The old refrigerant and lubricant in the existing piping
contain a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used indoors during
installation and both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Use ESTR , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enters, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
2
[2] Refrigerant recharging
(1) Refrigerant recharging process
1 Direct charging from the cylinder.
·R407C cylinder available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.
Gauge manifold·Only for R407C
Charge hose·Only for R407C
Electronic scale
Gas leak detector·Use the detector for R134a or R407C.
Adapter for reverse flow check·Attach to vacuum pump.
Refrigerant charge base
Refrigerant cylinder·For R407C ·Top of cylinder (Brown)
Refrigerant recovery equipment
Tool name
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
·Use pressure performance of 5.10MPa·G or over.
·Cylinder with syphon
Specifications
—
—
—
33
Cautions for units utilizing refrigerant R410A
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
4
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold ·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector ·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check ·Attach to vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder ·Only for R410A ·Top of cylinder (Pink)
·Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
5
3
Indoor unit
PART NAMES AND FUNCTIONS
Air intake
Filter
Grille
Louver
Vane
Air outlet
6
Wiredremote controller
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
Low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
at which time the airflow direction
also changes.
Room Temperature display
Shows the room temperature. The room
temperature display range is 8–39.
The display blinks if the temperature
is less than 8 or 39 or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
Note:
●
“PLEASE WAIT” message
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
“NOT AVAILABLE” message
●
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
77
Wirelessremote controller
CHECK
TEST RUN
display
CHECK and TEST RUN display indicate that
the unit is being checked or test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
display
SET TEMP. display indicates the set desired
temperature.
display
OPERATION MODE display
Operation mode display indicates which
operation mode is in effect.
display
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Used to change the fan speed.
MODE SELECT button
Used to switch the operation mode between
cooling, drying, fan, heating and auto mode.
+ In case the outdoor unit is cool only type,
the heating and auto mode are not
available.
CHECK-TEST RUN button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
VANE CONTROL button
Used to change the air flow direction.
CHECK
TEST RUN
MODEL SELECT
NOT AVAILABLE
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSETCLOCK
°C
AMPM
AMPM
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is
set, the air conditioner will be automatically
stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
h and min buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
LOUVER button
Changes left/right airflow direction.
(Not available for this model.)
CLOCK button
RESET button
SET button
8
4
SPECIFICATION
4-1. SPECIFICATIONS
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
Heating capacity
(Nominal )
Power input
Current input
External finish
External dimension H x W x D
Net weight
Heat exchanger
Fan
Type x Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-Mid2-Mid1-High)
Noise level (Low-Mid2-Mid1-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
refrigerant pipe
Liquid
(R22, R407C)
Gas
(R22, R407C)
Field drain pipe size
Standard
attachment
Remark
Document
Accessory
Optional parts
External LEV Box
* Nominal conditions *
* Due to continuing improvement, above specification may be subject to change without notice.
*1 Nominal cooling conditions
Indoor :
Outdoor :
27°CDB/19°CWB (81°FDB/66°FWB)
35°CDB (95°FDB)
7.5 m (24-9/16 ft)
0 m (0 ft)
1, *3 are subject to JIS B8615-1.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
*2 Nominal cooling conditions
27°CDB/19.5°CWB (81°FDB/67°FWB)
35°CDB (95°FDB)
5 m (16-3/8 ft)
0 m (0 ft)
*3 Nominal heating conditions
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
3
cfm = m
lb = kg/0.4536
*Above specification data is
subject to rounding variation.
