This manual does not cover the
following outdoor units. When
serving them, please refer to the
service manual No.OC152 or
OC127 and this manual in a set.
<Service Ref.>
PU-1.6VLJA1.TH
PU-2VJA1.TH
PU-2NJA.TH
PU-2.5VJA1.TH
PU-2.5NJA.TH
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttons
2
● Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
● If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not
present at the parent unit.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
3
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, blowing, heating and auto
mode.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating mode is not available.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
● Wireless remote controller
4
2
SPECIFICATIONS
2-1. STANDARD SPECIFICATIONS
Service Ref.
Item
50Hz
Cooling capacity w1
60Hz
Cooling capacity w2
Total input (50Hz) w3
Service Ref.
External finish
Fan motor output
Airflow Lo-Hi
External static pressure
Operation control & Thermostat
Indoor unitIndoor grillOutdoor unit
Noise level Low-High
Cond. drain connection OD
Dimensions
Weight
External finish
Dimensions
Weight
Service Ref.
External finish
Refrigerant (R-22) control
Crankcase Heater w4
Compressor output
Protection devices
Fan motor output
phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V
A
V
A
°C
°C
°C
m
°C
°C
°C
°C
°C
PL-1.6KAK(L)
cooling
3,800
1.54
PL-1.6KAK(L)
1, 50
220
0.59
PU-1.6VLJA1.TH
1, 50
220
7.7
(19.8)
(5.3)
62.3
37.4
8.3
5
27
19
15.9
35
24
cooling
5,600
2.57
1, 50
220
0.60
PU-2VJA
1.TH
1, 50
220
11.3
(19.9)
(4.6)
75.9
48.9
13.1
5
27
19
14.4
35
24
PL-2KAK(L)Service Ref.
Electrical circuitTotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PL-2.5KAK(L)
PL-2KAK(L)PL-2.5KAK(L)
cooling
5,600
2.59
1, 60
220
0.65
PU-2NJA.TH
1, 60
220
11.9
(19.9)
(4.9)
63.6
46.0
5.8
5
27
19
14.4
35
24
cooling
6,500
2.59
1, 50
220
0.60
PU-2.5VJA
1.TH
1, 50
220
12.5
(19.6)
(4.9)
74.3
46.4
10.3
5
27
19
13.1
35
24
cooling
7,000
3.05
1, 60
220
0.66
PU-2.5NJA.TH
1, 60
220
13.5
(20.7)
(4.8)
83.4
47.6
7.2
5
27
19
13.0
35
24
Mpa
(kgf/F)
Mpa
1.94
0.52
1.95
0.45
1.95
0.48
1.92
0.48
2.03
0.47
(kgf/F)
D.B.
W.B.
D.B.
D.B.
W.B.
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(Mpa)=10.2(oof/ff)
3-3. ADDITIONAL REFRIGERANT CHARGE (R-22
Service Ref.
PL-1.6KAK(L)
PL-2KAK(L)
PL-2.5KAK(L)
Outdoor unit precharged (kg)
...
V
1.3
...
V
1.78, N
...
V
2.4, N
3-4. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
Air speed
Coverage range
Standard
Air flow
Air speed
Coverage range
High ceiling
Total width of discharge outlets
w The air coverage range is the value up to the position where the air speed is 0.25 m/sec. when air is blown out horizontally
from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture
inside the room.
(up to 20m)
...
1.9
...
2.4
CMM
m/sec.
m
CMM
m/sec.
m
mm
PL-1.6KAK(L)
20m(66ft)
0
0
0
15.0
5.2
5.7
16.0
5.6
6.0
0
10
......
Kg(lbs))
Refrigerant piping length (one way)
25m(82ft)
30m(98ft)
–
0.06(0.13)
0.06(0.13)
0.12(0.26)
0.12(0.26)
PL-2KAK(L)
16.0
5.6
6.0
17.0
5.9
6.4
0
–
35m(115ft)
–
–
–
PL-2.5KAK(L)
17.0
5.9
6.4
18.0
6.3
6.8
0
40m(131ft)
–
–
–
OUTLINES AND DIMENSIONS4
Terminal block for control
Terminal block for
wired remote
controller
Power terminal block
Drain water release hole
Ceiling hole
Ceiling hole
Suspension bolt pitch
640
690~710
25~3525~35
117
186
660
117
13
64
77507
25~35
145
154
25~35
Suspension bolt pitch
690~710
117117
660
68
2
1
7565
65~80
115
253
29830
54
+3
-2
42
Drain pipe
Connected to VP-25
Inspection hole
(Drain up machine)
Keep approximately
10 to 15mm space
between unit ceiling and ceilimg slab.
