Mitsubishi OCS06 TECHNICAL MANUAL

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
January 2006
No. OCS06
TECHNICAL DATA BOOK
<Indoor unit> [Model names]
<Outdoor unit> [Model names]
PLA-RP·AA PLA-RP·AA2 PEAD-RP·EA PEAD-RP·EA2 PEAD-RP·GA PKA-RP·GAL PKA-RP·FAL PCA-RP·GA PCA-RP·HA PSA-RP·GA
PUHZ-P100/125/140VHA
R410A
INVERTER
kW Model
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································10
4. WIRING DIAGRAM···································································28
5. REFRIGERANT SYSTEM DIAGRAM ······································38
6. PERFORMANCE CURVES······················································40
7. CORRECTION FACTORS························································42
9. AIR FLOW DATA······································································46
10. NOISE CRITERION CURVES ··················································58
11. OPTIONAL PARTS·····································································68
For information on service, please refer to the service manual as follows.
Model name Service Ref. Service
Manual No.
PLA-RP50/60/71AA
PLA-RP50/60/71AA.UK OC335
OC327
PLA-RP100/125/140AA2
PLA-RP50/60/71AA PLA-RP100/125/140AA2.UK OC357
PCA-RP50/60/71GA PCA-RP50/60/71GA OC328 PCA-RP100/125/140GA
PCA-RP100/125/140GA
PCA-RP71/125HA PCA-RP71/125HA OC329 PKA-RP50GAL PKA-RP50GAL OC330 PKA-RP60/71/100FAL PKA-RP60/71/100FAL OC331 PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA OC332 PEAD-RP50/60/71/125/140EA PEAD-RP50/60/71/125/140EA.UK
HWE05210
PEAD-RP100EA2
PEAD-RP100EA2.UK
PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK
HWE05060
1-2. OUTDOOR UNIT
Model name Service Ref. Service
Manual No.
OC359PUHZ-P100/125/140VHA
PUHZ-P100/125/140VHA.UK
1-1. INDOOR UNIT
1
REFERENCE SERVICE MANUAL
2
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46:
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5: w
Heating
Upper limit
D.B. 28˚C
D.B. 21:, W.B. 15:
Lower limit
D.B. 17˚C
D.B. -11:, W.B. -12:
4. Above data based on indicated voltage
w If optional Air protect guide installed. D.B.-15:
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz
Model name Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Outdoor unit PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0
)
13.6(5.5-15.0
) Total input kW 3.12 4.09 5.21 EER 3.01 3.01 2.61 Energy label class B B D SHF 0.80 0.75 0.72
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0
)
16.0(5.0-18.0
) Total input kW 3.28 4.11 4.98 COP 3.41 3.41 3.21 Energy label class B B C Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 19-21-23-27 24-25-27-30
(
Low-Medium2-Medium1-High
)
CFM 670-740-810-950 850-880-950-1060 External pressure Pa 0 0 Sound level dB(A
)
33-36-39-41 37-40-43-45
(
Low-Medium2-Medium1-High
)
External finish (Panel
)
White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950
)
Unit (Panel
)
D : mm 840 (950
)
H : mm 298 (30
)
W : inch 33-1/16 (37-3/8
)
D : inch 33-1/16 (37-3/8
)
H : inch 11-3/4 (1-3/16
)
Weight kg 32 (5
)
Unit (Panel
)
lbs 71 (11
)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling
dB(A
)
50 51 52
Sound level at heating
dB(A
)
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 123
lbs 165 271
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
3
2-2. CEILING-CONCEALED TYPE
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.12 4.38 5.21 EER 3.01 2.81 2.61 Energy label class B C D SHF 0.86 0.83 0.84
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.28 4.11 4.98 COP 3.41 3.41 3.21 Energy label class B B C Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 33.5-42 33.5-42 36.5-46
(
Low-High
)
CFM 1183-1483 1183-1483 1288-1624 External pressure Pa 70(130 Sound level dB(A (
Low-High
)(
)
44-50 44-50 46-51
130Pa : 46-52
)(
130Pa : 46-52 External finish Galvanized sheets Dimension W : mm 1415 1715
D : mm 740 H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8 H : inch 12-13/16
Weight kg 65 65 70
lbs 143 143 154
Unit drain pipe R1(External thread
)
)
)
13.6(5.5-15.0
16.0(5.0-18.0
)(
130Pa : 47-53
)
)
)
)
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling Sound level at heating
dB(A dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 123
lbs 165 271
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional Air protect guide installed. D.B.-15:
Single phase 230V 50Hz
4
Model name Indoor unit PEAD-RP100GA
Outdoor unit PUHZ-P100VHA
Cooling Capacity Btu/h 32,100
kW 9.4(4.9-11.2 Total input kW 3.60 EER 2.61 Energy label class D SHF 0.85
Heating Capacity Btu/h 38,200
kW 11.2(4.5-12.5 Total input kW 3.49 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32
Indoor unit Air flow CMM 26.5-33
(
Low-High
)
CFM 935-1165 External pressure Pa 10/50/70 Sound level dB(A (
Low-High
)(
)
40-43/42-45/42-46
10/50/70Pa External finish Galvanized sheets Dimension W : mm 1411
D : mm 740 H : mm 275
W : inch 55-9/16
D : inch 29-1/8 H : inch 10-13/16
Weight kg 50
lbs 111
Unit drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 60
CFM 2,120 Sound level at cooling Sound level at heating
dB(A dB(A
) )
50
54 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8
Weight kg 75
lbs 165
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional Air protect guide installed. D.B.-15:
)
)
)
Single phase 230V 50Hz
5
2-3. WALL-MOUNTED TYPE
Model name Indoor unit PKA-RP100FAL
Outdoor unit PUHZ-P100VHA
Cooling Capacity Btu/h 32,100
kW 9.4(4.9-11.2 Total input kW 3.12 EER 3.01 Energy label class B SHF 0.79
Heating Capacity Btu/h 38,200
kW 11.2(4.5-12.5 Total input kW 3.49 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32
Indoor unit Air flow CMM 22-28
(
Low-High External pressure Pa 0 Sound level dB(A (
Low-High External finish Dimension W : mm 1680
Weight kg 28
Unit drain pipe O.D. mm 20
Outdoor unit Air flow CMM 60
Sound level at cooling Sound level at heating External finish Dimension W : mm 950
Weight kg 75
Refrigerant pipe size
Gas side O.D. mm 15.88
Liquid side O.D. mm 9.52
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
)
CFM 780-990
)
41-46
)
Munsell 3.4Y 7.7/0.8
D : mm 235 H : mm 340
W : inch 66-1/8
D : inch 9-1/4 H : inch 13-3/8
lbs 62
inch 13/16
CFM 2,120
)
dB(A dB(A
)
50 54
Ivory Munsell 5Y 7/1
D : mm 330+30 H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8
lbs 165
inch 5/8
inch 3/8
)
)
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional Air protect guide installed. D.B.-15:
Single phase 230V 50Hz
6
2-4. CEILING-SUSPENDED TYPE
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.35 4.38 5.21 EER 2.81 2.81 2.61 Energy label class C C D SHF 0.77 0.78 0.76
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.49 4.98 4.98 COP 3.21 2.81 3.21 Energy label class C D C Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(
Low-Medium2-Medium1-High
)
CFM 705-840-810-885 955-1060-1130-1200 External pressure Pa 0 0 Sound level dB(A
(
Low-Medium2-Medium1-High
)
)
40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1310 1620
D : mm 680 H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4 H : inch 10-5/8
Weight kg 37 43 45
lbs 82 95 99
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling Sound level at heating
dB(A dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 123
lbs 165 271
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
)
)
13.6(5.5-15.0
16.0(5.0-18.0
)
)
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
7
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional Air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PCA-RP125HA
Outdoor unit PUHZ-P125VHA
Cooling Capacity Btu/h 42,000
kW 12.3(5.5-14.0 Total input kW 4.38 EER 2.81 Energy label class C SHF 0.78
Heating Capacity Btu/h 47,100
kW 13.8(5.0-16.0 Total input kW 4.30 COP 3.21 Energy label class C Booster heater kW -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 25
Indoor unit Air flow CMM 30-38
(
Low-High
)
CFM 1060-1350 External pressure Pa 0 Sound level dB(A (
Low-High
)
)
44-50
External finish Stainless steel Dimension W : mm 1520
D : mm 650 H : mm 280
W : inch 59-7/8
D : inch 25-5/8 H : inch 11
Weight kg 56
lbs 124
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530 Sound level at cooling Sound level at heating External finish
dB(A dB(A
) )
51 55
Ivory Munsell 5Y 7/1
Dimension W : mm 950
D : mm 330+30 H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 53-1/8
Weight kg 123
lbs 271
Refrigerant pipe size
Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
)
)
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional Air protect guide installed. D.B.-15:
Single phase 230V 50Hz
8
2-5. FLOOR STANDING TYPE
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Cooling Capacity Btu/h 32,100 42,000 46,400
kW 9.4(4.9-11.2
)
12.3(5.5-14.0 Total input kW 3.12 4.38 5.64 EER 3.01 2.81 2.41 Energy label class B C E SHF 0.83 0.76 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-12.5
)
14.0(5.0-16.0 Total input kW 3.28 4.98 5.69 COP 3.41 2.81 2.81 Energy label class B D D Booster heater kW - - -
Power supply Phase { 1
Cycle Hz 50 Voltage V 230 Breaker size A 32 40
Indoor unit Air flow CMM 24-31 26-33 27-35
(
Low-High
)
CFM 850-1060 920-1165 955-1240 External pressure Pa 0 Sound level dB(A (
Low-High
)
)
44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 600
D : mm 350 H : mm 1900
W : inch 23-5/8
D : inch 13-3/4 H : inch 74-13/16
Weight kg 51 53
lbs 112 117
Unit drain pipeO.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 60 100
CFM 2,120 3,530 Sound level at cooling Sound level at heating
dB(A dB(A
) )
50 51 52
54 55 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 950
D : mm 330+30 H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16 H : inch 37-1/8 53-1/8
Weight kg 75 123
lbs 165 271
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
Height difference m Max. 30 Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -11:, W.B. -12:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional Air protect guide installed. D.B.-15:
Single phase 230V 50Hz
)
)
13.6(5.5-15.0
16.0(5.0-18.0
)
)
9
3
PLA-RP60,71AA
PLA-RP50AA
Models
PLA-RP100,125,140AA2
241
281
A
258
298
B
80
84
C
Receiver
Operation lamp
DEFROST/STAND BY lamp
Emergency operation switch (cooling)
A
(WIRELESS PANEL)
Emergency operation switch (heating)
Branch duct hole (Cut out hole)
{175
{150
14 - {2.8 Burring hole
350
90
70_
100 100 90
100
130
155
167
Suspension bolt pitch
Ceiling hole
Branch duct hole
Suspension bolt pitch
Ceiling hole
840
197 159
159
605
159192
98
89
C
840
860 - 91020 - 45 20 - 45
20 - 4520 - 45
Fresh air intake
Branch duct hole
860 - 910
810
159
16
Terminal block
Drain pipe VP-25connection (O.D.{32)
Ceiling surface
Power line entry
Suspension bolt lower edge
Suspension bolt M10 or W3/8
Control wire entry
Feeding hole (Drain pump)
37428660
17
+5
0
30
190
170
140
50 - 70
105
A
B
1
2
High efficiency filter & Fresh air intake casement (option)
17
+5
0
135
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Air outlet hole
Air intake hole
411
Air intake hole
Air intake grille
577
77 51
M
M
M
A
M
950
51 77
950
577
411
RP50
Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size
Factory flare nut attachment to the heat-exchanger.
