SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
May 2006
No. OC392
Indoor unit
[Model names] [Service Ref.]
PSH-3GAK PSH-3GAK
PSH-4GAK PSH-4GAK
PSH-5GAK PSH-5GAK
PSH-6GAK PSH-6GAK
PSH-3GAKH PSH-3GAKH
PSH-4GAKH PSH-4GAKH
PSH-5GAKH PSH-5GAKH
PSH-6GAKH PSH-6GAKH
NOTE:
• This manual does not
cover the outdoor units.
When servicing them,
Please refer to the outdoor
unit’s service manual and
this manual in a set.
CONTENTS
1. REFERENCE MANUAL······································2
2. PART NAMES AND FUNCTIONS ···················3
3. SPECIFICATIONS············································5
4. DATA·································································9
5. OUTLINES AND DIMENSIONS·····················15
6.
WIRING DIAGRAM
7.
REFRIGERANT SYSTEM DIAGRAM
8. TROUBLESHOOTING ···································19
9. FUNCTION SETTING·····································32
10. SYSTEM CONTROL ·····································38
11. DISASSEMBLY PROCEDURE·······················52
12. PARTS LIST···················································56
13. OPTIONAL PARTS·························Back Cover
············································17
··················18
1
Service Ref. Service Manual No.
PUH-3VKA.TH
PUH-3YKA.TH
PUH-4/5/6YKSA.TH
PUH-3NKA.TH
PUH-4/5/6TKSA.TH
OC354
OC325
1-1. OUTDOOR UNIT’S SERVICE MANUAL
REFERENCE MANUAL
2
2
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
door.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To preceding operation
number.
Ventilation button
(
Operation button)
To next operation number.
PART NAMES AND FUNCTIONS
● Indoor Unit
Disperses air
up and down
Disperses air left
and right.
Removes dust and pollutants from intake air.
(Intakes air from room.)
● Controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttons
3
● Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
● If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not
present at the parent unit.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
4
SPECIFICATIONS3
Service Ref.
Power supply (phase, cycle,voltage)
External finish
Heat exchanger
Fan
Booster heater (220V/ 240V)
Operation control & Thermostat
Noise level (Low-High) (220V/ 240V)
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan(drive) o No.
Fan motor output
Airflow(Low-High) (220V/ 240V)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan(drive) o No.
Fan motor output
Airflow
Charge
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A
A
kW
K / min (CFM)
Pa
kW
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kW
A
A
kW
kW
K / min (CFM)
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kg,(lbs)
mm,(in.)
mm,(in.)
PSH-3GAK(H) PSH-3GAK
Cooling W1
7,700
26,300
3.31
Cooling W2
6,750
23,000
4.29
Heating W1
8,900 [11,000]
30,400 [37,500]
3.10 [5.20]
Heating W2
9,500
32,400
3.49
0.16
0.68
0.8
0.16
0.73
0.8
0.16 [2.26]
0.68 [9.43]
0.8 [9.6]
0.16
0.73
0.8
PUH-3VKA.TH
Single, 50Hz 220-240V
3.15
13.82/ 5.16
58/ 37
PUH-3YKA.TH
3, 50Hz 380-415V(4wires)
2.94
12.89/ 4.81
58/ 37
PUH-3NKA.TH
Single, 60Hz 220V
80
NH52YDAT
2.4
Anti-phase protector, Thermal relay,
Thermal switch, HP switch
PSH-3GAK(H)
Single, 50Hz, 220-240V
PSH-3GAK
Single, 60Hz, 220V
Munsell 0.70Y 8.59/ 0.97
Plate fin coil
Centrifugal (direct) o 1
0.03
0 (direct blow)
built-in
26 (1)
600 (23-5/8)
270 (10-5/8)
1900 (74-13/16)
43 (95) [45 (99)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o1
0.085
50(1764)
Reverse cycle
52
870 (34-1/4)
295+24 (11-5/8 add 1)
850 (33-7/16)
75 (165)
R-22
3.2 (7.0)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max. 50m
Max. 50m
1600 (MS-32)
(Cooling/Heating)
(Cooling/Heating)
NH52VNHT
2.2
Inner thermostat,
HP switch
NHJ47NADT
2.2
Inner thermostat,
HP switch
1.8/ 2.1
37-42/ 40-45
3.52/ 4.13
16.47/ 18.77
3.33
15.6
–—
37-42
Refrigerating oil (Model)
cc
14-17 (494-600)14-17 (494-600)/ 15-18 (530-635)
Notes:W 1 Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V>
(INDOOR) Cooling: 27 :DB, 19 :WB Heating: 20:DB
(OUTDOOR) Cooling: 35 :DB, 24 :WB Heating: 7:DB, 6°CWB
W 2 Rating Conditions < Single, 60Hz 220V >
(INDOOR) Cooling: 29 :DB, 19 :WB Heating: 21:DB
(OUTDOOR) Cooling: 46 :DB Heating: 7:DB, 6°CWB
5
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Heat exchanger
Fan
Booster heater (220V/ 240V)
Operation control & Thermostat
Noise level (Low-High) (220V/ 240V)
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan (drive) o No.
Fan motor output
Airflow (Low-High) (220V/ 240V)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A
A
kW
K / min (CFM)
Pa
kW
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kW
A
A
kW
kW
K / min (CFM)
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kg,(lbs)
mm,(in.)
mm,(in.)
