Mitsubishi OCS08A TECHNICAL MANUAL

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
September 2007
No. OCS08
REVISED EDITION-A
TECHNICAL DATA BOOK
<Indoor unit> [Model names]
<Outdoor unit>
INVERTER
PLA-RP·BA PEAD-RP·EA PEAD-RP·EA2 PEAD-RP·GA PEA-RP·GA PKA-RP·GAL PKA-RP·FAL PKA-RP·FAL2 PCA-RP·GA PCA-RP·GA2 PCA-RP·HA PSA-RP·GA
R410A
Revision:
PUHZ-P·YHA and PEA-RP·GA are added in REVISED EDI­TION-A.
Some descriptions have been modified.
Please void OCS08.
[Model names]
PUHZ-P100/125/140VHA2 PUHZ-P200/250YHA
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································12
4. WIRING DIAGRAM···································································34
5. REFRIGERANT SYSTEM DIAGRAM ······································46
6. PERFORMANCE CURVES······················································50
7. CORRECTION FACTORS························································52
9. AIR FLOW DATA······································································57
10. NOISE CRITERION CURVES ··················································69
11. OPTIONAL PARTS·····································································80
kW Model
For information on service, please refer to the service manual as follows.
1-2. OUTDOOR UNIT
Model name Service Ref.
PUHZ-P100/125/140VHA2
PUHZ-P100/125/140VHA2.UK
PUHZ-P200/250YHA
PUHZ-P200/250YHA
1-1. INDOOR UNIT
Model name Service Ref.
Service Manual No.
Service Manual No.
PLA-RP50/60/71/100/125/140BA
PLA-RP50/60/71/100/125/140BA.UK
OCH415 OCB415
OCH424 OCB424
OCH412 OCB412
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA OC328 PCA-RP50GA2 PCA-RP50GA2
PCA-RP71/125HA PCA-RP71/125HA OC329
PKA-RP50GAL PKA-RP50GAL OC330
PKA-RP60/71/100FAL PKA-RP50FAL2
PKA-RP60/71/100FAL PKA-RP50FAL2
OC331
PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA OC332
PEAD-RP50/60/71/125/140EA PEAD-RP50/60/71/125/140EA.UK
HWE05210
PEAD-RP100EA2 PEAD-RP100EA2.UK PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK
HWE05060
PEA-RP200/250/400/500GA PEA-RP200/250/400/500GA.TH-AF
PEA-RP200/250GA.TH-AFMF
HWE0708A
1
REFERENCE SERVICE MANUAL
2
2
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46:
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5: w
Heating
Upper limit
D.B. 28˚C
D.B. 21:, W.B. 15:
Lower limit
D.B. 17˚C
D.B. -11:, W.B. -12:
4. Above data are based on the indicated voltage.
w If optional air protect guide is installed : D.B.-15:
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz
Model name Indoor unit PLA-RP100BA PLA-RP125BA PLA-RP140BA
Outdoor unit PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0
)
13.6(5.5-15.0
) Total input kW 3.12 4.09 5.21 EER 3.01 3.01 2.61
Energy label class
BBD
SHF 0.74 0.71 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0
)
16.0(5.0-18.0
) Total input kW 3.28 4.11 4.98 COP 3.41 3.41 3.21
Energy label class
BBC
Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(
Low-Medium2-Medium1-High
)
CFM 710-810-920-1060 780-880-990-1090 External pressure Pa 0 0 Sound level dB(A
)
32-34-37-40 34-36-39-41
24-26-29-32
850-920-1020-1130
0
36-39-42-44
(
Low-Medium2-Medium1-High
)
External finish (Panel
)
White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950
)
Unit (Panel
)
D : mm 840 (950
)
H : mm 298 (35
)
W : inch 33-1/16 (37-3/8
)
D : inch 33-1/16 (37-3/8
)
H : inch 11-3/4 (1-3/8
)
Weight kg 25 (6
)
Unit (Panel
)
lbs 55 (13
)
27 (6
)
60 (13
)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling
dB(A
)
50 51 52
Sound level at heating
dB(A
)
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 99
lbs 165 218
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference
m Max. 30
Length
m Max. 50
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
3
2-2. CEILING-CONCEALED TYPE
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.12 4.38 5.21 EER 3.01 2.81 2.61 Energy label class B C D SHF 0.86 0.83 0.84
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.28 4.11 4.98 COP 3.41 3.41 3.21 Energy label class B B C Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 33.5-42 33.5-42 36.5-46
(
Low-High
)
CFM 1183-1483 1183-1483 1288-1624 External pressure Pa 70(130 Sound level dB(A (
Low-High
)(
)
44-50 44-50 46-51
130Pa : 46-52
)(
130Pa : 46-52 External finish Galvanized sheets Dimension W : mm 1415 1715
D : mm 740 H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8 H : inch 12-13/16
Weight kg 65 65 70
lbs 143 143 154
Unit drain pipe R1(External thread
)
)
)
)(
)
13.6(5.5-15.0
16.0(5.0-18.0
130Pa : 47-53
)
)
)
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling dB(A Sound level at heating dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 99
lbs 165 218
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor: D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide is installed : D.B.-15:
Single phase 230V 50Hz
4
Model name Indoor unit PEAD-RP100GA
Outdoor unit PUHZ-P100VHA2
Cooling Capacity Btu/h 32,100
kW 9.4(4.9-11.2
) Total input kW 3.60 EER 2.61 Energy label class D SHF 0.85
Heating Capacity Btu/h 38,200
kW 11.2(4.5-12.5
) Total input kW 3.49 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32
Indoor unit Air flow CMM 26.5-33
(
Low-High
)
CFM 935-1165 External pressure Pa 10/50/70 Sound level dB(A (
Low-High
)(
)
40-43/42-45/42-46
10/50/70Pa
) External finish Galvanized sheets Dimension W : mm 1411
D : mm 740 H : mm 275
W : inch 55-9/16
D : inch 29-1/8 H : inch 10-13/16
Weight kg 50
lbs 111
Unit drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 60
CFM 2,120 Sound level at cooling dB(A Sound level at heating dB(A
) )
50
54 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8
Weight kg 75
lbs 165
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
5
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional air protect guide is installed : D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PEA-RP200GA PEA-RP250GA
Outdoor unit PUHZ-P200YHA PUHZ-P250YHA
Cooling Capacity Btu/h 65,000 75,000
kW 19.0(9.0-22.4) 22.0(11.2-28.0) Total input kW 7.21 8.44 EER Energy label class
2.64 2.61 DD
SHF 0.81 0.86
Heating Capacity Btu/h 76,000 92,000
kW 22.4(9.5-25.0) 27.0(12.5-31.5) Total input kW 7.36 8.47 COP 3.04 3.19 Energy label class D D Booster heater kW - -
Power supply Phase [ 3
Cycle Hz 50 Voltage V 400 Breaker size A Indoor 15 / Outdoor 32
Indoor unit Air flow CMM 52-65 64-80
(Low-High) CFM 1835-2295 2260-2825 External pressure Pa 150 Sound level dB(A) 48-51 49-52 (Low-High) External finish Galvanized steel Dimension W : mm 16001400
D : mm 634 H : mm 400
W : inch 6355-1/8
D : inch 25 H : inch 15-3/4
Weight kg 70 77
lbs 155 170 Unit drain pipe R1
Outdoor unit Air flow CMM 130
CFM 4590 Sound level at cooling dB(A) 59 Sound level at heating dB(A) 59 External finish Ivory Munsell 3Y 7.8/1.1 Dimension W : mm 950
D : mm 330+30 H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 53-1/8
Weight kg 126
lbs 278
Refrigerant pipe size Gas side O.D. mm 25.4
inch 1
Liquid side O.D. mm 12.7
inch 1/2
9.52 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 70
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 342~457V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit 3 phase 400V 50Hz Outdoor unit
w1. If optional air protect guide is installed : D.B.-15:
3 phase 400V 50Hz
133 294
6
Model name Indoor unit PEA-RP400GA PEA-RP500GA
Outdoor unit PUHZ-P200YHAo2 PUHZ-P250YHAo2
Cooling Capacity Btu/h 130,000 150,000
kW 38.0(18.0-44.8) 44.0(22.4-56.0) Total input kW 13.97 17.36 EER 2.72 2.53 Energy label class D E SHF 0.75 0.77
Heating Capacity Btu/h 153,000 184,000
kW 44.8(19.0-50.0) 54.0(25.0-63.0) Total input kW 14.27 17.42 COP 3.14 3.10 Energy label class D D Booster heater kW - -
Power supply Phase [ 3
Cycle Hz 50 Voltage V 400 Breaker size A Indoor 15 / Outdoor 32 o2
Indoor unit Air flow CMM 120 160
(High) CFM 4240 5650 External pressure Pa 150 Sound level dB(A) 52 53 (High) External finish Galvanized steel Dimension W : mm 1947
D : mm 764 H : mm 595
W : inch 79-11/16
D : inch 30-1/8 H : inch 23-7/16
Weight kg 130 133
lbs 286 293
Unit drain pipe R1
Outdoor unit (Per 1 outdoor unit)
Air flow CMM 130
CFM 4590 Sound level at cooling dB(A) 59 Sound level at heating dB(A) 59 External finish Ivory Munsell 3Y 7.8/1.1 Dimension W : mm 950
D : mm 330+30 H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 53-1/8
Weight kg 126
lbs 278
Refrigerant pipe size Gas side O.D. mm 25.4 o 2
inch 1 o 2
Liquid side O.D. mm 12.7 o 2
inch 1/2 o 2
9.52 o 2 3/8 o 2
Refrigerant pipe length Height difference m Max. 30
Length m Max. 70 (per 1 outdoor unit)
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 342~457V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit 3 phase 400V 50Hz Outdoor unit
w1. If optional air protect guide is installed : D.B.-15:
3 phase 400V 50Hz
133 294
7
2-3. WALL-MOUNTED TYPE
Model name Indoor unit PKA-RP100FAL
Outdoor unit PUHZ-P100VHA2
Cooling Capacity Btu/h 32,100
kW 9.4(4.9-11.2 Total input kW 3.12 EER 3.01 Energy label class B SHF 0.79
Heating Capacity Btu/h 38,200
kW 11.2(4.5-12.5 Total input kW 3.49 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32
Indoor unit Air flow CMM 22-28
(
Low-High External pressure Pa 0 Sound level dB(A (
Low-High External finish Munsell 3.4Y 7.7/0.8 Dimension W : mm 1680
Weight kg 28
Field drain pipe I.D. mm 20
Outdoor unit Air flow CMM 60
Sound level at cooling dB(A Sound level at heating dB(A External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
Weight kg 75
Refrigerant pipe size Gas side O.D. mm 15.88
Liquid side O.D. mm 9.52
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit Upper limit
Heating
Lower limit
)
CFM 780-990
)
)
D : mm 235
H : mm 340 W : inch 66-1/8 D : inch 9-1/4 H : inch 13-3/8
lbs 62
inch 13/16
CFM 2,120
) )
D : mm 330+30
H : mm 943 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 37-1/8
lbs 165
inch 5/8
inch 3/8
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
41-46
50 54
3. Guaranteed voltage
4. Above data are based on the indicated voltage.
w1. If optional air protect guide is installed : D.B.-15:
)
)
198~264V, 50Hz
Indoor unit Single phase 230V 50Hz Outdoor unit
Single phase 230V 50Hz
8
2-4. CEILING-SUSPENDED TYPE
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.35 4.38 5.21 EER 2.81 2.81 2.61 Energy label class C C D SHF 0.77 0.78 0.76
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.49 4.98 4.98 COP 3.21 2.81 3.21 Energy label class C D C Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(
Low-Medium2-Medium1-High
)
CFM 705-840-810-885 955-1060-1130-1200 External pressure Pa 0 0 Sound level dB(A
(
Low-Medium2-Medium1-High
)
)
40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1310 1620
D : mm 680 H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4 H : inch 10-5/8
Weight kg 37 43 45
lbs829599
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling dB(A Sound level at heating dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 99
lbs 165 218
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide is installed : D.B.-15:
Single phase 230V 50Hz
)
)
13.6(5.5-15.0
16.0(5.0-18.0
)
)
9
Model name Indoor unit PCA-RP125HA
Outdoor unit PUHZ-P125VHA2
Cooling Capacity Btu/h 42,000
kW 12.3(5.5-14.0 Total input kW 4.38 EER 2.81 Energy label class C SHF 0.78
Heating Capacity Btu/h 47,100
kW 13.8(5.0-16.0 Total input kW 4.30 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 25
Indoor unit Air flow CMM 30-38
(
Low-High
)
CFM 1060-1350 External pressure Pa 0 Sound level dB(A (
Low-High
)
)
44-50
External finish Stainless steel Dimension W : mm 1520
D : mm 650 H : mm 280
W : inch 59-7/8
D : inch 25-5/8 H : inch 11
Weight kg 56
lbs 124
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530 Sound level at cooling dB(A Sound level at heating dB(A
) )
51
55 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 53-1/8
Weight kg 99
lbs 218
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
)
)
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional air protect guide is installed : D.B.-15:
Single phase 230V 50Hz
10
2-5. FLOOR STANDING TYPE
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.12 4.38 5.64 EER 3.01 2.81 2.41 Energy label class B C E SHF 0.83 0.76 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.28 4.98 5.69 COP 3.41 2.81 2.81 Energy label class B D D Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 24-31 26-33 27-35
(
Low-High
)
CFM 850-1060 920-1165 955-1240 External pressure Pa 0 Sound level dB(A (
Low-High
)
)
44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 600
D : mm 350 H : mm 1900
W : inch 23-5/8
D : inch 13-3/4 H : inch 74-13/16
Weight kg 51 53
lbs 112 117
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling dB(A Sound level at heating dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 99
lbs 165 218
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide is installed : D.B.-15:
Single phase 230V 50Hz
)
)
13.6(5.5-15.0
16.0(5.0-18.0
)
)
11
3
37728460
()
Ceiling hole
Branch duct hole
Drain pipe connected to VP-25
Ceiling
Grille
Drain hole
Models
Auto vane (Air outlet)
Air intake grille
Ceiling
Cut out hole
Cut out hole
Cut out hole
Burring hole pitch
Burring hole pitch
Burring hole
Burring hole
Power supply wire, Indoor unit/Outdoor unit connecting wire entry
Indoor unit/Outdoor connecting terminal
Indoor power supply terminal block(Option part)
Control wire entry
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
Connected the attached flexible pipe or socket.