1 LIQUID SIDE
2 GAS SIDE
RP60 RP71
[6.35 [6.35 [9.52 [9.52 [9.52 [9.52
[12.7
[15.88 [15.88 [15.88 [15.88
———[19.05
RP100, 125, 140
Detail drawing of fresh air intake
3 - {2.8 Burring hole
{125 Burring hole pitch
{100 (Cut out hole)
Ceiling surface
120_
120_
158
OUTLINES AND DIMENSIONS
INDOOR UNIT
PLA-RP50AA PLA-RP60AA PLA-RP71AA PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Unit : mm
10
PEAD-RP50EA
2
1
3 4 5 6 7
Refrigerant piping flare connection (liquid [ F copper tube):HP Refrigerant piping flare connection (gas [G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP-25(I.D.
[
32)
Filter
R407C Outdoor unit : 9.52
F
R410A Outdoor unit : 6.35 w
R407C Outdoor unit : 9.52 w
Outdoor unit (SUZ) : 6.35
EDCBA
804830
-
305772
Model
RP60
R407C Outdoor unit : 15.88
G
R410A Outdoor unit : 12.7 w
15.88
104410702902801012
RP50
w Setting at shipment
2
1
3
4
Air inlet
Air outlet
Access door
55
50~150
81
197
Service space:500 or more
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
5
6
75
44
18
365~465
B 81
10
56 355
7
159
243
Air outlet
Air inlet
7
Lifting bolt hole
(14×22)
10- [3 (RP35,50) 12-
[
3 (RP60)
In case of rear inlet
In case of bottom inlet
10- [3 (RP35,50) 12-
[
3 (RP60)
D
30
C
10
81BC
A
450
450
10- [3 (RP35,50) 12-
[
3 (RP60)
176
40
288
256
3.5
3.5
10
109
179
10
35
24
30640
30
21
277
80 45
282
13
13E
A
61 227
29
85
40
176
10
15
3.5 256
BC 81
10
81
A
Set
R407C outdoor unit : 19.05158416104704601552RP140
15.8810441070290
F
R410A Outdoor unit : 15.88 w
EDCBA
12841310370360
2801012
1252
Model
RP100,125
RP71
w
Setting at shipment
7
44
243
308
323
75
6
5
13
Refrigerant piping flare connection (liquid [9.52 copper tube):HP Refrigerant piping flare connection (gas [F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP25(I.D.[32) Filter
Service space:500 or more
81
365~465
197
81
50~150
55
29
Access door
Air outlet
Air inlet
4
3
1
2
7
6
5
4
3
2
1
113
307
122
12-[3
(14x22)
Lifting bolt hole
45
Set
210
12-[3
450
450
140
282
680
3.5
3.5
30
319
261
181
40
30
A C B
81
10
375
10
80
C B 81 A E 13
30D
20
35
30
1053 169
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
PEAD-RP60EA
Unit : mm
PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
11
PEAD-RP60GA
Model
ABCDE
7 7 9
8
9.52
9.52
15.88
15.88
8
10
FG H J
RP60
RP71
RP100
1125 1125
1365
1090 1090
1330
1050 1050
1290
1012 1012
1252
840 840
1080
Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 w
R410A Outdoor unit : 15.88 w R407C Outdoor unit : 19.05
w Setting at shipment
PEAD-RP71GA PEAD-RP100GA
Unit : mm
12
PKA-RP50GAL
BYOFF
ON STAND
HEATCOOL
OFF BY
ON STAND
COOL HEAT
ÅrÇoÇoÅqÅ@ëOñ Å@ÇeÇqÇnÇmÇs ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs
r.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
r.S
L
I
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
Knock out hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake
198
53
340
715 225
340 80 280 233
990
21
Left side
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
60
70
245
(Necessary clearance for
Unit installation)
Right side
Allowing clearances
Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear
piping hole
left-rear piping
R52.5
R52.5
Installation plate
balance point hole
Details of installation plate
49-[5hole
for tapping screw
Knock out hole for
right-rear piping
Right-rear
piping hole
Unit center
14-[14hole
Knock out hole for
425
420
170
190
210 230
0
322
0355580130
190
230
272
310
0
35
95
150
205
260
320
345
495
20 75 135 190 245 300 360
405
495
32
0
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
[90~[100[90
Through hole
Sleeve w1
50
Model
R52.5
R52.5
Gas pipe
Liquid pipe
Terminal block for
Terminal block to
outdoor unit
Filter grip
Service panel
(Power supply access)
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Unit drain pipe O.D.20
Front view(to open the grille)
700
449
86
581 54
31 280
35
Knock out hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395400
190
60
70 35
79
160 40
235
705
power supply (Heater (PKH-P50GALH only))
153
GAS SIDE
LIQUID SIDE
RP50
P50
[6.35
[9.52
[12.7
[15.88
[9.52—[15.88
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
: Factory flare nut attachment to the heat - exchanger.
Unit : mm
13
PKA-RP60FAL
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knock out hole for right piping Refrigerant pipe. Drain pipe
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Lower side Auto vanes
(Gas pipe)
Drain hose O.D.20
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe [9.52(3/8F) Gas pipe [15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for wiring
25
1110
183
240
B
1120
552
55 120
107 111
Air outlet
552
Air outlet
Louvers (manual)
Under panel Removable at left-hand
side piping
Knock out hole for under-piping Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for tapping screw
66-ø6 hole for tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240 280 314
610
90
Drainage range on left-hand side
Drainage range on right-hand side
10 91=(910)
180
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
PKA-RP71FAL
Unit : mm
14
PKA-RP100FAL
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Left side
1680
1370
Air intake
235
C
Knock out hole for right piping
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for wiring
25
1110
183
240
B
1400
55 120
102 111
694
Air outlet
694
Air outlet
Louvers (manual)
Under panel
(Removable at left-hand side piping)
Knock out hole for under-piping Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range on right-hand side
13 91=(1183)
180
Drainage range on left-hand side
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Drain hose O.D.20
: Factory flare nut attachment to the heat-exchanger.
GAS SIDE
LIQUID SIDE
RP100
[9.52 [15.88 [19.05
P100
[9.52
[19.05
Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size
Unit : mm
15
PCA-RP50GA
180
210
157
15
85
182 liquid 201 gas 241 (Drainage)
Air intake
918
161 90
254
680
506 56
Electrical box
226
70
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
525
928
352
263
171
138
86
46 175 1
131
38
38
79
161
32
179
42
6~7
Ceiling
Electrical box
[Front view]
When electrical box is pulled down
3
2
8
5
1
4
[15.88
[9.52
P50
[15.88
[12.7
[6.35
Available pipe size
[9.52
4 GAS SIDE
5 LIQUID SIDE
RP50
Use the current nuts meeting the pipe size of the outdoor unit.
: Factory flare nut attachment to the heat-exchanger.
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knock out hole for upper drain pipe arrangement 7 Knock out hole for left drain pipe arrangement 8 Knock out hole for wiring arrangement
16
PCA-RP60GA
161 90
254
680
506 56
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
Air intake
85
182 201 241
15
157
(liquid) (5/8F gas) (Drainage)
7
2
Electrical box
70
226
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1 46
: Factory flare nut attachment to the heat-exchanger.
4 GAS SIDE
5 LIQUID SIDE
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP71,P60,P71
RP60
[6.35 [9.52
[15.88
[9.52
[15.88
PCA-RP71GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knock out hole for upper drain pipe arrangement 7 Knock out hole for left drain pipe arrangement 8 Knock out hole for wiring arrangement
17
PCA-RP100GA
161 90
254
680
506 56
1228
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
18
70
6
87
182
198
245
16
217
(3/8F liquid) (5/8F, 3/4F gas) (Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
Use the current nuts meeting the pipe size of the outdoor unit.
:Factory flare nut attachment to the heat-exchanger.
