Mitsubishi OC392 Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
TECHNICAL & SERVICE MANUAL
May 2006
No. OC392
Indoor unit [Model names] [Service Ref.]
PSH-3GAK PSH-3GAK PSH-4GAK PSH-4GAK PSH-5GAK PSH-5GAK PSH-6GAK PSH-6GAK
PSH-3GAKH PSH-3GAKH PSH-4GAKH PSH-4GAKH PSH-5GAKH PSH-5GAKH PSH-6GAKH PSH-6GAKH
NOTE:
• This manual does not cover the outdoor units.
When servicing them,
Please refer to the outdoor unit’s service manual and this manual in a set.
CONTENTS
1. REFERENCE MANUAL······································2
2. PART NAMES AND FUNCTIONS ···················3
3. SPECIFICATIONS············································5
4. DATA·································································9
6.
WIRING DIAGRAM
7.
REFRIGERANT SYSTEM DIAGRAM
8. TROUBLESHOOTING ···································19
9. FUNCTION SETTING·····································32
10. SYSTEM CONTROL ·····································38
11. DISASSEMBLY PROCEDURE·······················52
12. PARTS LIST···················································56
13. OPTIONAL PARTS·························Back Cover
············································17
··················18
1
Service Ref. Service Manual No.
PUH-3VKA.TH PUH-3YKA.TH PUH-4/5/6YKSA.TH
PUH-3NKA.TH PUH-4/5/6TKSA.TH
OC354
OC325
1-1. OUTDOOR UNIT’S SERVICE MANUAL
REFERENCE MANUAL
2
2
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
PART NAMES AND FUNCTIONS
Indoor Unit
Disperses air up and down
Disperses air left and right.
Removes dust and pollutants from intake air.
(Intakes air from room.)
Controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
3
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indica­tion (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
4
SPECIFICATIONS3
Service Ref.
Power supply (phase, cycle,voltage)
External finish Heat exchanger Fan
Booster heater (220V/ 240V) Operation control & Thermostat Noise level (Low-High) (220V/ 240V) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan(drive) o No. Fan motor output Airflow(Low-High) (220V/ 240V) External static pressure
Input Running current Starting current
Model Motor output Starter type
Protection devices
Fan(drive) o No. Fan motor output Airflow
Charge
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A A
kW
K / min (CFM)
Pa
kW
dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kW
A A
kW
kW
K / min (CFM)
dB(A) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kg,(lbs) mm,(in.) mm,(in.)
PSH-3GAK(H) PSH-3GAK
Cooling W1
7,700
26,300
3.31
Cooling W2
6,750
23,000
4.29
Heating W1
8,900 [11,000]
30,400 [37,500]
3.10 [5.20]
Heating W2
9,500
32,400
3.49
0.16
0.68
0.8
0.16
0.73
0.8
0.16 [2.26]
0.68 [9.43]
0.8 [9.6]
0.16
0.73
0.8
PUH-3VKA.TH
Single, 50Hz 220-240V
3.15
13.82/ 5.16 58/ 37
PUH-3YKA.TH
3, 50Hz 380-415V(4wires)
2.94
12.89/ 4.81 58/ 37
PUH-3NKA.TH
Single, 60Hz 220V
80
NH52YDAT
2.4
Anti-phase protector, Thermal relay,
Thermal switch, HP switch
PSH-3GAK(H)
Single, 50Hz, 220-240V
PSH-3GAK
Single, 60Hz, 220V
Munsell 0.70Y 8.59/ 0.97
Plate fin coil
Centrifugal (direct) o 1
0.03
0 (direct blow)
built-in
26 (1) 600 (23-5/8) 270 (10-5/8)
1900 (74-13/16) 43 (95) [45 (99)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o1
0.085
50(1764)
Reverse cycle
52
870 (34-1/4)
295+24 (11-5/8 add 1)
850 (33-7/16)
75 (165)
R-22
3.2 (7.0)
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 50m Max. 50m
1600 (MS-32)
(Cooling/Heating) (Cooling/Heating)
NH52VNHT
2.2
Inner thermostat,
HP switch
NHJ47NADT
2.2
Inner thermostat,
HP switch
1.8/ 2.1
37-42/ 40-45
3.52/ 4.13
16.47/ 18.77
3.33
15.6
–—
37-42
Refrigerating oil (Model)
cc
14-17 (494-600)14-17 (494-600)/ 15-18 (530-635)
Notes:W 1 Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V>
(INDOOR) Cooling: 27 :DB, 19 :WB Heating: 20:DB (OUTDOOR) Cooling: 35 :DB, 24 :WB Heating: 7:DB, 6°CWB
W 2 Rating Conditions < Single, 60Hz 220V >
(INDOOR) Cooling: 29 :DB, 19 :WB Heating: 21:DB (OUTDOOR) Cooling: 46 :DB Heating: 7:DB, 6°CWB
5
Service Ref.
Power supply (phase, cycle, voltage)
External finish Heat exchanger Fan
Booster heater (220V/ 240V) Operation control & Thermostat Noise level (Low-High) (220V/ 240V) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan (drive) o No. Fan motor output Airflow (Low-High) (220V/ 240V) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan (drive) o No. Fan motor output Airflow
Charge
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A A
kW
K / min (CFM)
Pa
kW
dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kW
A A
kW
kW
K / min (CFM)
dB(A) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kg,(lbs) mm,(in.) mm,(in.)
