(Note)
When you connect P series indoor units with SUZ, always make sure to follow the piping size of SUZ.
Never use bigger sized pipings in order to ensure not only the system performance but also for your safety.
2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE).
Drain pump is included.
Max. liftng height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement
and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Wear dew.)
8. As for necessary installation/service space, please refer to the under at figure.
Models
DEFROST/STAND BY lamp
Operation lamp
Refrigerant pipe
···[6.35
Flared connection
···1/4"F
Refrigerant pipe
[6.35
Flared connection
1/4"F
Refrigerant pipe
···[9.52
Flared connection
···3/8"F
70°
[175
Burring hole
3-[2.8
Refrigerant pipe
···[12.7
Flared connection
··1/2"F
Refrigerant pipe
···[15.88
Flared connection
···5/8"F
9010010090
350
120
°
°
120
L.L Filter
AB12 CE
241 258
Detail connecting of branch duct(Both aspects)
Cut out hole
130
100
155
167
ww
14-[2.8
Burring hole
[150
Cut out hole
Burring hole pitch
[125
Cut out hole
[100
Ceiling
Auto Grille
Air intake grille up/down discharge
Ceiling
Max. 4.0m
Air intake grille
D
80
74
400
87
77
85
16
PLA-RP35AAPLA-RP50AAPLA-RP60AAPLA-RP71AAUnit : mm
90
100 100 90
_
70
{175
3 - {2.8
Burring hole
158
350
Detail drawing of fresh air intake
120
_
Branch duct hole
(Cut out hole)
{150
{125
Burring hole pitch
120_
{100
(Cut out hole)
Ceiling surface
100
14 - {2.8
Burring hole
130
167
155
Suspension bolt lower edge
Fresh air intake
159192
Branch duct hole
840
89
98
Suspension bolt M10
or W3/8
1
2
170
140
C
50 - 70
Power line entry
Ceiling hole
860 - 910
810
Suspension bolt pitch
159
Terminal block
197159
840
Feeding hole
(Drain pump)
Control wire entry
37428660
20 - 4520 - 45
16
Drain pipe
VP-25connection
(O.D.{32)
105
Ceiling surface
605
860 - 91020 - 4520 - 45
Ceiling hole
Suspension bolt pitch
159
A
B
190
0
+5
30
17
Branch
duct hole
135
0
+5
High efficiency filter
& Fresh air intake casement (option)
A
(WIRELESS PANEL)
Emergency operation switch (cooling)
Emergency operation switch (heating)
Receiver
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
1 LIQUID SIDE
DEFROST/STAND BY lamp
Operation lamp
RP35, 50
RP60RP71
[6.35[6.35—
17
(Unit : mm)(Unit : mm)
[9.52[9.52[9.52
2 GAS SIDE
[12.7——
[15.88[15.88[15.88
: Factory flare nut attachment to the heat-exchanger.
950
5177
Air intake grille
A
411
Air outlet hole
Models
PLA-RP35,50AA
PLA-RP60,71AA
M
577
Air intake hole
M
411
Air outlet hole
950
241A258B80
Grille
Drain hole
M
M
7751
C
Auto vane
577
Air intake hole
Vane motor
17
PCA-RP50GAUnit : mm
180
210
157
15
85
182 liquid
201 gas
241 (Drainage)
Air intake
918
16190
254
680
50656
Electrical box
226
70
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
525
928
352
263
171
138
86
46 175 1
131
38
38
79
161
32
179
42
6~7
Ceiling
Electrical box
[Front view]
When electrical
box is pulled
down
3
2
8
5
1
4
[15.88
[12.7
[6.35
Available pipe size
[9.52
4 GAS SIDE
5 LIQUID SIDE
RP50
Use the current nuts meeting the pipe size of the outdoor unit.
: Factory flare nut attachment to the heat-exchanger.
(Unit : mm)
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knock out hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
18
PCA-RP50GA2w
16190
254
680
50656
1240 (suspension bolt pitch)
140
150
32080
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
Air intake
85
182
201
241
15
157
(liquid)
(5/8F gas)
(Drainage)
7
2
Electrical box
70
226
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Ceiling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
: Factory flare nut attachment to the heat-exchanger.
