13. RoHS PARTS LIST ········································73
14. OPTIONAL PARTS ········································78
Page 2
1
1-1. OUTDOOR UNIT’S SERVICE MANUAL
Service Ref.Service Manual No.
PUH-3VKA.TH
PUH-3YKA.TH
PUH-4/5/6YKSA.TH
REFERENCE MANUAL
OC325
2
Page 3
2
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
door.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To preceding operation
number.
Ventilation button
(
Operation button)
To next operation number.
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Grille
Filter
Removes dust and pollutants
from intake air
Horizontal Air Outlet
Sets airflow of horizontal automatically
during cooling or dehumidifying.
Air Intake
Intakes air from room.
PART NAMES AND FUNCTIONS
● Indoor Unit
● Wired remote controller
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttons
3
Page 4
● Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
● If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not
present at the parent unit.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
4
Page 5
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, blowing, heating and auto
mode.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating mode is not available.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
● Wireless remote controller
5
Page 6
3
PLH-3AAK.UK/ PLH-3AAKH.UK
Cooling
26,300
7,700
3.32
0.17
0.81
1.00
UNIT : 840(33-1/6)
UNIT : 840(33-1/6)
UNIT : 258(10-1/8)
UNIT : 24(53) [26(57)]
3.15
13.82/5.16
58/37
Heating
28,700[35,800]
8,400[10,500]
3.11[5.21]
0.17[2.27]
0.81[9.47]
1.00[9.7]
PANEL : 950(37-3/8)
PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
2.94
12.89/4.81
58/37
PLH-3AAK.UK/ PLH-3AAKH.UK
Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.07
15-20(530-705)
0(direct blow)
[2.1]
Remote controller & built-in
28-34
32(1-1/4)
PUH-3VKA.TH/PUH-3YKA.TH
Single, 50Hz, 220-240V/3, 50Hz, 380-415V(4wires)
Munsell 3Y 7.8/ 1.1
Capillary tube
Hermetic
NH52VNHT/NH52YDAT
2.2/2.4
Line start
w1
Plate fin coil
Propeller (direct) o 1
0.085
50(1764)
Reverse cycle
52
870(34-1/4)
295+24 (11-5/8 add 1)
850(33-1/4)
75(165)
R-22
3.2(7.1)
1.6<MS-32>
9.52 (3/8)
15.88(5/8)
Flared
Flared
Max. 50m
Max. 50m
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Heat exchanger
Fan
Booster heater
Operation control & Thermostat
Noise level (Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan (drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
Oil<Model>
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/ min (CFM)
Pa
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
kW
K/ min (CFM)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
SPECIFICATIONS
w1 V …Internal Thermostat, HP switch
Notes:Rating condition (ISO T1<JIS B8616>)
Y…Anti-phase protector, thermal relay, thermal switch, HP switch
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Heating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°C
Refrigerant piping length(one way):5m(16ft)
6
Page 7
Item
Function
Capacity
Total input
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat
Noise level (Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
PIPING
Connection method
Fan (drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
Oil<Model>
REFRIGERANT
Between the indoor & outdoor units
Service Ref.
K/ min (CFM)
W
D
H
K/ min (CFM)
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Btu/h
W
kW
kW
A
A
kW
Pa
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
PLH-4AAK.UK/ PLH-4AAKH.UK
Cooling
33,100
9,700
3.46
PLH-4AAK.UK/ PLH-4AAKH.UK
Single, 50Hz, 220-240V
0.26
1.25
2.0
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.120
20-28(705-990)
0(direct blow)
[2.6]
Remote controller & built-in
33-41
32(1-1/4)
UNIT : 840(33-1/6)
UNIT : 840(33-1/6)
UNIT : 298(11-3/4)
UNIT : 30(66)[32(71)]
PUH-4YKSA.TH
3, 50Hz, 380V-415V(4wire)
3.20
5.24
40
Munsell 3Y 7.8/ 1.1
Capillary tube
Hermetic
NH56YDAT
2.7
Line start
Anti-phase protector, Thermal relay, Thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.065+0.065
95(3550)
Reverse cycle
54
870(34-1/4)
295+24(11-5/8 add 1)
1258(49-1/2)
94(207)
R-22
4.2(9.2)
1.6<MS-32>
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Heating
35,500[44,400]
10,400[13,000]
3.45[6.05]
0.26[2.86]
1.25[11.93]
2.0[12.7]
PANEL : 950(37-3/8)
PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
3.19
5.22
40
Notes:Rating condition (ISO T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Heating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°C
Refrigerant piping length(one way):5m(16ft)
7
Page 8
Cooling
42,300
12,400
4.51
0.30
1.43
2.0
UNIT : 840(33-1/16)
UNIT : 840(33-1/16)
UNIT : 298(11-3/4)
UNIT : 30(66) [32(71)]
4.21
6.89
53
Heating
47,800[58,000]
14,000[17,000]
4.46[7.46]
0.30[3.30]
1.43[13.77]
2.0[14.3]
PANEL : 950(37-3/8)
PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
4.16
6.81
53
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Heat exchanger
Fan
Booster heater
Operation control & Thermostat
Noise level (Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan (drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
Oil<Model>
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/ min (CFM)
Pa
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
kW
K/ min (CFM)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
PLH-5AAK.UK/ PLH-5AAKH.UK
PLH-5AAK.UK/ PLH-5AAKH.UK
Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.120
22-30(775-1,060)
0(direct blow)
[3.0]
Remote controller & built-in
35-43
32(1-1/4)
PUH-5YKSA.TH
3, 50Hz, 380-415V(4wire)
Munsell 3Y 7.8/ 1.1
Capillary tube
Hermetic
ZR61KC-TFD
3.5
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.085+0.085
95(3550)
Reverse cycle
55
970(38-3/16)
345+24(13-9/16 add 1)
1258(49-1/2)
114(251)
R-22
5.4(11.9)
2.130<SONTEX-200LT>
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Notes:Rating condition (ISO T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Heating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°C
Refrigerant piping length(one way):5m(16ft)
8
Page 9
Item
Function
Capacity
Total input
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat
Noise level (Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
PIPING
Connection method
Fan (drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
Oil<Model>
REFRIGERANT
Between the indoor & outdoor units
Service Ref.
K/ min (CFM)
W
D
H
K/ min (CFM)
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Btu/h
W
kW
kW
A
A
kW
Pa
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
PLH-6AAK.UK/ PLH-6AAKH.UK
Cooling
47,800
14,000
5.07
PLH-6AAK.UK/ PLH-6AAKH.UK
Single, 50Hz, 220-240V
0.34
1.64
2.0
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.120
22-30(775-1,060)
0(direct blow)
[3.0]
Remote controller & built-in
37-45
32(1-1/4)
UNIT : 840(33-1/16)
UNIT : 840(33-1/16)
UNIT : 298(11-3/4)
UNIT : 32(71)[34(75)]
PUH-6YKSA.TH
3, 50Hz, 380-415V(4wire)
4.73
7.74
74
Munsell 3Y 7.8/ 1.1
Capillary tube
Hermetic
ZR68KC-TFD
4.0
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Condensing temperature
Suction temperature
Ref. pipe length
Intake air
temperature
Discharge air temperature
Intake air
temperature
SHF
BF
Mode
Total
W
kW
V
A
V
A
MPa
(kgf/F)
MPa
(kgf/F)
°C
°C
°C
m
°C
°C
°C
°C
°C
PLH-3AAK.UK
PLH-3AAKH.UK
PLH-4AAK.UK
PLH-4AAKH.UK
PLH-5AAK.UK
PLH-5AAKH.UK
PLH-6AAK.UK
PLH-6AAKH.UK
Service Ref.