PSH-4GAK(H) PSH-4GAK
PSH-4GAK(H)
Single, 50Hz, 220-240V
PSH-4GAK
Single, 60Hz, 220V
Cooling W1
10,200 34,800
3.46
Cooling W2
9,850
33,600
5.27
Heating W1 10,850 [13,550] 37,000 [46,200]
3.45 [6.15]
Heating W2
12,450 42,600
4.22
0.26
1.10
1.5
0.26
1.20
1.5
0.26 [2.96]
1.10 [12.35]
1.5 [12.8]
0.26
1.20
1.5
PUH-4TKSA.TH
3, 60Hz 220V
69
NHJ56TKAT
PUH-4YKSA.TH
3, 50Hz 380-415V(4wires)
40
NH56YDAT
(Cooling/Heating) (Cooling/Heating)
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Centrifugal (direct) o 1
0.07
0 (direct blow)
built-in
26 (1) 600 (23-5/8) 350 (13-3/4)
1900 (74-13/16)
51 (112) [53 (117)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
2.7
Line start
Anti-phase protector, thermal relay, thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.065 + 0.065 95 (3350)
Reverse cycle
54
870 (34-1/4)
295+24 (11-5/8 add 1)
1258 (49-1/2)
94 (207)
R-22
4.2 (9.3)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max. 50m Max. 50m
1600 (MS-32)
3.20
5.24
3.19
5.22
4.14/ 5.01
11.81/ 14.14
3.96
11.3
22-28 (776-988)/ 24-31(847-1094) 22-30 (776-1056)
42-48
2.3/ 2.7
42-47/ 43-48
Refrigerating oil (Model)
cc
Notes:W 1 Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V>
(INDOOR) Cooling: 27 :DB, 19 :WB Heating: 20:DB (OUTDOOR) Cooling: 35 :DB, 24 :WB Heating: 7:DB, 6°CWB
W 2 Rating Conditions < 3, 60Hz 220V >
(INDOOR) Cooling: 29 :DB, 19 :WB Heating: 21:DB (OUTDOOR) Cooling: 46 :DB Heating: 7:DB, 6°CWB
6
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger Fan
Booster heater (220V/240V) Operation control & Thermostat Noise level(Low-High) (220V/240V) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan(drive) o No. Fan motor output Airflow(Low-High) (220V/240V) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive) o No. Fan motor output Airflow
Charge
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A A
kW
K / min (CFM)
Pa
kW
dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kW
A A
kW
kW
K / min (CFM)
dB(A) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kg,(lbs) mm,(in.) mm,(in.)
PSH-5GAK(H)
PSH-5GAK(H)
Single, 50Hz, 220-240V
PSH-5GAK
PSH-5GAK
Single, 60Hz, 220V
Cooling W1
12,500 42,700
4.51
Cooling W2
11,000 37,500
6.82
Heating W1 13,700 [16,700] 46,700 [57,000]
4.46 [7.46]
Heating W2
16,500 56,300
6.06
0.30
1.26
1.5
0.30
1.35
1.5
0.30
1.35
1.5
0.30 [3.30]
1.26 [13.76]
1.5 [14.6]
PUH-5YKSA.TH
3, 50Hz, 380-415V (4 wires)
53
ZR61KC-TFD
0.085 + 0.085 95 (3350)
PUH-5TKSA.TH
3, 60Hz, 220V
135
ZR61KC-TF5
0.10 + 0.10 100 (3530)
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Centrifugal (direct) o 1
0.110
0 (direct blow)
built-in
26 (1) 600 (23-5/8) 350 (13-3/4)
1900 (74-13/16)
51 (112) [53 (117)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
3.5
Line start
Anti-phase protector,Inner thermostat, Thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
Reverse cycle
55
970 (38 - 3/16)
345 + 24 (13-9/16 add 1)
1258 (49-1/2)
114 (251)
R-22
5.4 (11.9)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max. 50m Max. 50m
2130 (SONTEX-200)
(Cooling/Heating) (Cooling/Heating)
23-31 (812-1094)
43-49
23-31 (812-1094)/ 26-33 (918-1165)
2.5/ 3.0
43-49/ 46-51
4.21
6.89
4.16
6.81
6.52
19.23
5.76
17.38
Refrigerating oil(Model) cc
Notes :W1. Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V >
Cooling : Indoor : 27:DB, 19:WB Heating : Indoor : 20:DB,
W2. Rating Conditions < 3 , 60Hz 220V >
Cooling : Indoor : 29:DB, 19:WB Heating : Indoor : 21:DB,
Outdoor : 35:DB, 24:WB Outdoor : 7:DB, 6:WB.
Outdoor : 46:DB, Outdoor : 7:DB, 6:WB.
7
Service Ref.
Power supply (phase, cycle, voltage)
External finish Heat exchanger Fan
Booster heater (220V/240V) Operation control & Thermostat Noise level (Low-High) (220V/240V) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan (drive) o No. Fan motor output Airflow (Low-High) (220V/240V) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan (drive) o No. Fan motor output Airflow
Charge
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/ h
kW
kW
A A
kW
K/ min
(CFM)
Pa
kW
dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kW
A A
kW
kW
K/ min
(CFM)
dB(A) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kg,(lbs) mm,(in.) mm,(in.)