PSH-4GAK(H) PSH-4GAK
PSH-4GAK(H)
Single, 50Hz, 220-240V
PSH-4GAK
Single, 60Hz, 220V
Cooling W1
10,200
34,800
3.46
Cooling W2
9,850
33,600
5.27
Heating W1
10,850 [13,550]
37,000 [46,200]
3.45 [6.15]
Heating W2
12,450
42,600
4.22
0.26
1.10
1.5
0.26
1.20
1.5
0.26 [2.96]
1.10 [12.35]
1.5 [12.8]
0.26
1.20
1.5
PUH-4TKSA.TH
3, 60Hz 220V
69
NHJ56TKAT
PUH-4YKSA.TH
3, 50Hz 380-415V(4wires)
40
NH56YDAT
(Cooling/Heating)
(Cooling/Heating)
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Centrifugal (direct) o 1
0.07
0 (direct blow)
built-in
26 (1)
600 (23-5/8)
350 (13-3/4)
1900 (74-13/16)
51 (112) [53 (117)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
2.7
Line start
Anti-phase protector, thermal relay, thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.065 + 0.065
95 (3350)
Reverse cycle
54
870 (34-1/4)
295+24 (11-5/8 add 1)
1258 (49-1/2)
94 (207)
R-22
4.2 (9.3)
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
1600 (MS-32)
3.20
5.24
3.19
5.22
4.14/ 5.01
11.81/ 14.14
3.96
11.3
22-28 (776-988)/ 24-31(847-1094) 22-30 (776-1056)
—
42-48
2.3/ 2.7
42-47/ 43-48
Refrigerating oil (Model)
cc
Notes:W 1 Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V>
(INDOOR) Cooling: 27 :DB, 19 :WB Heating: 20:DB
(OUTDOOR) Cooling: 35 :DB, 24 :WB Heating: 7:DB, 6°CWB
W 2 Rating Conditions < 3, 60Hz 220V >
(INDOOR) Cooling: 29 :DB, 19 :WB Heating: 21:DB
(OUTDOOR) Cooling: 46 :DB Heating: 7:DB, 6°CWB
6
Service Ref.
Power supply(phase, cycle,voltage)
External finish
Heat exchanger
Fan
Booster heater (220V/240V)
Operation control & Thermostat
Noise level(Low-High) (220V/240V)
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan(drive) o No.
Fan motor output
Airflow(Low-High) (220V/240V)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan(drive) o No.
Fan motor output
Airflow
Charge
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/h
kW
kW
A
A
kW
K / min (CFM)
Pa
kW
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kW
A
A
kW
kW
K / min (CFM)
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kg,(lbs)
mm,(in.)
mm,(in.)
PSH-5GAK(H)
PSH-5GAK(H)
Single, 50Hz, 220-240V
PSH-5GAK
PSH-5GAK
Single, 60Hz, 220V
Cooling W1
12,500
42,700
4.51
Cooling W2
11,000
37,500
6.82
Heating W1
13,700 [16,700]
46,700 [57,000]
4.46 [7.46]
Heating W2
16,500
56,300
6.06
0.30
1.26
1.5
0.30
1.35
1.5
0.30
1.35
1.5
0.30 [3.30]
1.26 [13.76]
1.5 [14.6]
PUH-5YKSA.TH
3, 50Hz, 380-415V (4 wires)
53
ZR61KC-TFD
0.085 + 0.085
95 (3350)
PUH-5TKSA.TH
3, 60Hz, 220V
135
ZR61KC-TF5
0.10 + 0.10
100 (3530)
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Centrifugal (direct) o 1
0.110
0 (direct blow)
built-in
26 (1)
600 (23-5/8)
350 (13-3/4)
1900 (74-13/16)
51 (112) [53 (117)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
3.5
Line start
Anti-phase protector,Inner thermostat, Thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
Reverse cycle
55
970 (38 - 3/16)
345 + 24 (13-9/16 add 1)
1258 (49-1/2)
114 (251)
R-22
5.4 (11.9)
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
2130 (SONTEX-200)
(Cooling/Heating)
(Cooling/Heating)
23-31 (812-1094)
—
43-49
23-31 (812-1094)/ 26-33 (918-1165)
2.5/ 3.0
43-49/ 46-51
4.21
6.89
4.16
6.81
6.52
19.23
5.76
17.38
Refrigerating oil(Model) cc
Notes :W1. Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V >
Cooling : Indoor : 27:DB, 19:WB
Heating : Indoor : 20:DB,
W2. Rating Conditions < 3 , 60Hz 220V >
Cooling : Indoor : 29:DB, 19:WB
Heating : Indoor : 21:DB,
Outdoor : 35:DB, 24:WB
Outdoor : 7:DB, 6:WB.
Outdoor : 46:DB,
Outdoor : 7:DB, 6:WB.
7
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Heat exchanger
Fan
Booster heater (220V/240V)
Operation control & Thermostat
Noise level (Low-High) (220V/240V)
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
Fan
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input
Running current
Starting current
Fan (drive) o No.
Fan motor output
Airflow (Low-High) (220V/240V)
External static pressure
Input
Running current
Starting current
Model
Motor output
Starter type
Protection devices
Fan (drive) o No.
Fan motor output
Airflow
Charge
W
D
H
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
W
Btu/ h
kW
kW
A
A
kW
K/ min
(CFM)
Pa
kW
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kW
A
A
kW
kW
K/ min
(CFM)
dB(A)
mm,(in.)
mm,(in.)
mm,(in.)
kg,(lbs)
kg,(lbs)
mm,(in.)
mm,(in.)
