Note1. Please choose the grille from a standard grille or Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3)
The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Water dew.)
8. As for necessary installation/service space, please refer to the left figure.
OUTLINES AND DIMENSIONS
INDOOR UNIT
PLA-RP50BAPLA-RP60BAPLA-RP71BA
PLA-RP100BAPLA-RP125BAPLA-RP140BA
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
INTAKE AIR TEMP. THERMISTOR
(0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
DRAIN SENSOR
DRAIN PUMP
TH5
TH2
TH1
TB5
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCKTB4
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
CN41
CN32
CN2L
I.B.
SYMBOL
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)
for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram
for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting
superimposed system of power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to w A.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
INTAKE AIR TEMP.THERMISTOR
(0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to w A.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
36
PEA-RP200, 250GA
OUTDOOR UNIT
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP200,250GA:15A
DSR
DSA
(3P)
(Hi)
C02
(6P)
(Lo)
C01
C01
5
4
TH5
TH2
TH1
INDOOR UNIT
POWER SUPPLY
3N~PE
380/400/415V
50Hz
BLACK
WHITE
RED
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
Hi
Lo
321
52F
123
MF1
TB6
LCD
REMOTE CONTROLLER
FB
TB4
S3
S2
S1
X6X5X4
375 1
FAN
ZNR
FUSE
4123
SW2
OFF
ON
5
TAB1
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
CNDK
CND
CN32
CN31
CN51
12345
31
31
3112
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
1
2
TB5
Hi
52F
Lo
52F
X1
X1
X1
49F
51F
X6X5X4
12345
SW1
OFF
ON
SWE
OFF
ON
SWITCH (MODEL SELECTION)
SWITCH (CAPACITY CODE)
CONNECTOR (EMERGENCY OPERATION)
SNB
BOARD 1
ZNR5~7VARISTOR
DSA,DSRARRESTER
INDOOR UNIT
NAMESYMBOL
COND./EVA. TEMP.
LIQUID PIPE TEMP.
ROOM TEMP.
52FHiMAGNETIC CONTACTOR (INDOOR FAN MOTOR<HIGH SPEED>)
SURGE KILLERCR1,2
SW1
TH5
LED (TRANSMISSION<INDOOR·OUTDOOR>)
LED3
LED (POWER SUPPLY<REMOTE CONTROLLER>)LED2
LED (POWER SUPPLY)LED1
SWE
SW2
X4-6AUXILIARY RELAY
VARISTORZNR
FUSE (T6.3AL250V)FUSE
THERMISTOR
TERMINAL BLOCK
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TH2
TH1
TB2,4,5
49F
51F
MF1
52FLoMAGNETIC CONTACTOR (INDOOR FAN MOTOR<LOW SPEED>)
AUXILIARY RELAYX1
FERRITE COREFB
BOARD
CONTROLLER
INDOOR
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
4. Indoor and outdoor connecting wires have polarities, make sure
to match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
TERMINAL BLOCKTB6
SYMBOL
REMOTE CONTROLLER
NAME
SNB BOARD 1
REMOTE
CONTROLLER
BOARD
POWER BOARD
INDOOR
INDOOR
CONTROLLER
BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
Caution,
1. To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
6. mark is connector. mark is terminal.
CR1CR2
ZNR5~7
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
37
PEA-RP400, 500GA
GREEN/YELLOW
INDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
TAB1
TAB1
FAN
CNDK
31
1573
X4 X5 X6
CN20
CN21
CN41
CN29
123
4
121
2
2
1
CN2D
CN90
CN22
CN2L
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
3112
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
3
1
CNSK
2
1
CN2S
DC
13.1V
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
FAN
CNDK
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
31
3112
DC13.1V
1573
X4 X5 X6
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
FB11
S1
1
2
REMOTE CONTROLLER
S2
S3
TB5
TB6
LCD
X1
FB21
S1S2S3
X2
TH1-1
TH2-1
TH5-1
TH5-2
TH2-2
TH1-2
TB4-2
TB4-1
FB12
FB22
X4 X5 X6
X4 X5 X6
51F
BLUE
POWER SUPPLY
3N~PE
380/400/415V
50Hz
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP400,500GA:15A
BLACK
WHITE
RED
DSR
DSA
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
C01C02
123
MF1
123
52F
C01
5
4
X01
X02
49F
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
34
12
21
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
SW2
34
12
21
SW2
AUXILIARY RELAYX4-6
MF1
51F
49F
TB2,4-1,4-2,5
TH1-1,1-2
TH2-1,2-2
FAN MOTOR (INDOOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
TERMINAL BLOCK
THERMISTOR
INDOOR UNIT
FUSEFUSE (T6.3AL250V)
ZNRVARISTOR
TH5-1,5-2
CRSURGE KILLER
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)52F
ROOM TEMP.