Cooling
7,700
3.32
Heating
8,400
3.11
13.82/5.16
2.01
(20.5)
0.51
(5.2)
84
41
3.9
5
27
19
13.2
35
24
0.74
0.12
12.89/4.81
1.89
(19.3)
0.42
(4.3)
77
—
-2.0
5
20
15
42.8
7
6
—
—
0.810.81
PLH-3AAK.UK
PLH-3AAKH.UK
1, 50
240
PLH-4AAK.UK
PLH-4AAKH.UK
1, 50
240
PLH-5AAK.UK
PLH-5AAKH.UK
1,50
240
PLH-6AAK.UK
PLH-6AAKH.UK
1,50
240
PUH-3VKA.TH
PUH-3YKA.TH
1/3,50
240/415
Cooling
9,700
3.46
Heating
10,400
3.45
5.24
1.81
(18.5)
0.49
(5.0)
80
41
10.5
5
27
19
13.7
35
24
0.79
0.08
5.22
1.73
(17.6)
0.36
(3.7)
75
—
1.0
5
20
15
39.9
7
6
—
—
1.251.25
PUH-4YKSA.TH
3,50
415
Cooling
12,400
4.51
Heating
14,000
4.46
6.89
1.85
(18.9)
0.44
(4.5)
76
46
4.0
5
27
19
12.5
35
24
0.73
0.10
6.81
1.94
(19.8)
0.36
(3.7)
81
—
1.1
5
20
15
45.5
7
6
—
—
1.431.43
PUH-5YKSA.TH
3,50
415
Cooling
14,000
5.07
Heating
16,100
4.92
7.74
1.90
(19.4)
0.42
(4.3)
74
39
4.6
5
27
19
11.2
35
24
0.71
0.06
7.50
2.01
(20.5)
0.37
(3.8)
76
—
0.3
5
20
15
49.8
7
6
—
—
1.641.64
PUH-6YKSA.TH
3,50
415
Electrical circuitRefrigerant circuit
Indoor
side
Outdoor
side
D.B.
W.B.
D.B.
D.B.
W.B.
Air flow
Air speed
Coverage range
K/
mim(CFM)
m/W
m
PLH-4AAK.UK
PLH-4AAKH.UK
28(990)
4.9
7.4
PLH-3AAK.UK
PLH-3AAKH.UK
20(705)
4.0
5.7
PLH-6AAK.UK
PLH-6AAKH.UK
30(1,060)
6.6
8.9
PLH-5AAK.UK
PLH-5AAKH.UK
30(1,060)
5.2
7.9
Standard
4-4. STANDARD OPERATION DATA
The unit of pressure has been changed to Mpa based on the international SI system.
FF
The conversion factor is : 1(Mpa)=10.2(kgf/
)
4-5. OUTLET AIR SPEED AND COVERAGE RANGE
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
20
Page 21
4-6. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63125250500100020004000 8000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL,
BAND CENTER FREQUENCIES, Hz
(0dB=0.0002 µ BAR)
PLH-6AAK.UK
PLH-6AAKH.UK
High
NOTCH
Low
45
SPL(dB)
37
LINE
90
80
70
60
50
40
30
20
10
63125250500100020004000 8000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, (0dB=0.0002 µ BAR)
BAND CENTER FREQUENCIES, Hz
PLH-5AAK.UK
PLH-5AAKH.UK
High
NOTCH
Low
43
SPL(dB)
35
LINE
PLH-3AAK.UK
PLH-3AAKH.UK
NOTCH
High
Low
SPL(dB)28LINE
34
PLH-4AAK.UK
PLH-4AAKH.UK
NOTCH
High
Low
SPL(dB)
41
33
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, (0dB=0.0002 µ BAR)
90
80
70
60
50
40
30
APPROTIMATE
20
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
10
63125250500100020004000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
(0dB=0.0002 µ BAR)
50
40
30
APPROTIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL,
REARING FOR
CONTINUOUS
NOISE
10
63125250500100020004000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
21
Page 22
UNIT
1.5m
MICROPHONE
CEILING
Ambient temperature 27:
22
Page 23
5
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipe
VP-25connection
(O.D.{32)
Branch duct hole
(Cut out hole)
Ceiling surface
Suspension bolt pitch
Ceiling hole
Branch
duct hole
Suspension bolt pitch
Ceiling hole
Air outlet hole
Air intake hole
411
Air intake hole
Air intake grille
Receiver
Operation lamp
DEFROST/STAND BY lamp
Emergency operation switch (cooling)
High efficiency filter
& Fresh air intake casement (option)
1.For details on how to operate self-diagnosis with the wireless remote control, refer to the
technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the
remote control, the unit begins self-diagnosis.
and Check Codes generated in the past appear on the display.
For Check Codes and symptoms refer to the table below.
Check Code
P1
P2
P4
P5
Abnormality of room temperature thermistor (TH1).
Abnormality of pipe temperature thermistor/Liquid (TH2).
Abnormality of drain sensor (DS).
Malfunction of drain-up machine.
Symptom
P6
Freezing / overheating protection is working.
P8
E0-E5
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
Abnormality of the signal transmission between remote controller and indoor unit.
----
FFFF
No trouble generated in the past.
No corresponding unit.
Fb
Abnormality of indoor controller board.
[Emergency operation procedure]
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work
if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly
Emergency Operation.
WNote on the wireless remote control: when the remote control does not function, it is possible to
activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the
wireless signal receiver board).
However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and
3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) and
switch (SW6) on the indoor controller.
SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working.
SW6-1 : ON • Emergency operation of cooling mode.
SW6-1,2 : ON • Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the
remote control or temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of
the heating is activated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc.to their original positions.
(6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (8-3).
Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (8-4).
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (8-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit
OC: Outdoor unit
E Check code
F Unit No.
G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen.
2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
TROUBLESHOOTING
8-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are
summarized in the table below. Check the contents below before investigating details.
8-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
■ Wired remote controller
28
Page 29
<Malfunction-diagnosis method at maintenance service>
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Address
display
HOUR
button
ON/OFF
button
[Output pattern A] Errors detected by indoor unit
*1If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp flash
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
Beeper sounds/OPERATION
INDICATOR lamp flashes1 Check code
SymptomRemark
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
2
P2Pipe (TH2) sensor error
4P4Drain sensor error
5
P5
PA
Drain pump error
Forced compressor stop
6P6Freezing/ Overheating safeguard operation
8P8Pipe temperature error / Outdoor unit error
9E4, E5Remote controller signal receiving error
10
–
11
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
–E1, E2Remote controller control board error
Remote controller transmission error
■ Wireless remote controller
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• Select the address of the indoor unit
for the self-diagnosis.
Main indoor unit : “00”
Sub indoor unit : “01”
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
29
Page 30
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Opration lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes following power-on
After about 2
minutes has
expired following power-on
• For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block
•Incorrect wiring between indoor and outdoor
units
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
•
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
30
Page 31
8-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method
Abnormality of room temperature
thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: 90: or more
Open: -40: or less
Abnormality of pipe temperature
thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature
of 90: or more or -40: or
less.
5 Defective indoor controller board.
Countermeasure
1–3 Check resistance value of thermistor.
0: ······15.0k"
10: ····9.6k"
20: ····6.3k"
30: ····4.3k"
40: ····3.0k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be
detected.
(CN20)
(CN21)
8-7
. Turn
on
on
2 Check contact failure of connector
the indoor controller board. Refer to 8-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector
the indoor controller board. Refer to
the power on and check restart after inserting
connector again.
4
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is exclusively low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive
difference with actual pipe <liquid> temperature
replace indoor controller board.
,
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pump operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
0: ······6.0k"
10: ····3.9k"
20: ····2.6k"
30: ····1.8k"
40: ····1.3k"
2 Check contact failure of connector
the indoor controller board. Refer to
the power on again and check restart after
inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
Check the setting of lead wire of drain senso
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 8-7.
Turn the power off, and on again to operate
after check.
(CN31)
8-7
. Turn
on
r
31
Page 32
Error Code
P6
Meaning of error code and detection method
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention
mode if pipe temperature stays under
-15: for three minutes, three minutes
after the compressor started. Abnormal
if it stays under -15: for three minutes
again within 16 minutes after six-minute
resume prevention mode.