PSH-6GAK(H) PSH-6GAK
Cooling W1
14,200
48,450
5.11
Cooling W2
13,400
45,700
7.42
Heating W2
17,500
59,700
6.8
Heating W1
16,000 [19,000]
54,600 [64,800]
4.96 [7.96]
0.38
1.62
2.1
0.38
1.62
2.1
0.38
1.62
2.1
0.38 [3.38]
1.62 [14.12]
2.1 [14.6]
PUH-6YKSA.TH
3, 50Hz, 380-415V (4 wires)
74
ZR68KC-TFD
PUH-6TKSA.TH
3, 60Hz, 220V
140
ZR68KC-TF5
Munsell 0.70Y 8.59/ 0.97
Plate fin coil
Centrifugal (direct) o 1
0.12
0 (direct blow)
built-in
45-50
26 (1)
600 (23-5/ 8)
350 (13-3/ 4)
1900 (74-13/ 16)
53 (117) [55 (121)]
Munsell 3.0Y 7.8/ 1.1
Capillary tube
Hermetic
4.0
Line start
Anti-phase protector, Inner thermostat, thermal switch, HP switch
Plate fin coil
Propeller (direct) o 2
0.10 + 0.10
100 (3530)
Reverse cycle
56
970 (38-3/ 16)
345 + 24 (13-9/ 16 add 1)
1258 (49-1/ 2)
117 (313)
R-22
5.0(11)
9.52 (3/ 8)
19.05 (3/ 4)
Flared
Flared
Max. 50m
Max. 50m
1774 (SONTEX-200)
(Cooling/ Heating)
(Cooling/ Heating)
PSH-6GAK(H)
Single, 50Hz, 220-240V
PSH-6GAK
Single, 60Hz, 220V
—2.5/ 3.0
25-32 (882-1130)/ 27-35 (953-1236) 25-32 (882-1130)
4.73
7.74
4.58
7.50
7.04
20.3
6.42
18.51
Refrigerating oil (Model)
cc
Notes :W1. Rating Conditions < Single, 50Hz 240V / 3, 50Hz 415V >
Cooling : Indoor : 27:DB, 19:WB
Outdoor : 35:DB, 24:WB
Heating : Indoor : 20:DB,
W2. Rating Conditions < 3 , 60Hz 220V >
Outdoor : 7:DB, 6:WB.
Cooling : Indoor : 29:DB, 19:WB
Outdoor : 46:DB,
Heating : Indoor : 21:DB,
Outdoor : 7:DB, 6:WB.
8
4
P.C.
3.62
3.72
3.83
3.96
3.79
3.89
4.00
4.14
4.94
5.06
5.22
5.39
5.59
5.74
5.91
6.10
CA
6,342
6,793
7,270
7,773
8,401
8,999
9,631
10,297
10,332
11,053
11,814
12,617
11,737
12,556
13,421
14,333
P.C.
3.41
3.49
3.59
3.69
3.56
3.65
3.75
3.86
4.64
4.76
4.89
5.02
5.26
5.39
5.54
5.69
CA
6,671
7,130
7,616
8,128
8,837
9,445
10,088
10,767
10,858
11,590
12,365
13,184
12,334
13,166
14,047
14,977
P.C.
3.19
3.27
3.35
3.43
3.34
3.42
3.50
3.59
4.35
4.46
4.56
4.67
4.93
5.05
5.17
5.30
CA
6,983
7,452
7,948
8,470
9,250
9,872
10,528
11,220
11,336
12,098
12,902
13,750
12,878
13,743
14,657
15,621
P.C.
2.98
3.05
3.11
3.18
3.11
3.18
3.25
3.32
4.06
4.15
4.24
4.33
4.60
4.70
4.81
4.91
CA
7,278
7,760
8,267
8,799
9,641
10,279
10,951
11,656
11,815
12,597
13,420
14,284
13,421
14,310
15,246
16,227
P.C.
2.77
2.82
2.88
2.94
2.89
2.95
3.01
3.07
3.77
3.85
3.92
4.00
4.27
4.36
4.44
4.53
CA
7,555
8,053
8,573
9,115
10,008
10,668
11,356
12,074
12,265
13,073
13,917
14,797
13,933
14,851
15,810
16,809
P.C.
2.65
2.71
2.76
2.81
2.77
2.83
2.88
2.94
3.61
3.69
3.76
3.83
4.10
4.18
4.26
4.34
CA
7,768
8,271
8,779
9,293
10,290
10,956
11,630
12,310
12,611
13,427
14,252
15,086
14,326
15,253
16,190
17,138
20
Outdoor intake air DB:
25 30 35 40 45
Indoor
intake air
WB°C
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
Refrigerant piping length(one way)
5m
1.00
1.00
1.00
1.00
10m
0.981
0.989
0.981
0.975
15m
0.968
0.980
0.968
0.955
20m
0.952
0.970
0.952
0.935
25m
0.940
0.960
0.918
0.918
30m
0.925
0.950
0.925
0.900
35m
0.913
0.940
0.913
0.884
40m
0.900
0.930
0.900
0.869
45m
0.886
0.920
0.886
0.855
50m
0.874
0.910
0.874
0.840
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
P.C.
4.03
4.14
4.26
4.40
4.82
4.94
5.09
5.26
6.15
6.32
6.50
6.72
6.84
7.02
7.23
7.47
CA
6,300
6,749
7,223
7,723
9,183
9,837
10,528
11,256
10,707
11,469
12,275
13,124
12,518
13,410
14,352
15,345
P.C.
3.79
3.89
3.99
4.10
4.53
4.65
4.77
4.90
5.79
5.93
6.09
6.26
6.43
6.60
6.78
6.97
CA
6,628
7,084
7,566
8,076
9,660
10,324
11,028
11,770
11,263
12,037
12,858
13,723
13,168
14,074
15,034
16,046
P.C.
3.55
3.64
3.72
3.81
4.24
4.35
4.45
4.56
5.42
5.55
5.69
5.82
6.03
6.18
6.32
6.48
CA
6,938
7,404
7,896
8,415
10,112
10,791
11,509
12,265
11,789
12,581
13,419
14,301
13,785
14,711
15,689
16,721
P.C.
3.31
3.39
3.46
3.53
3.96
4.05
4.14
4.23
5.06
5.17
5.29
5.40
5.62
5.75
5.88
6.00
CA
7,231
7,709
8,213
8,742
10,539
11,237
11,971
12,742
12,287
13,101
13,957
14,856
14,367
15,318
16,319
17,370
P.C.
