring to
short out.
3. Install the parts that were removed back to their original condition.
4. Fasten each of the wires with the clamp under the electrical parts box.
A
Electrical box cover
B Fixing screw (Electrical box cover)
C Ground wire connection portion
D MA remote control terminal board: (1, 2) do not have polarity
E Transmission terminal board: (M1, M2, S) do not have polarity
F Power supply terminal board (L1, L2, GR).
G Lead
I Ground wire: Connect the ground wire in the direction illustrated in the diagram.
J MA remote controller
K Transmission cable
L Power supply cable
M Hook
N Conduit plate
O Bush (purchased locally)
P Lock nut (purchased locally)
Q Connector (purchased locally)
R Conduit (purchased locally)
S Conduit cover
T Fixing screw (Conduit cover)
S
~230V
AB
AB
~230V
T
Fig. 6-1
CCCCC
D
L1L2GR
C
TB2TB5TB15
M1
M2
D
S12
6.2. Power supply wiring
• Install an earth line longer than other cables.
• Power supply codes of appliance shall not be lighter than design 245IEC57 or
227IEC57, 245 IEC 53 or 227 IEC 53.
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 6-2]
A
Ground-fault interrupter
B Local switch/Wiring breaker
C Indoor unit
D Pull box
Fig. 6-2
Total operating current of the indoor unit
F0 = 15A or less *22.1/142.1/142.1/1415151515A current sensitivity *3
F0 = 20A or less *23.3/123.3/123.3/1220202020A current sensitivity *3
F0 = 30A or less *25.3/105.3/105.3/1030303030A current sensitivity *3
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unitV1V2
Type 1PLFY-NBMU, PMFY-NBMU, PEFY-NMSU,
PCFY-NKMU, PKFY-NHMU, PKFY-NKMU
Type 2PEFY-NMAU381.6
Type 3PEFY-NMHSU13.84.8
OthersOther indoor unit00
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
Main cableBranchGroundCapacityFuse
Minimum wire thickness (mm²/AWG)Breaker for wiring
(NFB)
18.62.4
Ground-fault interrupter *1
8
6. Electrical work
Sample chart
6000
<Example of "F2" calculation>
*Condition PEFY-NMSU × 4 + PEFY-NMAU × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05
→ 16A breaker (Tripping current = 8 × 16A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
G1Current sensitivity
30 or less30 mA 0.1sec or less
100 or less100 mA 0.1sec or less
Wire thickness (mm2/AWG)V3
2.1/1448
3.3/1256
5.3/1066
6.3. Types of control cables
1. Wiring transmission cables
Types of transmission cableShielding wire CVVS or CPEVS
Cable diameterMore than 1.25 mm
LengthLess than 200m, 219 yard
2. M-NET Remote control cables
Types of remote control cable
Cable diameterMore than 0.5 (AWG20) to 1.25 mm
LengthAdd any portion in excess of 10m, 33 ft to
3. MA Remote control cables
Types of remote control cable2-core cable (unshielded)
Cable diameter0.3 (AWG22) to 1.25 mm
LengthLess than 200m, 219 yard
600
60
10
Tripping Time [s]
1
0.1
0.01
12
Shielding wire MVVS
Rated Tripping current (x)
2
(AWG16)
SAMPLE
34 68C1020
2
(AWG16)
within the longest allowable transmission cable
length 200m, 219 yard.
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire) The “S”
on indoor unit TB5 is a shielding wire connection. For specifications about the
connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote
controller.
• Connect the remote controller’s transmission cable within 10 m, 33 ft using a
C
2
TB3
B
M1M2
AA
SM1 M2SM1M2
TB5TB5
C
1 MA Remote controller
• Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller
2
0.75 mm
(AWG22) core cable. If the distance is more than 10 m, 33 ft, use a
2
1.25 mm
(AWG16) junction cable.
polarized 2-wire)
• Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller.
(Nonpolarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
3 Wireless remote controller(When installing wireless signal receiver)
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor
C
C
3
con-troller board.
• When more than two units are run under group control using wireless remote
controller, connect TB15 each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless re-
mote controller. (In the default setting of indoor unit and wireless remote controller, Pair No. is 0.)
A
Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable(M1(A), M2(B), (S))
C Remote controller
D Wireless signal receiver
Fig. 6-3
E Wireless remote controller
9
6. Electrical work
A
ON
OFF
SW1
12345678910
SW12SW11
9
8
7
6
0
0
1
9
2
8
3
7
4
6
5
㧔U&+)+6㧔VJU&+)+6
Fig. 6-4
6.7. Electrical characteristics
Model
PKFY-P08, P12, P15, P18 NHMU-E2
7. Test run (Fig. 7-1)
SWA
3
ࠕ࠼ࠬ
2
1
1
2
3
4
5
CN43
ࠕ࠼ࠬ
CN82
SW14
0
1
F
2
E
3
D
4
C
5
B
6
A
7
9
8
ಽጘญ0Qࡍࠕ0Q
㧔$4#0%*0Q
(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11
(for 1 to 9) with “3”.
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection
number.
Remain other than series R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
6.6. Sensing room temperature with the built-in
sensor in a remote controller (Fig. 6-4)
If you want to sense room temperature with the built-in sensor in a remote
controller, set SW1-1 on the control board to “ON”. The setting of SW1-7 and
SW1-8 as necessary also makes it possible to adjust the air flow at a time when
the heating thermometer is OFF.
IFM: Indoor Fan Motor Output: Fan motor rated output
FCED
B
TEST RUN
COOL, HEAT
°F
TEMP.
MENU
ON/OFF
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
°F
OPERATION
SIMPLE
ON/OFF
FILTER
CHECK
TEST
CLEAR
MIHG
Fig. 7-1
A
A ON/OFF button
B Test run display
C Indoor temperature liquid
line temperature display
D ON/OFF lamp
E Power display
F Error code display
Test run remaining time
display
G Set temperature button
H Mode selection button
I Fan speed button
M TEST button
1 Turn on the power at least 12 hours before the test run.
2 Press the [TEST] button twice. “TEST RUN” liquid crystal display
3 Press the [Mode selection] button. Make sure that wind is blown out.
4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched.
6 Check operation of the outdoor unit fan.
7 Release test run by pressing the [ON/OFF] button. Stop
8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an
error occurs can be registered in the remote controller. The telephone number
will be displayed when an error occurs. For registration procedures, refer to the
operation manual for the indoor unit.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.