Disperses airflow up and
down as well as adjusts the
angle of air flow direction.
FilterAir intake grille
Air outletAir outlet
Swing louvers
Indicator lamp section
Air flow can be changed to horizontally
by moving the Guide vane to the left or
right.
Guide vane
● Indoor Unit
2
Page 3
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, blowing, heating and auto
mode.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating mode is not available.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
● Wireless remote controller
3
Page 4
2
w4
w5
22,700
6,650
3.54
3.44
15.8(99)
58
27/19.0°C, 35/24°C
Cooling (JIS B8616)
PK-2.5FAKL
PK-2.5FAKL
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 2
0.04
15 - 20(530-706)
0 (direct blow)
—
Wireless remote controller & Built-in
39 - 45
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
24 (53)
23,900
7,000
2.56 / 2.62
PU-2.5VJA
1.TH
Single, 50Hz, 220/240V
2.46 / 2.52
11.4 / 10.7 (98/98)
45 / 49
24,400
7,150
3.01
PU-2.5NJA.TH
Single, 60Hz, 220V
2.91
13.4 (99)
58
Munsell 3.0Y 7.8/1.1
Capillary tube
Hermetic
Line start
Inner thermostat, HP/LP switch
Plate fin coil
Propeller (direct) o 1
0.085
50 (1765)
—
870 (34-1/4)
295 (+24) (11-5/8 (add 1))
850 (33-7/16)
71 (157)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
w3 Max. 20m
w3 Max. 30m
NHJ41VMDT
2.0
32 / 38
NHJ38NBDT
1.7
—
5253
R-22 2.4 (5.3) R-22 2.4 (5.3)
Single, 60Hz, 220V
0.095
0.44 (98)
0.7
Single, 50Hz, 220/240V
0.095 / 0.095
0.44 / 0.44 (98/90)
0.7 / 0.8
Item
Service Ref.
Condition
Capacity w1
Total input w1
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
External finish
Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Booster heater
Operation control & Thermostat
Noise level (Low-High) w2
Unit drain pipe. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level w2
Dimensions
Weight
Refrigerant Charge
Pipe size O.D.
Connection method
Between the indoor &
outdoor units
Btu/h
W
kW
kW
A(%)
A
kW
m
3
/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A(%)
A
kW
W
kW
m
3
/min(CFM)
dB(A)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
Indoor, Outdoor D.B./W.B.°C
Liquid
Gas
W
D
H
W
D
H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side
Outdoor side
Height difference
Piping length
INDOOR UNIT
Fan
Fan
SPECIFICATIONS
2-1. STANDARD SPECIFICATION
w1 Refrigerant piping length (one way) : 5m (16ft)
w2 Noise level is measured in an unacoustic room based on JIS conditions.
w3 Up to 20m it is unnecessary to charge additional refrigerant.
w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C.
w5 Cooling SSA385, 386
4
Page 5
Item
Indoor, Outdoor D.B./W.B.°C
Condition
Capacity w1
Total input w1
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
External finish
Heat exchanger
Fan
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-High) w2
Unit drain pipe. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
OUTDOOR UNIT
Fan
Defrost method
Noise level w2
Dimensions
Weight
Refrigerant Charge
Pipe size O.D.
Connection method
Between the indoor &
outdoor units
REFRIGERANT PIPING
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Input
Running current (Power factor)
Starting current
Model
Motor output
Starter type
Protection devices
Crankcase heater
Fan(drive) o No.
Fan motor output
Airflow
Indoor side
Outdoor side
Height difference
Piping length
W
D
H
W
D
H
Liquid
Gas
Service Ref.
Btu/h
W
kW
kW
A(%)
A
kW
3
/min(CFM)
m
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A(%)
A
kW
W
kW
3
/min(CFM)
m
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
27,000
7,900
3.28 / 3.303.28 / 3.30
Single, 50Hz, 220/240V
0.095 / 0.095
0.44 / 0.44 (98/90)
0.7 / 0.8
Munsell 3.4Y 7.7/0.8(White)
Wireless remote controller & Built-in
PU-3VJC
Single, 50Hz, 220/240V
15.1/13.9(96/96)
NH52VNHT
1.TH
3.18 / 3.20
54 / 58
2.2
w6w7
32 / 38 32 / 38 38
R-22 2.8 (6.2)
PU-3YJC.TH
3, 50Hz, 380/415V
3.18 / 3.20
5.7/5.3(85/84)
NH52YDAT
5253
295 (+24) (11-5/8 (add 1))
PK-3FAKL
27/19.0°C, 35/24°C
Cooling (JIS B8616)
PK-3FAKL
Plate fin coil
Line flow (direct) o 2
15 - 20 (530-706)
0 (direct blow)
39 - 45
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
24 (53)
34 / 37
Munsell 3.0Y 7.8/1.1
Capillary tube
Hermetic
2.4
Line start
Plate fin coil
Propeller (direct) o 1
50 (1765)
870 (34-1/4)
850 (33-7/16)
73 (161)
9.52 (3/8)
15.88 (5/8)
w3 Max. 20m
w3 Max. 30m
w1 Refrigerant piping length (one way) : 5m (16ft)
w2 Noise level is measured in an unacoustic room based on JIS conditions.
w3 Up to 20m it is unnecessary to charge additional refrigerant.
w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C
w5 Cooling SSA385, 386
w6 Inner thermostat, HP switch, LP switch.
w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
0.04
—
0.085
—
Flared
Flared
27,300
8,000
3.54
Single, 60Hz, 220V
0.095
0.44 (98)
0.7
PU-3NJA.TH
Single, 60Hz, 220V
3.44
17.6(89)
80
NHJ47NADT
2.2
w6
R-22 3.5 (7.7)
w4
w5
23,500
6,900
4.19
4.09
20.9(89)
80
5
Page 6
Item
Service Ref.
