Mitsubishi OC384 Service Manual

Page 1
SPLIT-TYPE, AIR CONDITIONERS
ON/OFF
TEMP.
ON/OFF TEMP
TECHNICAL & SERVICE MANUAL
April 2006
No. OC384
Series PL
Indoor unit [Model names]
PL-1.6KAK
PL-2KAK PL-2KAK PL-2.5KAK PL-2.5KAK PL-1.6KAKL PL-1.6KAKL PL-2KAKL PL-2KAKL PL-2.5KAKL PL-2.5KAKL
INDOOR UNIT
Ceiling Cassettes
[Service Ref.]
PL-1.6KAK
This manual does not cover the following outdoor units. When serving them, please refer to the service manual No.OC152 or OC127 and this manual in a set. <Service Ref.> PU-1.6VLJA1.TH PU-2VJA1.TH PU-2NJA.TH PU-2.5VJA1.TH PU-2.5NJA.TH
CONTENTS
1. PART NAMES AND FUNCTIONS········2
2. SPECIFICATIONS·································5
3. DATA·····················································8
4. OUTLINES AND DIMENSIONS··········11
5. WIRING DIAGRAM ·····························14
REFRIGERANT SYSTEM DIAGRAM
7. TROUBLESHOOTING························16
8. FUNCTION SETTING ·························31
9. 4-WAY AIR FLOW SYSTEM···············38
10. SYSTEM CONTROL···························39
11. DISASSEMBLY PROCEDURE···········53
12. PARTS LIST········································56
13. OPTIONAL PARTS·····························60
······15
WIRELESS
REMOTE CONTROLLER
PL-1.6/2/2.5KAKL
REMOTE CONTROLLER
WIRED
PL-1.6/2/2.5KAK
Page 2
1
Disperses airflow up and down and adjusts the angle of airflow direction.
Grille
Filters Removes dust and pollutants from intake air
Sets airflow to horizontal automatically during cooling or dehumidifying.
Air Intake Intakes air from room.
Horizontal Air Outlet
Auto Air Swing Vane
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
PART NAMES AND FUNCTIONS
Indoor Unit
PL-1.6KAK PL-1.6KAKL PL-2KAK PL-2KAKL PL-2.5KAK PL-2.5KAKL
Wired remote controller
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
2
Page 3
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indica­tion (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
3
Page 4
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between cooling, drying, blowing, heating and auto mode.
CHECK-TEST RUN button
Only press this button to perform an inspec­tion check or test operation. Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when setting timer.
button
SET TEMPERATURE button sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating mode is not available.
Buttons used to set the “hour and minute” of the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temper­ature set.
display
FAN SPEED display indicates which fan speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor unit is mode using switches.
display
CHECK&TEST RUN display indicates that the unit is being checked or test-run.
display
OPERATION MODE display Operation mode display indicates which op­eration mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be au­tomatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatical­ly started at the preset time.
MODEL SELECT
CHECK
TEST RUN
Wireless remote controller
4
Page 5
2
SPECIFICATIONS
2-1. STANDARD SPECIFICATIONS
Service Ref.
Item
50Hz
Cooling capacity w1
60Hz
Cooling capacity w2 Total input (50Hz) w3
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Indoor unitIndoor grillOutdoor unit
Noise level Low-High Cond. drain connection OD
Dimensions
Weight External finish
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w4 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
Notes : w1 Rating conditions (JIS B8616) w2 Rating conditions (SSA 385, 386)
Indoor :D.B. 27°C (80°F), W.B. 19°C (66°F) Indoor : D.B. 29°C (84°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F) Refrigerant piping length (one way) : 5m (16ft) Refrigerant piping length (one way) : 5m (16ft)
w3 Total input based on indicated voltage w4 Capacity of crankcase heater (W) based on 220 volts.
Service Ref.
50Hz 1ph 220V/1ph 220V
Rating conditions (JIS B 8616)
PL-1.6KAK / PL-2KAK / PL-2.5KAK
60Hz
50Hz
60Hz
50Hz 60Hz
W
D H
W
D H
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
(Indoor / Outdoor)
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
CMM
CFM
CMM
CFM
mmAq,Pa
dB
dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW CMM(CFM) CMM(CFM)
dB mm(in.) mm(in.) mm(in.) kg(lbs.)
PL-1.6KAK PL-2KAK PL-2.5KAK
3,800
13,000
– – – –
1.54
PL-1.6KAK
0.03
13-15
460-530
– –
31-35
32 (1-1/4)
660 (26) 660 (26) 253 (10)
19 (42)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
PU-1.6VLJA
1.2/-
0.065
45(1588)
49/–
870(34-1/4)
650(25-5/8)
45(99)
Galvanized sheets with gray heat insulation
Remote control & Built-in
Munsell 0.70Y 8.59/0.97
1.TH
Inner thermostat, HP switch, LP switch
5,600
19,100
– – – –
2.57
PL-2KAK
0.03
13-16
460-565
– –
0 (Direct blow)
32-37
32 (1-1/4)
660 (26) 660 (26) 253 (10)
19 (42)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
PU-2VJA
Munsell 3.0Y 7.8/1.1
Capillary tube
870(34-1/4)
295+24(11-5/8+1)
650(25-5/8)
1.TH
32/–
2.0/-
0.065
45(1588)
– –
60(132)
PU-2.5VJA
6,500
22,200
– – – –
2.59
PL-2.5KAK
0.03
14-17
495-600
– –
35-39.5
32 (1-1/4)
660 (26) 660 (26) 253 (10)
20 (44)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
1.TH
32/–
2.0/-
0.085
50(1765)
– –
870(34-1/4)
850(33-7/16)
71(157)
5
Page 6
Service Ref.
Item
50Hz
Cooling capacity w1
60Hz
Cooling capacity w2 Total input (50/60Hz) w3
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Indoor unitIndoor grillOutdoor unit
Noise level Low-High Cond. drain connection OD
Dimensions
Weight External finish
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w4 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
Notes : w1 Rating conditions (JIS B8616) w2 Rating conditions (SSA 385, 386)
Indoor :D.B. 27°C (80°F), W.B. 19°C (66°F) Indoor : D.B. 29°C (84°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F) Refrigerant piping length (one way) : 5m (16ft) Refrigerant piping length (one way) : 5m (16ft)
w3 Total input based on indicated voltage w4 Capacity of crankcase heater (W) based on 220 volts.
Service Ref.
50Hz 1ph 220V/1ph 220V 60Hz 1ph 220V/1ph 220V
Rating conditions (JIS B 8616)
PL-1.6KAKL / PL-2KAKL / PL-2.5KAKL
60Hz
50Hz
60Hz
50Hz 60Hz
W
D H
W
D H
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
(Indoor / Outdoor)
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
CMM
CFM
CMM
CFM
mmAq,Pa
dB
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs.)
mm(in.) mm(in.) mm(in.)
kg(lbs.)
W
kW
kW CMM(CFM) CMM(CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs.)
PL-1.6KAKL PL-2KAKL PL-2.5KAKL
3,800
13,000
– – – –
1.54/-
PL-1.6KAKL
0.03
13-15
460-530
– –
31-35
32 (1-1/4)
660 (26) 660 (26) 253 (10)
19 (42)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
PU-1.6VLJA
1.2/-
0.065
45(1588)
49/–
870(34-1/4)
650(25-5/8)
45(99)
Galvanized sheets with gray heat insulation
Remote control & Built-in
Munsell 0.70Y 8.59/0.97
1.TH
Inner thermostat, HP switch, LP switch
PU-2VJA1.TH, PU-2NJA.TH
5,600
19,100
5,600
19,000
4,500
15,400
2.57/2.59
PL-2KAKL
0.03
13-16
460-565
13-16
460-565
0 (Direct blow)
32-37 32-37
32 (1-1/4)
660 (26) 660 (26) 253 (10)
19 (42)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
Munsell 3.0Y 7.8/1.1
Capillary tube
32/–
2.0/1.5
0.065 45(1588) 45(1588)
49/50
870(34-1/4)
295+24(11-5/8+1)
650(25-5/8)
60(132)
PL-2.5KAKL
PU-2.5VJA1.TH, PU-2.5NJA.TH
850(33-7/16)
6,500
22,200
7,000
23,900
5,950
20,300
2.59/3.05
0.03
14-17
495-600
14-17
495-600
35-39.5 35-39.5
32 (1-1/4)
660 (26) 660 (26) 253 (10)
20 (44)
760 (30) 760 (30)
30 (1-1/8)
3.7 (8)
32/–
2.0/1.7
0.085 50(1765) 50(1765)
52/53
870(34-1/4)
71(157)
6
Page 7
2-2. POWER SUPPLY & MODEL NAMES
A
kW
A
N : 220V 60Hz
PL-2KAKL
0.65
0.14
0.72
PU-2NJA.TH
PL-2.5KAKL
0.66
0.14
0.73
PU-2.5NJA.TH
Power supply (1 Phase)
Indoor unit Service Ref.
Current Input Starting current
Outdoor unit Service Ref.
Power supply
50Hz
1ph.
Service Ref. (Indoor unit) PL-1.6KAK
220V 220, 230, 240V
PU-1.6VLJA
Model name (Outdoor unit)
PL-2KAK
1.TH
PU-2VJA1.TH
PL-2.5KAK
PU-2.5VJA1.TH
Power supply
Service Ref. (Indoor unit) PL-1.6KAKL
50Hz
1ph.
220V 220, 230, 240V
60Hz
1ph.
Notes : 1. Power supply key N
220V
......
1ph, 220V, 60Hz
...
V(L)
1ph, 220, 230, 240V, 50Hz
2. Primary power supplies for all indoor units are single-phase.
2-3. ELECTRICAL SPECIFICATIONS
(1) Rating conditions -JIS B 8616 Series PL Indoor Unit (Single Phase)
Power supply (1 Phase)
Indoor unit Service Ref.
Current Input Starting current
Outdoor unit Service Ref.
A
kW
A
PU-1.6VLJA1.TH
Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
V : 220V 50Hz V : 230V 50Hz
PL-1.6KAK(L)
0.59
0.12
0.65
PL-2KAK(L)
0.60
0.13
0.66
PU-2VJA
1.TH
PU-1.6VLJA
PL-2.5KAK(L)
0.60
0.13
0.66
PU-2.5VJA1.TH
Model name (Outdoor unit)
PL-2KAKL
1.TH
PL-1.6KAK(L)
PU-2VJA
PU-2NJA
1.TH .TH
PL-2KAK(L)
0.62
0.13
0.68
PU-1.6VLJA1.TH
PU-2VJA
0.63
0.14
0.69
PL-2.5KAKL
PU-2.5VJA
PU-2.5NJA
PL-2.5KAK(L)
1.TH
PU-2.5VJA1.TH
1.TH .TH
0.63
0.14
0.69
Power supply (1 Phase)
Indoor unit Service Ref.
Current Input Starting current
Outdoor unit Service Ref.
