Mitsubishi MXZ-32SV-E1, MXZ-32SV-E2 Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Inverter-controlled multi system Models
Revision B:
“Check of HPS” and PARTS LIST have been corrected.
Please void OB254 REVISED EDITION-A.
No. OB254
REVISED EDITION-B
MXZ-32SV ­MXZ-32SV -
Model indication
E1
E2
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. INDOOR/OUTDOOR CORRESPONDENCE TABLE ···························3
4. INDOOR UNITS COMBINATION ·······················4
5. SPECIFICATION·················································8
6. NOISE CRITERIA CURVES······························ 9
7. OUTLINES AND DIMENSIONS······················ 10
9. REFRIGERANT SYSTEM DIAGRAM··············12
10. PERFORMANCE CURVES······························13
11. MICROPROCESSOR CONTROL·····················19
12. TROUBLESHOOTING ······································25
13. DISASSEMBLY INSTRUCTIONS·····················37
14. PARTS LIST······················································40
15. OPTIONAL PARTS ···········································43
This manual describes technical data of outdoor unit. For indoor unit, refer to the service manuals No. OB229, OB227, OB252, OB212, OB239 and OC165.
Page 2
Revision A:
• MXZ-32SV - has been added.
Revision B:
• “Check of HPS” and PARTS LIST have been corrected.
1
MXZ-32RV - ➔ MXZ-32SV -
1. The combination pattern of the indoor unit has been increased.
2. Crankcase heater has been disused.
3. Refrigerant circuit has been changed.
• Disuse of 2-way valve.
• Disuse of capillary tube
• Disuse of low pressure switch.
• Disuse of suction pipe temperature thermistor.
MXZ-32SV - MXZ-32SV -
1. Combinations of the connectable indoor units have been increased.
2. Noise filter P.C. board has been changed to improve the capacity for protecting the inverter-controlled circuit when the voltage higher than the rated one is aupplied with the inverter-controlled circuit.
3. Noise filter P.C. board for “E1” and “E2” are not interchangeable.
4. Service parts have been changed as follows according to above change;
•The value of R(resistor)has been changed. 1020
•TB6(terminal block) has been removed.
E2
TECHNICAL CHANGES
E1E1
[3 o [2 o 500.
E2E1
2
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MXZ-32SV­MXZ-32SV-
E1 E2
Air outlet
Air inlet
Model indication
(back and side)
2
Page 3
3
There is no combination other than this table.
MXZ-32SV- E1 , MXZ-32SV- E2
OUTDOOR UNIT
Combination of the connectable indoor units
07+07 07+09 07+12 07+18 09+09 09+12 09+18 12+12 12+18
18+18 07+07+07 07+07+09 07+07+12 07+07+18 07+09+09 07+09+12 07+09+18 07+12+12 07+12+18 07+18+18 09+09+09 09+09+12 09+09+18 09+12+12 09+12+18 09+18+18 12+12+12 12+12+18
07+07+07+07 07+07+07+09 07+07+07+12 07+07+07+18 07+07+09+09 07+07+09+12 07+07+09+18 07+07+12+12 07+07+12+18 07+09+09+09 07+09+09+12 07+09+09+18 07+09+12+12 09+09+09+09 09+09+09+12 09+09+09+18 09+09+12+12
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
INDOOR / OUTDOOR CORRESPONDENCE TABLE
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU). MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
3
Page 4
07
09
12
18
07+07
07+09
07+12
07+18
09+09
09+12
09+18
12+12
12+18
18+18