TO OUTDOOR UNIT
BC CONTROLLER
M-NET REMOTE CONTROLLER
DC24-30V
RED
13
TB2
L
N
GRN /YLW
BREAKER
(16A)
POWER SUPPLY
~/N 220-240V 50Hz
~/N 220V 60Hz
2
CN53P
(RED)
12
CN2M
M-NET
(BLU)
M1 M2
BLU
FAN
(GRN)
F.C
TB5
BLU
WHT
146
RED
ZNR
BLK
BLU
CND
(RED)
C1
FUSE
250V
6.3A
U
TO NEXT
INDOOR UNIT
PULL
BOX
FUSE
(16A)
LED on indoor board for service
MarkMeaning
Main power supply
LED1
Power supply for
LED2
MA-Remote controller
MODELSSW2
ON
P15
OFF
1234
Function
Main power supply (indoor unit:220-240V)
power on lamp is lit
Power supply for MA-Remote controller
on lamp is lit
MODELSSW2
ON
P20
OFF
1234
1313
MODELSSW2
ON
P25
OFF
1234
<*1>
7
REFRIGERANT SYSTEM DIAGRAM
PKFY-P15VBM-E
PKFY-P20VBM-E(R1)
PKFY-P25VBM-E(R1)
Models
Gas pipe
8
Item
Liquid pipe
TROUBLESHOOTING
Gas pipe temperature thermistor
TH23
Liquid pipe temperature thermistor
TH22
Heat exchanger
Room temperature thermistor
TH21
Strainer
(#100mesh)
Linear expansion
valve
Unit: mm(inch)
PKFY-P15VBM-E PKFY-P20VBM-E(R1) PKFY-P25VBM-E(R1)
{12.7 (1/2”)
{6.35 (1/4”)
Gas pipe
Strainer
(#100mesh)
Liquid pipe
Strainer
(#100mesh)
Flare
8-1. HOW TO CHECK THE PARTS
PKFY-P15VBM-E PKFY-P20VBM-E(R1) PKFY-P25VBM-E(R1)
Parts nameCheck points
Room temperature
thermistor (TH21)
Liquid pipe temperature
thermistor (TH22)
Gas
pipe temperature
thermistor (TH23)
Vane motor (MV)
4
Orange
Pink or
2
White
Red
1
Connect pin No.
Ye l l o w
M
53
Fan motor (MF)
FAN
White
1
Red
4
Black
6
Linear expansion
valve (LEV)
LEV
White
Yellow
Orange
Blue
Red
Brown
CN60
Disconnect the connector then measure the resistance using a tester.
(At the ambient temperature 10~30)
Normal
4.3k~9.6k
Abnormal
Open or short
Refer to the next page for the details.
Measure the resistance between the terminals using a tester. (At the ambient temperature 25)
Blue
NormalNormal
-
Red-Pink or White
Red-Blue
-
Red-Orange
400 7%
-
-
Red-Yellow
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (At the ambient temperature 20)
Abnormal
Open or short
White-Black
Red-Black
Normal
286
200
Disconnect the connector then measure the resistance valve using a tester.
(Coil temperature 20)
1
2
3
4
5
6
(1)-(5)
White-Red
Yellow-Brown
(2)-(6)
Normal
Orange-Red
150 10%
(3)-(5)
(4)-(6)
Blue-Brown
Abnormal
Open or short
14
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor (TH21)
Liquid pipe temperature thermistor (TH22)
Gas pipe temperature thermistor (TH23)
Thermistor R0=15k' ± 3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+t
0: 15k'
1
273
10: 9.6k'
20: 6.3k'
25: 5.4k'
30: 4.3k'
40: 3.0k'
< Thermistor for lower temperature >
50
40
30
Resistance (K)
20
10
0
-20 -1001020 30 40 50
Temperature ()
Linear expansion valve
1 Operation summary of the linear expansion valve
• Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Controller board
DC12V
Linear expansion valve
4
M
6
2
5
White
1
Red
3
Orange
Blue
Brown
Yellow
:4
:3
:2
:1
Brown
Red
Blue
Orange
Yellow
White
Connector(CN60)
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
6
5
4
3
2
1
Drive circuit
:4
:3
:2
:1
1515
<Output pulse signal and the valve operation>
Output
(Phase)
{1
{2
{3
{4
Linear expansion valve operation
2
Open
Valve position (capacity)
Close
1
ON
ON
OFF
OFF
Close
A
E
B
Output
2
OFF
ON
ON
OFF
OFF
OFF
ON
ON
D
Open
Pulse number
3
4
ON
OFF
Closing a valve : 1 → 2 → 3 → 4 → 1
Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phase
become OFF.