Ceiling side
Suspension bolt M10
or W3/8
Suspension bolt lower edge
Control wire opening
135
435
54
+3
-2
Power switch wire opening
Refrigerant piping side
Wiring arrangement opening side
Connect the attached
flexible pipe or socket.
466
Air intake
460
66 35
6635
760
Air outlet
460
760
Air outlet
466
Air intake
Grille
Vane motor
4-Auto vane
Intake grille
opening closing side.
Intake grille
(Air intake)
Optional multifunctional casement
Optional high performance filter
1 (Liquid)2 (Gas)
1.6/2/2.5
Refrigerant pipe {9.52
Flaredconnection 3/8F
Refrigerant pipe {15.88
Flaredconnection 5/8F
Note 1:
Note 2:
Note 3:
For the installation of the optional humidifier(suspended type), it
requires minimum 360mm space between transom and ceiling.
Electrical box may be removed for the service purpose. Make
sure to slack the electrical wire little bit for control/power wires
connection.
For the installation of the optional high efficiency filter or optional
multiple casement, it requires minimum 440mm space between
transom and ceiling for the installation (Optional high
performance filter can be also installed).
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work properly,
if you set the switch (SWE,SW6) on the indoor control board, the indoor unit will begin Emergency Operation.
wNote on the wireless remote control: when the remote control does not function, it is possible to activate
Emergency Operation by using the indoor unit emergency operation switch(SW1,SW2 of the wireless signal receiver board)
.
However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and 3 below as in the ca
se of the wired remote control.
2.When you activate emergency operation of the cooling, you have to set the switch(SWE) and switch (SW6) on the indoor controll
er.
SWE : ON
•
Indoor fan is running at high speed.
•
Drain-up machine is working.
SW6-1 : ON
•
Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
•
the outdoor unit malfunctions.
•
the indoor fan malfunctions.
•
when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activ
ated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc.to their original positions.
[Self-diagnosis
]
1.For details on how to operate self-diagnosis with the wireless remote control,refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control,
the unit begins self-diagnosis. and Check Codes generated in the past appear on the display.
For Check Codes and symptoms refer to the table below.
Check Code
P1
P2
P4
P5
Abnormality of room temperature thermistor (TH1).
Abnormality of pipe temperature thermistor/Liquid (TH2).
Abnormality of drain sensor (DS).
Malfunction of drain-up machine.
Symptom
P6
Freezing / overheating protection is working.
P8
E0-E5
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
Abnormality of the signal transmission between remote controller and indoor unit.
Fb
---FFFF
Abnormality of indoor controller board.
No trouble generated in the past.
No corresponding unit.
MODELS
Table 1
SW
1
Manufacture/Service
PL-KAK
PL-KAKL
O
N
O
F
F
1 2 3 4 5
12345678
O
N
O
F
F
M
O
D
E
LS
S
W
5
Manufacture/Service
PL-KAK
PL-KAKL
1 2 3 4 5
O
N
O
FF
MODELS
Table 2
Table 3
SW2
Manufacture/Service
PL-1.6KAK
PL-1.6KAKL
PL-2KAK
PL-2KAKL
1 2 3 4 5
O
N
O
FF
PL-2.5KAK
PL-2.5KAKL
1 2 3 4 5
O
N
O
FF
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual.
SW
6
1 2
ON
O
FF
1
2
3
3
2
1
M
F
C
RED
WHT
BLK
1
3
DS
TH1
1
2
TH2
TB5
1
2
1
2
TB6
R
.B
TRAN
SM
ISSION W
IRES DC12V
5
3
1
1
3
1
3
1
2
3
1
2
1
3
1
3
1
2
1
3
FAN
(WHT)
BCR
VANE
CNV
(GRN)
D.U.M
CNP
(BLU)
D.HEATER
CNC
(RED)
CN90
(WHT)
CN41 CN2L
CN32
CN25
CN51
ZNR
FUSE
X1
LED2
LED1
X3
X4
1
2
1
2
1
2
1
2
2
1
3
D.SENSOR
CN31
(WHT)
LIQUID
CN21
(WHT)
INTAKE
CN20
(RED)
W
IR
E
LE
S
S
X4
X1
X3
ON
OFF
SWE
SW2
SW1
SW5
I.B
DP
H2
2
7
5
10
M
V
G
R
IL
LE
LS
1
6
CN30
(BLK)
O
U
TD
O
O
R
CN2D
(WHT)
POWER
CNDK
(RED)
POWER
CND
(ORN)
POWER
Refer to tables 1, 2 and 3.