07+07+07
07+07+09
07+07+12
07+07+18
07+09+09
07+09+12
07+09+18
07+12+12
07+12+18
07+18+18
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
3.47
4.17
6.67
10.65
7.13
7.50
10.56
14.31
8.80
12.64
17.31
18.33
18.33
18.33
10.19
11.25
13.80
13.80
12.96
13.80
13.80
13.80
13.80
13.80
3.79
4.55
7.27
11.62
7.78
8.18
11.52
15.61
9.60
13.79
18.89
20.00
20.00
20.00
11.11
12.27
15.05
15.05
14.14
15.05
15.05
15.05
15.05
15.05
2.2
(0.9-2.7)
2.8
(0.9-3.2)
4.0
(0.9-4.5)
5.0
(0.9-5.4)
4.4
(1.8-5.4)
5.0
(1.8-5.8)
6.2
(1.8-6.6)
7.2
(1.8-7.7)
5.6
(1.8-6.2)
6.8
(1.8-7.3)
7.8
(1.8-8.5)
8.0
(1.8-8.8)
8.0
(1.8-8.8)
8.0
(1.8-8.8)
6.6
(2.4-8.1)
7.2
(2.4-8.6)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
7.8
(2.4-8.9)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
0.75
(0.26-0.93)
0.90
(0.26-1.04)
1.44
(0.26-1.70)
2.30
(0.26-2.98)
1.54
(0.58-1.96)
1.62
(0.58-2.05)
2.28
(0.58-2.51)
3.09
(0.58-3.65)
1.90
(0.58-2.18)
2.73
(0.58-3.22)
3.74
(0.58-4.56)
3.96
(0.58-4.90)
3.96
(0.58-4.90)
3.96
(0.58-4.90)
2.20
(0.70-3.65)
2.43
(0.70-4.11)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.80
(0.70-4.23)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.2
2.8
3.8
4.2
2.8
3.6
4.0
3.1
3.6
3.25
-
-
-
-
2.2
2.8
4.0
5.0
2.8
4.0
5.0
4.0
4.5
4.0
2.2
2.2
2.1
1.9
2.8
2.5
2.3
3.1
2.8
3.25
2.2
2.8
4.0
5.0
2.2
2.2
2.2
2.2
2.8
2.8
2.8
4.0
3.5
4.0
2.2
2.2
2.1
1.9
2.2
1.9
1.7
1.8
1.6
1.5
Indoor units combination
Unit A Unit B Unit C Unit D
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
220V 240V
NOTE: Electrical data is for outdoor unit only.
MXZ-32SV -
E1 ,
MXZ-32SV -
E2
4
INDOOR UNITS COMBINATION
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU). MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
4
Page 5
Indoor units combination
09+09+09
09+09+12
09+09+18
09+12+12
09+12+18
09+18+18
12+12+12
12+12+18
07+07+07+07
07+07+07+09
07+07+07+12
07+07+07+18
07+07+09+09
07+07+09+12
07+07+09+18
07+07+12+12
07+07+12+18
07+09+09+09
07+09+09+12
07+09+09+18
07+09+12+12
09+09+09+09
09+09+09+12
09+09+09+18
09+09+12+12
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU). MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
Unit A Unit B Unit C Unit D
2.67
2.3
2.1
2.0
1.9
1.8
2.67
2.45
2.0
1.87
1.7
1.5
1.8
1.6
1.5
1.4
1.3
1.7
1.5
1.4
1.35
2.0
1.8
1.67
1.65
2.67
2.67
2.45
1.87
1.75
1.75
1.67
1.65
Cooling capacity (kW)
2.67
2.3
2.1
3.0
2.7
3.1
2.0
1.7
1.5
1.8
1.6
1.5
1.4
1.3
2.1
1.9
2.0
1.8
3.4
3.8
3.0
3.4
3.1
2.67
3.1
2.0
1.87
1.7
1.5
2.2
2.0
1.8
2.6
2.4
2.1
1.9
1.75
2.45
2.0
1.8
1.67
2.35
-
-
-
-
-
-
-
-
2.0
2.4
2.9
3.5
2.2
2.8
3.2
2.6
3.0
2.1
2.7
3.1
2.45
2.0
2.6
3.0
2.35
Total
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.4-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
8.0
(2.8-9.0)
NOTE: Electrical data is for outdoor unit only.
Outdoor unit
power consumption
(kW)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.70-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
2.98
(0.80-4.27)
Current
(A)
220V 240V
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.80
15.05
13.08
15.05
13.08
15.05
13.08
15.05
Power
factor
(%)
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
5
Page 6
NOTE: Electrical data is for outdoor unit only.