<Frost prevention mode>
If pipe temperature is 1: or below
when 16 minutes has passed after compressor starts operating, unit will start
operating in frost prevention mode which
stops compressor operation. After that,
when pipe temperature stays 10: or
more for 3 minutes, frost prevention
mode will be released and compressor
will restart its operation.
2 Overheating protection (Heating mode)
The units is in six-minute resume
prevention mode if pipe temperature is
detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again
within 10 minutes after six-minute
resume prevention mode.
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Over-load (high temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
8 Bypass circuit of outdoor unit
Cause
operation beyond the tolerance
range
defective.
(clogs)
operation beyond the tolerance
range
defective.
(clogs)
is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 8-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's
winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 8-7.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
P8
Abnormality of pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes later of compressor start and 6 minutes later of the liquid pipe is out of cooling
range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -5 deg ] (TH2-TH1)
TH2: Liquid pipe temperature
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when
condenser/evaporator pipe temperature is
not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range : 5 deg [ (TH2-TH1)
Abnormality in outdoor unit
1 Slight temperature difference
between indoor room
temperature and pipe temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase
3 Protection device is working
4 Damaged outdoor coil thermis-
tor
1~4 Check pipe temperature with room
temperature display on remote
controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
1 Check the indoor/outdoor connecting wire.
2 Change the connection of electric wiring.
3 Check the protection device.
4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal,
replace the outdoor controller board.
32
Page 33
Error Code
E0
or
E4
E3
or
E5
Meaning of error code and detection method
Remote controller transmission
error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any
transmission from indoor unit of refrigerant address “0” for three minutes.
(Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two minutes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from
remote controller board or from other
indoor controller board for three minutes.
(Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two
minutes. (Error code: E4)
find blank of transmission path for six
seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
1 Contact failure at transmission
2 All remote controllers are set
3 Mis-wiring of remote controller.
4 Defective transmitting receiving
5 Defective transmitting receiving
6 Noise has entered into the
1 Two remote controller are set
2 Remote controller is connected
3 Repetition of refrigerant
4 Defective transmitting receiving
5 Defective transmitting receiving
6 Noise has entered into trans-
Cause
wire of remote controller
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
circuit of remote controller
circuit of indoor controller board
of refrigerant address “0”.
transmission wire of remote
controller.
as “main.”
(In case of 2 remote con-
trollers)
with two indoor units or more.
address.
circuit of remote controller.
circuit of indoor controller
board.
mission wire of remote con-
troller.
Countermeasure
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max.500m
(Do not use cable x 3 or more)
• The number of connecting indoor units:
max.16units
• The number of connecting remote con-
troller: max.2units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Put the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
[ c),d)→Noise may be causing abnormality. ]
∗ If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
1 Set a remote controller to main, and the
other to sub.
Remote controller is connected with only one
2
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem.
Put the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG”is displayed, replace
remote controller.
c)When “RC E3”or “ERC 00-66”is displayed,
noise may be causing abnormality.
33
Page 34
Error Code
Fb
E1
or
E2
PA
(2502)
(2500)
Meaning of error code and detection method
Abnormality of indoor controller board
Abnormal if data cannot be normally read
from the nonvolatile memory of the indoor
controller board.
Abnormality of remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Forced compressor stop
(due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor is detected whether
it is soaked in the water or not at the interval
of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be
soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection
is performed.
a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be
less than -10: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
liquid pipe temperature thermistor detection is defective.
Countermeasure
1 Replace indoor controller board.
1Check the drain pump.
Please confirm whether water can be drained.
2
3Confirm the resistance of the drain sensor.
4Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
34
Page 35
8-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Cause
Countermeasure
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected.
Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected.
Check the fuse on indoor controller
board.
Check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
• When no voltage output.
Check the wiring connection between
CNDK on indoor controller board and
CNSK on indoor power board.
If no problem are found,indoor power
board is defective.
• When DC12.5~13.7V is detected.
Check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found,indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant
system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires
4 Defective remote controller
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit.
Set main/sub using SW5-3 on indoor
controller board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller
board.
• When LED2 is blinking, check the shortcut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoor
connecting wires again, and; if LED2 is
blinking, outdoor unit’s controller board is
defective; if LED2 is lit, connection failure
of indoor/outdoor terminal block etc. has
returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
35
Page 36
Phenomena
4 After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage,
looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
4 Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M".
4 Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0M".
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
A ON/OFF button
B Test run display
C Indoor temperature liquid line
temperature display
D ON/OFF lamp
E Power display
F Error code display
Test run remaining time display
G Set temperature button
H Mode selection button
I Fan speed button
M TEST button
1 Turn on the power at least 12 hours before the test run.
2 Press the [TEST] button twice. ➜ "TEST RUN" liquid crystal display
3 Press the [Mode selection] button. Make sure that wind is blown out.
4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
➜ Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. ➜ Make sure that the wind speed is switched.
6 Check operation of the outdoor unit fan.
7 Release test run by pressing the [ON/OFF] button. ➜ Stop
8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in
HEAT mode. (Working of COOL protection function)
Cause
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board.
8-5. TEST RUN AND EMERGENCY OPERATION
8-5-1. Before test run
Countermeasure
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
8-5-2. Test run (Using wired remote controller)
36
Page 37
1 Turn on the power to the unit at least 12 hours before the test run.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.)
A and current operation mode are displayed.
TEST RUN
TEST RUN
3 Press the button to activate mode, then check whether
cool air is blown out from the unit.
MODE
4 Press the button to activate mode, then check whether
cool air is blown out from the unit.
MODE
COOL
HEAT
5 Press the button and check whether fan speed changes.
FAN
6 Press the button and check whether the auto vane operates properly.
VANE
7 Press the ON/OFF button to stop the test run.
Note:
•
Point the remote controller towards the indoor unit receiver while following steps 2 to 6.
• It is not possible to run the in FAN or DRY mode.
Receiver
Operation lamp
Emergency operation switch (cooling)
Emergency operation switch (heating)
Mode
Cooling
Heating
Set temperature
Fan speed
Airflow direction
24:
High
Downward (70deg)
24:
High
Horizontal (30deg)
wEmergency operation will be performed as follows.
8-5-3. Test run (Using wireless remote controller)
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work
if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly
Emergency Operation.
WNote on the wireless remote control: when the remote control does not function, it is possible to
activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the
wireless signal receiver board).
However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and
3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) and
switch (SW6) on the indoor controller.
SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working.
SW6-1 : ON • Emergency operation of cooling mode.
SW6-1,2 : ON • Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the
remote control or temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of
the heating is activated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc.to their original positions.
(6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.
A
TEST RUN
ON/OFF TEMP
7
FAN
AUTO STOP
3,4
VANE
MODE
LOUVER
CHECK
TEST RUN
2
RESETSETCLOCK
AUTO START
h
min
5
6
8-5-4. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
• Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation
• Press either emergency operation switch (cooling/heating).
8-5-5. When wired remote controller or indoor unit micro computer troubles
37
Page 38
8-6. HOW TO CHECK THE PARTS
Parts nameCheck points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature20:)
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor/liquid(TH2)
1
3
YLW
YLW
1
2
3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
NormalAbnormal
15k"Open or short
NormalAbnormal
290"Open or short
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
CN2D
Connect to the indoor
power board (CN2S)
(12.5~13.7V DC)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
SW6
Emergency operation
LED1
Power supply (I.B)
LED2
Power supply (R.B)
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN30
Transmission
(indoor/outdoor)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
FUSE
(6.3 A 250 V)
CND
Power supply input
(220~240V AC)
CNC
Dew prevention heater
(H2)
(220~240V AC)
CNP
Drain-pump output
(DP)
(220~240V AC)
SWE
Emergency operation
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
CN105/CN92
(RED)
CN51
Centrally control
CN24
Heater output
(12V DC)
CN32
Remote switch
CN2L
Connector
(LOSSNAY)
FAN
Fan motor output
Jumper wire J41, J42
Pair number setting with
wireless remote controller
41
SW2
Capacity setting
SW5
System setting
SW1
Model setting
Page 42
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model
settings
SW5
System
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Remarks
SW2
J41
J42
0
1
2
3 ~ 9
Wireless remote
controller setting
Control PCB setting
J41J42
<Settings at time of factory shipment>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disconnected.)