Keep approximately 10 to 15mm space between unit ceiling and ceiling slab.
Branch duct hole
Fresh air intake hole
Ceiling hole
Suspension bolt pitch
Suspension bolt pitch
Remote controller terminal block
Suspension bolt M10 or W3/8
(7.5)(7.5)
605
+35
- 5
620
DEFROST/STAND BY lamp
Receiver
Operation lamp
In case of standard grille : PLP-6BA / PLP-6BAMD
In case of wireless remote controller : PLP-6BALM
Auto Grille Air intake grille up/down discharge
Emergency operation switch<Cooling>and Emergency Up/Down switch<Up>
160
160
500
500
597
83 36
950
8336
950
597
A
17
+5
0
B35
190
156
105
140
50~70
160
840
150
90
C
D
840
187.5
20~45
860~910
20~45
810
20~45
860~910
20~45
24
160
ww
w
w
w
w
w
w
w
M
M
M
M
120
°
120°
[175
[125
167
158
Vane motor
2
1
Drain pump clean hole and Drain emergency drainage hole
130
100
70°
155
350
90 100 100 90
BACDE
241 258
80
87
74
400
298
85 77
440
281
2
1
Refrigerant pipe
···[6.35 Flared connection
···1/4 inch
Refrigerant pipe
···[9.52 Flared connection
···3/8 inch
Refrigerant pipe
···[12.7 Flared connection
···1/2 inch
Refrigerant pipe
···[15.88 Flared connection
···5/8 inch
Refrigerant pipe [6.35 / [9.52 Flared connection 1/4 inch/3/8 inch (compatible)
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP100,125,140BA
Detail drawing of fresh air intake hole
Detail connecting of branch duct(Both aspects)
3-[2.8
14-[2.8
[150
[100
Emergency switch<Heating>and Emergency Up/Down switch<Down>
In case of Auto-Grille : PLP-6BAJ
Suspension bolt lower edge
170
w
Ceiling
Air intake grille
Max. 4.0m
L.L Filter
Ceiling
Grille
Indoor unit
1500mm or more
1000mm
or more
3000mm or more
1800mm or more
from floor
For high attachment
Indoor unit
Obstacle
Floor
Note1. Please choose the grille from a standard grille or Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE). Drain pump is included. Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3)
The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/Water dew.)
8. As for necessary installation/service space, please refer to the left figure.
OUTLINES AND DIMENSIONS
INDOOR UNIT PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA PLA-RP140BA
12
Unit : mm
PEAD-RP50EA
1 Refrigerant piping flare connection (liquid [ F copper tube):HP 2 Refrigerant piping flare connection (gas [G copper tube):LP 3 Drain R1(External thread) 4 Electrical parts box 5 Drain Pump (Option) 6 Drain Pipe (Option) ... Flexible joint VP-25(I.D.
[
32)
7 Filter
R407C Outdoor unit : 9.52
F
R410A Outdoor unit : 6.35 w
R407C Outdoor unit : 9.52 w
Outdoor unit (SUZ) : 6.35
EDCBA
804830
-
305772
Model
RP60
R407C Outdoor unit : 15.88
G
R410A Outdoor unit : 12.7 w
15.88
104410702902801012
RP50
w Initial setting
2
1
3
4
Air inlet
Air outlet
Access door
55
50~150
81
197
Service space:500 or more
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
5
6
75
44
18
365~465
B 81
10
56 355
7
159
243
Air outlet
Air inlet
7
Lifting bolt hole
(14×22)
10- [3 (RP35,50) 12-
[
3 (RP60)
In case of rear inlet
In case of bottom inlet
10- [3 (RP35,50) 12-
[
3 (RP60)
D
30
C
10
81BC
A
450
450
10- [3 (RP35,50) 12-
[
3 (RP60)
176
40
288
256
3.5
3.5
10
109
179
10
35
24
30640
30
21
277
80 45
282
13
13E
A
61 227
29
85
40
176
10
15
3.5 256
BC 81
10
81
A
Set
R407C outdoor unit : 19.05158416104704601552RP140
15.8810441070290
F
R410A Outdoor unit : 15.88 w
EDCBA
12841310370360
2801012
1252
Model
RP100,125
RP71
w
Initial setting
7
44
243
308
323
75
6
5
13
1 Refrigerant piping flare connection (liquid [9.52 copper tube):HP 2 Refrigerant piping flare connection (gas [F copper tube):LP 3 Drain R1 (External thread) 4 Electrical parts box 5 Drain Pump (Option) 6 Drain Pipe (Option) ... Flexible joint VP25(I.D.[32) 7 Filter
Service space:500 or more
81
365~465
197
81
50~150
55
29
Access door
Air outlet
Air inlet
4
3
1
2
113
307
122
12-[3
(14x22)
Lifting bolt hole
45
Set
210
12-[3
450
450
140
282
680
3.5
3.5
30
319
261
181
40
30
A C B
81
10
375
10
80
C B 81 A E 13
30D
20
35
30
1053 169
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
PEAD-RP60EA
Unit : mm
PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
13
PEAD-RP60GA
Model
ABCDE
7 7 9
8
9.52
9.52
15.88
15.88
8
10
FG H J
RP60
RP71
RP100
1125 1125
1365
1090 1090
1330
1050 1050
1290
1012 1012
1252
840 840
1080
Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 w
R410A Outdoor unit : 15.88 w R407C Outdoor unit : 19.05
w Initial setting
PEAD-RP71GA PEAD-RP100GA
Unit : mm
14
PEA-RP200GA Unit : mm
Return air
sensor
A
Rubber bush <Remote
controller wiring>
Rubber bush
<Outdoor unit
connection wiring>
Rubber bush
<Power supply wiring>
A
4- [12
Drain R1
Top view
Control box
Return air
duct flange
Supply air
duct flange
<For hanging bolt M10>
[Field supply]
22- [3.1
24- [3 Holes
Refrigerant pipe
[9.52 (3/8 braze)
Refrigerant pipe
[25.4 (1 braze)
<Accessory>
Pipe cover···················2pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller········1pc.
Return air
Left side view
Supply air
Front view
75
55
12970
42
124 34
131
530
50
9525011
7x130(=910)
10
130
130
45
45
31 31
1102
200
10
8x130(=1040)
1300
20
199
100
40
20
462
144
1284
400
155 1000 105
40 1260 40
1340
1400
56539
22330
145
89
35
130
130
35
634
262 73
10
54
10
376
2510010025
15
PEA-RP250GA Unit : mm
Rubber bush <Remote
controller wiring>
Rubber bush
<Outdoor unit
connection wiring>
Rubber bush
<Power supply
wiring>
A
A
4- [12
Drain R1
Top view
Control box
22- [3.1
<For hanging bolt M10>
[Field supply]
Return air
duct flange
Supply air
duct flange
26- [3 Holes
Left side view
Supply air
Return air
Front view
Return air
sensor
<Accessory>
Pipe cover··················2pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller·······1pc.
Refrigerant pipe
[12.7 (1/2 braze)
Refrigerant pipe
[25.4 (1 braze)
42
144145
755570 129
124
131
50 530
34
130
9525011
10
66
1302
1484
7x130(=910)
130
45
45
200
20
100
20
199
40
1500
462
66 9X130(=1170)
10
25 100 100 25
10 10
1540
40146040
255 205
376
1000
1600
73262
400
39 565
54
634
35
130
89
330 22
130
35
16
PEA-RP400, 500GA Unit : mm
45
Refrigerant pipe
PEA-RP400GA :
[
9.52 (3/8 braze)
PEA-RP500GA :
[
12.7 (1/2 braze)
[2 places (*2 part)]
*2*1*2
*1
Refrigerant pipe [25.4 (1 braze)
[2 places (*1 part)]
Return air sensor
(2 places)
Drain R1
24- [3.1
36- [3 HOLES
Left side view
Front view
Top view
Return air
Supply air
4- [15
<For hanging bolt M12>
[Field supply]
Return air duct flange
Control box
Supply air duct flange
A
Rubber bush
<Remote controller wiring>
Rubber bush
<Power supply wiring>
Rubber bush
<Outdoor unit connection wiring>
A
<Accessory>
Pipe cover··················4pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller·······1pc.
81
117156117
10
20 1840
10
40
60
60
61
60
4040
1800
1880
50 664
525
22
102
22.5
120
4X120(=480)
22.5
595
1824
50
764
2801125395
340 18822
1947
570
40 130 130 40
10
33
29
130
12X130(=1560)
29
149 1618
100
42.5
130
8X130(=1040)42.5
10
203320141
20
42559
700
39
17
PKA-RP50GAL
BYOFF
ON STAND
HEATCOOL
OFF BY
ON STAND
COOL HEAT
ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs
r.SLI.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
r.S.S
L
I
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
knockout hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake
198
53
340
715 225
340 80 280 233
990
21
Left side
knockout hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
60
70
245
(Necessary clearance for
unit installation)
Right side
Allowing clearances
Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear
piping hole
left-rear piping
R52.5
R52.5
Installation plate
balance point hole
Details of installation plate
49-[5hole
for tapping screw
knockout hole for
right-rear piping
Right-rear
piping hole
Unit center
14-[14hole
knockout hole for
425
420
170
190
210 230
0
322
0355580130
190
230
272
310
0
35
95
150
205
260
320
345
495
20 75 135 190 245 300 360
405
495
32
0
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
[90~[100[90
Through hole
Sleeve w1
50
Model
R52.5
R
52.5
Gas pipe
Liquid pipe
Terminal block for
Terminal block to
outdoor unit
Filter grip
Service panel
(Power supply access)
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Unit drain pipe O.D.20
Front view(to open the grille)
700
449
86
581 54
31 280
35
knockout hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395400
190
60
70 35
79
160 40
235
705
power supply (Heater (PKH-P50GALH only))
153
GAS SIDE
LIQUID SIDE
RP50
P50
[6.35
[9.52
[12.7
[15.88
[9.52—[15.88
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
: Initial flare nut size
Unit : mm19Unit : mm
18
PKA-RP50FAL2
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knockout hole for right piping Refrigerant pipe. Drain pipe
Knockout hole for left piping
Drain hose for left-hand side piping
Drain hose
Lower side Auto vanes
(Gas pipe)
Drain hose O.D.20
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe [9.52(3/8F) Gas pipe [15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1120
552
55 120
107 111
Air outlet
552
Air outlet
Louvers (manual)
Under panel Removable at left-hand
side piping
Knockout hole for under-piping Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for tapping screw
66-ø6 hole for tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240 280 314
610
90
Drainage range on left-hand side
Drainage range on right-hand side
10 91=(910)
180
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
GAS SIDE
LIQUID SIDE
RP50
[
6.35
[
9.52
[
15.88
[
12.7
Available pipe size
[
9.52
[
15.88
[ 90
RP60,71 / P60,71
w
1 Sleeves are available on the market.
Use the current nuts meeting the pipe size of the outdoor unit.
Sleeve w1
Through hole
[ 90~ [ 100
:Initial flare nut size
PKA-RP60FAL PKA-RP71FAL
PKA-RP100FAL
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Left side
1680
1370
Air intake
235
C
Knockout hole for right piping
Knockout hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1400
55 120
102 111
694
Air outlet
694
Air outlet
Louvers (manual)
Under panel (Removable at left-hand side piping)
Knockout hole for under-piping Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range on right-hand side
13 91=(1183)
180
Drainage range on left-hand side
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Drain hose O.D.20
: Initial flare nut size
GAS SIDE
LIQUID SIDE
RP100
[9.52 [15.88 [19.05
P100
[9.52
[19.05
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
Unit : mm
20
PCA-RP50GA
180
210
157
15
85
182 liquid 201 gas 241 (Drainage)
Air intake
918
161 90
254
680
506 56
Electrical box
226
70
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
525
928
352
263
171
138
86
46 175 1
131
38
38
79
161
32
179
42
6~7
Ceiling
Electrical box
[Front view]
When electrical box is pulled down
3
2
8
5
1
4
[15.88
[9.52
P50
[15.88
[12.7
[6.35
Available pipe size
[9.52
4 GAS SIDE
5 LIQUID SIDE
RP50
Use the current nuts meeting the pipe size of the outdoor unit.
: Initial flare nut size
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knockout hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
21
PCA-RP50GA2
161 90
254
680
506 56
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
Air intake
85
182 201 241
15
157
(liquid) (5/8 inch gas) (Drainage)
7
2
Electrical box
70
226
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1 46
: Initial flare nut size
4 GAS SIDE
5 LIQUID SIDE
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP71,P60,P71
RP60
[6.35 [9.52
[15.88
RP50
[6.35 [9.52 [12.7 [15.88
[9.52
[15.88
PCA-RP60GA PCA-RP71GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knockout hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
22
PCA-RP100GA
161 90
254
680
506 56
1228
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
18
70
6
87
182
198
245
16
217
(3/8F liquid) (5/8 inch,
3/4 inch gas) (Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
Use the current nuts meeting the pipe size of the outdoor unit.