PK-4FAKL
27/19.0°C, 35/24°C
Cooling (JIS B8616)
w4
w5
33,800
9,900
5.08
37,500
11,000
4.38
33,400
9,800
3.46 / 3.633.40 / 3.47
PU-4VLJSA
2.TH
Single, 50Hz, 220/240V
3.35 / 3.52
16.9 / 16.3 (90/90)
79 / 79
PU-4YJSA
1.TH
3, 50Hz, 380/415V
3.29 / 3.36
5.7 / 5.5 (87/85)
38 / 38
NH56VNDT
2.7
NHJ56YDAT
2.7
Line start
Munsell 3.0Y 7.8/1.1
Capillary tube
Hermetic
Plate fin coil
Propeller (direct) o 2
0.065 + 0.065
95 (3352)
—
870 (34-1/4)
295 (+24) (11-5/8 (add 1))
1258 (49-1/2)
94 (207)
9.52 (3/8)
19.05 (4/3)
Flared
Flared
w3 Max. 30m
w3 Max. 40m
PU-4TJSA.TH
3, 60Hz, 220V
4.27
12.2 (92)
69
NHJ56TKAT
2.7
w6w7w7
545555
32 / 3832 / 3838
R-22 3.8 (8.4)R-22 4.6 (10.1)R-22 4.6 (10.1)
4.97
14.0(93)
69
PK-4FAKL
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 2
0.07
22 - 28 (777 - 989)
0 (direct blow)
—
Wireless remote controller & Built-in
41 - 46
20 (13/16)
1,680 (66-1/8)
235 (9-1/4)
340 (13-3/8)
28 (62)
Single, 50Hz, 220/240V
0.114 / 0.114
0.53 / 0.53 (98/90)
0.8 / 0.9
Single, 60Hz, 220V
0.114
0.53 (98)
0.8
Condition
Capacity w1
Total input w1
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
External finish
Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure
Booster heater
Operation control & Thermostat
Noise level (Low-High) w2
Unit drain pipe. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level w2
Dimensions
Weight
Refrigerant Charge
Pipe size O.D.
Connection method
Between the indoor &
outdoor units
Btu/h
W
kW
kW
A(%)
A
kW
m
3
/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A(%)
A
kW
W
kW
m
3
/min(CFM)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
Liquid
Gas
W
D
H
W
D
H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side
Outdoor side
Height difference
Piping length
INDOOR UNIT
Indoor, Outdoor D.B./W.B.°C
Fan
Fan
w1 Refrigerant piping length (one way) : 5m (16ft)
w2 Noise level is measured in an unacoustic room based on JIS conditions.
w3 Up to 20m it is unnecessary to charge additional refrigerant.
w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C
w5 Cooling SSA385, 386
w6 Inner thermostat, HP switch, LP switch, Thermal switch
w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
Condensing temperature
Suction temp.
Ref. pipe length
Intake air temperature
Discharge air temperature
Indoor side
Intake air temperature
side
Outdoor
D.B.
W.B.
D.B.
D.B.
W.B.
W
kw
Mpa
(O/F)
Mpa
(O/F)
:
:
:
m
:
:
:
:
:
Total Electrical circuit Refrigerant circuit Indoor side Outdoor side
The unit of pressure has been changed to Mpa on the international system of unit(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
BAND CENTER FREQUENCIES, Hz
PK-2.5FAKL
PK-3FAKL
High
Low
45
SPL(dB)39LINE
NOTCH
UNIT
WALL
1m
1m
MICROPHONE
90
80
70
60
50
40
30
20
10
631252505001000 2000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
BAND CENTER FREQUENCIES, Hz
PK-4FAKL
High
NOTCH
Low
46
SPL(dB)
41
LINE
w The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally
from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture inside the room.
3-5. NOISE CRITERION CURVES
11
Page 12
4
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
15
Terminal block for power supply
Terminal block for control
Terminal block for
wired remote controller
(Liquid pipe)
Liquid pipe 9.52(3/8F)
Gas pipe 15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for piping
25
1110
183
240
B
1120
552
55
120
107
111
Air outlet
552
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for
tapping screw
66-ø6 hole for
tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240280314
610
90
Drainage range
on left-hand side
Drainage range
on right-hand side
10 91=(910)
180
OUTLINES AND DIMENSIONS
PK-2.5FAKL
PK-3FAKL
Unit : mm
12
Page 13
Terminal block for
wired remote controller
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1680
1370
Air intake
235
C
Knock out hole for right piping
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
Terminal block for power supply
Terminal block for control
(Liquid pipe)
Gas pipe 19.05(3/4F)
Liquid pipe 9.52(3/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for wiring
25
1110
183
240
B
1400
55
120
102
111
694
Air outlet
694
Air outlet
Change vane (manual)
Under panel
(Removable at left-hand side piping)
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
[Servicing]
Fasten terminal of the terminal board"TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
WHT
BOARD)
LED2
BLK
CN30
ORN
RED
(POWER
CNDK
WHT
(POWER
BOARD)
CN2D
)
BLU
(
REMOCON
CN22
BLU
I.B
LED1
BLU
R.B
WIRED REMOTE CONTROLLER BOARD
(OPTION)
TB6
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE >
W.B
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
RU
BZ
BUZZER
LED1
LED<RUN INDICATOR >
LED2
LED<HOT ADJUST>
SW1
SWITCH<HEATING ON/OFF>
SW2
SWITCH<COOLING ON/OFF
H2
DEW PREVENTION HEATER
DS
DRAIN SENSOR
DP
DRAIN-UP MACHINE
XP
RELAY (DRAIN-UP MACHINE)
P.B
CNSK
1 2
3
(RED)
DC13.1V
CN2S
1 2
(WHT)
BLK
1
WHT
2
)
TB5
1
TRANSMISSION WIRES DC12V
2
NAMESYMBOL
GRN/YLW
R.B
(OPTION)
TB6
TB2
TB4
L
N
1
2
3
12
POWER SUPPLY
~(1 PHASE)
220-240V 50Hz
220V 60Hz
TO OUTDOOR UNIT
Table 1
SW1
1 2 3 4 5
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (1, 2, 3).