SW5-3 Main/Sub setting
OFF : Main ON : Sub
SW5-4 Rotaion operation setting
OFF : Not avairable ON : avairable
MODELSSW1
MODELSSW5
MODELSSW2
1 2 3 4 5
ON
OFF
PLH-AAK.UK
1 2 3 4 5
ON
OFF
PLH-3AAK.UK
PLH-3AAKH.UK
PLH-4AAK.UK
PLH-4AAKH.UK
PLH-5AAK.UK
PLH-5AAKH.UK
PLH-6AAK.UK
PLH-6AAKH.UK
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
PLH-AAKH.UK
12345678
12345678
ON
OFF
PLH-AAK.UK
ON
OFF
PLH-AAKH.UK
8-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
4242
Page 43
8-9 OUTDOOR UNIT SERVICE FUNCTIONS (OUTDOOR CONTROLLER BOARD)
(1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
● During HEAT mode
● The compressor is ON.
● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
● The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2
fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again.
2SW3 setting is changed.
3The compressor stops.
4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch)
SW2: Switches the output state indication and the check code display (push-button switch)
SW3-1,2: Switches the output state indication items (dip switch)
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting.
Open-circuit of CN22 restarts the normal fan control.
(5) Time shortening
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds → 3 seconds
2Three-minutes time delay function : 3 minutes → 3 seconds
3Max. time of defrosting : 15 minutes → 15 seconds
4Defrost interval : 30 ~ 120 minutes → 3 ~ 12 seconds
5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes → 3 seconds
6Compressor ON time to start other functions : x minutes → x seconds
7Crankcase heater operation : 1 hour → 6 seconds
(6) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and 1hour OFF, after the compressor stops.
2
Fan speed when theExtra low1
heating thermostat is OFF
Stop
252
Set fan speed
3
Quiet operation modeDisabled (Standard
)
26
1
--- -
of PLH-AAK(H) (Fan speed)Enabled (Quiet operation mode
)
2
--- -
Fan speed when the
Set fan speed
27
1
cooling thermostat is OFFStop
2
Detection of abnormality ofAvailable
28
1
the pipe temperature (P8)Not available
2
}
PLH-AAK(H)
PLH-KAK(H)
-
-
-
-
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
LOSSNAY
connectivity
Power supply
voltage
Frost prevention
temperature
Humidifier control
Rotation
OFF
ON
Indoor unit's (Main) internal sensor
Remote controller's internal sensor w1
Not supported
Supported (indoor unit not equipped with outdoor air intake)
Supported (indoor unit equipped with outdoor air intake)
240V
220V,230V
1: (Normal)
-3:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
24h cycle
168h cycle
Back up function
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
3
01
02
03
04
15
16
20
The setting is
applied to all
the units in the
same
refrigerant
system.
FUNCTION SETTING
9-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-02 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number.
• When setting functions for a simultaneous- Twin indoor unit system, set the unit number to 01 to 02 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
44
Page 45
Rotation setting (Function setting mode No.20
)
Function setting
FeaturesIndoor controller board
Mode No.
This system can correspond only by the pattern of two refrigerant group by 1 : 1
(indoor and outdoor unit combination) systems.
Setting No.
SW5-3 setting SW5-4 setting
20
01
(
24hours cycle
)
02
ON
OFF : Main
ON : Sub
(
168hours cycle
)
03
(
Back up
function
)
When abnormality occurs while
operating, it changes as a back up unit
,
and operating continues.
Each system operates alternately for
24hours.
Each system operates alternately for
168hours.
Example of unit's operation
(Setting No. = 01 or 02)
Main Unit is abnormal
Operation starts Main➝SubSub➝Main
(Setting No. = 02
• • •
168hours cycle)
Outdoor
unit
(Setting No. = 03)
Main Unit is abnormal
Indoor
Operation startsMain➝Sub
unit
Remote
Controller
Main➝Sub
ON
OFF
OFF
Main
ON
OFF
ON
ON
OFF
9-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room
temperature detection position is given.
For actual operations, refer to steps 1 to 0 .
Setting number
AddressUnit number
Mode number
F
E
G
C
D
J
B
A
I
Modes 01 to 14 can be activated
by pressing buttons
A
and
B
simultaneously, and modes 15 to
28 by pressing buttons
B
and J.
indoor
unit
Sub
indoor
unit
24h24h
Main
Main
indoor
unit
Sub
indoor
unit
Sub
45
Page 46
Selecting functions using the wired remote controller
The above procedure must be carried out only if changes are necessary.
1 : 1 systemSimultaneous twin systemRotation system
Indoor unit
address = 00
unit No. = 01
Main indoor unit
address = 00
unit No. = 01
Sub indoor unit
address = 01
unit No. = 02
Outdoor unit
Indoor unit
Remote controller
Outdoor unitOutdoor unitOutdoor unit
Main
indoor unit
Sub
indoor unit
Remote controller
Main indoor unit
address = 00
unit No. = 01
Sub indoor unit
address = 01
unit No. = 01
Main
indoor unit
Sub
indoor unit
Remote controller
1
Check the function selection setting.
2
Switch to function setting mode.
(Press
A
and B at the same time
For modes 15 and higher,
press
with the remote controller stopped.)
3
Specify address
(Use
C
4
Specify unit No.
and D.)
Refer to address unit No. to the figure below
J
and B at the same time.
5
Enter the setting.
(Press
6
Select mode No. 02
E
.)
(Specified indoor unit:
BLOW operation)
(room temperature detection position).
7
Select setting No. 03 (remote controller fixed).
(Use
F
and G.)
8
Enter the setting.
(Press
E
.)
Example:
Selecting room temperature
detection position
NO
Finished
YES
0
Ending function display
(Press
A
and B at the same time.)
NO
YES
Change refrigerant
address unit No.
9
46
Page 47
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2
to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
B ( mode 15 or more) and
buttons
simultaneously for at least two seconds.
will start to flash,
and then the remote controller's display content will change as shown below.
3 Set the outdoor address.
C Press the [ CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
* If the unit stops after
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
Check to see if there are any sources of noise or interference near the transmission path.
Note :
If you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2.
4 Set the indoor unit number.
D Press the
button so that " - -" flashes in the unit number display
area.
C Press the [
CLOCK] buttons ( and ) to select the unit number
of the indoor unit for which you want to perform function selection. The unit
number changes to "00", "01", "02","03",04" and "AL" each time a button is
pressed.
* To set modes 01 to 06 or 15 to 22 select unit number "00".
* To set modes 07 to 14 or 23 to 28 carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.
E Press the
button to confirm the address and unit
number.
After a while, "- - " will start to flash in the mode number display area.
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
helps you find the location of the indoor unit for which you want to perform function
selection. However, if "00" or "AL" is selected as the unit number, all the indoor
units corresponding to the specified address will start fan operation.
*"88" will flash in the room temperature display area if the selected address
does not exist in the system.
Furthermore, if
"F"
appears and flashes in the unit number display area and the
address display area also flashes, there are no units that correspond to the
selected unit number. In this case, the address and unit number may be incorrect,
so repeat steps 2 and 3 to set the correct ones.
* When grouping different systems, if an indoor unit other than the
one to which the address has been set performs fan operation,
there may be another address that is the same as the specified one.
In this case, check the DIP switch of the outdoor unit to see
whether such a address exists.
6 Select the mode number.
F Press the [
TEMP] buttons ( and ) to set the desired mode
number.
(Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
button. The currently selected setting number will
flash, so check the currently set content.
F Press the [
TEMP] buttons ( and ) to select the desired setting
number.
8 Register the settings you have made in steps 3 to 7 .
E Press the
button. The mode number and setting number will start
to flash and registration starts.