:Initial flare nut size
4 GAS SIDE
5
LIQUID SIDE
Available pipe size
RP100
[9.52
[15.88 [19.05
P100
[9.52
[19.05
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knockout hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
23
PCA-RP125GA
161 90
254
680
506 56
1535
Air intake
1524
270
207
81 96
1620
Air outlet
1547(suspension bolt pitch)
140
150
320 80
18
70
6
87
182 198 245
16
217
(3/8F liquid) (5/8 inch,
3/4 inch gas) (Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1545
687
263
171
138
86
192
236
1
45
: Initial flare nut size
RP125,140
[19.05
[15.88
[9.52
Use the current nuts meeting the pipe size of the outdoor unit.
4 GAS SIDE
5 LIQUID SIDE
Available pipe size
P125,140
[19.05
[9.52
PCA-RP140GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knockout hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
24
PCA-RP71HA
Unit : mm
(Gap to ceiling)
90˚
130
9
[222
[200
Terminal block box
78
(122)
480
Allowing clearances
6
4
85
14018
45
1
210
2
165
120
90
366
38
318
176
105
650
Less than
Rear wall
Adjustable part
2 ~ 3
300
Ceiling
Less than
Less than
250
500
1001136
or more
or more
295
254
70~90
43
320 80
495
<Suspension bolt pitch>
243
75
75
1 Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch)
4 Knockout hole for behind refrigerant-piping arrangement
2 Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch)
<gas>
197
<liquid>
175
110
21
130 15
5
2
6 Knockout hole for wiring arrangement : 2- [ 27
7 Terminal block(indoor/outdoor connecting line)
5 Knockout hole for upper refrigerant-pipe arrangement
3 Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
8 Terminal block(remote controller)
9 Knockout hole (duct for fresh air intake): 2- [ 200
Suspension bolt
1
280
<Air outlet>
3
13
70
289
650
<Flexible hose(accessory)>
Inspection port
(pipe sensor)
75
<Air outlet>
1224
<Suspension bolt pitch>
1180
986
1136
handle
16
288
<Filter contour dimension>
<Air intake>
Filter (3-pieces)
258 110 102
or more
100
360
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
1098
<Air intake>
Terminal block box
Electrical box
25
The half bottom of FAN CASING
can be separated.
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
PCA-RP125HA
(Gap to ceiling)
90˚
[222
[200
9
130
440440298
2~3
250
Less than
or more
500
Unit : mm
78
Allowing clearances
Terminal block box
(122)246
6
90 120
295
254
243
280
<Air outlet>
110 102
38 210
176
105
3
13
70
289
650
Rear wall
Adjustable part
handle
<Flexible hose(accessory)>
16
<Filter contour dimension>
Inspection port
(pipe sensor)
Filter (4-pieces)
4
2
8545
14018
165
1
70~90
43
320 801564
495
<Suspension bolt pitch>
75
3 Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
2 Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch)
1 Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch, 3/4 inch)
4 Knockout hole for behind refrigerant-piping arrangement
<gas> <liquid>
21
7 Terminal block(indoor/outdoor connecting line)
5 Knockout hole for upper refrigerant-pipe arrangement
110
8 Terminal block(remote controller)
175
197
6 Knockout hole for wiring arrangement : 2- [ 27
Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
9 Knockout hole (duct for fresh air intake) : 2- [ 200
1
75
Suspension bolt
650
Less than
288
258
300
Less than
1001520100
or more
Ceiling
or more
: Initial flare nut size
360
[ 9.52
<Air intake>
Filter element for the exchange
RP125
model:PAC-SG38KF-E (12pcs.)
[ 15.88
[ 19.05
130 15
5
2
Terminal block box
Electrical box
<Suspension bolt pitch>
1608
<Air outlet>
1370 75
1520
The half bottom of
FAN CASING
can be separated.
1482
<Air intake>
2 LIQUID SIDE
Available pipe size
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
1 GAS SIDE
Use the current nuts meeting the pipe size
of the outdoor unit.
26
PSA-RP71GA
Knockout hole
for under-piping
Unit : mm
5 or more
300 or more
2
1
Front 1,000 or more
1. Service access allows for
insertion of screw driver.
100 or more 100 or more
40 66
55 143
Gas pipe [15.88(5/8 inch)
Liquid pipe [9.52(3/8 inch)
2. Adjustable
186
Drain pipe
590
480
110
Knockout hole
for branch duct
Front side
218
VIEW "A"
95
Knockout hole for
under-piping(120 70 oval)
132
130 100
100
Rear side
20
160
90
Knockout hole
for bottom fixing
175
270
250
40 50260
Metal fixture
against overturning
277
130130
95
Electrical parts box
46122
Terminal block for
indoor/outdoor
connection.
Terminal block for
heater power supply
(Only PSH-P·GAH)
1900
766
608
105
47
Knockout hole for piping and wiring
(140 80 oval)
A
Knockout hole for
wiring.[27
(Provided on both sides)
Knockout hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
767 714 123
20
115
50
180
235
70
216
240
Rear side
10 3838
15
111
130 71
530
125
340
370
520
260
240
controller
Front side
10
2010
82730
600
27
PSA-RP100GA PSA-RP125GA PSA-RP140GA
[ 9.52
P100,125,140—[ 19.05
300 or more 1
5 or more 2
Front 1,000 or more
100 or more 100 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
Unit : mm
[ 9.52
RP100,125,140
[ 15.88
[ 19.05
Use the current nuts meeting the pipe size
of the outdoor unit.
Knockout hole
218
LIQUID SIDE
Available pipe size
for under-piping
Front side
: Initial flare nut size
GAS SIDE
77
201
120
Rear side
20
120
277
VIEW "A"
95
140
Knockout hole
255
Knockout hole for
under-piping(120 70 oval)
for bottom fixing
95
Electrical parts box
Terminal block for
indoor/outdoor
connection.
Terminal block for
heater power supply
40 66
Liquid pipe [9.52(3/8 inch)
Gas pipe [15.88(5/8 inch)
46122
(Only PSH-P·GAH)
261
Drain pipe
[19.05(3/4 inch)
590
480
110
105
47
Knockout hole for piping and wiring
(140 80 oval)
A
767 714 123
20
115
50
Knockout hole for wiring
[27 (Provided on both sides)
132
Knockout hole
for branch duct
240
Rear side
10 3838
15
111
260
350
330
40
130 100
125
340
370
Front side
10
50260
Metal fixture
against overturning
520
260
240
2010
130130
controller
766
130 71
1900
608
82730
216
315
70
Knockout hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
530
600
28
417
66 42
45
56
(19)37028
53
175600175
330
2-12o36 oval holes
(Foundation Bolt M10)
Air Discharge
Rear Air Intake
Side Air Intake
2-U Shaped notched holes
(Foundfation Bolt M10)
Installation Feet
,
,
,,,
,
,
,,
,
,
,
,,,
,
,
,
,
,,
,
,
,
30
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Piping Knockout Hole Details
Example of Notes
1···Refrigerant GAS pipe connction (FLARE){15.88(5/8 inch)
2···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8 inch)
w1 ···Indication of STOP VALVE connection location.
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
Over10
500
500
Over100
Dimensions of space needed
for service access are
shown in the below diagram.
Service space
30
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Handle for moving
Side Air Intake
Front piping cover
Rear piping cover
14522030 145
81 219
145
71
71
Drain hole
(5-{33)
Bottom piping hole
(Knockout)
Air Intake
Rear Air Intake
Handle for moving
Handle for moving
23
943
473
950
322
w 1 447
w 1 443
670
Terminal Connections
Left···Power supply wiring
Reight···Indoor/Outdoor wiring
Earth terminal
Service panel
Handle for moving
Handle for moving
1
2
19 55
23 27 92
92
4075
73 63
Right piping hole
(Knockout)
Right trunking hole
(Knockout)
Power supply wiring hole
(2-{27Knockout)
{
92
27 55
7323 63
40
92
65
45
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
Power supply wiring hole
(2-{27Knockout)
{
92
4045
65
92
27 55 23 73 63
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Power supply wiring hole
(2-{27Knockout)
{
92
FOUNDATION
FREE
Over
500mm
O
v
e
r 1
0
m
m
Over 10mm
Over 100mm
OUTDOOR UNIT PUHZ-P100VHA2
Unit : mm
29
PUHZ-P125VHA2 PUHZ-P140VHA2
Unit : mm
(19)28 370
2-U Shaped notched holes
(Foundation Bolt M10)
600175 175
Rear Air Intake
Installation Feet
417
45
330
Side Air Intake
53 56
42 66
2-12 x 36 Oval holes
(Foundation Bolt M10)
Air Discharge
30
Terminal connection
Left···Power supply wiring
950
Earth terminal
322
Handle for moving
Right···Indoor/Outdoor wiring
Service panel
1076
Handle for moving
1350
Front piping cover
w 1 447 w 1 443
2
1
371 635
Rear piping cover
71
23
Bottom piping hole
(Knockout)
71
81 219
Drain hole
(5-{33)
14514522030 145
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
FOUNDATION
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
3 FOUNDATION BOLTS
Dimensions of space needed
for service access are
shown in the below diagram.
2 SERVICE SPACE
<Foundation bolt height>
150
Over
FREE
m
500
Over
10
Over
ver 150m
O
30
Less than
500
Over
Service space
ver 10m
O
m
Side Air Intake
Rear Air Intake
Handle for moving
Handle for moving
Handle for moving
Air intake
27Knockout)
{
Power supply wiring hole
(2-
Rear trunking hole
(Knockout)
45 40
Right trunking hole
(Knockout)
27Knockout)
{
Power supply wiring hole
(2-
75 40
Right piping hole
(Knockout)
4540
27Knockout)
{
Power supply wiring hole
(2-
2
9
{
92
{
73 63
92
{
Rear piping hole
(Knockout)
92
65
27 55
23 73 63
92
19 55
73 63 23 27 92
23 27 55
65
92
The diagram below shows a
basic example.
Explantion of particular details are
1 FREE SPACE (Around the unit)
given in the installation manuals etc.
Over 10mm
Over1000mm
···Refrigerant GAS pipe connction (FLARE){15.88(5/8 inch)
Example of Notes
1
w1 ···Indication of STOP VALVE connection location.
2···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8 inch)
30
Piping Knockout Hole Details
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
Rear piping cover
Front piping cover
Side Air Intake
Handle for moving
Piping Knockout Hole Details
637323
5527
92
65
4045
Power supply wiring hole
(2-[27Knockout)
Rear trunking hole
(Knockout)
Rear piping hole
(Knockout)
[92
922723
6373
4075
92
5519
Power supply wiring hole
(2-[27Knockout)
Right trunking hole
(Knockout)
Right piping hole
(Knockout)
[92
637323
5527
40 45
65
92
Power supply wiring hole
(2-[27Knockout)
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
[92
Over
Over
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Dimensions of space needed
for service access are
shown in the below diagram.
The diagram below shows a basic
example.
Explantion of particular details are
given in the installation manuals etc.
30
FOUNDATION
10
500
500
150
Service space
FREE
O
v
e
r 1
0
m
m
O
v
e
r 1
0
m
m
Over 150mm
Over 1000mm
53
40560
70
175600175
33030
37028 19
417
60 37
2-12o36 oval holes
(Foundation Bolt M10)
2-U Shaped notched holes
(foundation Bolt M10)
Side Air Intake
Rear Air Intake
Air Discharge
Installation Feet
999 995
*1 A
*2 339
950
322
23
371
635
1350
*1 439
Handle for moving
Handle for moving
Terminal Connections
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Service Panel
(
Earth terminal
Brazing
1
2
)
PUHZ-P250YHA
PUHZ-P200YHA
[9.52
(3/8 inch)
[12.7
(1/2 inch)
421
A
447
2
1
· · · ·Refrigerant GAS pipe connction (FLARE)[19.05(3/4 inch)
2
· · · ·Refrigerant LIQUID pipe connection (FLARE) *1· · · ·Indication of STOP VALVE connection location.
*2· · · ·Refrigerant GAS PIPE connention(BRAZING) O.D[25.4
Example of Notes
14514514522030
81 219
71
71
Drain hole
(5-[33)
Bottom piping hole
(Knockout)
Side Air Intake
Air Intake
Rear Air Intake
Handle for moving
Handle for moving
PUHZ-P200YHA PUHZ-P250YHA
Unit : mm
31
WIRED REMOTE CONTROLLER
130
120
19
43.5
Unit : mm
32
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
33
4
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
<Table 2>SW2(CAPACITY CODE)
Manufacture/Service
PLA-RP35BA
MODELS
SW2
ON OFF
12345
Manufacture/Service
PLA-RP100BA
MODELS
ON OFF
12345
PLA-RP50BA
ON OFF
12345
PLA-RP125BA
ON OFF
12345
PLA-RP60BA
ON OFF
12345
PLA-RP140BA
ON OFF
12345
PLA-RP71BA
ON OFF
12345
114169
113
1 3
4
51
41
1234567891011121314151617
18
19
20
CN2L
ON OFF
SWE
J42J41
SW2SW1
LED3 LED2 LED1
LED2 LED1
RU
SW2
SW1
CNB
3
9
5555
4 5
3
t° t° t°
FS
TH2 TH5 TH1
MV
BZ
MVMVMV
MMMM
W.B
TB6
R.B
I.B
MT
M
14
21
21
21
1
2
1
2
Refer to tables 1 and 2
TRANSMISSION WIRES DC12V
TB4
YLW
ORN
ORN BRN
YLW
YLW
ORN
DCL
TO OUTDOOR UNIT
135
31
DC280V
X1
M
1~ DP
D.U.M
CNP
(BLU)
ZNR02
ZNR01
FUSE
DSA
OUTDOOR
CN01
(BLK)
RECTIFICATION
U
U
S1 S2 S3
741
3~
MF
MS
CN3G
U.B
AUTOMATIC FILTER ELEVATION PANEL (OPTION PART)
CN3A
31
AUTO GRILLE
POWER
CNAC
(WHT)
1
3
REMOCON
CN22
(BLU)
I-SEE SENSOR
CN4Y
(WHT)
I-SEE
SENSOR MOTOR
CN6Y (RED)
WIRELESS
CN90
(WHT)
AUTO GRILLE
CN3G (BLK)
I-SEE SENSOR CORNER PANEL (OPTION PART)
I-SEE SENSOR
GRILLE
VANE
CNV(
WHT)
Pair No.