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
[Self-diagnosis]
Please refer to technical manuals etc.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6)on the
indoor control board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set the switch(SWE)and switch(SW6)on indoor controller.
SWE:ON · Indoor fan is running high speed. · Drain-up machine(Optional)is working.
SW6-1:ON · Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions.
(2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or temperature
control etc. does not function.
(3) Emergency cooling should be limited to 10 hours maximum(The indoor unit heat exchanger may freeze).
(4) After emergency operation has been deactivated, set the switches etc. to their original positions.
(5) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate
position.
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
7-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are
summarized in the table below. Check the contents below before investigating details.
17
Page 18
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Address
display
HOUR
button
ON/OFF
button
[Output pattern A] Errors detected by indoor unit
*1If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp flash
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
Beeper sounds/OPERATION
INDICATOR lamp flashes1 Check code
SymptomRemark
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
2
P2Pipe (TH2) sensor error
4P4Drain sensor error
5
P5
PA
Drain pump error
Forced compressor stop
6P6Freezing/ Overheating safeguard operation
8P8Pipe temperature error / Outdoor unit error
9E4, E5Remote controller signal receiving error
10
–
11
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
–E1, E2Remote controller control board error
Remote controller transmission error
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
■ Wireless remote controller
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• Select the address of the indoor unit
for the self-diagnosis.
Main indoor unit : “00”
Sub indoor unit : “01”
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
18
Page 19
If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
•
Symptom
Wired remote controller
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
LED2 (power for wired remote controller)
For about 2
minutes following power-on
After about 2
minutes has
expired following power-on
• For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block
•Incorrect wiring between indoor and outdoor
units
•Remote controller wire short
always lit.
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
Cause
19
Page 20
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method
Abnormality of room temperature
thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: 90: or more
Open: -40: or less
Abnormality of pipe temperature
thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature
of 90: or more or -40: or
less.
5 Defective indoor controller board.
Countermeasure
1–3 Check resistance value of thermistor.
0: ······15.0k"
10: ····9.6k"
20: ····6.3k"
30: ····4.3k"
40: ····3.0k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 7-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 7-7. Turn
the power on and check restart after inserting
connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is exclusively low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive
difference with actual pipe <liquid> temperature,
replace indoor controller board.
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pump operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
0: ······6.0k"
10: ····3.9k"
20: ····2.6k"
30: ····1.8k"
40: ····1.3k"
2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 7-7. Turn
the power on again and check restart after
inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 7-7.
Turn the power off, and on again to operate
after check.
20
Page 21
Error Code
P6
Meaning of error code and detection method
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention
mode if pipe temperature stays under
-15: for three minutes, three minutes
after the compressor started. Abnormal
if it stays under -15: for three minutes
again within 16 minutes after six-minute
resume prevention mode.
<Frost prevention mode>
If pipe temperature is 1: or below
when 16 minutes has passed after compressor starts operating, unit will start
operating in frost prevention mode which
stops compressor operation. After that,
when pipe temperature stays 10: or
more for 3 minutes, frost prevention
mode will be released and compressor
will restart its operation.
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
Cause
operation beyond the tolerance
range
defective.
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) onthe indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 7-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
P8
E0
or
E4
Abnormality of pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes later of compressor start and 6 minutes later of the liquid pipe is out of cooling
range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -5 deg ] (TH2-TH1)
TH2: Liquid pipe temperature
TH1: Intake temperature
troller can not receive normally any
transmission from indoor unit of refrigerant address “0” for three minutes.
(Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two minutes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from
remote controller board or from other
indoor controller board for three minutes.
(Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two
minutes. (Error code: E4)
1 Slight temperature difference
between indoor room
temperature and pipe temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase
3 Protection device is working
4 Damaged outdoor coil thermis-
tor
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
3 Mis-wiring of remote controller.
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote
controller.
1~4Check pipe temperature with room
temperature display on remote
controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
1 Check the indoor/outdoor connecting wire.
2 Change the connection of electric wiring.
3 Check the protection device.
4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal,
replace the outdoor controller board.
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max.500m
(Do not use cable x 3 or more)
• The number of connecting indoor units:
max.16units
• The number of connecting remote con-
troller: max.2units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Put the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
[ c),d)→Noise may be causing abnormality. ]
∗ If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
trollers)
with two indoor units or more.
address.
circuit of remote controller.
circuit of indoor controller
board.
mission wire of remote con-
troller.
board.
· Drain pump clogging
· Drain pipe clogging
side heater
connector
sensor
· Drain water descends along
lead wire.
· Drain water waving due to filter
clogging.
difference at twin, triple,
quadruple system.
connecting at twin, triple,
quadruple system.
liquid pipe temperature thermis-
tor detection is defective.
Countermeasure
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem.
Put the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG”is displayed, replace
remote controller.
c)When “RC E3”or “ERC 00-66”is displayed,
noise may be causing abnormality.
1 Replace indoor controller board.
Check the drain pump.
Performance
Please confirm whether water can be drained.
Confirm the resistance of the drain sensor side
heater.
Check the connector contact failure.
1 Check the drain sensor leadwire mounted.
2 Check the filter clogging
Check the piping connection.
Check the indoor/ outdoor connecting wires.
Check the room temperature display of remote
controller.
Check the indoor liquid pipe temperature dis-
play of outdoor controller board.
22
Page 23
7-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Cause
Countermeasure
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected.
Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected.
Check the fuse on indoor controller
board.
Check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
• When no voltage output.
Check the wiring connection between
CNDK on indoor controller board and
CNSK on indoor power board.
If no problem are found,indoor power
board is defective.
• When DC12.5~13.7V is detected.
Check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found,indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant
system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires
4 Defective remote controller
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit.
Set main/sub using SW5-3 on indoor
controller board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller
board.
• When LED2 is blinking, check the shortcut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoor
connecting wires again, and; if LED2 is
blinking, outdoor unit’s controller board is
defective; if LED2 is lit, connection failure
of indoor/outdoor terminal block etc. has
returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
23
Page 24
1 Turn on the power to the unit at least 12 hours before the test run.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.)