The mode number and setting number will stop flashing and remain lit, indicating the
end of registration.
* If " - - - " is displayed for both the mode number and setting number and "
" flashes in the room temperature display area, a transmission error may have occurred.
Check to see if there are any sources of noise or interference near the transmission path.
9 If you wish to continue to select other functions, repeat steps 3 to 8 .
0 Complete function selection.
A Hold down the
buttons simultaneously for at least two seconds.
After a while, the function selection screen will disappear and the air conditioner OFF screen will reappear.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
Note :
If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check"
column of Table 1 to indicate the change.
Unit number
display section
Mode number
display section
00 address
Indoor unit
Fan draft
Remote controller
MainSub
Outdoor unit
Designate operation
Example) When the address is set to 01 and the unit number is 02.
Mode number
display section
Mode number 02 = Indoor temperature detection
Setting number display section
Setting number 3 = Remote controller built-in sensor
Setting number 1 = Indoor unit operating average
( mode 15 or more) and
FILTER
Address
display section
FUNCTION
SELECTION
FUNCTION
SELECTION
TEST
ON/OFF
MODE
MENU
MODE
MODE
FILTER
TEST
47
Page 48
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn
off the function that raises the set temperature by 4 degrees during HEAT operation .
The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode.
(Enter address "50" in troubleshooting
mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when
you press the INSPECT button twice to display
"INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation
area, the unit ends function selection mode
automatically if nothing is input for 10 minutes
or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change
unit No.
YES
NO
7
9-1-2. Selecting functions using the wireless remote controller
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refrigerant system with wireless function. Address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings.
2 Press the button twice continuously. → CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press
the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation.
Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same
refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number.
Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number.
7 Repeat steps 3 to 5 to change unit number and make function settings on it.
8 Complete the function settings
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
The setting of the following remote controller functions can be changed using the remote controller function selection mode.
Change the setting when needed.
Item 1
1.Change Language
("CHANGE LANGUAGE")
2.Function limit
("FUNCTION SELECTION")
3.Mode selection
("MODE SELECTION")
4.Display change
("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (: or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
[Function selection flowchart] Refer to next page.
[1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting.
(Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔➔
➔➔
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2English (GB), 3 German (D), 4 Spanish (E),
5 Russian (RU), 6 Italian (I), 7 Chinese (CH),8 French (F)
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button.
1 no1: Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons.
3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER]
and [ ON/OFF] buttons at the same time for two seconds.) on
the normal screen after the above setting is made..
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has automatic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button.
1 ON (Initial setting value) : The automatic mode is displayed when
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller.
2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ON/OFF] button.
1 ON : The clock function can be used.
2 OFF:The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [ON/OFF] button (Choose one of
the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button.
1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.
4 OFF (initial setting) : The temperature range limit is not active.
*
When the setting, other than OFF, is made, the temperature range limit setting
on cooling, heating and automatic mode is made at the same time. However
the range cannot be limited when the set temperature range has not changed.
•
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
•
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
CALL_: The contact number can be set when the display is as
shown on the left.
• Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and
(
)] button to move the cursor to the right (left). Press the [CLOCK
(
) and ( )] button to set the numbers.
[4] -4. Display change setting
(1) Temperature display :/ F setting
• To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used.
2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
• To switch the setting, press the [ON/OFF] button.
1 ON : The suction air temperature is displayed.
2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
• To switch the setting, press the [ON/OFF] button.
1 ON : One of "A utomatic cooling" and "A utomatic heating" is display ed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
49
Page 50
Hold down the E button and press the D button for 2 seconds.
Hold down the
E
button and press the D button for 2 seconds.
Remote controller function selection mode
E
Press the operation mode button.
G
Press the TIMER MENU button.
D
Press the TIMER ON/OFF button.
Item1Item2
Dot display
Item3
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed
under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
Normal display
(Display when the air condition is not running)
Change
Language
Function
selection
Mode
selection
Display
mode setting
Operation lock setting is not used.
(Initial setting value)
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is
selected. (Initial setting value)
The automatic mode is not displayed when the operation mode
is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error.
(Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit
:
is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Flowchart of Function Setting
Setting language (English)
E
E
E
G
EN
GE
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
C
ON/OFF
OPERATION
D
E
PAR-21MAA
G
ON/OFF
CHECK
CLEAR
I
FILTER
A
TEST
B
H
JA
D
OFF
D
on1
D
D
D
D
D
on2
ON
D
OFF
OFF
D
G
G
G
G
G
G
D
D
D
E
G
D
D
G
G
D
D
D
G
G
D
D
D
G
G
D
D
D
D
ON
D
OFF
D
OFF
D
CALL-
:
D
°F
ON
D
OFF
ON
D
OFF
50
Page 51
10
Blowout direction
pattern
4-direction<Table 1>3-direction2-directionNote1.
For 3 and 2-directional,
please use the air outlet
shutter plate (option).
Pattern 1 Factory settingPattern 4 One air outlet
fully closed
Pattern 6 Two air outlet
fully closed
Fresh air intake hole
Fresh air intake hole diagram
3 - {2.8
Burring hole
{125
Burring hole pitch
{100
(Cut out hole)
Refrigerant pipeDrain pipe
Ceiling surface
120
_
120_
w158
4-WAY AIR FLOW SYSTEM
10-1. PLACEMENT OF THE AIR OUTLETS
• For this grille, the blowout direction comes in 11 patterns.
Also,by unit function setting by the remote controller, you can adjust the air flow and speed. Select the settings from Table
according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set
the unit function setting by the remote controller.
Correspondence of ceiling heights to numbers of air outlets.
Ceiling height & discharge direction
(Unit : m)
PLH-3AAK(H).UK
4 direction2.7m
3 direction
2 direction
PLH-4, 5, 6AAK(H).UK
4 direction
3 direction
2 direction
Standard
High ceiling 1
3.0m
3.3m3.5m
Standard
High ceiling 1
3.2m
3.6m
4.0m4.2m
3.0m
3.3m
3.6m
4.0m
High ceiling 2
3.5m
3.5m
—
High ceiling 2
4.2m
4.2m
—
10-2. FRESH AIR INTAKE (INSTALLATION OF SITE)
• At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
Note :
Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement
(Option)
51
Page 52
Static pressure [Pa]
Air flow [m
3
/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
123456
Static pressure [Pa]
Air flow [m
3
/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
123456
Static pressure [Pa]
Air flow [m
3
/min]
50
-50
-100
-150
-200
0
123456
Static pressure [Pa]
Air flow
[m
3
/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
123456789
Static pressure [Pa]
Air flow
[m
3
/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
123456789
Static pressure [Pa]
Air flow [m
3
/min]
50
-50
-100
-150
-200
0
123456789
10-3. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
Q
0
B
A
C
1
Curve in the
left praphs.
Duct characteristics
at site
Q
A
EC
2
Q
Qa
AD
3
ll
PLH-3AAK.UK PLH-3AAKH.UK
Multifunction casement + Standard filter
Multifunction casement + High efficiency filter
Taking air into the unit
How to read curves
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust system for air flow amount Q <Pa>
Multifunction casement + Standard filterMultifunction casement + High efficiency filter
<m
3
/mim>
<Pa>
<Pa>
<Pa>
<Pa>
Taking air into the unit
52
Page 53
Fresh air intake hole
Refrigerant pipeDrain pipe
Branch duct hole
(Cut out hole)
Branch duct hole diagram
(view from either side)
Branch
duct hole
{175
Burring hole pitch
{150
Cut out hole
14 - {2.8
Burring hole
350
90
70_
100 100 90
100
130
w155
w167
Branch
duct hole
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m.
CN51
Be sure to secure insulation
material by tape and such
5
Green
Yellow
Orange
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape and such
Installation at site
CN51
on
indoor
controller
board
Red
Brown
1
~
MB
10-4. INTERLOCKING OPERATION METHOD WITH DUCT FAN (BOOSTER FAN)
●Whenever the indoor unit is operating, the duct fan also
operates.