3.08
3.14
3.20
3.26
3.68
3.75
3.83
3.90
4.70
4.79
4.89
4.98
5.22
5.33
5.44
5.54
CA
7,506
8,001
8,517
9,056
10,941
11,661
12,414
13,199
12,756
13,596
14,474
15,389
14,915
15,897
16,923
17,993
P.C.
2.95
3.01
3.07
3.12
3.53
3.60
3.67
3.73
4.50
5.59
4.68
4.77
5.01
5.11
5.21
5.30
CA
7,718
8,217
8,722
9,233
11,249
11,977
12,713
13,457
13,115
13,964
14,822
15,690
15,334
16,327
17,330
18,345
20
Outdoor intake air DB°C
25 30 35 40 45
Indoor
intake air
WB°C
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
PSH-3GAK
PSH-4GAK
PSH-5GAK
PSH-6GAK
Service Ref.
DATA
4-1. PERFORMANCE DATA
1) COOLING CAPACITY (50Hz 240/415V)
(60Hz,220V)
Note CA :Capacity (W)
P.C.:Power consumption (kW)
Cooling capacity correction factors
9
2) HEATING CAPACITY (50Hz 240/415V)
CA
6,095
5,836
5,609
7,430
7,115
6,837
9,382
8,983
8,633
10,957
10,492
10,083
P.C.
2.11
2.28
2.42
2.35
2.54
2.69
3.04
3.28
3.48
3.38
3.65
3.87
-10
CA
6,985
6,711
6,438
8,516
8,181
7,849
10,753
10,330
9,911
12,558
12,065
11,575
P.C.
2.34
2.52
2.68
2.60
2.80
2.99
3.36
3.62
3.86
3.74
4.03
4.30
-5
CA
7,962
7,661
7,357
9,706
9,340
8,969
12,256
11,793
11,325
14,313
13,773
13,227
P.C.
2.57
2.77
2.97
2.86
3.09
3.30
3.70
3.99
4.27
4.12
4.44
4.74
0
CA
9,023
8,686
8,365
10,999
10,589
10,197
13,889
13,371
12,876
16,220
15,616
15,037
P.C.
2.83
3.04
3.26
3.14
3.39
3.63
4.06
4.38
4.69
4.52
4.87
5.22
5
CA
10,167
9,784
9,459
12,394
11,928
11,532
15,650
15,061
14,561
18,277
17,590
17,006
P.C.
3.09
3.33
3.57
3.44
3.70
3.97
4.45
4.79
5.13
4.94
5.33
5.71
10
CA
11,392
10,955
10,641
13,888
13,355
12,973
17,536
16,864
16,381
20,480
19,695
19,131
P.C.
3.37
3.63
3.89
3.75
4.04
4.33
4.85
5.22
5.60
5.39
5.80
6.23
15
Outdoor intake air DB°C
Indoor
intake air
WB°C
15
20
25
15
20
25
15
20
25
15
20
25
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
Refrigerant piping length(one way)
5m
1.00
1.00
1.00
1.00
10m
1.00
1.00
1.00
1.00
15m
1.00
1.00
1.00
1.00
20m
1.00
1.00
1.00
1.00
25m
1.00
1.00
1.00
1.00
30m
1.00
1.00
1.00
1.00
35m
0.998
0.998
0.998
0.998
40m
0.995
0.995
0.995
0.995
45m
0.993
0.993
0.993
0.993
50m
0.990
0.990
0.990
0.990
PSH-3GAK(H)
PSH-4GAK(H)
PSH-5GAK(H)
PSH-6GAK(H)
Service Ref.
CA
6,553
6,275
6,030
8,588
8,224
7,903
11,299
10,820
10,398
11,984
11,475
11,028
P.C.
2.35
2.53
2.69
2.84
3.06
3.25
4.13
4.45
4.73
4.64
5.00
5.31
-10
CA
7,511
7,216
6,923
9,843
9,457
9,073
12,950
12,442
11,936
13,735
13,196
12,660
P.C.
2.59
2.80
2.98
3.14
3.38
3.60
4.57
4.92
5.25
5.13
5.53
5.89
-5
CA
8,561
8,238
7,911
11,219
10,796
10,367
14,760
14,204
13,640
15,655
15,065
14,467
P.C.
2.86
3.08
3.29
3.45
3.72
3.98
5.03
5.42
5.80
5.65
6.09
6.50
0
CA
9,701
9,340
8,994
12,714
12,240
11,787
16,727
16,104
15,507
17,741
17,080
16,447
P.C.
3.14
3.38
3.62
3.79
4.09
4.38
5.52
5.95
6.37
6.20
6.68
7.15
5
CA
10,931
10,521
10,171
14,326
13,787
13,330
18,848
18,140
17,537
19,990
19,239
18,600
P.C.
3.43
3.70
3.96
4.15
4.47
4.79
6.04
6.51
6.98
6.78
7.30
7.38
10
CA
12,249
11,779
11,442
16,053
15,437
14,995
21,120
20,310
19,728
22,401
21,541
20,924
P.C.
3.74
4.03
4.32
4.52
4.82
5.22
6.59
7.09
7.61
7.39
7.96
8.54
15
Outdoor intake air DB°C
Indoor
intake air
WB°C
15
20
25
15
20
25
15
20
25
15
20
25
PSH-3GAK
PSH-4GAK
PSH-5GAK
PSH-6GAK
Service Ref.