(2) Rating conditions -SSA 385,386 Series PL Indoor Unit (Single Phase)
A
kW
A
PL-1.6KAK(L)
0.64
0.14
0.70
PU-1.6VLJA1.TH
Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
V : 240V 50Hz N : 220V 60Hz
PL-2KAK(L)
0.65
0.15
0.72
PU-2VJA
1.TH
PL-2.5KAK(L)
0.65
0.15
0.72
PU-2.5VJA1.TH
PL-2KAKL
0.65
0.14
0.72
PU-2NJA.TH
PL-2.5KAKL
PU-2.5NJA.TH
7
0.66
0.14
0.73
Page 8
3
PL-2.5KAK(L)PL-2KAK(L)
17
0.10
0.75
Evaporator airflow (CMM)
Bypass factors
S.H.F. at rating conditions
16
0.19
0.74
15
0.14
0.80
Service Ref.
Temperature
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
PL-1.6KAK(L)
0.81
0.82
0.83
0.83
0.84
0.85 16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
3.8
4.0
4.1
4.2
4.3
4.5
0.83
0.85
0.86
0.86
0.87
0.88
5.4
5.8
6.0
6.1
6.2
6.6
0.84
0.85
0.86
0.87
0.87
0.88
6.4
6.8
7.0
7.2
7.3
7.8
0.83
0.85
0.86
0.86
0.87
0.88
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
3.5
3.7
3.8
3.8
3.9
4.2
0.97
0.99
1.00
1.01
1.02
1.04
5.0
5.4
5.6
5.7
5.8
6.1
0.96
0.99
1.00
1.01
1.01
1.03
5.9
6.3
6.5
6.6
6.7
7.2
0.97
0.99
1.00
1.01
1.02
1.04
1.03
1.05
1.06
1.07
1.08
1.12 16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
3.3
3.6
3.6
3.7
3.8
4.1
1.03
1.05
1.06
1.07
1.08
1.12
4.8
5.1
5.3
5.3
5.4
5.8
1.03
1.06
1.08
1.08
1.09
1.12
5.7
6.1
6.2
6.3
6.4
7.0
1.03
1.05
1.06
1.07
1.08
1.12
1.09
1.12
1.14
1.15
1.16
1.20
3.2
3.3
3.5
3.6
3.6
3.8
1.10
1.13
1.15
1.16
1.17
1.21
4.5
4.9
5.0
5.1
5.2
5.6
1.11
1.13
1.15
1.16
1.17
1.22
5.4
5.7
6.0
6.1
6.2
6.6
1.10
1.13
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
4.3
4.6
4.8
4.8
4.9
5.3
1.18
1.21
1.24
1.25
1.26
1.32
5.0
5.3
5.5
5.6
5.7
6.2
1.18
1.22
1.24
1.25
1.26
1.32
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
3.6
3.8
4.0
4.0
4.1
4.3
0.90
0.92
0.93
0.93
0.94
0.96
5.2
5.6
5.8
5.9
5.9
6.3
0.90
0.92
0.93
0.94
0.94
0.96
6.2
6.6
6.8
6.8
7.0
7.4
0.90
0.92
0.93
0.93
0.94
0.96
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
3.8
4.1
4.2
4.3
4.3
4.6
3.6
3.8
3.9
4.0
4.1
4.3
3.3
3.6
3.6
3.7
3.8
4.1
3.2
3.4
3.5
3.6
3.7
3.9
5.6
5.9
6.1
6.2
6.3
6.7
6.6
7.0
7.2
7.3
7.4
7.8
5.2
5.5
5.7
5.7
5.8
6.2
6.1
6.5
6.7
6.8
7.0
7.4
4.8
5.2
5.3
5.4
5.5
5.9
5.7
6.1
6.2
6.3
6.4
7.0
4.6
4.9
5.1
5.1
5.2
6.2
5.5
5.8
6.0
6.2
6.3
6.6
4.3
4.6
4.8
4.9
5.0
5.4
5.1
5.5
5.7
5.7
5.9
6.2
0.81
0.82
0.83
0.83
0.84
0.85
0.81
0.82
0.83
0.84
0.84
0.85
0.91
0.93
0.95
0.95
0.96
0.98
0.93
0.95
0.96
0.97
0.97
0.99
0.91
0.93
0.95
0.95
0.96
0.98
1.03
1.05
1.06
1.07
1.08
1.12
1.03
1.06
1.07
1.08
1.08
1.12
1.09
1.12
1.14
1.15
1.16
1.20
1.09
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
Indoor W.B.Outdoor D.B.
T.C. C.F.
(T.I.)
C.F. (T.I.)
T.C.C.F.
(T.I.)
T.C.
DATA
3-1. PERFORMANCE DATA
Cooling capacity 50Hz
Notes : 1. T.C. : Total capacity (kW) ... (kcal/h) = (kW) 860, (Btu/h) = 4 (kW) 860
Cooling capacity correction factors 50Hz
Service Ref.
PL-1.6KAK(L) PL-2KAK(L) PL-2.5KAK(L)
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operation range (cooling) : Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F). Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F). w
5m (16ft)
1.0
1.0
1.0
10m (33ft)
0.992
0.985
0.983
15m (49ft)
0.987
0.975
0.972
0.982
0.964
0.961
8
wVL ... Outdoor : D.B. 46°C (115°F).
25m (82ft)
0.954
0.951
Refrigerant piping length (one way)
20m (66ft)
30m (98ft)
0.944
0.940
35m (115ft)
– – –
40m (131ft)
– – –
Page 9
Cooling capacity 60Hz
PL-2.5KAKL
17
0.09
0.79
Evaporator airflow (CMM)
Bypass factors
S.H.F. at rating conditions
16
0.19
0.74
Service Ref.
Temperature
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
PL-2KAKL
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
5.4
5.8
6.0
6.1
6.2
6.6
0.84
0.85
0.86
0.87
0.87
0.88
6.9
7.4
7.6
7.7
7.8
8.3
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
5.0
5.4
5.6
5.7
5.8
6.1
0.96
0.99
1.00
1.01
1.01
1.03
6.4
6.8
7.0
7.1
7.2
7.7
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
4.8
5.1
5.3
5.3
5.4
5.8
1.03
1.06
1.08
1.08
1.09
1.12
6.1
6.6
6.7
6.8
6.9
7.5
4.5
4.9
5.0
5.1
5.2
5.6
1.11
1.13
1.15
1.16
1.17
1.22
5.8
6.2
6.4
6.6
6.7
7.1
4.3
4.6
4.8
4.8
4.9
5.3
1.18
1.21
1.24
1.25
1.26
1.32
5.4
5.7
6.0
6.0
6.2
6.7
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
5.2
5.6
5.8
5.9
5.9
6.3
0.90
0.92
0.93
0.94
0.94
0.96
6.7
7.1
7.3
7.4
7.5
8.0
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
16°C (60.8°F) 18°C (64.4°F) 19°C (66.2°F)
19.4°C (67°F) 20°C (68°F) 22°C (71.6°F)
5.6
5.9
6.1
6.2
6.3
6.7
5.2
5.5
5.7
5.7
5.8
6.2
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.1
5.2
6.2
4.3
4.6
4.8
4.9
5.0
5.4
0.81
0.82
0.83
0.84
0.84
0.85
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.12
1.09
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
0.83
0.85
0.86
0.86
0.87
0.88
0.97
0.99
1.00
1.01
1.02
1.04
1.03
1.05
1.06
1.07
1.08
1.12
1.10
1.13
1.15
1.16
1.17
1.21
1.18
1.22
1.24
1.25
1.26
1.32
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.85
0.91
0.93
0.95
0.95
0.96
0.98
1.03
1.05
1.06
1.07
1.08
1.12
1.09
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
7.1
7.5
7.7
7.8
8.0
8.4
6.6
7.0
7.2
7.4
7.5
8.0
6.1
6.6
6.7
6.8
6.9
7.5
5.9
6.2
6.5
6.7
6.8
7.1
5.5
5.9
6.1
6.2
6.3
6.7
Indoor W.B.Outdoor D.B.
C.F. (T.I.)
T.C.C.F.
(T.I.)
T.C.
Notes : 1. T.C. : Total capacity (kW)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operation range (cooling) :
Cooling capacity correction factors 60Hz
Service Ref. PL-2KAKL
PL-2.5KAKL
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F). Upper limit ... Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F).
5m (16ft)
1.0
1.0
10m (33ft)
0.985
0.978
...
(kcal/h) = (kW) 860, (Btu/h) = 4 (kW) 860
15m (49ft)
0.975
0.963
Refrigerant piping length (one way)
20m (66ft)
0.964
0.948
9
25m (82ft)
0.954
0.934
30m (98ft)
0.944
0.921
35m (115ft)
– –
40m (131ft)
– –
Page 10
3-2. STANDARD OPERATION DATA
Capacity Input
Indoor unit Service Ref.
phase, Hz Volts Amperes
Outdoor unit Service Ref.
phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
°C °C °C
m
°C °C °C °C °C
PL-1.6KAK(L)
cooling
3,800
1.54
PL-1.6KAK(L)
1, 50
220
0.59
PU-1.6VLJA1.TH
1, 50
220
7.7
(19.8)
(5.3)
62.3
37.4
8.3 5
27 19
15.9 35 24
cooling
5,600
2.57
1, 50
220
0.60
PU-2VJA
1.TH
1, 50
220
11.3
(19.9)
(4.6)
75.9
48.9
13.1 5
27 19
14.4
35 24
PL-2KAK(L)Service Ref.
Electrical circuit TotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PL-2.5KAK(L)
PL-2KAK(L) PL-2.5KAK(L)
cooling
5,600
2.59
1, 60
220
0.65
PU-2NJA.TH
1, 60
220
11.9
(19.9)
(4.9)
63.6
46.0
5.8 5
27 19
14.4 35 24
cooling
6,500
2.59
1, 50
220
0.60
PU-2.5VJA
1.TH
1, 50
220
12.5
(19.6)
(4.9)
74.3
46.4
10.3 5
27 19
13.1
35 24
cooling
7,000
3.05
1, 60
220
0.66
PU-2.5NJA.TH
1, 60
220
13.5
(20.7)
(4.8)
83.4
47.6
7.2 5
27 19
13.0 35 24
Mpa
(kgf/F)
Mpa
1.94
0.52
1.95
0.45
1.95
0.48
1.92
0.48
2.03
0.47
(kgf/F)
D.B.
W.B.
D.B. D.B.
W.B.
The unit of pressure has been changed to Mpa based on the international SI system. The conversion factor is : 1(Mpa)=10.2(oof/ff)
3-3. ADDITIONAL REFRIGERANT CHARGE (R-22
Service Ref.
PL-1.6KAK(L) PL-2KAK(L) PL-2.5KAK(L)
Outdoor unit precharged (kg)
...
V
1.3
...
V
1.78, N
...