4 GAS SIDE
5
LIQUID SIDE
Available pipe size
RP100
[9.52
[15.88 [19.05
P100
[9.52
[19.05
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knock out hole for upper drain pipe arrangement 7 Knock out hole for left drain pipe arrangement 8 Knock out hole for wiring arrangement
18
PCA-RP125GA
161 90
254
680
506 56
1535
Air intake
1524
270
207
81 96
1620
Air outlet
1547(suspension bolt pitch)
140
150
320 80
18
70
6
87
182 198 245
16
217
(3/8F liquid) (5/8F, 3/4F gas) (Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1545
687
263
171
138
86
192
236
1
45
:Factory flare nut attachment to the heat-exchanger.
RP125,140
[19.05
[15.88
[9.52
Use the current nuts meeting the pipe size of the outdoor unit.
4 GAS SIDE
5 LIQUID SIDE
Available pipe size
P125,140
[19.05
[9.52
PCA-RP140GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
Unit : mm
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knock out hole for upper drain pipe arrangement 7 Knock out hole for left drain pipe arrangement 8 Knock out hole for wiring arrangement
19
PCA-RP71HA
Unit : mm
(Gap to ceiling)
90˚
130
9
[222
[200
Terminal block box
78
(122)
480
Allowing clearances
6
4
85
14018
45
1
210
2
165
120
90
366
38
318
176
105
650
Less than
Rear wall
Adjustable part
2 ~ 3
300
Ceiling
Less than
Less than
250
500
1001136
or more
or more
295
254
70~90
43
320 80
495
<Suspension bolt pitch>
243
75
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
Terminal block(remote controller)
Terminal block(indoor/outdoor connecting line)
Knock out hole for upper refrigerant-pipe arrangement
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
1
Knock out hole for behind refrigerant-piping arrangement
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
2
3
130 15
5
2
5
4
<gas> <liquid>
175
110
21
Knock out hole for wiring arrangement : 2- [ 27
6
197
Knock out hole (duct for fresh air intake): 2- [ 200
8
7
9
75
Suspension bolt
280
<Air outlet>
1
3
13
70
289
650
Inspection port
75
<Air outlet>
1224
<Suspension bolt pitch>
1180
986
1136
handle
<Flexible hose(accessory)>
16
288
<Filter contour dimension>
(pipe sensor)
Filter (3-pieces)
258 110 102
or more
100
360
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
<Air intake>
1098
<Air intake>
Terminal block box
Electrical box
20
The half bottom of FAN CASING
can be separated.
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
PCA-RP125HA
(Gap to ceiling)
90˚
[222
[200
9
130
440440298
2~3
250
Less than
or more
500
Unit : mm
78
Terminal block box
(122)246
6
90 120
295
254
243
280
<Air outlet>
110 102
38 210
176
105
Adjustable part
3
13
70
289
650
<Flexible hose(accessory)>
Inspection port
(pipe sensor)
Filter (4-pieces)
4
2
8545
14018
165
1
70~90
43
320 801564
495
<Suspension bolt pitch>
75
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F, 3/4F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Knock out hole for behind refrigerant-piping arrangement
Knock out hole for upper refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
4
3156728
<gas>
197
175
<liquid>
110
21
Knock out hole (duct for fresh air intake) : 2- [ 200
Terminal block(indoor/outdoor connecting line)
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
Terminal block(remote controller)
9
1
75
Suspension bolt
Allowing clearances
650
Rear wall
Less than
300
Ceiling
handle
360
16
288
<Filter contour dimension>
258
<Air intake>
Filter element for the exchange
Less than
1001520100
or more
or more
: Factory flare nut attachment to the heat-exchanger
[ 9.52
RP125
[ 15.88
model:PAC-SG38KF-E (12pcs.)
[ 19.05
130 15
5
2
Terminal block box
Electrical box
<Suspension bolt pitch>
1608
<Air outlet>
1370 75
1520
The half bottom of FAN CASING
can be separated.
21
1482
<Air intake>
2 LIQUID SIDE
Available pipe size
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
1 GAS SIDE
Use the current nuts meeting the pipe size
of the outdoor unit.
PSA-RP71GA
300 or more 1
5 or more 2
Unit : mm
Front 1,000 or more
Knock out hole
for under-piping
Front side
218
VIEW "A"
95
100
90
175
55 143
Rear side
20
160
Knock out hole
for bottom fixing
277
100 or more 100 or more
40 66
Liquid pipe [9.52(3/8F)
95
Electrical parts box
46122
Terminal block for
indoor/outdoor
connection.
1. Service access allows for
insertion of screw driver.
2. Adjustable
186
Drain pipe
Gas pipe [15.88(5/8F)
47
767 714 123
590
480
110
105
Knock out hole for piping and wiring
(140 80 oval)
20
A
132
Knock out hole
for branch duct
240
Rear side
10 3838
15
111
Knock out hole for
under-piping(120 70 oval)
130 100
125
340
370
Front side
10
270
250
40 50260
Metal fixture
against overturning
520
260
240
2010
130130
controller
766
130 71
Terminal block for
heater power supply
(Only PSH-P•GAH)
1900
50
608
82730
216
115
Knock out hole for
wiring.[27
(Provided on both sides)
180
235
70
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
530
600
22
PSA-RP100GA PSA-RP125GA PSA-RP140GA
300 or more 1
5 or more 2
Unit : mm
Front 1,000 or more
Knock out hole
for under-piping
Front side
218
VIEW "A"
95
Knock out hole for
under-piping(120 70 oval)
[ 9.52
P100,125,140—[ 19.05
[ 9.52
RP100,125,140
[ 15.88
[ 19.05
: Factry flare nut attachment to
LIQUID SIDE
Use the current nuts meeting the pipe size
of the outdoor unit.
Available pipe size
77
201
120
Rear side
20
140
Knock out hole
255
GAS SIDE
120
277
for bottom fixing
the heat-exchanger
Terminal block for
indoor/outdoor
100 or more 100 or more
40 66
Liquid pipe [9.52(3/8F)
95
Electrical parts box
46122
connection.
Terminal block for
heater power supply
(Only PSH-P•GAH)
1. Service access allows for
insertion of screw driver.
2. Adjustable
261
[19.05(3/4F)
Drain pipe
Gas pipe [15.88(5/8F)
47
767 714 123
590
480
110
105
Knock out hole for piping and wiring
(140 80 oval)
20
115
50
Knock out hole for
wiring.[27 (Provided on both sides)
A
132
Knock out hole
for branch duct
240
Rear side
10 3838
15
111
260
350
330
40
130 100
125
340
370
Front side
10
50260
Metal fixture
against overturning
520
260
240
2010
130130
controller
766
130 71
1900
608
82730
216
315
70
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
530
600
23
417
66 42
45
56
(19)37028
53
175600175
330
2-12o36 oval holes
(Foundation Bolt M10)
Air Discharge
Rear Air Intake
Side Air Intake
2-U Shaped notched holes
(Foundfation Bolt M10)
Installation Feet
,,
,,,,
,,,,,,
,,,,,,
,,
,,,
30
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Piping Knock-Out Hole Details
Example of Notes
···Refrigerant GAS pipe connction (FLARE){15.88(5/8F)
···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8F) w1 ···Indication of STOP VALVE connection location.
1
2
Over 10mm
Over 500mm
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
Over 10mm
Over 100mm
FREE
Over10
500
500
Over100
Dimensions of space needed
for service access are
shown in the below diagram.
Service space
30
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Handle for moving
Side Air Intake
Front piping cover
Rear piping cover
14522030 145
81 219
145
71
71
Drain hole
(5-{33)
Bottom piping hole
(Knock-Out)
Air Intake
Rear Air Intake
Handle for moving
Handle for moving
23
943
473
950
322
w 1 447 w 1 443
670
Terminal Connections
Left···Power supply wiring
Reight···Indoor/Outdoor wiring
Earth terminal
Service panel
Handle for moving
Handle for moving
1
2
19 55
23 27 92
92
4075
73 63
Right piping hole
(Knock-Out)
Right trunking hole
(Knock-Out)
Power supply wiring hole
(2-{27Knock-Out)
{
92
27 55
7323 63
40
92
65
45
Front piping hole
(Knock-Out)
Front trunking hole
(Knock-Out)
Power supply wiring hole
(2-{27Knock-Out)
{
92
4045
65
92
27 55 23 73 63
Rear piping hole
(Knock-Out)
Rear trunking hole
(Knock-Out)
Power supply wiring hole
(2-{27Knock-Out)
{
92
FOUNDATION
OUTDOOR UNIT PUHZ-P100VHA
Unit : mm
24
PUHZ-P125VHA PUHZ-P140VHA
Unit : mm
(19)28 370
2-U Shaped notched holes
(Foundation Bolt M10)
600175 175
Rear Air Intake
Installation Feet
417
45
330
Side Air Intake
53 56
42 66
2-12 x 36 Oval holes
(Foundation Bolt M10)
Air Discharge
30
Terminal connection
Left···Power supply wiring
950
Earth terminal
322
Handle for moving
Right···Indoor/Outdoor wiring
Service panel
1076
Handle for moving
1350
Front piping cover
w 1 447 w 1 443
2
1
371 635
Rear piping cover
71
23
Bottom piping hole
(Knock-Out)
71
Drain hole
(5-{33)
14514522030 145
81 219
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
4 PIPING-WIRING DIRECTIONS
FOUNDATION
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
3 FOUNDATION BOLTS
2 SERVICE SPACE
Dimensions of space needed
for service access are
shown in the below diagram.