(1)Connect the optional multiple remote controller
adapter(PAC-SA88HA-E)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines.
(w)Use a relay under 1W.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
10-5. BRANCH DUCT (INSTALLATION AT SITE)
Discharge by branch duct becomes possible by installing a branch duce at site. Knockout holes on the wall panel of the indoor
unit must be removed.
Branch Duct Installation Procedure
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
Note :
The figure marked with wwin the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Use of two controllers enables
operation of the air
conditioner both
from a distance
and nearby.
C.Group control
operation
Use of one remote
controller to control multiple air
conditioners with
the same settings
simultaneously.
D.Remote/local
combined control
operation
Allows start/stop
of the air conditioner from a distance, and prohibits/permits start/
stop from remote
controllers.
E.Operation by
external signal
F.
Control and remote
display by external
signal (extraction
of monitor signal)
Enables you to
display the operation state and
control start/stop
from a distance.
• There are two types of remote controllers: wired type
and wireless type.
• Simultaneous twin indoor units are started or stopped
simultaneously.
• Up to two remote controllers can be connected to
one group.
• Simultaneous twin units are counted as each unit.
• Operation control by the latest command (last entered priority)
• Wired and wireless remote controllers can be combined as a pair.
• One group can consist of up to 16 indoor units, and
they can be started sequentially by connecting the
remote controller to them and assigning an address
to each inter face.
• Simultaneous twin units are counted as one unit.
• All the units belonging to the same group are operated in the same mode, but thermostats can be
turned ON/OFF individually for each indoor unit.
• Up to two remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectively
from a distance.
• Operation can be switched between the remote operating panel and local controller.
• Operations (e.g., temperature adjustment, airflow, airflow direction) except for start/stop operations can be
performed even if the remote controller is being operated.
• In the case of simultaneous twin units,connect the controller to one indoor unit only. If connected to two indoor
units, an error (operation stop) may occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote ON/ OFF adapter" enables
remote control via relay. (Level signal)
Extraction of non-voltage contact output
• Use of optional "remote operation adapter" and
"remote display panel" (Part to be provided at your
site) provides non-voltage contact outputs of signals
(opera-tion, error) and operation/stop input function.
Extraction of DC12 V contact output
• Use of optional "multiple remote controller adapter"
and "re
mote display panel" (Part to be provided at
your site)
provides DC12 V contact outputs of
signals (operation, error) and operation/stop input
function.
* One of the wired remote con-
trollers must be set as a sub
remote controller.
Wired remote controller (additional)
(PAR-21MAA)
Inter face MAC-397IF-E
Remote ON/OFF adapter
(PAC-SE55RA-E)
Relay box
(Part to be provided at your site)
Remote operating panel
(Part to be provided at your site)
Remote ON/OFF adapter
(PAC–SE55RA-E)
Remote operation adapter
(PAC-SF40RM-E)
Remote display panel
(Part to be provided at your site)
Multiple remote controller adapter
(PAC-SA88HA)
Remote display panel
(Part to be provided at your site)
external timer,
refer to Remote/
handheld combined control operation".
H.Interlock opera-
tion with peripheral equipment
Enables control of
Mitsubishi Lossnay
ventilator by remote
controller.
I.Rotation
• Weekly timer:
In addition to ON/OFF, up to eight temperature
patterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
performed once within 72 hours (can
be set in 1-hour increments).
• Auto off timer:Operation is stopped when the preset
time elapses following the start of
operation.
The time can be set from 30 minutes
to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
• Connecting a Lossnay ventilator and an indoor unit
enables control of interlock/solo ventilation operation and airflow.
(Only the microcomputer type Lossnay ventilator
can be used.)
•
•
MA Remote controller
(PAR-21MAA)
When abnormality occurs while operating, it changes
into operating the back up unit, and operating is
continued.
(Unit function Mode No. 20 setting No.3 , Indoor
controller board SW-5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
Each system operates alternately for 24 hours or 168
hours.
(Unit function Mode No. 20 setting No.1: 24 hours/
No.2 : 168 hours, Indoor controller board SW 5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
This system can correspond only by
the pattern of two refrigerant group
by 1 : 1 (indoor and outdoor unit
combination) systems.
• Remote controller cable terminal block
1,2 (No polarity)
(2) Wireless remote controller
(Reference)
1 If simultaneous twin, connect the remote controller to an indoor unit. All functions of the indoor unit can control even if
different models (different types) are mixed. Note that there may be some restrictions of the functions.
2 Electrical wiring diagram
58
Page 59
11-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
(R: Wired remote controller)
Slim Air Conditioner System
Standard 1:1Simultaneous Twin
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some function may
be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
3 Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of
different models. However, some functions may be restricted.
2
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring
.
In the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with
3
systems consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the
pair numbers will be "0" (factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since
the operation made last by any of the remote controllers will be effective.
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless
remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system
consists of different models. However, some functions may be restricted.
2
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
3
When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
operation made last by any of the wireless remote controllers will be effective.
(R': Wireless remote controller receiver)
2
2
2
Remote controller cable
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor/outdoor
connection cable
OC
Remote
controller
cable
R-1
3
IC
2
2
R-2
Indoor/outdoor
connection cable
Receiver
connection
cable
OC
3
IC-1
R'-1
IC-2
99
R'-2
Remote
controller
cable
OC
3
IC
Receiver
connection
9
2
cable
R
R'
Indoor/outdoor
connection cable
59
Page 60
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the
connecting cable used for each system.
• The cables connected to the Indoor unit should be mounted on or near the Indoor unit.
If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
• Set the interface dip switch (SW500–502) settings before turning on the power.
• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
11-4. GROUP CONTROL OPERATION
COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16)
●
●
●
●
Group control can be operated by using MAC-397IF-E.
The setting of wired remote controller is subjected to variation according to the function of the indoor unit.
(for mode operation, setting temperature, fan step, air direction)
The display of remote controller and operating the indoor unit might be different.
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
Indoor control board
INDOOR
CN105
CN92
or
Connect the connecting cable that comes with the
interface unit to the connector
CN105 or CN92 on the indoor control board.
Mounting screws (black) 3.5 o 12
Interface unit mounting cord clamp or mounting
cord clamps
Connecting cable for each system
Mounting cord clamp
Electrical wire mounting
bracket
Mounting screws 4 o 16
Mounting screws 4 o 10
Mounting cord clamp
60
Page 61
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller..
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10: and 38:.
CN560
TB580
2
1
2
A
B
Indoor unit
Remote control cord that came with
the MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set.
SW501:
SW501- No. 1-4: Refrigerant address
• Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
• Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1
234
ON
1
234
ON
1
234
ON
1
234
1Outdoor unit
2Outdoor unit
3Indoor unit
4Interface
5MA remote controller
Refrigerant
address
0
1
2
15
Interface unit
Refrigerant
address "0"
Refrigerant
address "1"
Refrigerant
address "2"
MA remote controller
(PAR-21MAA)
* PAR-20MAA cannot be used
with this interface.
SW501- No. 5–6
ON
5
6
In case of connecting MAC-397IF-E to this model,
No. 5 should be set to OFF and No.6 should be set to ON.
112
3333
4
5
44
61
Page 62
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1
No. 2
No. 3
No. 4
FunctionsOFFONComments
Only specify these settings when connecting an
MA remote controller.
Functions
Room temperature detector
The model of Mr. SLIM exists in the
same group.
This should be set to ON.
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
Refrigerant address 0
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
OFF
Indoor unit
Not mixed
ON
Remote control
Mixed
Comments
This should be set to OFF.
SW No.
No. 5
No. 6
62
Page 63
SW502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
Cooling only type/ Heat pump type
Auto mode
Fan speed
Functions
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
4 speeds
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
3 speeds (2-speed
model set ON)
Comments
Set the mode in accordance with the operation
manual for the indoor unit.
Heat pump type : Set to ON.
Cooling only type : Set to OFF.
Set to OFF.