07
09
12
18
07+07
07+09
07+12
07+18
09+09
09+12
09+18
12+12
12+18
18+18
07+07+07
07+07+09
07+07+12
07+07+18
07+09+09
07+09+12
07+09+18
07+12+12
07+12+18
07+18+18
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
5.23
6.11
8.84
10.65
8.94
9.49
11.81
12.41
10.88
12.13
12.87
12.87
12.87
12.87
11.20
11.57
12.87
12.87
12.87
12.87
12.87
12.87
12.87
12.87
5.71
6.67
9.65
11.62
9.75
10.35
12.88
13.54
11.87
13.23
14.04
14.04
14.04
14.04
12.22
12.63
14.04
14.04
14.04
14.04
14.04
14.04
14.04
14.04
3.2
(0.9-4.1)
4.0
(0.9-4.8)
6.0
(0.9-7.2)
7.1
(0.9-7.8)
6.4
(1.8-7.2)
7.2
(1.8-8.7)
8.6
(1.8-10.6)
9.0
(1.8-10.9)
8.0
(1.8-10.1)
8.8
(1.8-10.8)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
9.3
(1.8-11.2)
8.6
(2.1-10.6)
9.0
(2.1-11.1)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
1.13
(0.27-1.60)
1.32
(0.27-1.70)
1.91
(0.27-2.57)
2.30
(0.27-2.83)
1.93
(0.48-2.30)
2.05
(0.48-2.68)
2.55
(0.48-3.80)
2.68
(0.48-3.89)
2.35
(0.48-3.56)
2.62
(0.48-3.86)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.78
(0.48-3.98)
2.42
(0.52-3.00)
2.50
(0.52-3.30)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.87
3.5
4.5
4.9
3.3
4.25
4.6
3.65
4.05
3.8
-
-
-
-
3.2
4.0
5.4
6.2
4.0
5.3
5.95
4.65
5.0
4.65
2.87
2.75
2.4
2.2
3.3
2.8
2.6
3.65
3.4
3.8
3.2
4.0
6.0
7.1
3.2
3.2
3.2
2.8
4.0
3.5
3.35
4.65
4.3
4.65
2.87
2.75
2.4
2.2
2.7
2.25
2.1
2.0
1.85
1.7
Indoor units combination
Unit A Unit B Unit C Unit D
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
220V 240V
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU). MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
6
Page 7
Indoor units combination
09+09+09
09+09+12
09+09+18
09+12+12
09+12+18
09+18+18
12+12+12
12+12+18
07+07+07+07
07+07+07+09
07+07+07+12
07+07+07+18
07+07+09+09
07+07+09+12
07+07+09+18
07+07+12+12
07+07+12+18
07+09+09+09
07+09+09+12
07+09+09+18
07+09+12+12
09+09+09+09
09+09+09+12
09+09+09+18
09+09+12+12
Heating capacity (kW)
Unit A Unit B Unit C Unit D
3.1
2.65
2.45
2.3
2.2
2.0
3.1
2.9
2.32
2.2
1.9
1.8
2.1
1.8
1.7
1.6
1.6
1.95
1.75
1.65
1.55
2.32
2.05
1.95
1.85
3.1
2.65
2.45
3.5
3.3
3.65
3.1
2.9
2.32
2.2
1.9
1.8
2.1
1.8
1.7
1.6
1.6
2.45
2.15
2.0
1.95
2.32
2.05
1.95
1.85
3.1
4.0
4.4
3.5
3.8
3.65
3.1
3.5
2.32
2.2
1.9
1.8
2.55
2.3
2.15
3.05
2.8
2.45
2.15
2.0
2.9
2.32
2.05
1.95
2.8
-
-
-
-
-
-
-
-
2.32
2.7
3.6
3.9
2.55
3.4
3.75
3.05
3.3
2.45
3.25
3.65
2.9
2.32
3.15
3.45
2.8
Total
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.1-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
9.3
(2.8-11.6)
NOTE: Electrical data is for outdoor unit only.