<Foundation bolt height>
100
Over
FREE
Over 150mm
30
Less than
500
Over
Over
10
Over
Service space
Over 10mm
500
Side Air Intake
Rear Air Intake
Handle for moving
Handle for moving
Handle for moving
Air intake
27Knock-Out)
{
Power supply wiring hole
(2-
Rear trunking hole
(Knock-Out)
45 40
Right trunking hole
(Knock-Out)
27Knock-Out)
{
Power supply wiring hole
(2-
75 40
Right piping hole
(Knock-Out)
4540
27Knock-Out)
{
Power supply wiring hole
(2-
92
{
92
{
73 63
92
{
Rear piping hole
(Knock-Out)
92
65
27 55
23 73 63
92
19 55
73 63 23 27 92
23 27 55
65
92
Over1000mm
Over 10mm
1 FREE SPACE (Around the unit)
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
···Refrigerant GAS pipe connction (FLARE){15.88(5/8F)
···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8F)
Example of Notes
2
1
w1 ···Indication of STOP VALVE connection location.
25
Piping Knock-Out Hole Details
Front trunking hole
(Knock-Out)
Front piping hole
(Knock-Out)
WIRED REMOTE CONTROLLER
130
120
19
Unit : mm
26
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
27
4
INDOOR POWER BOARD
[LEGEND]
P.B
INDOOR CONTROLLER BOARDI.B FUSE(T6.3AL250V)FUSE
CN2L
VARISTORZNR
CONNECTOR(LOSSNAY)
CN32
FAN CONTROL ELEMENTBCR
CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION) See table 1
SWITCH(
CAPACITY CORD
) See table 2
SW2 SWE
CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP) X4 RELAY(FAN MOTOR)
LED1 POWER SUPPLY(I.B) LED2 POWER SUPPLY(I.B) LED3 TRANSMISSION(INDOOR-OUTDOOR)
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C CAPACITOR(FAN MOTOR)
MF FAN MOTOR MV VANE MOTOR
DP DRAIN-UP MACHINE DS DRAIN SENSOR
H2 DEW PREVENTION HEATER
TB4
TERMINAL BLOCK (INDOOR/ OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (INDOOR UNIT POWER(OPTION))
TB5, TB6 TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR
(0˚C/15k,25˚C/5.4k DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15k,25˚C/5.4k DETECT)
TH5 COND./EVA. TEMP. THERMISTOR
(0˚C/15k,25˚C/5.4k DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER BOARD RU RECEIVING UNIT BZ BUZZER LED1 LED(RUN INDICATOR) LED2 LED(HOT ADJUST) SW1 SWITCH(HEATING ON/OFF) SW2 SWITCH(COOLING ON/OFF)
321
321
531
MF
FAN
(WHT)
RED
WHT
BLK
BLK
X1
X4
X1X4
C
BCR
31
DP
D.U.M
CNP
(BLU)
YLW
YLW
ORN
ORN
YLW
31 31 31 31
YLW
YLW
D.HEATER
CNC(RED)
RED
WHT
WHT
BRN
POWER CNDK (RED)
POWER CND (ORN)
21
POWER CN2D (WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
CN41CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
VANE CN6V
(GRN)
CN2S
(WHT)
CNSK (RED)
W.B
LED2
CNB
LED1
SW1 SW2
RU
21
2
21
1
REMOCON
CN22 (BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
321 21 21
D.SENSOR
CN31
(WHT)
INTAKE
CN20 (RED)
HEATER
CN24
(YLW)
LIQUID
CN21
(WHT)
DS
TH2
21
PIPE CN29 (BLK)
TH3
TH1
LED3 LED2 LED1
ON OFF
SWE
Refer to tables 1 and 2.
SW2 SW1
9 5
10
76321 84
5MV5MV5
5
MV5MV
GRILLE
H2
S1 S2
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
BLU
YLW
ORN
ORN
BRN
GRN/YLW
S3
TB4
TO OUTDOOR UNIT
TO OUTDOOR UNIT
L
S1 S2
S3
N
DC
13.1V
1
2
2
3
1
P.B
ZNR
FUSE
I.B
I.B
YLW ORN
BRN
ORN
YLW
ORN
1 (Fig.1)
NOTES:
1.Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4.This dlagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal.
1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1. 2 ; For power supply system of this unit, refer to the caution label located near this diagram.
Please set the voltage using the remote controller. For the setting method. please refer to the indoor unit Installation Manual.
1 2 3 4 5
ON OFF
MODELS
Table 1
SW1
Service board
PLA-RP. AA
MODELS
Table 2
SW2
Service board
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
WIRING DIAGRAM
PLA-RP50AA PLA-RP60AA PLA-RP71AA
28
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
INDOOR POWER BOARD
[LEGEND]
P.B
INDOOR CONTROLLER BOARDI.B CN2L CONNECTOR(LOSSNAY) CN32
CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION)wSee table 1
SWITCH(
CAPACITY CORD
)wSee table 2
SW2 SWE
CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP)
LED1 POWER SUPPLY(I.B) LED2 POWER SUPPLY(I.B) LED3 TRANSMISSION(INDOOR-OUTDOOR)
FUSE
FUSE(T5AL250V) ZNR VARISTOR IPM POWER MODULE
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MF FAN MOTOR
MV VANE MOTOR
DP DRAIN-UP MACHINE DS DRAIN SENSOR
DCL REACTOR
H2 DEW PREVENTION HEATER
TB2
TERMINAL BLOCK (Indoor unit Power (option))
TB4 TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TB5, TB6 TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR
(0:/15k",25:/5.4k" DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID
(0:/15k",25:/5.4k" DETECT)
TH5 COND./EVA. TEMP. THERMISTOR
(0:/15k",25:/5.4k" DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER BOARD RU RECEIVING UNIT BZ BUZZER LED1 LED(RUN INDICATOR) LED2 LED(HOT ADJUST) SW1 SWITCH(HEATING ON/OFF) SW2 SWITCH(COOLING ON/OFF)
Please set the voltage using the remote controller. For the setting method. please refer to the indoor unit Installation Manual.
S1 S2 S3
TB4
TO OUTDOOR UNIT
YLW ORN
YLWYLW ORN
BRN
ORN
1
11
2
1
2
2
3
1
2
3
1
3
5
53
RECTIFIER
TRANS
IPM
MF
1
2
3
9 5
10
76321 84
5MV5MV5
5
MV5MV
GRILLE
H2
GRILLE
BLK
X1
J41
J42
X1
3131 5
DP
D.U.M
CNP
(BLU)
YLW
YLW
ORN
ORN
YLW
BLK
WHT
PNK
31 31 31
YLW
YLW
D.HEATER
CNC
(RED)
CN33
(GRN)
CN02
(GRN)
CN01 (BLK)
POSITION DETECTION
SENSOR INPUT
CN3
(WHT)
CN03 (BLU)
CN2S (WHT)
FAN CN2 (GRN)
CN4 (WHT)
FUSE
ZNR
DCL
FAN
WHT
BRN
POWER CND (ORN)
21
POWER CN2D (WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
CN41CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
5
VANE CN6V
(GRN)
W.B
I.B
LED2
CNB
LED1
SW1 SW2
RU
21
2
21
1
REMOCON
CN22 (BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
21 21 21
D.SENSOR
CN31
(WHT)
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
DS
TH2
21
PIPE CN29 (BLK)
TH5
TH1
LED3
Pair No.
LED2 LED1
ON OFF
SWE
Refer to tables 1 and 2.
wBe sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor)
SW2 SW1
BLK WHT RED
31
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB4
YLW ORN
ORN
BRN
TO OUTDOOR UNIT
S1 S2
S3
I.B
P.B
TB2
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED BLU
GRN/YLW
L
N
3 1
5
CN01 (BLK)
YLW
ORN
w1 (Fig.1)
1 2 3 4 5
ON OFF
(Table 1) SW1 (MODEL SELECTION)
SW1
Manufacture/Service
(Table 2) SW2 (CAPACITY CORD)
1 2 3 4 5
ON OFF
MODELS
SW2
Manufacture/Service
PLA-RP100AA2 PLA-RP140AA2
PLA-RP125AA2
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
Manufacture/Service
1.Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4.This dlagram shows the wiring of indoor and outdoor connecting wires. (specification of 230V), adopting superimposed system of power and signal.
w1 ; When work to supply power separately to indoor and outdoor unit was applied, refer to Fig1. w2 ; For power supply system of this unit, refer to the caution label located near this diagram.
NOTES:
29
PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
<wA>
N
L
S1 S2
12
21
12
S3
TO CND
TO OUTDOOR UNIT
TO CN3C
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
54321
OFF
ON
50EA
60EA
71EA
35EA(2)
100EA(2)
125EA
140EA
Capacity cord switch
Model selection switch
SW2
SW1
MODELS
POWER SUPPLY ~(1PHASE) 230V 50Hz
(IN CASE OF CONNECT THE REPLACEMENT WIRING)
NOTE 1.SINCE THE OUTDOOR SIDE ELECTRIC WIRING MAY CHANGE BE SURE TO CHECK THE OUTDOOR UNIT ELECTRIC WIRING FOR SERVICING.
2.INDOOR AND OUTDOOR CONNECTING WIRES ARE MADE WITH POLARITIES, MAKE WIRING MATCHING TERMINAL NUMBERS(S1,S2,S3).
3.SYMBOLS USED IN WIRING DIAGRAM ABOVE ARE, : CONNECTOR, : TERMINAL.
4.THE WIRING BETWEEN MA-REMOTE CONTROLLER AND TB5 IS INCLUDED IN THE PACKAGE.
TO OUTDOOR UNIT
TO MA-REMOTE CONTROLLER DC8.7-13V
I.B.
X6
X4
X5
X1
ZNR
FUSE
P.B.