FAN CNMF (WHT)
INTAKE
CN20 (RED)
FLOAT SW
CN4F
(WHT)
LIQUID/PIPE
CN44 (WHT)
TB5
CN32
(WHT)
CN51(WHT)
CN41(WHT)
<Table 1>SW1(MODEL SELECTION)
Manufacture/Service
SW1
ON OFF
12345
w Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor.)
13135
SYMBOL SYMBOLNAME NAME
I.B
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
SURGE ABSORBER
CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL)
POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR)
RELAY (DRAIN PUMP)
SWITCH (MODEL SELECTION) wSee table 1 SWITCH (CAPACITY CORD) wSee table 2 CONNECTOR (EMERGENCY OPERATION)
FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE DRAIN FLOAT SWITCH
TERMINAL BLOCK (Indoor unit Power (option)) TERMINAL BLOCK (
INDOOR/OUTDOOR CONNECTING LINE
) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
REACTOR
ROOM TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT) PIPE TEMP. THERMISTOR/LIQUID (0: / 15k", 25: / 5. 4k" DETECT) COND. / EVA. TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT)
MF
FUSE
MV
ZNR01,02
DSA
DP
CN2L
FS
CN32
TB2 CN41 CN51
TB4
DCL
LED1
TB5,TB6
LED2
TH1
LED3
X1
TH2
SW1
TH5 SW2 SWE
[LEGEND]
TO OUTDOOR UNIT
1
3
5
31
CN01 (BLK)
ORN
YLW
BLU
RED
GRN/YLW
I.B
w1(Fig. 1)
I.B
TB2
POWER SUPPLY ~(1PHASE) 230V 50Hz
ORN ORN
YLW
BRN
TB4
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
L
N
S1 S2 S3
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
W.B
RU
BZ LED1 LED2
SW1 SW2
OPTION PART
PCB FOR WIRELESS REMOTE CONTROLLER
RECEIVING UNIT
BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE)
EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
WIRING DIAGRAM
PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA PLA-RP140BA
34
PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
<wA>
N
L
S1 S2
12
21
12
S3
TO CND
TO OUTDOOR UNIT
TO CN3C
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
54321
OFF
ON
50EA
60EA
71EA
35EA(2)
100EA(2)
125EA
140EA
Capacity cord
switch
Model selection switch
SW2
SW1
MODELS
POWER SUPPLY ~(1PHASE) 230V 50Hz
(IN CASE OF CONNECT THE REPLACEMENT WIRING)
TO OUTDOOR UNIT
TO MA-REMOTE CONTROLLER DC8.7-13V
I.B.
X6
X4
X5
X1
ZNR
FUSE
P.B.
CN31
1
3
DS
INSIDE SECTION OF CONTROL BOX
B
L
U
B L U
B L U
B L U
TB5
(RED)
643521
C
MF
X6X5X4
X1
(RED) CNDK
(BLU)
CNP
(WHT)
FAN
1
Y L W
O R N
(ORN)
31
CND
2
1
(RED)
LED1 LED2 LED3
CN2L
OFF
ON
SWE
SW2
SW1
(RED)
(WHT)
P N K
P N K
B
L
K
B L K
W H T
B L K
B L K
W H T
W H
T
W H T
1
2
31
CN2S
CNSK
(WHT)
(RED)
YLW
ORN
BRN
B R N
O R N
(BLU)
WHT
BLK
CN2D (WHT)
(BLU)
(RED)
(WHT)
(BLK)
(WHT)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
wA
DP
643521
2 1
TB4
S3 S1
S2
2
1331
643521
MF
C
12
CN24
321
12
3
1
2
1
2
1
2
TH5TH2TH1
1
2
CN3C
31
1375
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789 432154321
<PEAD-RP71•100•125•140EA, 100EA2> External static pressure 130Pa
<PEAD-RP71•100•125•140EA, 100EA2>
External static pressure 70Pa <PEAD-RP35•50•60EA, 35EA2> External static pressure 70Pa
Optional parts
Optional parts
<PEAD-RP35•50•60EA, 35EA2> External static pressure 30Pa
(OPTIONAL PARTS)
DRAIN PUMP
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS) DP
DS
TRANSMISSION(INDOOR•OUTDOOR)
LED3
SWITCH(MODEL SELECTION)
SW1
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t,25:/5.4t DETECT)
INTAKE AIR TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
DRAIN SENSOR
DRAIN PUMP
TH5
TH2
TH1
TB5
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCKTB4
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
CN41
CN32
CN2L
I.B.
SYMBOL
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to w A. w2: For power supply system of this unit, refer to the caution label located near this diagram.
PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
35
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Capacity cord switch
Model selection switch
SW2SW1
ON OFF
12345
ON OFF
12345
ON OFF
12345
54321
OFF
ON
100GA
71GA
60GA
MODELS
<wA>
N
L
S1 S2
12
21
12
S3
TO CND
TO OUTDOOR UNIT
TO CN3C
POWER SUPPLY ~(1PHASE) 230V 50Hz
(IN CASE OF CONNECT THE REPLACEMENT WIRING)
TO MA-REMOTE CONTROLLER DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1
ZNR
FUSE
P.B.
I.B.
X1
Y L W
O
R N
X6X5X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B
L
U
B L U
B L
U
B L U
(BLK)
(WHT)
(RED)
(BLU)
B L K
W H T
BLK
WHT
(WHT)
(BLU)
B R N
BRN
O R N
ORN YLW
(BLU)(RED)(ORN)
(RED)
(WHT)
B L K
W H T
B L K
W H T
(WHT)
(WHT)
O
R
G
B L K
B
L
U
B L K
Y
L
W
Y L W
G R Y
wA
*
(INITIAL SETTING)
240V230V220V 20Pa
60Pa 75Pa
10Pa 50Pa 70Pa50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2 1
TB5
TB4
S3 S1
S2
2 1
CNP
1331
31
13
CNSK
2
1
CN2S
643521
MF
C
1
2
CN24
3
21
12
3
1
2
1
2
1
2
TH5TH2
TH1
LED1 LED2 LED3
1
2
CN2D
CN3C
31
CND CNDK
137
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789
4
321
54321
INSIDE SECTION OF CONTROL BOX
*External static pressure
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR•OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t,25:/5.4t DETECT)
INTAKE AIR TEMP.THERMISTOR (0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to w A. w2: For power supply system of this unit, refer to the caution label located near this diagram.
36
PEA-RP200, 250GA
OUTDOOR UNIT
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP200,250GA:15A
DSR
DSA
(3P)
(Hi)
C02
(6P)
(Lo)
C01
C01
5
4
TH5
TH2
TH1
INDOOR UNIT
POWER SUPPLY
3N~PE
380/400/415V
50Hz
BLACK
WHITE
RED
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
Hi
Lo
321
52F
123
MF1
TB6
LCD
REMOTE CONTROLLER
FB
TB4
S3
S2
S1
X6X5X4
375 1
FAN
ZNR
FUSE
4123
SW2
OFF
ON
5
TAB1
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
CNDK
CND
CN32
CN31
CN51
12345
31
31
3112
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
1
2
TB5
Hi
52F
Lo
52F
X1
X1
X1
49F
51F
X6X5X4
12345
SW1
OFF
ON
SWE
OFF
ON
SWITCH (MODEL SELECTION)
SWITCH (CAPACITY CODE)
CONNECTOR (EMERGENCY OPERATION)
SNB
BOARD 1
ZNR5~7 VARISTOR
DSA,DSR ARRESTER
INDOOR UNIT
NAMESYMBOL
COND./EVA. TEMP.
LIQUID PIPE TEMP.
ROOM TEMP.
52FHi MAGNETIC CONTACTOR (INDOOR FAN MOTOR<HIGH SPEED>)
SURGE KILLERCR1,2
SW1
TH5
LED (TRANSMISSION<INDOOR·OUTDOOR>)
LED3
LED (POWER SUPPLY<REMOTE CONTROLLER>)LED2
LED (POWER SUPPLY)LED1
SWE
SW2
X4-6 AUXILIARY RELAY
VARISTORZNR
FUSE (T6.3AL250V)FUSE
THERMISTOR
TERMINAL BLOCK
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TH2
TH1
TB2,4,5
49F
51F
MF1
52FLo MAGNETIC CONTACTOR (INDOOR FAN MOTOR<LOW SPEED>)
AUXILIARY RELAYX1
FERRITE COREFB
BOARD
CONTROLLER
INDOOR
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
4. Indoor and outdoor connecting wires have polarities, make sure
to match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
TERMINAL BLOCKTB6
SYMBOL
REMOTE CONTROLLER
NAME
SNB BOARD 1
REMOTE
CONTROLLER
BOARD
POWER BOARD
INDOOR
INDOOR
CONTROLLER
BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
Caution,
1. To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
6. mark is connector. mark is terminal.
CR1CR2
ZNR5~7
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
37
PEA-RP400, 500GA
GREEN/YELLOW
INDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
TAB1
TAB1
FAN
CNDK
31
1573
X4 X5 X6
CN20
CN21
CN41
CN29
123
4
121
2
2
1
CN2D
CN90
CN22
CN2L
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
3112
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
3
1
CNSK
2
1
CN2S
DC
13.1V
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
FAN
CNDK
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
31
3112
DC13.1V
1573
X4 X5 X6
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
FB11
S1
1
2
REMOTE CONTROLLER
S2
S3
TB5
TB6
LCD
X1
FB21
S1S2S3
X2
TH1-1
TH2-1
TH5-1
TH5-2
TH2-2
TH1-2
TB4-2
TB4-1
FB12
FB22
X4 X5 X6
X4 X5 X6
51F
BLUE
POWER SUPPLY
3N~PE
380/400/415V
50Hz
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP400,500GA:15A
BLACK
WHITE
RED
DSR
DSA
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
C01 C02
123
MF1
123
52F
C01
5
4
X01
X02
49F
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
34
12
21
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
SW2
34
12
21
SW2
AUXILIARY RELAYX4-6
MF1
51F
49F
TB2,4-1,4-2,5
TH1-1,1-2
TH2-1,2-2
FAN MOTOR (INDOOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
TERMINAL BLOCK
THERMISTOR
INDOOR UNIT
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
TH5-1,5-2
CR SURGE KILLER
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)52F
ROOM TEMP.
LIQUID PIPE TEMP.
COND./EVA. TEMP.
FERRITE COREFB11,FB12
FB21,FB22
INDOOR
CONTROLLER
BOARD
X1,2 AUXILIARY RELAY
NAMESYMBOL
SNB
BOARD 1
ZNR5~7 VARISTOR
DSA,DSR ARRESTER
SW2
SWE
LED1 LED (POWER SUPPLY)
LED2 LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED3 LED (TRANSMISSION<INDOOR·OUTDOOR>)
SWITCH (MODEL SELECTION)SW1
SWITCH (CAPACITY CORD)
CONNECTOR (EMERGENCY OPERATION)
OUTDOOR UNIT
TERMINAL BLOCK
NAMESYMBOL
TB3,TB8
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
REMOTE CONTROLLER
TERMINAL BLOCK
NAMESYMBOL
TB6
4. Indoor and outdoor connecting wires have polarities, make sure to
match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
(No.2)
INDOOR
CONTROLLER
BOARD
(No.1)
REMOTE
CONTROLLER
BOARD
INDOOR
POWER
BOARD
(No.1)
(No.2)
INDOOR
CONTROLLER
BOARD
(No.2)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
SNB BOARD 1
(No.1)
INDOOR
POWER BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
6. mark is connector. mark is terminal.
Caution,
1.To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
CR
ZNR5~7
38
PKA-RP50GAL
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
PIPE CN29
(
BLK
)
1 2
1 2
1 2
1 31 31 3 1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L CN51 CN32
WIRELESS CN90
(
WHT
)
VANE CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1 2
1 2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
POWER
CNDK (RED)
CNDK
(RED)
DC13.1V
CN2S
(WHT)
POWER
CND
(ORN)
POWER CN2D(WHT)
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
BLU
YLW ORN
ORN BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
w1 (Fig.1)
Refer to tables 1 and 2 for service PCB.
GRN/YLW
TB2
I.B
HEATER
CN24 (YLW)
POWER SUPPLY ~(1PHASE) 230V 50Hz
88H
FS2
26H
H1
L
REDRED 5 3RED
BLU
GRN/YLW
WHT
RED
61
REDGRY
N
2
1
2
6 5
1
FS1
88H
YLW
YLW
P.B
INDOOR POWER BOARD
SYMBOL
[LEGEND]
NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR <LOSSNAY> CN32 CONNECTOR <REMOTE SWITCH> CN41 CONNECTOR <HA TERMINAL-A> CN51 CONNECTOR <CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION>wSee Table 1. SW2 SWITCH <CAPACITY CODE>wSee Table 2. SWE SWITCH <EMERGENCY OPERATION> X4 RELAY <FAN MOTOR> BCR
POWER SUPPLY <R.B>
LED1 POWER SUPPLY <I.B> LED2
TRANSMISSION <INDOOR-OUTDOOR>LED3
FAN CONTROL ELEMENT
C CAPACITOR <FAN MOTOR>
FAN MOTOR VANE MOTOR
MF MV
SYMBOL NAME
TB4
TERMINAL BLOCK <INDOOR/ OUTDOOR
TB2
TERMINAL BLOCK (HEATER) wPKH-P.GALH models only or option for PKA-RP.GAL models.
