Mitsubishi OCS03A TECHNICAL MANUAL

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
May 2007
No. OCS03
REVISED EDITION-A
TECHNICAL DATA BOOK
<Indoor unit> [Model names]
MFZ-KA·VA SLZ-KA·VA SLZ-KA·VAL SEZ-KC·VA SEZ-KA·VA PLA-RP·BA PLA-RP·AA PCA-RP·GA PCA-RP·GA2 PEAD-RP·EA PEAD-RP·EA2 PEAD-RP·GA PEA-RP·EA
R410A
INVERTER
Revision:
• PLA-RP·BA and PCA­RP50GA2 are added in REVISED EDITION-A.
Some descriptions have been modified.
Please void OCS03.
<Outdoor unit> [Model names]
SUZ-KA25/35/50/60/71VA SUZ-KA25/35VAH
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································12
4. WIRING DIAGRAM···································································28
5. REFRIGERANT SYSTEM DIAGRAM ······································42
6. PERFORMANCE CURVES······················································45
7. APPLICABLE EXTENSION PIPE FOR EACH MODEL··········49
9. NOISE CRITERION CURVES ··················································67
10. OPTIONAL PARTS ····················································Back Cover
kW Model
1-1. Indoor Unit
Model name Service Ref. Service
Manual No.
1-2. Outdoor Unit
Model name Service Ref.
For information on service, please refer to the service manual as follows.
Service Manual No.
SLZ-KA25/35/50VA SLZ-KA25/35/50VA.TH
OC320
SLZ-KA25/35/50VAL SLZ-KA25/35/50VAL.TH
SEZ-KA35/50/60/71VA SEZ-KA35/50/60/71VA.TH OC321
MFZ-KA25/35/50VA-E1 MFZ-KA25/35/50VA-E1 OB409
SEZ-KC25VA SEZ-KC25VA.W MEE04K350
MFZ-KA25/35/50VA-A1 MFZ-KA25/35/50VA-A1 OB410
OCH412 OCB412
OCH416 OCB416
PLA-RP35/50/60/71AA
PLA-RP35/50/60/71BA
PLA-RP35/50/60/71AA.UK
PLA-RP35/50/60/71BA.UK
PLA-RP35/50/60/71BA
OC335
PLA-RP35/50/60/71AA OC327
PCA-RP50/60/71GA PCA-RP50GA2
PCA-RP50/60/71GA OC328
PEAD-RP50/60/71EA PEAD-RP50/6071EA.UK PEAD-RP35EA2 PEAD-RP35EA2.UK
HWE05210
PEAD-RP60/71GA PEAD-RP60/71GA.UK HWE05060
PEA-RP71EA PEA-RP71EA.TH-A OC326
SUZ-KA25/35/50/60/71VA SUZ-KA25/35/50/60/71VA(1).TH
OC322
SUZ-KA25/35VAH SUZ-KA25/35VAH.TH
SUZ-KA25/35/50/60/71VA SUZ-KA25/35/50/60/71VA(1).TH-A OC323
1
REFERENCE SERVICE MANUAL
(Note) When you connect P series indoor units with SUZ, always make sure to follow the piping size of SUZ. Never use bigger sized pipings in order to ensure not only the system performance but also for your safety.
2
SPECIFICATIONS2
Model name
Indoor unit
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
Outdoor unit
SUZ-KA25VA(H) SUZ-KA35VA(H) SUZ-KA50VA
Cooling
Capacity
Btu/h 8,500 11,900 16,400
kW 2.5(0.9-3.4) 3.5(0.9-3.9) 4.8(0.9-5.4)
Total input
kW 0.58 1.09 1.55
EER
4.31 3.21 3.1
Energy label class
AAB
SHF
0.66 0.65 0.63
Heating
Capacity
Btu/h 11,600 13,600 20,500
kW 3.4(0.9-5.1) 4.0(0.9-6.2) 6.0(0.9-7.9)
Total input
kW 0.835 1.10 1.86
COP
4.07 3.64 3.23
Energy label class
AAC
Booster heater
kW - - -
Power supply
Phase
[ 111
Cycle
Hz 50 50 50
Voltage
V 230 230 230
Breaker size
A10 10 20
Indoor unit
Air flow at cooling
CMM 4.8 - 5.8 - 7.1 - 8.7 5.0 - 6.1 - 7.4 - 9.1 7.1 - 7.9 - 9.2 - 10.7
(Low-Medium-High-Super High)
CFM 170 - 205 - 250 - 310 180 - 215 - 260 - 320 250 - 280 - 325 - 380
Air flow at heating
CMM 5.0 - 6.2 - 7.6 - 9.1 5.2 - 6.2 - 7.8 - 9.5 7.4 - 8.8 - 9.8 - 11.8
(Low-Medium-High-Super High)
CFM 180 - 220 - 270 - 320 185 - 220 - 275 - 335 260 - 310 - 345 - 415
External static pressure
Pa 0 0 0
Sound level at cooling
dB(A) 22 - 27 - 32 - 37 23 - 28 - 33 - 38 32 - 35 - 39 - 43
(Low-Medium-High-Super High) Sound level at heating
dB(A) 22 - 27 - 32 - 37 25 - 28 - 33 - 38 32 - 35 - 39 - 44
(Low-Medium-High-Super High) External finish (Panel)
White Munsell 1.0Y 9.2/0.2
Dimension
W : mm 700
Unit (Panel)
D : mm 200
H : mm 600 W : inch 27 - 5/8 D : inch 7 - 7/8 H : inch 23 - 5/8
Weight
kg 14
Unit (Panel)
lbs 31
Outdoor unit
Air flow at cooling
CMM 34.3 33.4 27.5 - 49
(Low - High)
CFM 1,210 1,180 970 - 1,730
Air flow at heating
CMM 32.3 33.4 36.8 - 49
(Low - High)
CFM 1,140 1,180 1,300 - 1,730
Sound level at cooling
dB(A) 46 47 51 - 53
(Low - High) Sound level at heating
dB(A) 46 48 53 - 55
(Low - High) External finish
Ivory Munsell 3.0Y 7.8/1.1
Dimension
W : mm 800 800 840
D : mm 285 285 330
H : mm 550 550 850 W : inch 31 - 1/2 31 - 1/2 33 - 1/16 D : inch 11 - 1/4 11 - 1/4 13 H : inch 21 - 5/8 21 - 5/8 33 - 7/16
Weight kg 33 37 53
lbs 73 82 117
Refrigerant pipe size Gas side O.D. mm 9.52 9.52 12.7
inch 3/8 3/8 1/2
Liquid side . mm 6.35 6.35 6.35
inch 1/4 1/4 1/4
Refrigerant pipe length
Height difference
m
Max. 12 Max. 12 Max. 30
Length
m
Max. 20 Max. 20 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor: D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
32˚C D.B. , 23˚C W.B.
46˚C D.B. 46˚C D.B.43˚C D.B.
KA25, KA35VA
KA25, KA35VAH
KA50
Lower limit
21˚C D.B. , 15˚C W.B. -15˚C D.B.-10˚C D.B. -10˚C D.B.
Heating
Upper limit
27˚C D.B.
24˚C D.B. , 18˚C W.B.
Lower limit
20˚C D.B.
-10˚C D.B. ,-11˚C W.B.
-20˚C D.B. ,-21˚C W.B.
4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz
Single phase, 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
2-1. FLOOR STANDING TYPE
3
2-2. CEILING CASSETTE TYPE
Model name
Indoor unit
SLZ-KA25VA(L) SLZ-KA35VA(L) SLZ-KA50VA(L)
Outdoor unit
SUZ-KA25VA(H) SUZ-KA35VA(H) SUZ-KA50VA
Cooling
Capacity
Btu/h 8,500 11,900 15,700
kW 2.5(0.9 - 3.2) 3.5(1.0 - 3.9) 4.6(1.1 - 5.2)
Total input
kW 0.69 1.06 1.63
EER
3.62 3.30 2.82
Energy label class
AAC
SHF
0.86 0.77 0.68
Heating
Capacity
Btu/h 10,200 13,600 17,100
kW 3.0(0.9 - 4.5) 4.0(0.9 - 5.0) 5.0(0.9 - 6.5)
Total input
kW 0.83 1.10 1.55
COP
3.61 3.64 3.23
Energy label class
AAC
Booster heater
kW - - -
Power supply
Phase
[ 111
Cycle
Hz 50 50 50
Voltage
V 230 230 230
Breaker size
A10 10 20
Indoor unit
Air flow
CMM 8 - 9 - 10 8 - 9 - 11 8 - 9 - 11
(Low - Medium - High)
CFM 280 - 320 - 355 280 - 320 - 390 280 - 320 - 390
External static pressure
Pa 0 0 0
Sound level
dB(A) 28 - 31 - 37 29 - 33 - 38 30 - 34 - 39
(Low - Medium - High) External finish (Panel)
White Munsell 0.70Y 8.59/0.97
Dimension
W : mm 570(650)
Unit(Panel)
D : mm 570(650)
H : mm 208(20) W : inch 22 - 7/16(25 - 9/16) D : inch 22 - 7/16(25 - 9/16) H : inch 8-3/16(13/16)
Weight
kg 16.5(3)
Unit (Panel)
lbs 36(7)
Field drain pipe O.D.
mm 32
inch 1 - 1/4
Outdoor unit
Air flow at cooling
CMM 34.3 33.4 27.5 - 49
(Low - High)
CFM 1,210 1,180 970 - 1,730
Air flow at heating
CMM 32.3 33.4 36.8 - 49
(Low - High)
CFM 1,140 1,180 1,300 - 1,730
Sound level at cooling
dB(A) 46 47 51 - 53
(Low - High) Sound level at heating
dB(A) 46 48 53 - 55
(Low - High) External finish
Ivory Munsell 3.0Y 7.8/1.1
Dimension
W : mm 800 800 840
D : mm 285 285 330
H : mm 550 550 850 W : inch 31 - 1/2 31 - 1/2 33 - 1/16 D : inch 11 - 1/4 11 - 1/4 13 H : inch 21 - 5/8 21 - 5/8 33 - 7/16
Weight
kg 33 37 53
lbs 73 82 117
Refrigerant pipe size
Gas side O.D.
mm 9.52 9.52 12.7
inch 3/8 3/8 1/2
Liquid side O.D.
mm 6.35 6.35 6.35
inch 1/4 1/4 1/4
Refrigerant pipe length
Height difference
m Max. 12 Max. 12 Max. 30
Length
m Max. 20 Max. 20 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
32˚C D.B. , 23˚C W.B.
46˚C D.B. 46˚C D.B.43˚C D.B.
KA25, KA35VA
KA25, KA35VAH
KA50
Lower limit
21˚C D.B. , 15˚C W.B. -15˚C D.B.-10˚C D.B. -10˚C D.B.
Heating
Upper limit
27˚C D.B.
24˚C D.B. , 18˚C W.B.
Lower limit
20˚C D.B.
-10˚C D.B. ,-11˚C W.B.
-20˚C D.B. ,-21˚C W.B.
4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz
Single phase, 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
4
Model name Indoor unit PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA
Outdoor unit SUZ-KA35VA(H) SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Cooling Capacity Btu/h 11,900 17,100 19,400 24,200
kW 3.5(1.0 - 3.9) 5.0(1.1 - 5.6) 5.7(1.1 - 6.3) 7.1(0.9 - 8.1) Total input kW 1.09 1.78 1.94 2.53 EER 3.21 2.81 2.94 2.81 Energy label class A C C C SHF 0.84 0.81 0.76 0.73
Heating Capacity Btu/h 14,000 20,500 23,500 27,300
kW 4.1(0.9 - 5.0) 6.0(0.9 - 7.2) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) Total input kW 1.11 1.82 2.11 2.49 COP 3.69 3.30 3.27 3.21 Energy label class A C C C Booster heater kW - - - -
Power supply Phase [ 1111
Cycle Hz 50 50 50 50 Voltage V 230 230 230 230 Breaker size A 10 20 20 20
Indoor unit Air flow CMM 11 - 12 - 13 - 15 12 - 14 - 16 - 18 12 - 14 - 16 - 18 14 - 16 - 18 - 21
(Low-Medium2-Medium1-High)
CFM
390 - 425 - 460 - 530 425 - 495 - 565 - 635 425 - 495 - 565 - 635 495 - 565 - 635 - 740 External static pressure Pa 0 0 0 0 Sound level dB(A) 27 - 28 - 29 - 31 28 - 29 - 31 - 32 28 - 29 - 31 - 32 28 - 30 - 32 - 34 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950)
H : mm 258 (35)
W : inch 33 - 1/16 (37 - 3/8)
D : inch 33 - 1/16 (37 - 3/8)
H : inch 10 - 3/16 (1 - 3/8) Weight kg 23 (6) Unit (Panel) lbs 51 (13)
22 (6)
49 (13)
Field drain pipe O.D. mm 32
inch 1 - 1/4
Outdoor unit Air flow at cooling CMM 33.4 27.5 - 49 27.5 - 49 27.5 - 49
(Low - High) CFM 1,180 970 - 1,730 970 - 1,730 970 - 1,730 Air flow at heating CMM 33.4 36.8 - 49 36.8 - 49 36.8 - 49 (Low - High) CFM 1,180 1,300 - 1,730 1,300 - 1,730 1,300 - 1,730 Sound level at cooling dB(A) 47 51 - 53 51 - 53 51 - 53 (Low - High) Sound level at heating dB(A) 48 53 - 55 53 - 55 53 - 55 (Low - High) External finish Ivory Munsell 3.0Y 7.8/1.1 Dimension W : mm 800 840 840 840
D : mm 285 330 330 330
H : mm 550 850 850 850
W : inch 31 - 1/2 33 - 1/16 33 - 1/16 33 - 1/16
D : inch 11 - 1/4 13 13 13
H : inch 21 - 5/8 33 - 7/16 33 - 7/16 33 - 7/16 Weight kg 37 53 53 58
lbs 82 117 117 128
Refrigerant pipe size Gas side O.D. mm 9.52 12.7 15.88 15.88
inch 3/8 1/2 5/8 5/8
Liquid side O.D. mm 6.35 6.35 6.35 9.52
inch 1/4 1/4 1/4 3/8
Refrigerant pipe length Height difference m Max. 12 Max. 30 Max. 30 Max. 30
Length m Max. 20 Max. 30 Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit Upper limit
Heating
Lower limit
Indoor Outdoor
32˚C D.B. , 23˚C W.B. 21˚C D.B. , 15˚C W.B. -15˚C D.B. -10˚C D.B.-10˚C D.B.