CN31
1
3
DS
INSIDE SECTION OF CONTROL BOX
B
L
U
B L
U
B L U
B
L
U
TB5
(RED)
643521
C
MF
X6X5X4
X1
(RED)
CNDK
(BLU)
CNP
(WHT)
FAN
1
Y L
W
O R N
(ORN)
31
CND
2
1
(RED)
LED1 LED2 LED3
CN2L
OFF
ON
SWE
SW2
SW1
(RED)
(WHT)
P N K
P N K
B L K
B L K
W H
T
B L K
B
L
K
W H T
W H T
W H T
1
2
31
CN2S
CNSK
(WHT)
(RED)
YLW
ORN
BRN
B R N
O R N
(BLU)
WHT
BLK
CN2D
(WHT)
(BLU)
(RED)
(WHT)
(BLK)
(WHT)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
wA
DP
643521
2 1
TB4
S3 S1
S2
2
1331
643521
MF
C
12
CN24
321
12
3
1
2
1
2
1
2
TH5TH2TH1
1
2
CN3C
31
1375
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789 432154321
<PEAD-RP71•100•125•140EA, 100EA2> External static pressure 130Pa
<PEAD-RP71•100•125•140EA, 100EA2>
External static pressure 70Pa <PEAD-RP35•50•60EA, 35EA2> External static pressure 70Pa
Optional parts
Optional parts
<PEAD-RP35•50•60EA, 35EA2>
External static
pressure 30Pa
(OPTIONAL PARTS)
DRAIN PUMP
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS) DP
DS
TRANSMISSION(INDOOR•OUTDOOR)
LED3
SWITCH(MODEL SELECTION)
SW1
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t,25:/5.4t DETECT)
INTAKE AIR TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
DRAIN SENSOR
DRAIN PUMP
TH5
TH2
TH1
TB5
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCKTB4
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
CN41
CN32
CN2L
I.B.
SYMBOL
PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
30
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Capacity cord switch
Model selection switch
SW2SW1
ON OFF
12345
ON OFF
12345
ON OFF
12345
54321
OFF
ON
100GA
71GA
60GA
MODELS
<wA>
N
L
S1 S2
12
21
12
S3
TO CND
TO OUTDOOR UNIT
TO CN3C
POWER SUPPLY ~(1PHASE) 230V 50Hz
(IN CASE OF CONNECT THE REPLACEMENT WIRING)
NOTE 1.SINCE THE OUTDOOR SIDE ELECTRIC WIRING MAY CHANGE BE SURE TO CHECK THE OUTDOOR UNIT ELECTRIC WIRING FOR SERVICING.
2.INDOOR AND OUTDOOR CONNECTING WIRES ARE MADE WITH POLARITIES, MAKE WIRING MATCHING TERMINAL NUMBERS(S1,S2,S3).
3.SYMBOLS USED IN WIRING DIAGRAM ABOVE ARE, : CONNECTOR, : TERMINAL.
4.THE WIRING BETWEEN MA-REMOTE CONTROLLER AND TB5 IS INCLUDED IN THE PACKAGE.
TO MA-REMOTE CONTROLLER DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1ZNR
FUSE
P.B.
I.B.
X1
Y L W
O R N
X6X5X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B L U
B L U
B L U
B L U
(BLK)
(WHT)
(RED)
(BLU)
B L K
W H
T
BLK
WHT
(WHT)
(BLU)
B R N
BRN
O
R N
ORN YLW
(BLU)(RED)(ORN)
(RED)
(WHT)
B
L
K
W
H T
B L K
W H T
(WHT)
(WHT)
O R G
B L K
B L
U
B
L
K
Y L
W
Y
L
W
G R Y
wA
*
(FACTORY SHIPMENT)
240V230V220V 20Pa
60Pa 75Pa
10Pa 50Pa 70Pa50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2 1
TB5
TB4
S3 S1
S2
2 1
CNP
1331
31
13
CNSK
2
1
CN2S
643521
MF
C
1
2
CN24
3
21
12
3
1
2
121
2
TH5TH2
TH1
LED1 LED2 LED3
1
2
CN2D
CN3C
31
CND CNDK
137
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789
4
321
54321
INSIDE SECTION OF CONTROL BOX
*External static pressure
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR•OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t,25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t,25:/5.4t DETECT)
INTAKE AIR TEMP.THERMISTOR (0: /15t,25:/5.4t DETECT)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
31
PKA-RP50GAL
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
PIPE CN29
(
BLK
)
1 2
1 2
1 2
1 31 31 3 1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L CN51 CN32
WIRELESS CN90
(
WHT
)
VANE CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1 2
1 2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
POWER
CNDK (RED)
CNDK (RED)
DC13.1V
CN2S
(WHT)
POWER
CND
(ORN)
POWER CN2D(WHT)
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
BLU
YLW ORN
ORN BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
w1 (Fig.1)
Refer to tables 1 and 2 for service PCB.
GRN/YLW
TB2
I.B
HEATER
CN24 (YLW)
POWER SUPPLY ~(1PHASE) 230V 50Hz
88H
FS2
26H
H1
L
REDRED 5 3RED BLU
GRN/YLW
WHT
RED
61
REDGRY
N
2
1
2
6 5
1
FS1
88H
YLW
YLW
SW1
Service board
SW2
Service board
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
PKA-RP50GAL PKH-P50GALH
Please set the voltage using the remote controller. For the setting method,please refer to the indoor unit Installation Manual.
PKH-P50GALH models only
P.B
INDOOR POWER BOARD
SYMBOL NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR <LOSSNAY> CN32 CONNECTOR <REMOTE SWITCH> CN41 CONNECTOR <HA TERMINAL-A> CN51 CONNECTOR <CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION>wSee Table 1. SW2 SWITCH <CAPACITY CODE>wSee Table 2. SWE SWITCH <EMERGENCY OPERATION> X4 RELAY <FAN MOTOR> BCR
POWER SUPPLY <R.B>
LED1 POWER SUPPLY <I.B> LED2
TRANSMISSION <INDOOR-OUTDOOR>LED3
FAN CONTROL ELEMENT
C CAPACITOR <FAN MOTOR>
FAN MOTOR VANE MOTOR
MF MV
SYMBOL NAME
TB4
TERMINAL BLOCK <INDOOR/ OUTDOOR
TB2
TERMINAL BLOCK (HEATER) wPKH-P.GALH models only or option for PKA-RP.GAL models.
CONNECTING LINE> TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE> <OPTION> ROOM TEMP.THERMISTOR <0:/ 15k", 25:/ 5.4k" DETECT> PIPE TEMP.THERMISTOR/ LIQUID <0:/ 15k", 25:/ 5.4k" DETECT> COND./ EVA.TEMP.THERMISTOR <0:/ 15k", 25:/ 5.4k" DETECT>
TB5,TB6
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED <RUN INDICATOR> LED <HOT ADJUST> SWITCH (HEATING ON/ OFF> SWITCH (COOLING ON/ OFF> WIRED REMOTE CONTROLLER BOARD
R.B HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
THERMAL FUSE <84:10A>
FS2
THERMAL FUSE <104:10A>
FS1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
w1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1. w2. For power supply system of this unit, refer to the caution label located near this diagram.
32
PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
PIPE CN29
(
BLK
)
1 2
1 2
1 2
1 31 31 3 1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L CN51 CN32
WIRELESS CN90
(
WHT
)
VANE CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1 2
1 2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual
SW1
Table 1
Service board
SW2
Table 2
Service board Service board Service board
POWER
CNDK (RED)
CNDK (RED)
DC13.1V
CN2S
(WHT)
POWER
CND
(ORN)
POWER CN2D(WHT)
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY (1PHASE) 230V 50Hz
RED BLU
YLW ORN
ORN BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
w
1 (Fig.1)
Refer to tables 1 and 2 for service PCB.
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
PKA-RP60FAL PKH-P60FALH
1 2 3 4 5
ON OFF
MODELS
PKA-RP71FAL PKH-P71FALH
1 2 3 4 5
ON OFF
MODELS
PKA-RP100FAL PKH-P100FALH
TB2
I.B
HEATER
CN24 (YLW)
PKH-P60 P100FALH models only
POWER SUPPLY (1PHASE) 230V 50Hz
88H
FS2
26H
H1
L
REDRED 5 3RED BLU
GRN/YLW
WHT
RED
61
REDGRY
N
2
1
2
6 5
1
FS1
88H
YLW
YLW
GRN/YLW
P.B
INDOOR POWER BOARD
SYMBOL NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE(T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) SW1 SWITCH (MODEL SELECTION)
w
See Table 1.
SW2 SWITCH (CAPACITY CODE)
w
See Table 2. SWE SWITCH(EMERGENCY OPERATION) X4 RELAY(FAN MOTOR) BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B) LED2
TRANSMISSION(INDOOR-OUTDOOR)LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR VANE MOTOR
MF MV
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (HEATER)
w
PKH-P.FALH
models only or option for PKA-RP.FAL models. CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE )(OPTION) ROOM TEMP.THERMISTOR (0
;
/15k', 25;/5.4k' DETECT) PIPE TEMP.THERMISTOR/LIQUID (0
;
/15k', 25;/5.4k' DETECT) COND./EVA.TEMP.THERMISTOR (0
;
/15k', 25;/5.4k' DETECT)
TB5
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED(RUN INDICATOR ) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) WIREDREMOTE CONTROLLER BOARD(OPTION) TERMINAL BLOCK(REMOTE CONTROLLER
THERMAL FUSE(117
;
10A:60,71FALH/
117
;
16A:100FALH)
TRANSMISSION LINE)