OFF
• At phase interruption or when phase does not shift in order, motor
does not rotate smoothly and motor will lock and vibrate.
ON
• When the switch is turned on, 2200 pulse closing valve signal will
be sent till it goes to point A in order to define the valve
position.
C
Outdoor unit R410A model : 1400 pulse
Outdoor unit R22/R407C model : 2000 pulse
Opening a valve
all the way
When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valves : however, when the
pulse number moves from E to A or when the valve is locked,
more noise can be heard than in a normal situation.
• Noise can be detected by placing the ear against the screw
driver handle while putting the screw driver tip to the linear
expansion valve.
Extra tightening (200~800 pulse)
Troubleshooting
3
Symptom
Operation circuit
failure of the micro
processor
Linear expansion
valve mechanism is
locked.
Short or breakage
of the motor coil of
the linear expansion
valve
Valve doesn't close
completely.
Wrong connection
of the connector or
contact failure
Check points
Disconnect the connector on the controller board, then con-
nect LED for checking.
When power is turned on, pulse signals will output for 10
seconds. There must be some defects in the operation circuit
if the LED does not light while the signals are output or keeps
lighting even after the signals stop.
Motor will idle and make a ticking noise when the motor is
operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality.
Measure the resistance between each coil (white-red, yellow-
brown, orange-red, blue-brown) using a tester. It is normal if
the resistance is in the range of 150" ±10%.
To check the linear expansion valve, operate the indoor unit
in fan mode and at the same time operate other indoor units
in cooling mode, then check the pipe temperature <liquid
Thermistor
(Liquid pipe)
Linear
expansion
valve
It is not necessary to exchange the linear expansion valve, if
the leakage is small and not affecting normal operation.
Check the color of lead wire and missing terminal of the con-
nector.
pipe temperature> of the indoor unit by the
outdoor multi controller board operation
monitor. During fan operation, linear expansion valve is closed completely and if there
is any leaking, detecting temperature of
the thermistor will go lower. If the detected
temperature is much lower than the temperature indicated in the remote controller,
it means the valve is not closed all the way.
LED1k
6
5
4
3
2
1
Countermeasures
Exchange the indoor controller board at drive circuit
failure.
Exchange the linear expansion vale.
Exchange the linear expansion valve.
If large amount of refrigerant is leaked, exchange
the linear expansion valve.
Disconnect the connector
at the controller board,
then check the continuity.
16
8-2. FUNCTION OF DIP SWITCH
PKFY-P15VBM-E PKFY-P20VBM-E(R1) PKFY-P25VBM-E(R1)
Switch
Pole
SW1
Mode
selection
10
SW2
Capacity
code
1~4
switch
Function
Operation by switch
ONOFF
Thermistor<Intake temperature>
1
position
Filter cloggingProvideNot provide
2
Filter sign indication2,500 hr100 hr
3
Air intakeNot effective Not effective
4
Remote indication switchingThermo ON signal indicationFan output indication
5
Humidifier control
6
7
Air flow set in case of heat
thermo OFF
8
Auto restart functionEffectiveNot effective
9
Power ON/OFFEffectiveNot effective
MODELSW2
PKFY-P15VBM-E
PKFY-P20VBM-E
PKFY-P25VBM-E
Built-in remote controller
+2
Fan operation at Heating mode
Low +1
Setting air flow +1Depends on SW1-7
ON
OFF
1234
ON
OFF
1234
ON
OFF
1234
Indoor unit
Thermo ON operation at
heating mode
Extra low +1
Effective
timing
NOTE:
1
+
Under
suspension
SW1-7
OFF
ON
OFF
ON
+2 It is impossible to intake
the fresh air.