A and current operation mode are displayed.
TEST RUN
TEST RUN
3 Press the button to activate mode, then check whether
cool air is blown out from the unit.
MODE
COOL
4 Press the button and check whether fan speed changes.
FAN
5 Press the button and check whether the auto vane operates properly.
VANE
6 Press the ON/OFF button to stop the test run.
Note:
•
Point the remote controller towards the indoor unit receiver while following steps 2 to 6.
• It is not possible to run the in FAN or DRY mode.
Phenomena
• After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage,
looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
• Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M".
• Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0M".
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in
HEAT mode. (Working of COOL protection function)
Cause
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board.
7-5. TEST RUN AND EMERGENCY OPERATION
7-5-1. Before test run
Countermeasure
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
7-5-2. Test run (Using wireless remote controller)
A
TEST RUN
ON/OFF TEMP
6
FAN
AUTO STOP
3
2
CHECK
TEST RUN
LOUVER
RESETSETCLOCK
VANE
MODE
4
AUTO START
5
h
min
24
Page 25
7-5-3. When wireless remote controller troubles or its battery is exhausted
Receiver
Operation lamp
Emergency operation switch (cooling)
Mode
Cooling
Set temperature
Fan speed
Airflow direction
24:
High
Horizontal (30deg)
wEmergency operation will be performed as follows.
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6)on the
indoor control board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set the switch(SWE)and switch(SW6)on indoor controller.
SWE:ON · Indoor fan is running high speed. · Drain-up machine(Optional)is working.
SW6-1:ON · Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points:
(1)
Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions.
(2)
Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or
temperaturecontrol etc. does not function.
(3)
Emergency cooling should be limited to 10 hours maximum(The indoor unit heat exchanger may freeze).
(4)
After emergency operation has been deactivated, set the switches etc. to their original positions.
(5) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate
position.
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation
• Press either emergency operation switch.
7-5-4. When wired remote controller or indoor unit micro computer troubles
25
Page 26
7-6. HOW TO CHECK THE PARTS
0
10
20
30
40
50
-20 -10010 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Fan motor (MF)
Disconnect the connector, then measure the resistance using a tester.
(Surrounding temperature 10°C~30°C)
Measure the resistance between the terminals using a tester.
Normal
4.3k"~9.6k"
Abnormal
Open or short
Motor terminal
or
Relay connector
Normal
PK-
2.5, 3FAKL
Abnormal
Red-White
99.5"i10%
Open or short
White-Black
103.5"i10%
Protector
OFF : 130i5˚C
ON : 80i20˚C
Parts nameCheck points
4
FAKL
62.6"i10%
74.0"i10%
Vane motor (MV)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20°C~30°C)
Normal
186~214"
Abnormal
Open or short
3 6 1
4
5
2
M
Pink
Connector
Red
Orange
Blue
Brown
Yellow
Brown-Yellow
Brown-Blue
Red-Orange
Red-Pink
PK-2.5FAKL PK-3FAKL PK-4FAKL
Relay connector
1
Red
1
White
2
3
Black
3
5
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Thermistor R0=15k' ±3%
Fixed number of B=3480 ± 2%
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
FUSE
(6.3 A 250 V)
CND
Power supply input
(220~240V AC)
CNP
Drew prevention
heater (H2)
(220-240V AC)
CN2D
Connect to the indoor
power board (CN2S)
(12.5~13.7V DC)
LED1
Power supply (I.B)
LED2
Power supply (R.B)
SW6
Emergency
operation
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN30
Transmission
(Indoor/outdoor)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
CN51
Centrally control
SWE
Emergency operation
FAN
Fan motor output
Jumper wire J41, J42
Pair number setting with
wireless remote controller
28
SW2
Capacity setting
CN105/92
(RED)
CN24
Heater output
(12V DC)
CN27
Drain pump output(DP)
(12V DC)
CN32
Remote switch
CN2L
Connector
(LOSSNAY)
SW5
System setting
SW1
Model setting
Page 29
7-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model
settings
SW5
System
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Remarks
SW2
J41
J42
0
1
2
3 ~ 9
Wireless remote
controller setting
Control PCB setting
J41J42
<Settings at time of factory shipment>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disconnected.)
(Marks in the table below) Jumper wire ( : Short : Open)
SW5-3 Main/Sub setting
OFF : Main ON : Sub
SW5-4 Rotaion operation setting
OFF : Not avairable ON : avairable
SW1
ON
OFF
1 2 3 4 5
SW5
ON
OFF
1 2 3 4 5 6 7 8
SW2MODELS
PK-2.5FAKL
PK-3FAKL
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
PK-4FAKL
1 2 3 4 5
ON
OFF
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
29
Page 30
8FUNCTION SETTING
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
LOSSNAY
connectivity
Power supply
voltage
Frost prevention
temperature
Humidifier control
Rotation
OFF
ON
Indoor unit's (Main) internal sensor
Remote controller's internal sensor w1
Not supported
Supported (indoor unit not equipped with outdoor air intake)
Supported (indoor unit equipped with outdoor air intake)
240V
220V,230V
1: (Normal)
-3:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
24h cycle
168h cycle
Back up function
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
3
01
02
03
04
15
16
20
The setting is
applied to all
the units in the
same
refrigerant
system.
8-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number.
• When setting functions for a simultaneous- Twin indoor unit system, set the unit number to 01 to 02 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
30
Page 31
Rotation setting (Function setting mode No.20
)
Function setting
FeaturesIndoor controller board
Mode No.
This system can correspond only by the pattern of two refrigerant group by 1 : 1
(indoor and outdoor unit combination) systems.
Setting No.
SW5-3 setting SW5-4 setting
20
01
(
24hours cycle
)
02
ON
OFF : Main
ON : Sub
(
168hours cycle
)
03
(
Back up
function
)
When abnormality occurs while
operating, it changes as a back up unit
,
and operating continues.
Each system operates alternately for
24hours.
Each system operates alternately for
168hours.