R.B
HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
TB6
FS1,2
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
w
1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
w
2. For power supply system of this unit, refer to the caution label located near this diagram.
33
PCA-RP50GA PCA-RP60GA PCA-RP71GA
X4 X1
FAN
(
WHT
)
1 3 1 3 1 3 1 35
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK (RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1 2
1 2
3
P.B
I.B
CNDK (RED)
DC13.1V
CN2S
(WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER CN2D(WHT)
1 3
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
SWE ON OFF
SW2 SW1
Refer to tables 1 and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41 CN2L CN51 CN32
VANE CN6V
(
GRN
)
MV
6 6
9
MV
6 6
WIRELESS CN90
(
WHT
)
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
D.SENSOR CN31
(
WHT
)
CN31
DRAIN SENSOR
DS
PIPE CN29
(
BLK
)
1 21 2 3
1 2 3
1 2
1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2 SW1
100~140 TYPE
MV
5 5
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED BLU
YLW
GRN/YLW
ORN ORN
BRN
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
W
1 (Fig.1)
(
WHT
)
I.B
HEATER
CN24 (YLW)
26H
RED
61
REDGRY
2
6 5
1
88H
YLW
YLW
TB2
POWER SUPPLY ~(1PHASE) 230V 50Hz
88H
FS2
H1
L
REDRED 5 3RED
BLU
GRN/YLW
WHT
N
2
1
FS1
PCH-P50~P140GAH models only
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SW1
Table 1
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP.GA PCH-P.GAH
SW2
Table 2
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP50GA PCH-P50GAH
1 2 3 4 5
ON OFF
PCA-RP60GA PCH-P60GAH
1 2 3 4 5
ON OFF
PCA-RP71GA PCH-P71GAH
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP100GA PCH-P100GAH
1 2 3 4 5
ON OFF
PCA-RP125GA PCH-P125GAH
1 2 3 4 5
ON OFF
PCA-RP140GA PCH-P140GAH
P.B
INDOOR POWER BOARD
SYMBOL NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) SW1 SWITCH (MODEL SELECTION) WSee Table 1. SW2 SWITCH (CAPACITY CODE) WSee Table 2. SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
X1 RELAY(DRAIN PUMP) BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B) LED2
TRANSMISSION(INDOOR-OUTDOOR)LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR VANE MOTOR
MF MV
DRAIN-UP MACHINE (OPTION)
DP
DRAIN SENSOR (OPTION)
DS
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER) WPCH-P.GAH models only or option for PCA RP.GA models.
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE ) ROOM TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT) PIPE TEMP.THERMISTOR/LIQUID (0;/15k', 25;/5.4k' DETECT) COND./EVA.TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT)
TB5,TB6
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD(OPTION) RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
THERMAL FUSE(
98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
FS1,2
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
W
1. When work to supply power separately to
Indoor and Outdoor unit was applied, refer to Fig 1.
W
2. For power supply system of this unit,
refer to the caution label located near this diagram.
[Servicing] Fasten terminal of the terminal board "TB4"equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
When installing drain-up machine (Optional part).
W
When installing optional drain-up machine disconnect the CN31 jumper connector and replace it with the drain sensor (DS).
PCA-RP100GA PCA-RP125GA PCA-RP140GA
34
SYMBOL
[ LEGEND ]
NAME SYMBOL NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V)
MF1, MF2 C1, C2 H2
FAN MOTOR CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER VARISTOR CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROLL) POWER SUPPLY (I. B) POWER SUPPLY (R. B) TRANSMISSION(INDOOR-OUTDOOR) RELAY (DEW PREVENTION HEATER) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) SWITCH (MODEL SELECTION)
See Table 1. SWITCH (CAPACITY CODE) See Table 2. SWITCH (EMERGENCY OPERATION)
P. B I. B
FUSE ZNR CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 X4 X5 X6 SW1
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R. B
TERMINAL BLOCK(INDOOR UNIT POWER (OPTION))
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0˚C/15k, 25˚C/5.4k DETECT) COND./ EVA.TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
WIRED REMOTE CONTROLLER BOARD SW2 SWE
Service board
SW1
Table 1
1 2 3 4 5
ON OFF
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PCA-RP71HA
ON OFF
Service board
1 2 3 4 5
MODELS
PCA-RP125HA
ON OFF
1357
MF1
BLU
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
ORN
C1
RED
RED
13 13 13 12
1 2
1 2
3
13
11
654321
MF2
BLU
YLW
YLW
ORN
BLK
RED
WHT
WHT
YLW
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
BRN
C2
GRY
RED
654321
D.HEATER CNC (RED)
For PCA-RP125HA
X6 X5 X4
X6 X5 X4
ZNR
FUSE
SWE
FAN
(WHT)
SW2 SW1
LED3 LED2 LED1
H2
OFF
ON
12 12 12
12 13
12
WHT
WHT
REMOCON
CN22 (BLU)
TH1 TH2 TH5
BLU
BLU
BLK
BLK
1
2
2
1
TB5
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
PIPE CN29 (BLK)
R.B
TB6
TRANSMISSION WIRES DC12V
CN41 CN2L
CN32CN51
ROWER
CNDK (RED)
ROWER
CND
(ORN)
DC13.1V
CNDK
(RED)
CN2S
(WHT)
P.B
I.B
BRN
YLW ORN ORN
S1
S2
S3
TB4
TO OUTDOOR UNIT
ROWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
Refer to tables 1 and 2 for service PCB.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
TB2
BLU
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
ORN ORN
YLW
GRN/YLW
BRN
w1 (Fig.1)
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are, : Connector, : Terminal (block). 1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1. 2 ; For power supply system of this unit, refer to the caution label located near this diagram.
PCA-RP71HA PCA-RP125HA
35
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
1357
MF
ORN
C
RED
BLK
BLU
YLW
13 13 13 12
1
2
2 1
3
13
ML
YLW
YLW
BLK
ORN
YLW
YLW ORNS1S2
S3
WHT
WHT
WHT
BRN
ORN
RED
I.B
FAN (WHT)
LOUVER CNL (YLW)
X4X5X6
X6
X5 X4
X2
ZNR
FUSE
X2
LED3 LED2 LED1
SWE
ON OFF
POWER CNDK (RED)
POWER CND (ORN)
POWER CN2D (WHT)
WIRELESS
CN90
(WHT)
2 1
REMOCON
CN22
(BLU)
CN32
CN2L
2
1
TB6
2 2
1 1
2 1
LIQUID CN21 (WHT)
INTAKE CN20 (RED)
PIPE CN29 (BLK)
CN24 CN41
CN51
R.B
TRANSMISSION WIRES DC12V
BLU BLU
TH1
TH2
TH5
SW1SW2
TB4
REDRED
WHT
RED BLU
GRN/YLW
88H
FS1FS2
H
53
1 2
L N
TB2
POWER SUPPLY ~(1 PHASE) 230V 50Hz
2 1
6 5
RED RED
YLW
26H
88H
YLW
YLW
16
HEATER
CN24 (YLW)
I.B
PSH -P.GAH
models only
INDOOR UNIT
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
Refer to tables 1 and 2 for service PCB.
P.B
CNSK (RED)
CN2S (WHT)
DC13.1V
TO OUTDOOR UNIT
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
TB2
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
BLU
GRY/YLW
RED
BLU
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
ORN
BRN
1 (Fig.1)
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PSA-RP71GA PSH-P71GAH
PSA-RP100GA PSH-P100GAH
PSA-RP125GA PSH-P125GAH
PSA-RP140GA PSH-P140GAH
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
Service board
SW2
Table 1
1 2 3 4 5
MODELS
PSA-RP.GA PSH-P.GAH
ON OFF
P.B
INDOOR POWER BOARD
SYMBOL NAME SYMBOL NAME SYMBOL NAME
I.B
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR (LOSSNAY) CN32 CONNECTOR (REMOTE SWITCH) CN41 CONNECTOR (HA TERMINAL-A) CN51 CONNECTOR (CENTRALLY CONTROL)
SW1
SWITCH (MODEL SELECTION) See Table 1.
SW2
SWITCH (CAPACITY CODE) See Table 2.
SWE SWITCH (EMERGENCY OPERATION)
X4 RELAY (FAN MOTOR) X5 RELAY (FAN MOTOR) X6 RELAY (FAN MOTOR)
X2
RELAY (LOUVER)
POWER SUPPLY (R.B)
LED1 POWER SUPPLY (I.B) LED2
TRANSMISSION (INDOOR-OUTDOOR)LED3
WIRED REMOTE CONTROLLER BOARD TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
R.B
TB6
HEATER
HEATER
THERMAL FUSE (110˚C16A)
H
FS1,2
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
C CAPACITOR (FAN MOTOR)
FAN MOTOR
MF
LOUVER MOTOR
ML TB2
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TB4
TERMINAL BLOCK (HEATER) PSH-P.GAH models only or option for PSA-RP.GA models.
ROOM TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
PIPE TEMP.THERMISTOR/LIQUID (0˚C/15k, 25˚C/5.4k DETECT)
COND./EVA.TEMP.THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
TH1
TH2
TH5
[NOTES]
1.Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4.This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal.
1 ; When work to supply power separately to Indoor and Outdoor unit
was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label
located near this diagram.