4 GAS SIDE
5 LIQUID SIDE
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP71RP60
[6.35
[9.52
[15.88
[9.52
[15.88
(Unit : mm)
[15.88
[12.7
[6.35
[9.52
RP50
PCA-RP60GA
PCA-RP71GAUnit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knock out hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
• Area in which the remote controller is not exposed to direct sunshine
• Area in which there is no heating source nearby
• Area in which the remote controller is not exposed to cold (or warm) winds
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children
Installation method
1 Attach the remote controller holder to the desired location using two tapping screws.
2 Place the lower end of the controller into the holder.
A Wireless remote controller (Accessory)
B Wall
C Remote controller holder (Accessory)
D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there are interferences of fluorescent
lights or strong sunlight.
26
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
27
4
WIRING DIAGRAM
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
INDOOR UNIT
TO OUTDOOR
UNIT
CONNECTING
RT15
RT12
RT13
RT14
RT11
LS1
LS2
230V~
12-24V
TB
S1
S2
S3
1
2
3
4
1
2
3
4
5
6
CN
111
CN
1X1
CN
1Y1
BLK
WHT
WHT
RED
DISP REC
P.C.BOARD
CNCN
106
CN113
CN112
3
2
CN201
1
125
MV1
62
F11
NR11
3
2
1
CN202
ML1
MV2
55
CN
151
DB111
LD103
GRN
ML2
55
CN
152
MF1
5
1
2
3
4
5
6
CN211
T11
INDOOR ELECTRONIC
CONTROL P.C. BOARD
MF2
5
1
2
3
4
5
6
CN212
[LEGEND]
SYMBOL
DB111
F11
LS1
LS2
MF1
MF2
ML1
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
DIODE STACK
FUSE (T3.15AL250V)
DAMPER LIMIT SWITCH (OPEN)
DAMPER LIMIT SWITCH (CLOSE)
UPPER INDOOR FAN MOTOR
LOWER INDOOR FAN MOTOR
DAMPER LOCK MOTOR (RIGHT)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate :
/: Terminal block, : Connector
NAME
SYMBOL
ML2
MV1
MV2
NR11
RT11
RT12
RT13
NAME
DAMPER LOCK MOTOR (LEFT)
HORIZONTAL VANE MOTOR
DAMPER MOTOR
VARISTOR
ROOM TEMPERATURE THERMIST OR
INDOOR COIL THERMISTOR (MAIN 1)
INDOOR COIL THERMISTOR (SUB)
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system of
power and signal.
w1:When work to Supply power separately to indoor and outdoor units was applied, refer to Fig 1.
w2:For power supply system of this unit, refer to the caution label located near this diagram.
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
SYMBOLNAME
W.B
RU
BZ
LED1
LED2
SW1
SW2
OPTION PART
PCB FOR WIRELESS REMOTE CONTROLLER
RECEIVING UNIT
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
[Servicing]
Fasten terminal of the terminal board "TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
When installing drain-up
machine (Optional part).
X4X1
FAN
(
WHT
)
1 31 31 31 35
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK
(RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1
2
1
2
3
P.B
I.B
CNDK
(RED)
DC13.1V
CN2S
(WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER
CN2D(WHT)
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
SWE
ON
OFF
SW2SW1
Refer to tables 1
and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR
UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41CN2L
CN51CN32
VANE
CN6V
(
GRN
)
MV
66
9
MV
66
WIRELESS
CN90
(
WHT
)
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
D.SENSOR
CN31
(
WHT
)
PIPE
CN29
(
BLK
)
1 21 2 3
1 2
1 2
TH5TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
100~140 TYPE
MV
55
W
When installing optional
drain-up machine, disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
NOTES:
1.
Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers
(S1, S2, S3) for correct wirings.
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
w The air coverage range is the distance to which the 0.25m/sec air can reach,when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
51
Detail drawing of fresh air intake
Ceiling surface
Refrigerant pipe
Drain pipe
Electrical Box
Cut out hole
[73.4
Burring hole
3-[2.8 hole
[100
118
25
120
°
120
°
Fresh air intake
Static pressure : P [Pa]
Air flow : Q [m
3
/min]
50
-50
-100
-150
-200
-250
-300
0
0.5 1.0 1.5 2.0 2.5 3.0 3.5
Q
0
B
A
C
1
Curve in the
left graphs.