(60Hz,220V)
Note CA :Capacity (W)
P.C. :Power consumption (kW)
Heating capacity correction factors
10
PERFORMANCE CURVE
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 25 35 46 52
OUTDOOR DB (:)
INDOOR WB (:)
INDOOR WB (:)
CAPACITY(RATIO)TOTAL INPUT(RATIO)
22
20
18
16
22
20
18
16
Cooling (60Hz)
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-15-10 -5 0 5 10 15
OUTDOOR WB (:)
INDOOR DB (:)
INDOOR DB (:)
CAPACITY(RATIO)TOTAL INPUT(RATIO)
15
20
25
25
20
15
Heating (60Hz)
1.4
1.2
1.0
0.8
CAPACITY(RATIO)TOTAL INPUT(RATIO)
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 25 35 46
OUTDOOR DB (:)
INDOOR WB (:)
22
20
18
16
INDOOR WB (:)
22
20
18
16
1.4
1.2
1.0
0.8
CAPACITY(RATIO)
0.6
1.4
1.2
1.0
0.8
TOTAL INPUT(RATIO)
0.6
0.4
-12-10 -5 0 5 10 15
OUTDOOR WB (:)
15
20
25
INDOOR DB (:)
INDOORDB (:)
25
20
15
11
Service Ref.
Mode
Capacity (W)
Total input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Indoor unit
Outdoor unit
Cool
6,750
4.29
0.16
0.73
0.8
4.13
18.77
80
Heat
9,500
3.49
0.16
0.73
0.8
3.33
15.6
80
Cool
9,850
5.27
0.26
1.20
1.5
5.01
14.14
69
Heat
12,450
4.22
0.26
1.20
1.5
3.96
11.3
69
Cool
11,000
6.82
0.30
1.35
1.5
6.52
19.23
135
Heat
16,500
6.06
0.30
1.35
1.5
5.76
17.38
135
Cool
13,400
7.42
0.38
1.62
2.1
7.04
20.30
140
Heat
17,500
6.80
0.38
1.62
2.1
6.42
18.51
140
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK
4-2. ELECTRICAL DATA
Service Ref.
Mode
Capacity (W)
Total input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Indoor unit
Outdoor unit
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
8,800
[10,600]
3.06
[4.86]
0.14
[1.94]
0.64
[8.82]
10,650
[12,950]
3.38
[5.68]
0.22
[2.52]
1.02
[11.47]
13,400
[15,900]
4,39
[6.89]
0.26
[2.76]
1.20
[12.56]
15,600
[18,100]
4.90
[7.40]
0.34
[2.84]
1.56
[12.92]
Cool
7,500
3.27
0.14
0.64
0.8
3.13
14.67/5.23
54/34
Heat
0.8
2.92
13.68/4.88
54/34
Cool
10,100
3.39
0.22
1.02
1.5
3.17
5.29
37
Heat
1.5
3.16
5.28
37
Cool
12,200
4.45
0.26
1.20
1.5
4.19
7.32
49
Heat
1.5
4.13
7.21
49
Cool
14,000
4.98
0.34
1.56
2.1
4.64
8.10
68
Heat
2.1
4.56
7.96
68
Service Ref.
Mode
Capacity (W)
Total input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Indoor unit
Outdoor unit
8,850
[10,750]
3.08
[4.98]
0.15
[2.05]
0.66
[8.92]
10,750
[13,250]
3.42
[5.92]
0.24
[2.74]
1.06
[11.93]
13,550
[16,250]
4.43
[7.13]
0.28
[2.98]
1.23
[12.97]
15,800
[18,500]
4.93
[7.63]
0.36
[3.06]
1.59
[13.33]
Cool
7,600
3.29
0.15
0.66
0.8
3.14
14.22/5.21
56/36
Heat
0.8
2.93
13.27/4.86
56/36
Cool
10,150
3.43
0.24
1.06
1.5
3.19
5.23
39
Heat
1.5
3.18
5.22
39
Cool
12,350
4.48
0.28
1.23
1.5
4.20
7.05
51
Heat
1.5
4.15
6.97
51
Cool
14,100
5.05
0.36
1.59
2.1
4.69
7.87
71
Heat
2.1
4.57
7.67
71
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
Service Ref.
Mode
Capacity (W)
Total input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Indoor unit
Outdoor unit
8,900
[11,000]
3.10
[5.20]
0.16
[2.26]
0.68
[9.43]
10,850
[13,550]
3.45
[6.15]
0.26
[2.96]
1.10
[12.35]
13,700
[16,700]
4.46
[7.46]
0.30
[3.30]
1.26
[13.76]
16,000
[19,000]
4.96
[7.96]
0.38
[3.38]
1.62
[14.12]
Cool
7,700
3.31
0.16
0.68
0.8
3.15
13.82/5.16
58/37
Heat
0.8
2.94
12.89/4.81
58/37
Cool
10,200
3.46
0.26
1.10
1.5
3.20
5.24
40
Heat
1.5
3.19
5.22
40
Cool
12,500
4.51
0.30
1.26
1.5
4.21
6.89
53
Heat
1.5
4.16
6.81
53
Cool
14,200
5.11
0.38
1.62
2.1
4.73
7.74
74
Heat
2.1
4.58
7.50
74
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
Indoor ······ 220V 50Hz 1 phase
Outdoor···· 220V 50Hz 1phase / 380V 50Hz 3phase
Indoor······ 230V 50Hz 1 phase
Outdoor ··· 230V 50Hz 1 phase / 400V 50Hz 3phase
Indoor ······ 240V 50Hz 1 phase
Outdoor···· 240V 50Hz 1 phase / 415V 50Hz 3 phase
Indoor ······ 220V 60Hz 1 phase
Outdoor···· 220V 60Hz 1 phase / 220V 60Hz 3 phase
12
4-3. STANDARD OPERATION DATA
Service Ref.