Indoor controller board
Before
power
Set for each capacity.
supply
ON
Remarks
Address board
<Initial setting>
ON
OFF
12345678910
SW1-8
Fan speed
OFF
Extra low
OFF
Low
ON
Setting air flow
ON
Stop
<Initial setting>
SW3
Function
selection
10
Heat pump/Cool only Cooling only Heat pump
1
Louver
2
Vane
3
Vane swing
4
Vane horizontal angleSecond setting First setting
5
Vane cooling limit angle setting
6
Changing the opening of linear
7
expansion valve
Heating 4 degree up Not effective Effective
8
Superheat setting temperature
9
Subcool setting temperature
AvailableNot available
Horizontal angleDown B,C
+1
EffectiveNot effective
+2
—
+2
— —
—
—
+3
—
—
—
Indoor controller board
Under
suspension
+1 At cooling mode, each angle
can be used only 1 hour.
+2 Please do not use SW3-9,10
as trouble might be caused
by the usage condition.
+3 Second setting is the same
as first setting.
<Initial setting>
ON
OFF
123456789 10
17
Operation by switch SwitchRemarks
Effective
timing
SW11
1s digit
address
setting
SW12
10ths digit
address
setting
SW14
Branch
No.
Setting
SW5
Voltage
selection
Rotary switch
Rotary switch
2
SW12
0
9
8
7
6
10
220V
1
2
3
4
5
SW14
F
E
D
C
B
A
0
1
8
9
SW11
9
8
7
6
1
2
3
4
5
6
7
0
1
2
How to set address
3
4
5
Example : If address is "3", remain SW12
(for over 10) at "0", and match SW11 (for 1 to 9)
with "3".
How to set branch number SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC
contoller’s end connection number
Remain other than series R2 at "0".
240V
If the unit is used at the 230V or 240V area,
set the voltage to 240V.
If the unit is used at the 220V, set the voltage
to 220V.
Before
power
supply
ON
Address board
<Initial setting>
SW12
SW11
0
0
1
9
8
7
6
5
1
9
2
2
8
3
4
3
7
4
6
5
Address board
<Initial setting>
SW14
0
1
2
F
3
E
4
D
5
C
6
B
7
A
8
9
Address board
<Initial setting>
220V
240V
J41, J42
Wireless
remote
controller
Pair No.
• To operate each indoor unit by each remote controller when installed 2 indoor
units or more are near, Pair No. setting is necessary.
(Setting
patterns
Pair No. setting is available with the 4 patterns
A to D).
Make setting for J41, J42 of indoor controller board and the Pair No. of
wireless remote controller.
• You may not set it when operating it by one remote controller.
Setting for indoor unit
Jumper wire J41, J42 on the indoor controller board are cut according to
the table below.
Wireless remote controller pair number:
Setting operation
1. Press the SET button (using a pointed implimaent). Check that the
Jumper
remote controller’s display has stopped before continuing.
MODEL SELECT flashes, and the model No. (3 digits) appears (steadily-lit).
2. Press the MINUTE button twice. The pair number appears flashing.
3. Press the temperature buttons to select the pair number to set.
4. Press the SET button (using a pointed implemet). The set pair number is
displayed (steadily-lit) for 3 seconds, then disappears.
Indoor controller
Setting pattern
jumper wire
J41J42
A
B
C
D
—
Cut
—
Cut
Pair No.4-9 of wireless remote controller is setting pattern D.