Example of unit's operation
(Setting No. = 01 or 02)
Main Unit is abnormal
Operation starts Main➝SubSub➝Main
(Setting No. = 02
• • •
168hours cycle)
Outdoor
unit
(Setting No. = 03)
Main Unit is abnormal
Indoor
Operation startsMain➝Sub
unit
Remote
Controller
Main➝Sub
ON
OFF
OFF
Main
ON
OFF
ON
ON
OFF
indoor
unit
Sub
indoor
unit
24h24h
Main
indoor
unit
Sub
indoor
unit
Main
Sub
31
Page 32
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn
off the function that raises the set temperature by 4 degrees during HEAT operation .
The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode.
(Enter address "50" in troubleshooting
mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when
you press the INSPECT button twice to display
"INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation
area, the unit ends function selection mode
automatically if nothing is input for 10 minutes
or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change
unit No.
YES
NO
7
Selecting functions using the wireless remote controller (Type C)
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refrigerant system with wireless function. Address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings.
2 Press the button twice continuously. → CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press
the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation.
Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same
refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number.
Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number.
7 Repeat steps 3 to 5 to change unit number and make function settings on it.
8 Complete the function settings
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
Use of two controllers enables
operation of the air
conditioner both
from a distance
and nearby.
C.Group control
operation
Use of one remote
controller to control multiple air
conditioners with
the same settings
simultaneously.
D.Remote/local
combined control
operation
Allows start/stop
of the air conditioner from a distance, and prohibits/permits start/
stop from remote
controllers.
E.Operation by
external signal
F.
Control and remote
display by external
signal (extraction
of monitor signal)
Enables you to
display the operation state and
control start/stop
from a distance.
• There are two types of remote controllers: wired type
and wireless type.
• Simultaneous twin indoor units are started or stopped
simultaneously.
• Up to two remote controllers can be connected to
one group.
• Simultaneous twin units are counted as each unit.
• Operation control by the latest command (last entered priority)
• Wired and wireless remote controllers can be combined as a pair.
• One group can consist of up to 16 indoor units, and
they can be started sequentially by connecting the
remote controller to them and assigning an address
to each inter face.
• Simultaneous twin units are counted as one unit.
• All the units belonging to the same group are operated in the same mode, but thermostats can be
turned ON/OFF individually for each indoor unit.
• Up to two remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectively
from a distance.
• Operation can be switched between the remote operating panel and local controller.
• Operations (e.g., temperature adjustment, airflow, airflow direction) except for start/stop operations can be
performed even if the remote controller is being operated.
• In the case of simultaneous twin units connect the
controller to one indoor unit only. If connected to two
indoor units, an error (operation stop) may occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote ON/OFF adapter" enables
remote control via relay. (Level signal)
Extraction of non-voltage contact output
Extraction of DC12 V contact output
* One of the wired remote con-
trollers must be set as a sub
remote controller.
Wired remote controller (additional)
(PAR-21MAA)
Inter face MAC-397IF-E
Remote ON/OFF adapter
(PAC-SE55RA-E)
Relay box
(Part to be provided at your site)
Remote operating panel
(Part to be provided at your site)
Remote ON/OFF adapter
(PAC–SE55RA-E)
Remote operation adapter
(PAC-SF40RM-E)
Remote display panel
(Part to be provided at your site)
Remote display adapter
(PAC-SA88HA)
Remote display panel
(Part to be provided at your site)
• Use of optional "remote operation adapter" and
"remote display panel" (Part to be provided at your site)
provides non-voltage contact outputs of signals
(operation, error) and operation/stop input function.
• Use of optional "remote display adapter" and "remote display panel" (Part to be provided at your site)
provides DC12 V contact outputs of signals
(operation, error) and operation/stop input function.
external timer,
refer to Remote/
handheld combined control operation".
H.Interlock opera-
tion with periph-
eral equipment
Enables control of
Mitsubishi Lossnay
ventilator by remote
controller.
I.Rotation
• Weekly timer:
In addition to ON/OFF, up to eight temperature
patterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
performed once within 72 hours (can
be set in 1-hour increments).
• Auto off timer:Operation is stopped when the preset
time elapses following the start of
operation.
The time can be set from 30 minutes
to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
• Connecting a Lossnay ventilator and an indoor unit
enables control of interlock/solo ventilation operation and airflow.
(Only the microcomputer type Lossnay ventilator
can be used.)
•
•
MA Remote controller
(PAR-21MAA)
When abnormality occurs while operating, it changes
into operating the back up unit, and operating is
continued.
(Unit function Mode No. 20 setting No.3 , Indoor
controller board SW-5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
Each system operates alternately for 24 hours or 168
hours.
(Unit function Mode No. 20 setting No.1: 24 hours/
No.2 : 168 hours, Indoor controller board SW 5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
This system can correspond only by
the pattern of two refrigerant group
by 1 : 1 (indoor and outdoor unit
combination) systems.
• Remote controller cable terminal block
1,2 (No polarity)
(2) Wireless remote controller
(Reference)
11
If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions.
22
Electrical wiring diagram
35
Page 36
9-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
(R: Wired remote controller)
Slim Air Conditioner System
Standard 1:1Simultaneous Twin
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some function may be
restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
3 Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different
models. However, some functions may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
In the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with systems
3
consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the pair numbers
will be "0" (factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
operation made last by any of the remote controllers will be effective.
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless
remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system
consists of different models. However, some functions may be restricted.
2
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
3
When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
operation made last by any of the wireless remote controllers will be effective.
(R': Wireless remote controller receiver)
2
2
2
Remote controller cable
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Remote
controller
cable
OC
2
IC
2
R-1
Indoor/outdoor
connection cable
R-2
2
Indoor/outdoor
connection cable
Receiver
connection
cable
OC
2
IC-1
99
R'-1
IC-2
R'-2
Remote
controller
cable
OC
3(2)
IC
Receiver
connection
9
2
cable
R
R'
Indoor/outdoor
connection cable
36
Page 37
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the
connecting cable used for each system.