27˚C D.B. 20˚C D.B.
KA35VA KA35VAH
46˚C D.B. 46˚C D.B.43˚C D.B.
-10˚C D.B. ,-11˚C W.B.
KA50, KA60, KA71
24˚C D.B. , 18˚C W.B.
5
3. Guaranteed voltage
4. Above data are based on the indicated voltage.
-20˚C D.B. ,-21˚C W.B.
198~264V, 50Hz
Indoor unit Single phase, 230V 50Hz Outdoor unit
Single phase, 230V 50Hz
Model name Indoor unit PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
Outdoor unit SUZ-KA35VA(H) SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Cooling Capacity Btu/h 11,900 17,100 19,400 24,200
kW 3.5(1.0 - 3.9) 5.0(1.1 - 5.6) 5.7(1.1 - 6.3) 7.1(0.9 - 8.1) Total input kW 1.09 1.78 1.94 2.53 EER 3.21 2.81 2.94 2.81 Energy label class A C C C SHF 0.88 0.86 0.83 0.77
Heating Capacity Btu/h 14,000 20,500 23,500 27,300
kW 4.1(0.9 - 5.0) 6.0(0.9 - 7.2) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) Total input kW 1.11 1.76 2.11 2.49 COP 3.69 3.41 3.27 3.21 Energy label class A B C C Booster heater kW - - - -
Power supply Phase [ 1111
Cycle Hz 50 50 50 50 Voltage V 230 230 230 130 Breaker size A 10 20 20 20
Indoor unit Air flow CMM 11 - 12 - 13 - 14 14 - 15 - 16 - 18 14 - 15 - 16 - 18 15 - 16 - 18 - 20
(Low-Medium2-Medium1-High)
CFM
390 - 425 - 460 - 495 495 - 530 - 565 - 635 495 - 530 - 565 - 635 530 - 565 - 635 - 705 External static pressure Pa 0 0 0 0 Sound level dB(A) 27 - 28 - 29 - 31 28 - 29 - 31 - 33 28 - 29 - 31 - 33 28 - 30 - 32 - 34 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33 - 1/16 (37 - 3/8)
D : inch 33 - 1/16 (37 - 3/8)
H : inch 10 - 3/16 (1 - 3/16) Weight kg 24 (5) Unit (Panel) lbs 53 (11) Field drain pipe I.D. mm 32
inch 1 - 1/4
Outdoor unit Air flow at cooling CMM 33.4 27.5 - 49 27.5 - 49 27.5 - 49
(Low - High) CFM 1,180 970 - 1,730 970 - 1,730 970 - 1,730 Air flow at heating CMM 33.4 36.8 - 49 36.8 - 49 36.8 - 49 (Low - High) CFM 1,180 1,300 - 1,730 1,300 - 1,730 1,300 - 1,730 Sound level at cooling dB(A) 47 51 - 53 51 - 53 51 - 53 (Low - High) Sound level at heating dB(A) 48 53 - 55 53 - 55 53 - 55 (Low - High) External finish Ivory Munsell 3.0Y 7.8/1.1 Dimension W : mm 800 840 840 840
D : mm 285 330 330 330
H : mm 550 850 850 850
W : inch 31 - 1/2 33 - 1/16 33 - 1/16 33 - 1/16
D : inch 11 - 1/4 13 13 13
H : inch 21 - 5/8 33 - 7/16 33 - 7/16 33 - 7/16 Weight kg 37 53 53 58
lbs 82 117 117 128
Refrigerant pipe size Gas side O.D. mm 9.52 12.7 15.88 15.88
inch 3/8 1/2 5/8 5/8
Liquid side O.D. mm 6.35 6.35 6.35 9.52
inch 1/4 1/4 1/4 3/8
Refrigerant pipe length Height difference m Max. 12 Max. 30 Max. 30 Max. 30
Length m Max. 20 Max. 30 Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor Outdoor
32˚C D.B. , 23˚C W.B. 21˚C D.B. , 15˚C W.B. -15˚C D.B. -10˚C D.B.-10˚C D.B.
27˚C D.B. 20˚C D.B.
KA35VA KA35VAH
46˚C D.B. 46˚C D.B.43˚C D.B.
-10˚C D.B. ,-11˚C W.B.
KA50, KA60, KA71
24˚C D.B. , 18˚C W.B.
-20˚C D.B. ,-21˚C W.B.
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase, 230V 50Hz Outdoor unit
Single phase, 230V 50Hz
6
2-3. CEILING-SUSPENDED TYPE
Model name Indoor unit PCA-RP50GA PCA-RP60GA PCA-RP71GA
Outdoor unit SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Cooling Capacity Btu/h 16,000 18,800 24,200
kW 4.7(1.1 - 5.4) 5.5(1.1 - 6.3) 7.1(0.9 - 8.1)
Total input
kW 1.80 1.92 2.53
EER 2.61 2.86 2.81 Energy label class
DCC
SHF 0.70 0.79 0.71
Heating Capacity Btu/h 18,800 23,500 27,300
kW 5.5(0.9 - 6.6) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) Total input kW 1.92 2.05 2.49 COP 2.86 3.37 3.21
Energy label class
DCC
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50 Voltage V 230 Breaker size A 20
Indoor unit Air flow CMM 10 - 11 - 12 - 13 14 - 15 - 16 - 18
(Low-Medium2-Medium1-High)
CFM
355 - 390 - 425 - 460
495 - 530 - 565 - 635 External static pressure Pa 0 0 Sound level dB(A) 37 - 38 - 40 - 42 37 - 39 - 41 - 43
(Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1000 1310
D : mm 680 H : mm 210
W : inch 39 - 3/8 51 - 9/16
D : inch 26 - 3/4 H : inch 8 - 1/4
Weight
kg
27 34
lbs 60 75
Field
drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow at cooling CMM 27.5 - 49 27.5 - 49 27.5 - 49
(Low - High)
CFM 970 - 1,730 970 - 1,730 970 - 1,730
Air flow at heating CMM 36.8 - 49 36.8 - 49
27.5 - 49
970 - 1,730
36.8 - 49 36.8 - 49
(Low - High)
CFM 1,300 - 1,730 1,300 - 1,730 1,300 - 1,730
Sound level at cooling dB(A) 51 - 53 51 - 53 51 - 53 (Low - High)
Sound level at heating dB(A) 53 - 55 53 - 55
51 - 53
53 - 55 53 - 55
(Low - High) External finish
Ivory Munsell 3.0Y 7.8/1.1
Dimension W : mm 840 840 840
D : mm 330 330 330 H : mm 850 850 850
W : inch 33 - 1/16 33 - 1/16 33 - 1/16
D : inch 13 13 13 H : inch 33 - 7/16 33 - 7/16 33 - 7/16
Weight
kg
53 53 58
lbs 117 117 128
Refrigerant pipe size Gas side O.D. mm 12.7 15.88 15.88
inch 1/2 5/8 5/8
Liquid side O.D. mm 6.35 6.35 9.52
inch 1/4 1/4 3/8
Refrigerant pipe length
Height difference
m Max. 30 Max. 30 Max. 30
Length
m Max. 30 Max. 30 Max. 30
PCA-RP50GA2
SUZ-KA50VA
17,000
5.0(1.1 - 5.6)
1.78
2.81 C
0.81
20,500
6.0(0.9 - 7.2)
1.76
3.41 B
-
970 - 1,730
840 330 850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4 Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32˚C, W.B. 23˚C
D.B. 43˚C
Lower limit
D.B. 21˚C, W.B. 15˚C D.B. -15˚C
Heating
Upper limit
D.B. 27˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 20˚C
D.B. -10˚C, W.B. -11˚C
4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz
Single phase, 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
7
2-4. CEILING-CONCEALED TYPE
Model name Indoor unit SEZ-KC25VA SEZ-KA35VA SEZ-KA50VA SEZ-KA60VA SEZ-KA71VA
Cooling Capacity Btu/h 8,500 11,900 17,100 18,800 24,200
Heating Capacity Btu/h 10,200 13,600 20,100 23,500 27,600
Power supply Phase [ 11111
Indoor unit Air flow CMM 4.8 - 7.9 10 - 13 12 - 17 12 - 20 12 - 20
Outdoor unit SUZ-KA25VA(H)SUZ-KA35VA(H)SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
kW 2.5(0.9 - 3.2
)
3.5(1.0 - 3.9
)
5.0(1.1 - 5.6
)
5.5(1.1 - 6.3
)
7.1(0.9 - 8.3 Total input kW 0.73 1.06 1.78 1.96 2.46 EER 3.42 3.30 2.81 2.81 2.89 Energy label class A A C C C SHF 0.74 0.77 0.75 0.75 0.74
kW 3.0(0.9 - 4.5
)
4.0(0.9 - 5.0
)
5.9(1.1 - 7.2
)
6.9(0.9 - 8.0
)
8.1(0.9 - 10.4 Total input kW 0.83 1.10 1.84 2.45 2.36 COP 3.61 3.64 3.21 2.82 3.43 Energy label class A A C D B Booster heater kW - - - - -
Cycle Hz 50 50 50 50 50 Voltage V 230 230 230 230 230 Breaker size A 10 10 20 20 20
(
Low - High External static pressure Sound level dB(A (
Low - High
)
CFM 170 - 280 355 - 460 425 - 600 425 - 705 425 - 705
Pa Std:5 Max:5 Std:30 Max:50 Std:30 Max:50 Std:30 Max:50 Std:30 Max:50
)
25 - 36 30 - 35 31 - 39 32 - 43 32 - 43
) External finish Galvanized sheets Dimension W : mm 790 1100
D : mm 550 700 H : mm 225 270
W : inch 31 - 1/8 43 - 5/16
D : inch 21 - 5/8 27 - 9/16 H : inch 8 - 7/8 10 - 5/8
Weight kg 19 33.5 35
lbs 42 74 77
Unit drain pipe R1(External thread
)
R1(External thread
)
)
)
Outdoor unit Air flow at cooling CMM 34.3 33.4 27.5 - 49 27.5 - 49 27.5 - 49
(
Low - High
)
CFM 1,210 1,180 970 - 1,730 970 - 1,730 970 - 1,730 Air flow at heating CMM 32.3 33.4 36.8 - 49 36.8 - 49 36.8 - 49 (
Low - High Sound level at cooling dB(A (
Low - High Sound level at heating dB(A (
Low - High
)
CFM 1,140 1,180 1,300 - 1,730 1.300 - 1,730 1,300 - 1,730
)
46 47 51 - 53 51 - 53 51 - 53
)
)
46 48 53 - 55 53 - 55 53 - 55
) External finish Ivory Munsell 3.0Y 7.8/1.1 Dimension W : mm 800 800 840 840 840
D : mm 285 285 330 330 330 H : mm 550 550 850 850 850
W : inch 31 - 1/2 31 - 1/2 33 - 1/16 33 - 1/16 33 - 1/16
D : inch 11 - 1/4 11 - 1/4 13 13 13 H : inch 21 - 5/8 21 - 5/8 33 - 7/16 33 - 7/16 33 - 7/16
Weight kg 33 37 53 53 58
lbs 73 82 117 117 128
Refrigerant pipe size Gas side O.D. mm 9.52 9.52 12.7 15.88 15.88
inch 3/8 3/8 1/2 5/8 5/8
Liquid side O.D. mm 6.35 6.35 6.35 6.35 9.52
inch 1/4 1/4 1/4 1/4 3/8
Refrigerant pipe length Height difference m Max. 12 Max. 12 Max. 30 Max. 30 Max. 30
Length m Max. 20 Max. 20 Max. 30 Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Heating
Upper limit Lower limit
Indoor Outdoor
32˚C D.B. , 23˚C W.B. 21˚C D.B. , 15˚C W.B. -15˚C D.B.
27˚C D.B. 20˚C D.B.
KA25, KA35VA
46˚C D.B. 46˚C D.B.
-10˚C D.B. -10˚C D.B.
-10˚C D.B. ,-11˚C W.B.
KA50, KA60, KA71
43˚C D.B.
24˚C D.B. , 18˚C W.B.
KA25, KA35VAH
-20˚C D.B. ,-21˚C W.B.