36
PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
CY2
CY1
CY1, CY2
Capacitor
T6.3AL250V
37
5
Thermistor TH2 Pipe temperature (Liquid)
Distributor with strainer(#50)
Thermistor TH5 (Cond./Eva. temperature)
Thermistor TH1 (Room temperature)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer(#50)
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·AA(2) PCA-RP·GA PCA-RP·HA PKA-RP·GAL PKA-RP·FAL PSA-RP·GA PEAD-RP·EA(2) PEAD-RP·GA
38
5-2. OUTDOOR UNIT
Outdoor heat exchanger
Thermistor (TH3)
Thermistor (TH6)
Distributor
Service port (check)
Accumulator
Compressor
Refrigerant GAS pipe
15.88A({5/8")
Refrigerant LIQUID pipe
9.52A({3/8") Stop valve
(with service port)
4-way valve
Service port (check)
High pressure protect switch
Refrigerant flow in cooling Refrigerant flow in heating
Liner expansion valve
Thermistor (TH4)
Muffler
Ball valve
Bypass valve
(#50)
Strainer
(#100)
Strainer
Strainer (#40)
(#100)
Strainer
Service port (check)
Accumulator
Compressor
Refrigerant GAS pipe
15.88A({5/8")
Refrigerant LIQUID pipe
9.52A({3/8")
4-way valve
Service port (check)
High pressure protect switch
Liner expansion valve
Muffler
Thermistor (TH4)
Refrigerant flow in cooling Refrigerant flow in heating
Ball valve
(#50)
Strainer
Strainer
(#100)
Strainer (#100)
Strainer
(#100)
Stop valve
(with service port)
Strainer (#40)
Thermistor (TH3) Capillary tube
([4.0o[3.0-L200)o2
Thermistor (TH6)
Distributor
PUHZ-P100VHA
PUHZ-P125,140VHA
39
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.6
0.8
1.0
1.2
1.4
Cooling capacity ratio
Outdoor intake air dry-bulb temperature <D.B. :>
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.4
0.6
0.8
1.0
1.2
Cooling input ratio
Outdoor intake air dry-bulb temperature <D.B. :>
6
6-1. FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-P100~140VHA
PERFORMANCE CURVES
Cooling capacity
Indoor intake air wet-bulb temperature <W.B. :>
Cooling input
Indoor intake air wet-bulb temperature <W.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
40
Heating capacity
Indoor intake air dry-bulb temperature <D.B. :>
Heating input
Outdoor intake air wet-bulb temperature <W.B. :>
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
41
7
Refrigerant piping length (one way)
55m50m40m30m
20m
10m5m
Outdoor unit
7-1. COOLING CAPACITY CORRECTION FACTORS
PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Outdoor unit
PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA
Refrigerant piping length (one way)
55m50m40m30m
20m
10m5m
7-2. HEATING CAPACITY CORRECTION FACTORS
1.00
1.00
1.00
0.985
0.981
0.976
0.957
0.946
0.931
0.931
0.914
0.893
0.908
0.885
0.858
0.886
0.858
0.827
0.876
0.845
0.813
1.00
1.00
1.00
0.997
0.997
0.997
0.991
0.991
0.991
0.985
0.985
0.985
0.979
0.979
0.979
0.973
0.973
0.973
0.970
0.970
0.970
CORRECTION FACTORS
42
APPLI CABLE EXTENSION PIPE FOR EACH MODEL8
<Table 1> Maximum pipe length
50m
[30m]
<Marks in the table>
The maximum pipe length Charge-less pipe length
: It can be used. : Cooling capacity is lowered. : Additional refrigerant charge is required when the pipe length exceeds 10m.
P100
P125,P140
Liquid
pipe
(mm)
OD
Thickness
OD
Thickness
Gas pipe
(mm)
ø12.7
t0.8
ø15.88
t1.0
Standard size
50m
[20m]
Standard size
50m
[30m]
ø19.05
t1.0
50m
[20m]
50m
[30m]
ø15.88
t1.0
25m
[10m]
30m
[10m]
ø19.05
t1.0
25m
[10m]
30m
[10m]
ø9.52
t0.8
ø12.7
t0.8
ø9.52
ø15.88
Standard size
50m
[20m]
50m
[20m]
ø9.52 ø15.88
Standard size
50m
[30m]
ø9.52
ø19.05
50m
[20m]
50m
[20m]
ø9.52
ø19.05
50m
[30m]
ø12.7
ø19.05
25m
[10m]
25m
[10m]
ø12.7 ø19.05
30m
[10m]
P100(RP50o2)
P125(RP60o2) • P140(RP71o2)
ø6.35 ø12.7
ø9.52
ø15.88
ø12.7
ø19.05
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Branch
pipe
(mm)
[B, C]
Main pipe
(mm)
[A]
<Table 2> Maximum pipe length
ø
9.52
ø15.88
Standard size
50m
[30m]
50m
[30m]
ø
9.52
ø19.05
50m
[30m]
50m
[30m]
ø
12.7
ø19.05
30m
[10m]
30m
[10m]
P140(RP50o2)
ø6.35 ø12.7
ø9.52
ø15.88
ø12.7
ø19.05
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Branch
pipe
(mm)
[B, C, D]
Main pipe
(mm)
[A]
<Table 3> Maximum pipe length
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe
H
h
<TWIN SYSTEM> Total length A + B + C P100-140: 50 m
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
D
Indoor unit
Indoor unit
Distribution pipe
H
h
<TRIPLE SYSTEM> Total length A + B + C + D P140: 50 m
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM Pipe length
8-1-2. TWIN AND TRIPLE SYSTEM (1) TWIN SYSTEM (2) TRIPLE SYSTEM
43
(3) Pipe size and refrigerant pipe limits.
Outdoor unit
Outdoor unit side Indoor unit side Outdoor unit side Indoor unit side
Total length A+B+C+D
Branch pipe B, C, D
Gas side
Pipe size (mm) Actual piping leng <m>
Indoor ~ Outdoor
Indoor ~ Indoor
(Note 1) No. of bend
Height deffence <m>
Liquid side
TWIN TRIPLE
100-140 140
{15.88<5/8>
RP50 {12.7<1/2> RP60,71
{15.88<5/8>
{9.52<3/8>
RP50 {6.35<1/4> RP60,71 {9.52<3/8>
50m
20m
Indoor ~
Indoor |B-C| 8m |B-C| |C-D| |B-D| 8m
H30m h 1m 15
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe
H
h
<TWIN SYSTEM> Total length A + B + C P100-140: 50 m
<Table 5> Required additional charge when the pipe size is larger than the standard diameter (1:1 SYSTEM)
[12.7 [12.7
P100 P125,140
Liquid pipe dia
Chargeless
25m 30m
100 g per 1 m longer than 10 m 100 g per 1 m longer than 10 m
10m 10m
Max. pipe length
Refrigerant amount to be added
<Table 6> Required additional charge when the pipe size is larger than the standard diameter (TWIN/TRIPLE SYSTEM)
Capacity P100,125,140
When the extension pipe length (main piping + branch piping) exceed 10 m Additional refrigerant amount W(g) = (100 o L1) + (60 o L2) + (30 o L3) - 2000
If the calculation produces a negative number ( W [ 0), additional charging is not necessary. L1:
[12.7 liquid pipe length (m)
L2:
[9.52 liquid pipe length (m)
L3:
[6.35 liquid pipe length (m)
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
D
Indoor unit
Indoor unit
Distribution pipe
H
h
<TRIPLE SYSTEM> Total length A + B + C + D P140: 50 m
2.7kg
4.5kg
21 — 30m
0.6kg 0kg
31 — 40m
1.2kg
0.6kg
41 — 50m
1.8kg
1.2kg
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
Amount of unit filling refrigerant (kg)
PUHZ-P100VHA PUHZ-P125,140VHA
50m or less 50m or less
Note1. The number of bendsin the refrigerant pipe is respectively 8 or less in the range of <A+B> <A+C> <A+D>
2. PUHZ-P100: 20 m chargeless, PUHZ-P125,140: 30 m chargeless
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
Check additional refrigerant charging amount referring to table 5.6 when liquid pipe is one size larger than standard diameter.
44
8-3. CAPACITY CURVE
80
85
90
95
100
5 10152025303540455055
Corrected pipe length
Capacity ratio [%]
Heating
Cooling
P140
P125
P100
P100-140
45
9
PLA-RP71AA
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
28
4.9
7.4
30
6.6
8.9
30
6.6
8.9
Air flow Air speed Coverage range
m
3
/min.
m/sec.
m
20
4.0
5.7
18
3.6
5.2
18
3.6
5.2
PLA-RP50AA
PLA-RP60AA
Air flow Air speed Coverage range
m
3
/min
m/sec
m
PCA-RP50GA PCA-RP60GA PCA-RP71GA PCA-RP100GA
PCA-RP125GA PCA-RP140GA
25
4.1
12.6
34
4.4
15.2
34
4.4
15.2
18
3.8
10.4
18
3.8
10.4
13
3.7
8.8
Air flow Air speed Coverage range
m3/min
m/sec
m
19
2.9
7.9
38
4.2
13.2
PCA-RP71HA PCA-RP125HA
Air flow m3/min Air speed m/sec Coverage range m (ft)
12
5.3
10(32.8)
PKA-RP50GAL
Air flow m3/min Air speed m/sec Coverage range m (ft)
20
4.9
12.4(40.7)
PKA-RP71FAL
20
4.9
12.4(40.7)
PKA-RP60FAL
28
5.4
15.3(50.2)
PKA-RP100FAL
Air flow Air speed Coverage range
m
3
/min
m/sec
m
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
18
2.6
8.3
31
4.5
14.3
33
4.8
15.2
35
4.9
16.1
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni­ture inside the room.