LIQUID PIPE TEMP.
COND./EVA. TEMP.
FERRITE COREFB11,FB12
FB21,FB22
INDOOR
CONTROLLER
BOARD
X1,2AUXILIARY RELAY
NAMESYMBOL
SNB
BOARD 1
ZNR5~7VARISTOR
DSA,DSR ARRESTER
SW2
SWE
LED1LED (POWER SUPPLY)
LED2LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED3LED (TRANSMISSION<INDOOR·OUTDOOR>)
SWITCH (MODEL SELECTION)SW1
SWITCH (CAPACITY CORD)
CONNECTOR (EMERGENCY OPERATION)
OUTDOOR UNIT
TERMINAL BLOCK
NAMESYMBOL
TB3,TB8
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
REMOTE CONTROLLER
TERMINAL BLOCK
NAMESYMBOL
TB6
4. Indoor and outdoor connecting wires have polarities, make sure to
match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
(No.2)
INDOOR
CONTROLLER
BOARD
(No.1)
REMOTE
CONTROLLER
BOARD
INDOOR
POWER
BOARD
(No.1)
(No.2)
INDOOR
CONTROLLER
BOARD
(No.2)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
SNB BOARD 1
(No.1)
INDOOR
POWER BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
6. mark is connector. mark is terminal.
Caution,
1.To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED <RUN INDICATOR>
LED <HOT ADJUST>
SWITCH (HEATING ON/ OFF>
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU
BZ
LED1
LED2
SW1
SW2
NAMESYMBOL
HEATER
H1
THERMAL FUSE <84:10A>
FS2
THERMAL FUSE <104:10A>
FS1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
SW1
Service board
SW2
Service board
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
MODELS
PKA-RP50GAL
PKH-P50GALH
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
PKH-P50GALH models only
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
39
PKA-RP50FAL2PKA-RP60FALPKA-RP71FALPKA-RP100FAL
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
PIPE
CN29
(
BLK
)
1 2
1 2
1 2
1 31 31 31 2
TH5TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON
OFF
SW2SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41CN2L
CN51CN32
WIRELESS
CN90
(
WHT
)
VANE
CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1
2
1
2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO
OUTDOOR
UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
40
PCA-RP50GAPCA-RP50GA2PCA-RP60GAPCA-RP71GA
X4X1
FAN
(
WHT
)
1 31 31 31 35
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK
(RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1
2
1
2
3
P.B
I.B
CNDK
(RED)
DC13.1V
CN2S
(WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER
CN2D(WHT)
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
SWE
ON
OFF
SW2SW1
Refer to tables 1
and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41CN2L
CN51CN32
VANE
CN6V
(
GRN
)
MV
66
9
MV
66
WIRELESS
CN90
(
WHT
)
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
D.SENSOR
CN31
(
WHT
)
CN31
DRAIN SENSOR
DS
PIPE
CN29
(
BLK
)
1 21 2 3
1 2 3
1 2
1 2
TH5TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2 SW1
100~140 TYPE
MV
55
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
YLW
GRN/YLW
ORN
ORN
BRN
TO OUTDOOR UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
W
1 (Fig.1)
(
WHT
)
I.B
HEATER
CN24
(YLW)
26H
RED
61
REDGRY
2
6
5
1
88H
YLW
YLW
TB2
POWER SUPPLY
~(1PHASE)
230V 50Hz
88H
FS2
H1
L
REDRED 53RED
BLU
GRN/YLW
WHT
N
2
1
FS1
PCH-P50~P140GAH
models only
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
[Servicing]
Fasten terminal of the terminal board "TB4" that equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
When installing drain-up
machine (Optional part)
W
When installing optional
drain-up machine, disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied,
refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this
diagram.