3. Guaranteed voltage
4. Above data are based on the indicated voltage.
198~264V, 50Hz
Indoor unit Single phase, 230V 50Hz Outdoor unit
Single phase, 230V 50Hz
8
Model name Indoor unit PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
Outdoor unit SUZ-KA35VA(H
)
SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Cooling Capacity Btu/h 12,300 16,700 20,500 24,200
kW 3.6(1.0 - 3.9
)
4.9(1.1 - 5.6
)
6.0(1.1 - 6.3
)
7.1(0.9 - 8.1
) Total input kW 1.12 1.74 2.05 2.53 EER 3.21 2.82 2.93 2.81 Energy label class A C C C SHF 0.90 0.79 0.80 0.81
Heating Capacity Btu/h 14,000 20,100 23,900 27,300
kW 4.1(0.9 - 5.0
)
5.9(0.9 - 7.2
)
7.0(0.9 - 8.0
)
8.0(0.9 - 10.2
) Total input kW 1.13 1.69 2.07 2.49 COP 3.63 3.49 3.38 3.21 Energy label class A B C C Booster heater kW - - - -
Power supply Phase [ 1111
Cycle Hz 50 50 50 50 Voltage V 230 230 230 230 Breaker size A 10 20 20 20
Indoor unit Air flow CMM 13.5 - 17 17 - 21 20 - 25
(
Low - High External static pressure Pa 30(70 Sound level dB(A (
Low - High
)
)(
CFM 476 - 600 600 - 741 706 - 883
)
)
36 - 40 37 - 41 37 - 41
70Pa : 38 - 44
)(
30(70
70Pa : 39 - 46
)
)(
)
70(130
130Pa : 40 - 45
) External finish Galvanized sheets Galvanized sheets Dimension W : mm 935 1175
D : mm 700 700 740 H : mm 295 295 325
W : inch 36 - 13/16 46 - 1/8
D : inch 27 - 5/8 27 - 5/8 29 - 1/8 H : inch 11 - 5/8 11 - 5/8 12 - 13/16
Weight kg 33 35 42 44
lbs 73 77 92 97
Unit drain pipe R1(External thread
)
R1(External thread
)
Outdoor unit Air flow at cooling CMM 33.4 27.5 - 49 27.5 - 49 27.5 - 49
(
Low - High
)
CFM 1,180 970 - 1,730 970 - 1,730 970 - 1,730 Air flow at heating CMM 33.4 36.8 - 49 36.8 - 49 36.8 - 49 (
Low - High Sound level at cooling dB(A (
Low - High Sound level at heating dB(A (
Low - High
)
CFM 1,180 1,300 - 1,730 1,300 - 1,730 1,300 - 1,730
)
47 51 - 53 51 - 53 51 - 53
)
)
48 53 - 55 53 - 55 53 - 55
) External finish Ivory Munsell 3.0Y 7.8/1.1 Dimension W : mm 800 840 840 840
D : mm 285 330 330 330 H : mm 550 850 850 850
W : inch 31 - 1/2 33 - 1/16 33 - 1/16 33 - 1/16
D : inch 11 - 1/4 13 13 13 H : inch 21 - 5/8 33 - 7/16 33 - 7/16 33 - 7/16
Weight kg 37 53 53 58
lbs 82 117 117 128
Refrigerant pipe size Gas side O.D. mm 9.52 12.7 15.88 15.88
inch 3/8 1/2 5/8 5/8
Liquid side O.D. mm 6.35 6.35 6.35 9.52
inch 1/4 1/4 1/4 3/8
Refrigerant pipe length Height difference m Max. 12 Max. 30 Max. 30 Max. 30
Length m Max. 20 Max. 30 Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor Outdoor
32˚C D.B. , 23˚C W.B. 21˚C D.B. , 15˚C W.B. -15˚C D.B.
27˚C D.B. 20˚C D.B.
KA25, KA35VA
46˚C D.B. 46˚C D.B.
-10˚C D.B. -10˚C D.B.
-10˚C D.B. ,-11˚C W.B.
KA50, KA60, KA71
43˚C D.B.
24˚C D.B. , 18˚C W.B.
KA25, KA35VAH
-20˚C D.B. ,-21˚C W.B.
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase, 230V 50Hz Outdoor unit
Single phase, 230V 50Hz
9
Model name Indoor unit PEAD-RP60GA PEAD-RP71GA
Outdoor unit SUZ-KA60VA SUZ-KA71VA
Cooling Capacity Btu/h 19,400 24,200
kW 5.7(1.1 - 6.3) 7.1(0.9 - 8.1) Total input kW 2.03 2.53 EER 2.81 2.81 Energy label class C C SHF 0.82 0.81
Heating Capacity Btu/h 23,900 27,300
kW 7.0(0.9 - 8.0) 8.0(0.9 - 10.2) Total input kW 2.05 2.49 COP 3.41 3.21 Energy label class B C Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50 Voltage V 230 Breaker size A 20
Indoor unit Air flow CMM 16.5 - 21 20 - 25
(Low - High) CFM 582 - 741 706 - 883 External static pressure Pa 10/50/70 Sound level dB(A)
33 - 37/35 - 40/36 - 42 35 - 38/37 - 41/37 - 43 (Low - High) (10/50/70Pa) (10/50/70Pa) External finish Galvanized sheets Dimension W : mm 1171
D : mm 740
H : mm 275 W : inch 46 - 1/8 D : inch 29 - 1/8 H : inch 10 - 13/16
Weight kg 42
lbs 93
Unit drain pipe O.D. mm 32
inch 1 - 1/4
Outdoor unit Air flow at cooling CMM 27.5 - 49 27.5 - 49
(Low - High) CFM 970 - 1,730 970 - 1,730 Air flow at heating CMM 36.8 - 49 36.8 - 49 (Low - High) CFM 1,300 - 1,730 1,300 - 1,730 Sound level at cooling dB(A) 51 - 53 51 - 53 (Low - High) Sound level at heating dB(A) 53 - 55 53 - 55 (Low - High) External finish Ivory Munsell 3.0Y 7.8/1.1 Dimension W : mm 840 840
D : mm 330 330
H : mm 850 850 W : inch 33 - 1/16 33 - 1/16 D : inch 13 13 H : inch 33 - 7/16 33 - 7/16
Weight kg 53 58
lbs 117 128
Refrigerant pipe size Gas side O.D. mm 15.88 15.88
inch 5/8 5/8
Liquid side O.D. mm 6.35 9.52
inch 1/4 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 30 Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor Outdoor
32˚C D.B. , 23˚C W.B. 21˚C D.B. , 15˚C W.B. -15˚C D.B.
27˚C D.B. 20˚C D.B.
KA60, KA71
43˚C D.B.
24˚C D.B. , 18˚C W.B.
-10˚C D.B. ,-11˚C W.B.
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase, 230V 50Hz Outdoor unit
Single phase, 230V 50Hz
10
Model name Indoor unit PEA-RP71EA
Outdoor unit SUZ-KA71VA
Cooling Capacity Btu/h 23,500
kW 6.9 Total input kW 2.90 EER 2.38 SHF 0.84
Heating Capacity Btu/h 27,300
kW 8.0 Total input kW 2.49 COP 3.21 Booster heater kW -
Power supply Phase [ 1
Cycle Hz 50 Voltage V 230 Breaker size A 20
Indoor unit Air flow CMM 22 - 27
(Low - High) R/s 367 - 450 External static pressure Pa 125 Sound level dB(A) 52 - 55 (Low - High) External finish Galvanized sheets Dimension W : mm 785
D : mm 690 H : mm 428
W : inch 31
D : inch 27 - 1/16 H : inch 16 - 7/8
Weight kg 46
lbs 101
Unit drain pipe R1(External therad)
Outdoor unit Air flow at cooling CMM 27.5 - 49
(Low - High) CFM 970 - 1,730 Air flow at heating CMM 36.8 - 49 (Low - High) CFM 1,300 - 1,730 Sound level at cooling dB(A) 51 - 53 (Low - High) Sound level at heating dB(A) 53 - 55 (Low - High) External finish
Ivory Munsell 3.0Y 7.8/1.1
Dimension W : mm 840
D : mm 330 H : mm 850
W : inch 33 - 1/16
D : inch 13 H : inch 33 - 7/16
Weight kg 58
lbs 128
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max.
30
Length m Max. 30
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
32˚C D.B. , 23˚C W.B.
43˚C D.B.
KA71
Lower limit
21˚C D.B. , 15˚C W.B. -15˚C D.B.
Heating
Upper limit
27˚C D.B.
24˚C D.B. , 18˚C W.B.
Lower limit
20˚C D.B.
-10˚C D.B. ,-11˚C W.B.
4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz
Single phase, 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
11
OUTLINES AND DIMENSIONS3
INDOOR UNIT
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
125
60
12
19
60
700
More than
100mm
607
46.5 46.5
More than 100mm
54 508 137
110
More than 100mm
45
35
600
Air out
Air out
Air in
drain
11
123
Unit : mm
20012
118
96
12
128
12
Gas pipe 25, 35:[9.52(flared)3/8" 50:[12.7(flared)1/2"
Liquid pipe [6.35(flared)1/4
6019
60
125
165
205
4-
[6 Hole
Installation plate
Indoor unit
60
363
454155
337 337
147
72 60 80
131131
7
333210
593
12
SLZ-KA25VAL
SLZ-KA50VA(L)
SLZ-KA35VA(L)
SLZ-KA25VA(L)
Brand label
(Case of Wired remote controller)
Terminal block
Terminal block
87
Suspension bolt
M10 or 3/8
(procure locally)
1/4"F
flared connection
{ 6.35mm
1/4"F
flared connection
{ 6.35mm
{ 9.52mm
flared connection
3/8"F
1/2"F
flared connection
Refrigerent pipe (liquid)
Refrigerent pipe (gas)
Models
{ 6.35mm
flared connection
1/4"F
Refrigerent pipe
(liquid)
Refrigerent pipe
(gas)
{ 12.7mm
{ 9.52mm
flared connection
3/8"F
15~37 15~37
576~620
570
530
Grille
Fresh air
intake
Drain pipe
VP-25 connection
(O.D. { 32)
Vane motor
Drain hole
V/M
Air intake grille
55 35
35 55
Auto vane
Grille
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
301
301
Emergency operation switch(cooling)
Emergency operation switch(heating)
Operation lamp
DEFROST/STAND BY lamp
(WIRELESS PANEL)
Receiver
Detail drawing of fresh air intake
Ceiling surface
Cut out hole
{ 73.4
Burring hole
3- { 2.8 hole
{ 100
118
25
120°
120°
377
377
650
650
Suspension bolt
lower edge
230
18248
Wiring entry
Ceiling surface
235
208
27
+5
0
193
20
93
38~58
66121
17 202
56 57
31
Ceiling hole
Suspension bolt pitch
15~37 15~37576~620
420
570 335
199
352
335
Suspension bolt
pitch
Ceiling hole
V/M
V/M
V/M
SLZ-KA35VAL SLZ-KA50VAL SLZ-KA25VA SLZ-KA35VA SLZ-KA50VA
Unit : mm
13
SEZ-KC25VA
Make the access door at the appointed position properly
for service maintenance.
Ceiling surfaceAccess door
Required space for service and maintenance
Lifting plate
(4-14o30)
Air filter
80
Control box
Terminal bed
(Power source)
Bottom plate
23 664(Lifting bolt pitch)
710
The part air intake duct is attached.(w3)
(When the air intake duct is used)
610
50
150
790
582
204.5
42.5
30
225(w2)
15
148
13.55050
510
14127
56.5
(52)
(57)
129
55301 301
189
Detailed chart around the air intake duct flange(w3)
(Duct and flange should be supplied in the field.)
550(w1)
More than 20mm
More than 20mm
6- [3hole
55
50X11=550
16
2X12- [ 3hole
14
459(Lifting bolt pitch)
15
113
Air outlet
Air inlet
450
50~150
300
450
2X3- [3hole
25
500
50~150
Note 1. Use M10 screw for the lifting bolt (field supply).
2. Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.
3. The direction of air intake can be changed from the bottom to
the rear by attaching the bottom plate to the air intake side.
4. Drain Pan is changeable from right and left.
5. The dimension is changed, in case the optional long-life filter
is attached.
Rear Air-Intake spec. :Depth is increased by 30mm(w1)
Bottom Air-Intake spec. :Height is increased by 30mm(w2)
Refrigerant piping flare connection
(gas [9.52 copper tube):LP ········1
Refrigerant piping flare connection
(liquid [6.35 copper tube):HP ········2
Drain piping connection R1 (External thread) ········3
1
2
3
Unit : mm
14
SEZ-KA35VA
(10) 50
50
880
7o100=700
100
40
9 o 2-{2.9 holes
1000
50
38
60
680
350
Suspension
bolt pitch
In case of bottom side suction, mount the PLATE (A) on the rear side.
Air inlet (rear side) dimensions
240
1016
42
930
back side or bottom side.
29
955
7o100=700
100
77.5
12012.5
(Inlet size)
24-
{2.9 holes
50
27
Air inlet (rear side)
Air outlet duct flange
120
12.5 240
(It is necessary to maintain a working service area from the ceiling.)
150
32.5
25
(10) 50
77
600
700
Access door
Service space
Air outlet
Suspension bolt pitch
1070
(Suspension bolt pitch)
Electrical parts box
(1070)
20 or more30
20
PLATE (B)o2
After installation, remove the transportation support PLATE (B).
25
(Inlet size)
215
450150
Electrical parts box
w Select the either
SEZ-KA60VA
SEZ-KA50VA
Terminal block
3/8"F
flared connection
{9.52mm
{6.35mm
flared connection 1/4"F
Air outlet duct flange
51
25
930
(Inlet size)
39
955
7o100=700
100
77.5
(Inlet size)
215
Air inlet (bottom side) dimensions
24-{2.9 holes
flared connection
{6.35mm
Electrical parts box
2
o2-{2.9
holes
flared connection
{15.88mm
5/8"F
flared connection 1/2"F
{12.7mm
Refrigerent pipe (gas)
Refrigerent pipe (liquid)
1/4"F
flared connection
{6.35mm
SEZ-KA35VA
Models
Wiring entry
Refrigerent pipe (liquid)
Refrigerent pipe (gas)
Drain plug R1 (male)
108
94 80
25
350
1/4"F
SEZ-KA71VA
flared connection
{9.52mm
flared connection 5/8"F
{15.88mm
3/8"F
w Select the either back side or bottom side.