Mode
Capacity
Total
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Electrical cricuitRefrigerant circuit
Volts
Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Indoor side
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
PSH-3GAK(H) PSH-4GAK(H) PSH-5GAK(H) PSH-6GAK(H)
Cooling
W
kW
7700
3.31
PSH-3GAK(H)
1,50
240
0.68
PUH-3VKA.TH, PUH-3YKA.TH
1/3, 50
240 / 415
13.82 / 5.16
Mpa.G
(kgf/cm
Mpa.G
(kgf/cm
°C
°C
°C
m
DB°C
WB°C
DB°C
DB°C
WB°C
2.1
2.
(21.4)
G)
0.46
2.
G)
(4.69)
91.4
53.5
5.7
5
27
19
12.2
35
24
0.72
0.09
Heating
8900
3.10
[5.20]
0.68
[9.43]
12.89 / 4.81
1.91
(19.5)
0.35
(3.57)
85.6
5
20
15.5
46.0
7
6
Cooling
10200
3.46
PSH-4GAK(H)
1,50
240
1.10
PUH-4YKSA.TH
3,50
415
5.24
1.85
(18.9)
0.52
(5.3)
79.4
48.7
7.2
5
27
19
13.6
35
24
0.72
0.09
Heating
10850
3.45
[6.15]
1.10
[12.35]
5.22
1.72
(17.5)
0.37
(3.77)
77.4
5
20
15.5
38.8
7
6
Cooling
12500
4.51
PSH-5GAK(H)
1,50
240
1.26
PUH-5YKSA.TH
3,50
415
6.89
1.87
(19.1)
0.47
(4.79)
71.0
49.4
11.2
5
27
19
13.5
35
24
0.74
0.13
Heating
13700
4.46
[7.46]
1.26
[13.76]
6.81
1.82
(18.6)
0.36
(3.67)
72.9
5
20
15.5
42.2
7
6
Cooling
14200
5.11
PSH-6GAK(H)
1,50
240
1.62
PUH-6YKSA.TH
3,50
415
7.74
1.87
(19.1)
0.44
(4.49)
71.2
49.2
3.3
5
27
19
11.5
35
24
0.69
0.12
Heating
16000
4.96
[7.96]
1.62
[14.12]
7.50
1.82
(18.6)
0.37
(3.77)
72.5
-1.3-1.2-0.8-1.6
5
20
15.5
48.7
7
6
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(Mpa.G)= 10.2(kgf/cm
2
.
G)
13
Capacity
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Refrigerant pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V
A
V
A
Mpa·G
Mpa·G
:
:
:
m
DB:
WB:
DB:
DB:
WB:
TotalElectrical circuitRefrigerant circuitIndoor side
Outdoor
side
Service Ref.
Mode
PSH-3GAK
1, 60
220
PUH-3NKA.TH
1, 60
220
PSH-4GAK
1, 60
220
PUH-4TKSA.TH
3, 60
220
PSH-5GAK
1, 60
220
PUH-5TKSA.TH
3, 60
220
PSH-6GAK
1, 60
220
PUH-6TKSA.TH
3, 60
220
SHF
BF
Cooling
7,650
3.68
0.73
16.49
2.03
0.44
75.8
52.6
3.9
5
27
19
11.8
35
24
0.72
0.09
Heating
9,500
3.49
0.73
15.6
2.06
0.42
91.2
–
-2.1
5
20
15.5
49.5
7
6
–
–
Cooling
11,150
4.40
1.20
11.81
1.95
0.47
83.2
50.7
6.9
5
27
19
12.3
35
24
0.72
0.09
Heating
12,450
4.22
1.20
11.3
2.05
0.36
95.6
–
-2.0
5
20
15.5
46.6
7
6
–
–
Cooling
13,000
5.62
1.35
16.32
1.92
0.38
78.2
50.8
0.6
5
27
19
12.9
35
24
0.70
0.17
Heating
16,500
6.06
1.35
17.38
2.23
0.33
94.3
–
-2.9
5
20
15.5
49.5
7
6
–
–
Cooling
15,200
6.25
1.62
17.31
1.97
0.36
78.9
51.7
0.2
5
27
19
11.8
35
24
0.66
0.20
Heating
17,500
6.80
1.62
18.51
2.37
0.33
91.9
–
-2.1
5
20
15.5
50.3
7
6
–
–
(Of/F·G)
(Of/F·G)
(20.7)
(4.49)
(21.0)
(4.28)
(19.9)
(4.79)
(20.9)
(3.67)
(19.6)
(3.88)
(22.8)
(3.37)
(20.1)
(3.67)
(24.1)
(3.37)
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK
Refrigerant piping length(one way)
5m
2.5
3.5
4.7
4.3
10m
2.7
3.6
4.8
4.4
15m
2.8
3.8
5.0
4.6
20m
2.9
3.9
5.1
4.7
25m
3.1
4.1
5.3
4.9
30m
3.2
4.2
5.4
5.0
35m
3.3
4.4
5.6
5.2
40m
3.4
4.5
5.7
5.3
45m
3.6
4.6
5.9
5.5
50m
3.7
4.8
6.0
5.6
PSH-3GAK(H)
PSH-3GAK
PSH-4GAK(H)
PSH-4GAK
PSH-5GAK(H)
PSH-5GAK
PSH-6GAK(H)
PSH-6GAK
PUH-3VKA.TH
PUH-3YKA.TH
PUH-3NKA.TH
PUH-4YKSA.TH
PUH-4TKSA.TH
PUH-5YKSA.TH
PUH-5TKSA.TH
PUH-6YKSA.TH
PUH-6TKSA.TH
Service Ref.
INDOOR OUTDOOR
FACTORY
CHARGED
UP TO
3.2kg
4.2kg
5.4kg
5.0kg
Air flow
Air speed
Coverage range
K/X
m/W.
m
PSH-3GAK(H)
17
2.6
8.3
PSH-4GAK(H)
30
4.6
14.6
PSH-5GAK(H)
32
4.9
15.5
PSH-6GAK(H)
33
5.0
16.0
Service Ref.