PCA-RP100GAPCA-RP125GAPCA-RP140GA
41
PCA-RP71HAPCA-RP125HA
SYMBOL
[ LEGEND ]
NAMESYMBOLNAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
MF1, MF2
C1, C2
H2
FAN MOTOR
CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROLL)
POWER SUPPLY (I. B)
POWER SUPPLY (R. B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY (DEW PREVENTION HEATER)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH (MODEL SELECTION)
See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SWITCH (EMERGENCY OPERATION)
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB4
POWER
SUPPLY
~(1PHASE)
230V 50Hz
RED
TB2
BLU
TO
OUTDOOR
UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
ORN
ORN
YLW
GRN/YLW
BRN
w1 (Fig.1)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
42
PSA-RP71GAPSA-RP100GAPSA-RP125GAPSA-RP140GA
1357
MF
ORN
C
RED
BLK
BLU
YLW
13131312
1
2
2
1
3
13
ML
YLW
YLW
BLK
ORN
YLW
YLW
ORNS1S2
S3
WHT
WHT
WHT
BRN
ORN
RED
I.B
FAN
(WHT)
LOUVER
CNL
(YLW)
X4X5X6
X6
X5 X4
X2
ZNR
FUSE
X2
LED3 LED2 LED1
SWE
ON
OFF
POWER
CNDK
(RED)
POWER
CND
(ORN)
POWER
CN2D
(WHT)
WIRELESS
CN90
(WHT)
2
1
REMOCON
CN22
(BLU)
CN32
CN2L
2
1
TB6
2
2
1
1
2
1
LIQUID
CN21
(WHT)
INTAKE
CN20
(RED)
PIPE
CN29
(BLK)
CN24CN41
CN51
R.B
TRANSMISSION
WIRES DC12V
BLU
BLU
TH1
TH2
TH5
SW1SW2
TB4
REDRED
WHT
RED
BLU
GRN/YLW
88H
FS1FS2
H
53
1
2
L
N
TB2
POWER SUPPLY
~(1 PHASE)
230V 50Hz
2
1
6
5
RED
RED
YLW
26H
88H
YLW
YLW
16
HEATER
CN24
(YLW)
I.B
PSH -P.GAH
models only
INDOOR UNIT
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers
(S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric
wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of
230V), adopting superimposed system of power and signal.
w1: When work to supply power separately to indoor and outdoor units was applied,
refer to Fig 1.
w2: For power supply system of this unit, refer to the caution label located near this diagram.
43
PUHZ-P100VHA2 PUHZ-P125VHA2 PUHZ-P140VHA2
123456
OFF
ON
100V
MODEL
SW5-6 w
3
w 1 MODEL SELECT
123456
OFF
ON
125V
123456
78
78
78
OFF
ON
140V
123456
OFF
ON
SW6
123456
OFF
ON
123456
OFF
ON
TB1
MC
MF1,MF2
21S4
63H
TH3
TH4
TH6
TH7
TH8
LEV-A
DCL
Terminal Block<Power Supply, Indoor/Outdoor >
Motor Compressor
Fan Motors
Refrigerant flow in cooling
Refrigerant flow in heating
Outdoor heat exchanger
Thermistor
(TH7)
Thermistor
(TH6)
Thermistor
(TH3)
Distributor
49
6
-5051015202530354046
16
18
20
22
0.6
0.8
1.0
1.2
1.4
Cooling capacity ratio
Outdoor intake air dry-bulb temperature <D.B. :>
-5051015202530354046
16
18
20
22
0.4
0.6
0.8
1.0
1.2
Cooling input ratio
Outdoor intake air dry-bulb temperature <D.B. :>
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-P·VHA2, PUHZ-P·YHA
Cooling capacity
Indoor intake air wet-bulb temperature <W.B. :>
Cooling input
Indoor intake air wet-bulb temperature <W.B. :>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
50
Heating capacity
Indoor intake air dry-bulb temperature <D.B. :>
Heating input
Outdoor intake air wet-bulb temperature <W.B. :>
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
51
7
Refrigerant piping length (one way)