Air inlet (bottom side)
100
75 170
Suspension bolt M10 or 3/8 (procure locally)
1100
270
Access door
PLATE (A)
SEZ-KA50VA SEZ-KA60VA SEZ-KA71VA
Unit : mm
15
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA Unit : mm
Branch duct hole
840
Suspension bolt M10 or W3/8
Suspension bolt lower edge
Air intake grille
Ceiling
Grille
1500mm or more
20~45
Fresh air intake hole
160
150
C
90
1
2
170
140
w
w
500
950
8336
Indoor unit
Obstacle
D
50~70
w
Control wire entry
Air outlet hole
M
1000mm
or more
Ceiling hole
Suspension bolt pitch
160
Remote controller terminal block
Indoor unit/Outdoor connecting terminal
Indoor power supply terminal block(Option part)
187.5
Power supply wire, Indoor unit/Outdoor unit connecting wire entry
Air intake hole
M
Air outlet hole
3000mm or more
Floor
860~910
810
840
597
500
950
37728460
M
Indoor unit
20~45
24
160
105
w
Ceiling
Grille
Drain hole Drain pump clean hole and Drain emergency drainage hole
M
597
Vane motor
83 36
1800mm or more
from floor
For high attachment
20~45
(7.5)(7.5)
+35
620
605
- 5
Suspension bolt pitch
160
Drain pipe connected to VP-25
A
190
156
w
w
0
+5
17
Branch duct hole
860~910
Ceiling hole
Burring hole pitch
Detail drawing of fresh air intake hole
20~45
Connected the attached
()
flexible pipe or socket.
Keep approximately 10 to 15mm space between unit ceiling and ceiling slab.
B35
w
In case of standard grille : PLP-6BA / PLP-6BAMD
158
w
In case of Auto-Grille : PLP-6BAJ In case of wireless remote controller : PLP-6BALM
Auto vane (Air outlet)
Air intake hole
Note : 1. Please choose the Grille from a standard grille, Auto-Grille.
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA
Emergency operation switch<Cooling>and Emergency Up/Down switch<Up>
Emergency switch<Heating>and Emergency Up/Down switch<Down>
Receiver
2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE). Drain pump is included. Max. liftng height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/Wear dew.)
8. As for necessary installation/service space, please refer to the under at figure.
Models
DEFROST/STAND BY lamp
Operation lamp
Refrigerant pipe
···[6.35 Flared connection
···1/4"F Refrigerant pipe
[6.35 Flared connection 1/4"F
Refrigerant pipe
···[9.52 Flared connection
···3/8"F
70°
[175
Burring hole
3-[2.8
Refrigerant pipe
···[12.7 Flared connection
··1/2"F
Refrigerant pipe
···[15.88 Flared connection
···5/8"F
90 100 100 90
350
120
°
°
120
L.L Filter
AB12 CE
241 258
Detail connecting of branch duct(Both aspects)
Cut out hole
130
100
155
167
ww
14-[2.8
Burring hole
[150
Cut out hole
Burring hole pitch
[125
Cut out hole
[100
Ceiling
Auto Grille Air intake grille up/down discharge
Ceiling
Max. 4.0m
Air intake grille
D
80
74
400
87
77
85
16
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA Unit : mm
90
100 100 90
_
70
{175
3 - {2.8 Burring hole
158
350
Detail drawing of fresh air intake
120
_
Branch duct hole (Cut out hole)
{150
{125
Burring hole pitch
120_
{100 (Cut out hole)
Ceiling surface
100
14 - {2.8 Burring hole
130
167
155
Suspension bolt lower edge
Fresh air intake
159192
Branch duct hole
840
89
98
Suspension bolt M10 or W3/8
1
2
170
140
C
50 - 70
Power line entry
Ceiling hole
860 - 910
810
Suspension bolt pitch
159
Terminal block
197 159
840
Feeding hole
(Drain pump)
Control wire entry
37428660
20 - 4520 - 45
16
Drain pipe VP-25connection (O.D.{32)
105
Ceiling surface
605
860 - 91020 - 45 20 - 45
Ceiling hole
Suspension bolt pitch
159
A
B
190
0
+5
30
17
Branch duct hole
135
0
+5
High efficiency filter & Fresh air intake casement (option)
A
(WIRELESS PANEL)
Emergency operation switch (cooling)
Emergency operation switch (heating)
Receiver
Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size
1 LIQUID SIDE
DEFROST/STAND BY lamp
Operation lamp
RP35, 50
RP60 RP71
[6.35 [6.35
17
(Unit : mm) (Unit : mm)
[9.52 [9.52 [9.52
2 GAS SIDE
[12.7
[15.88 [15.88 [15.88
: Factory flare nut attachment to the heat-exchanger.
950
51 77
Air intake grille
A
411
Air outlet hole
Models
PLA-RP35,50AA PLA-RP60,71AA
M
577
Air intake hole
M
411
Air outlet hole
950
241A258B80
Grille
Drain hole
M
M
77 51
C
Auto vane
577
Air intake hole
Vane motor
17
PCA-RP50GA Unit : mm
180
210
157
15
85
182 liquid 201 gas 241 (Drainage)
Air intake
918
161 90
254
680
506 56
Electrical box
226
70
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
525
928
352
263
171
138
86
46 175 1
131
38
38
79
161
32
179
42
6~7
Ceiling
Electrical box
[Front view]
When electrical box is pulled down
3
2
8
5
1
4
[15.88
[12.7
[6.35
Available pipe size
[9.52
4 GAS SIDE
5 LIQUID SIDE
RP50
Use the current nuts meeting the pipe size of the outdoor unit.
: Factory flare nut attachment to the heat-exchanger.
(Unit : mm)
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
18
PCA-RP50GA2w
161 90
254
680
506 56
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
Air intake
85
182 201 241
15
157
(liquid) (5/8F gas) (Drainage)
7
2
Electrical box
70
226
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
[ Front view ]
Ceiling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1 46
: Factory flare nut attachment to the heat-exchanger.
4 GAS SIDE
5 LIQUID SIDE
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP71RP60
[6.35 [9.52
[15.88
[9.52
[15.88
(Unit : mm)
[15.88
[12.7
[6.35 [9.52
RP50
PCA-RP60GA PCA-RP71GA Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping.
1 Drainage pipe connection (26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 3 Knock out hole for left drain-piping arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 5 Refrigerant-pipe connection (liquid pipe side/flared connection) 6 Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement
19
PEAD-RP35EA2 Unit : mm
2
1
3 4 5 6 7
Refrigerant piping flare connection (liquid [ F copper tube):HP Refrigerant piping flare connection (gas [G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP-25(I.D.
[
32)
Filter
R407C Outdoor unit : 9.52
F
R410A Outdoor unit : 6.35 w
R407C Outdoor unit : 9.52 w
Outdoor unit (SUZ) : 6.35
EDCBA
804830
-
305772
Model
RP60
R407C Outdoor unit : 15.88
G
R410A Outdoor unit : 12.7 w
15.88
104410702902801012
RP35,50
w Setting at shipment
2
1
3
4
Air inlet
Air outlet
Access door
55
50~150
81
197
Service space:500 or more
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
5
6
75
44
18
365~465
B 81
10
56 355
7
159
243
Air outlet
Air inlet
7
Lifting bolt hole
(14×22)
10- [3 (RP35,50) 12-
[
3 (RP60)
In case of rear inlet
In case of bottom inlet
10- [3 (RP35,50) 12-
[
3 (RP60)
D
30
C
10
81BC
A
450
450
10- [3 (RP35,50) 12-
[
3 (RP60)
176
40
288
256
3.5
3.5
10
109
179
10
35
24
30640
30
21
277
80 45
282
13
13E
A
61 227
29
85
40
176
10
15
3.5 256
BC 81
10
81
A
Set
(Unit : mm)
15.8810441070290
FEDCBA
2801012
Model RP71
w
Setting at shipment
(Unit : mm)
7
44
243
308
323
75
6
5
13
Refrigerant piping flare connection (liquid [9.52 copper tube):HP Refrigerant piping flare connection (gas [F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP25(I.D.[32) Filter
Service space:500 or more
81
365~465
197
81
50~150
55
29
Access door
Air outlet
Air inlet
4
3
1
2
7
6
5
4
3
2
1
113
307
122
12-[3
(14x22)
Lifting bolt hole
45
Set
210
12-[3
450
450
140
282
680
3.5
3.5
30
319
261
181
40
30
A C B
81
10
375
10
80
C B 81 A E 13
30D
20
35
30
1053 169
Keep duct-work length 850mm or more. Be sure to apply the air filter
near the air inlet grille.
PEAD-RP50EA PEAD-RP60EA
PEAD-RP71EA
20
PEAD-RP60GA Unit : mm
Model A B C D E
7 7
8
9.52 15.88
15.88
(Unit : mm)
8
F
GHJ RP60 RP71
1125 1125
1090 1090
1050 1050
1012 1012
840 840
Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 w
w Setting at shipment
PEAD-RP71GA
21
50
55
530
690
(130)
22.5
4070
105 510 35
40 40
650
15
15
730
155 155155
14 220 120
3.2
300242
2656075
35
45
20 345
11
11
672
22.5
20 20690
15
2512512525
100
600
70
(530)
300
900
(10)
25
562
21
(10)381
858525
15
70
11
14514524.5
33920
418
90
200 200
250 175
Terminal block
4-12 30 oblong Suspension bolt holes
Air intake
Air outlet
Service space (opening) in the ceiling
Heat insulator t10
(Drainage pan)
Room temperature thermistor
Drainage pan connection R1
Wiring entry(2-[22holes)
Refrigerant-pipe flared connection [15.88(5/8)
Refrigerant-pipe flared connection [9.52(3/8)
Electrical parts box
Service panel
(Condenser/evaporator temperature thermistor)
Service panel (Room temperature thermistor)
Air intake
Air intake duct flange
14-[2.9 holes For air intake duct connection
Heat insulator t10
Air outlet duct flange
Air outlet
(Drainage pan)
12-[2.9 holes For air outlet duct connection
Mounting plate
PEA-RP71EA Unit : mm
22
OUTDOOR UNIT
SUZ-KA25VA SUZ-KA25VAH SUZ-KA35VA SUZ-KA35VAH
400
Air in
44
Air in
285
344.5
Drain hole [42 (SUZ-KA25/KA35VA) Drain hole [33 (SUZ-KA25/KA35VAH)
304~325
installation
Bolt pitch for
Unit: mm
2 holes 10X21
22.3
Handle
550
280
10
150
REQUIRED SPACE
Air out
302.5 500 Bolt pitch for installation
800
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
40
69
17.5 23
164.5
99.5 Service port
Service panel
170.5
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
-
35
43-
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
100mm or more
Open two sides of left, right, or rear side.
100mm or more
350mm or more
200mm or more
23
30
-
35-
155
90
198
40
515
299
66
34
51
330
360
850
430
500
80
121
840
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
Open as a rule 500mm or more if the back, both sides and top are open
350mm or more
100mm or more
Service panel
Gas refrigerant pipe joint Refrigerant pipe(flared)
[12.7·····(SUZ-KA50VA) [15.88···(SUZ-KA60/KA71VA)
Liquid refrigerant pipe joint Refrigerant pipe(flared)
[6.35·····(SUZ-KA50/KA60VA) [9.52·····(SUZ-KA71VA)
REQUIRED SPACE
SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Unit: mm
24
WIRED REMOTE CONTROLLER
130
120
19
43.5
Unit : mm
25
WIRELESS REMOTE CONTROLLER
SLZ-KA25/35/50VAL
Unit : mm
57 17.5
h
B
D
C
A
140
ON/OFF
AUTO COOL
HEAT
MODE
DRY
TOO
WARM
FAN
VANE
TOO
COOL
SELECT
TIME
RESET
Installation area
• Area in which the remote controller is not exposed to direct sunshine
• Area in which there is no heating source nearby
• Area in which the remote controller is not exposed to cold (or warm) winds
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children
Installation method
1 Attach the remote controller holder to the desired location using two tapping screws. 2 Place the lower end of the controller into the holder.
A Wireless remote controller (Accessory) B Wall C Remote controller holder (Accessory) D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45 degrees to both right and left of the center line of the receiver. In addition, the signal may not be received if there are interferences of fluorescent lights or strong sunlight.
