PKH-P1.6GALH1, PKH-P2GALH1, PKA-P1.6GAL1 and PKA-P2GAL1
are added in Revised Edition-B.
Please void OC176 Revised Edition-A.
Refer to the OCT03 Revised Edition-C as regarding control relation.
This manual does not cover outdoor units. When servicing them,
please refer to the service manual No.OC180 Revised Edition-A,
OC261 and this manual in a set.
● Outdoor units which are connected to PKH-P·GALH, PKH-P·GALH1.PKA-P·GAL and PKA-P·GAL1 have been added.
● The parts No. of REMOTE CONTROLLER has changed.
(The following parts numbers are interchangeable.)
➔
[ T7W E02 714 ][ T7W E06 714 ]
2COMBINATION OF INDOOR AND OUTDOOR UNITS
Outdoor unit (OC180 REVISED EDITION-A)
Heat pump with
electric heater
Heat pump without
electric heater
or
Cooling only
Indoor unit
PKH-P1.6GALH
PKH-P2GALH
PKA-P1.6GAL
PKA-P2GAL
Indoor unit
Heat pump type
PUH-P
1.6VGA 1.6YGA 2VGA2YGA 1.6VGA 2VGA
—
—
—
—
—
—
Outdoor unit (OC261)
Heat pump type
PUH-P
1.6VGAA.UK 1.6YGAA.UK
2VGAA.UK 2YGAA.UK
Cooling only type
PU-P
—
—
—
—
—
Cooling only type
1.6VGAA.UK 1.6YGAA.UK
—
—
—
PU-P
2VGAA.UK 2YGAA.UK
Heat pump with
electric heater
Heat pump without
electric heater
or
Cooling only
PKH-P1.6GALH1
PKH-P2GALH
PKA-P1.6GAL
PKA-P2GAL
1
—
—
1
1
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2
3
SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.
(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Don’t use the drier which is sold in the field.
-The drier for R407C refrigerant is Per-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant.
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool nameSpecifications
Gauge manifold·Only for R407C.
1
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
Charge hose·Only for R407C.
2
·Use pressure performance of 5.10MPa·G or over.
Electronic scale
3
Gas leak detector·Use the detector for R407C.
4
Adapter for reverse flow check·Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder·For R407C·Top of cylinder (Brown)
7
·Cylinder with syphon
Refrigerant recovery equipment
8
3
Gravimeter
Unit
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
Lights up while transmission to the indoor unit
is mode using switches.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
• FUNCTION
Lights up when function are set..
display
• TEST RUN • CHECK display
CHECK&TEST RUN display indicates that the
unit is being checked or test-run.
display
Displays when batteries are dead.
display
The vertical direction of airflow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ADDRESS display
Displays the refrigerant address.
UNIT NO. display
Displays the number of unit..
FUNCTION NO. display
Displays the mode.
SELECTION NO. display
Displays the selection number..
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
FUNCTION
TEST RUN
CHECK
ON/OFF
MODEFAN
RESET
VANE
AM
PM
AM
PM
TEMP.
˚C
START
STOP
HR.
MIN.
display
SET TEMP. display indicates desired temperature set.
CLOCK display
DIsplays the current time.
“ ”display
Flashes when the current time is displayed.
TIMER display
Displays when in timer operation or when setting timer.
➡
“ ” “ ” display
➡
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
▼
“ ” “ ” display
Displays when the current time and the timer
time can be changed.
▼
TEMP. button
display
The unit is turned ON and OFF alternately
each time the button is pressed.
● When cover is open.
MODE SELECT button
Used to switch the operation mode between
cooling , drying , blowing , heating and auto
mode.
FAN SPEED SELECT button
Used to change the fan speed.
VANE CONTROL button
Used to change the airflow direction.
ON/OFF
MODEFAN
RESET
5
VANE
TEMP.
START
STOP
HR.
MIN.
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
STOP (OFF timer): when this switch is set,
the air conditioner will be automatically
stopped at the preset time.
START(ON timer): when this switch is set, the
air conditioner will be automatically started at
the preset time.
HR. and MIN.buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
button
RESET button
●Wireless remote controller
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, blowing, heating and auto
mode.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating and auto mode not available.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
PKH-P1.6GALH
1, PKH-P2GALH1
PKA-P1.6GAL1,PKA-P2GAL1
● When cover is open.
6
5
Cooling
15,000
4,400
1.78
0.07
0.33
0.40
7.66 / 2.67
Heating
17,100(19,800)
5,000(5,800)
1.90(2.70)
0.07<0.80>
0.33<3.33>
0.40<3.33>
8.19 / 2.86
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(318-353-388-424)
0(direct blow)
<0.80>
Wireless remote controller & built-in
36-38-41-43
20(13/16)
990(39)
235(9-1/4)
340(13-3/8)
17(37)
16(35)
PUH-P1.6VGA / PUH-P1.6YGA
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)
36 / 20
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
RE277VHSM / RE277YFKM
1.3
Line start
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
30
Plate fin coil
Propeller (direct) x 1
0.070
45(1,590)
Reverse cycle
46
48
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
55(121)
R407C
2.6(5.7)
0.57 (Ester)MEL56
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max. 40m
Max. 40m
PKH-P1.6GALH
PKA-P1.6GAL
Service Ref.
With Electric heater
Without Electric heater
With Electric heater
Without Electric heater
With Electric heater
Without Electric heater
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacityw1
Total inputw1
Service Ref.
Power supply(phase, cycle,voltage)
Inputw2
Running currentw2
Starting currentw2
External finish
Heat exchanger
FanFan(drive) x No.
Fan motor output
Airflow(Lo-Mi2-Mi1-Hi)
External static pressure
Booster heaterw2
Operation control & Thermostat
Noise level(Lo-Mi2-Mi1-Hi)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length