CONNECTING LINE> TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE> <OPTION> ROOM TEMP.THERMISTOR <0:/ 15k", 25:/ 5.4k" DETECT> PIPE TEMP.THERMISTOR/ LIQUID <0:/ 15k", 25:/ 5.4k" DETECT> COND./ EVA.TEMP.THERMISTOR <0:/ 15k", 25:/ 5.4k" DETECT>
TB5,TB6
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED <RUN INDICATOR> LED <HOT ADJUST> SWITCH (HEATING ON/ OFF> SWITCH (COOLING ON/ OFF> WIRED REMOTE CONTROLLER BOARD
R.B HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
THERMAL FUSE <84:10A>
FS2
THERMAL FUSE <104:10A>
FS1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
SW1
Service board
SW2
Service board
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
PKA-RP50GAL PKH-P50GALH
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
PKH-P50GALH models only
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
39
PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
PIPE CN29
(
BLK
)
1 2
1 2
1 2
1 31 31 3 1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L CN51 CN32
WIRELESS CN90
(
WHT
)
VANE CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1 2
1 2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual
SW1
Table 1
Service board
SW2
Table 2
Service board Service board Service board
POWER
CNDK (RED)
CNDK (RED)
DC13.1V
CN2S (WHT)
POWER
CND
(ORN)
POWER CN2D(WHT)
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY (1PHASE) 230V 50Hz
RED
BLU
YLW ORN
ORN BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
w
1 (Fig.1)
Refer to tables 1 and 2 for service PCB.
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
PKA-RP50FAL2
PKA-RP60FAL
PKH-P60FALH
1 2 3 4 5
ON OFF
MODELS
PKA-RP71FAL PKH-P71FALH
1 2 3 4 5
ON OFF
MODELS
PKA-RP100FAL PKH-P100FALH
TB2
I.B
HEATER
CN24 (YLW)
PKH-P60 P100FALH models only
POWER SUPPLY (1PHASE) 230V 50Hz
88H
FS2
26H
H1
L
REDRED 5 3RED BLU
GRN/YLW
WHT
RED
61
REDGRY
N
2
1
2
6 5
1
FS1
88H
YLW
YLW
GRN/YLW
P.B
INDOOR POWER BOARD
SYMBOL
[LEGEND]
NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE(T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) SW1 SWITCH (MODEL SELECTION)
w
See Table 1.
SW2 SWITCH (CAPACITY CODE)
w
See Table 2. SWE SWITCH(EMERGENCY OPERATION) X4 RELAY(FAN MOTOR) BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B) LED2
TRANSMISSION(INDOOR-OUTDOOR)LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR VANE MOTOR
MF MV
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (HEATER)
w
PKH-P.FALH
models only or option for PKA-RP.FAL models. CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE )(OPTION) ROOM TEMP.THERMISTOR (0
;
/15k', 25;/5.4k' DETECT) PIPE TEMP.THERMISTOR/LIQUID (0
;
/15k', 25;/5.4k' DETECT) COND./EVA.TEMP.THERMISTOR (0
;
/15k', 25;/5.4k' DETECT)
TB5
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED(RUN INDICATOR ) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) WIREDREMOTE CONTROLLER BOARD(OPTION) TERMINAL BLOCK(REMOTE CONTROLLER
THERMAL FUSE(117
;
10A:60,71FALH/
117
;
16A:100FALH)
TRANSMISSION LINE)
R.B
HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
TB6
FS1,2
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
40
PCA-RP50GA PCA-RP50GA2 PCA-RP60GA PCA-RP71GA
X4 X1
FAN
(
WHT
)
1 3 1 3 1 3 1 35
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK (RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1 2
1 2
3
P.B
I.B
CNDK (RED)
DC13.1V
CN2S (WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER CN2D(WHT)
1 3
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
SWE ON OFF
SW2 SW1
Refer to tables 1 and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41 CN2L CN51 CN32
VANE CN6V
(
GRN
)
MV
6 6
9
MV
6 6
WIRELESS CN90
(
WHT
)
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
D.SENSOR CN31
(
WHT
)
CN31
DRAIN SENSOR
DS
PIPE CN29
(
BLK
)
1 21 2 3
1 2 3
1 2
1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2 SW1
100~140 TYPE
MV
5 5
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
BLU
YLW
GRN/YLW
ORN ORN
BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
W
1 (Fig.1)
(
WHT
)
I.B
HEATER
CN24 (YLW)
26H
RED
61
REDGRY
2
6 5
1
88H
YLW
YLW
TB2
POWER SUPPLY ~(1PHASE) 230V 50Hz
88H
FS2
H1
L
REDRED 5 3RED
BLU
GRN/YLW
WHT
N
2
1
FS1
PCH-P50~P140GAH models only
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SW1
Table 1
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP.GA PCH-P.GAH
SW2
Table 2
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP50GA PCH-P50GAH
1 2 3 4 5
ON OFF
PCA-RP50GA2
PCA-RP60GA PCH-P60GAH
1 2 3 4 5
ON OFF
PCA-RP71GA PCH-P71GAH
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP100GA PCH-P100GAH
1 2 3 4 5
ON OFF
PCA-RP125GA PCH-P125GAH
1 2 3 4 5
ON OFF
PCA-RP140GA PCH-P140GAH
P.B
INDOOR POWER BOARD
SYMBOL
[LEGEND]
NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) SW1 SWITCH (MODEL SELECTION) WSee Table 1. SW2 SWITCH (CAPACITY CODE) WSee Table 2. SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
X1 RELAY(DRAIN PUMP) BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B) LED2
TRANSMISSION(INDOOR-OUTDOOR)LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR VANE MOTOR
MF MV
DRAIN-UP MACHINE (OPTION)
DP
DRAIN SENSOR (OPTION)
DS
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER) WPCH-P.GAH models only or option for PCA RP.GA models.
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE ) ROOM TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT) PIPE TEMP.THERMISTOR/LIQUID (0;/15k', 25;/5.4k' DETECT) COND./EVA.TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT)
TB5,TB6
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD(OPTION) RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
THERMAL FUSE(
98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
FS1,2
[Servicing] Fasten terminal of the terminal board "TB4" that equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
When installing drain-up machine (Optional part)
W
When installing optional drain-up machine, disconnect the CN31 jumper connector and replace it with the drain sensor (DS).
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
PCA-RP100GA PCA-RP125GA PCA-RP140GA
41
PCA-RP71HA PCA-RP125HA
SYMBOL
[ LEGEND ]
NAME SYMBOL NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V)
MF1, MF2 C1, C2 H2
FAN MOTOR CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER VARISTOR CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROLL) POWER SUPPLY (I. B) POWER SUPPLY (R. B) TRANSMISSION(INDOOR-OUTDOOR) RELAY (DEW PREVENTION HEATER) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) SWITCH (MODEL SELECTION)
See Table 1. SWITCH (CAPACITY CODE) See Table 2. SWITCH (EMERGENCY OPERATION)
P. B I. B
FUSE ZNR CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 X4 X5 X6 SW1
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R. B
TERMINAL BLOCK(INDOOR UNIT POWER (OPTION))
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0˚C/15k, 25˚C/5.4k DETECT) COND./ EVA.TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
WIRED REMOTE CONTROLLER BOARD SW2 SWE
Service board
SW1
Table 1
1 2 3 4 5
ON OFF
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PCA-RP71HA
ON OFF
Service board
1 2 3 4 5
MODELS
PCA-RP125HA
ON OFF
1357
MF1
BLU
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
ORN
C1
RED
RED
13 13 13 12
1 2
1 2
3
13
11
654321
MF2
BLU
YLW
YLW
ORN
BLK
RED
WHT
WHT
YLW
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
BRN
C2
GRY
RED
654321
D.HEATER CNC (RED)
For PCA-RP125HA
X6 X5 X4
X6 X5 X4
ZNR
FUSE
SWE
FAN
(WHT)
SW2 SW1
LED3 LED2 LED1
H2
OFF
ON
12 12 12
12 13
12
WHT
WHT
REMOCON
CN22
(BLU)
TH1 TH2 TH5
BLU
BLU
BLK
BLK
1
2
2
1
TB5
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
PIPE CN29 (BLK)
R.B
TB6
TRANSMISSION WIRES DC12V
CN41 CN2L
CN32CN51
ROWER
CNDK (RED)
ROWER
CND
(ORN)
DC13.1V
CNDK
(RED)
CN2S
(WHT)
P.B
I.B
BRN
YLW ORN ORN
S1
S2
S3
TB4
TO OUTDOOR UNIT
ROWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
Refer to tables 1 and 2 for service PCB.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
TB2
BLU
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
ORN ORN
YLW
GRN/YLW
BRN
w1 (Fig.1)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
42
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
1357
MF
ORN
C
RED
BLK
BLU
YLW
13 13 13 12
1
2
2 1
3
13
ML
YLW
YLW
BLK
ORN
YLW
YLW ORNS1S2
S3
WHT
WHT
WHT
BRN
ORN
RED
I.B
FAN (WHT)
LOUVER CNL (YLW)
X4X5X6
X6
X5 X4
X2
ZNR
FUSE
X2
LED3 LED2 LED1
SWE
ON OFF
POWER CNDK (RED)
POWER CND (ORN)
POWER CN2D (WHT)
WIRELESS
CN90
(WHT)
2 1
REMOCON
CN22
(BLU)
CN32
CN2L
2
1
TB6
2 2
1 1
2 1
LIQUID CN21 (WHT)
INTAKE CN20 (RED)
PIPE CN29 (BLK)
CN24 CN41
CN51
R.B
TRANSMISSION WIRES DC12V
BLU BLU
TH1
TH2
TH5
SW1SW2
TB4
REDRED
WHT
RED BLU
GRN/YLW
88H
FS1FS2
H
53
1 2
L N
TB2
POWER SUPPLY ~(1 PHASE) 230V 50Hz
2 1
6 5
RED RED
YLW
26H
88H
YLW
YLW
16
HEATER
CN24
(YLW)
I.B
PSH -P.GAH
models only
INDOOR UNIT
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
Refer to tables 1 and 2 for service PCB.
P.B
CNSK (RED)
CN2S (WHT)
DC13.1V
TO OUTDOOR UNIT
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED BLU
GRY/YLW
RED BLU
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
ORN
BRN
1 (Fig.1)
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PSA-RP71GA PSH-P71GAH
PSA-RP100GA PSH-P100GAH
PSA-RP125GA PSH-P125GAH
PSA-RP140GA PSH-P140GAH
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
Service board
SW2
Table 1
1 2 3 4 5
MODELS
PSA-RP.GA PSH-P.GAH
ON OFF
P.B
INDOOR POWER BOARD
SYMBOL
[LEGEND]
NAME SYMBOL NAME SYMBOL NAME
I.B
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR (LOSSNAY) CN32 CONNECTOR (REMOTE SWITCH) CN41 CONNECTOR (HA TERMINAL-A) CN51 CONNECTOR (CENTRALLY CONTROL)
SW1
SWITCH (MODEL SELECTION) See Table 1.
SW2
SWITCH (CAPACITY CODE) See Table 2.
SWE SWITCH (EMERGENCY OPERATION)
X4 RELAY (FAN MOTOR) X5 RELAY (FAN MOTOR) X6 RELAY (FAN MOTOR)
X2
RELAY (LOUVER)
POWER SUPPLY (R.B)
LED1 POWER SUPPLY (I.B) LED2
TRANSMISSION (INDOOR-OUTDOOR)LED3
WIRED REMOTE CONTROLLER BOARD TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
R.B
TB6
HEATER
HEATER
THERMAL FUSE (110˚C16A)
H
FS1,2
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
C CAPACITOR (FAN MOTOR)
FAN MOTOR
MF
LOUVER MOTOR
ML TB2
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TB4
TERMINAL BLOCK (HEATER) PSH-P.GAH models only or option for PSA-RP.GA models.
ROOM TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
PIPE TEMP.THERMISTOR/LIQUID (0˚C/15k, 25˚C/5.4k DETECT)
COND./EVA.TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
TH1
TH2
TH5
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram.
43
PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
123456
OFF
ON
100V
MODEL
SW5-6 w
3
w 1 MODEL SELECT
123456
OFF
ON
125V
123456
78
78
78
OFF
ON
140V
123456
OFF
ON
SW6
123456
OFF
ON
123456
OFF
ON
TB1 MC MF1,MF2 21S4
63H TH3 TH4 TH6 TH7 TH8 LEV-A DCL
Terminal Block<Power Supply, Indoor/Outdoor > Motor Compressor Fan Motors
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV Solenoid Valve (Bypass Valve) CH Crankcase Heater
Thermistor<Outdoor Pipe>
Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Electronic Expansion Valve
Reactor
ACTM
Active Filter Module
CB
Main Smoothing Capacitor
Diode Bridge
Noise Filter Circuit Board
N.F.
Controller Circuit Board
Switch<Pump Down> Connector<Emergency Operation>
SWP CN31
C.B.
DS2,3
Power Module
IPM
SYMBOL
[LEGEND]
NAME SYMBOL NAME SYMBOL NAME
Connection Terminal<DC Voltage>
Connection Terminal<L/N- Phase>
TABP1/P2/P
TABS/T
Connection Terminal<DC Voltage>
TABN1/N2/N
Power Circuit Board Connection Terminal<U/V/W-Phase>
P.B.
