Mitsubishi MXZ-3C24NAHZ2 Submittal

M-SERIES
Job Name:
System Reference: Date:
Outdoor Unit: MXZ-3C24NAHZ2
Cooling* (Non-ducted / Ducted)
Heating at 47°F* (Non-ducted / Ducted)
Heating at 17°F* (Non-ducted/Ducted)
Heating at 5°F* Maximum Capacity Btu/h 25,000
Energy Star
®
(ENERGY STAR products are third-party certied by an EPA-recognized Certication Body.) Yes
Electrical Requirements
Voltage
Compressor DC INVERTER-driven Twin Rotary Fan Motor (ECM) F.L.A. 2.43 Sound Pressure Level
(Non-ducted/Ducted)
External Dimensions (H x W x D) In / mm
Net Weight Lbs / kg 189 / 86 External Finish Munsell No. 3Y 7.8/11 Refrigerant Pipe Size O.D. ―
Eight Ports Max. Refrigerant Line Length Ft / m 230 / 70 Max. Piping Length for Each Indoor Unit Ft / m 82 / 25 Max. Refrigerant Pipe Height
Difference Connection Method Flared/Flared Refrigerant R410A
* Rating Conditions per AHRI Standard:
Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB Cooling | Outdoor: 95º F (35º C) DB / W.B. 23.9° C (75° F)
Rated Capacity Btu/h 22,000 / 23,600
Capacity Range Btu/h 6,000 - 23,600
Rated Total Input W 1,630 / 2,360
Rated Capacity Btu/h 25,000 / 24,600
Capacity Range Btu/h 7,200 - 30,600
Rated Total Input W 1,725 / 1,871
Rated Capacity Btu/h 14,000 / 14,000
Maximum Capacity Btu/h 25,000 / 24, 600
Rated Total Input W 1,622 / 1,635
Power Supply Voltage, Phase, Hertz 208 / 230V, 1-Phase, 60 Hz Recommended Fuse/Breaker Size A 40
MCA A 30.5
Indoor - Outdoor S1-S2 V AC 208 / 230 Indoor - Outdoor S2-S3 V DC ±24
Cooling Heating 58
Liquid (High Pressure) Gas (Low Pressure) A:1/2 / 12.7 ; B,C: 3/8 / 9.52
If IDU is Above ODU If IDU is Below ODU 49 / 15
MULTI-INDOOR INVERTER HEAT-PUMP SYSTEM
ACCESSORIES
3/8" x 1/2" Port Adapter (MAC-A454JP-E) □ 1/2" x 3/8" Port Adapter (MAC-A455JP-E) □ 1/2" x 5/8" Port Adapter (MAC-A456JP-E) □ M-NET Adapter (PAC-IF01MNT-E) □ Airow Guide (PAC-SH96SG-E)
(For data on specic indoor units, see the MXZ-C Technical and Service Manual.)
Specications Model Name
Unit Type MXZ-3C24NAHZ2
dB(A)
54
41-9/32 x 37-13/32 x 13
1048 x 950 x 330
In / mm
Ft / m
Heatin g at 47ºF | Indoor: 70º F (21º C) DB / 60º F (16º C) WB Heatin g at 47ºF | Outdo or: 47º F (8º C) DB / 43º F (6º C) WB
Heatin g at 17º F | Indoor: 70º F (21º C) DB Heatin g at 17º F | Outdoor: 17º F (-8º C) DB / 15º F (-9º C) WB
1/4 / 6.35
49 / 15
SUBMITTAL DATA: MXZ-3C24NAHZ2
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
SPECIFICATIONS: MXZ-3C24NAHZ2
OPERATING RANGE:
Outdoor
Cooling D.B. 14 to 115° F [ D.B. −10 to 46° C]*1
Heating W.B. -13 to 65° F [ W.B. −25 to 18° C ]
*1. D.B. 5 to 115° F [ D.B. −15 to 46° C ], when an optional Air Outlet Guide is installed.