PSH-6GAK(H) PSH-6GAK
Cooling W1
14,200 48,450
5.11
Cooling W2
13,400 45,700
7.42
Heating W2
17,500 59,700
6.8
Heating W1 16,000 [19,000] 54,600 [64,800]
4.96 [7.96]
0.38
1.62
2.1
0.38
1.62
2.1
0.38
1.62
2.1
0.38 [3.38]
1.62 [14.12]
2.1 [14.6]
PUH-6YKSA.TH
3, 50Hz, 380-415V (4 wires)
74
ZR68KC-TFD
PUH-6TKSA.TH
3, 60Hz, 220V
140
ZR68KC-TF5
Munsell 0.70Y 8.59/ 0.97
Plate fin coil
Centrifugal (direct) o 1
0.12
0 (direct blow)
built-in
45-50
26 (1) 600 (23-5/ 8) 350 (13-3/ 4)
1900 (74-13/ 16)
53 (117) [55 (121)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
4.0
Line start
Anti-phase protector, Inner thermostat, thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.10 + 0.10 100 (3530)
Reverse cycle
56
970 (38-3/ 16)
345 + 24 (13-9/ 16 add 1)
1258 (49-1/ 2)
117 (313)
R-22
5.0(11)
9.52 (3/ 8)
19.05 (3/ 4)
Flared
Flared Max. 50m Max. 50m
1774 (SONTEX-200)
(Cooling/ Heating) (Cooling/ Heating)
PSH-6GAK(H)
Single, 50Hz, 220-240V
PSH-6GAK
Single, 60Hz, 220V
2.5/ 3.0
25-32 (882-1130)/ 27-35 (953-1236) 25-32 (882-1130)
4.73
7.74
4.58
7.50
7.04
20.3
6.42
18.51
Refrigerating oil (Model)
cc
Notes :W1. Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V >
Cooling : Indoor : 27:DB, 19:WB
Outdoor : 35:DB, 24:WB
Heating : Indoor : 20:DB,
W2. Rating Conditions < 3 , 60Hz 220V >
Outdoor : 7:DB, 6:WB.
Cooling : Indoor : 29:DB, 19:WB
Outdoor : 46:DB,
Heating : Indoor : 21:DB,
Outdoor : 7:DB, 6:WB.
8
4
P.C.
3.62
3.72
3.83
3.96
3.79
3.89
4.00
4.14
4.94
5.06
5.22
5.39
5.59
5.74
5.91
6.10
CA
6,342 6,793 7,270 7,773 8,401 8,999
9,631 10,297 10,332 11,053 11,814 12,617 11,737 12,556 13,421 14,333
P.C.
3.41
3.49
3.59
3.69
3.56
3.65
3.75
3.86
4.64
4.76
4.89
5.02
5.26
5.39
5.54
5.69
CA
6,671 7,130 7,616 8,128 8,837
9,445 10,088 10,767 10,858 11,590 12,365 13,184 12,334 13,166 14,047 14,977
P.C.
3.19
3.27
3.35
3.43
3.34
3.42
3.50
3.59
4.35
4.46
4.56
4.67
4.93
5.05
5.17
5.30
CA
6,983 7,452 7,948 8,470 9,250
9,872 10,528 11,220 11,336 12,098 12,902 13,750 12,878 13,743 14,657 15,621
P.C.
2.98
3.05
3.11
3.18
3.11
3.18
3.25
3.32
4.06
4.15
4.24
4.33
4.60
4.70
4.81
4.91
CA
7,278 7,760 8,267 8,799
9,641 10,279 10,951 11,656 11,815 12,597 13,420 14,284 13,421 14,310 15,246 16,227
P.C.
2.77
2.82
2.88
2.94
2.89
2.95
3.01
3.07
3.77
3.85
3.92
4.00
4.27
4.36
4.44
4.53
CA
7,555 8,053 8,573
9,115 10,008 10,668 11,356 12,074 12,265 13,073 13,917 14,797 13,933 14,851 15,810 16,809
P.C.
2.65
2.71
2.76
2.81
2.77
2.83
2.88
2.94
3.61
3.69
3.76
3.83
4.10
4.18
4.26
4.34
CA
7,768 8,271 8,779
9,293 10,290 10,956 11,630 12,310 12,611 13,427 14,252 15,086 14,326 15,253 16,190 17,138
20
Outdoor intake air DB:
25 30 35 40 45
Indoor
intake air
WB°C
16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
Refrigerant piping length(one way)
5m
1.00
1.00
1.00
1.00
10m
0.981
0.989
0.981
0.975
15m
0.968
0.980
0.968
0.955
20m
0.952
0.970
0.952
0.935
25m
0.940
0.960
0.918
0.918
30m
0.925
0.950
0.925
0.900
35m
0.913
0.940
0.913
0.884
40m
0.900
0.930
0.900
0.869
45m
0.886
0.920
0.886
0.855
50m
0.874
0.910
0.874
0.840
PSH-3GAK(H) PSH-4GAK(H) PSH-5GAK(H) PSH-6GAK(H)
Service Ref.
P.C.
4.03
4.14
4.26
4.40
4.82
4.94
5.09
5.26
6.15
6.32
6.50
6.72
6.84
7.02
7.23
7.47
CA 6,300 6,749 7,223 7,723 9,183 9,837
10,528 11,256 10,707 11,469 12,275 13,124 12,518 13,410 14,352 15,345
P.C.
3.79
3.89
3.99
4.10
4.53
4.65
4.77
4.90
5.79
5.93
6.09
6.26
6.43
6.60
6.78
6.97
CA 6,628 7,084 7,566 8,076 9,660
10,324 11,028 11,770 11,263 12,037 12,858 13,723 13,168 14,074 15,034 16,046
P.C.
3.55
3.64
3.72
3.81
4.24
4.35
4.45
4.56
5.42
5.55
5.69
5.82
6.03
6.18
6.32
6.48
CA 6,938 7,404 7,896 8,415
10,112 10,791 11,509 12,265 11,789 12,581 13,419 14,301 13,785 14,711 15,689 16,721
P.C.
3.31
3.39
3.46
3.53
3.96
4.05
4.14
4.23
5.06
5.17
5.29
5.40
5.62
5.75
5.88
6.00
CA 7,231 7,709 8,213 8,742
10,539 11,237 11,971 12,742 12,287 13,101 13,957 14,856 14,367 15,318 16,319 17,370
P.C.