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(Mpa·G)=10.2(kgf/
4-4. REFILLING REFRIGERANT CHARGE (R-22 : kg)
4-5. OUTLET AIR SPEED AND COVERAGE RANGE
FF
·G).
14
5
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Knock out hole
for branch duct
100
10
3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
VIEW "A"
A
340
370
520
260
240
130 71
530
600
270
250
70
180
235
Knock out hole for
wiring.[27
(Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Terminal block for
indoor/outdoor
connection.
Terminal block for
Remote controller
Electrical parts box
Liquid pipe [9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe [15.88(5/8F)
Drain pipe
Terminal block for
power supply
95
46122
47
Front side
Rear side
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
277
160
20
218
175
90
55 143
100
95
40 66
186
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
10
OUTLINES AND DIMENSIONS
PSH-3GAK PSH-3GAKH
Unit : mm
15
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Knock out hole
for branch duct
100
10
3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
340
370
520
260
240
130 71
530
600
350
330
70
260
315
Knock out hole for
wiring.[27 (Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Electrical parts box
Liquid pipe [9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe [19.05(3/4F)
Drain pipe
95
46122
47
Front side
Rear side
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
277
120
20
218
255
140
77
201
120
95
40 66
261
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
10
VIEW "A"
A
Terminal block for
indoor/outdoor
connection.
Terminal block for
Remote controller
Terminal block for
power supply
Use the current nuts meeting the pipe sizeUse the current nuts meeting the pipe size
of the outdoor unit.of the outdoor unit.
Availabailable pipe sizle pipe size
: Factory flare nut attachment to : Factory flare nut attachment to
the heat-exchanger the heat-exchanger
LIQUID SIDE
GAS SIDEGAS SIDE
[ 9.52 9.52
[ 19.05 19.05
PSH-4GAK PSH-4GAKH
PSH-5GAK PSH-5GAKH
PSH-6GAK PSH-6GAKH
Unit : mm
16
WIRING DIAGRAM6
SW1
Table 1
1 2 3 4 5
ON
OFF
SW5
Table 2
1 2 3 4 5 6 7 8
ON
OFF
SW6
SWE
ON
OFF
ON
OFF
1 2
SW5SW1
Refer to tables 1, 2.
WHT
(
WIRERESS
)
CN90
RED
(INTAKE)
CN20
1 2
WHT
(PIPE)
CN21
BLU
(
REMOCON
)
CN22
YLW
(
HEATER
)
CN24
BLK
(
INDOOR/OUTDOOR
COMUNICATION
)
CN30
1 2 1 2
TH1 TH2
R.B
CN41 CN2L
CN51 CN32
I.B
LED1
LED2
X4X5X6 X2
I.B
P.B
CNSK
(RED)
DC13.1V
CN2S
(WHT)
TO OUTDOOR UNIT
POWER SUPPLY
~(1 PHASE)
220-240V 50Hz
220V 60Hz
POWER SUPPLY
~(1 PHASE)
220-240V 50Hz
220V 60Hz
PSH-3~6GAKH models only
TB4
TB2
1
2
3
L
N
GRN/YLW
ZNR
WHT
(FAN)
FAN
YLW
(LOUVER)
CNL
FUSE
ORN
(POWER)
CND
RED
(POWER
BOARD)
CNDK
WHT
(POWER
BOARD)
CN2D
1 3 1 3 1 3 1 3
1
1
2
1 2
5
6
2
1 2
3
1
2
5 7
BLK
RED
YLW
ORN
BRN
BLU
BLU
BLU
BLU
RED
RED
ORN
BLK
BRN
RED
RED
BRN
RED
35
6
1
88H
26H
BLU
BRN
FS2FS1
H1
WHT
WHT
WHT
WHT
YLW
YLW
BLU
BLU
GRY
GRY
YLW
MF
X4 X2
X5
X6
1 2 3
TB6
TB5
1
1
2
2
TB2
L
N
GRN/YLW
88H
ML
1
2
[Servicing]
Fasten terminal of the terminal board"TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
P.B
INDOOR POWER BOARD
SYMBOL NAME
I.B
INDOOR CONTROLLER BOARD
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR<LOSSNAY>
CN32 CONNECTOR<REMOTE SWITCH>
CN41 CONNECTOR<HA TERMINAL-A>
CN51 CONNECTOR<CENTRALLY CONTROL>
SW1 SWITCH <MODEL SELECTION> wSee Table 1.
SWE,SW6
SWITCH<EMERGENCY OPERATION>
SW5 SWITCH<SYSTEM SELECTION> wSee Table 2.
X4 RELAY<FAN MOTOR>
X5 RELAY<FAN MOTOR>
X6 RELAY<FAN MOTOR>
X2 RELAY<LOUVER>
POWER SUPPLY<R.B>
LED1 POWER SUPPLY<I.B>
LED2
C CAPACITOR<FAN MOTOR>
FAN MOTOR
LOUVER MOTOR
MF
ML
SYMBOL NAME
TB4
TERMINAL BLOCK<INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (POWER SUPPLY)
CONNECTING LINE>
TB5
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE>
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE >
ROOM TEMP.THERMISTOR
<0:/15k", 25:/5.4k" DETECT>
PIPE TEMP.THERMISTOR/LIQUID
<0:/15k", 25:/5.4k" DETECT>
THERMAL FUSE<110::16A>
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
TH1
TH2
R.B
HEATER
WIRED REMOTE CONTROLLER BOARD
TB6
H1
26H
88H
FS1,2
NOTES:
1. Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (1, 2, 3).
3. Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
Check code
Symptom
Fb
Abnormality of indoor controller board.
FFFF
No corresponding unit.
– – – –
No trouble generated in the past.
P4
Abnormality of drain sensor(DS).