26
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
27
4
WIRING DIAGRAM
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
RT15
RT12 RT13 RT14
RT11
LS1 LS2
230V~
12-24V
TB
S1
S2
S3
1 2 3 4
1 2 3 4 5 6
CN
111
CN
1X1
CN
1Y1
BLK WHT
WHT RED
DISP REC P.C.BOARD
CN CN
106
CN113
CN112
3 2
CN201
1
125
MV1
62
F11
NR11
3 2 1
CN202
ML1
MV2
55
CN
151
DB111
LD103
GRN
ML2
55
CN
152
MF1
5
1 2 3 4 5 6
CN211
T11
INDOOR ELECTRONIC CONTROL P.C. BOARD
MF2
5
1 2 3 4 5 6
CN212
[LEGEND]
SYMBOL
DB111
F11 LS1
LS2 MF1 MF2
ML1
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
DIODE STACK FUSE (T3.15AL250V) DAMPER LIMIT SWITCH (OPEN) DAMPER LIMIT SWITCH (CLOSE) UPPER INDOOR FAN MOTOR LOWER INDOOR FAN MOTOR DAMPER LOCK MOTOR (RIGHT)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate :
/: Terminal block, : Connector
NAME
SYMBOL
ML2 MV1
MV2 NR11 RT11 RT12 RT13
NAME DAMPER LOCK MOTOR (LEFT) HORIZONTAL VANE MOTOR DAMPER MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN 1) INDOOR COIL THERMISTOR (SUB)
SYMBOL
RT14 TR15
T11
NAME INDOOR COIL THERMISTOR (MAIN 2) INDOOR COIL THERMISTOR (MAIN 3) TRANSFORMER
28
SLZ-KA25VAL SLZ-KA25VA
SWE
GRILLE
OFF
ON
SW3
OFF
54321
ON
SW2
OFF
54321
ON
WHT
RED
RED
CNDK
(POWER BOARD)
ZNR
X1
RED
ORN
YLW
YLW
BLU
BLU
BLU
BLU
LED3
CN2L
CN32 CN51 CN41
(REMOCON)
BLU
TO OUTDOOR UNIT
S3
ORN
MF
MV
MV
MV
MV
5
5
5
5
H2
5
31
P.B
3
TB4
S1 S2
TB15
1 2
TO MA-REMOTE CONTROLLER DC8.7-13V
}
REMOTE CONTROLLER
W.R
9
5
CN6V
(VANE)
GRN
BLU
WHT
ORN
RED
YLW
YLW
X5
X5 X4
X4X7X6
X6 X7
97531
C1
BLK
WHT
BLU
YLW
BRN
RED
I.B
CNB
BZ
LED2
LED1
SW1
SW2
RU
W.B
9
CN22
1
(2 PHASE)
CN29
BLK
WHT
RED
(INTAKE)
(LIQUID)
CN31
3
CN20
CN21
112
212
2
12
DS
TH5
TH1
TH2
X1
YLW
BLU
(D·U·M)
CNP
RED
(D·HEATER)
CNC
313131
CND
(POWER)
ORN
FUSE
(CONTROL)
CN3C
BLU
3131
LED1
12
12
TRANS
DC13.1V CN2S(WHT)
AC220-240V CNSK(RED)
WHT
BLK
2
1
(POWER
BOARD)
CN2D
WHT
LED2
* Case of wireress model
* Case of wired model
See fig:w1
MODELS
KA25
KA35
KA50
<fig:w1>
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
SW2
YLW
YLW
RED
ORN
YLW
WHT
BLU
17451089236
DP
GRY
VLT
BLU
YLW
ORN
RED
BRN
SKYBLU
PINK
WHT
(WIRELESS)
CN90
987654321
654321
(FAN)
FAN
WHT
BRN RED ORN YLW
BLU
VLT GRY PINK
SKY BLU
123456789
(DRAIN)
WHT
w For details on how to operate self-diagnosis, refer to the technical manuals etc.
SWITCH(COOLING ON/OFF)
LED(RUN INDICATOR)
SWITCH(HEATING ON/OFF)
LED(HOT ADJUST)
BUZZER
RECEIVING UNIT
WIRELESS REMOTE CONTROLLER BOARD
SW2
SW1
LED2
RU
LED1
BZ
W.B
H2
DP DS
MV
MF FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE DRAIN SENSOR DEW PREVENTION HEATER
C1 CAPACITOR(FAN MOTOR)
FUSE(T6.3AL250V)
X7
X6
X5
X4
X1
ZNR
RELAY(FAN MOTOR Me)
RELAY(FAN MOTOR Hi)
RELAY(FAN MOTOR LL) RELAY(FAN MOTOR Lo)
DRAIN PUMP/DEW PREVENTION HEATER
VARISTOR
SYMBOL NAME
SWITCH(CAPACITY CODE)
SW3
SW2
SWE SWITCH(EMERGENCY OPERATION)
SWITCH(MODE SELECTION)
TRANSMISSION(INDOOR-OUTDOOR)
LED1 LED2 LED3
POWER SUPPLY(I.B) POWER SUPPLY(I.B)
CN51
CENTRALLY CONTROL
FUSE
P.B
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(LOSSNAY)
CN41
CN32
CN2L
INDOOR CONTROLLER BOARD
INDOOR POWER BOARD
I.B
NAMESYMBOL
TB4
TB15
TH1
TH2
TH5
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0°C/15k, 25°C/5.4k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0°C/15k, 25°C/5.4k DETECT) COND./EVA.TEMP.THERMISTOR (0°C/15k, 25°C/5.4k DETECT)
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
SLZ-KA35VAL SLZ-KA35VA SLZ-KA50VAL SLZ-KA50VA
29
SEZ-KC25VA
TO OUTDOOR UNIT
S1S2S3
TB4
P.B.
AC220-240V
CNSK(RED)
213
I.B.
TRANS
BLU
131313
ORN
(POWER)
CND
DC13.1V
CN2S(WHT)
12
CN3C
(CONTROL)
ZNR
FUSE
1
2
WHT
(POWER
BOARD)
CN2D
LED3
LED1
LED2
RED
BLK
2121
BLU
CN22
(REMOCON)
WHT
CN21
(LIQUID)
2121
CN20
(INTAKE)
CN29
(2 PHASE)
TO MA-REMOTE
CONTROLLER
DC8.7-13V
1
2
TB15
TH2
TH1TH5
electric wiring diagram for servicing.
numbers (1, 2) for correct wirings.
NOTE:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
3. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
4.The wiring between MA-REMOTE CONTROLLER and TB15 is included in the package.
1234675
MF
6457321
BLU
The motor connector is
6457321
INSERT
connected with 230V,240V
power at factory shipment.
If 220V power is used,
Insert the attachment.
Color/Power source
RED
WHT
312 4567
C
WHT/230,240V
BLU/220V
(POWER BOARD)
CNDK
FAN
(FAN)
X6 X5 X4
X6 X5 X4
SW3
SWE
ON
ON
OFF
OFF
CN90
NAME
CN51 CN41
CN2L
5432
SW2
ON
CN32
12345
OFF
1
1
CAPACITOR (FAN MOTOR)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
C
MF FAN MOTOR
SYMBOL
NAME
SYMBOL
[LEGEND]
TB4
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
INDOOR POWER BOARD
CN2L
I.B.
P.B.
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
INTAKE AIR TEMP. THERMISTOR
(0˚C/15k. 25˚C/5.2k DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0˚C/15k. 25˚C/5.2k DETECT)
COND./EVA. TEMP. THERMISTOR
(0˚C/15k. 25˚C/5.2k DETECT)
TB15
TH1
TH2
TH5
SWITCH (MODE SELECTION)
SWITCH (CAPACITY CODE)
TRANSMISSION (INDOOR-OUTDOOR)
POWER SUPPLY (I.B.)
POWER SUPPLY (I.B.)
FUSE (6.3A)
CONNECTOR (WIRELESS)
CENTRALLY CONTROL
CONNECTOR (HA TERMINAL-A)
CONNECTOR (REMOTE SWITCH)
LED1
FUSE
CN32
CN41
CN51
CN90
LED2
LED3
SW2
SW3
SWITCH (EMERGENCY OPERATION)
SWE
RELAY (FAN MOTOR Lo)
RELAY (FAN MOTOR LL)
X5
X4
VARISTOR
RELAY (FAN MOTOR HI)
ZNR
X6
30
SWE
OFF
ON
SW3
OFF
54321
ON
SW2
OFF
54321
ON
(POWER BOARD)
CNDK
RED
RED
WHT
ZNR
FUSE
RED
BLU
CND
(POWER)
ORN
BLU
YLW
WHT
BRN
BLU
BLK
1234567
87654321
BLU
BRN
YLW
ORN
87123456
RED
BLK
RED
WHT
C1
MF
ORN
WHT
FAN
(FAN)
CN90
BLU
BLU
(REMOCON)
BLU
TO OUTDOOR UNIT
S3
P.B
123
TB4
S1 S2
TB15
1 2
TO MA-REMOTE
CONTROLLER DC8.7-13V
}
I.B
12
CN22
12
WHT
RED
(INTAKE)
(LIQUID)
CN20
CN21
122
TH1 TH2
13
(CONTROL)
CN3C
BLU
3
LED1
12
TRANS
DC13.1V CN2S(WHT)
AC220-240V CNSK(RED)
WHT
BLK
2
1
(POWER
BOARD)
CN2D
WHT
LED2
ORN
BLU
LED3
CN2L
CN32
CN51
CN41
X5
X5 X4
X4X6
X6
(2 PHASE)
CN29
BLK
1
TH5
311
54321
OFF
ON
KA60
54321
OFF
ON
KA71
<fig:w1>
MODELS
KA35
KA50
ON
OFF
12345
ON
OFF
12345
SW2
See fig:w1.
SYMBOL NAME
CONNECTOR(WIRELESS)
Indoor Fan Motor(MF) for 60Hz
wFor details on how to operate self-diagnosis, refer to the technical manuals etc.
CN90
MF
C1
TB4
TB15
TH1
TH2
TH5
FAN MOTOR
CAPACITOR(FAN MOTOR)
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0°C/15kΩ,25°C/5.4kΩ DETECT) PIPE TEMP.THERMISTOR/LIQUID (0°C/15kΩ,25°C/5.4kΩ DETECT) COND./EVA.TEMP.THERMISTOR (0°C/15kΩ,25°C/5.4kΩ DETECT)
FUSE(T6.3AL250V)
X6
X5
X4
ZNR
RELAY(FAN MOTOR Hi)
RELAY(FAN MOTOR LL) RELAY(FAN MOTOR Lo)
VARISTOR
SWITCH(CAPACITY CODE)
SW3
SW2
SWE
SWITCH(EMERGENCY OPERATION)
SWITCH(MODE SELECTION)
TRANSMISSION(INDOOR-OUTDOOR)
LED1 LED2 LED3
POWER SUPPLY(I.B) POWER SUPPLY(I.B)
CN51
CENTRALLY CONTROL
FUSE
P.B
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(LOSSNAY)
CN41
CN32
CN2L
INDOOR CONTROLLER BOARD
INDOOR POWER BOARD
I.B
NAMESYMBOL
YELLOW
BLUE
BLUE
<fig:w2>
50
60
[LEGEND]
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. Since the indoor fan motor(MF) is connected with 50Hz power, if 60Hz power is used, change the wiring connection shown in fig:w2.
SEZ-KA35VA SEZ-KA50VA SEZ-KA60VA SEZ-KA71VA
31
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
<Table 2>SW2(CAPACITY CODE)
12345
12345
12345
12345
Manufacture/Service
PLA-RP35BA
MODELS
SW2
ON OFF
PLA-RP50BA
ON OFF
PLA-RP60BA
ON OFF
PLA-RP71BA
ON OFF
114169
113
1 3
4
51
41
1234567891011121314151617
18
19
20
CN2L
ON OFF
SWE
J42J41
SW2SW1
LED3 LED2 LED1
LED2 LED1
RU
SW2
SW1
CNB
3
9
5555
4 5
3
t° t° t°
FS
TH2 TH5 TH1
MV
BZ
MVMVMV
MMMM
W.B
TB6
R.B
I.B
MT
M
14
21
21
21
1
2
1
2
Refer to tables 1 and 2
TRANSMISSION WIRES DC12V
TB4 YLW ORN
ORN BRN
YLW
YLW
ORN
DCL
TO OUTDOOR UNIT
135
31
DC280V
X1
M
1~ DP
D.U.M
CNP
(BLU)
ZNR02
ZNR01
FUSE
DSA
OUTDOOR
CN01
(BLK)
RECTIFICATION
U
U
S1 S2 S3
741
3~ MF
MS
CN3G
U.B
AUTOMATIC FILTER ELEVATION PANEL (OPTION PART)
CN3A
31
AUTO GRILLE
POWER
CNAC
(WHT)
1
3
REMOCON
CN22
(BLU)
I-SEE SENSOR
CN4Y
(WHT)
I-SEE
SENSOR MOTOR
CN6Y (RED)
WIRELESS
CN90
(WHT)
AUTO GRILLE
CN3G (BLK)
I-SEE SENSOR CORNER PANEL (OPTION PART)
I-SEE SENSOR
GRILLE
VANE
CNV(
WHT)
Pair No.