When operating a 2-speed model with the 3-speed
setting (ON), the MA remote controller display will
indicate 3 fan speeds.
The table below shows the displays and the actual
outputs at that time.
DisplayMeaningIndoor unit output
Low speedLow speed
Medium speedHigh speed
High speed
High speed
No. 5
Vane
No. 6
Swing
No. 7
Not in use
No. 8
Fan mode
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
Available
Available
–
Not available
Not available
Not available
–
Available
The Vane function of either of indoor unit :
When the function is provided, it is Available (OFF).
When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit :
When the function is provided, it is Available (OFF).
When the function is not provided, it is Not available (ON).
Permanently set to OFF.
Set to ON.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
DC 12 V is not being supplied from the
air conditioner.
Device is not communicating properly
with the air conditioner.
Device is not communicating properly
with the MA remote controller.
Lamp off
DC 12 V is being supplied from the air
conditioner.
* Use the table above to check the device operations.
4. Mounting the Remote Control Interface Unit
Lamp on
–
–
Blinking at approx. 1 second intervals: Device is
communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is communicating normally with the MA remote controller.
Blinking
–
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit.
The device will not function properly if the connecting cable is extended so the connecting cable should not be extended.
Mount the interface unit securely to a pillar or wall using 2 or more screws.
■ When Using Wall Mounting Brackets
2
1
Attach the wall mounting brackets to the interface unit
Mount the unit to a pillar or wall using 2 mounting screws.
using 2 mounting screws.
Interface unit
Wall mounting
brackets
Mounting screws
Mounting screws
Cord clamp for
wiring
Mounting screws
63
Page 64
■ When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting
screws.
Interface case
mounting screws
Mounting
screws
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not
fall.
Interface unit
Cushioning material
When mounting the interface unit inside a ceiling
or wall, install an access door to facilitate maintenance.
When the interface unit is mounted
above an indoor unit, it should be
positioned 40 mm or more away from the
unit to ensure that ceiling grills can be
removed.
40 mm or more
Attach the interface unit connecting cable here.
Store extra connecting cable in the ductwork space
behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
64
Page 65
11-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Indoor unitIndoor unitIndoor unit
Remote controller
Control roomroom 1room 2room 3
Indoor unit
Relay boxRelay boxRelay box
Indoor unit
Control circuit
power supply
Indoor unitIndoor unit
Remote
controller
Remote/Local
selection switch
Control room W
room 1room 2room 3
Remote
controller
Remote
controller
Remote
controller
• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go
from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the
unit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a
clear determination of whether or not there was a power failure. When it has been determined that there has been a power
failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has
appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller.
• When there is group control, selection of all refrigerants is required.
11-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or centralized monitoring of the air conditioners in each room can be attained.
• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote controllers with 0.3 to 1.25 mm22-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
11-7. COMBINED REMOTE/LOCAL CONTROL
• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter
(PAC-SE55RA-E sold separately) through the relay box installed on site. When this remote control is cancelled, the local
remote controller can be used for operating and stopping the air conditioner.
1. Basic system wiring
• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes
from the relay box and remote/local selection switch and connect it to the CN32 connector on the printed circuit board for
the indoor unit
<Points of precaution>
1 Match the rated power supply voltage of the remote/local selection switch and relay (X2) with the power supply for the con-
troller.
2 When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not start
at the same time. If this is not performed, all of the units will start at one time creating an over current that will cause the circuit
breaker to operate.
3 An on-delay system is one that includes specifications for operating a limited time when an on signal is received and has a tem-
porary off timer for recovery operations.
4 Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-
vided, abnormal operation will occur.
(1) System diagram
W The AC for the control room is usually disconnected from the remote/local control system.
65
Page 66
Control circuit
power supply
Dedicated short
circuit prevention
device
Remote/Local
selection switch
No.1 unit
relay box
No.2 unit
relay box
3 Relay box
2
Adapter for
remote start/stop
1
Remote/Local
selection switch
T Timer
(On delay system)
X Relay
Model
PAC-SE55RA-E
(Sold separately)
(Example)
Single polarity
single-throw switch
(125V rating)
To
next
unit
T
Brown
Red
X
2X2
T
One method of easily
distinguishing the on/off
status of SW1 and SW2
is to use together with a
"illuminated switch R" or
pilot lamp.
T
X
2
SW1
SW2
T
X
2
OrangeOrange
Brown
Red
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
Remote
control
OFFON
Description of
functions
OFFON
SW1
SW2
OFFON
Remote/Local
selection switch
(2) Basic wiring diagram
Indoor unit
circuit board
CN32
Orange
Red
Brown
On site wiringOn site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used.
Protect exposed wire by
wrapping with insulating tape
On site wiring
SW1
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW1
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
For remote operation
For timer operation
(3) Part specifications
Note: When using group address, connect to refrigerant
address "0" on the inside.
2. Examples of system applications
In any of the following examples, there is a five to six second delay from the time the operating command is issued until the
operation begins.
1 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited.
2 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be separated.
3 This is when starting and stopping is performed by remote operation and then allowing starting or stopping by remote con-
trol at any time.
4 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
Use momentary switch for SW2. (Manual operation/automatic recover switch on
time is more than one second.)
Press SW2 (on time is more than one second) and operation starts. After this has
been done, stopping or restarting can be down by remote controller.
If SW2 is on, operation by remote controller cannot be
performed.
If SW2 is off, operation by remote controller is permitted.
66
Page 67
11-8. OBTAINING REMOTE DISPLAY
CN90CN1
CN41
Wireless
3
TB3
External input
TB2
Error
TB1
Operation
2
Indoor control circuit boardRemote operation adapter
5
External input
Error output
(No voltage momentary "a" contact)
Operating output
(No voltage momentary "a" contact)
No voltage
(Momentary "a" contact)
HA
Power supply for controller
Timer control
panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
Use the remote operation adapter (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off input
function.
(1) Wiring method
..
Caution
TB3 is a dedicated terminal for contact point input. Never input voltage. It will damage
the indoor control circuit board.
<Connections on the indoor unit side>
1 When using external output function
Insert the 9-prong connector (3-core) of the attached cable to CN90 on the indoor control circuit board.
2 When using the external input function
Insert the 4-prong connector (2-core) of the attached cable to CN41 on the indoor control circuit board.
W The connector is direction-sensitive. Use care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2) Locally procured parts
ItemNameModel and specifications
External output functionExternal output signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent.
Wire size:Stranded wire 0.5mm
2
to 1.25mm
Single straged: {0.65mm to 1.25mm
Display lamp, etc.No voltage “a” contact AC200V (DC30V), 1Aor less
External input functionExternal input signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent.
Wire size:Stranded wire 0.5mm2to 1.25mm
Single straged: {0.65mm to 1.2mm
SwitchNo voltage “a” contact
(Start and stop operation is switched by inputting a
pulse of 200ms or more)
2
2
11-9. TIMER OPERATION
● Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in
10-minute increments within a 24-hour period.
● When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can
be stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
Operating with on-site timer
(1) Summary of system
If the “Remote ON/OFF adapter” (PACSE55RA-E) (sold separately) is used, the
on-site timer can be operated to turn each
unit on and off.
67
Page 68
(2) Basic pattern for timer control
Orange
As selected by remote controller operation switch.
From indoor unit
Red
Brown
T
SW ON
SW OFF
Timer control
Remote controller control
SW
Orange
From indoor unit
Red
Brown
T
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage
(PAC-SB81VS)
External control
input terminal
block
1
2
3
Connector
(CN2L)
Basic wiring
X: Relay
(DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box
(On-site tinstallation)
Relay box
(On-site tinstallation)
Remote controller
Humidifier unit
Humidifier
unit
Use a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply).
a) Timer-independent controlb) Combined control by timer and remote controller
(3) Basic system
Refer to 11-7. COMBINED REMOTE/LOCAL CONTROL.
11-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT
■ Lossnay operation
● Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - sold
separately) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from the
remote controller.