75m70m60m55m50m40m30m
20m
10m5m
Outdoor unit
Cooling capacity correction factors
PUHZ-P100VHA2
PUHZ-P125VHA2
PUHZ-P140VHA2
PUHZ-P200YHA
PUHZ-P250YHA
Heating capacity correction factors
1.00
1.00
1.00
1.00
1.00
0.985
0.981
0.976
0.985
0.981
0.957
0.946
0.931
0.958
0.946
0.931
0.914
0.893
0.931
0.914
0.908
0.885
0.858
0.908
0.885
0.886
0.858
0.827
0.887
0.858
0.876
0.845
0.813
0.876
0.845
—
—
—
0.865
0.834
—
—
—
0.847
0.812
—
—
—
0.838
0.802
Refrigerant piping length (one way)
75m70m60m55m50m40m30m
20m
10m5m
Outdoor unit
PUHZ-P100VHA2
PUHZ-P125VHA2
PUHZ-P140VHA2
PUHZ-P200YHA
PUHZ-P250YHA
1.00
1.00
1.00
1.00
1.00
0.997
0.997
0.997
0.997
0.997
0.991
0.991
0.991
0.991
0.991
0.985
0.985
0.985
0.985
0.985
0.979
0.979
0.979
0.979
0.979
0.973
0.973
0.973
0.973
0.973
0.970
0.970
0.970
0.970
0.970
—
—
—
0.967
0.967
—
—
—
0.961
0.961
—
—
—
0.958
0.958
CORRECTION FACTORS
PUHZ-P·VHA2PUHZ-P·YHA
52
APPLICABLE EXTENSION PIPE FOR EACH MODEL8
<Table 1-1> Maximum pipe length (P100-140)
50m
[20m]
<Marks in the table>
The maximum pipe length
Charge-less pipe length
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when
the pipe length exceeds
10m(P100-140)/20m(P200, 250).
<Table 1-2> Maximum pipe length (P200, 250)
Note : Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
Liquid
pipe
(mm)
Gas
pipe
(mm)
OD
Thickness
OD
Thickness
P200
P250
[9.52
t0.8
[12.7
t0.8
[15.88
t1.0
[22.2
t1.0
50m
[30m]
50m
[30m]
[25.4
t1.0
Normal piping
70m
[30m]
70m
[30m]
[28.58
t1.0
70m
[30m]
70m
[30m]
[22.2
t1.0
50m
[20m]
50m
[30m]
[25.4
t1.0
50m
[20m]
Nomal piping
70m
[30m]
[22.2
t1.0
40m
[20m]
45m
[20m]
[25.4
t1.0
40m
[20m]
45m
[20m]
[28.58
t1.0
40m
[20m]
45m
[20m]
[28.58
t1.0
50m
[20m]
70m
[30m]
[31.75
t1.0
40m
[20m]
45m
[20m]
<Table 2-1> Maximum pipe length(P100-140)
<Table 2-2> Maximum pipe length(P200, 250)
<Table 3-2> Maximum pipe length(P200, 250)
<Table 3-1> Maximum pipe length(P140)
ø
9.52
ø15.88
Standard size
50m
[30m]
50m
[30m]
ø
9.52
ø19.05
50m
[30m]
50m
[30m]
ø
12.7
ø19.05
30m
[10m]
30m
[10m]
P140(RP50o3)
ø6.35
ø12.7
ø9.52
ø15.88
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
P100
P125,P140
Liquid
pipe
(mm)
OD
Thickness
OD
Thickness
Gas
pipe
(mm)
ø15.88
t1.0
Standard size
50m
[20m]
Standard size
50m
[30m]
ø19.05
t1.0
50m
[20m]
50m
[30m]
ø15.88
t1.0
25m
[10m]
30m
[10m]
ø19.05
t1.0
25m
[10m]
30m
[10m]
ø9.52
t0.8
ø9.52
ø15.88
Standard size
50m
[20m]
50m
[20m]
ø9.52
ø15.88
Standard size
50m
[30m]
ø9.52
ø19.05
50m
[20m]
50m
[20m]
ø9.52
ø19.05
50m
[30m]
ø12.7
ø19.05
25m
[10m]
25m
[10m]
ø12.7
ø19.05
30m
[10m]
P100(RP50o2)
P125(RP60o2)·P140(RP71o2)
ø6.35
ø12.7
ø9.52
ø15.88
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Branch
pipe
(mm)
[B, C]
Main pipe
(mm)
[A]
Branch
pipe
(mm)
[B, C, D]
Main pipe
(mm)
[A]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[20m]
[25.4
t1.0
50m
[20m]
[28.58
t1.0
50m
[20m]
[22.2
t1.0
40m
[20m]
[25.4
t1.0
40m
[20m]
[28.58
t1.0
40m
[20m]
[31.75
t1.1
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Main
pipe
(mm)
[A]
Branch
pipe
(mm)
[B,C]
Liquid
pipe
Gas
pipe
Liquid
pipe
Gas
pipe
[9.52
[15.88
[9.52O.D.