V
2.4, N
3-4. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow Air speed Coverage range
Standard
Air flow Air speed Coverage range
High ceiling
Total width of discharge outlets
w The air coverage range is the value up to the position where the air speed is 0.25 m/sec. when air is blown out horizontally
from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture inside the room.
(up to 20m)
...
1.9
...
2.4
CMM
m/sec.
m
CMM
m/sec.
m
mm
PL-1.6KAK(L)
20m(66ft)
0 0 0
15.0
5.2
5.7
16.0
5.6
6.0 0
10
......
Kg(lbs))
Refrigerant piping length (one way)
25m(82ft)
30m(98ft)
0.06(0.13)
0.06(0.13)
0.12(0.26)
0.12(0.26)
PL-2KAK(L)
16.0
5.6
6.0
17.0
5.9
6.4 0
35m(115ft)
– – –
PL-2.5KAK(L)
17.0
5.9
6.4
18.0
6.3
6.8 0
40m(131ft)
– – –
Page 11
OUTLINES AND DIMENSIONS4
Terminal block for control
Terminal block for wired remote controller
Power terminal block
Drain water release hole
Ceiling hole
Ceiling hole
Suspension bolt pitch
640
690~710
25~3525~35
117
186
660
117
13
64
77 507
25~35
145
154
25~35
Suspension bolt pitch
690~710
117117
660
68
2
1
75 65
65~80
115
253
29830
54
+3
-2
42
Drain pipe Connected to VP-25
Inspection hole (Drain up machine)
Keep approximately 10 to 15mm space between unit ceiling and ceilimg slab.
Ceiling side
Suspension bolt M10 or W3/8
Suspension bolt lower edge
Control wire opening
135
435
54
+3
-2
Power switch wire opening
Refrigerant piping side Wiring arrangement opening side
Connect the attached flexible pipe or socket.
466
Air intake
460
66 35
6635
760
Air outlet
460
760
Air outlet
466
Air intake
Grille
Vane motor
4-Auto vane
Intake grille opening closing side.
Intake grille
(Air intake)
Optional multifunctional casement
Optional high performance filter
1 (Liquid) 2 (Gas)
1.6/2/2.5
Refrigerant pipe {9.52 Flaredconnection 3/8F
Refrigerant pipe {15.88 Flaredconnection 5/8F
Note 1:
Note 2:
Note 3:
For the installation of the optional humidifier(suspended type), it requires minimum 360mm space between transom and ceiling.
Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.
For the installation of the optional high efficiency filter or optional multiple casement, it requires minimum 440mm space between transom and ceiling for the installation (Optional high performance filter can be also installed).
A
wireless panel
Operation lamp Receiver
Emergency operetion switch(cooling)
A(indication area)
wOnly for PL-1.6/2/2.5KAL
4-1. INDOOR UNIT
PL-1.6KAK / PL-2KAK / PL-2.5KAK PL-1.6KAKL / PL-2KAKL / PL-2.5KAKL
Unit : mm
11
Page 12
WIRED REMOTE CONTROLLER
unit : mm
130
120
19
12
Page 13
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
13
Page 14
WIRING DIAGRAM5
SYMBOL
NAME
P.B
INDOOR POWER BOARD
I.B
INDOOR CONTROLLER BOARD
FUSE
FUSE (T6.3AL250V)
ZNR
VARISTOR
BCR
FAN CONTROL ELEMENT
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
X1
RELAY (DRAIN PUMP)
X4
RELAY (FAN MOTOR)
SW1
SWITCH (MODEL SELECTION)
wSee table 1
SW2
SWITCH (CAPACITY CORD)
wSee table 2
SW5
SWITCH (SYSTEM SELECTION)
wSee table 3
SWE,SW6
CONNECTOR (EMERGENCY OPERATION)
[LEGEND]
SYMBOL
NAME
MF
FAN MOTOR
MV
VANE MOTOR
LS
LIM
IT SWITCH
H2
DEW PREVEMTION HEATER
DP
DRAIN-UP MACHINE
DS
DRAIN SENSOR
TB4
TERM
INAL BLOCK (INDOOR/OUTDO
OR CONNECTING LINE)
R.B
WIRED REMOTE CONTROLLER BOARD
TB2
TERMINAL BLOCK (POWER SUPPLY)
TB5,TB6
TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR (0
:
/15
", 25
:
/5.4k
" DETECT)
TH2
PIPE TEM
P. THERMISTOR/LIQUID
(0
:
/15k
", 25
:
/5.4k
" DETECT)
C
CAPACITOR (FAN MOTOR)
SYM
BO
L
N
AM
E
W
.B
W
IR
ELESS
R
EM
OTE
C
ON
TR
O
LLER
BO
AR
D
R
U
R
ECE
IVING
U
N
IT
BZ
BU
ZZER
LED
1
LE
D
(R
U
N IN
D
IC
ATO
R
)
SW
1
SW
ITC
H
(H
EATING
O
N
/O
FF)
SW
2
SW
ITCH
(C
O
OLIN
G
O
N
/O
FF)
[Emergency operation procedure
]
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work properly, if you set the switch (SWE,SW6) on the indoor control board, the indoor unit will begin Emergency Operation. wNote on the wireless remote control: when the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit emergency operation switch(SW1,SW2 of the wireless signal receiver board)
.
However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and 3 below as in the ca
se of the wired remote control.
2.When you activate emergency operation of the cooling, you have to set the switch(SWE) and switch (SW6) on the indoor controll
er.
SWE : ON
Indoor fan is running at high speed.
Drain-up machine is working.
SW6-1 : ON
Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when:
the outdoor unit malfunctions.
the indoor fan malfunctions.
when it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control etc,dose not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activ
ated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions.
[Self-diagnosis
]
1.For details on how to operate self-diagnosis with the wireless remote control,refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis. and Check Codes generated in the past appear on the display. For Check Codes and symptoms refer to the table below.
Check Code
P1 P2
P4 P5
Abnormality of room temperature thermistor (TH1). Abnormality of pipe temperature thermistor/Liquid (TH2). Abnormality of drain sensor (DS).
Malfunction of drain-up machine.
Symptom
P6
Freezing / overheating protection is working.
P8
E0-E5
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
Abnormality of the signal transmission between remote controller and indoor unit.
Fb
---­FFFF
Abnormality of indoor controller board. No trouble generated in the past. No corresponding unit.
MODELS
Table 1
SW
1
Manufacture/Service
PL-KAK PL-KAKL
O
N
O
F
F
1 2 3 4 5
12345678
O
N
O
F
F
M
O
D
E
LS
S
W
5
Manufacture/Service
PL-KAK PL-KAKL
1 2 3 4 5
O
N
O
FF
MODELS
Table 2
Table 3
SW2
Manufacture/Service
PL-1.6KAK PL-1.6KAKL
PL-2KAK PL-2KAKL
1 2 3 4 5
O
N
O
FF
PL-2.5KAK PL-2.5KAKL
1 2 3 4 5
O
N
O
FF
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SW
6
1 2
ON O
FF
1
2
3
3
2
1
M
F
C
RED
WHT
BLK
1 3
DS
TH1
1
2
TH2
TB5
1
2
1
2
TB6
R
.B
TRAN
SM
ISSION W
IRES DC12V
5 3 1
1
3
1
3
1
2
3
1
2
1
3
1
3
1
2
1
3
FAN
(WHT)
BCR
VANE
CNV
(GRN)
D.U.M
CNP
(BLU)
D.HEATER
CNC
(RED)
CN90
(WHT)
CN41 CN2L
CN32
CN25
CN51
ZNR
FUSE
X1
LED2
LED1
X3
X4
1
2
1
2
1
2
1
2
2
1
3
D.SENSOR
CN31
(WHT)
LIQUID
CN21
(WHT)
INTAKE
CN20
(RED)
W
IR
E
LE
S
S
X4
X1
X3
ON OFF
SWE
SW2
SW1
SW5
I.B
DP
H2
2 7
5
10
M
V
G
R
IL
LE
LS
1 6
CN30 (BLK)
O
U
TD
O
O
R
CN2D
(WHT)
POWER
CNDK
(RED)
POWER
CND
(ORN)
POWER
Refer to tables 1, 2 and 3.
RED
WHT
YLW
ORN
R
E
D
B
L
U
B
LK
B
L
U
B
L
K
B
L
K
BLK
BLK
RED
RED
B
LU
B
R
N
B
R
N
VANE
CN23
(GRN
)
YLW
YLW
REMOCON
CN22 (BLU)
1 2 3
L N
TB4
TB2
R
ED
BLU
G
R
N
/Y
LW
To outdoor unit
P
O
W
E
R
S
U
P
P
LY
~(1P
H
A
S
E
)
2
20
-240V
50H
z
220V
60H
z
BZ
CNB
LED1
SW1
SW2
RU
RECEIVER
<F
or P
L-K
A
K
L m
odels>
CN2S
(WHT)
CNSK
(RED)
P.B
DC13.1V
3 2 1
1
2
WHT
NOTES:
1. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers(1, 2, 3).
3. Since the outdoor side electric wiring may change be sure to check the outdoor
W.B.
PL-1.6KAK / PL-2KAK / PL-2.5KAK / PL-1.6KAKL / PL-2KAKL / PL-2.5KAKL
14
Page 15
6
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
INDOOR UNIT
PL-1.6KAK(L) PL-2KAK(L)
OUTDOOR UNIT
PU-1.6JA PU-2JA
Outdoor heat exchanger
Capillary tube for injection (Only PU-2)
Flexible tube
Flared connection
Flared connection
Ball valve
(with service port) Refrigerant pipe {9.52(3/8) (With insulator) option
Refrigerant pipe {15.88(5/8) (With insulator) option
Accumulator
Compressor
Capillary tube
Capillary tube size
: flow of refrigerant
PU-1.6(O.D.3.2 X I.D.1.8– L900) PU-2 (O.D.3.2 X I.D.2.0– L430)
Strainer
Check plug
High pressure switch
Low pressure switch
Charge plug
Ball valve
INDOOR UNIT
PL-2.5KAK(L)
OUTDOOR UNIT
PU-2.5JA
Outdoor heat exchanger
Capillary tube PU-2.5 (O.D.3.2 X I.D.1.6 – L760) x2pcs
Flexible tube
Flared connection
Flared connection
Ball valve
(with service port) Refrigerant pipe {9.52(3/8) (With insulator) option
Refrigerant pipe {15.88(5/8) (With insulator) option
Accumulator
Compressor
: flow of refrigerant
Muffler
Strainer
High pressure switch
Low pressure switch
Charge plug
Check plug
Ball valve
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
REFRIGERANT SYSTEM DIAGRAM
PL-1.6KAK(L) / PU-1.6VLJA1.TH PL-2KAK(L) / PU-2VJA1.TH, PU-2NJA.TH
Unit : mm
PL-2.5KAK(L) / PU-2.5VJA
1.TH, PU-2.5NJA.TH
Unit : mm
15
Page 16
7 TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (7-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (7-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code
F Unit No. G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen. 2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past. F F F F : No corresponding unit.