Duct characteristics
at site
Q
A
EC
2
Q
Qa
AD
3
8-2. SLZ-KA•VA SLZ-KA•VAL
8-2-1. Fresh air intake (Location for installation)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
8-2-2. Fresh air intake amount & static pressure characteristics
Taking air into the unit
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
How to read curves
Q…Designed amount of fresh air intake
<m3/min>
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q<Pa>
B…Forced static pressure at air
conditioner inlet with air flow
amount Q<Pa>
C…Static pressure of booster fan
with air flow amount Q<Pa>
D…Static pressure loss increase
amount of fresh air intake dust
system for air flow amount Q
<Pa>
E…Static pressure of indoor unit
with air flow amount Q
Qa…Estimated amount of fresh air
intake without D<m3/min>
52
8-3. SEZ-KA•VA
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA35VA
80
60
40
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
SEZ-KA50VA
80
60
40
Fan Performance
Recommended range
105 7152025
Air flow (K/X)
Fan Performance
Recommended range
Corrected Air flow
1.1
1.0
0.9
Correction factor
0.8
1.3
1.2
1.1
1.0
Correction factor
0.9
0.8
Corrected Airflow
1.1
1.0
0.9
Correction factor
0.8
1.2
Capacity
Cooling
1051520
Air flow (K/X)
Heating
5101520
Air flow (K/X)
Cooling
510152025
Air flow (K/X)
Heating
Input
25
25
Capacity
Input
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
15510 2025
Air flow (K/X)
1.1
1.0
0.9
Correction factor
0.8
510152025
Air flow (K/X)
53
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
Air flow (K/X)
Recommended range
80
60
40
20
0
155102025
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
SEZ-KA60VA
SEZ-KA71VA
Corrected Air flow
1.1
0.9
1.0
0.8
1015202530
Correction factor
Capacity
Input
Cooling
Air flow (K/X)
0.9
1.0
1.2
1.1
1.3
1015202530
Correction factor
Heating
Air flow (K/X)
Air flow (K/X)
Recommended range
80
60
40
20
0
155102025
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
Corrected Air flow
1.1
0.9
1.0
0.8
1015202530
Correction factor
Capacity
Input
Cooling
Air flow (K/X)
0.9
1.0
1.2
1.1
1.3
1015202530
Correction factor
Heating
Air flow (K/X)
54
8-4. PLA-RP·BA
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Branch duct hole
A
A
A
14-[2.8 burring hole
Indoor unit
[150 cut out hole
Fresh air intake hole
[175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-[2.8 burring hole
Branch duct
hole diagram
(view from
either side)
[125 burring
hole pitch
[100 cut
out hole
Ceiling
*158
120
120
350
90
70°
100 100 90
100
130
*155
*167
Fig. 1
8-4-1 FRESH AIR INTAKE AND BRANCH DUCT
55
3. Fresh air intake volume & static pressure characteristics
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 Direct intake to unit
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
Air flow rate [m3/min]
Air flow rate [m
3
/min]
Air flow rate [m
3
/min]
1 At using multi-function casement, standard filter
PLA-RP35~71BA
Static pressure[Pa]
56
4. Change of outlet numbers
<4- way air flow and branch duct>
w Branch duct should be connected to one of the branch duct holes on the main unit.
Branch
duct
Air intake
Air
outlet
<3- way air flow and branch duct>
w Close the outlet on the side or branch duct and air flows in 3 directions.
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
Airoutletclosedposition
<2- way air flow and branch duct>
w The outlet on the side or branch duct and one of the other outlets are closed.
Air flows in 2 directions.
Air intake
Branch
duct
Air
outlet
closed
position
Air
outlet
closed
position
[The optional air outlet is necessary.]
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
(When the air outlets are closed, close the vane by
removing the vane connector.)