RED
WHT
YLW
ORN
R
E
D
B
L
U
B
LK
B
L
U
B
L
K
B
L
K
BLK
BLK
RED
RED
B
LU
B
R
N
B
R
N
VANE
CN23
(GRN
)
YLW
YLW
REMOCON
CN22
(BLU)
1
2
3
L
N
TB4
TB2
R
ED
BLU
G
R
N
/Y
LW
To
outdoor
unit
P
O
W
E
R
S
U
P
P
LY
~(1P
H
A
S
E
)
2
20
-240V
50H
z
220V
60H
z
BZ
CNB
LED1
SW1
SW2
RU
RECEIVER
<F
or P
L-K
A
K
L m
odels>
CN2S
(WHT)
CNSK
(RED)
P.B
DC13.1V
3
2
1
1
2
WHT
NOTES:
1. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers(1, 2, 3).
3. Since the outdoor side electric wiring may change be sure to check the outdoor
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit
OC: Outdoor unit
E Check code
F Unit No.
G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen.
2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
7-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are
summarized in the table below. Check the contents below before investigating details.
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
■ Wired remote controller
16
<Malfunction-diagnosis method at maintenance service>
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Address
display
HOUR
button
ON/OFF
button
[Output pattern A] Errors detected by indoor unit
*1If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp flash
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
Beeper sounds/OPERATION
INDICATOR lamp flashes1 Check code
SymptomRemark
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
2
P2Pipe (TH2) sensor error
4P4Drain sensor error
5
P5
PA
Drain pump error
Forced compressor stop
6P6Freezing/ Overheating safeguard operation
8P8Pipe temperature error / Outdoor unit error
9E4, E5Remote controller signal receiving error
10
–
11
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
–E1, E2Remote controller control board error
Remote controller transmission error
■ Wireless remote controller
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• Select the address of the indoor unit
for the self-diagnosis.
Main indoor unit : “00”
Sub indoor unit : “01”
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
17
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes following power-on
After about 2
minutes has
expired following power-on
• For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block
•Incorrect wiring between indoor and outdoor
units
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
•
If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
18
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method
Abnormality of room temperature
thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: 90: or more
Open: -40: or less
Abnormality of pipe temperature
thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after three
minutes. (The unit returns to normal
operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature
of 90: or more or -40: or
less.
5 Defective indoor controller board.
Countermeasure
1–3 Check resistance value of thermistor.
0: ······15.0k"
10: ····9.6k"
20: ····6.3k"
30: ····4.3k"
40: ····3.0k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 7-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 7-7. Turn
the power on and check restart after inserting
connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is exclusively low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive
difference with actual pipe <liquid> temperature,
replace indoor controller board.
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pump operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
0: ······6.0k"
10: ····3.9k"
20: ····2.6k"
30: ····1.8k"
40: ····1.3k"
2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 7-7. Turn
the power on again and check restart after
inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 7-7.
Turn the power off, and on again to operate
after check.
19
Error Code
P6
Meaning of error code and detection method
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
-15: for three minutes, three minutes
after the compressor started. Abnormal
if it stays under -15: for three minutes
again within 16 minutes after six-minute
resume prevention mode.
<Frost prevention mode>
If pipe <liquid or condenser-evaporator>
temperature is 1: or below when 16
minutes has passed after compressor
starts operating, unit will start operating
in frost prevention mode which stops
compressor operation. After that, when
pipe <liquid or condenser/evaporator>
temperature stays 10: or more for 3
minutes, frost prevention mode will be
released and compressor will restart its
operation.
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
Cause
operation beyond the tolerance
range
defective.
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 7-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
P8
Abnormality of pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes later of compressor start and 6 minutes later of the liquid pipe is out of cooling
range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -5 deg ] (TH2-TH1)
TH2: Liquid pipe temperature
TH1: Intake temperature
Abnormality in outdoor unit
1 Slight temperature difference
between indoor room
temperature and pipe temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase
3 Protection device is working
4 Damaged outdoor coil thermis-
tor
1~4 Check pipe temperature with room
temperature display on remote
controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
1 Check the indoor/outdoor connecting wire.
2 Change the connection of electric wiring.
3 Check the protection device.
4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal,
replace the outdoor controller board.
20
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.