FAN CNMF (WHT)
INTAKE
CN20 (RED)
FLOAT SW
CN4F
(WHT)
LIQUID/PIPE
CN44
(WHT)
TB5
CN32
(WHT)
CN51(WHT)
CN41(WHT)
<Table 1>SW1(MODEL SELECTION)
Manufacture/Service
SW1
ON OFF
12345
w Be sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor)
13135
SYMBOL SYMBOLNAME NAME
I.B
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
SURGE ABSORBER
CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL)
POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR)
RELAY (DRAIN PUMP)
SWITCH (MODEL SELECTION) wSee table 1 SWITCH (CAPACITY CORD) wSee table 2 CONNECTOR (EMERGENCY OPERATION)
FAN MOTOR VANE MOTOR TERMINAL BLOCK (Indoor unit Power (option)) TERMINAL BLOCK (
INDOOR/OUTDOOR CONNECTING LINE
) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT) PIPE TEMP. THERMISTOR/LIQUID (0: / 15k", 25: / 5. 4k" DETECT) COND. / EVA. TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT)
MF
FUSE
MV
ZNR01,02
DSA
CN2L CN32
TB2
CN41 CN51
TB4
DRAIN-UP MACHINE DRAIN FLOAT SWITCH
REACTOR DP FS
DCL
LED1
TB5,TB6
LED2
TH1
LED3
X1
TH2
SW1
TH5
SW2 SWE
[LEGEND]
TO OUTDOOR UNIT
1
3
5
31
CN01 (BLK)
ORN
YLW
BLU
RED
GRN/YLW
I.B
w1(Fig. 1)
I.B
TB2
POWER SUPPLY ~(1PHASE) 230V 50Hz
ORN ORN
YLW
BRN
TB4
INDOOR/OUTDOOR
COMMUNICATION
CN3C (BLU)
L
N
S1
S2
S3
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system of power and signal. w1:When work to Supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2:For power supply system of this unit, refer to the caution label located near this diagram.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SYMBOL NAME
W.B
RU
BZ LED1 LED2
SW1 SW2
OPTION PART
PCB FOR WIRELESS REMOTE CONTROLLER
RECEIVING UNIT
BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE)
EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP)
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA
32
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
INDOOR POWER BOARD
[LEGEND]
P.B
INDOOR CONTROLLER BOARDI.B FUSE(T6.3AL250V)FUSE
CN2L
VARISTORZNR
CONNECTOR(LOSSNAY)
CN32
FAN CONTROL ELEMENTBCR
CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION) See table 1
SWITCH(
CAPACITY CORD
) See table 2
SW2 SWE
CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP) X4 RELAY(FAN MOTOR)
LED1 POWER SUPPLY(I.B) LED2 POWER SUPPLY(I.B) LED3 TRANSMISSION(INDOOR-OUTDOOR)
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C CAPACITOR(FAN MOTOR)
MF FAN MOTOR MV VANE MOTOR
DP DRAIN-UP MACHINE DS DRAIN SENSOR
H2 DEW PREVENTION HEATER
TB4
TERMINAL BLOCK (INDOOR/ OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (INDOOR UNIT POWER(OPTION))
TB5, TB6 TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR
(0˚C/15k,25˚C/5.4k DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15k,25˚C/5.4k DETECT)
TH5 COND./EVA. TEMP. THERMISTOR
(0˚C/15k,25˚C/5.4k DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER BOARD RU RECEIVING UNIT BZ BUZZER LED1 LED(RUN INDICATOR) LED2 LED(HOT ADJUST) SW1 SWITCH(HEATING ON/OFF) SW2 SWITCH(COOLING ON/OFF)
321
321
531
MF
FAN
(WHT)
RED
WHT
BLK
BLK
X1
X4
X1X4
C
BCR
31
DP
D.U.M
CNP
(BLU)
YLW
YLW
ORN
ORN
YLW
31 31 31 31
YLW
YLW
D.HEATER CNC(RED)
RED
WHT
WHT
BRN
POWER CNDK (RED)
POWER CND (ORN)
21
POWER CN2D (WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
CN41CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
VANE CN6V
(GRN)
CN2S
(WHT)
CNSK (RED)
W.B
LED2
CNB
LED1
SW1 SW2
RU
21
2
21
1
REMOCON
CN22 (BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
321 21 21
D.SENSOR
CN31 (WHT)
INTAKE
CN20
(RED)
HEATER
CN24
(YLW)
LIQUID
CN21
(WHT)
DS
TH2
21
PIPE CN29 (BLK)
TH3
TH1
LED3 LED2 LED1
ON OFF
SWE
Refer to tables 1 and 2.
SW2 SW1
9 5
10
76321 84
5MV5MV5
5
MV5MV
GRILLE
H2
S1 S2
S3
TB4
TO OUTDOOR UNIT
DC
13.1V
1
2
2
3
1
P.B
ZNR
FUSE
I.B
YLW ORN
BRN
ORN
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
1 2 3 4 5
ON OFF
MODELS
Table 1
SW1
Service board
PLA-RP. AA
1 2 3 4 5
ON OFF
MODELS
Table 2
SW2
Service board
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal.
33
PCA-RP50GA PCA-RP50GA2 PCA-RP60GA PCA-RP71GA
CN31 DRAIN SENSOR
DS
1 2 3
(
WHT
)
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SW1
Table 1
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP.GA
SW2
Table 2
Service board
1 2 3 4 5
ON OFF
MODELS
PCA-RP50GA
1 2 3 4 5
ON OFF
PCA-RP50GA2
PCA-RP60GA
1 2 3 4 5
ON OFF
PCA-RP71GA
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) SW1 SWITCH (MODEL SELECTION) WSee Table 1. SW2 SWITCH (CAPACITY CODE) WSee Table 2. SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
X1 RELAY(DRAIN PUMP) BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B) LED2
TRANSMISSION(INDOOR-OUTDOOR)LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR VANE MOTOR
MF MV
DRAIN-UP MACHINE (OPTION)
DP
DRAIN SENSOR (OPTION)
DS
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER) WPCH-P.GAH models only or option for PCA RP.GA models.
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE ) ROOM TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT) PIPE TEMP.THERMISTOR/LIQUID (0;/15k', 25;/5.4k' DETECT) COND./EVA.TEMP.THERMISTOR (0;/15k', 25;/5.4k' DETECT)
TB5,TB6
TH5
TH1 TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD(OPTION) RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU BZ LED1 LED2 SW1 SW2
NAMESYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
THERMAL FUSE(
98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
FS1,2
[Servicing] Fasten terminal of the terminal board "TB4"equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
When installing drain-up machine (Optional part).
X4 X1
FAN
(
WHT
)
1 3 1 3 1 3 1 35
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK (RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1 2
1 2
3
P.B
I.B
CNDK
(RED)
DC13.1V
CN2S (WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER CN2D(WHT)
1 3
INDOOR/OUTDOOR COMMUNICATION CN3C(BLU)
SWE
ON OFF
SW2 SW1
Refer to tables 1 and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1 S2 S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41 CN2L CN51 CN32
VANE CN6V
(
GRN
)
MV
6 6
9
MV
6 6
WIRELESS CN90
(
WHT
)
INTAKE CN20
(
RED
)
LIQUID CN21
(
WHT
)
D.SENSOR CN31
(
WHT
)
PIPE CN29
(
BLK
)
1 21 2 3
1 2
1 2
TH5TH1
TH2
REMOCON CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
100~140 TYPE
MV
5 5
W
When installing optional drain-up machine, disconnect the CN31 jumper connector and replace it with the drain sensor (DS).
NOTES:
1.
Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers
(S1, S2, S3) for correct wirings.
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
34
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
ON OFF
12345
ON OFF
12345
ON OFF
12345
ON OFF
12345
54321
OFF
ON
50EA
60EA
71EA
35EA2
Capacity cord
switch
Model selection switch
SW2
SW1
MODELS
TO OUTDOOR UNIT
TO MA-REMOTE CONTROLLER DC8.7-13V
I.B.
X6
X4
X5
X1
ZNR
FUSE
P.B.
CN31
1
3
DS
INSIDE SECTION OF CONTROL BOX
B L
U
B L U
B L U
B L U
TB5
(RED)
643521
C
MF
X6X5X4
X1
(RED)
CNDK
(BLU)
CNP
(WHT)
FAN
1
Y L W
O R N
(ORN)
31
CND
2
1
(RED)
LED1 LED2 LED3
CN2L
OFF
ON
SWE
SW2
SW1
(RED)
(WHT)
P N K
P N K
B L K
B L K
W H T
B
L
K
B L K
W H T
W H T
W H T
1
2
31
CN2S
CNSK
(WHT)
(RED)
YLW
ORN
BRN
B R N
O R N
(BLU)
WHT
BLK
CN2D
(WHT)
(BLU)
(RED)
(WHT)
(BLK)
(WHT)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
DP
643521
2 1
TB4
S3 S1
S2
2
1331
643521
MF
C
12
CN24
321
12
3
1
2
1
2
1
2
TH5TH2TH1
1
2
CN3C
31
1375
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789 432145321
<PEAD-RP71•100•125•140EA, 100EA2> External static pressure 130Pa
<PEAD-RP71•100•125•140EA, 100EA2>
External static pressure 70Pa <PEAD-RP35•50•60EA, 35EA2> External static pressure 70Pa
Optional parts
Optional parts
<PEAD-RP35•50•60EA, 35EA2> External static pressure 30Pa
(OPTIONAL PARTS)
DRAIN PUMP
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS) DP
DS
TRANSMISSION(INDOOR•OUTDOOR)
LED3
SWITCH(MODEL SELECTION)
SW1
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t, 25:/5.4t DETECT)
INTAKE AIR TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
DRAIN SENSOR
DRAIN PUMP
TH5
TH2
TH1
TB5
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCKTB4
MF
C
NAMENAME
NAME
[LEGEND]
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
CN41
CN32
CN2L
I.B.
SYMBOL SYMBOL SYMBOL
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. The wiring between MA-Remote controller and TB5 is included in the package.
35
PEAD-RP60GA PEAD-RP71GA
Capacity cord switch
Model selection switch
SW2SW1
ON OFF
12345
ON OFF
12345
54321
OFF
ON
71GA
60GA
MODELS
TO MA-REMOTE CONTROLLER DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1
ZNR
FUSE
P.B.
I.B.
X1
Y
L
W
O R N
X6X5X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B L U
B L U
B L U
B L U
(BLK)
(WHT)
(RED)
(BLU)
B L K
W H
T
BLK
WHT
(WHT)
(BLU)
B R N
BRN
O
R N
ORN YLW
(BLU)(RED)(ORN)
(RED)
(WHT)
B L K
W
H T
B L K
W H T
(WHT)
(WHT)
O R G
B L K
B
L
U
B L K
Y L W
Y
L
W
G R Y
*
(FACTORY SHIPMENT)
240V230V220V 20Pa
60Pa 75Pa
10Pa 50Pa 70Pa50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2
1
TB5
TB4
S3 S1
S2
2 1
CNP
1331
31
13
CNSK
2
1
CN2S
643521
MF
C
1
2
CN24
3
21
12
3
1
2
1
212
TH5TH2
TH1
LED1 LED2 LED3
1
2
CN2D
CN3C
31
CND CNDK
137
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789
4
321
54321
INSIDE SECTION OF CONTROL BOX
*External static pressure
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR•OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0: /15t, 25:/5.4t DETECT)
INTAKE AIR TEMP.THERMISTOR (0: /15t, 25:/5.4t DETECT)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
[LEGEND]
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. The wiring between MA-Remote controller and TB5 is included in the package.
36
PEA-RP71EA
ORN
RED
WHT
BRN
BLU
BLK
561432
Refer to tables 1 and 2.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit installation Manual.
Table 2Table 1
21
BLU BLU
TB5
INDOOR UNIT
TB6
R.B
REMOTE CONTROLLER BOARD TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSON LINE)
SW1 SW2
SWITCH(MODEL SELECTION)wSee table 1 SWITCH(CAPACITY CODE)wSee table 2
TB5
TRANSMISSION LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
SYMBOL SYMBOL SYMBOL P.B I.B
FUSE ZNR CN2L CN32 CN41 CN51 LED1 LED2 LED3
FUSE(T6.3AL250V) VARISTOR
INDOOR CONTROLLER BOARD
INDOOR POWER BOARD
CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH)) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) POWER SUPPLY(I.B) POWER SUPPLY(R.B) TRANSMISSOION(INDOOR • OUTDOOR)
NAME
[LEGEND]
I.B
SWE X4 X5 X6
SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR)
NAME
NAME
C MF
TB2 TB4
TH1
TH2
TH5
CAPACITOR(FAN MOTOR) FAN MOTOR
TERMINAL BLOCK(INDOOR UNIT POWER(OPTION))
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
ROOM TEMPERATURE THERMISTOR (0;/15K', 25;/5.4K' DETECT)
PIPE TEMPERATURE THERMISTOR/LIQUID (0;/15K', 25;/5.4K' DETECT)
COND./EVA. TEMPERATURE THERMISTOR (0;/15K', 25;/5.4K' DETECT)
TO OUTDOOR UNIT
ORN
YLW
TB4
S3
S2
S1
13
1
2
OFF
ON
SWE
I.B
1
FAN (WHT)
X6
X6
REMOCON CN22 (BLU)
WIRELESS CN90 (WHT)
CN3C (BLU)
INDOOR/OUTDOOR COMMUNICATION
ORN
BRN
1 2
TH1
TH5
CN2L
BLU
TRANSMISSION WIRE DC12V
TB6
1
1
2
3112
2 1
357
13
SW1SW2
1
2
2 1
R.B
P.B
CN2S (WHT)
CNSK (RED)
23
DC13.1V
X5 X4
X5 X4
LED3 LED2 LED1
TH2
LIQUID CN21 (WHT)
INTAKE CN20 (RED)
PIPE CN29 (BLK)
CN32
CN41
CN24
POWER CN2D (WHT)
WHT
BLK
ORN
YLW
ZNR
FUSE
POWER CND (ORN)
WHT
RED
POWER CNDK (RED)
BLU
MF
C
Manufacture/Service
MODELS
Manufacture/Service
MODELS
PEA-RP71EA
123 54
SW2
ON OFF
123 54
PEA-RP.EA
SW1
ON OFF
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. This diagram shows the wiring of Indoor and Outdoor connecting wires(speclfication of 230V), adopting superimposed system of power and signal.