3.08
3.14
3.20
3.26
3.68
3.75
3.83
3.90
4.70
4.79
4.89
4.98
5.22
5.33
5.44
5.54
CA 7,506 8,001 8,517 9,056
10,941 11,661 12,414 13,199 12,756 13,596 14,474 15,389 14,915 15,897 16,923 17,993
P.C.
2.95
3.01
3.07
3.12
3.53
3.60
3.67
3.73
4.50
5.59
4.68
4.77
5.01
5.11
5.21
5.30
CA 7,718 8,217 8,722 9,233
11,249 11,977 12,713 13,457 13,115 13,964 14,822 15,690 15,334 16,327 17,330 18,345
20
Outdoor intake air DB°C
25 30 35 40 45
Indoor
intake air
WB°C
16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
PSH-3GAK
PSH-4GAK
PSH-5GAK
PSH-6GAK
Service Ref.
DATA
4-1. PERFORMANCE DATA
1) COOLING CAPACITY (50Hz 240/415V)
(60Hz,220V)
Note CA :Capacity (W)
P.C.:Power consumption (kW)
Cooling capacity correction factors
9
2) HEATING CAPACITY (50Hz 240/415V)
CA 6,095 5,836 5,609 7,430 7,115 6,837 9,382 8,983 8,633
10,957 10,492 10,083
P.C.
2.11
2.28
2.42
2.35
2.54
2.69
3.04
3.28
3.48
3.38
3.65
3.87
-10
CA 6,985 6,711 6,438 8,516 8,181 7,849
10,753 10,330
9,911
12,558 12,065 11,575
P.C.
2.34
2.52
2.68
2.60
2.80
2.99
3.36
3.62
3.86
3.74
4.03
4.30
-5
CA 7,962 7,661 7,357 9,706 9,340 8,969
12,256 11,793 11,325 14,313 13,773 13,227
P.C.
2.57
2.77
2.97
2.86
3.09
3.30
3.70
3.99
4.27
4.12
4.44
4.74
0
CA 9,023 8,686 8,365
10,999 10,589 10,197 13,889 13,371 12,876 16,220 15,616 15,037
P.C.
2.83
3.04
3.26
3.14
3.39
3.63
4.06
4.38
4.69
4.52
4.87
5.22
5
CA
10,167
9,784
9,459 12,394 11,928 11,532 15,650 15,061 14,561 18,277 17,590 17,006
P.C.
3.09
3.33
3.57
3.44
3.70
3.97
4.45
4.79
5.13
4.94
5.33
5.71
10
CA 11,392 10,955 10,641 13,888 13,355 12,973 17,536 16,864 16,381 20,480 19,695 19,131
P.C.
3.37
3.63
3.89
3.75
4.04
4.33
4.85
5.22
5.60
5.39
5.80
6.23
15
Outdoor intake air DB°C
Indoor
intake air
WB°C
15 20 25 15 20 25 15 20 25 15 20 25
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
Refrigerant piping length(one way)
5m
1.00
1.00
1.00
1.00
10m
1.00
1.00
1.00
1.00
15m
1.00
1.00
1.00
1.00
20m
1.00
1.00
1.00
1.00
25m
1.00
1.00
1.00
1.00
30m
1.00
1.00
1.00
1.00
35m
0.998
0.998
0.998
0.998
40m
0.995
0.995
0.995
0.995
45m
0.993
0.993
0.993
0.993
50m
0.990
0.990
0.990
0.990
PSH-3GAK(H) PSH-4GAK(H) PSH-5GAK(H) PSH-6GAK(H)
Service Ref.
CA 6,553 6,275 6,030 8,588 8,224 7,903
11,299 10,820 10,398 11,984 11,475 11,028
P.C.
2.35
2.53
2.69
2.84
3.06
3.25
4.13
4.45
4.73
4.64
5.00
5.31
-10 CA
7,511 7,216 6,923 9,843 9,457
9,073 12,950 12,442 11,936 13,735 13,196 12,660
P.C.
2.59
2.80
2.98
3.14
3.38
3.60
4.57
4.92
5.25
5.13
5.53
5.89
-5 CA
8,561 8,238
7,911 11,219 10,796 10,367 14,760 14,204 13,640 15,655 15,065 14,467
P.C.
2.86
3.08
3.29
3.45
3.72
3.98
5.03
5.42
5.80
5.65
6.09
6.50
0
CA 9,701 9,340 8,994
12,714 12,240 11,787 16,727 16,104 15,507 17,741 17,080 16,447
P.C.
3.14
3.38
3.62
3.79
4.09
4.38
5.52
5.95
6.37
6.20
6.68
7.15
5
CA 10,931 10,521 10,171 14,326 13,787 13,330 18,848 18,140 17,537 19,990 19,239 18,600
P.C.
3.43
3.70
3.96
4.15
4.47
4.79
6.04
6.51
6.98
6.78
7.30
7.38
10
CA 12,249 11,779 11,442 16,053 15,437 14,995 21,120 20,310 19,728 22,401 21,541 20,924
P.C.
3.74
4.03
4.32
4.52
4.82
5.22
6.59
7.09
7.61
7.39
7.96
8.54
15
Outdoor intake air DB°C
Indoor
intake air
WB°C
15 20 25 15 20 25 15 20 25 15 20 25
PSH-3GAK
PSH-4GAK
PSH-5GAK
PSH-6GAK
Service Ref.