Thickness
O.D.
Thickness
t0.8t0.8t1.0t1.0t0.8t0.8
[12.7[15.88[9.52[12.7[15.88
P200(RP100x2)
P250(RP125x2)
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[20m]
[25.4
t1.0
50m
[20m]
[28.58
t1.0
50m
[20m]
[22.2
t1.0
40m
[20m]
[25.4
t1.0
40m
[20m]
[28.58
t1.0
40m
[20m]
[31.75
t1.1
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
Standard
size
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Main
pipe
(mm)
[A]
Branch
pipe
(mm)
[B,C]
Liquid
pipe
Gas
pipe
Liquid
pipe
Gas
pipe
[9.52
[15.88
[9.52
O.D.
Thickness
O.D.
Thickness
t0.8t0.8t1.0t1.0t0.8t0.8
[12.7[15.88[9.52[12.7[15.88
P200(RP60x3)
P250(RP71x3)
ø12.7
t0.8
ø12.7
t0.8
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM and 1:2(1 indoor / 2 outdoor) SYSTEM
8-1-2. TWIN TRIPLE AND QUADRUPLE SYSTEM
(1) TWIN SYSTEM
(2) TRIPLE SYSTEM
53
Outdoor
unit
Outdoor unit side Indoor unit side Outdoor unit side Indoor unit side
Total length
A+B+C+D+E
Branch
pipe
B, C, D
Gas side
Pipe size (mm)Actual piping length <m>
Indoor ~
Outdoor
Indoor ~
Indoor
(Note 1)
No. of
bend
Height deffence <m>
Liquid side
TWIN
TRIPLE
100-140
140
{15.88
<5/8>
RP50
{12.7<1/2>
RP60,71
{15.88<5/8>
{9.52<3/8>
RP50
{6.35<1/4>
RP60,71
{9.52<3/8>
50m
20m
Indoor ~
Indoor
|B-C|
8m
|B-C| |C-D| |B-D|
8m
H30mh 1m15
TWIN
TRIPLE
QUADRUPLE
200, 250
{25.4 <1>
RP60,71
100, 125
{15.88<5/8>
RP50
{
12.7
<1/2>
RP60
{15.88<5/8>
RP50
{
6.35
<1/4>
RP60
{
9.52<3/8>
{9.52<3/8>
(P200)
{12.7<1/2>
(P250)
RP60,71
100, 125
{9.52<3/8>
70m
30m
|B-C|
8m
|B-C| |C-D| |B-D|
8m
|B-C| |B-D| |B-E|
|C-D| |C-D| |C-E|
8m
(3) QUADRUPLE SYSTEM
<Table 2-2> Maximum pipe length(P200, 250)
Main
pipe
(mm)
[A]
Branch
pipe
(mm)
[B,C]
Liquid
pipe
Gas
pipe
Liquid
pipe
Gas
pipe
Liquid
pipe
Gas
pipe
Thickness
O.D.