TABU/V/W
Fuse<T6.3AL250V> Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
F1~F4 SW1
SW4 SW5 SW6
SW8
Switch
SW9
Switch<Function Setup>
SW7
Switch
LED1,LED2
Light Emitting Diodes <Operation Inspection Indicators>
CNM CNMNT CNVMNT CNDM
Connector<A-Control Service Inspection Kit> Connector<Connected to Optional M-NET Adapter Board> Connector<Connected to Optional M-NET Adapter Board> Connector< Connected for Option (Contact Input)>
X51,X52,X54,X55
Relay
CNVMNT
(WHT)
CNMNT
(WHT)
CNM
(WHT)
CN5
(WHT)
CN2M
(WHT)
CND
(WHT)
CN4
(WHT)
CN2
(WHT)
21S4
(GRN)
SS
(WHT)
CN52C
(BLK)
CN5
(RED)
(RED)
CNAC2
(WHT)
CNAC1
NO
LO
SV2
(BLU)
w 2
CNDM
(WHT)
CN51
(WHT)
5
5
5
3
1
1
5
1
16
1
12
CN52C
(RED)
1
1
1
3
5
2
2
14
3
LEV-A
(WHT)
LED2
LED1
TH7/6 (RED)
TH3
(WHT)
CNF1
(WHT)
CNF2 (
WHT)
CNS (
WHT)
CNAC
(
WHT)
CNDC
(
PNK)
F2
F1
F3
X52
X55
X51
F4
21S4
TRANS
MF1
C.B.
w 2
MS
3~
63H
(YLW)
TH4
(WHT)
63H
LEV-A
M
TH7 TH6 TH3 TH4
SW7
SW6SW1
SW9
CN31
w 1w 1
SW5SW8SW4 SWP
TABN TABP
DCL
UVW
MC
P
L1 L2
Io
N1 N2
CN3
(WHT)
CNAF
(WHT)
CNDC
(PNK)
CN2
(WHT)
IPM
TABT
DS3
DS2
TABS
TABP1
U
TH8
CN4
(WHT)
CN5
(RED)
CB
17
14
7
7
1
31
12 34
4
7
1
1
7 1 2
6
3
2
–~
~
~
~
+
1
+
+
3
2
1
1
122
1
3
1
1
2
2
7
31
t°t° t°t°
MF2
MS
3~
MS
3~
31
SV
52C
31
SV1/CH
(GRY)
CH
w
2
X54
31
N.F.
P.B.
LED2 LED3 LED4
LED5
LED1
31
3
SW1
SW11
SW12
TB7
M-NET SUBSTRATE
M-NET
ABS
When M-NET adaptor is connected
1 2
2 2
+
1 2
4
+
16
TABP2
TABN2
TABN1
TABURED
BLK
TABW
TABVWHT
+
3
2
2
1
1
3 1
U
U
1 2
2
E2
EI
CY1 CY2
TB1
S3S2S1NL
INDOOR UNIT
LI
NI
POWER SUPPLY ~/N 230V 50Hz
ACTM
w 2 P125,P140 only w 3 SW5-1 to 5 : Function Switch
t°
44
PUHZ-P200YHA PUHZ-P250YHA
TH7/6 (RED)
TH3
(WHT)
TH4
(WHT)
TH7TH6 TH3 TH4
412121
t°t°t°t
°
63H
LEV-A (WHT)
LEV-A
M
LED1
LED2
61
CNVMNT
(WHT)
31
CNMNT
(WHT)
CNM
(WHT)
51
35
5
141
63H
(YLW)
31
CN2
(WHT)
7
7
1
CN2
(WHT)
7
7
1
CNDM
(WHT)
CN3S
(WHT)
CN51
(WHT)
131315
X51
X52
SW7
SW6SW1
SW9
CN31
w1w1
SW5SW8SW4
SWP
CN4
(WHT)
12
1313
2
21S4
SS
(WHT)
21S4
(GRN)
CNAC (WHT)
F4
F3
21
43
2
3
1
CNDC
(PNK)
CNS
(WHT)
31
TRANS
CNF1
(WHT)
CNF2
(WHT)
MF1
MS
3~
7
1
7
1
MF2
MS
3~
C. B.
P. B.
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3 LED4
TB7
LED1
LED5
2 1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
ABS
When M-NET adapter is connected
3
5
1
2
2
1 2
2
1
CN4
(WHT)
CN5
(RED)
WHT
FUSE1
FUSE2
WHT
REDRED
MS
3~
POWER SUPPLY 3N~ 400V 50Hz
INDOOR UNIT
TB1
L3
L2
L1
N
U
U
UU
U
31
2
2
13
CNDC (PNK)
CNL
(BLU)
3112
CNCT (RED)
CNAC2
(RED)
31
CNAC1
(WHT)
BLK
BLK
WHT
WHT
U
LO 1
LO 2
LO3
LI 1
LI 2
LI 3
NI
RED
WHT
BLU
BLK
GRN/YLW
GD2GD1
RED
WHT
BLK
N. F.
TB2
DCL
ACL4
S3
S2
S1
ORN
YLW
CY2
CY1
BRN
NO FUSE BREAKER
RED
RED
RS
RED
WHT
WHT
WHT
BLK
BLK
BLK
X52A
BLK
BLK
TB-P2
TB-P1
TB-C1 TB-N1
CB1 CB2
W
V
MC
U
TB-L1
TB-L2
TB-L3
SC-U
SC-V
SC-W
RED
MODEL
SW6
w1 MODEL SELECT
SW5-6 w2
12345678
w2. SW5 -1 to 5 : Function Switch
OFF
123456
OFF
ON
200Y
ON
12345678
OFF
123456
OFF
ON
250Y
ON
FUSE1, FUSE2
Connector<Connection for Option>
CN51
Relay
X51,X52
Connector<Connection for Option>
CN3S
TB1 MC
MF1,MF2 21S4 63H TH3 TH4 TH6 TH7 LEV-A
DCL
Terminal Block<Power Supply>
TB2 Terminal Block<Indoor/Outdoor>
Motor for Compressor Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
SC-U/V/W
TB-L1/L2/L3
Connection Terminal<U/V/W -Phase>
Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor>
Fuse<
T15AL250V>
Capacitor
Electronic Expansion Valve
Reactor
ACL4
Reactor
Connection Terminal<L1/L2/L3-Power supply>
P.B.
Power Circuit Board
RS
Rush Current Protect Resistor
CB1,CB2
CY1,CY2
Main Smoothing Capacitor
Connection Terminal
Noise Filter Circuit Board Connection Terminal<
L1/L2/L3/NI-Power supply>
Connection Terminal<Ground>
52C Relay
N.F.
LI1/ LI2/LI3/NI LO1/ LO2/LO3
Connection Terminal<
L1/L2/L3-Power supply>
GD1,GD2
Controller Circuit Board
C.B.
TB-C1
X52A
Connection Terminal
TB-N1
SYMBOL
[LEGEND]
NAME SYMBOL NAME SYMBOL NAME
Connection Terminal
TB-P1
Connection Terminal
TB-P2
Switch<Function Setup> Switch<Function Setup>
Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address>
Switch<Test Operation> Switch<Function Switch> Switch<Model Select>
SW7
SW1 SW4
SW5 SW6
SW8
Switch
SW9
Switch<Pump Down>
SWP
Connector<Emergency Operation> LED<Operation Inspection Indicators>
CN31
F3,F4
CNMNT CNVMNT
CNDM
Connector < Connected for Option (Contact Input)>
Fuse< T6.3AL250V>
LED1,LED2
CNM
Connector<A-Control Service Inspection Kit>
SS
Connector<Connection for Option>
Connector <Connected to Optional M-NET Adapter Board>
Connector <Connected to Optional M-NET Adapter Board>
Terminal Block(M-NET connection)
Connector<
Transmission>
Connector<
Power Supply>
LED<
Power Supply:DC5V>
LED<
Power Supply:DC12V>
LED<
Connection to Outdoor Unit>
LED<
Transmission:Sending>
LED<
Transmission:Receiving>
Connector<
M-NET communication>
SYMBOL
NAME
Switch<Address setting:2nd digit>
Switch<Status of communi
cation>
Switch<Address setting:1st digit>
TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5
M-NET ADAPTER
45
5
Thermistor TH2 Pipe temperature (Liquid)
Distributor with strainer(#50)
Thermistor TH5 (Cond./Eva. temperature)
Thermistor TH1 (Room temperature)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer(#50)
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·BA PCA-RP·GA(2) PCA-RP·HA PKA-RP·GAL PKA-RP·FAL(2) PSA-RP·GA PEAD-RP·EA(2) PEAD-RP·GA
46
PEA-RP200, 250GA
Heat exchanger
Condenser/evaporator temperature thermistor (TH5)
Room temperature thermistor(TH1)
Pie temperature thermistor/Liquid (TH2)
PEA-RP400GA PEA-RP500GA
Unit : mm
Strainer
Refrigerant GAS pipe connection Brazing
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant LIQUID pipe connection Brazing
Strainer
Heat exchanger
Condenser/evaporator temperature thermistor (TH5-2)
Pie temperature thermistor/Liquid (TH2-2)
Condenser/evaporator temperature thermistor (TH5-1)
Strainer
Refrigerant GAS pipe connection Brazing
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant LIQUID pipe connection Brazing
Strainer
Strainer
Refrigerant GAS pipe connection Brazing
Room temperature thermistor(TH1-1)
Room temperature thermistor(TH1-2)
Pie temperature thermistor/Liquid (TH2-1)
Refrigerant LIQUID pipe connection Brazing
Strainer
47
5-2. OUTDOOR UNIT Unit : mm
PUHZ-P100VHA2
Refrigerant GAS pipe
inch
15.88mm([5/8
Refrigerant LIQUID pipe
9.52mm([3/8
)
inch
Stop valve
Accumulator
)
Stop valve (with service port)
(#50)
Strainer
Service port (check)
Strainer (#40)
4-way valve
Muffler
Service port (check)
Compressor
Refrigerant flow in cooling Refrigerant flow in heating
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH4)
(#100)
Strainer
Linear expansion valve
Thermistor (TH6)
Thermistor (TH3)
Distributor
(#100)
Strainer
PUHZ-P125VHA2 PUHZ-P140VHA2
Refrigerant GAS pipe
mm([
15.88
Refrigerant LIQUID pipe
9.52
mm([
5/8 inch)
3/8 inch)
(with service port)
Stop valve
(#50)
Strainer
Strainer (#40)
Stop valve
Service port (check)
4-way valve
Accumulator
Bypass valve
Compressor
Strainer
(#100)
Service port (check)
High pressure protect switch
Muffler
Thermistor (TH4)
Strainer
(#100)
Linear expansion valve
Thermistor (TH6)
Distributor
Thermistor (TH3)
Capillary tube (
[
4.0o[3.0o-L200)o2
48
Unit : mm
PUHZ-P200YHA PUHZ-P250YHA
Refrigerant GAS pipe [25.4([1 inch)
Refrigerant LIQUID pipe P200 : [9.52([3/8 inch) P250 : [12.7([1/2 inch)
Ball valve
Strainer
Accumulator
Stop valve (with service port)
Service port
(check)
(#50)
Strainer (#40)
4-way valve
Strainer (#100)
Strainer (#100)
Service port
(check)
High pressure protect switch
Muffler
Thermistor (TH4)
Compressor
Linear expansion valve
Strainer (#100)
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
49
6
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.6
0.8
1.0
1.2
1.4
Cooling capacity ratio
Outdoor intake air dry-bulb temperature <D.B. :>
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.4
0.6
0.8
1.0
1.2
Cooling input ratio
Outdoor intake air dry-bulb temperature <D.B. :>
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-P·VHA2, PUHZ-P·YHA
Cooling capacity
Indoor intake air wet-bulb temperature <W.B. :>
Cooling input
Indoor intake air wet-bulb temperature <W.B. :>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
50
Heating capacity
Indoor intake air dry-bulb temperature <D.B. :>
Heating input
Outdoor intake air wet-bulb temperature <W.B. :>
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
51
7
Refrigerant piping length (one way)
75m70m60m55m50m40m30m
20m
10m5m
Outdoor unit
Cooling capacity correction factors
PUHZ-P100VHA2
PUHZ-P125VHA2
PUHZ-P140VHA2
PUHZ-P200YHA
PUHZ-P250YHA
Heating capacity correction factors
1.00
1.00
1.00
1.00
1.00
0.985
0.981
0.976
0.985
0.981
0.957
0.946
0.931
0.958
0.946
0.931
0.914
0.893
0.931
0.914
0.908
0.885
0.858
0.908
0.885
0.886
0.858
0.827
0.887
0.858
0.876
0.845
0.813
0.876
0.845
— — —
0.865
0.834
— — —
0.847
0.812
— — —
0.838
0.802
Refrigerant piping length (one way)
75m70m60m55m50m40m30m
20m
10m5m
Outdoor unit
PUHZ-P100VHA2
PUHZ-P125VHA2
PUHZ-P140VHA2
PUHZ-P200YHA
PUHZ-P250YHA
1.00
1.00
1.00
1.00
1.00
0.997
0.997
0.997
0.997
0.997
0.991
0.991
0.991
0.991
0.991
0.985
0.985
0.985
0.985
0.985
0.979
0.979
0.979
0.979
0.979
0.973
0.973
0.973
0.973
0.973
0.970
0.970
0.970
0.970
0.970
— — —
0.967
0.967
— — —
0.961
0.961
— — —
0.958
0.958
CORRECTION FACTORS
PUHZ-P·VHA2 PUHZ-P·YHA
52
APPLICABLE EXTENSION PIPE FOR EACH MODEL8
<Table 1-1> Maximum pipe length (P100-140)
50m
[20m]
<Marks in the table>
The maximum pipe length Charge-less pipe length
: It can be used. : Cooling capacity is lowered. : Additional refrigerant charge is required when the pipe length exceeds 10m(P100-140)/20m(P200, 250).