7-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
16
Page 17
<Malfunction-diagnosis method at maintenance service>
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Address display
HOUR button
ON/OFF button
[Output pattern A] Errors detected by indoor unit
*1If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION INDICATOR lamp flash pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
• Refer to the following tables for details on the check codes. [Output pattern A]
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit. 3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
Beeper sounds/OPERATION
INDICATOR lamp flashes 1 Check code
Symptom Remark
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
2
P2 Pipe (TH2) sensor error
4 P4 Drain sensor error 5
P5 PA
Drain pump error
Forced compressor stop 6 P6 Freezing/ Overheating safeguard operation 8 P8 Pipe temperature error / Outdoor unit error 9 E4, E5 Remote controller signal receiving error
10
11
– –
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
E1, E2 Remote controller control board error
Remote controller transmission error
Wireless remote controller
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and address "00" flash­es.
• Check that the remote controller's display has stopped before continuing.
2. Press the temperature buttons.
3. Point the remote controller at the
sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and press the ON/OFF button.
• Select the address of the indoor unit for the self-diagnosis.
Main indoor unit : “00” Sub indoor unit : “01”
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­tent buzzer sound, the operation light flashes, and the error code is output. (It takes 3 seconds at most for error code to appear.)
• The check mode is cancelled.
17
Page 18
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
For about 2 minutes follow­ing power-on
After about 2 minutes has expired follow­ing power-on
• For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection device is not connected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block
•Incorrect wiring between indoor and outdoor units
•Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
18
Page 19
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90: or more Open: -40: or less
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90: or more Open: -40: or less
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90: or more or -40: or less.
5 Defective indoor controller board.
Countermeasure
13 Check resistance value of thermistor. 0: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 7-7. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 7-7. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg (Except defrosting)
• When pipe <liquid> temperature or room temperature is short/open temperature.
• During drain pump operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from lead wire.
• Clogged filter is causing wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. 0: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 7-7. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited, and abnormality reappears.
Turn the power off, and on again to operate after check.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 7-7.
Turn the power off, and on again to operate after check.
19
Page 20
Error Code
P6
Meaning of error code and detection method Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evap­orator> temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode. <Frost prevention mode> If pipe <liquid or condenser-evaporator> temperature is 1: or below when 16 minutes has passed after compressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe <liquid or condenser/evaporator> temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
Cause
operation beyond the tolerance range
defective.
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 7-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
P8
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -5 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
Abnormality in outdoor unit
1 Slight temperature difference
between indoor room temperature and pipe tempera­ture thermistor
• Shortage of refrigerant
• Disconnected holder of pipe thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase 3 Protection device is working 4 Damaged outdoor coil thermis-
tor
1~4 Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Check the indoor/outdoor connecting wire. 2 Change the connection of electric wiring. 3 Check the protection device. 4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal, replace the outdoor controller board.
20
Page 21
Error Code
E0
or
E4
E3
or
E5
Meaning of error code and detection method
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive any signal for two minutes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit. (Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Contact failure at transmission 2 All remote controllers are set
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
5 Defective transmitting receiving
6 Noise has entered into the
1 Two remote controller are set
2 Remote controller is connected 3 Repetition of refrigerant 4 Defective transmitting receiving 5 Defective transmitting receiving
6 Noise has entered into trans-
Cause
wire of remote controller as “sub” remote controller. In
this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
circuit of remote controller circuit of indoor controller board
of refrigerant address “0”. transmission wire of remote
controller.
as “main.”
(In case of 2 remote con-
trollers) with two indoor units or more. address. circuit of remote controller. circuit of indoor controller
board. mission wire of remote con-
troller.
Countermeasure
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max.500m (Do not use cable x 3 or more)
• The number of connecting indoor units: max.16units
• The number of connecting remote con­troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller. c) When “RC E3” is displayed, d) When “ERC 00-06” is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem. Put the power off,and on again to check. When becoming abnormal again, replace
indoor controller board.
b)When “RC NG”is displayed, replace
remote controller.
c)When “RC E3”or “ERC 00-66”is displayed,
noise may be causing abnormality.
21
Page 22
Error Code
Fb
E1
or
E2
PA (2502) (2500)
Meaning of error code and detection method Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
Abnormality of remote controller con­trol board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be
soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection
is performed. a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be less than -10: for a total of 30 minutes. (When the drain sensor is detected to
be NOT soaked in the water, the detection record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
1 Defective indoor controller
1 Defective remote controller. 1 Replace remote controller.
1 Drain pump trouble 2 Drain defective
3 Open circuit of drain sensor
4 Contact failure of drain sensor
5 Dew condensation on drain
6 Extension piping connection
7 Mis-wiring of indoor/ outdoor
8 Room temperature thermistor /
Cause
board.
· Drain pump clogging
· Drain pipe clogging
side heater
connector
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
difference at twin, triple, quadruple system.
connecting at twin, triple, quadruple system.
liquid pipe temperature thermis­tor detection is defective.
Countermeasure
1 Replace indoor controller board.
Check the drain pump. Performance Please confirm whether water can be drained.
Confirm the resistance of the drain sensor side heater.
Check the connector contact failure.
1 Check the drain sensor leadwire mounted. 2 Check the filter clogging
Check the piping connection.
Check the indoor/ outdoor connecting wires.
Check the room temperature display of remote controller. Check the indoor liquid pipe temperature dis­play of outdoor controller board.
22
Page 23
7-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Cause
Countermeasure
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected. Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
• When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
• When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
• When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor con­troller board is defective.
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires 4 Defective remote controller
1 Reconfirm the setting of main/sub for
indoor unit Set the main unit. Set main/sub using SW5-3 on indoor controller board.
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller board.
• When LED2 is blinking, check the short­cut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoor connecting wires again, and; if LED2 is blinking, outdoor unit’s controller board is defective; if LED2 is lit, connection failure of indoor/outdoor terminal block etc. has returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
23
Page 24
Phenomena
• After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
• Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M".
• Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0M".
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. "TEST RUN" liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling mode.
Make sure that cold wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the operation manual for the indoor unit.
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
Cause
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller. 2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board.
7-5. TEST RUN AND EMERGENCY OPERATION
7-5-1. Before test run
Countermeasure
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How to check the parts”.)
• Check for breaking of wire or connec­tion failure of connector.
• Check “Up/down vane setting”. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector, replace indoor controller board. When the same trouble occurs even if indoor controller board is replaced, replace wireless remote controller board.
7-5-2. Test run (Using wired remote controller)
24
Page 25
Receiver
Operation lamp
Emergency operation switch (cooling)
Mode
Cooling
Set temperature
Fan speed
Airflow direction
24:
High
Horizontal (30deg)
wEmergency operation will be performed as follows.
7-5-3. Test run (Using wireless remote controller)
1 Turn on the power to the unit at least 12 hours before the test run. 2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.) A and current operation mode are displayed.
TEST RUN
TEST RUN
3 Press the button to activate mode, then check whether cool air is blown out from the unit.
MODE
COOL
4 Press the button and check whether fan speed changes.
FAN
5 Press the button and check whether the auto vane operates properly.
VANE
6 Press the ON/OFF button to stop the test run.
Note:
Point the remote controller towards the indoor unit receiver while following steps 2 to 6.
• It is not possible to run the in FAN or DRY mode.
A
TEST RUN
ON/OFF TEMP
6
FAN
AUTO STOP
AUTO START
h
min
4
5
3
2
CHECK
TEST RUN
LOUVER
RESETSET CLOCK
VANE
MODE
7-5-4. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation
• Press either emergency operation switch.
7-5-5. When wired remote controller or indoor unit micro computer troubles
1.When the wired remote control or the indoor unit microcomputer has failed,but all other components work if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly Emergency Operation.
w Note on the wireless remote control: when the remote control does not function, it is possible to activate Emergency
Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,if the indoor unit microcomputer has failed, it is necessary to proceed with points 2 and 3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling, you have to set the switch (SWE) and switch (SW6) on the indoor controller. SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working. SW6-1 : ON • Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or
temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is
activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions.
25
Page 26
7-6. HOW TO CHECK THE PARTS
PL-1.6KAK PL-2KAK PL-2.5KAK PL-1.6KAKL PL-2KAKL PL-2.5KAKL
Parts name Check points
Room temperature thermistor
(TH1)
Indoor coil thermistor
(TH2)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C)
Normal
4.3k'~9.6k'
Abnormal
Open or short
(Refer to the thermistor)
Fan motor
Relay connector
3
2
1
Protector
Vane motor
Drain-up mechanism
Drain sensor
Red
White
Black
1 2
Measure the resistance between the terminals using a tester.
Motor terminal
1 2 3
or
Relay connector
Red-Black
White-Black
Normal
PL-KAK(L)
1.6, 2, 2.5
136.2'
197.5'
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C)
Normal
Approx.14k'
Abnormal
Open or short
Measure the resistance between the terminals using a tester.(Surrounding temperature : 20°C~30°C)
Normal
327'
Abnormal
Open or short
Measure the resistance between the terminals using a tester. Measure the resistance after 3 minutes have passed since the power supply was intercepted.
1 2 3
(Surrounding temperature 0:~60:)
Normal
0.6k'~6.0k'
Abnormal
Open or short
(Refer to the thermistor)
26
Page 27
<Thermistor Characteristic graph>
-200 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
Thermistor for lower temperature
Room temperature thermistor(TH1) Pipe temperature thermistor/liquid(TH2)
Thermistor R0=15k' ±3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+t
1
273
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.4k' 30: 4.3k' 40: 3.0k'
Thermistor for drain sensor
< Thermistor for lower temperature >
50
40
30
20
Resistance (K")
10
0
-20 -10 0 10 20 30 40 50 Temperature (:)
Thermistor R0=6.0k' ±5% Fixed number of B=3390 ±2%
Rt= 6 exp { 3390( ) }
0: 6.0k' 10: 3.9k' 20: 2.6k' 25: 2.2k' 30: 1.8k' 40: 1.3k' 60: 0.6k'
1
273+t
1
273
27
Page 28
7-7.TEST POINT DIAGRAM
7-7-1. Power board PL-1.6KAK PL-2KAK PL-2.5KAK PL-1.6KAKL PL-2KAKL PL-2.5KAKL
CN2S Connect to the indoor controller board (CN2D) Between 1 to 3 12.6-13.7V DC (Pin1 (+))
CNSK Connect to the indoor controller board (CNDK) Between 1 to 3 220-240V AC
28
Page 29
7-7-2. Indoor controller board PL-1.6KAK PL-2KAK PL-2.5KAK PL-1.6KAKL PL-2KAKL PL-2.5KAKL
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
SW6 Emergency operation
FUSE (6.3 A 250 V)
CND Power supply input (220~240V AC)
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2)
CNV Vane motor output (MV) (220~240V AC)
CN2D Connect to the indoor power board (CN2S) (12.5~13.7V DC)
LED1 Power supply (I.B)
LED2 Power supply (R.B)
CN22 Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN30 Transmission (indoor/outdoor)
CN23 Limited switch input (LS)
CN20 Room temperature thermistor (TH1)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN31 Drain sensor (DS)
CN90 Connect to the wireless
remote controller board
(CNB)
CN6V Vane motor output (MV)
CN41 Connector (HA terminal-A)
CN105/CN92 (RED)
CN51 Centrally control
SWE Emergency operation
FAN Fan motor output
Jumper wire J41, J42 Pair number setting with wireless remote controller
29
SW2 Capacity setting
CN32 Remote switch
CN2L Connector (LOSSNAY)
SW5 System setting
SW1 Model setting
Page 30
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model settings
SW5
System settings
Capacity settings
Pair number setting with wireless remote controller
Remarks
SW2
J41 J42
0 1 2
3 ~ 9
Wireless remote
controller setting
Control PCB setting
J41 J42
<Settings at time of factory shipment> Wireless remote controller: 0 Control PCB: (for both J41 and J42) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper line is disco­nnected.)