Thickness
[6.35
[12.7
[9.52
[15.88
[9.52O.D.
t0.8t0.8t1.0t1.0t0.8t0.8
[22.2
[25.4
t1.0
Standard
size
70m
[30m]
70m
[30m]
[28.58
t1.0
70m
[30m]
70m
[30m]
t1.0
50m
[30m]
50m
[30m]
P200(RP50x4)
[12.7[15.88[9.52[12.7[15.88
[22.2
[25.4
t1.0
50m
[20m]
50m
[20m]
[28.58
t1.0
50m
[20m]
50m
[20m]
t1.0
50m
[20m]
50m
[20m]
[22.2
t1.0
40m
[20m]
40m
[20m]
[25.4
t1.0
40m
[20m]
40m
[20m]
[28.58
t1.0
40m
[20m]
40m
[20m]
[31.75
t1.1
40m
[20m]
40m
[20m]
[22.2
t1.0
50m
[30m]
[25.4
t1.0
70m
[30m]
[28.58
t1.0
70m
[30m]
[22.2
t1.0
50m
[30m]
P250(RP60x4)
[28.58
[25.4
t1.0
t1.0
Standard
size
70m
70m
[30m]
[30m]
[22.2
t1.0
45m
[20m]
[25.4
t1.0
45m
[20m]
[28.58
t1.0
45m
[20m]
[31.75
t1.1
45m
[20m]
Indoor unit
h
H
Distribution pipe
Indoor unit side
B
Indoor unit
C
Outdoor unit side
A
<TWIN SYSTEM>
Total length A + B + C
P100-140: 50 m
P200, 250: 70 m
h
H
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe
Indoor unit side
Indoor unit
h
B
Indoor unit
C
D
Indoor unit
H
Distribution pipe
Outdoor unit side
Outdoor unit
A
<TRIPLE SYSTEM>
Total length A + B + C + D
P140: 50 m
P200, 250: 70 m
Indoor unit
B
D
C
E
Indoor unit
Outdoor unit
A
<QUADRUPLE SYSTEM>
Total length A + B + C + D + E
P200, 250 : 70 m
(4) Pipe size and refrigerant pipe limits
54
Note1. The number of bends in the refrigerant pipe is respectively 8 or less in the range of <A+B> <A+C> <A+D>.
2. PUHZ-P100: 20 m chargelessPUHZ-P125-250: 30 m chargeless
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
3.0kg
4.5kg
4.5kg
5.8kg
7.1kg
21 — 30m
0.6kg
31 — 40m
1.2kg
0.6kg
0.6kg
0.9kg
1.2kg
41 — 50m
1.8kg
1.2kg
1.2kg
1.8kg
2.4kg
51 — 60m
2.7kg
3.6kg
61 — 70m
3.6kg
4.8kg
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
If the calculation produces a negative number ( W [ 0), additional charging is not necessary.
• Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter.
55
8-3. CAPACITY CURVE
PUHZ-P100, 125, 140 VHA2<Standard size>
100
95
90
P100-140
Cooling
Heating
Capacity ratio [%]
85
80
5 10152025303540455055
Corrected pipe length [m]
PUHZ-P200, 250YHA<Standard size>
100
95
90
85
80
Capacity ratio [%]
75
P100
P125
P140
P200, 250
Cooling
Heating
P200
P250
70
5 10152025303540455055606570
Corrected pipe length [m]
PUHZ-P200, 250YHA<Gas pipe’s diameter is one size smaller than the standard size.>
100
P200, 250([22.2)
95
Cooling
90
85
80
Heating
P200([22.2)
Capacity ratio [%]
75
70
5 10152025303540455055
P250([22.2)
Corrected pipe length [m]
56
9
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
PCA-RP50GA
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA PCA-RP100GA
PCA-RP125GA PCA-RP140GA
25
4.1
12.6
34
4.4
15.2
34
4.4
15.2
18
3.8
10.4
18
3.8
10.4
13
3.7
8.8
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
19
2.9
7.9
38
4.2
13.2
PCA-RP71HAPCA-RP125HA
12
5.3
10(32.8)
PKA-RP50GAL
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m(ft)
20
4.9
12.4(40.7)
PKA-RP71FAL
20
4.9
12.4(40.7)
PKA-RP50FAL2
PKA-RP60FAL
28
5.4
15.3(50.2)
PKA-RP100FAL
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m(ft)
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
PSA-RP71GAPSA-RP100GAPSA-RP125GAPSA-RP140GA
18
2.6
8.3
31
4.5
14.3
33
4.8
15.2
35
4.9
16.1
PLA-RP71BA
PLA-RP100BAPLA-RP125BAPLA-RP140BA
30
5.3
8.0
32
5.6
8.5
31
5.4
8.2
Airflow
Air speed
Coverage range
m
3
/min.