(60Hz,220V)
Note CA :Capacity (W)
P.C. :Power consumption (kW)
Heating capacity correction factors
10
PERFORMANCE CURVE
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 25 35 46 52
OUTDOOR DB (:)
INDOOR WB (:)
INDOOR WB (:)
CAPACITY(RATIO)TOTAL INPUT(RATIO)
22 20 18 16
22 20 18 16
Cooling (60Hz)
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-15-10 -5 0 5 10 15
OUTDOOR WB (:)
INDOOR DB (:)
INDOOR DB (:)
CAPACITY(RATIO)TOTAL INPUT(RATIO)
15 20 25
25 20
15
Heating (60Hz)
1.4
1.2
1.0
0.8
CAPACITY(RATIO)TOTAL INPUT(RATIO)
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 25 35 46
OUTDOOR DB (:)
INDOOR WB (:)
22 20 18 16
INDOOR WB (:)
22 20 18 16
1.4
1.2
1.0
0.8
CAPACITY(RATIO)
0.6
1.4
1.2
1.0
0.8
TOTAL INPUT(RATIO)
0.6
0.4
-12-10 -5 0 5 10 15
OUTDOOR WB (:)
15 20 25
INDOOR DB (:)
INDOORDB (:)
25 20
15
11
Service Ref.
Mode Capacity (W) Total input (kW)
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Indoor unit
Outdoor unit
Cool
6,750
4.29
0.16
0.73
0.8
4.13
18.77 80
Heat
9,500
3.49
0.16
0.73
0.8
3.33
15.6 80
Cool
9,850
5.27
0.26
1.20
1.5
5.01
14.14 69
Heat
12,450
4.22
0.26
1.20
1.5
3.96
11.3 69
Cool
11,000
6.82
0.30
1.35
1.5
6.52
19.23 135
Heat
16,500
6.06
0.30
1.35
1.5
5.76
17.38 135
Cool
13,400
7.42
0.38
1.62
2.1
7.04
20.30 140
Heat
17,500
6.80
0.38
1.62
2.1
6.42
18.51 140
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK
4-2. ELECTRICAL DATA
Service Ref.
Mode Capacity (W) Total input (kW)
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Indoor unit
Outdoor unit
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
8,800
[10,600]
3.06
[4.86]
0.14
[1.94]
0.64
[8.82]
10,650
[12,950]
3.38
[5.68]
0.22
[2.52]
1.02
[11.47]
13,400
[15,900]
4,39
[6.89]
0.26
[2.76]
1.20
[12.56]
15,600
[18,100]
4.90
[7.40]
0.34
[2.84]
1.56
[12.92]
Cool
7,500
3.27
0.14
0.64
0.8
3.13
14.67/5.23 54/34
Heat
0.8
2.92
13.68/4.88 54/34
Cool
10,100
3.39
0.22
1.02
1.5
3.17
5.29 37
Heat
1.5
3.16
5.28 37
Cool
12,200
4.45
0.26
1.20
1.5
4.19
7.32 49
Heat
1.5
4.13
7.21 49
Cool
14,000
4.98
0.34
1.56
2.1
4.64
8.10 68
Heat
2.1
4.56
7.96 68
Service Ref.
Mode Capacity (W) Total input (kW)
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Indoor unit
Outdoor unit
8,850
[10,750]
3.08
[4.98]
0.15
[2.05]
0.66
[8.92]
10,750
[13,250]
3.42
[5.92]
0.24
[2.74]
1.06
[11.93]
13,550
[16,250]
4.43
[7.13]
0.28
[2.98]
1.23
[12.97]
15,800
[18,500]
4.93
[7.63]
0.36
[3.06]
1.59
[13.33]
Cool
7,600
3.29
0.15
0.66
0.8
3.14
14.22/5.21 56/36
Heat
0.8
2.93
13.27/4.86 56/36
Cool
10,150
3.43
0.24
1.06
1.5
3.19
5.23 39
Heat
1.5
3.18
5.22 39
Cool
12,350
4.48
0.28
1.23
1.5
4.20
7.05 51
Heat
1.5
4.15
6.97 51
Cool
14,100
5.05
0.36
1.59
2.1
4.69
7.87 71
Heat
2.1
4.57
7.67 71
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
Service Ref.
Mode Capacity (W) Total input (kW)
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Indoor unit
Outdoor unit
8,900
[11,000]
3.10
[5.20]
0.16
[2.26]
0.68
[9.43]
10,850
[13,550]
3.45
[6.15]
0.26
[2.96]
1.10
[12.35]
13,700
[16,700]
4.46
[7.46]
0.30
[3.30]
1.26
[13.76]
16,000
[19,000]
4.96
[7.96]
0.38
[3.38]
1.62
[14.12]
Cool
7,700
3.31
0.16
0.68
0.8
3.15
13.82/5.16 58/37
Heat
0.8
2.94
12.89/4.81 58/37
Cool
10,200
3.46
0.26
1.10
1.5
3.20
5.24 40
Heat
1.5
3.19
5.22 40
Cool
12,500
4.51
0.30
1.26
1.5
4.21
6.89 53
Heat
1.5
4.16
6.81 53
Cool
14,200
5.11
0.38
1.62
2.1
4.73
7.74 74
Heat
2.1
4.58
7.50 74
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
Indoor ······ 220V 50Hz 1 phase Outdoor···· 220V 50Hz 1phase / 380V 50Hz 3phase
Indoor······ 230V 50Hz 1 phase Outdoor ··· 230V 50Hz 1 phase / 400V 50Hz 3phase
Indoor ······ 240V 50Hz 1 phase Outdoor···· 240V 50Hz 1 phase / 415V 50Hz 3 phase
Indoor ······ 220V 60Hz 1 phase Outdoor···· 220V 60Hz 1 phase / 220V 60Hz 3 phase
12
4-3. STANDARD OPERATION DATA
Service Ref.