<Table 1-2> Maximum pipe length (P200, 250)
Note : Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
Liquid
pipe
(mm)
Gas
pipe
(mm)
OD
Thickness
OD
Thickness
P200
P250
[9.52
t0.8
[12.7
t0.8
[15.88
t1.0
[22.2
t1.0
50m
[30m]
50m
[30m]
[25.4
t1.0
Normal piping
70m
[30m]
70m
[30m]
[28.58
t1.0
70m
[30m]
70m
[30m]
[22.2
t1.0
50m
[20m]
50m
[30m]
[25.4
t1.0
50m
[20m]
Nomal piping
70m
[30m]
[22.2
t1.0
40m
[20m]
45m
[20m]
[25.4
t1.0
40m
[20m]
45m
[20m]
[28.58
t1.0
40m
[20m]
45m
[20m]
[28.58
t1.0
50m
[20m]
70m
[30m]
[31.75
t1.0
40m
[20m]
45m
[20m]
<Table 2-1> Maximum pipe length(P100-140)
<Table 2-2> Maximum pipe length(P200, 250)
<Table 3-2> Maximum pipe length(P200, 250)
<Table 3-1> Maximum pipe length(P140)
ø
9.52
ø15.88
Standard size
50m
[30m]
50m
[30m]
ø
9.52
ø19.05
50m
[30m]
50m
[30m]
ø
12.7
ø19.05
30m
[10m]
30m
[10m]
P140(RP50o3)
ø6.35 ø12.7 ø9.52
ø15.88
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
P100
P125,P140
Liquid
pipe
(mm)
OD
Thickness
OD
Thickness
Gas pipe
(mm)
ø15.88
t1.0
Standard size
50m
[20m]
Standard size
50m
[30m]
ø19.05
t1.0
50m
[20m]
50m
[30m]
ø15.88
t1.0
25m
[10m]
30m
[10m]
ø19.05
t1.0
25m
[10m]
30m
[10m]
ø9.52
t0.8
ø9.52
ø15.88
Standard size
50m
[20m]
50m
[20m]
ø9.52
ø15.88
Standard size
50m
[30m]
ø9.52
ø19.05
50m
[20m]
50m
[20m]
ø9.52
ø19.05
50m
[30m]
ø12.7
ø19.05
25m
[10m]
25m
[10m]
ø12.7
ø19.05
30m
[10m]
P100(RP50o2)
P125(RP60o2)·P140(RP71o2)
ø6.35 ø12.7 ø9.52
ø15.88
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Branch
pipe
(mm)
[B, C]
Main pipe
(mm)
[A]
Branch
pipe
(mm)
[B, C, D]
Main pipe
(mm)
[A]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[20m]
[25.4
t1.0
50m
[20m]
[28.58
t1.0
50m
[20m]
[22.2
t1.0
40m
[20m]
[25.4
t1.0
40m
[20m]
[28.58
t1.0
40m
[20m]
[31.75
t1.1
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Main
pipe
(mm)
[A]
Branch
pipe
(mm)
[B,C]
Liquid
pipe Gas
pipe
Liquid
pipe Gas pipe
[9.52 [15.88
[9.52O.D.
Thickness
O.D.
Thickness
t0.8 t0.8 t1.0 t1.0t0.8 t0.8
[12.7 [15.88 [9.52 [12.7 [15.88
P200(RP100x2)
P250(RP125x2)
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[20m]
[25.4
t1.0
50m
[20m]
[28.58
t1.0
50m
[20m]
[22.2
t1.0
40m
[20m]
[25.4
t1.0
40m
[20m]
[28.58
t1.0
40m
[20m]
[31.75
t1.1
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Main
pipe
(mm)
[A]
Branch
pipe (mm) [B,C]
Liquid
pipe Gas pipe
Liquid
pipe Gas pipe
[9.52 [15.88
[9.52
O.D.
Thickness
O.D.
Thickness
t0.8 t0.8 t1.0 t1.0t0.8 t0.8
[12.7 [15.88 [9.52 [12.7 [15.88
P200(RP60x3)
P250(RP71x3)
ø12.7
t0.8
ø12.7
t0.8
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM and 1:2(1 indoor / 2 outdoor) SYSTEM
8-1-2. TWIN TRIPLE AND QUADRUPLE SYSTEM (1) TWIN SYSTEM
(2) TRIPLE SYSTEM
53
Outdoor unit
Outdoor unit side Indoor unit side Outdoor unit side Indoor unit side
Total length A+B+C+D+E
Branch pipe B, C, D
Gas side
Pipe size (mm) Actual piping length <m>
Indoor ~ Outdoor
Indoor ~ Indoor
(Note 1) No. of bend
Height deffence <m>
Liquid side
TWIN TRIPLE
100-140 140
{15.88 <5/8>
RP50 {12.7<1/2> RP60,71
{15.88<5/8>
{9.52<3/8>
RP50 {6.35<1/4> RP60,71 {9.52<3/8>
50m
20m
Indoor ~
Indoor |B-C| 8m |B-C| |C-D| |B-D| 8m
H30m h 1m 15
TWIN TRIPLE
QUADRUPLE
200, 250
{25.4 <1>
RP60,71 100, 125 {15.88<5/8>
RP50
{
12.7
<1/2> RP60 {15.88<5/8>
RP50
{
6.35
<1/4>
RP60
{
9.52<3/8>
{9.52<3/8> (P200) {12.7<1/2> (P250)
RP60,71 100, 125 {9.52<3/8>
70m
30m
|B-C| 8m |B-C| |C-D| |B-D| 8m
|B-C| |B-D| |B-E| |C-D| |C-D| |C-E| 8m
(3) QUADRUPLE SYSTEM
<Table 2-2> Maximum pipe length(P200, 250)
Main
pipe
(mm)
[A]
Branch
pipe (mm) [B,C]
Liquid
pipe Gas
pipe
Liquid
pipe Gas pipe
Liquid
pipe Gas pipe
Thickness
O.D.
Thickness
[6.35 [12.7
[9.52 [15.88
[9.52O.D.
t0.8 t0.8 t1.0 t1.0t0.8 t0.8
[22.2
[25.4
t1.0
Standard
size
70m
[30m]
70m
[30m]
[28.58
t1.0
70m
[30m]
70m
[30m]
t1.0
50m
[30m]
50m
[30m]
P200(RP50x4)
[12.7 [15.88 [9.52 [12.7 [15.88
[22.2
[25.4
t1.0
50m
[20m]
50m
[20m]
[28.58
t1.0
50m
[20m]
50m
[20m]
t1.0
50m
[20m]
50m
[20m]
[22.2
t1.0
40m
[20m]
40m
[20m]
[25.4
t1.0
40m
[20m]
40m
[20m]
[28.58
t1.0
40m
[20m]
40m
[20m]
[31.75
t1.1
40m
[20m]
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
P250(RP60x4)
[28.58
[25.4
t1.0
t1.0
Standard
size
70m
70m
[30m]
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Indoor unit
h
H
Distribution pipe
Indoor unit side
B
Indoor unit
C
Outdoor unit side
A
<TWIN SYSTEM> Total length A + B + C P100-140: 50 m P200, 250: 70 m
h
H
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe
Indoor unit side
Indoor unit
h
B
Indoor unit
C D
Indoor unit
H
Distribution pipe
Outdoor unit side
Outdoor unit
A
<TRIPLE SYSTEM> Total length A + B + C + D P140: 50 m P200, 250: 70 m
Indoor unit
B
D
C
E
Indoor unit
Outdoor unit
A
<QUADRUPLE SYSTEM> Total length A + B + C + D + E P200, 250 : 70 m
(4) Pipe size and refrigerant pipe limits
54
Note1. The number of bends in the refrigerant pipe is respectively 8 or less in the range of <A+B> <A+C> <A+D>.
2. PUHZ-P100: 20 m chargeless PUHZ-P125-250: 30 m chargeless
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
3.0kg
4.5kg
4.5kg
5.8kg
7.1kg
21 — 30m
0.6kg
31 — 40m
1.2kg
0.6kg
0.6kg
0.9kg
1.2kg
41 — 50m
1.8kg
1.2kg
1.2kg
1.8kg
2.4kg
51 — 60m
2.7kg
3.6kg
61 — 70m
3.6kg
4.8kg
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Outdoor unit
Max.
pipe length
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
Amount of unit
filling refrigerant (kg)
PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2 PUHZ-P200YHA PUHZ-P250YHA
50m 50m 50m 70m 70m
<Table 5> Required additional charge when the liquid pipe is one size larger than the standard diameter (1:1 SYSTEM)
[12.7
[12.7 [15.88 [15.88
P100 P125,140 P200 P250
Liquid pipe dia. Chargeless
25m 30m 40m 45m
100 g per 1 m longer than 10 m 100 g per 1 m longer than 10 m Additional refrigerant amount (Longer than 20 m) W(g) = 180 o pipe length(m) - 3000
10m 10m 20m 20m
Max. pipe length
Refrigerant amount to be added
<Table 6> Required additional charge when the liquid pipe is one size larger than the standard diameter
(TWIN/TRIPLE/QUADRUPLE SYSTEM) Capacity P100,125,140 P200, 250
When the extension pipe length (main piping + branch piping) exceeds 10 m(P100-140)/20m(P200, 250) Additional refrigerant amount W(g) = (100 o L2) + (60 o L3) + (30 o L4) - 2000 Additional refrigerant amount W(g) = (180 o L1) + (120 o L2) + (90 o L3) + (30 o L4)- 3000
If the calculation produces a negative number ( W [ 0), additional charging is not necessary. L1:
[15.88 liquid pipe length (m) L2: [12.7 liquid pipe length (m)
L3: [9.52 liquid pipe length (m) L4: [6.35 liquid pipe length (m)
If the calculation produces a negative number ( W [ 0), additional charging is not necessary.
Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter.
55
8-3. CAPACITY CURVE
PUHZ-P100, 125, 140 VHA2<Standard size>
100
95
90
P100-140
Cooling Heating
Capacity ratio [%]
85
80
5 10152025303540455055
Corrected pipe length [m]
PUHZ-P200, 250YHA<Standard size>
100
95
90
85
80
Capacity ratio [%]
75
P100
P125
P140
P200, 250
Cooling Heating
P200
P250
70
5 10152025303540455055606570
Corrected pipe length [m]
PUHZ-P200, 250YHA<Gas pipe’s diameter is one size smaller than the standard size.>
100
P200, 250([22.2)
95
Cooling
90
85
80
Heating
P200([22.2)
Capacity ratio [%]
75
70
5 10152025303540455055
P250([22.2)
Corrected pipe length [m]
56
9
Airflow Air speed Coverage range
m
3
/min
m/sec
m
PCA-RP50GA
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA PCA-RP100GA
PCA-RP125GA PCA-RP140GA
25
4.1
12.6
34
4.4
15.2
34
4.4
15.2
18
3.8
10.4
18
3.8
10.4
13
3.7
8.8
Airflow Air speed Coverage range
m
3
/min
m/sec
m
19
2.9
7.9
38
4.2
13.2
PCA-RP71HA PCA-RP125HA
12
5.3
10(32.8)
PKA-RP50GAL
Airflow Air speed Coverage range
m
3
/min
m/sec
m(ft)
20
4.9
12.4(40.7)
PKA-RP71FAL
20
4.9
12.4(40.7)
PKA-RP50FAL2
PKA-RP60FAL
28
5.4
15.3(50.2)
PKA-RP100FAL
Airflow Air speed Coverage range
m
3
/min
m/sec
m(ft)
Airflow Air speed Coverage range
m
3
/min
m/sec
m
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
18
2.6
8.3
31
4.5
14.3
33
4.8
15.2
35
4.9
16.1
PLA-RP71BA
PLA-RP100BA PLA-RP125BA PLA-RP140BA
30
5.3
8.0
32
5.6
8.5
31
5.4
8.2
Airflow Air speed Coverage range
m
3
/min.
m/sec.
m
21
3.7
5.6
18
3.2
4.8
18
3.2
4.8
PLA-RP50BA PLA-RP60BA
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
57
9-2. PLA-RP·BA
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Branch duct hole
A
A
A
14-[2.8 burring hole
Indoor unit
[150 cut out hole
Fresh air intake hole
[175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-[2.8 burring hole
Unit : mm
Branch duct hole diagram (view from either side)
[125 burring hole pitch
[100 cut out hole
Ceiling
*158
120
120
350
90
70°
100 100 90
100
130
*155
*167
Fig. 1
9-2-1 FRESH AIR INTAKE AND BRANCH DUCT
58
3. Fresh air intake volume & static pressure characteristics
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 Direct intake to unit
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
2 Direct intake to unit
Static pressure[Pa]
Static pressure[Pa]
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
2 - inlet
1 - inlet
1 At using multi-function casement, standard filter
-200
-150
-100
-50
0
50
02468
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
Airflow rate [m3/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
1 At using multi-function casement, standard filter
PLA-RP50~71BA
PLA-RP100~140BA
Static pressure[Pa]
59
4. Change of outlet numbers
<4- way air flow and branch duct>
w Branch duct should be connected to one of the branch duct holes on the main unit.
Branch duct
Air intake
Air outlet
<3- way air flow and branch duct>
w Close the outlet on the side of branch duct and air flows in 3 directions.
Branch duct
Air intake
Air outlet
Air outlet closed position
Air outlet closed position
<2- way air flow and branch duct>
w Close the outlet on the side of branch duct and one of the other outlets. Air flows in 2 directions.
Air intake
Branch duct
Air outlet closed position
Air outlet closed position
[The optional air outlet is necessary.] To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter.
(When the air outlets are closed, close the vane by removing the vane connector.)