CN3A
Connected to the
MA-Remote controller
Between 1 to 3 8.7-13V DC
(Pin1 (+))
CN20
Room temperature
thermistor (TH21)
CN41
Connector
(HA terminal-A)
CN32
Connector
(Remote switch)
LED2
Power supply for
MA-Remote controller
CN35M
Connected to the indoor
power board (CN35P)
19
CN53M
Connected to the indoor power board (CN53P)
Between 1 to 2 24-30V DC (non-polat)
Between 3 to 5 12.5-13.7V DC (Pin3 (+))
Between 4 to 5 11.5-12.7V DC (Pin4 (+))
8-3-2. Indoor power board
PKFY-P15VBM-E
PKFY-P20VBM-E(R1)
PKFY-P25VBM-E(R1)
CN2M
Connected to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN35P
Connected to the indoor controller board
(CN35M)
CN53P
Connected to the indoor controller board
(CN53M)
Between 1 to 2 24-30V DC (non-polat)
Between 3 to 5 12.5-13.7V DC (Pin3 (+))
Between 4 to 5 11.5-12.7V DC (Pin4 (+))
FAN
Fan motor output (MF)
CND
Power supply for
indoor controller board
Between 1 to 3 220-240V AC
1. REMOVING THE LOWER SIDE OF THE INDOOR UNIT
FROM THE INSTALLATION PLATE
When there is removing plate
(1) Remove the corner box at right lower side of the indoor
unit and remove the removing plate from the corner box.
(Figure 3)
(2) Insert the removing plate at the back side of the corner
box to remove the indoor unit.
(3) Remove the hook by pulling the lower side of the indoor
unit down as shown in the Figure 1.
When there is no removing plate or it cannot be used for
some reason.
(1) Remove the front panel.
(2) Insert the screw driver to the corner hole at both left and
right side as shown in the Figure 2.
(3) Push it up, then pull down the lower side of indoor unit and
remove the hook.
Figure 1Figure 2
Indoor unit
removing plate
Insert
the edge
Figure 3
Pull
Be careful
not to damage
the airflow
adjustment
plate with the
screw driver.
Push
Corner hole
Push
Down
2. REMOVING THE FRONT PANEL
* Before removing the front panel, leave the open space at
upper side of the vane approximately 2 to 3 cm.
(1) Remove the 3 screw caps then remove the 3 set screws.
(Refer to the Photo 1)
(2) Remove the grille.
(3) Remove the left side of the front panel, then right side.
(4) After removing the lower side of the front panel a little,
remove it as pulling the upper side toward you.
* Please pay attention to the nozzle assembly.
INSTALLING THE FRONT PANEL
(1) Insert the lower side of the front panel under the vane.
(2) Set the upper side of the front panel. (Figure 4)
(3) Set the lower side of the front panel then fix it with the
screws.
(4) Press the area indicated as arrow sign and set it to the air
conditioner unit.
(5) Attach the screw caps.
Photo 1
Front panel
Figure 4
Corner box
Set screws
(4) Push
Grille
Van e
(2)
2121
(3)
OPERATION PROCEDUREPHOTOS & ILLUSTRATIONS
PHOTOS & ILLUSTRATIONSOPERATION PROCEDURE
3. REMOVING THE INDOOR CONTROLLER BOARD AND
INDOOR POWER BOARD
(1) Remove the front panel. (Refer to 2)
(2) Remove the electrical box cover (screw 4 × 10).
(Refer to the Photo 2)
INDOOR CONTROLLER BOARD
(1) Disconnect the following connectors on the indoor
controller board.
(connector in front of)
CN60, CN5V, CN90, CN29, CN21
CN42, CN81, CN3A, CN20
(2) Pull out the indoor controller board toward you, then
disconnect the rest of connectors.
CN53M, CN35M (See the Photo 3)
INDOOR POWER BOARD
(1) Disconnect the following connectors on the indoor power
board.
FAN, CN53P, CN35P, CN2M, CND
(2) Remove the earth wire for TAB1.
(3) Pull out the indoor power board toward you.