Mode
Capacity
Total
Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz
Electrical cricuitRefrigerant circuit
Volts Amperes
Discharge pressure Suction pressure Discahrge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Indoor side
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
PSH-3GAK(H) PSH-4GAK(H) PSH-5GAK(H) PSH-6GAK(H)
Cooling
W
kW
7700
3.31
PSH-3GAK(H)
1,50
240
0.68
PUH-3VKA.TH, PUH-3YKA.TH
1/3, 50
240 / 415
13.82 / 5.16
Mpa.G
(kgf/cm
Mpa.G
(kgf/cm
°C °C °C
m
DB°C
WB°C
DB°C DB°C
WB°C
2.1
2.
(21.4)
G)
0.46
2.
G)
(4.69)
91.4
53.5
5.7 5
27 19
12.2 35 24
0.72
0.09
Heating
8900
3.10
[5.20]
0.68
[9.43]
12.89 / 4.81
1.91
(19.5)
0.35
(3.57)
85.6
5
20
15.5
46.0 7
6
Cooling
10200
3.46
PSH-4GAK(H)
1,50
240
1.10
PUH-4YKSA.TH
3,50 415
5.24
1.85
(18.9)
0.52
(5.3)
79.4
48.7
7.2 5
27 19
13.6 35
24
0.72
0.09
Heating
10850
3.45
[6.15]
1.10
[12.35]
5.22
1.72
(17.5)
0.37
(3.77)
77.4
5
20
15.5
38.8 7
6
Cooling
12500
4.51
PSH-5GAK(H)
1,50 240
1.26
PUH-5YKSA.TH
3,50 415
6.89
1.87
(19.1)
0.47
(4.79)
71.0
49.4
11.2 5
27 19
13.5
35 24
0.74
0.13
Heating
13700
4.46
[7.46]
1.26
[13.76]
6.81
1.82
(18.6)
0.36
(3.67)
72.9
5
20
15.5
42.2 7
6
Cooling
14200
5.11
PSH-6GAK(H)
1,50
240
1.62
PUH-6YKSA.TH
3,50
415
7.74
1.87
(19.1)
0.44
(4.49)
71.2
49.2
3.3
5
27 19
11.5 35
24
0.69
0.12
Heating
16000
4.96
[7.96]
1.62
[14.12]
7.50
1.82
(18.6)
0.37
(3.77)
72.5
-1.3-1.2-0.8-1.6 5
20
15.5
48.7
7 6
The unit of pressure has been changed to Mpa based on the international SI system. The conversion factor is : 1(Mpa.G)= 10.2(kgf/cm
2
.
G)
13
Capacity Input
Indoor unit Service Ref.
Phase,Hz Volts Amperes
Outdoor unit Service Ref.
Phase,Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Refrigerant pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
Mpa·G Mpa·G
:
:
:
m
DB:
WB:
DB: DB:
WB:
TotalElectrical circuitRefrigerant circuitIndoor side
Outdoor
side
Service Ref.
Mode
PSH-3GAK
1, 60
220
PUH-3NKA.TH
1, 60
220
PSH-4GAK
1, 60
220
PUH-4TKSA.TH
3, 60
220
PSH-5GAK
1, 60
220
PUH-5TKSA.TH
3, 60
220
PSH-6GAK
1, 60
220
PUH-6TKSA.TH
3, 60
220
SHF
BF
Cooling
7,650
3.68
0.73
16.49
2.03
0.44
75.8
52.6
3.9 5
27 19
11.8 35 24
0.72
0.09
Heating
9,500
3.49
0.73
15.6
2.06
0.42
91.2 –
-2.1 5
20
15.5
49.5 7 6 – –
Cooling
11,150
4.40
1.20
11.81
1.95
0.47
83.2
50.7
6.9 5
27 19
12.3 35 24
0.72
0.09
Heating
12,450
4.22
1.20
11.3
2.05
0.36
95.6 –
-2.0 5
20
15.5
46.6 7 6 – –
Cooling
13,000
5.62
1.35
16.32
1.92
0.38
78.2
50.8
0.6 5
27 19
12.9 35 24
0.70
0.17
Heating
16,500
6.06
1.35
17.38
2.23
0.33
94.3 –
-2.9 5
20
15.5
49.5 7 6 – –
Cooling
15,200
6.25
1.62
17.31
1.97
0.36
78.9
51.7
0.2 5
27 19
11.8 35 24
0.66
0.20
Heating
17,500
6.80
1.62
18.51
2.37
0.33
91.9 –
-2.1 5
20
15.5
50.3 7 6 – –
(Of/F·G) (Of/F·G)
(20.7) (4.49)
(21.0) (4.28)
(19.9) (4.79)
(20.9) (3.67)
(19.6) (3.88)
(22.8) (3.37)
(20.1) (3.67)
(24.1) (3.37)
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK
Refrigerant piping length(one way)
5m
2.5
3.5
4.7
4.3
10m
2.7
3.6
4.8
4.4
15m
2.8
3.8
5.0
4.6
20m
2.9
3.9
5.1
4.7
25m
3.1
4.1
5.3
4.9
30m
3.2
4.2
5.4
5.0
35m
3.3
4.4
5.6
5.2
40m
3.4
4.5
5.7
5.3
45m
3.6
4.6
5.9
5.5
50m
3.7
4.8
6.0
5.6
PSH-3GAK(H) PSH-3GAK
PSH-4GAK(H) PSH-4GAK PSH-5GAK(H) PSH-5GAK PSH-6GAK(H) PSH-6GAK
PUH-3VKA.TH PUH-3YKA.TH PUH-3NKA.TH PUH-4YKSA.TH PUH-4TKSA.TH PUH-5YKSA.TH PUH-5TKSA.TH PUH-6YKSA.TH PUH-6TKSA.TH
Service Ref.