37
SUZ-KA25VA SUZ-KA35VA
BLK
BLK
U
2
1
WHT
BLK
LD-V
LD-U
CT761
U
V
P
F801
+++
DB61
W
RED
RED
C63C
C63B
C63A
LD70
MC
3
CN61
LD-W
W
N
V
WHT
CN724
CT781
IPM
R61
T801
BLK
6
LD69
LEV
F901
IC801
TR821
TB800
MF
CN932
315 2
5 42
42 3
CN931
IC932
1
CN642
21213412
CN641
13
INVERTER P.C. BOARD
CN643
45 231
CN601
GRN
DB65
R831
LDY
CN725
RT61 RT62 RT64RT65
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor electric wiring, refer to
NAME
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
EXPANSION VALVE COIL
R61,R831
R64A,R64B
TB1,TB2
TR821
T801
X63,X64
21S4
SYMBOL
LEV
L61
BLK
TAB63
TAB61
TB2
L63
L62
WHT
F61
WHT
S1
230V~
R64AR64B
BLU
S2
BLU
3
X64
4
CT
NR63
TAB62
NR64
RED
S3
12-24V
CONNECTING TO INDDOR UNIT
21S4
6
1
2
CN727
CN721
X63
F71
DSA61
LDE
GRN
L
GRN/YLW
N
~/N
230V 50Hz
PE
POWER
SUPPLY
TB1
CIRCUIT BREAKER
4
CN726
POWER P.C. BOARD
WHITE
BLU
RED
NAME
REACTOR
SYMBOL
L61
NAME
CURRENT TRANSFORMER
SYMBOL
CT,CT761,CT781
[LEGEND]
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
L62,L63MCMF
SMOOTHING CAPACITOR
C63A,C63B,C63C
NR63,NR64
RT61
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
DB61,DB65
DSA61
F61
F71
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
RT62
RT64
RT65
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
F801,F901
IC801
IPM,IC932
38
SUZ-KA25VAH SUZ-KA35VAH
BLK
U
1
WHT
BLK
LD-V
LD-U
CT761
U
P
+++
W
2
V
F801
MC
RED
3
RED
N
C63C
C63B
C63A
CN61
LD-W
CT781
W
R61
V
WHT
IPM
T801
CN724
6
LEV
F901
IC801
TR821
MF
CN932
3 212 4 1
5
5
3
IC932
R831
3
CN931
12 4
431212
CN641 CN642
21
INVERTER P.C. BOARD
CN643
LDY
RT65 RT64RT62RT61
GRN
NAME
CURRENT-LIMITING RESISTOR
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor electric wiring, refer to
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
DEFROST HEATER
HEATER PROTECTOR
BLK
L61
BLK
DB61
TAB63
R64A
R64B
L63
L62
TAB61
WHT
F61
WHT
TB2
S1
~
230V
BLU
S2
LD70
X64
TAB62
RED
S3
12-24V
LD69
TB800
BLK
BLU
21S4
1
2
3
4
CT
NR64 NR63
CONNECTING TO INDDOR UNIT
CN721
X63
F71
DSA61
GRN
TB1
L
N
CIRCUIT BREAKER
POWER
~/N
230V 50Hz
CN725
4
CN726
X66
CN722
RED
1
BLK BLK
23145
CN601
312
YLW
2
BLKBLK
26H
BLK
1
2
BLK
BLK
H
DB65
6
CN727
LDE
POWER P.C. BOARD
GRN/YLW
PE
SUPPLY
WHITE
BLU
RED
SYMBOL
R64A,R64B
NAME
REACTOR
SYMBOL
L61
NAME
CURRENT TRANSFORMER
SYMBOL
CT,CT761,CT781
[LEGEND]
TB1,TB2
TR821
T801
X63,X64,X66
21S4H26H
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
NR63,NR64
L62,L63MCMF
SMOOTHING CAPACITOR
DIODE MODULE
C63A,C63B,C63C
DB61,DB65
RT61
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
DSA61
F61
F71
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
CURRENT-DETECTING RESISTOR
RT62
RT64
RT65
R61,R831
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
F801,F901
IC801
IPM,IC932
LEV
39
SUZ-KA50VA
R64B
YLW
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
RED
WHT
RS2
RS1
R64A
RS3
RS4
F801
CN901
NR64
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
L
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
W
CN4
TB2
S1
1
CN601
3
S2
1567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
23134512
MF
CN932
3X64
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
4
1
RED
YLW
3
2
RED
S
R
21
CN903
21
CN902
21
CN5
6543 1
CN2
27
TAB4
V
MC
W
U
V
WHT
RT61 RT62 RT68
LEV
:Terminal block :Connector
3.Symbols below indicate.
2.Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1.About the indoor electric wiring,NOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGENT POWER MODULE
CT61
FUSE (T2AL 250V)
F64
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
SMOOTHING CAPACITOR
CB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B
RESISTOR
PFC
NF
NR64
VARISTOR
AMBIENT TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
R.V. COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT65
FIN TEMPERATURE THERMISTOR
RT64
T801
TRANSFORMER
SSR61
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
[LEGEND]
SYMBOL
SUZ-KA60VA
40
SUZ-KA71VA
BLK
CN902
12
CN903
12
TAB4
X64 3
R64A R64B
RED
2
3
1
4
L
YLW
YLW
RED
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
HPS
RED
RED
RED
WHT
RS2
RS1 RS3
RS4
F801
CN901
NR64
CN681
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
12
W
CN4
TB2
S1
1
CN601
3
S2
1567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
23134512
MF
CN932
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
S
R
21
CN5
6543 1
CN2
27
V
MC
W
U
V
WHT
RT61RT62 RT68
LEV
:Terminal block :Connector
3.Symbols below indicate.
2.Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1.About the indoor electric wiring,NOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGEMT POWER MODULE
HPS
HIGH PRESSURE SWITCH
CT61
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGEMT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
F64
FUSE (T2AL 250V)
SMOOTHING CAPACITORCB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B RESISTOR
PFC
NF
NR64
VARISTOR
FIN TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
R.V. COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT64
T801
TRANSFORMER
SSR61
AMBIENT TEMPERATURE THERMISTOR
RT65
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
[LEGEND]
SYMBOL
41
5
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT12, RT14, RT15 (main) RT13 (sub)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [9.52 (MFZ-KA25/35VA) Refrigerant pipe [12.7 (MFZ-KA50VA) (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12 (main)
Distributor
Thermistor TH2 Pipe temperature (Liquid)
Distributor with strainer(#50)
Thermistor TH5 (Cond./Eva. temperature)
Thermistor TH1 (Room temperature)
Strainer(#50)
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT MFZ-KA25VA
MFZ-KA35VA MFZ-KA50VA
Unit : mm
SLZ-KA·VA SLZ-KA·VAL SEZ-KC·VA SEZ-KA·VA Unit : mm PLA-RP·BA PLA-RP·AA PCA-RP·GA(2) PEAD-RP·EA(2) PEAD-RP·GA PEA-RP·EA
42
5-2. OUTDOOR UNIT Unit:mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Capillary tube [3.0[2.0240
Compressor
4-way valve
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Expansion valve
R.V. coil heating ON cooling OFF
Strainer #100
Muffler
Muffler
Ambient temperature thermistor RT65
Muffler
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Compressor
4-way valve
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube [3.0[1.8600(2)
Expansion valve
Ambient temperature thermistor RT65
Muffler
Muffler
Muffler
SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH Unit:mm
43
SUZ-KA50VA Unit:mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube [3.6[2.450
Compressor
4-way valve
Refrigerant pipe
[12.7 (SUZ-KA50VA)
(with heat insulator)
[15.88 (SUZ-KA60VA)
Refrigerant pipe [6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube [3.6[2.450
Capillary tube [1.8[0.61000
Compressor
4-way valve
Refrigerant pipe [15.88 (with heat insulator)
Refrigerant pipe [9.52 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Oil separator
High-pressure switch
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Strainer
#100
Strainer
#100
Ambient temperature thermistor RT65
SUZ-KA60VA
SUZ-KA71VA Unit:mm
44
6
Cooling capacity
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature(:)
Capacity correction factors
26
24
22 20 18
Outdoor intake air Dry-bulb temperature(:)
Input correction factors
Total input (cooling)
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10 -5 0 5 10 15 20 25 30 35 40 45
26
24
22 20 18
Indoor intake air Wet-bulb temperature(:)
Indoor intake air Wet-bulb temperature(:)
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA25VA(H)
PERFORMANCE CURVES
45
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA35VA(H)
Cooling capacity
1.5
1.4
1.3
Indoor intake air Wet-bulb temperature(:)
:
26
)
1.2
1.1
1.0
0.9
0.8
Capacity correction factors
0.7
0.6
-10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature(
Total input (cooling)
1.5
1.4
1.3
Indoor intake air Wet-bulb temperature(:)
24
22 20 18
1.2
1.1
1.0
0.9
26
correction factors
0.8
Input
0.7
0.6
-10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature(
:
)
46
24
22 20 18
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA50/60/71VA
Cooling capacity
1.5
1.4
1.3
Indoor intake air Wet-bulb temperature(:)
1.2
1.1
1.0
0.9
0.8
0.7
Capacity correction factors
0.6
-10 -5 0 5 10 15 20 25 30 35 40 45
-15
Outdoor intake air Dry-bulb temperature(:)
1.3
1.2
1.1
Total input (cooling)
Indoor intake air Wet-bulb temperature(:)
26
26
24
24
22 20 18
22 20 18
1.0
0.9
0.8
0.7
0.6
Input correction factors
0.5
0.4
-10
-15 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature (:)
47
Heating capacity
1.3
1.2
1.1
1.0
0.9
0.8
0.7
Capacity correction factors
0.6
-10 -5 0 5 10 15
Indoor intake air Dry-bulb temperature(:)
Outdoor intake air Wet-bulb temperature (:)
15 20
26
Total inputting (heating)
1.3
1.2
1.1
1.0
0.9
0.8
0.7
Input correction factors
0.6
-10 -5 0 5 10 15
Indoor intake air Dry-bulb temperature(:)
Outdoor intake air Wet-bulb temperature (:)
26 20 15
NOTE:The above curves are for the heating operation without any frost.
48
7 APPLICABLE EXTENSION PIPE FOR EACH MODEL
Outdoor unit
precharged
900
1,050
14m
270
270
7m
0
0
6m
0
0
5m
0
0
11m
180
180
Models
Refrigerant piping length (one way)
Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)
8m
90
90
9m
120
120
10m
150
150
12m
210
210
13m
240
240
15m
300
300
20m
450
450
SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
Refrigerant Piping Max. length A
w Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
w Max. Height
difference 12m
Indoor unit
Outdoor unit
Refrigerant piping
Max. length : m
A
20
Gas
9.52
Liquid
6.35
Piping size O.D : mm
Models
SUZ-KA25VA SUZ-KA35VA SUZ-KA25VAH SUZ-KA35VAH
SUZ-KA25VA SUZ-KA25VAH SUZ-KA35VA SUZ-KA35VAH
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
49
Refrigerant piping
Max. length : m
A
30
Gas
12.7
15.88
Liquid
6.35
9.52
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
Model
Piping size O.D : mm
Refrigerant piping length (one way)
Outdoor unit
precharged
15m
160
160
20m
260
260
25m
360
360
30m
460
460
7m
0
0
10m
60
60
Model
SUZ-KA50VA
SUZ-KA60VA
1,600
1,800
SUZ-KA50VA
Outdoor unit
precharged
2,000
0 165 440 715 990 1,265
Refrigerant piping length (one way)
15m10m7m
Model
SUZ-KA71VA
20m
25m 30m
SUZ-KA60VA SUZ-KA71VA
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
Indoor unit
w Max. Height
difference 30m
Refrigerant Piping Max. length A
w Height difference should be within 30m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Outdoor unit
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
Calculation : Xg=55g/mo(Refrigerant piping length(m)-7)
50
8
PLA-RP71AA
Air flow Air speed Coverage range
m3/min.
m/sec.
m
20
4.0
5.7
14
2.8
4.0
18
3.6
5.2
18
3.6
5.2
PLA-RP35AA PLA-RP50AA
PLA-RP60AA
Air flow Air speed Coverage range
m3/min.
m/sec.
m
10
3.4
3.7
11
3.7
4.1
11
3.7
4.1
SLZ-KA25VA
SLZ-KA25VAL
SLZ-KA35VA
SLZ-KA35VAL
SLZ-KA50VA
SLZ-KA50VAL
Air flow Air speed Coverage range
m3/min.
m/sec.
m
8.7
1.8
5.1
9.1
1.9
5.3
10.7
2.2
6.2
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
Air flow Air speed Coverage range
m3/min
m/sec
m
PCA-RP50GA PCA-RP60GA PCA-RP71GA
18
3.8
10.4
18
3.8
10.4
PCA-RP50GA2
18
3.8
10.4
13
3.7
8.8
PLA-RP71BA
Air flow Air speed Coverage range
m3/min.
m/sec.
m
21
3.7
5.6
15
2.6
4.1
18
3.2
4.8
18
3.2
4.8
PLA-RP35BA PLA-RP50BA
PLA-RP60BA
AIR FLOW DATA
8-1. OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the distance to which the 0.25m/sec air can reach,when air is blown out horizontally from the unit
at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
51
Detail drawing of fresh air intake
Ceiling surface
Refrigerant pipe
Drain pipe
Electrical Box
Cut out hole
[73.4
Burring hole
3-[2.8 hole
[100
118
25
120
°
120
°
Fresh air intake
Static pressure : P [Pa]
Air flow : Q [m
3
/min]
50
-50
-100
-150
-200
-250
-300
0
0.5 1.0 1.5 2.0 2.5 3.0 3.5
Q
0
B
A
C
1
Curve in the left graphs.