Outdoor unit
power consumption
(kW)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.52-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
2.78
(0.60-3.50)
Current
(A)
220V 240V
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
12.87
14.04
Power
factor
(%)
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
NOTE: SLH-1AR is equivalent to class 09 (9000BTU).
MCFH-13NV, SEH-1.6AR, SLH-1.6AR is equivalent to class 12 (12000BTU). MCFH-18NV, SEH-2AR,SLH-2AR is equivalent to class 18 (18000BTU).
7
Page 8
5
Outdoor model
Indoor units number Indoor units total capacity (Connectable) indoor units total capacity (Simultaneous operation) Piping total length Connecting pipe length Height difference (Indoor ~ Outdoor) Height difference (Indoor ~ Indoor) Function Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Crankcase heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level (Hi) Fan speed (Hi) Fan speed regulator Refrigerant filling capacity(R-22) Refrigerating oil (Model) Thermistor RT61 Thermistor RT62 Thermistor RT63 Thermistor RT65 Thermistor RT66,67 Thermistor RT68,69
kW
R/h
K /h
A A
W
A(kW)
W %
A A A
W
"
  
"
mm
kg
dB
rpm
kg
cc k" k" k" k" k" k"
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity System
Coefficient of performance(C.O.P)
Outdoor unit power supply
MXZ-32SV -
E1
,
MXZ-32SV - E2
Single phase
220-240V,50Hz
2 to 4 Total model name 42 Total model name 42
Max. 60 Max. 25
10 10
2400-2640
25
— —
90.0
15.05-13.80
0.6
THV-247FBA (ROTARY)
2100
U-V 0.61
V-W 0.61 W-U 0.61
RA6V60-BA WHT-BLK 78.7 BLK-YLW 26.9 YLW-BLU 11.7 BLU-RED 83.6
900o900o320 (+35)
79
630-675
3
3.9
870 (MS-56)
13.4 (at 100:)
10.0 (at 25:)
17.0 (at 50:)
10.0 (at 25:)
10.0 (at 25:)
10.0 (at 25:)
Cooling
8.0 (0.9~9.0) —
15.05-13.80
2980(260~4270)
15.71-14.35
2.68
45-47
Heating
9.3 (0.9~11.6) —
14.04-12.87
2780(270~3500)
13.44-12.27
3.35
46-48
1 Electrical data is for only outdoor unit.
TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
SPECIFICATION
HEATING INDOOR DB20.0°C
OUTDOOR DB35.0°C WB24.0°C OUTDOOR DB 7.0°C WB 6.0°C
8
Page 9
NOISE CRITERIA CURVES6
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35: WB24: Heating :DB 7: WB 6:
COOL(220V)
NOTCH
COOL(240V)
HEAT(220V) HEAT(240V)
45
SPL(dB(A))
47 46
48
LINE
MXZ-32SV -
E1
MXZ-32SV - E2
9
Page 10
7
OUTLINES AND DIMENSIONS
OUTDOOR UNIT
MXZ-32SV ­MXZ-32SV -
Handle for moving
E1 E2
Less than
25
Veranda
Base bolt length
Base
Rubber cushion
Air in
Air in
10 35320
23
Unit: mm
200 200
Air in
460
33
317
500 Air in
Air out
2-12 36 Oval hole
(Base bolt M10)
900
2-U-shape notched holes
(Base bolt M10)
(16) (16)
27 40
387
355
[
9.52 (flared) 3/8 (C , D unit)
12.7 (flared) 1/2 (A , B unit)
[
Indoor and outdoor connect wiring 2345 hole
50
23
350.0
480.8
900
531.3
Liquid pipe
[
6.35 (flared) 1/4
88
D unit connection C unit connection
B unit connection A unit connection
1.Installation space
Note : Leave front and both sides clearance fully.
Note : Leave front and overhead clearance fully.