INDOOR OUTDOOR
FACTORY CHARGED UP TO
3.2kg
4.2kg
5.4kg
5.0kg
Air flow Air speed Coverage range
 K/X
m/W. m
PSH-3GAK(H)
17
2.6
8.3
PSH-4GAK(H)
30
4.6
14.6
PSH-5GAK(H)
32
4.9
15.5
PSH-6GAK(H)
33
5.0
16.0
Service Ref.
The unit of pressure has been changed to Mpa based on the international SI system. The conversion factor is : 1(Mpa·G)=10.2(kgf/
4-4. REFILLING REFRIGERANT CHARGE (R-22 : kg)
4-5. OUTLET AIR SPEED AND COVERAGE RANGE
FF
·G).
14
5
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Knock out hole
for branch duct
100
10 3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
VIEW "A"
A
340
370
520
260
240
130 71
530
600
270
250
70
180
235
Knock out hole for
wiring.[27
(Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Terminal block for
indoor/outdoor
connection.
Terminal block for
Remote controller
Electrical parts box
Liquid pipe [9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe [15.88(5/8F)
Drain pipe
Terminal block for
power supply
95
46122
47
Front side
Rear side
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
277
160
20
218
175
90
55 143
100
95
40 66
186
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
10
OUTLINES AND DIMENSIONS
PSH-3GAK PSH-3GAKH
Unit : mm
15
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Knock out hole
for branch duct
100
10 3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
340
370
520
260
240
130 71
530
600
350
330
70
260
315
Knock out hole for
wiring.[27 (Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Electrical parts box
Liquid pipe [9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe [19.05(3/4F)
Drain pipe
95
46122
47
Front side
Rear side
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
277
120
20
218
255
140
77
201
120
95
40 66
261
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
10
VIEW "A"
A
Terminal block for
indoor/outdoor
connection.
Terminal block for
Remote controller
Terminal block for
power supply
Use the current nuts meeting the pipe sizeUse the current nuts meeting the pipe size
of the outdoor unit.of the outdoor unit.
Availabailable pipe sizle pipe size
: Factory flare nut attachment to : Factory flare nut attachment to
the heat-exchanger the heat-exchanger
LIQUID SIDE
GAS SIDEGAS SIDE
[ 9.52 9.52
[ 19.05 19.05
PSH-4GAK PSH-4GAKH PSH-5GAK PSH-5GAKH PSH-6GAK PSH-6GAKH
Unit : mm
16
WIRING DIAGRAM6
SW1
Table 1
1 2 3 4 5
ON OFF
SW5
Table 2
1 2 3 4 5 6 7 8
ON OFF
SW6
SWE
ON OFF
ON OFF
1 2
SW5SW1
Refer to tables 1, 2.
WHT
(
WIRERESS
)
CN90
RED
(INTAKE)
CN20
1 2
WHT (PIPE) CN21
BLU
(
REMOCON
)
CN22
YLW
(
HEATER
)
CN24
BLK
(
INDOOR/OUTDOOR
COMUNICATION
)
CN30
1 2 1 2
TH1 TH2
R.B
CN41 CN2L
CN51 CN32
I.B
LED1
LED2
X4X5X6 X2
I.B
P.B
CNSK (RED)
DC13.1V
CN2S (WHT)
TO OUTDOOR UNIT
POWER SUPPLY ~(1 PHASE) 220-240V 50Hz 220V 60Hz
POWER SUPPLY ~(1 PHASE) 220-240V 50Hz 220V 60Hz
PSH-3~6GAKH models only
TB4
TB2
1 2 3
L N
GRN/YLW
ZNR
WHT
(FAN)
FAN
YLW
(LOUVER)
CNL
FUSE
ORN
(POWER)
CND
RED
(POWER
BOARD)
CNDK
WHT
(POWER
BOARD)
CN2D
1 3 1 3 1 3 1 3
1
1 2
1 2
5 6
2
1 2
3
1 2
5 7
BLK
RED
YLW
ORN
BRN
BLU
BLU BLU
BLU
RED
RED
ORN
BLK
BRN
RED RED
BRN
RED
35
6
1
88H
26H
BLU
BRN
FS2FS1
H1
WHT
WHT
WHT
WHT
YLW
YLW
BLU
BLU
GRY
GRY
YLW
MF
X4 X2
X5
X6
1 2 3
TB6
TB5
1
1 2
2
TB2
L N
GRN/YLW
88H
ML
1 2
[Servicing] Fasten terminal of the terminal board"TB4"equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
P.B
INDOOR POWER BOARD
SYMBOL NAME
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR<LOSSNAY> CN32 CONNECTOR<REMOTE SWITCH> CN41 CONNECTOR<HA TERMINAL-A> CN51 CONNECTOR<CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION> wSee Table 1.
SWE,SW6
SWITCH<EMERGENCY OPERATION>
SW5 SWITCH<SYSTEM SELECTION> wSee Table 2.
X4 RELAY<FAN MOTOR> X5 RELAY<FAN MOTOR> X6 RELAY<FAN MOTOR>
X2 RELAY<LOUVER>
POWER SUPPLY<R.B>
LED1 POWER SUPPLY<I.B> LED2
C CAPACITOR<FAN MOTOR>
FAN MOTOR
LOUVER MOTOR
MF
ML
SYMBOL NAME
TB4
TERMINAL BLOCK<INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (POWER SUPPLY) CONNECTING LINE>
TB5
TERMINAL BLOCK<REMOTE CONTROLLER TRANSMISSION LINE>
TERMINAL BLOCK<REMOTE CONTROLLER TRANSMISSION LINE >
ROOM TEMP.THERMISTOR <0:/15k", 25:/5.4k" DETECT> PIPE TEMP.THERMISTOR/LIQUID <0:/15k", 25:/5.4k" DETECT>
THERMAL FUSE<110::16A> HEATER HEATER THERMAL SWITCH HEATER CONTACTOR
TH1 TH2 R.B
HEATER
WIRED REMOTE CONTROLLER BOARD
TB6
H1 26H 88H
FS1,2
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (1, 2, 3).