1 Summary of wiring
● Connect the Lossnay linkage cable (Model PACSB81VS) connector to CN2L on the indoor unit on the
circuit board of the indoor unit.
● Connect the lead wire of the Lossnay linkage cable to
the Lossnay external control input terminal blocks (1)
and (2)
(At this time, the input terminal blocks (1) and (2)
have no polarity.)
2 Precautions when wiring
● The Lossnay linkage cable can be extended up to a maximum of 500 meters.
When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation.
(Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm
● Lossnay linked cable
● Arrange wiring so that there can be no contact between the Lossnay linkage cable and the power supply cord. Contact
may cause malfunctioning. (Separate by 5cm or more.)
2
)
11-11. OBTAINING HUMIDIFIER SIGNAL
● The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the
adapter for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifier
unit via the on-site relay box. There is no output when the thermostat is off, during heating preparation and during
defrosting.
W Please consult your nearest Mitsubishi Electric
representative for information about obtaining the
adapter for humidifier signal.
11-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR
● Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model
PAC-SE41TS-E - sold separately) to the CN20 connector on the circuit board for the indoor unit.
● The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is
required.
Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
68
Page 69
11-13. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple remote
controller adapter
The maximum distance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Be sure to secure insulation
material by tape and such
5
Green
Yellow
Orange
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape and such
Installation at site
CN51
on
indoor
controller
board
Red
Brown
1
~
MB
You can control several units with a multiple remote control display, by
wiring an optional multiple remote controller adapter (PAC-SA88HA-E) with
relays and lamps on the market.
How to wire
(1) Connect the multiple remote controller adapter to the connector CN51
on the indoor controller board.
(2) Wire three of the five wires from the multiple remote controller adapter
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to pretend the
grille from dropping.
(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
2. Removing the room temperature thermistor
(1) Remove the screw(✕1) in the room temperature thermistor
holder to remove the holder and the room temperature
thermistor.
(2) Remove the 1 screw from the bell mouth, and unscrew the
another 2 screws (fixed to the oval hole which has different
diameter) to remove the bell mouth.
(3) Hold the holder claw, and remove the room temperature
thermistor and holder.
(4) Disconnect the connector (red) in the indoor control board.
Figure 1
Air intake grille
Grille
Air intake grille knob
Photo 1
Screws
Bell mouth
Room
temperature
thermistor
Air intake grille
3. Removing the electrical box
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).
(2) Remove the room temperature thermistor with the holder.
(3) Remove the bell mouth.(See photo 1)
(4) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor power supply
Green (6P) for auxiliary heater
(5) Disconnect the connector on the indoor controller board in
the electrical box.
White (2P) for pipe temperature detecting thermistor
Blue (2P) for drain pump
White (3P) for drain sensor
(6) Remove the 3 screws from the electrical box, loosen
another 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power supply board
Terminal block
Capacitor
Heater contactor
Photo 2
Turbo fan
Electrical
box
Power
supply
board
Nut
Indoor controller board
Capacitor
Heater
contactor
Terminal
block
Connector
70
Page 71
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
4. Remove the fan motor
(1) Remove the bell mouth.(See photo 1)
(2) Remove the electrical box.(See photo 2)
(3) Remove the turbo fan nut.
(4) Pull out the turbo fan.
(5) Disconnect the connector of the fan motor lead wire.
(6) Remove the 4 nuts of the fan motor.
5. Removing the pipe temperature thermistor
(1) Remove the bell mouth.(See photo 2)
(2) Remove the electrical box.(See photo 3)
(3) Remove the turbo fan.
(4) Remove the screw of the service panel.
(5) Remove the service panel.
(6) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.
(7) Disconnect the 2-pin white connector.
Photo 3
Photo 4
Fan motor
Nut
Pipe temperature thermistor
Connector
Nut
6. Removing the panel
(1) Remove the air intake grille.(See figure 1)
Corner panel (See figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.
Panel (See photo 5)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a large diameter of the
oval hole, which has two different diameters.)
7. Removing the drain pan
(1) Remove the panel. (See photo 5)
(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.
(3) Remove the corner cover. (2 screws)
(4) Remove the bell mouth (See photo 1)
(5) Remove the electrical box. (See photo 2)
(6) Remove the lead wire holder. (1 screw)
(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Figure 2
Corner
panel
Photo 5
Connector
Screw
Photo 6
Screw
Drain pan
Screw
Service entrance
Screw
Corner
panel
Panel
Screw
Panel
Screw
71
Lead
wire
holder
Drain plug(Larger one)
Screw
Corner cover
Page 72
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
8. Removing the drain pump and drain sensor
(1) Remove the panel. (See photo 5)
(2) Remove the bell mouth. (See photo 1)
(3) Remove the electrical box. (See photo 2)
(4) Remove the drain pan. (See photo 6)
(5) Remove the 3 screws of the drain pump.
(6) Cut the drain hose band, pull out the drain hose from the
drain pump.
(7) Pull out the drain pump.
(8) Remove the drain sensor and the holder.
9. Removing the heat exchanger
(1) Remove the panel. (See photo 5)
(2) Remove the bell mouth. (See photo 1)
(3) Remove the electrical box. (See photo 2)
(4) Remove the drain pan. (See photo 6)
(5) Remove the turbo fan. (See photo 3)
(6) Remove the 3 screws of the piping cover, and pull out
piping cover.
(7) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.
(8) Remove the screw of the coil support.
(9) Remove the 2 screws of the coil.
(10) Pull out the heat exchanger.
Photo 8
Screw
Drain hose
Photo 9
Heat exchanger
Coil
support
Fixing band
Coil support
Drain sensor
Screw
Drain pump
Coil screws
Coil
support
10. Removing the heater
(1) Remove the panel. (See photo 5)
(2) Remove the electrical box. (See photo 2)
(3) Remove the bell mouth.(See photo 1)
(4) Remove the drain pan.(See photo 6)
(5) Remove the turbo fan.(See photo 3)
(6) Remove the 5 screws of the heater assembly.
(7) Remove the clamp(1 screw) securing the lead wire.
(8) Pull the heater assembly out.
PANEL PARTS
PLH-3AAK.UKPLH-3AAKH.UK
PLH-4AAK.UKPLH-4AAKH.UK
PLH-5AAK.UKPLH-5AAKH.UK
PLH-6AAK.UKPLH-6AAKH.UK
1
GEAR
12
GEAR
(VANE)
11
VANE
2
BUSH
10
9
STEPPING
MOTOR
3
8
13
14
15
73
4
5
6
7
RECEIVER
Page 74
No.
Parts No.
Parts Name
Q'ty / set
PLH-·AAK.UK
345
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Price
1
2
3
4
5
6
7
8
9
10
11
12
13
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
BASE
LEG
DRUM 1 ASSY
DRUM 1 ASSY
LEG
TURBO FAN
TURBO FAN
SPL WASHER / NUT
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
INNER COVER
INNER COVER
LEG
FAN MOTOR
FAN MOTOR
MOTOR MOUNT
DRUM 2 ASSY
DRUM 2 ASSY
FUNCTIONAL PARTS
PLH-3AAK.UK
PLH-4AAK.UK
PLH-5AAK.UK
PLH-6AAK.UK
13
1211
10
1
SPL WASHER
2
2
3
4
9
5
6
7
8
PIPE TEMPERATURE
THERMISTOR
74
Page 75
No.
Parts No.
Parts Name
Q'ty / set
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Price
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
BASE
LEG
DRUM 1 ASSY
DRUM 1 ASSY
LEG
TURBO FAN
TURBO FAN
SPL WASHER
HEATER ELEMENT
HEATER ELEMENT
HEATER ELEMENT
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
INSULATOR
HEATER THERMAL SWITCH
THERMAL FUSE
THERMAL FUSE
THERMAL FUSE
INNER COVER
INNER COVER
LEG
FAN MOTOR
FAN MOTOR
MOTOR MOUNT
DRUM 2 ASSY
DRUM 2 ASSY
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
Note 2. The following main parts are contained in the optional refrigerant piping kit.