Indoor unit
5. Branch duct and change of outlet numbers
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
Outlet concave
portion
Air outlet shutter plate
(Option)
57
PLA-RP71BA
4-way air flow (horizontal vane) Round duct4-way air flow (horizontal vane) Rectangular duct
30
20
30
DuctDuct
20
10
Static pressure [Pa]
High
Low
0
02
468
Air flow rate [m
3
/min]
3-way air flow (horizontal vane) Round duct3-way air flow (horizontal vane) Rectangular duct
80
70
High
Duct
Close
3
/min]
60
50
40
30
Static pressure [Pa]
20
Low
10
0
0246810
Air flow rate [m
10
Static pressure [Pa]
High
Low
0
02468
Air flow rate [m3/min]
80
70
60
Duct
Close
50
40
30
Static pressure [Pa]
High
20
Low
10
0
0246810
Air flow rate [m
3
/min]
2-way air flow (horizontal vane) Round duct
100
90
80
Duct
Close
70
60
50
40
Static pressure [Pa]
30
20
High
Low
10
0
024681012
Air flow rate [m
3
/min]
Close
2-way air flow (horizontal vane) Rectangular duct
100
90
80
70
60
50
40
Static pressure [Pa]
30
20
Low
10
0
024681012
Duct
Close
High
Air flow rate [m
3
/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-RP35~60BA can be calculated from the air flow rate based on the characteristic
of the duct for PLA-RP71BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
Close
58
8-5. PLA-RP·AA
8-5-1. Fresh air intake amount
59
8-5-2. BRANCH DUCT (Installation at site)
60
Branch duct air flow rate/static pressure characteristics
PLA-RP35AA
4-way air flow (horizontal vane) Rectangular duct4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct2-way air flow (horizontal vane) Round duct
61
PLA-RP50AA
PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct2-way air flow (horizontal vane) Round duct
62
PLA-RP71AA
4-way air flow (horizontal vane) Rectangular duct4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3
/min]
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3-way air flow (horizontal vane) Rectangular duct3-way air flow (horizontal vane) Round duct
Static pressure [Pa]
60
50
40
30
20
10
High
Low
0
123456789
Air flow rate [m
3
/min]
Static pressure [Pa]
60
50
40
30
20
10
High
Low
0
123456789
Air flow rate [m
3
/min]
3
/min]
2-way air flow (horizontal vane) Rectangular duct2-way air flow (horizontal vane) Round duct
100
Static pressure [Pa]
90
80
70
60
50
40
30
20
10
0
1234567891011
Low
High
Air flow rate [m
3
/min]
100
90
80
70
60
50
40
30
20
Static pressure [Pa]
10
0
1234567
Air flow rate [m
Low
High
3
/min]
63
8-6. PEAD-RP·EA, EA2, GA
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
6810 12 14 16 18 20
810121416182022
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 10121416182022
810121416182022
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 1012141618202224
12 14 1618 2022 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
10 12 14 16 18 20 22 24 26
12 14 1618 2022 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
8-6-1. Fan performance and corrected air flow
PEAD-RP35EA2 PEAD-RP50EA
PEAD-RP60EA
64
PEAD-RP71EA
Lo
Hi
140
120
100
200
180
160
80
60
40
20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140
120
100
180
160
80
60
40
20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
Hi
Corrected Air Flow
Capacity
Input
1.1
1.0
0.9
0.8
121620242832
Air flow (CMM)
Correction factor
Cooling
=
1.1
1.0
1.3
1.2
0.9
0.8
121620242832
Air flow (CMM)
Correction factor
Heating
PEAD-RP60GA
65
PEAD-RP71GA
Air flow (CMM)
Recommended range
200
150
100
50
Hi
Lo
0
201517253035
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
Corrected Air flow
1.05
0.95
1.0
0.9
17 202530
Correction factor
Capacity
Input
Cooling
Air flow (CMM)
1.05
1.15
1.1
0.95
1.0
1.2
17 202530
Correction factor
Heating
Air flow (CMM)
8-7. PEA-RP·EA
8-7-1. Fan performance and corrected air flow
PEA-RP71EA
66
9
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
43
44
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
37
37
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
38
38
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOOR UNIT
WALL
1m
1m
MICROPHONE
NOISE CRITERION CURVES
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
67
90
80
70
60
50
40
30
20
10
6312525050010002000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA35VAL
SLZ-KA35VA
High
Medium
38
SPL(dB)33LINE
<50Hz>
NOTCH
Low
29
90
80
70
60
50
40
30
20
10
6312525050010002000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA25VAL
SLZ-KA25VA
High
Medium
37
SPL(dB)31LINE
<50Hz>
NOTCH
Low
28
UNIT
1.5m
MICROPHONE
CEILING
90
80
70
60
50
40
30
20
10
6312525050010002000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA50VAL
SLZ-KA50VA
High
Medium
39
SPL(dB)34LINE
<50Hz>
NOTCH
Low
30
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.
68
SEZ-KC25VA
Appro
70
60
50
40
30
20
631252505001000200040008000
10
0
NC60
NC50
NC40
NC30
NC20
Approximate minimum
audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
High
Low
36
SPL(dB)
25
<50Hz>
NOTCH
High speed
Low speed
2m
Aux.duct
1m
1.5m
Measurement location
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.