Indoor unit
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
Outlet concave portion
Air outlet shutter plate (Option)
60
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
2-way airflow (horizontal vane) Round duct
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP50, 60BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP71BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
2-way airflow (horizontal vane) Rectangular duct
0
10
20
30
02
High
Low
High
Low
High
Low
High
Low
High
Low
468
Airflow rate [m
3
/min]
02468
Airflow rate [m3/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Static pressure [Pa]
0
10
20
30
Static pressure [Pa]
0
10
20
30
40
50
60
70
80
0246810
Airflow rate [m
3
/min]
0246810
Static pressure [Pa]
0
10
20
30
40
50
60
70
80
Static pressure [Pa]
0
10
20
30
40
50
60
70
80
90
100
0 2 4 6 8 10 12
Airflow rate [m
3
/min]
024681012
Static pressure [Pa]
0
10
20
30
40
50
60
70
80
90
100
Static pressure [Pa]
High
Low
Duct Duct
Duct
Close
Duct
Close
Duct
Close
Close
Duct
Close
Close
PLA-RP71BA
61
PLA-RP125BA
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
30
30
Low
Duct
High
Duct
Close
High
Duct
20
10
Static pressure [Pa]
Low
0
02468
Airflow rate [m
High
3
/min] Airflow rate [m3/min]
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
80
70
60
50
40
Static pressure [Pa]
30
Duct
Close
High
20
10
Static pressure [Pa]
0
02468
80
70
60
50
40
Static pressure [Pa]
30
20
10
0
0246810
Low
Airflow rate [m3/min] Airflow rate [m3/min]
20
10
0
0246810
Low
2-way airflow (horizontal vane) Round duct 2-way airflow (horizontal vane) Rectangular duct
100
90
80
70
60
50
40
Duct
Close
High
Static pressure [Pa]
30
Low
20
10
0
024681012
Airflow rate [m3/min] Airflow rate [m3/min]
Close
100
90
80
70
60
50
40
Static pressure [Pa]
30
20
10
0
024681012
Low
Duct
Close
High
Close
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP100BA, PLA-RP140BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP125BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
62
9-3. PEAD-RP·EA,EA2,GA
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Airflow (CMM)
6 8 10 12 14 16 18 20
810121416182022
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Airflow
Capacity
input
Cooling
Airflow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Airflow (CMM)
8 10121416182022
810121416182022
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Airflow (CMM)
Correction factor
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Airflow (CMM)
8 1012141618202224
12 14 16 18 20 22 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Airflow
Capacity
input
Cooling
Airflow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Airflow (CMM)
10 12 14 16 18 20 22 24 26
12 14 16 18 20 22 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Airflow (CMM)
Correction factor
9-3-1. FAN PERFORMANCE AND CORRECTED AIRFLOW PEAD-RP50EA
PEAD-RP60EA
63
PEAD-RP71EA
Lo
Hi
140 120 100
200 180 160
80 60 40 20
12 16 20 24 28 32
Airflow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140 120 100
180 160
80 60 40 20
12 16 20 24 28 32
Airflow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
Hi
Corrected Airflow
Capacity Input
1.1
1.0
0.9
0.8
12 16 20 24 28 32
Airflow (CMM)
Correction factor
Cooling
=
1.1
1.0
1.3
1.2
0.9
0.8 12 16 20 24 28 32
Airflow (CMM)
Correction factor
Heating
Lo
Hi
140 120 100
200
220
180 160
80 60 40 20
32 34 36 38 40 42 44 46 48
Airflow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140 120 100
200
220
180 160
80 60 40 20
32 34 36 38 40 42 44 46
Airflow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
Lo
Hi
Corrected Airflow
Capacity Input
1.1
1.0
0.9
0.8 32 34 36 38 40 42 44 46 48
Airflow (CMM)
Correction factor
Cooling
1.1
1.0
1.2
0.9
0.8 32 34 36 38 40 42 44 46 48
Airflow (CMM)
Correction factor
Heating
=
=
PEAD-RP100EA2 PEAD-RP125EA
64
PEAD-RP140EA
1.2
1.1
1.0
0.9
0.8 36 38 40 42 44 46
48
50 52
Airflow (CMM)
Correction factor
Heating
Corrected Airflow
Capacity Input
1.1
1.0
0.9
0.8 36 38 40 42 44 46
48 50
52
Airflow (CMM)
Correction factor
Cooling
Lo
Hi
200 180
160 140 120 100 80 60 40 20
36
38 40 42 44 46 48
50
Airflow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
200
220
180 160 140 120 100 80 60 40 20
36
38 40 42 44 46 48 50
52
Airflow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Hi
65
PEAD-RP60GA
PEAD-RP71GA
66
PEAD-RP100GA
67
9-4. PEA-RP·GA
PEA-RP200GA Fan Performance Curve 50Hz
PEA-RP250GA Fan Performance Curve 50Hz
PEA-RP400GA Fan Performance Curve 50Hz
PEA-RP500GA Fan Performance Curve 50Hz
70.0 80.0 100.0 110.0 120.0 130.090.0
(Pa)
(Pa) (Pa)
External static pressure
Airflow
(CMM)
0
50
100
150
200
300
250
110.0100.0 120.0 130.0 140.0 150.0 160.0 170.0
(Pa)
External static pressure
Airflow
(CMM)
0
50
100
150
200
350
300
250
Hi
Lo
45.0 50.0 55.0 60.0 65.0 70.0
Hi
Lo
0
50
100
150
200
250
300
0
50
100
150
200
250
60.0 65.0 70.0 75.0 80.0 85.0 90.0
External static pressure
Airflow Airflow
(CMM)
(CMM)
External static pressure
Fan Performance Curve
68
PLA-RP50BA
NOTCH SPL(dB) LINE
High 32 Medium1 31 Medium2 29
Low 28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PLA-RP60BA
NOTCH SPL(dB) LINE
High 32
Medium1 31 Medium2 29
Low 28
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PLA-RP71BA
NOTCH SPL(dB) LINE
High 34 Medium1 32 Medium2 30
Low 28
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PLA-RP100BA
NOTCH SPL(dB) LINE
High 40 Medium1 37 Medium2 34
Low 32
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
10
NOISE CRITERION CURVES
10-1. INDOOR UNIT
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
69
PLA-RP125BA
NOTCH SPL(dB) LINE
High 41 Medium1 39 Medium2 36
Low 34
PLA-RP140BA
NOTCH SPL(dB) LINE
High 44 Medium1 42 Medium2 39
Low 36
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
CEILING
UNIT
1.5m
MICROPHONE
70
High Low
High Low
High Low
High Low
NC60
NC50
NC40
NC30
NC20
70
60
50
40
30
20
63 125 250 500 1000 2000 4000 8000
10
0
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
Approximate minimum audible limit on continuous noise
NC60
NC50
NC40
NC30
NC20
70
60
50
40
30
20
63 125 250 500 1000 2000 4000 8000
10
0
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
Approximate minimum audible limit on continuous noise
NC60
NC50
NC40
NC30
NC20
70
60
50
40
30
20
63 125 250 500 1000 2000 4000 8000
10
0
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
Approximate minimum audible limit on continuous noise
NC60
NC50
NC40
NC30
NC20
70
60
50
40
30
20
63 125 250 500 1000 2000 4000 8000
10
0
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
Approximate minimum audible limit on continuous noise
PEAD-RP50EA
(External static pressure 30Pa)
PEAD-RP50EA
(External static pressure 70Pa)
PEAD-RP60EA
(External static pressure 30Pa)
PEAD-RP60EA
(External static pressure 70Pa)
71
72
Sound Data
Model
PEA-RP200GA
PEA-RP250GA
PEA-RP200, 250 : Upper High/Lower Low
SPL
dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21 52 56 55 52 50 48 44 34 28 49 51 51 48 47 45 41 30 22
OCTAVE BAND FREQ.Hz
PEA-RP400GA
PEA-RP500GA
52 53 51 52 50 46 44 39 30
53 55 54 51 50 48 44 40 31
Position measurement
Indoor unit
2m
Outlet
1m
Inlet
Measurement point
1.5m
73
PKA-RP50GAL
NOTCH
High Medium1 Medium2
Low
SPL(dB)
43 41 38 36
LINE
PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL
NOTCH
High
Low
SPL(dB)39LINE
45
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PKA-RP100FAL
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
46 41
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
WALL
1m
1m
MICROPHONE
74
PCA-RP50GA
NOTCH
High Medium1 Medium2
Low
SPL(dB)
42 40 38 37
LINE
PCA-RP50GA2 PCA-RP60GA PCA-RP71GA
NOTCH
High Medium1 Medium2
Low
SPL(dB)
43 41 39 37
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PCA-RP100GA
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
45 43 41 40
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PCA-RP125GA
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
46 45 43 41
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
75
PCA-RP140GA
90
80
NOTCH
High Medium1 Medium2
Low
SPL(dB)
48 46 44 42
LINE
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
PCA-RP71HA
90
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
SPL(dB)
38 34
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
1m
1m
about 1.4m
MICROPHONE
PCA-RP125HA
90
NOTCH
High
Low
SPL(dB)
50 44
ceiling
unit
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
76
PSA-RP71GA
NOTCH
High
Low
SPL(dB)
45 40
LINE
PSA-RP100GA
NOTCH
High
Low
SPL(dB)
49 44
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PSA-RP125GA
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
51 46
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
77
PSA-RP140GA
90
80
NOTCH
High
Low
SPL(dB)
52 47
LINE
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
THRESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
unit
1m
1m
floor
78
10-2. OUTDOOR UNIT
1.5m
1m
MICROPHONE
UNIT
GROUND
PUHZ-P100VHA2
90
MODE
COOLING
HEATING
SPL(dB)
50 54
LINE
PUHZ-P125VHA2
90
MODE
COOLING
HEATING
SPL(dB)
51 55
LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUHZ-P140VHA2
90
MODE
COOLING
HEATING
SPL(dB)
52 56
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
PUHZ-P200YHA PUHZ-P250YHA
90
BAND CENTER FREQUENCIES, Hz
SPL(dB)
MODE
COOLING
HEATING
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE 59 59
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
79
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
11
11-1. INDOOR UNIT
Part Name Model Name Applicable model
Remote sensor PAC-SE41TS-E
PAC-SA88HA-E (1pc.) PAC-725AD (10pcs.)
Remote operation adapter Multiple remote controller adapter
PAC-SF40RM-E
All models
Remote on/off adapter PAC-SE55RA-E Power supply terminal kit L/N/Earth PAC-SG96HR-E
PAC-SH52HR-E
PEAD-RP·EA(2),
PCA-RP·GA(2) PKA-RP·GAL/FAL(2) PSA-RP·GA PLA-RP·BA
L/N PAC-SG97HR-E PCA-RP·HA
PEAD-RP·GA
Wireless remote controller + Wireless Adapter PAR-SL99B-E PCA-RP·GA(2) Drain lift up mechanism PAC-SH20DM-E PCA-RP50,60GA(2)
PAC-SH21DM-E PCA-RP71GA PAC-SH22DM-E PCA-RP100,125,140GA
High-efficiency filter PAC-SE80KF-E PCA-RP50GA
PAC-SE81KF-E PCA-RP60,71,100GA,50GA2 PAC-SE82KF-E PCA-RP125,140GA
Oil mist filter element (12pcs)
Duct flange for fresh air PAC-SF28OF-E PCA-RP·HA
PAC-SG38KF-E PAC-SF81KC-E PCA-RP71HA
(Front + Suspending bracket cover) PAC-SF82KC-E PCA-RP125HA
Decoration cover
Motor
Wired remote controller PAR-21MAAT-E PKA-RP·GAL (with terminal bed) PKA-RP·FAL(2) Drain lift up mechanism PAC-SE90DM-E PKA-RP·FAL(2)
PAC-SK003MT-F PEAD-RP125,140EA (for high external static pressure) PEAD-RP100EA2 Drain lift up mechanism PAC-KE03DM-F PEAD-RP·EA,EA2 Insulation kit PAC-SK010DK PEAD-RP·GA
Multi-function casement
PAC-SH53TM-E PAC-SH65OF-E
High-efficiency filter element
Flange for fresh air intake
PAC-SH59KF-E
(PAC-SH53TM-E is needed.)
Decoration panel with Wireless remote controller
PLP-6BALM
PLA-RP·BA
Decoration panel with Wired remote controller
PLP-6BAMD
Automatic filter elevation panel
PLP-6BAJ
i-see sensor corner panel
PAC-SA1ME-E
Wireless signal receiver
PAR-SA9FA-E
Space panel
PAC-SH48AS-E
Air outlet shutter plate
PAC-SH51SP-E
Decoration panel
PLP-6BA
OPTIONAL PARTS
80
11-2. OUTDOOR UNIT
Part Name Model Name
Applicable model
M-NET adapter PAC-SF80MA-E PUHZ-P100-250 A-control service tool PAC-SK52ST Drain socket PAC-SG61DS-E PUHZ-P100-250 Air outlet guide (P125-250 need 2 pieces.) PAC-SG59SG-E PUHZ-P100-250
PUHZ-P100-250
Air protect guide (P125-250 need 2 pieces.)
PAC-SG57AG-E PUHZ-P100-250 Drain pan PAC-SG64DP-E PUHZ-P100-250 Filter dryer
(([9.52)
PAC-SG82DR-E PUHZ-P100-250
[12.7)
PAC-SG85DR-E PUHZ-P250 Distribution pipe
(Twin)
MSDD-50SR-E PUHZ-P100-140
MSDD-50WR-E PUHZ-P200, 250
(Triple)
MSDT-111R-E PUHZ-P140-250
(Quadruple)
MSDF-1111R-E PUHZ-P200, 250 Joint pipe
(Unit Extension pipe)
([15.88 [19.05)
PAC-SG75RJ-E PUHZ-P100-140
81