46
9-2. PLA-RP·AA(2)
9-2-1. FRESH AIR INTAKE AMOUNT
47
9-2-2. BRANCH DUCT (Installation at site)
48
PLA-RP50AA PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
49
PLA-RP71AA
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3
/min]
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
Static pressure [Pa]
60
50
40
30
20
10
High
Low
0
123456789
Air flow rate [m
3
/min]
60
50
40
30
20
10
Static pressure [Pa]
High
Low
0
123456789
Air flow rate [m
3
/min]
3
/min]
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
100
Static pressure [Pa]
90
80
70 60
50
40
30 20
10
0
1234567891011
Low
High
Air flow rate [m
3
/min]
100
90
80
70
60
50
40
30
20
Static pressure [Pa]
10
0
1234567
Air flow rate [m
Low
High
3
/min]
50
PLA-RP100AA2
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
50
40
30
20
10
0
1234 5678910
Low
High
Air flow rate [m
3
/min]
Static pressure [Pa]
50
40
30
20
10
0
Low
1234 5678910
High
Air flow rate [m
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
100
Static pressure [Pa]
90 80 70 60
50 40 30
20 10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Low
High
Air flow rate [m
3
/min]
100
90 80 70 60
50 40
Static pressure [Pa]
30 20
10
0
Low
1 2 3 4 5 6 7 8 9 10 11 12 13 14
High
Air flow rate [m
3
/min]
3
/min]
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
120
110
100
Static pressure [Pa]
90
80
70 60
50
40
30
20 10
0
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1
High
Low
Air flow rate [m
3
/min]
120
110
100
90
80
70 60
50
40
30
Static pressure
20 10
0
1
Low
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
High
Air flow rate [m
51
3
/min]
PLA-RP125AA2 PLA-RP140AA2
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
50
40
30
20
10
0
Low
12345678910
High
Air flow rate [m
Static pressure [Pa]
50
40
30
20
10
0
12345678910
Low
High
Air flow rate [m
3
/min]
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
100
Static pressure [Pa]
90 80 70 60 50 40 30 20 10
0
1234567891011121314
Low
High
Air flow rate [m
3
/min]
100
Static pressure [Pa]
90 80 70 60 50 40 30 20 10
0
1234567891011121314
Low
High
Air flow rate [m
3
/min]
3
/min]
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
120
110
100
Static pressure [Pa]
90
80
70 60
50
40
30
20 10
0
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1
Air flow rate [m
Low
High
3
/min]
120
110
100
Static pressure[Pa]
90
80
70 60
50
40
30
20 10
0
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1
Low
High
Air flow rate [m
52
3
/min]
9-2. PEAD-RP·EA,EA2,GA
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
6 8 10 12 14 16 18 20
8 10121416 1820 22
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 10121416182022
8 10121416 1820 22
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 1012141618202224
12 14 16 18 20 22 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
10 12 14 16 18 20 22 24 26
12 14 16 18 20 22 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
9-2-1. FAN PERFORMANCE AND CORRECTED AIR FLOW
PEAD-RP50EA
PEAD-RP60EA
53
PEAD-RP71EA
Lo
Hi
140 120 100
200 180 160
80 60 40 20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140 120 100
180 160
80 60 40 20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
Hi
Corrected Air Flow
Capacity Input
1.1
1.0
0.9
0.8
12 16 20 24 28 32
Air flow (CMM)
Correction factor
Cooling
=
1.1
1.0
1.3
1.2
0.9
0.8 12 16 20 24 28 32
Air flow (CMM)
Correction factor
Heating
Lo
Hi
140 120 100
200
220
180 160
80 60 40 20
32 34 36 38 40 42 44 46 48
Air flow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140 120 100
200
220
180 160
80 60 40 20
32 34 36 38 40 42 44 46
Air flow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
Lo
Hi
Corrected Air Flow
Capacity Input
1.1
1.0
0.9
0.8 32 34 36 38 40 42 44 46 48
Air flow (CMM)
Correction factor
Cooling
1.1
1.0
1.2
0.9
0.8 32 34 36 38 40 42 44 46 48
Air flow (CMM)
Correction factor
Heating
=
=
PEAD-RP100EA2 PEAD-RP125EA
54
PEAD-RP140EA
1.2
1.1
1.0
0.9
0.8 36 38 40 42 44 46
48
50 52
Air flow (CMM)
Correction factor
Heating
Corrected Air Flow
Capacity Input
1.1
1.0
0.9
0.8 36 38 40 42 44 46
48 50
52
Air flow (CMM)
Correction factor
Cooling
Lo
Hi
200 180
160 140 120 100 80 60 40 20
36
38 40 42 44 46 48
50
Air flow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
200
220
180 160 140 120 100 80 60 40 20
36
38 40 42 44 46 48 50
52
Air flow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Hi
55
PEAD-RP60GA
PEAD-RP71GA
56
PEAD-RP100GA
57
10
PLA-RP71AA
NOTCH SPL(dB) LINE
34 32 30 28
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
High Medium1 Medium2
Low
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE CRITERION CURVES
PLA-RP50AA PLA-RP60AA
90
80
NOTCH SPL(dB) LINE
High Medium1 Medium2
Low
33 31 29 28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PLA-RP100AA2
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NOTCH SPL(dB) LINE
High Medium1 Medium2
Low
41 39 36 33
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
10
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
58
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NOTCH SPL(dB) LINE
PLA-RP125AA2 PLA-RP140AA2
High Medium1 Medium2
Low
45 43 40 37
NOTCH SPL(dB) LINE
High Medium1 Medium2
Low
45 43 40 37
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
UNIT
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
CEILING
1.5m
MICROPHONE
59
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 30Pa)
High Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 70Pa)
High Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 30Pa)
High Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 70Pa)
High Low
NC60
NC50
NC40
NC30
NC20
60
61
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
BAND CENTER FREQUENCIES, Hz
PKA-RP60FAL PKA-RP71FAL
High Low
45
SPL(dB)39LINE
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
BAND CENTER FREQUENCIES, Hz
PKA-RP100FAL
High
NOTCH
Low
46
SPL(dB)
41
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PKA-RP50GAL
High
NOTCH
Medium1 Medium2
Low
43
SPL(dB)
41 38 36
LINE
UNIT
WALL
1m
1m
MICROPHONE
62
PCA-RP50GA
NOTCH
High Medium1 Medium2
Low
SPL(dB)
42 40 38 37
LINE
PCA-RP60GA PCA-RP71GA
NOTCH
High Medium1 Medium2
Low
SPL(dB)
43 41 39 37
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PCA-RP100GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
45 43 41 40
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PCA-RP125GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
46 45 43 41
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
63
PCA-RP140GA
90
NOTCH
High Medium1 Medium2
Low
SPL(dB)
48 46 44 42
LINE
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
PCA-RP71HA
90
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
SPL(dB)
38 34
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
1m
1m
about 1.4m
MICROPHONE
PCA-RP125HA
90
NOTCH
High Low
unit
SPL(dB)
50 44
ceiling
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
64
PSA-RP71GA
NOTCH
High
Low
SPL(dB)
45 40
LINE
PSA-RP100GA
NOTCH
High Low
SPL(dB)
49 44
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
90
80
70
60
50
40
30
APPROXIMATE
20
HERESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
90
80
70
60
50
40
30
APPROXIMATE
20
HERESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PSA-RP125GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
APPROXIMATE
20
HERESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
51 46
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
65
PSA-RP140GA
90
80
NOTCH
High
Low
SPL(dB)
52 47
LINE
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
APPROXIMATE
20
HERESHOLD OF REARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
MICROPHONE
1m
1m
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
unit
floor
66
MICROPHONE
1.5m
1m
UNIT
PUHZ-P100VHA
90
80
70
MODE
COOLING
HEATING
SPL(dB)
50 54
LINE
NC-70
PUHZ-P125VHA
90
80
70
MODE
COOLING
HEATING
GROUND
SPL(dB)
51 55
LINE
NC-70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUHZ-P140VHA
90
80
70
MODE
COOLING
HEATING
SPL(dB)
52 56
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
67
11
11-1. INDOOR UNIT
Part Name Model Name Applicable model
Remote sensor PAC-SE41TS-E Remote operation adapter PAC-SF40RM-E All models Remote on/off adapter PAC-SE55RA-E Power supply terminal kit L/N/Earth PAC-SG96HR-E All models
except PCA-RP·HA and PEAD-RP·GA
L/N PAC-SG97HR-E PCA-RP·HA
PEAD-RP·GA Multi-functional casement PAC-SG03TM-E High-efficiency filter element PAC-SG01KF (PAC-SG03TM-E is needed.) Grille + Wireless remote controller PLP-6AALM PLA-RP·AA
PLA-RP·AA2
Grille + Wired remote controller PLP-6AAMD Air outlet shutter plate PAC-SG06SP-E (20 set, 2pcs/set)
Wireless remote controller + Wireless Adapter PAR-SL99B-E PCA-RP·GA
Drain lift up mechanism PAC-SH20DM-E PCA-RP50,60GA
PAC-SH21DM-E PCA-RP71GA PAC-SH22DM-E PCA-RP100,125,140GA
High-efficiency filter PAC-SE80KF-E PCA-RP50GA
PAC-SE81KF-E PCA-RP60,71,100GA
PAC-SE82KF-E PCA-RP125,140GA Duct flange for fresh air PAC-SF28OF-E PCA-RP·HA Filter element PAC-SG38KF-E Decoration cover PAC-SF81KC-E PCA-RP71HA (Front + Suspending bracket cover) PAC-SF82KC-E PCA-RP125HA Wired remote controller PAR-21MAAT-E PKA-RP·GAL (with terminal bed) PKA-RP·FAL Drain lift up mechanism PAC-SE90DM-E PKA-RP·FAL Motor PAC-SK003MT-F PEAD-RP125,140EA (for high external static pressure) PEAD-RP100EA2 Drain lift up mechanism PAC-KE03DM-F PEAD-RP·EA,EA2 Insulation kit PAC-SK010DK PEAD-RP·GA Wiring kit PAC-SK020EC
OPTIONAL PARTS
68
11-2. OUTDOOR UNIT
Part Name Model Name
Applicable model
M-NET adapter PAC-SF80MA-E PUHZ-P100-140 A-control service tool PAC-SK52ST Drain socket PAC-SG61DS-E PUHZ-P100-140 Air outlet guide (RP100,125,140 needs two piece.) PAC-SG59SG-E PUHZ-P100-140
PUHZ-P100-140
Air protect guide PAC-SH63AG-E PUHZ-P100
PAC-SG57AG-E PUHZ-P125-140 Drain pan PAC-SG64DP-E PUHZ-P100-140 Filter dryer
([9.52)
PAC-SG82DR-E PUHZ-P100-140 Distribution pipe
(Twin)
MSDD-50SR-E PUHZ-P100-140
(Triple)
MSDT-111R-E PUHZ-P140 Joint pipe
(Unit Extension pipe)
([15.88 [19.05)
PAC-SG75RJ-E PUHZ-P100-140
69
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Jan. 2006 No.OCS06 PDF 8 Made in Japan.
New publication, effective Jan. 2006. Specifications subject to change without notice.