(See the Photo 3)
Photo 2
Photo 3
Coil cover
fixing screw
Coil cover
Electrical box cover
Screw
Electrical box
Indoor controller board
Indoor power
board
Terminal block
(TB5)
Room temperature thermistor
cover
4. REMOVING THE ELECTRICAL BOX
(1) Remove the front panel. (Refer to 2)
(2) Remove the electrical box cover. (See the Photo 2)
(3) Pull the nozzle assembly toward you as opening the catch
of the nozzle assembly. (See the Photo 5)
(4) Disconnect the indoor/outdoor transmission wiring of TB5.
(5) Disconnect the power supply wiring of TB2.
(6) Disconnect the relay connector of MA-remote controller.
(7) Disconnect the following connector on the indoor controller
board.
CN60, CN5V, CN29, CN21, CN90, (CN3A)
(8) Disconnect the connector (FAN) on the indoor power board.
(9) Remove the ground wire fixing screw.
(10) Pull the disconnected lead wire out from the electrical box.
(11) Push up the upper fixture catch to remove the box, then
pull the lower fixture and remove it from the box fixture.
Terminal block (TB2)
Photo 4
Linear expansion valve
Liquid pipe temp.
thermistor (TH22)
Gas pipe temp.
thermistor (TH23)
Indoor controller board
Indoor power
board
MA-remote
controller
connector
Terminal block
(TB5)
Terminal block
(TB2)
Ground wire set screw
22
5. REMOVING THE NOZZLE ASSEMBLY AND DRAIN HOSE
(1) Remove the front panel (Refer to 2).
(2) Remove the electrical box cover.
(3) Disconnect the connector (CN5V) on the indoor controller
board.
(4) After unhook the right side of the corner box, press the
upper left side and remove the corner box.
(5) Remove the nozzle assembly from the fixture.
(See the Photo 5)
(6) Remove the drain hose.
PHOTOS & ILLUSTRATIONSOPERATION PROCEDURE
Photo 5
fixture
Heat exchanger
Nozzle assembly
Electrical box
Drain hose
Drain hose
fixture
6. REMOVING THE LINE FLOW FAN AND THE FAN MOTOR
(1) Remove the front panel. (Refer to 2)
(2) Remove the nozzle assembly. (Refer to 5)
(3) Remove the electrical parts box.
(4) Remove the fixture while pressing the right side of motor
fixture catch. (See the Photo 6)
(5) Remove the left side of the motor fixture.
(6) Loosen the screw which fixes the line flow fan to the fan
motor, then remove the fan motor by sliding it to the right
side. (See the Photo 6)
(7) Pull the left-hand side of the heat exchanger toward you.
(See the Photo 7)
(8) Remove the line flow fan.
7. REMOVING THE VANE MOTOR
(1) Remove the front panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor.
Disconnect the relay connector and remove the motor
from the shaft.
(4) Disconnect the vane motor connector (CN5V) on the indoor
controller board.
Heat exchanger
Photo 6
Line flow fan
set screws
Photo 7
Heat exchanger
fixture (left)
Photo 8
Heat exchanger
Vane motor
Vane motor fixing
screws
Fan motor
fixture (right)
fixture (left)
fixture set screws
Drain hose
Nozzle assembly
Heat exchanger
Nozzle assembly
8. REMOVING THE LIQUID PIPE THERMISTOR AND GAS
PIPE THERMISTOR
(1) Remove the front panel. (Refer to 2)
(2) Remove the electrical box cover.
(3) Remove the coil cover.
(4) Cut the wiring fixed band.
(5) Remove the liquid pipe thermistor and gas pipe thermistor.
(See the Photo 9)
(6) Disconnect the connector (CN29) (CN21) on the indoor
controller board.
23
Photo 9
Gas pipe
thermistor
Heat exchanger
Liquid pipe thermistor
Electrical box
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Nov. 2008 No. OCH418 REVISED EDITION-A PDF 7
Distributed in May 2007 No. OCH418 PDF 9
Made in Japan
New publication, effective Nov. 2008
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.