Note : Leave front, overhead and both clearance fully.
More than
100
More than
500
More than 100
More than
200
More than 350
More than
500
Note : Obstacles on front and rear side only
The unit can be used by attaching an optional outdoor outlet guide (MAC-855SG) (but both sides and the top are open).
2.Service space
More than
100
More than
350
More than 350
More than
100
Service space
More than
500
10
Page 11
8
POWER SUPPLY ~/N 220-240V 50Hz
INDOOR UNIT (A)
CIRCUIT BREAKER
TB2
TB3
BLU RED
TB4
X64
GRN/YLW
GRN
CN720
CN601
0
4
X64
LD62
CN913
CN791
CN901
6 4
2
CN902
CN851 CN852
MF61
21S4
1 2
2 1
2 1
1 2
1 2
3 4
1 2 3 4 5 6
1 2 3 4 5 6 7
1 2 3 4 5 6
C65
LD63
LD64
LDB
LDB
LD61
LDE
L61
F911
SSR61
X63
X62
X61
1
6
L N
3
N
INDOOR UNIT (B)
BLU ORN
CN602
1 2
3
3
3
N
INDOOR UNIT (C)
BLU YLW
CN603
1 2
N
INDOOR UNIT (D)
BLU BRN
CN604
1 2
N
BLK
BRN
GRY
BLK
BLK
WHT
YLW
RED
RED
RED
BRN
BLU
ORN
YLW
WHT
ORN
WHT
BLK
BLU
YLW
RED
ORN
ORN
RED
RED
YLW
YLW
BLK
BLK
ORN ORN
BRN GRY
X65
X66
X67
63H2
CN552
CN553
BLK
RELAY
P.C. BOARD
WHT
WHT
RED
WHT
V
U W
A
K
L
WHT
NOISE FILTER P.C.BOARD
RED
DS61
DS62
C61
CT
61
C63 C62
+
+
-
+-+
-
-
BLKREDR
BLU
LEV A
CN792
1 2 3 4 5 6
RED
BRN
BLU
ORN
YLW
WHT
LEV B
CN793
1 2 3 4 5 6
RED
BRN
BLU
ORN
YLW
WHT
LEV C
CN794 CN722 CN663
63H1 RT63
1 2 3 4 5 6
CN662
1 2 3 4 5 6 7 81 2 1 23 4
RED
RED
RED
BLK
BLK
RT66 RT68
RT67 RT69
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
CN661
CN705
7 6 5 4 3 2 1
CN515
1 2 3 4
4 3 2 1
CN801
CN501
TAB62
TAB63
T801
CT62
TAB66
TAB65
TAB64
I.P.M P.C. BOARD
F801
(1A)
CN704
CN514
CN554CN551
1 2 3 4 5 6 7 8
RT62
RT61
RT65
GRY
GRY
BLK
BLK
GRY
GRY
BRN
BLU
ORN
YLW
WHT
LEV D
ELECTRONIC CONTROL P.C. BOARD
MC
PE
(1A)
FROM INDOOR UNIT
CONNECTING 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61 DS62
F801 F911
L
L61
SYMBOL LEV A~D
MC
MF61
R RT61 RT62 RT63 RT65
RT66,67 RT68,69
NAME POWER FACTOR CAPACITOR SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR CURRENT TRANSFORMER DIODE MODULE DIODE STACK FUSE (1A) FUSE (1A) REACTOR COMMON MODE CHOKE COIL
NAME EXPANSION VALVE COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) RESISTOR DISCHARGE TEMPERATURE THERMISTOR DEFROST TEMPERATURE THERMISTOR EVAPORATION TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR GAS PIPE TEMPERATURE THERMISTOR GAS PIPE TEMPERATURE THERMISTOR
SYMBOL
SSR61
T801
TB2,3,4
X61,62,63
X64,65 X66,67
21S4 63H1 63H2