P5
Malfunction of drain-up machine.
P6
Freezing / overheating protection is working.
P8
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
P2
Abnormality of pipe temperature thermistor / Liquid.(TH2).
P1
Abnormality of room temperature thermistor.(TH1).
E0—E5
Abnormality of the signal transmission between remote
controller and indoor unit.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6)on the indoor control
board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling or heating, you have to set the switch(SWE)and switch(SW6)on indoor controller.
SWE:ON · Indoor fan is running high speed.
SW6-1:ON · Emergency operation of cooling mode.
SW6-1,2:ON · Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions.
(2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or temperature
control etc. does not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated,
because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc. to their original positions.
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless
remote control, refer to the technical manuals etc.
2. For the wired remote control : When you quickly press twice the
CHECK switch on the remote control, the unit begins self-diagnosis,
and Check Codes generated in the past appear on the display.
For Check Codes and Symptoms refer to the table.
PSH-3GAK PSH-4GAK PSH-5GAK PSH-6GAK
PSH-3GAKH PSH-4GAKH PSH-5GAKH PSH-6GAKH
17
7
Indoor
heat
exchanger
Distributor
with
strainer
PSH-5··········O.D.4.0oI.D.2.4-R350
PSH-6··········O.D.4.0oI.D.3.0-R1,200
Thermistor
TH2
Restrictor
valve
Flexible tube
Flexible tube
Flared
connection
Refrigerant pipe
(option)
19.05mm ([3/4)
(with heat insulator)
Refrigerant pipe
(option)
9.52mm ([3/8)
(with heat insulator)
Ball valve
4-way valve
Oil separator
Service
port
High pressure
control switch
THERMAL
SWITCH
Outdoor heat exchanger
Capillary
tube
Capillary tube
Thermistor
RT
Capillary
tube
Compressor
Bypass
valve
Restrictor
valve
Accumulator
Ball valve
(with service port)
w3:PUH-5,6TKSA only
w3
DDR
Strainer
Strainer
Strainer
Service
port
PUH-5Y·················(O.D.4.0oI.D.2.4- R840)o2
PUH-6Y·················(O.D.4.0oI.D.2.4- R1,200)o2
PUH-5T·················(O.D.4.0oI.D.2.4- R840)o2
PUH-6T·················(O.D.4.0oI.D.2.4- R740)o2
Indoor
heat
exchanger
Distributor
with
strainer
PSH-4··········O.D.4.0oI.D.2.0-R400
Thermistor
TH2
Restrictor
valve
Flexible tube
Flexible tube
Flared
connection
Refrigerant pipe
(option)
19.05mm ([3/4)
(with heat insulator)
Refrigerant pipe
(option)
9.52mm ([3/8)
(with heat insulation)
Ball valve
4-way valve
Oil separator
Service
port
High pressure
control switch
Outdoor heat exchanger
Capillary
tube
Thermistor
RT
Capillary
tube
Compressor
Bypass
valve
Restrictor
valve
Accumulator
Ball valve
(with service port)
Strainer
Strainer
Strainer
Service
port
(O.D.3.2oI.D.2.0-R820)o2
Indoor
heat
exchanger
Distributor
with
strainer
PSH-3············O.D.4.0oI.D.2.0-R500
Thermistor
TH2
Restrictor
valve
Flexible tube
Flared
connection
Refrigerant pipe
(option)
15.88mm ([5/8)
(with heat insulator)
Refrigerant pipe
(option)
9.52mm ([3/8)
(with heat insulator)
Ball valve
4-way valve
Oil separator
Service
port
High pressure
control switch
Outdoor heat exchanger
Capillary
tube
Thermistor
RT
Capillary
tube
Compressor
Bypass
valve
Muffler
Capillay
tube
w1
w2
Restrictor
valve
Accumulator
Ball valve
(with service port)
Strainer
Strainer
Strainer
Service
port
w2.PUH-3V,3Y·················O.D. 4.0 o I.D. 2.4 - R1,070
PUH-3N······················ O.D. 3.2 o I.D. 1.2 - R1250
w1.PUH-3N······················O.D. 4.0 o I.D. 2.4 - R600
Refrigerant flow in cooling
Refrigerant flow in heating
R.V coil
Heating ON
Cooling OFF
REFRIGERANT SYSTEM DIAGRAM
PSH-3GAK(H)/PUH-3VKA.TH,PUH-3YKA.TH
PSH-3GAK/PUH-3NKA.TH
PSH-4GAK(H)/PUH-4YKSA.TH
PSH-4GAK/PUH-4TKSA.TH
PSH-5GAK(H)/PUH-5YKSA.TH
PSH-5GAK/PUH-5TKSA.TH
PSH-6GAK(H)/PUH-6YKSA.TH
PSH-6GAK/PUH-6TKSA.TH
18
8
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is
reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (8-3).
Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (8-4).
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (8-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit
OC: Outdoor unit
E Check code
F Unit No.
G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen.
2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
TROUBLESHOOTING
8-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are
summarized in the table below. Check the contents below before investigating details.
8-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
■ Wired remote controller
19
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes following power-on
After about 2
minutes has
expired following power-on
• For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block
•Incorrect wiring between indoor and outdoor
units
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
•
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
• On wired remote controller
1Check code displayed in the LCD.
1 Check code
Symptom Remark
Wired remote controller
P1
Intake sensor error
P2
Pipe (TH2) sensor error
P4
Drain sensor error
P5
PA
Drain pump error
Forced compressor stop
P6
Freezing/ Overheating safeguard operation
P8
Pipe temperature error / Outdoor unit error
E4, E5
Remote controller signal receiving error
–
–
–
–
Fb
Indoor unit control system error (memory error, etc.)
E0, E3
E1, E2
Remote controller control board error
Remote controller transmission error
20