(Marks in the table below) Jumper wire ( : Short : Open)
SW5-3 Main/Sub setting OFF : Main ON : Sub SW5-4 Rotaion operation setting OFF : Not avairable ON : avairable
MODELS
SW1
Manufacture/Service
PL-KAK(L)
ON OFF
1 2 3 4 5
12345678
ON OFF
MODELS
SW5
Manufacture/Service
PL-KAK
(L)
1 2 3 4 5
ON OFF
MODELS
SW2
Manufacture/Service
PL-1.6KAK(L)
PL-2KAK(L)
1 2 3 4 5
ON OFF
PL-2.5KAK(L)
1 2 3 4 5
ON OFF
7-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
30
Page 31
8 FUNCTION SETTING
Function Settings
No.
Mode
No.
Setting
Initial setting (Factory setting
)
- : Not available
4-Way cassette
PL-KAK(L)
Filter sign 100Hr 1
2500Hr 07 2 No filter sign indicator
3 Air flow Quiet 1 (
Fan speed
)
Standard
08 2
High ceiling
3 No.of air outlets 4 directions 1
3 directions 09 2 2 directions
3 Optional high efficiency
Not supported
10
1 filter Supported
2 Vane setting
No vane
1
Vane No.1 setting
11 2
Vane No.2 setting
3 Energy saving air Disabled
12
1 flow (Heating mode
)
Enabled
2 Optional humidifier Not supported
13
1
Supported
2 Vane differential setting No.1 setting (TH2: 24-28:
)
1 in heating mode No.2 setting (Standard, TH2:28-32:)14 2 (
cold wind prevention
)
No.3 setting (TH2: 32-38:
)
3 Swing Not available
23
1
Available
2 Quiet operation mode Disabled (Standard
)
26
1 (
Fan speed
)
Enabled (Quiet operation mode
)
2 Fan speed when the
Set fan speed
27
1 cooling thermostat is OFF Stop
2 Detection of abnormality of Available
28
1 the pipe temperature (P8)Not available
2
— —
— —
— —
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Rotation
OFF ON Indoor unit's (Main) internal sensor
Remote controller's internal sensor w1 Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 1: (Normal)
-3: When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. 24h cycle 168h cycle Back up function
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2 3
01
02
03
04 15 16
20
The setting is applied to all the units in the same refrigerant system.
8-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the indoor unit number.
• When setting functions for a simultaneous Twin-indoor unit system, set the unit number to 01 to 02 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
31
Page 32
Rotation setting (Function setting mode No.20
)
Function setting
Features Indoor controller board
Mode No.
This system can correspond only by the pattern of two refrigerant group by 1 : 1 (indoor and outdoor unit combination) systems.
Setting No.
SW5-3 setting SW5-4 setting
20 01
(
24hours cycle
)
02
ON
OFF : Main ON : Sub
(
168hours cycle
)
03
(
Back up function
)
When abnormality occurs while operating
,
it changes as a back up unit
,
and operating continues.
Each system operates alternately for 24hours.
Each system operates alternately for 168hours.
Example of unit's operation
(Setting No. = 01 or 02)
Main Unit is abnormal
Operation starts MainSub SubMain
(Setting No. = 02
• • •
168hours cycle)
Outdoor unit
(Setting No. = 03)
Main Unit is abnormal
Indoor
Operation starts MainSub
unit
Remote Controller
MainSub
ON
OFF
OFF
Main
ON
OFF
ON
ON
OFF
8-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 .
Setting number
Address Unit number
Mode number
F
E
G
C
D
J
B
A
I
Modes 01 to 13 can be activated by pressing buttons
A
and
B
simultaneously, and modes 15 to 28 by pressing buttons
B
and J.
indoor unit
Sub indoor unit
24h 24h
Main
Main indoor unit
Sub indoor unit
Sub
32
Page 33
Selecting functions using the wired remote controller
1
Check the function selection setting.
2
Switch to function setting mode.
(Press
A
and B at the same time
For modes 15 and higher, press
with the remote controller stopped.)
3
Specify address
(Use
C
4
Specify unit No.
and D.)
Refer to address unit No. to the figure below
J
and B at the same time.
5
Enter the setting.
(Press
6
Select mode No. 02
(Specified indoor unit:
E
.)
BLOW operation)
NO
Change refrigerant address unit No.
YES
(room temperature detection position).
7
Select setting No. 03 (remote controller fixed).
(Use
F
and G.)
8
Enter the setting.
(Press
E
.)
Example: Selecting room temperature detection position
9
NO
Finished
YES
0
Ending function display
(Press
1 : 1 system Simultaneous twin system Rotation system
A
and B at the same time.)
The above procedure must be carried out only if changes are necessary.
Outdoor unit
Indoor unit
Remote controller
Indoor unit address = 00 unit No. = 01
Main indoor unit
Main indoor unit address = 00 unit No. = 01
Outdoor unit Outdoor unit Outdoor unit
Sub indoor unit
Remote controller
Sub indoor unit address = 01 unit No. = 02
Main indoor unit
Main indoor unit address = 00 unit No. = 01
Sub indoor unit
Remote controller
Sub indoor unit address = 01 unit No. = 01
33
Page 34
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
buttons and then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path. Note
If you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2.
4 Set the indoor unit number.
D Press the
area.
FILTER
simultaneously for at least two seconds.
Address display section
FUNCTION
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
SELECTION
ON/OFF
button so that " - -" flashes in the unit number display
Unit number display section
FUNCTION SELECTION
B ( mode 15 or more) and
TEST
will start to flash,
3 Set the outdoor address.
C Press the [ CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
C Press the [
of the indoor unit for which you want to perform function selection. The unit number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.
E Press the
number. After a while, "- - " will start to flash in the mode number display area.
Mode number display section
* "88" will flash in the room temperature display area if the selected address
does not exist in the system. Furthermore, if address display area also flashes, there are no units that correspond to the selected unit number. In this case, the address and unit number may be incorrect, so repeat steps 2 and 3 to set the correct ones.
6 Select the mode number.
F Press the [
number. (Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
flash, so check the currently set content.
8 Register the settings you have made in steps 3 to 7 .
E Press the
to flash and registration starts.
MODE
button to confirm the address and unit
MODE
"F"
appears and flashes in the unit number display area and the
TEMP] buttons ( and ) to set the desired mode
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
Setting number 1 = Indoor unit operating average
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified address will start fan operation.
Example) When the address is set to 01 and the unit number is 02.
00 address
Outdoor unit
Indoor unit
Designate operation
* When grouping different systems, if an indoor unit other than the
one to which the address has been set performs fan operation, there may be another address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a address exists.
Mode number display section
F Press the [
number.
The mode number and setting number will stop flashing and remain lit, indicating the end of registration.
TEMP] buttons ( and ) to select the desired setting
Main Sub
Remote controller
Mode number 02 = Indoor temperature detection
Setting number 3 = Remote controller built-in sensor
Fan draft
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path. 9 If you wish to continue to select other functions, repeat steps 3 to 8 . 0 Complete function selection.
A Hold down the
buttons simultaneously for at least After a while, the function selection screen will disappear and the air condi­tioner OFF screen will reappear.
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table 1 to indicate the change.
FILTER TEST
( mode 15 or more) and
two seconds.
" flashes in the room temperature display area, a transmission error may have occurred.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
34
Page 35
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation . The procedure is given after the flow chart.
1 Check the function selection setting. 2 Switch to function selection mode.
(Enter address "50" in troubleshooting mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when you press the INSPECT button twice to display "INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address. 4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation area, the unit ends function selection mode automatically if nothing is input for 10 minutes or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change unit No.
YES
NO
7
8-1-2. Selecting functions using the wireless remote controller (Type C)
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger­ant system with wireless function. Address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings. 2 Press the button twice continuously. CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.) Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number. Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available) Direct the wireless remote controller toward the receiver of the indoor unit and press the button. The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting. * If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number. 7 Repeat steps 3 to 5 to change unit number and make function settings on it. 8 Complete the function settings
Press button.
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
3 = 3 beeps (one second each)
2 = 2 beeps (0.4 seconds each, repeated twice) 3 = 2 beeps (0.4 seconds each, repeated three times)
35
Page 36
8-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller *
When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (: or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6 Italian (I), 7 Chinese (CH), 8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button. 1 no1 : Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button.
1 ON :The clock function can be used. 2 OFF:The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
• Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19: Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17: Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
• Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and
(
)] button to move the cursor to the right (left). Press the [ CLOCK
(
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
• To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
• To switch the setting, press the [ ON/OFF] button.
1 ON :The suction air temperature is displayed. 2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
• To switch the setting, press the [ ON/OFF] button. 1 ON : One of "Automatic cooling" and "A utomatic heating" is displayed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
36
Page 37
Flowchart of Function Setting
Setting language (English)
Normal display (Display when the air condition is not running)
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
Item1 Item2
Change Language
E
Hold down the
G
EN
E button and press the D button for 2 seconds.
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
Dot display
GE
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
E
G
MONITOR/SET
BACK DAY
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
CHECK
CLEAR
I
FILTER
A
TEST
B
H
D
C
Function selection
Mode selection
JA
G
G
E
G
G
E
G
G
E
G
G
G
D
D
D
D
D
D
Item3
D
D
D
D
D
D
OFF
on1
on2
ON
OFF
OFF
Operation lock setting is not used. (Initial setting value)
D
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
D
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
D
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
D
The remote controller will be the sub controller.
ON
OFF
The clock function can be used. (Initial setting value)
D
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
D
Auto off timer can be used.
Simple timer can be used.
Display mode setting
Timer mode can not be used.
D
OFF
D
CALL-
G
G
G
G
D
:
°F
D
D
ON
OFF
D
D
ON
OFF
D
The set contact numbers are not displayed in case of error. (Initial setting value)
D
The set contact numbers are displayed in case of error.
The temperature unit
D
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
:
is used. (Initial setting value)
D
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
D
Only "Automatic" is displayed under the automatic mode.