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
Check code
Symptom
Fb
Abnormality of indoor controller board.
FFFF
No corresponding unit.
– – – –
No trouble generated in the past.
P4
Abnormality of drain sensor(DS).
P5
Malfunction of drain-up machine.
P6
Freezing / overheating protection is working.
P8
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
P2
Abnormality of pipe temperature thermistor / Liquid.(TH2).
P1
Abnormality of room temperature thermistor.(TH1).
E0—E5
Abnormality of the signal transmission between remote controller and indoor unit.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6)on the indoor control board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling or heating, you have to set the switch(SWE)and switch(SW6)on indoor controller. SWE:ON · Indoor fan is running high speed. SW6-1:ON · Emergency operation of cooling mode. SW6-1,2:ON · Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions.
(2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or temperature control etc. does not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc. to their original positions.
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2. For the wired remote control : When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display. For Check Codes and Symptoms refer to the table.
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
17
7
Indoor heat exchanger
Distributor with strainer
PSH-5··········O.D.4.0oI.D.2.4-R350 PSH-6··········O.D.4.0oI.D.3.0-R1,200
Thermistor
TH2
Restrictor valve
Flexible tube
Flexible tube
Flared connection
Refrigerant pipe (option)
19.05mm ([3/4) (with heat insulator)
Refrigerant pipe (option)
9.52mm ([3/8) (with heat insulator)
Ball valve
4-way valve
Oil separator
Service port
High pressure control switch
THERMAL SWITCH
Outdoor heat exchanger
Capillary tube
Capillary tube
Thermistor
RT
Capillary tube
Compressor
Bypass valve
Restrictor valve
Accumulator
Ball valve (with service port)
w3:PUH-5,6TKSA only
w3
DDR
Strainer
Strainer
Strainer
Service port
PUH-5Y·················(O.D.4.0oI.D.2.4- R840)o2 PUH-6Y·················(O.D.4.0oI.D.2.4- R1,200)o2 PUH-5T·················(O.D.4.0oI.D.2.4- R840)o2 PUH-6T·················(O.D.4.0oI.D.2.4- R740)o2
Indoor heat exchanger
Distributor with strainer
PSH-4··········O.D.4.0oI.D.2.0-R400
Thermistor
TH2
Restrictor valve
Flexible tube
Flexible tube
Flared connection
Refrigerant pipe (option)
19.05mm ([3/4) (with heat insulator)
Refrigerant pipe (option)
9.52mm ([3/8) (with heat insulation)
Ball valve
4-way valve
Oil separator
Service port
High pressure control switch
Outdoor heat exchanger
Capillary tube
Thermistor
RT
Capillary tube
Compressor
Bypass valve
Restrictor valve
Accumulator
Ball valve (with service port)
Strainer
Strainer
Strainer
Service port
(O.D.3.2oI.D.2.0-R820)o2
Indoor heat exchanger
Distributor with strainer
PSH-3············O.D.4.0oI.D.2.0-R500
Thermistor
TH2
Restrictor valve
Flexible tube
Flared connection
Refrigerant pipe (option)
15.88mm ([5/8) (with heat insulator)
Refrigerant pipe (option)
9.52mm ([3/8) (with heat insulator)
Ball valve
4-way valve
Oil separator
Service port
High pressure control switch
Outdoor heat exchanger
Capillary tube
Thermistor
RT
Capillary tube
Compressor
Bypass valve
Muffler
Capillay tube
w1
w2
Restrictor valve
Accumulator
Ball valve (with service port)
Strainer
Strainer
Strainer
Service port
w2.PUH-3V,3Y·················O.D. 4.0 o I.D. 2.4 - R1,070 PUH-3N······················ O.D. 3.2 o I.D. 1.2 - R1250
w1.PUH-3N······················O.D. 4.0 o I.D. 2.4 - R600
Refrigerant flow in cooling Refrigerant flow in heating
R.V coil Heating ON Cooling OFF
REFRIGERANT SYSTEM DIAGRAM
PSH-3GAK(H)/PUH-3VKA.TH,PUH-3YKA.TH PSH-3GAK/PUH-3NKA.TH
PSH-4GAK(H)/PUH-4YKSA.TH PSH-4GAK/PUH-4TKSA.TH
PSH-5GAK(H)/PUH-5YKSA.TH PSH-5GAK/PUH-5TKSA.TH PSH-6GAK(H)/PUH-6YKSA.TH PSH-6GAK/PUH-6TKSA.TH
18
8
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (8-3).
Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (8-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (8-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code
F Unit No. G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen. 2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past. F F F F : No corresponding unit.
TROUBLESHOOTING
8-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
8-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
19
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
For about 2 minutes follow­ing power-on
After about 2 minutes has expired follow­ing power-on
• For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection device is not connected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block
•Incorrect wiring between indoor and outdoor units
•Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
• On wired remote controller
1Check code displayed in the LCD.
1 Check code
Symptom Remark
Wired remote controller
P1
Intake sensor error
P2
Pipe (TH2) sensor error
P4
Drain sensor error P5 PA
Drain pump error
Forced compressor stop P6
Freezing/ Overheating safeguard operation P8
Pipe temperature error / Outdoor unit error E4, E5
Remote controller signal receiving error
– –
– –
Fb
Indoor unit control system error (memory error, etc.) E0, E3
E1, E2
Remote controller control board error
Remote controller transmission error
20
Loading...
+ 44 hidden pages