• The cables connected to the Indoor unit should be mounted on or near the Indoor unit.
If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
• Set the interface dip switch (SW500–502) settings before turning on the power.
• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
INDOOR
9-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
●
●
●
●
Group control can be operated by using MAC-397IF-E.
The setting of wired remote controller is subjected to variation according to the function of the indoor unit.
(for mode operation, setting temperature, fan step, air direction)
The display of remote controller and operating the indoor unit might be different.
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
CN105
or
CN92
Indoor control board
Mounting screws (black) 3.5 o 12
Connect the connecting cable that comes with the
interface unit to the connector
CN105 or CN92 on the indoor control board.
Interface unit mounting cord clamp or mounting
cord clamps
Connecting cable for each system
Mounting cord clamp
Electrical wire mounting
bracket
Mounting screws 4 o 16
Mounting screws 4 o 10
Mounting cord clamp
37
Page 38
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller..
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10: and 38:.
CN560
TB580
2
1
2
A
B
Indoor unit
Remote control cord that came with
the MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set.
SW501:
SW501- No. 1-4: Refrigerant address
Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1
234
ON
1
234
ON
1
234
ON
1
234
1Outdoor unit
2Outdoor unit
3Indoor unit
4Interface
5MA remote controller
Refrigerant
address
0
1
2
15
SW501- No. 5–6
ON
5
6
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller.
* This can be switched when an accurate room temperature cannot be detected by the air conditioner unit.
PK-FAK series do not have a room temperature sensor on their MA remote controllers.
No. 5 should normally be set to OFF.
Under the following conditions, No.6 should normally be set to ON.
Interface unit
Refrigerant
address "0"
Refrigerant
address "1"
Refrigerant
address "2"
MA remote controller
(PAR-21MAA)
* PAR-20MAA cannot be used
with this interface.
112
3333
4
5
44
38
Page 39
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1
No. 2
No. 3
No. 4
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
FunctionsOFFONComments
Only specify these settings when connecting an
23456
Refrigerant address 0
MA remote controller.
Refrigerant address 1
23456
Refrigerant address 2
23456
Refrigerant address 3
23456
Refrigerant address 4
23456
Refrigerant address 5
23456
Refrigerant address 6
23456
Refrigerant address 7
23456
Refrigerant address 8
23456
Refrigerant address 9
23456
Refrigerant address 10
23456
Refrigerant address 11
23456
Refrigerant address 12
23456
Refrigerant address 13
23456
Refrigerant address 14
23456
Refrigerant address 15
23456
SW No.
No. 5
No. 6
Functions
Room temperature detector
The model of Mr. SLIM exists in the
same group.
Indoor unit
Not mixed
OFF
39
ON
Remote control
Mixed
Comments
This should normally be set to OFF.
This should normally be set to ON.
Page 40
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
Lamp off
DC 12 V is not being supplied from the
air conditioner.
Device is not communicating properly
with the air conditioner.
Device is not communicating properly
with the MA remote controller.
Lamp on
DC 12 V is being supplied from the air
conditioner.
–
–
Blinking
–
Blinking at approx. 1 second intervals: Device is
communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is communicating normally with the MA remote controller.
SW502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
No. 8
Functions
Cooling only type/ Heat pump type
Auto mode
Fan speed
Vane
Swing
Not in use
Fan mode
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
Available
Available
–
Not available
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
Not available
Not available
–
Available
Comments
Set to OFF.
Permanently set to OFF.
4 speeds
3 speeds (2-speed
model set ON)
When operating a 2-speed model with the 3-speed
setting (ON), the MA remote controller display will
indicate 3 fan speeds.
The table below shows the displays and the actual
outputs at that time.
DisplayMeaningIndoor unit output
Low speedLow speed
Medium speedHigh speed
High speed
Set the mode in accordance with the operation
manual for the indoor unit.
Heat pump type : Set to ON.
Cooling only type : Set to OFF.
The Vane function of either of indoor unit :
When the function is provided, it is Available (OFF).
When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit :
When the function is provided, it is Available (OFF).
When the function is not provided, it is Not available (ON).
Set to ON.
High speed
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit.
The device will not function properly if the connecting cable is extended so the connecting cable should not be extended.
Mount the interface unit securely to a pillar or wall using 2 or more screws.
■ When Using Wall Mounting Brackets
1
Attach the wall mounting brackets to the interface unit
using 2 mounting screws.
2
Mount the unit to a pillar or wall using 2 mounting screws.
Interface unit
Wall mounting
brackets
Mounting screws
Mounting screws
Cord clamp for
wiring
Mounting screws
40
Page 41
■ When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting
screws.
Interface case
mounting screws
Mounting
screws
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not
fall.
Interface unit
Cushioning material
When mounting the interface unit inside a ceiling
or wall, install an access door to facilitate maintenance.
When the interface unit is mounted
above an indoor unit, it should be
positioned 40 mm or more away from the
unit to ensure that ceiling grills can be
removed.
40 mm or more
Attach the interface unit connecting cable here.
Store extra connecting cable in the ductwork space
behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
41
Page 42
9-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Indoor unitIndoor unitIndoor unit
Remote controller
Control roomroom 1room 2room 3
Indoor unit
Relay boxRelay boxRelay box
Indoor unit
Control circuit
power supply
Indoor unitIndoor unit
Remote
controller
Remote/Local
selection switch
Control room W
room 1room 2room 3
Remote
controller
Remote
controller
Remote
controller
• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go
from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the
unit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a
clear determination of whether or not there was a power failure. When it has been determined that there has been a power
failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has
appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller.
• When there is group control, selection of all refrigerants is required.
9-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or centralized monitoring of the air conditioners in each room can be attained.
• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote controllers with 0.3 to 1.25 mm22-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
9-7. COMBINED REMOTE/LOCAL CONTROL
• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter
(PAC-SE55RA-E sold separately) through the relay box installed on site. When this remote control is cancelled, the local
remote controller can be used for operating and stopping the air conditioner.