69
SEZ-KA35VA
NOTCH
High
Low
<50Hz>
SPL(dB)
35
30
LINE
SEZ-KA50VA
NOTCH
High
Low
<50Hz>
SPL(dB)
39
31
LINE
90
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
SEZ-KA60VA
SEZ-KA71VA
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
<50Hz>
SPL(dB)
43
32
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
External static
pressure 30Pa
MICROPHONE
UNIT
1.5m
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.
70
PLA-RP35BAPLA-RP50BA
NOTCH SPL(dB) LINE
High31
Medium129
Medium228
Low27
NOTCH SPL(dB) LINE
High32
Medium131
Medium229
Low28
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PLA-RP60BAPLA-RP71BA
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB) LINE
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
High32
Medium131
Medium229
Low28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB) LINE
High34
Medium132
Medium230
Low28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
71
NOTCH SPL(dB) LINE
PLA-RP35AAPLA-RP50AA
High
Medium1
Medium2
Low
31
29
28
PLA-RP60AA
27
NOTCH SPL(dB) LINE
High
Medium1
Medium2
Low
33
31
29
28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PLA-RP71AA
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
NOTCH SPL(dB) LINE
High
Medium1
Medium2
Low
BAND CENTER FREQUENCIES, Hz
34
32
UNIT
30
28
CEILING
1.5m
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MICROPHONE
72
Noise level at an echoic room (Low-High)
Model
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
PEAD-RP71EA
External static pressure
30Pa
36-40
36-40
38-44*
38-44*
37-4139-46*
-
37-41
* Optional motor
70Pa
Unit : dB(A)
130Pa
-
-
-
40-45*
PEAD-RP35EA2
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63125 250500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63125 250500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 30Pa)
(External static
pressure 30Pa)
High
Low
High
Low
NC60
NC50
NC40
NC30
NC20
NC60
NC50
NC40
NC30
NC20
PEAD-RP35EA2
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63125 250500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63125 250500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
(External static
pressure 70Pa)
High
Low
High
Low
NC60
NC50
NC40
NC30
NC20
NC60
NC50
NC40
NC30
NC20
73
1m
ceiling
1m
about 1.4m
MICROPHONE
PCA-RP50GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
NOTCH
High
Medium1
Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
42
40
38
37
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
unit
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
6312525050010002000 40008000
NOTCH
High
Medium1
Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
43
41
39
37
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PEA-RP71EA
90
80
70
60
50
40
30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
10
631252505001000 2000 4000 8000
SPL(dB)52LINE
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
55
UNIT
1m
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
External static
pressure 125Pa
74
SUZ-KA25VA
90
80
70
60
50
40
30
20
10
63125250500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
FAN SPEED
HEATING
47
48
Test conditions,
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OUTDOORUNIT
MICROPHONE
1m
High
Med.
COOLING
FUNCTION
SPL(dB(A))LINE
High
FAN SPEED
HEATING
53
55
90
80
70
60
50
40
30
20
10
63125250500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
SUZ-KA25VAH
SUZ-KA35VA
SUZ-KA35VAH
FAN SPEED
High
Med.
Test conditions,
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
Drain lift up mechanismPAC-SH20DM-EPCA-RP50,60GA(2)
MFZ-KA·VA
SEZ-KA·VA
PAC-SH21DM-EPCA-RP71GA
High-efficiency filterPAC-SE80KF-EPCA-RP50GA(2)
PAC-SE81KF-EPCA-RP60,71GA
Motor (for high external static pressure)PAC-SK005MT-FPEAD-RP71EA
Drain lift up mechanismPAC-KE03DM-FPEAD-RP·EA, EA2
Insulation kitPAC-SK010DKPEAD-RP·GA
PAC-SH65OF-E
High-efficiency filter element (PAC-SH53TM-E is needed.)
Flange for fresh air intake
PAC-SH59KF-E
Decoration panel with wireless remote controller
PLP-6BALM
PLA-RP·BA
Decoration panel with wired remote controller
PLP-6BAM
Automatic filter elevation panel
PLP-6BAJ
i-see sensor corner panel
PAC-SA1ME-E
Wireless signal receiver
PAR-SA9FA-E
Space panel
PAC-SH48AS-E
Air outlet shutter plate
PAC-SH51SP-E
Decoration panel
PLP-6BA
OPTIONAL PARTS
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2007 No.OCS03 REVISED EDITION-A PDF 7
Distributed in May 2006 No.OCS03 PDF 8
Made in Japan
New publication, effective May 2007
Specifications subject to change without notice.