NOTES:
ENERGY EFFICIENCIES:
Indoor Unit Type SEER EER HSPF
Non-ducted (06 + 06 + 09)
Ducted and Non-ducted
Ducted (09 + 09 + 09)
19.0 13.5 10.0 4.25 2.53
17.3 11.75 9.5 4.03 2.52
15.5 10.0 9.0 3.80 2.51
• Minimum of two Indoor Units must be connected to the MXZ-3C24NAHZ2.
• Minimum installed capacity cannot be less than 12,000 Btu/h.
• Total connected capacity must not exceed 130% of outdoor unit capacity.
• System can operate with only one Indoor Unit turned on.
• Information provided at 208/230V.
• For Reference:
- MXZ-C Technical & Service Manual for detailed specications and additional information per Indoor Unit Combination.
- MXZ Series Multi-Zone Indoor/Outdoor Combination Table for allowed unit combinations.
MVZ CONNECTION RULES:
• Only 1 MVZ may be used on any system.
• When an MVZ is connected, total connected capacity must be 100% or less.
• When an MVZ is connected, no P-Series indoor units can be used (PCA, PLA, or PEAD).
COP @
47°F
COP
@ 17°F
Notes:
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
DUCTED:
Operational Performance for Indoor Unit Combinations (Unit A + Unit B + Unit C)
9
12
15
18
9 + 9
9 + 12
9 + 15
9 + 18
12 + 12
12 + 15
9 + 9 + 9
MXZ-3C24NAHZ2 OPERATIONAL PERFORMANCE
Cooling Capacity Range (Btu/h) Heating Capacity Range (Btu/h)
Unit A Unit B Unit C
9000 0 0
10900 0 0
12000 0 0
13600 0 0
15000 0 0
18000 0 0
17200 0 0
21600 0 0
9000 9000 0
10900 10900 0
9000 12000 0
9343 12457 0
8175 13625 0
8175 13625 0
7267 14533 0
7267 14533 0
10900 10900 0
10900 10900 0
9689 1 2 111 0
9689 1 2 111 0
7867 7867 7867
8200 8200 8200
Power Usage Range (W) Current (208/230V)
TBD
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
NON-DUCTED:
Operational Performance for Indoor Unit Combinations (Unit A + Unit B + Unit C)
6
9
12
15
18
6 + 6
6 + 9
6 + 12
6 + 15
6 + 18
9 + 9
9 + 12
9 + 15
9 + 18
12 + 12
12 + 15
6 + 6 + 6
6 + 6 + 9
6 + 6 + 12
6 + 6 + 15
6 + 9 + 9
6 + 9 + 12
9 + 9 + 9
MXZ-3C24NAHZ2 OPERATIONAL PERFORMANCE, contd.
Cooling Capacity Range (Btu/h) Heating Capacity Range (Btu/h)
Unit A Unit B Unit C
6000 0 0
7400 0 0
9000 0 0
11000 0 0
12000 0 0
14400 0 0
14000 0 0
18000 0 0
17200 0 0
21600 0 0
6000 6000 0
7400 7400 0
6000 9000 0
7360 11040 0
6000 12000 0
7333 14667 0
5714 14286 0
6286 15714 0
5450 16350 0
5500 16500 0
9000 9000 0
11000 11000 0
8571 11429 0
9429 12571 0
8175 13625 0
8250 13750 0
7267 14533 0
7333 14667 0
10900 10900 0
11000 11000 0
9689 1 2 111 0
9778 12222 0
6000 6000 6000
7400 7400 7400
6000 6000
7086 7086 10629
5500 5500 11000
6250 6250 12500
5333 5333 13333
5556 5556 13889
5500 8250 8250
6250 9375 9375
5333 8000 10667
5556 8333 11111
8000 8000 8000
8333 8333 8333
9000
Power Usage Range (W) Current (208/230V)
TBD
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
DIMENSIONS: MXZ-3C24NAHZ2
MXZ-3C24NAHZ MXZ-3C30NAHZ
Unit: inch (mm)
Unit: inch (mm)
Lock nut
Conduit plate Top
Conduit connector
Conduit plate Under
1340 Satellite Boulevard. Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com
FORM# MXZ-3C24NAHZ2 for Multiple Indoor Unit Styles - 201605
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.