1. Basic system wiring
• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes
from the relay box and remote/local selection switch and connect it to the CN32 connector on the printed circuit board for
the indoor unit
<Points of precaution>
11
Match the rated power supply voltage of the remote/local selection switch and relay (X2) with the power supply for the con-
troller.
22
When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not start
at the same time. If this is not performed, all of the units will start at one time creating an over current that will cause the circuit
breaker to operate.
33
An on-delay system is one that includes specifications for operating a limited time when an on signal is received and has a tem-
porary off timer for recovery operations.
44
Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-
vided, abnormal operation will occur.
(1) System diagram
W The AC for the control room is usually disconnected from the remote/local control system.
42
Page 43
Control circuit
power supply
Dedicated short
circuit prevention
device
Remote/Local
selection switch
No.1 unit
relay box
No.2 unit
relay box
3 Relay box
2
Adapter for
remote start/stop
1
Remote/Local
selection switch
T Timer
(On delay system)
X Relay
Model
PAC-SE55RA-E
(Sold separately)
(Example)
Single polarity
single-throw switch
(125V rating)
To
next
unit
T
Brown
Red
X
2X2
T
One method of easily
distinguishing the on/off
status of SW1 and SW2
is to use together with a
"illuminated switch R" or
pilot lamp.
T
X
2
SW1
SW2
T
X
2
OrangeOrange
Brown
Red
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
Remote
control
OFFON
Description of
functions
OFFON
SW1
SW2
OFFON
Remote/Local
selection switch
(2) Basic wiring diagram
Indoor unit
circuit board
CN32
Orange
Red
Brown
On site wiringOn site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used.
Protect exposed wire by
wrapping with insulating tape
On site wiring
SW1
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW1
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
For remote operation
For timer operation
(3) Part specifications
Note: When using group address, connect to refrigerant
address "0" on the inside.
2. Examples of system applications
In any of the following examples, there is a five to six second delay from the time the operating command is issued until the
operation begins.
1 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited.
2 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be separated.
3 This is when starting and stopping is performed by remote operation and then allowing starting or stopping by remote con-
trol at any time.
4 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
Use momentary switch for SW2. (Manual operation/automatic recover switch on
time is more than one second.)
Press SW2 (on time is more than one second) and operation starts. After this has
been done, stopping or restarting can be down by remote controller.
43
If SW2 is on, operation by remote controller cannot be
performed.
If SW2 is off, operation by remote controller is permitted.
Page 44
9-8. OBTAINING REMOTE DISPLAY
CN90CN1
CN41
Wireless
3
TB3
External input
TB2
Error
TB1
Operation
2
Indoor control circuit boardRemote operation adapter
5
External input
Error output
(No voltage momentary "a" contact)
Operating output
(No voltage momentary "a" contact)
No voltage
(Momentary "a" contact)
HA
Power supply for controller
Timer control
panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
Use the remote operation adapter (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off input
function.
(1) Wiring method
..
Caution
TB3 is a dedicated terminal for contact point input. Never input voltage. It will damage
the indoor control circuit board.
<Connections on the indoor unit side>
1 When using external output function
Insert the 9-prong connector (3-core) of the attached cable to CN90 on the indoor control circuit board.
2 When using the external input function
Insert the 4-prong connector (2-core) of the attached cable to CN41 on the indoor control circuit board.
W The connector is direction-sensitive. Use care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2) Locally procured parts
ItemNameModel and specifications
External output functionExternal output signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent.
Wire size:Stranded wire 0.5mm
2
to 1.25mm
Single straged: {0.65mm to 1.25mm
Display lamp, etc.No voltage “a” contact AC200V (DC30V), 1Aor less
External input functionExternal input signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent.
Wire size:Stranded wire 0.5mm2to 1.25mm
Single straged: {0.65mm to 1.2mm
SwitchNo voltage “a” contact
(Start and stop operation is switched by inputting a
pulse of 200ms or more)
2
2
9-9. TIMER OPERATION
● Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in
10-minute increments within a 24-hour period.
● When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can
be stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
1.Operating with on-site timer
(1) Summary of system
If the “Remote ON/OFF adapter” (PACSE55RA-E) (sold separately) is used, the
on-site timer can be operated to turn each
unit on and off.
44
Page 45
(2) Basic pattern for timer control
Orange
As selected by remote controller operation switch.
From indoor unit
Red
Brown
T
SW ON
SW OFF
Timer control
Remote controller control
SW
Orange
From indoor unit
Red
Brown
T
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage
(PAC-SB81VS)
External control
input terminal
block
1
2
3
Connector
(CN2L)
Basic wiring
X: Relay
(DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box
(On-site tinstallation)
Relay box
(On-site tinstallation)
Remote controller
Humidifier unit
Humidifier
unit
Use a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply).
a) Timer-independent controlb) Combined control by timer and remote controller
(3) Basic system
Refer to 9-7.
9-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT
■ Lossnay operation
● Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - sold
separately) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from the
remote controller.
1 Summary of wiring
● Connect the Lossnay linkage cable (Model PACSB81VS) connector to CN2L on the indoor unit on the
circuit board of the indoor unit.
● Connect the lead wire of the Lossnay linkage cable to
the Lossnay external control input terminal blocks (1)
and (2).
(At this time, the input terminal blocks (1) and (2)
have no polarity.)
2 Precautions when wiring
● The Lossnay linkage cable can be extended up to a maximum of 500 meters.
When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation.
(Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm
● Lossnay linked cable
● Arrange wiring so that there can be no contact between the Lossnay linkage cable and the power supply cord. Contact
may cause malfunctioning. (Separate by 5cm or more.)
2
)
9-11. OBTAINING HUMIDIFIER SIGNAL
9-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR
● The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the
adapter for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifier
unit via the on-site relay box. There is no output when the thermostat is off, during heating preparation and during
defrosting.
W Please consult your nearest Mitsubishi Electric
representative for information about obtaining the
adapter for humidifier signal.
● Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model
PAC-SE41TS-E - sold separately) to the CN20 connector on the circuit board for the indoor unit.
● The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is
required.
Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
45
Page 46
9-13. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display
adapter
The maximum distance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
You can control several units with a multiple remote control display, by
wiring an optional multiple display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Figure 1
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Disconnect the connector from the adapter case.
(3) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical box cover, and remove
the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
Figure 2
Photo 1
Indoor controller
board
Electrical
box cover
Catches
4. Removing the electrical box
(1) Remove the right side panel.
(2) Remove the screw of the electrical box cover, and remove
the cover.
(3) Remove the room temperature thermistor and the pipe
temperature thermistor.
(4) Disconnect the vane motor connector on the indoor
controller board.
(5) Remove the 2 screws of the electrical box.
(6) Disconnect the connector of the heater lead wire connec-
tor.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical box.
47
Photo 2
Room temperature thermistor
Pipe temperature thermistor
Screws
Electrical box
Page 48
OPERATING PROCEDUREPHOTOS & ILLUSTRATION
Catch on the left side panel
Catch on
the unit
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the indoor power board and the fan capacitor can be
serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Indoor
power board
Electrical parts box
Screws
6. Removing the intake grille
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See
Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely.
(3) Remove the air filters.
(4) Hold and press the centre cover.
(5) Remove the screws of the grille.
(6) Pull the lower side of the grille toward you and slide the
upper to the right to remove the grille.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grille.
(3) Remove the electrical box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove drain pan.
Vane motor
Figure 3
Photo 5
Left side panel
Photo 6
Indoor controller board
Slide to the
right
Screws for grille
Drain pan
Screws
Grille
Drain hose
band
Drain hose
48
Page 49
OPERATING PROCEDUREPHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grille.
(3) Remove the electrical box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the screw of the centre support, and remove the
support. (See Photo 10. )
(9) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(10) Pull the left-hand side of the heat exchanger toward you,
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
BOX ASSEMBLY
DRAIN SOCKET
PK-•FAKL
Price
2.5, 3
STRUCTURAL PARTS
PK-2.5FAKL
PK-3FAKL
1112
1
13
8
910
2
3
5
7
4
6
Part numbers that is circled is not shown in the figure.
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
BOX ASSEMBLY
INTAKE GRILLE
DRAIN SOCKET
4
PK-•FAKL
Price
STRUCTURAL PARTS
PK-4FAKL
1112
14
13
8
910
1
2
3
7
5
4
6
Part numbers that is circled is not shown in the figure.
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN
GUIDE V ANE
ARM
CENTER COVER
JOINT SHAFT
AUT O V ANE
DRAIN HOSE
GUIDE V ANE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
TERMINAL COVER
CAPACITOR
INDOOR CONTROLLER BOARD
FUSE
CONTROLLER COVER
CONTROLLER CASE
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERA TURE THERMISTOR
PIPE TEMPERA TURE THERMISTOR
MOTOR BAND
FAN MOTOR
RUBBER MOUNT
MOTOR BAND
RIGHT LINEFLOW FAN
CENTER SUPPORT
BEARING BAND
BEARING MOUNT
SLEEVE BEARING
MOTOR LEG
FUN GUARD
SLEEVE BEARING
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
250V 6.3A
2P(1, 2)
3P(1, 2, 3)
3P(L,N,;)
PN4S40-K
(BG02A648G03)
(BG25J080H02)
(BG02H065H01)
(BG02H178H01)
(BG00R259G07)
(BG02L462H02)
(BG02A534H16)
FUSE
P.B
TB5
TB4
TB2
TH1
TH2
MF
Part No.Part Name
Specification
2.53
PK-•FAKL
Unit
Remarks
(
Drawing No.
)
Wiring
Diagram
Symbol
Recommended
Q,ty
Amount
Price
Q,ty/set
No.
From the previous page.
53
Page 54
Part No.
Specification
No.
Wiring
Diagram
Symbol
Recommended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PK-•FAKL
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
R01 Z61 102
R01 17G 114
R01 46G 480
T7W E14 529
—
—
R01 12G 621
R01 12G 063
R01 16G 002
R01 KV5 527
—
R01 E05 223
R01 E03 317
—
R01 576 255
T7W E47 310
Part Name
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
DRAIN PAN
GUIDE V ANE
ARM
CENTER COVER
JOINT SHAFT
AUT O V ANE
DRAIN HOSE
GUIDE V ANE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
TERMINAL COVER
CAPACITOR
INDOOR CONTROLLER BOARD
1
1
1
1
22
4
1
1
2
1
4
1
1
1
1
1
(BG25J821H01)
(BG25H301H02)
(BG25J821H02)
(BG02J608H07)
MV
W.B
C
I.B
3.0= 440V
ELECTRICAL PARTS
PK-4FAKL
1
37
36
2
32
33
34
35
3
4
31
5
30
29
27
6
28
7
8
25
22
21
20
26
19
23
18
9
24
11
10
13
14
1516 1712
54
Continued to the next page.
Page 55
From the previous page.
Part No.Part Name
No.
17
R01 E02 239
18
19
20
T7W E24 313
21
T7W 512 716
22
T7W E27 716
23
T7W A14 716
24
T7W E12 202
25
R01 E02 202
26
27
T7W 571 762
28
R01 16G 105
29
30
R01 17G 115
31
32
33
R01 KV5 102
34
R01 12G 103
35
36
T7W B03 675
37
R01 005 103
—
—
—
—
—
—
—
FUSE
CONTROLLER COVER
CONTROLLER CASE
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERA TURE THERMISTOR
PIPE TEMPERA TURE THERMISTOR
MOTOR BAND
FAN MOTOR
RUBBER MOUNT
MOTOR BAND
RIGHT LINEFLOW FAN
CENTER SUPPORT
BEARING BAND
BEARING MOUNT
SLEEVE BEARING
MOTOR LEG
FUN GUARD
SLEEVE BEARING
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
Note 2. The following main parts are contained in the optional refrigerant piping kit.