Duct characteristics at site
Q
A
EC
2
Q
Qa
AD
3
8-2. SLZ-KA•VA SLZ-KA•VAL
8-2-1. Fresh air intake (Location for installation)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
8-2-2. Fresh air intake amount & static pressure characteristics Taking air into the unit
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
How to read curves
Q…Designed amount of fresh air intake
<m3/min>
A…Static pressure loss of fresh air
intake duct system with air flow amount Q <Pa>
B…Forced static pressure at air
conditioner inlet with air flow amount Q <Pa>
C…Static pressure of booster fan
with air flow amount Q <Pa>
D…Static pressure loss increase
amount of fresh air intake dust system for air flow amount Q
<Pa>
E…Static pressure of indoor unit
with air flow amount Q
Qa…Estimated amount of fresh air
intake without D <m3/min>
52
8-3. SEZ-KA•VA INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA35VA
80
60
40
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
SEZ-KA50VA
80
60
40
Fan Performance
Recommended range
105 7 15 20 25
Air flow (K/X)
Fan Performance
Recommended range
Corrected Air flow
1.1
1.0
0.9
Correction factor
0.8
1.3
1.2
1.1
1.0
Correction factor
0.9
0.8
Corrected Airflow
1.1
1.0
0.9
Correction factor
0.8
1.2
Capacity
Cooling
1051520
Air flow (K/X)
Heating
5101520
Air flow (K/X)
Cooling
510152025
Air flow (K/X)
Heating
Input
25
25
Capacity Input
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
15510 2025
Air flow (K/X)
1.1
1.0
0.9
Correction factor
0.8 510152025
Air flow (K/X)
53
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
Air flow (K/X)
Recommended range
80
60
40
20
0
15510 2025
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
SEZ-KA60VA
SEZ-KA71VA
Corrected Air flow
1.1
0.9
1.0
0.8 10 15 20 25 30
Correction factor
Capacity Input
Cooling
Air flow (K/X)
0.9
1.0
1.2
1.1
1.3
10 15 20 25 30
Correction factor
Heating
Air flow (K/X)
Air flow (K/X)
Recommended range
80
60
40
20
0
15510 2025
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
Corrected Air flow
1.1
0.9
1.0
0.8 10 15 20 25 30
Correction factor
Capacity Input
Cooling
Air flow (K/X)
0.9
1.0
1.2
1.1
1.3
10 15 20 25 30
Correction factor
Heating
Air flow (K/X)
54
8-4. PLA-RP·BA
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Branch duct hole
A
A
A
14-[2.8 burring hole
Indoor unit
[150 cut out hole
Fresh air intake hole
[175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-[2.8 burring hole
Branch duct hole diagram (view from either side)
[125 burring hole pitch
[100 cut out hole
Ceiling
*158
120
120
350
90
70°
100 100 90
100
130
*155
*167
Fig. 1
8-4-1 FRESH AIR INTAKE AND BRANCH DUCT
55
3. Fresh air intake volume & static pressure characteristics
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
3 At using multi-function casement, high efficiency filter
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 Direct intake to unit
Static pressure[Pa]
-200
-150
-100
-50
0
50
0123456
2 - inlet
1 - inlet
Air flow rate [m3/min]
Air flow rate [m
3
/min]
Air flow rate [m
3
/min]
1 At using multi-function casement, standard filter
PLA-RP35~71BA
Static pressure[Pa]
56
4. Change of outlet numbers
<4- way air flow and branch duct>
w Branch duct should be connected to one of the branch duct holes on the main unit.
Branch duct
Air intake
Air outlet
<3- way air flow and branch duct>
w Close the outlet on the side or branch duct and air flows in 3 directions.
Branch duct
Air intake
Air outlet
Air outlet closed position
Air outlet closed position
<2- way air flow and branch duct>
w The outlet on the side or branch duct and one of the other outlets are closed. Air flows in 2 directions.
Air intake
Branch duct
Air outlet closed position
Air outlet closed position
[The optional air outlet is necessary.] To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter.
(When the air outlets are closed, close the vane by removing the vane connector.)
Indoor unit
5. Branch duct and change of outlet numbers
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
Outlet concave portion
Air outlet shutter plate (Option)
57
PLA-RP71BA
4-way air flow (horizontal vane) Round duct 4-way air flow (horizontal vane) Rectangular duct
30
20
30
Duct Duct
20
10
Static pressure [Pa]
High
Low
0
02
468
Air flow rate [m
3
/min]
3-way air flow (horizontal vane) Round duct 3-way air flow (horizontal vane) Rectangular duct
80
70
High
Duct
Close
3
/min]
60
50
40
30
Static pressure [Pa]
20
Low
10
0
0246810
Air flow rate [m
10
Static pressure [Pa]
High
Low
0
02468
Air flow rate [m3/min]
80
70
60
Duct
Close
50
40
30
Static pressure [Pa]
High
20
Low
10
0
0246810
Air flow rate [m
3
/min]
2-way air flow (horizontal vane) Round duct
100
90 80
Duct
Close
70 60 50 40
Static pressure [Pa]
30 20
High
Low
10
0
0 2 4 6 8 10 12
Air flow rate [m
3
/min]
Close
2-way air flow (horizontal vane) Rectangular duct
100
90 80 70 60 50 40
Static pressure [Pa]
30 20
Low
10
0
024681012
Duct
Close
High
Air flow rate [m
3
/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-RP35~60BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-RP71BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
Close
58
8-5. PLA-RP·AA
8-5-1. Fresh air intake amount
59
8-5-2. BRANCH DUCT (Installation at site)
60
Branch duct air flow rate/static pressure characteristics
PLA-RP35AA
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
61
PLA-RP50AA PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
62
PLA-RP71AA
4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3
/min]
Static pressure [Pa]
30
20
10
High
Low
0
123456
Air flow rate [m
3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct
Static pressure [Pa]
60
50
40
30
20
10
High
Low
0
123456789
Air flow rate [m
3
/min]
Static pressure [Pa]
60
50
40
30
20
10
High
Low
0
123456789
Air flow rate [m
3
/min]
3
/min]
2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct
100
Static pressure [Pa]
90
80
70 60
50
40
30 20
10
0
1234567891011
Low
High
Air flow rate [m
3
/min]
100
90
80
70
60
50
40
30
20
Static pressure [Pa]
10
0
1234567
Air flow rate [m
Low
High
3
/min]
63
8-6. PEAD-RP·EA, EA2, GA
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
6 8 10 12 14 16 18 20
810121416182022
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 10121416182022
810121416182022
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
8 1012141618202224
12 14 16 18 20 22 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAq)
Air Flow (CMM)
10 12 14 16 18 20 22 24 26
12 14 16 18 20 22 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
8-6-1. Fan performance and corrected air flow
PEAD-RP35EA2 PEAD-RP50EA
PEAD-RP60EA
64
PEAD-RP71EA
Lo
Hi
140 120 100
200 180 160
80 60 40 20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
140 120 100
180 160
80 60 40 20
12 16 20 24 28 32
Air flow
(CMM)
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
(1Pa 0.1mmAq)
=
Lo
Hi
Corrected Air Flow
Capacity Input
1.1
1.0
0.9
0.8
12 16 20 24 28 32
Air flow (CMM)
Correction factor
Cooling
=
1.1
1.0
1.3
1.2
0.9
0.8 12 16 20 24 28 32
Air flow (CMM)
Correction factor
Heating
PEAD-RP60GA
65
PEAD-RP71GA
Air flow (CMM)
Recommended range
200
150
100
50
Hi
Lo
0
201517 25 30 35
External static pressure(Pa)
(1Pa = 0.1mmAq)
Fan Performance
Corrected Air flow
1.05
0.95
1.0
0.9 17 20 25 30
Correction factor
Capacity Input
Cooling
Air flow (CMM)
1.05
1.15
1.1
0.95
1.0
1.2
17 20 25 30
Correction factor
Heating
Air flow (CMM)
8-7. PEA-RP·EA
8-7-1. Fan performance and corrected air flow PEA-RP71EA
66
9
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 44
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
37 37
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
38 38
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOOR UNIT
WALL
1m
1m
MICROPHONE
NOISE CRITERION CURVES
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
67
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA35VAL SLZ-KA35VA
High
Medium
38
SPL(dB)33LINE
<50Hz>
NOTCH
Low
29
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA25VAL SLZ-KA25VA
High
Medium
37
SPL(dB)31LINE
<50Hz>
NOTCH
Low
28
UNIT
1.5m
MICROPHONE
CEILING
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA50VAL SLZ-KA50VA
High
Medium
39
SPL(dB)34LINE
<50Hz>
NOTCH
Low
30
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be high­er by about 2 dB than the indicated level during cooling and heating operation.
68
SEZ-KC25VA
Appro
70
60
50
40
30
20
63 125 250 500 1000 2000 4000 8000
10
0
NC60
NC50
NC40
NC30
NC20
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND CENTER FREQUENCIES (Hz)
High
Low
36
SPL(dB)
25
<50Hz>
NOTCH
High speed Low speed
2m
Aux.duct
1m
1.5m
Measurement location
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be high­er by about 2 dB than the indicated level during cooling and heating operation.
69
SEZ-KA35VA
NOTCH
High Low
<50Hz>
SPL(dB)
35 30
LINE
SEZ-KA50VA
NOTCH
High
Low
<50Hz>
SPL(dB)
39 31
LINE
90
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
SEZ-KA60VA SEZ-KA71VA
BAND CENTER FREQUENCIES, Hz
NOTCH
High Low
<50Hz>
SPL(dB)
43 32
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
External static pressure 30Pa
MICROPHONE
UNIT
1.5m
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be high­er by about 2 dB than the indicated level during cooling and heating operation.
70
PLA-RP35BA PLA-RP50BA
NOTCH SPL(dB) LINE
High 31 Medium1 29 Medium2 28
Low 27
NOTCH SPL(dB) LINE
High 32 Medium1 31 Medium2 29
Low 28
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PLA-RP60BA PLA-RP71BA
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB) LINE
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
High 32
Medium1 31 Medium2 29
Low 28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB) LINE
High 34 Medium1 32 Medium2 30
Low 28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
71
NOTCH SPL(dB) LINE
PLA-RP35AA PLA-RP50AA
High Medium1 Medium2
Low
31 29 28
PLA-RP60AA
27
NOTCH SPL(dB) LINE
High Medium1 Medium2
Low
33 31 29 28
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PLA-RP71AA
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
34 32
UNIT
30 28
CEILING
1.5m
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MICROPHONE
72
Noise level at an echoic room (Low-High)
Model
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA
PEAD-RP71EA
External static pressure
30Pa 36-40 36-40
38-44* 38-44*
37-41 39-46*
-
37-41
* Optional motor
70Pa
Unit : dB(A)
130Pa
-
-
-
40-45*
PEAD-RP35EA2 PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 30Pa)
(External static pressure 30Pa)
High Low
High Low
NC60
NC50
NC40
NC30
NC20
NC60
NC50
NC40
NC30
NC20
PEAD-RP35EA2 PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum audible limit on continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static pressure 70Pa)
(External static pressure 70Pa)
High Low
High Low
NC60
NC50
NC40
NC30
NC20
NC60
NC50
NC40
NC30
NC20
73
1m
ceiling
1m
about 1.4m
MICROPHONE
PCA-RP50GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
42 40 38 37
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
unit
PCA-RP50GA2 PCA-RP60GA PCA-RP71GA
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High Medium1 Medium2
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
43 41 39 37
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PEA-RP71EA
90
80
70
60
50
40
30
20
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
10
63 125 250 500 1000 2000 4000 8000
SPL(dB)52LINE
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
55
UNIT
1m
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
External static pressure 125Pa
74
SUZ-KA25VA
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
FAN SPEED
HEATING
47 48
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OUTDOORUNIT
MICROPHONE
1m
High
Med.
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
53 55
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
FAN SPEED
High
Med.
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µ BAR
CONTINUOUS NOISE
10
SUZ-KA50VA SUZ-KA60VA
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))
46 46
SUZ-KA71VA
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
75
10
10-1. INDOOR UNIT
Part Name Model Name Applicable model
Remote sensor PAC-SE41TS-E Remote operation adapter PAC-SF40RM-E All models
except MFZ-KA
VA
Remote on/off adapter PAC-SE55RA-E
Anti-allergy enzyme filter(Air cleaning filter) MAC-415FT-E Air filter PAC-1000FT
Multiple remote controller adapter
PAC-SA88HA-E(1pc.) PAC-725AD(10pcs.)
Multi-functional casement PAC-SG03TM-E High-efficiency filter element PAC-SG01KF (PAC-SG03TM-E is needed.) Grille + Wireless remote controller PLP-6AALM
PLA-RP·AA
Grille + Wired remote controller PLP-6AAMD Air outlet shutter plate (20 set, 2pcs/set) PAC-SG06SP-E
Wireless remote controller + Wireless Adapter PAR-SL99B-E PCA-RP·GA(2)
Drain lift up mechanism PAC-SH20DM-E PCA-RP50,60GA(2)
MFZ-KA·VA SEZ-KA·VA
PAC-SH21DM-E PCA-RP71GA
High-efficiency filter PAC-SE80KF-E PCA-RP50GA(2)
PAC-SE81KF-E PCA-RP60,71GA Motor (for high external static pressure) PAC-SK005MT-F PEAD-RP71EA Drain lift up mechanism PAC-KE03DM-F PEAD-RP·EA, EA2 Insulation kit PAC-SK010DK PEAD-RP·GA
MA & contact terminal interface
MAC-397IF-E
All models
10-2. OUTDOOR UNIT
Part Name Model Name
Applicable model
Drain socket MAC-851DS Drain socket assembly MAC-811DS SUZ-KA50,60,71VA
SUZ-KA25,35VA
Multi-function casement
PAC-SH53TM-E
PAC-SH65OF-E High-efficiency filter element (PAC-SH53TM-E is needed.)
Flange for fresh air intake
PAC-SH59KF-E Decoration panel with wireless remote controller
PLP-6BALM
PLA-RP·BA
Decoration panel with wired remote controller
PLP-6BAM Automatic filter elevation panel
PLP-6BAJ i-see sensor corner panel
PAC-SA1ME-E Wireless signal receiver
PAR-SA9FA-E Space panel
PAC-SH48AS-E Air outlet shutter plate
PAC-SH51SP-E Decoration panel
PLP-6BA
OPTIONAL PARTS
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in May 2007 No.OCS03 REVISED EDITION-A PDF 7 Distributed in May 2006 No.OCS03 PDF 8 Made in Japan
New publication, effective May 2007 Specifications subject to change without notice.
Loading...