m/sec.
m
21
3.7
5.6
18
3.2
4.8
18
3.2
4.8
PLA-RP50BAPLA-RP60BA
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
57
9-2. PLA-RP·BA
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Branch duct hole
A
A
A
14-[2.8 burring hole
Indoor unit
[150 cut out hole
Fresh air intake hole
[175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-[2.8 burring hole
Unit : mm
Branch duct
hole diagram
(view from
either side)
[125 burring
hole pitch
[100 cut
out hole
Ceiling
*158
120
120
350
90
70°
100 100 90
100
130
*155
*167
Fig. 1
9-2-1 FRESH AIR INTAKE AND BRANCH DUCT
58
3. Fresh air intake volume & static pressure characteristics
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 Direct intake to unit
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
2 Direct intake to unit
Static pressure[Pa]
Static pressure[Pa]
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
2 - inlet
1 - inlet
1 At using multi-function casement, standard filter
-200
-150
-100
-50
0
50
02468
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
Airflow rate [m3/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
1 At using multi-function casement, standard filter
PLA-RP50~71BA
PLA-RP100~140BA
Static pressure[Pa]
59
4. Change of outlet numbers
<4- way air flow and branch duct>
w Branch duct should be connected to one of the branch duct holes on the main unit.
Branch
duct
Air intake
Air
outlet
<3- way air flow and branch duct>
w Close the outlet on the side of branch duct and air flows in 3 directions.
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
Airoutletclosedposition
<2- way air flow and branch duct>
w Close the outlet on the side of branch duct and one of the other outlets.
Air flows in 2 directions.
Air intake
Branch
duct
Air
outlet
closed
position
Air
outlet
closed
position
[The optional air outlet is necessary.]
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
(When the air outlets are closed, close the vane by
removing the vane connector.)
Wired remote controllerPAR-21MAAT-EPKA-RP·GAL
(with terminal bed)PKA-RP·FAL(2)
Drain lift up mechanismPAC-SE90DM-EPKA-RP·FAL(2)
PAC-SK003MT-FPEAD-RP125,140EA
(for high external static pressure)PEAD-RP100EA2
Drain lift up mechanismPAC-KE03DM-FPEAD-RP·EA,EA2
Insulation kitPAC-SK010DKPEAD-RP·GA
Multi-function casement
PAC-SH53TM-E
PAC-SH65OF-E
High-efficiency filter element
Flange for fresh air intake
PAC-SH59KF-E
(PAC-SH53TM-E is needed.)
Decoration panel with Wireless remote controller
PLP-6BALM
PLA-RP·BA
Decoration panel with Wired remote controller
PLP-6BAMD
Automatic filter elevation panel
PLP-6BAJ
i-see sensor corner panel
PAC-SA1ME-E
Wireless signal receiver
PAR-SA9FA-E
Space panel
PAC-SH48AS-E
Air outlet shutter plate
PAC-SH51SP-E
Decoration panel
PLP-6BA
OPTIONAL PARTS
80
11-2. OUTDOOR UNIT
Part NameModel Name
Applicable model
M-NET adapterPAC-SF80MA-EPUHZ-P100-250
A-control service toolPAC-SK52ST
Drain socketPAC-SG61DS-EPUHZ-P100-250
Air outlet guide (P125-250 need 2 pieces.)PAC-SG59SG-EPUHZ-P100-250
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Sep. 2007 No.OCS08 REVISED EDITION-A PDF 7