37
Page 38
9
Indoor unit
Shutter plate
4-WAY AIR FLOW SYSTEM
9-1. Placement of the air outlets
For this grill, the airflow direction comes in 5 patterns. Also, by unit function setting by the remote controller, you can adjust the air flow and speed. Select the settings from the Tables according to the location in which you want to install the unit.
1) Decide on the pattern of the discharge direction.
<Table 1>
pattern
Airflow direction
2) According to the number of air outlets and the height of the ceiling to install the unit, be sure to set the unit function set­ting by the remote controller.
<Table 2>
No. of air outlets
4-directional 3-directional
4-direction 3-direction
Pattern 1 Pattern 4
Factory setting
Air flow
Silent
2.4m
2.7m
One air outlet fully closed
Standard High ceiling
2.7m 3.0m
3.0m 3.3m
Note 1. For the 3-direction airflow, install the air outlet
shutter plate(PAC-SF38SP-E)
Note 2. The 2-direction airflow is unavailable.
9-2. Installing the outlet shutter plate (PAC-SF38SP-E)
For the 3-direction discharge, close one air outlet fully by installing the air outlet shutter plate before installing the grill. <Caution> Installing the shutter plate not securely will cause air leak and water dripping.
<How to attach the shutter plate> Peel off the separation sheet from the shutter plate, and attach the shutter plate to the air outlet of the indoor unit.
38
Page 39
SYSTEM CONTROL10
System Name System Diagram Features
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
A.Remote control-
ler operation (Standard)
B.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
C.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
D.
Remote/local combined control operation
Allows start/stop of the air condi­tioner from a dis­tance, and prohib­its/permits start/ stop from remote controllers.
E.Operation by
external signal
F.
Control and remote display by external signal (extraction of monitor signal)
Enables you to display the op­eration state and control start/stop from a distance.
• There are two types of remote controllers: wired type and wireless type.
• Simultaneous twin indoor units are started or stopped simultaneously.
• Up to two remote controllers can be connected to one group.
• Simultaneous twin units are counted as each unit.
• Operation control by the latest command (last en­tered priority)
• Wired and wireless remote controllers can be com­bined as a pair.
• One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each inter face.
• Simultaneous twin units are counted as one unit.
• All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each indoor unit.
• Up to two remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectively from a distance.
• Operation can be switched between the remote operat­ing panel and local controller.
• Operations (e.g., temperature adjustment, airflow, air­flow direction) except for start/stop operations can be performed even if the remote controller is being oper­ated.
• In the case of simultaneous twin units,connect the controller to one indoor unit only. If connected to two indoor units, an error (operation stop) may occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote ON/OFF adapter" enables remote control via relay. (Level signal)
Extraction of non-voltage contact output
• Use of optional "remote operation adapter" and "remote display panel" (Part to be provided at your site)
provides non-voltage contact outputs of signals (operation, error) and operation/stop input function.
Extraction of DC12 V contact output
• Use of optional "remote display adapter" and "re­mote display panel"
(Part to be provided at your site) provides DC12 V contact outputs of signals (operation, error)and operation/stop input function.
* One of the wired remote con-
trollers must be set as a sub remote controller.
Wired remote controller (addi­tional) (PAR-21MAA)
Inter face MAC-397IF-E
Remote ON/OFF adapter (PAC-SE55RA-E) Relay box (Part to be provided at your site) Remote operating panel (Part to be provided at your site)
Remote ON/OFF adapter (PAC–SE55RA-E)
Remote operation adapter (PAC-SF40RM-E) Remote display panel (Part to be provided at your site)
Remote display adapter (PAC-SA88HA) Remote display panel (Part to be provided at your site)
10-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
Indoor unit
Outdoor unit
Remote Controller
Relay box
Indoor unit
Remote Controller
Remote operating panel
Remote Controller
Indoor unit
Remote Controller
Inter face Indoor
unit Outdoor unit
Remote
display kit
Indoor unit
Remote Controller
Remote display (operation, error)
39
Page 40
System Name System Diagram Features
• Weekly timer: In addition to ON/OFF, up to eight temperature patterns can be set for each day of the week.
G. Timer operation
Enables control of start and stop.
* For control by
external timer, refer to Remote/ handheld com­bined control op­eration".
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
performed once within 72 hours (can be set in 1-hour increments).
• Auto off timer:Operation is stopped when the preset
time elapses following the start of operation. The time can be set from 30 minutes to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
MA Remote controller (PAR-21MAA)
H.Interlock opera-
tion with periph-
eral equipment
Enables control of Mitsubishi Lossnay ventilator by remote controller.
I.Rotation
Lossnay ventilator
Main
Remote Controller
Sub
Indoor unit
Remote Controller
Indoor unit
Outdoor unit
• Connecting a Lossnay ventilator and an indoor unit enables control of interlock/solo ventilation opera­tion and airflow. (Only the microcomputer type Lossnay ventilator can be used.)
When abnormality occurs while operating, it changes into operating the back up unit, and operating is continued. (Unit function Mode No. 20 setting No.3 , Indoor controller board SW-5-4 ON) Main / Sub setting Main : Indoor controller board SW5-3 : OFF Sub : Indoor controller board SW5-3 : ON
Each system operates alternately for 24 hours or 168 hours. (Unit function Mode No. 20 setting No.1: 24 hours/ No.2 : 168 hours, Indoor controller board SW 5-4 ON) Main / Sub setting Main : Indoor controller board SW5-3 : OFF Sub : Indoor controller board SW5-3 : ON
This system can correspond only by the pattern of two refrigerant group by 1 : 1 (indoor and outdoor unit combination) systems.
40
Page 41
10-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
IC-2
2
2
OC
IC-1
R
2
2
Standard 1:1 Simultaneous Twin Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
OC IC
1 2
LN
Power source wiring
1 2
1 2
1 2
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
Slim Air Conditioners System
Remote controller optical receiver section connection circuit
Outdoor unit OC
Indoor unit IC
Wireless remote controller receiver section R'
Indoor/Outdoor connection cable
Wireless remote controller cable
Wireless remote controller cable
Remote controller cable
OC
IC-1
R'
IC-2
2
2
9
OC
IC-1
R'
2
9
Standard 1:1 Simultaneous Twin Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
CN90
Controller board
Indoor unit IC
9
CNB
12
Wireless remote controller
optical receiver section R’
Remote controller cable terminal block
(1) One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
(Reference)
1 If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions.
2 Electrical wiring diagram
• Power supply terminal block L, N
• Indoor/outdoor connection cable terminal block 1,2 (Polarity)
• Remote controller cable terminal block 1,2 (No polarity)
(2) Wireless remote controller
(Reference)
1 If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions.
2 Electrical wiring diagram
41
Page 42
10-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
Slim Air Conditioner System
Outdoor unit OC
Indoor unit IC
Remote controller connection circuit (Controller cable)
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
[Reference] 1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some function may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring. 3 Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function
selection.
Standard 1:1 Simultaneous Twin
Remote controller cable
OC
IC
R-1
OC
2
IC
2
2
R-1
2
2
R-2
2
R-2
Indoor/outdoor connection cable
(R: Wired remote controller)
OC
2
IC-1
R-1
OC
2
IC-1
2
R-1
IC-2
2
2
2
R-2
IC-2
2
2
R-2
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
(2) Two Wireless Remote Controllers
Slim Air Conditioner System
Outdoor unit
Remote
OC
controller receiver
Indoor unit IC
connection circuit
Wireless remote controller receiver section R'
Standard 1:1 Simultaneous Twin
(R': Wireless remote controller receiver)
Indoor/outdoor connection cable
OC
IC-1 Receiver connection cable
9 9
R'-1
Remote controller cable
2
IC-2
2
Indoor controller board switch setting
SW5-3
OFF
ON
R'-2
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately. [Reference] 1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some functions may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
In the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with systems
3
consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the pair numbers will be "0" (factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
operation made last by any of the remote controllers will be effective.
(3) One Wired and One Wireless Remote Controller
(R: Wired remote controller, R': Wireless remote controller receiver)
Slim Air Conditioner System
Outdoor unit
Remote
OC
controller receiver
Indoor unit IC
connection circuit
•Wired remote controller R
•Receiver R'
Standard 1:1 Simultaneous Twin
Indoor/outdoor connection cable
Remote controller cable
OC
3(2)
IC
R
Receiver connection
9
2
cable
R'
OC
IC-1
2
IC-2
2
9
2
R
R'
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
[Reference]
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless
1
remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some functions may be restricted. In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
2
When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
3
operation made last by any of the wireless remote controllers will be effective.
42
Page 43
10-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
Group control can be operated by using MAC-397IF-E. The setting of wired remote controller is subjected to variation according to the function of the indoor unit. (for mode operation, setting temperature, fan step, air direction) The display of remote controller and operating the indoor unit might be different. Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA & CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also, keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
INDOOR
CN105
or
CN92
Indoor control board
Connect the connecting cable that comes with the interface unit to the connector CN105 or CN92 on the indoor control board.
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the connecting cable used for each system.
Interface unit mounting cord clamp or mounting
Mounting screws (black) 3.5 o 12
Connecting cable for each system
cord clamps
• The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
Mounting screws 4 o 10
Electrical wire mounting
Mounting cord clamp
bracket
Mounting screws 4 o 16
Mounting cord clamp
• Set the interface dip switch (SW500–502) settings before turning on the power.
• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
43
Page 44
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller..
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10: and 38:.
Indoor unit
Interface unit
CN560
TB580 1 2 A B
Remote control cord that came with the MA remote controller (Non polarity)
2
MA remote controller (PAR-21MAA) * PAR-20MAA cannot be used
with this interface.
Dip switch settings
SW500 does not have to be set.
SW501: SW501- No. 1-4: Refrigerant address
• Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
• Always start the refrigerant address at "0". Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
Refrigerant address
0
1
2
15
1
112
3333
4
Refrigerant address "0"
5
1Outdoor unit 2Outdoor unit 3Indoor unit 4Interface 5MA remote controller
44
Refrigerant address "1"
Refrigerant address "2"
ON
1
ON
1
ON
1
ON
1
2 3 4
2 3 4
2 3 4
2 3 4
SW501- No. 5–6
ON
No. 5 should normally be set to OFF. Under the following conditions, No.6 should normally be set to ON.
6
5
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller. * This can be switched when an accurate room temperature cannot be detected by the air conditioner unit. PL-KAK series do not have a room temperature sensor on their MA remote controllers.
44
Page 45
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1 No. 2 No. 3 No. 4
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
Functions OFF ON Comments
Only specify these settings when connecting an
Refrigerant address 0
MA remote controller.
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
SW No.
No. 5 No. 6
Functions Room temperature detector The model of Mr. SLIM exists in the
same group.
OFF Indoor unit Not mixed
45
ON Remote control Mixed
Comments This should normally be set to OFF. This should normally be set to ON.
Page 46
S
W502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
Cooling only type/ Heat pump type
Auto mode
Fan speed
Functions
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
4 speeds
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
3 speeds (2-speed
model set ON)
Comments
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON. Cooling only type : Set to OFF.
Set to OFF. When operating a 2-speed model with the 3-speed
setting (ON), the MA remote controller display will indicate 3 fan speeds. The table below shows the displays and the actual outputs at that time.
Display Meaning Indoor unit output
Low speedLow speed
Medium speed High speed
High speed
High speed
No. 5
Vane
No. 6
Swing
No. 7
Not in use
No. 8
Fan mode
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
Available
Available
Not available
Not available
Not available
Available
The Vane function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
Permanently set to OFF. Set to ON.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
DC 12 V is not being supplied from the air conditioner.
Device is not communicating properly with the air conditioner.
Device is not communicating properly with the MA remote controller.
Lamp off
Lamp on
DC 12 V is being supplied from the air conditioner.
Blinking
Blinking at approx. 1 second intervals: Device is communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com­municating normally with the MA remote controller.
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit. The device will not function properly if the connecting cable is extended so the connecting cable should not be extended. Mount the interface unit securely to a pillar or wall using 2 or more screws.
When Using Wall Mounting Brackets
1
Attach the wall mounting brackets to the interface unit using 2 mounting screws.
Interface unit
Wall mounting brackets
Mounting screws
2
Mount the unit to a pillar or wall using 2 mounting screws.
Mounting screws
46
Cord clamp for wiring
Mounting screws
Page 47
When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting screws.
Interface case mounting screws
Mounting screws
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
When mounting the interface unit inside a ceiling or wall, install an access door to facilitate mainte­nance.
When the interface unit is mounted above an indoor unit, it should be positioned 40 mm or more away from the unit to ensure that ceiling grills can be removed.
40 mm or more
Attach the interface unit connecting cable here. Store extra connecting cable in the ductwork space behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
47
Page 48
10-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
Indoor unit
Relay box Relay box Relay box
Indoor unit
Control circuit power supply
Indoor unit Indoor unit
Remote controller
Remote/ local selection switch
Control room W
room 1 room 2 room 3
Remote controller
Remote controller
Remote controller
• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode. w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the unit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a clear determination of whether or not there was a power failure. When it has been determined that there has been a power failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.) When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller.
• When there is group control, selection of all refrigerants is required.
10-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central­ized monitoring of the air conditioners in each room can be attained.
• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con­trollers with 0.3 to 1.25 mm22-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
10-7. COMBINED REMOTE/ LOCAL CONTROL
• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter (PAC-SE55RA-E sold separately) through the relay box installed on site. When this remote control is cancelled, the local remote controller can be used for operating and stopping the air conditioner.
1. Basic system wiring
• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes from the relay box and remote/local selection switch and connect it to the CN32 connector on the printed circuit board for the indoor unit
<Points of precaution>
1 Match the rated power supply voltage of the remote/local selection switch and relay (X2) with the power supply for the con-
troller.
2 When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not start
at the same time. If this is not performed, all of the units will start at one time creating an over current that will cause the circuit breaker to operate.
3 An on-delay system is one that includes specifications for operating a limited time when an on signal is received and has a tem-
porary off timer for recovery operations.
4 Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-
vided, abnormal operation will occur.
(1) System diagram
W The AC for the control room is usually disconnected from the remote/local control system.
48
Page 49
Control circuit power supply
Dedicated short circuit prevention device
Remote/local selection switch
No.1 unit relay box
No.2 unit relay box
3 Relay box
2
Adapter for
remote start/stop
1
Remote/local
selection switch
T Timer
(On delay system)
X Relay
Model PAC-SE55RA-E (Sold separately)
(Example) Single polarity single-throw switch (125V rating)
To next unit
T
Brown
Red
X
2 X2
T
One method of easily distinguishing the on/off status of SW1 and SW2 is to use together with a "illuminated switch R" or pilot lamp.
T
X
2
SW1 SW2
T
X
2
Orange Orange
Brown
Red
Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• AC is in operation.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• AC is in operation.
• Starting/stopping by remote operation enabled.
Remote control
OFFON
Description of functions
OFFON
SW1 SW2
OFFON
Remote/local selection switch
(2) Basic wiring diagram
Indoor unit circuit board
CN32
Orange Red
Brown
On site wiring On site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used. Protect exposed wire by wrapping with insulating tape
On site wiring
SW1
Indoor unit circuit board
CN32
Orange Red
Brown
SW1 SW2
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
Indoor unit circuit board
CN32
Orange Red
Brown
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
For remote operation
For timer operation
(3) Part specifications
Note: When using group address, connect to refrigerant
address "0" on the inside.
2. Examples of system applications
In any of the following examples, there is a five to six second delay from the time the operating command is issued until the operation begins. 1 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited.
2 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be separated.
3 This is when starting and stopping is performed by remote operation and then allowing starting or stopping by remote con-
trol at any time.
4 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
Use momentary switch for SW2. (Manual operation/automatic recover switch on time is more than one second.) Press SW2 (on time is more than one second) and operation starts. After this has been done, stopping or restarting can be down by remote controller.
49
If SW2 is on, operation by remote controller cannot be performed. If SW2 is off, operation by remote controller is permitted.
Page 50
10-8. OBTAINING REMOTE DISPLAY
CN90 CN1
CN41
Wireless
3
TB3
External input
TB2
Error
TB1
Operation
2
Indoor control circuit board Remote operation adapter
5
External input
Error output (No voltage momentary "a" contact)
Operating output (No voltage momentary "a" contact)
No voltage (Momentary "a" contact)
HA
Power supply for controller
Timer control
panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
Use the remote operation adapter (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off input function.
(1) Wiring method
..
Caution
TB3 is a dedicated terminal for contact point input. Never input voltage. It will damage the indoor control circuit board.
<Connections on the indoor unit side>
1 When using external output function
Insert the 9-prong connector (3-core) of the attached cable to CN90 on the indoor control circuit board.
2 When using the external input function
Insert the 4-prong connector (2-core) of the attached cable to CN41 on the indoor control circuit board. W The connector is direction-sensitive. Use care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2) Locally procured parts
Item Name Model and specifications
External output function External output signal wire Use sheathed vinyl coated cord or cable.
Wire type: CV, CVS or equivalent. Wire size: Stranded wire 0.5mm
2
to 1.25mm
Single straged: {0.65mm to 1.25mm
Display lamp, etc. No voltage “a” contact AC200V (DC30V), 1A or less
External input function External input signal wire Use sheathed vinyl coated cord or cable.
Wire type: CV, CVS or equivalent. Wire size: Stranded wire 0.5mm2to 1.25mm
Single straged: {0.65mm to 1.2mm
Switch No voltage “a” contact
(Start and stop operation is switched by inputting a pulse of 200ms or more)
2
2
10-9. TIMER OPERATION
Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in 10-minute increments within a 24-hour period.
When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can be stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
1.Operating with on-site timer
(1) Summary of system
If the “Remote ON/OFF adapter” (PAC­SE55RA-E) (sold separately) is used, the on-site timer can be operated to turn each unit on and off.
50
Page 51
(2) Basic pattern for timer control
Orange
As selected by remote controller operation switch.
From indoor unit
Red Brown
T
SW ON SW OFF
Timer control Remote controller control
SW
Orange
From indoor unit
Red Brown
T
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage
(PAC-SB81VS)
External control
input terminal
block
1 2
3
Connector
(CN2L)
Basic wiring
X: Relay (DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box (On-site tinstallation)
Relay box
(On-site tinstallation)
Remote controller
Humidifier unit
Humidifier
unit
Use a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply). a) Timer-independent control b) Combined control by timer and remote controller
(3) Basic system
Refer to 10-7 COMBINED REMOTE / LOCAL REMOTE CONTROL.
10-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT
Lossnay operation
Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - sold
separately) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from the remote controller.
1 Summary of wiring
Connect the Lossnay linkage cable (Model PAC­SB81VS) connector to CN2L on the indoor unit on the circuit board of the indoor unit.
Connect the lead wire of the Lossnay linkage cable to the Lossnay external control input terminal blocks (1) and (2). (At this time, the input terminal blocks (1) and (2) have no polarity.)
2 Precautions when wiring
The Lossnay linkage cable can be extended up to a maximum of 500 meters. When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation. (Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm
Lossnay linked cable
Arrange wiring so that there can be no contact between the Lossnay linkage cable and the power supply cord. Contact
may cause malfunctioning. (Separate by 5cm or more.)
2
)
10-11. OBTAINING HUMIDIFIER SIGNAL
10-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR
The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the adaptor for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifier unit via the on-site relay box. There is no output when the thermostat is off, during heating preparation and during defrosting.
W Please consult your nearest Mitsubishi Electric
representative for information about obtaining the adapter for humidifier signal.
Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model PAC-SE41TS-E - sold separately) to the CN20 connector on the circuit board for the indoor unit.
The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is required. Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
51
Page 52
10-13. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display adapter
The maximum distance between indoor board and relay is 10m.
YELLOW ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power supply
Remote controller cable
Relay box (Field supply)
Remote controller
Remote controller
Remote controller
3wires 3wires 3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control ON-OFF display (Field supply)
(Operation check)
<System>
Power supply
RL-1 GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect to the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2 GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Be sure to secure insulation material by tape and such
5
Green
Yellow Orange
Connector (5P)
Package side
Multiple remote controller adapter PAC-SA88HA-E
Be sure to secure insulation material by tape and such
Installation at site
CN51 on indoor controller board
Red
Brown
1
~
MB
Indoor controller board
CN51
You can control several units with a multiple remote control display, by wiring an optional multiple display adapter (PAC-SA88HA-E) with relays and lamps on the market.
How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
Indoor controller board
[Notes on Signs] X1:Relay (for operation lamp) X2:Relay (for check lamp) RL:Operation Lamp GL:Check Lamp [Field supplied parts] Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
10-14. INTERLOCKING OPERATION METHOD WITH DUCT FAN (Booster fan)
Whenever the indoor unit is operating, the duct fan operates. (1)Connect the optional multiple remote
controller adapter(PAC-SA88HA-E)to the connector CN51 on the indoor controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow and
Orange connector lines. Use a relay under 1W. MB: Electromagnetic switch power relay
for duct fan.
X: Auxiliary relay (12V DC LY-1F)
52
Page 53
11
DISASSEMBLY PROCEDURE
PL-1.6KAK / PL-2KAK / PL-2.5KAK PL-1.6KAKL / PL-2KAKL / PL-2.5KAKL
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
Be careful on removing heavy parts.
1. Removing the air intake grille
(1) Press the button. (2) Open the intake grille 90°. (3) Remove the clip. (4) Slide the shaft in the hinge to the left and remove the
intake grille.
2. Removing the controller cove assy (electrical parts)
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the red connector (10P). (2) Remove 2 of 4 screws from the bell mouth. (3) Remove the electrical parts cover. (4) Disconnect the following connectors from the box.
(5) Disconnect the blue ground wire of the controller cover assy. (6) Remove 3 of 4 screws from the controller cover assy, and
loosen the other screw. (7) Pull out the controller cover assy.
(Electrical parts inside the controller cover assy) Terminal block power board Indoor fan capacitor Room temperature thermistor (TH1) Indoor controller board
PUSH
Red (3P) for the fan motor White (2P) for the pipe temperature thermistor (TH2) Blue (2P) for the drain pump White (3P) for the drain sensor
Figure 1
PUSH button
Photo 1
Photo 2
Nut
Radiator aluminum cap
Screws
Lead wire for vane motor
Shaft
Intake grille
Clamp
Indoor controller board
Screws
Connector
Bell mouth
3. Removing the fan motor
(1) Remove the turbo-fan nut and radiator aluminum cap. (2) Pull out the turbo fan. (3) Disconnect the connector of the fan motor lead wire. (4) Remove the 3nuts of fan motor.
53
Screws
Connector
Photo 3
Power board
Fan motorConnector
Screws
nut
Terminal block
Room temperature thermistor (TH1)
Page 54
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
4. Removing the room temperature thermistor
(1) Remove the electrical box cover (2) Remove the holder and the room temperature thermistor
by pulling the catch.
(3) Disconnect the red connector,CN20,on the indoor con-
troller board.
5. Removing the indoor coil thermistor
(1) Remove the electrical box cover. (2) Remove the electrical box. (3) Remove the turbo fan. (4) Remove the screw of the service panel. (5) Remove the service panel. (6) Remove the indoor coil thermistor from the holder
attached to the copper pipe.
(7) Disconnect the 2-pin white connector.
Photo 4
Room temperature thermistor
Photo 5
Indoor controller board
Indoor coil thermistor
6. Removing the panel
(1) Open the intake grille. (2) Disconnect the connector of the vane motor. (3) Remove 4 screws of the panel. (4) Pulling the temporary handing hook, remove the panel.
7. Removing the drain pan
(1) Remove the panel. (2) Remove the rubber bushing. (3) Drain the remaining water in the drain pan. (4) Remove the electrical box cover. (5) Remove the electrical box. (6) Remove the screw of the V.A. cover, and remove the V.A.
cover.
(7) Remove each screw of the corner supports 1, 2, and 3,
and remove the corner supports 1, 2 and 3.
(8) Pull out the drain pan.
wPull the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Photo 6
Screws
Panel
Photo 7
Corner cover screws
Mounting hole
Temporary hanging hook
Corner cover
Screws
Temporary hanging hook
Screws
Drain pan
54
Screws
Screws
Page 55
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
8. Removing the drain pump and drain sensor
(1) Remove the panel. (2) Remove the electrical parts cover. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Remove 4 screws of the drain pump. (6) Pulling the clip of the drain hose, pull out the drain hose
from the drain pump. (7) Remove the drain sensor and the holder. (8) Pull out the drain pump.
9. Removing the heat exchanger
(1) Remove the panel. (2) Remove the electrical parts cover. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Remove the turbo fan. (6) Remove the screw of the coil support A. (7) Remove the 2 screws of the coil support B. (8) Remove the 2 screws of the coil. (9) Remove 4 screws of the piping cover of the outer wall,
and pull out the piping cover.
Photo 8
Drain hose
Clip
Drain pump
Photo 9
Drain sensor holder
Screws
Coil set screws
Heat exchanger
Photo 10
Screw
Coil support A
Screw of the coil support A
Screw
Piping cover
55
Page 56
12
KAK KAKL
WIRED
WIRELESS
No.
Parts No. Parts Name Specifications
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set
PL-1.6/2/2.5
Price
1
2 3 4 5 6 7 8
9 10 11 12 13
AIR OUTLET GRILLE AIR OUTLET GRILLE RECEIVER ADAPTER CASE WIRELESS REMOTE CONTROLLLER BOARD AIR FILTER INTAKE GRILLE GRILLE HANGER HINGE REMOTE CONTROLLER REMOTE CONTROLLER REMOTE CONTROLLER DOOR REMOTE CONTROLLER HOLDER REMOTE CONTROLLER CABLE
1
1 1 1 2 1
1
(BG25L641H02)
(BG88H096H01)
W.B.
R.B
Remarks
(Drawing No.)
T7W 560 003 T7W E06 003 R01 24K 658
– R01 E05 317 R01 29H 500 R01 29H 691
– R01 29H 061 T7W E08 713 T7W E06 714 R01 E01 049 R01 E00 075 T7W E01 305
1 1 1 1 1 1 1 2
1 1 1
PARTS LIST
PANEL PARTS PL-1.6KAK PL-1.6KAKL PL-2KAK PL-2KAKL PL-2.5KAK PL-2.5KAKL
1 2
3
8
4
7
5
6
9
10
11
12
13
56
Page 57
PANEL PARTS PL-1.6KAK PL-1.6KAKL PL-2KAK PL-2KAKL PL-2.5KAK PL-2.5KAKL
10
1
1
2 3
1
10
10
1
4
5
5
9
6
5
5
8
Part numberthat is circled is not shown in the figure.
No.
Parts No. Parts Name Specifications
1
R01 29H 002
2
T7W 33K 063
3
R01 29H 223
4
R01 29H 085
5
R01 29H 047
6
R01 29H 041
7
R01 29H 040
8
T7W 560 258
9
R01 29H 056
10
R01 29H 063
11
R01 E01 673
AUTO VANE SPRING JOINT VANE MOTOR AIR GUIDE VANE SUPPORT GRILLE GEAR(LEFT) GRILLE GEAR(RIGHT) CORD HEATER PUSH BUTTON SPRING JOINT 1 SCREW ASSY
240V 28.8W
5
Q'ty / set
PL-1.6/2/2.5
KAK
WIRED
WIRELESS
4 1 1 1 8 1 1 1 1 1 1
KAKL
4 1 1 1 8 1 1 1 1 1 1
Remarks
<3/SET>
Wiring
Diagram
Symbol
MV
H2
Recom­mended
Q'ty
7
Price
Unit
Amount
57
Page 58
FUNCTIONAL PARTS PL-1.6KAK PL-1.6KAKL PL-2KAK PL-2KAKL PL-2.5KAK PL-2.5KAKL
1 2 3
4
32
31 30
29
5
6
7
8
9
10
28
27
PIPE TEMPERATURE
26
THERMISTOR
25
24 23
22
21
20 19
FUSE
11
12
13
18
17
16
15
14
58
Page 59
1.6
2
2.5
No.
Parts No. Parts Name Specifications
PL-
KAK(L)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
Part number that is circled is not shown in the figure.
1 2 3 4 5 6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33
BASE MOTOR MOUNT INDOOR FAN MOTOR LEG LEG SPL WASHER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN INDOOR FAN CAPACITOR CONTROLLER CASE INDOOR CONTROLLER BOARD FUSE ELECTRICAL PARTS COVER BELL MOUTH ROOM TEMPERATURE THERMISTOR POWER BOARD TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK DRAIN PLUG CORNER COVER SENSOR HOLDER DRAIN SENSOR DRAIN PUMP DRAIN SOCKET INDOOR COIL THERMISTOR MOTOR CAP TURBO FAN INNER COVER COVER DRUM LEG LEG DRAIN HOSE
1 3 1 1 1 1
1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 3 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 3 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
MF
C
I.B
FUSE
TH1
P.B TB2 TB5 TB4
DS DP
TH2
3P(L,N,;) 2P(1,2)
Remarks
(Drawing No.)
— R01 29H 105 T7W E00 762
— R01 08K 097 T7W E03 480 T7W E04 480 T7W E05 480 R01 E18 529 R01 29H 255
— T7W
E47 310
R01 E02 239
— R01 E33 202 T7W E24 313 T7W 521 716 T7W 512 716 T7W E27 716 R01 A48 524
— R01 31K 241 R01 E09 266 T7W E00 355 R01 41N 523 R01 08K 202 R01 E00 122 R01 41N 114
R01 W28 527
(BG02Y348G09)
(BG00T672G08)
(BG00T672G09) (BG00T672G10)
(BG00T673G02)
(BG00T718G11) (BG00T712G11)
(BG00T713G05)
(BG25J080H02)
(BG00L601G32) (BG00A662G30)
2.5+ 400V
250V 6.3A
3P(1,2,3)
59
Page 60
13
OPTIONAL PARTS
13-1. REFRIGERANT PIPES
Service Ref. : PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
Part No. Pipe length Pipe size O.D. Connection method
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant piping contains refrigerant at the above atmospheric pressure. As long as connec­tion takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 20m, an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
PAC-05FFS-E
5m
PAC-07FFS-E
7m
Liquid:ø9.52
Indoor unit:Flared
13-2. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
Part No.
Applicable Service Ref.
1 2 3 4 5
BRN RED ORN YLW GRN
PAC-SA88HA-E
PL-1.6/2/2.5KAK(L)
PAC-10FFS-E
10m
Gas:ø15.88 Outdoor unit:Flared
PAC-15FFS-E
15m
13-3. REMOTE ON/OFF ADAPTER
Part No.
Applicable Service Ref.
13-4. REMOTE SENSOR
Part No.
Applicable Service Ref.
13-5. REMOTE OPERATION ADAPTER
Part No.
Applicable Service Ref.
PAC-SE55RA-E
PL-1.6/2/2.5KAK(L)
PAC-SE41TS-E
PL-1.6/2/2.5KAK(L)
PAC-SF40RM-E
PL-1.6/2/2.5KAK(L)
60
Page 61
13-6. SPACE PANEL
750
Hole
16
R7.8
R26
750
R26
R7.8
965
Hole
965
R25
R37
R
6
R31
R25
R37
R
6
R31
R18047.5
R18102.5
440
122 99
65
42
13
Part No. PAC-SE01AS-E
Applied Model PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
13-7. WIDE PANEL
Part No. PAC-SE06WP-E
Applied Model PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
13-8. AIR OUTLET SHUTTER PLATE
Part No. PAC-SF38SP-E
Applied Model PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
61
Page 62
13-9. MULTI-FUNCTIONAL CASEMENT
Part No. PAC-SE21TM-E
Applied Model PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
Casement
1pc
Screw with
washer
4pcs
M5x0.8x15
Duct flange
1pc
Tapping
screw
6pcs
4x10
Hook Band
2pcs 1pc
13-10. HIGH-EFFICIENCY FILTER ELEMENT (MULTI-FUNCTIONAL CASEMENT is required.)
Part No. PAC-SE13KF-E
Applied Model PL-1.6KAK(L) / PL-2KAK(L) / PL-2.5KAK(L)
62
Page 63
63
Page 64
HEAD OFFICE : TOKYO BLDG.2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Apr. 2006 No. OC384 PDF9 Made in Japan.
New publication, effective Apr. 2006 Specifications subject to change without notice.
Loading...