NAME SOLENOID COIL RELAY TRANSFORMER TERMINAL BLOCK FAN MOTOR RELAY RELAY RELAY R.V. COIL HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block : Connector
POWER SUPPLY ~/N 220-240V 50Hz
INDOOR UNIT (A)
CIRCUIT BREAKER
TB1
TB2
BLU RED
X64
GRN/YLW
GRN
CN720
CN601
0
4
X64
LD62
CN913
CN791
CN901
6 4
2
CN902
CN851 CN852
MF61
21S4
1 2
2 1
2 1
1 2
1 2
3 4
1 2 3 4 5 6
1 2 3 4 5 6 7
1 2 3 4 5 6
C65
LD63
LD64
LDB
LDB
LD61
LDE
L61
F911
SSR61
X63
X62
X61
1
6
L N
3
N
INDOOR UNIT (B)
BLU ORN
CN602
1 2
3
3
3
N
INDOOR UNIT (C)
BLU YLW
CN603
1 2
N
INDOOR UNIT (D)
BLU BRN
CN604
1 2
N
BLK
BRN
GRY
BLK
BLK
WHT
YLW
RED
RED
RED
BRN
BLU
ORN
YLW
WHT
ORN
WHT
BLK
BLU
YLW
RED
ORN
ORN
RED
RED
YLW
YLW
BLK
BLK
ORN ORN
BRN GRY
X65
X66
X67
63H2
CN552
CN553
BLK
RELAY
P.C. BOARD
WHT
WHT
RED
WHT
V
U W
A
K
L
WHT
NOISE FILTER P.C.BOARD
RED
DS61
DS62
C61
CT
61
C63 C62
+
+
-
+-+
-
-
BLK
RED
R
BLU
LEV A
CN792
1 2 3 4 5 6
RED
BRN
BLU
ORN
YLW
WHT
LEV B
CN793
1 2 3 4 5 6
RED
BRN
BLU
ORN
YLW
WHT
LEV C
CN794 CN722 CN663
63H1 RT63
1 2 3 4 5 6
CN662
1 2 3 4 5 6 7 81 2 1 23 4
RED
RED
RED
BLK
BLK
RT66 RT68
RT67 RT69
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
CN661
CN705
7 6 5 4 3 2 1
CN515
1 2 3 4
4 3 2 1
CN801
CN501
TAB62
TAB63
T801
CT62
TAB66
TAB65
TAB64
I.P.M P.C. BOARD
F801
(1A)
CN704
CN514
CN554CN551
1 2 3 4 5 6 7 8
RT62
RT61
RT65
GRY
GRY
BLK
BLK
GRY
GRY
BRN
BLU
ORN
YLW
WHT
LEV D
ELECTRONIC CONTROL P.C. BOARD
MC
PE
(1A)
FROM INDOOR UNIT
CONNECTING 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61 DS62 F801
F911
L
L61
LEV A~D
SYMBOL
MC
MF61
R RT61 RT62 RT63 RT65
RT66,67 RT68,69
SSR61
T801
NAME POWER FACTOR CAPACITOR SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR CURRENT TRANSFORMER DIODE MODULE DIODE STACK FUSE (1A) FUSE (1A) REACTOR COMMON MODE CHOKE COIL EXPANSION VALVE
NAME COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) RESISTOR DISCHARGE TEMPERATURE THERMISTOR DEFROST TEMPERATURE THERMISTOR EVAPORATION TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR GAS PIPE TEMPERATURE THERMISTOR GAS PIPE TEMPERATURE THERMISTOR SOLENOID COIL RELAY TRANSFORMER
SYMBOL
TB1,2,3,4,5
X61,62,63
X64,65 X66,67
21S4 63H1 63H2
F912
NR63
NAME TERMINAL BLOCK FAN MOTOR RELAY RELAY RELAY R.V. COIL HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH FUSE(3.15A) VARISTOR
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block : Connector
TB3
TB4
TB5
(3.15A)
N
LD65
F912
NR63
SG79Y085H01
WIRING DIAGRAM
OUTDOOR UNIT
MODEL MXZ-32SV-
MODEL MXZ-32SV-
E1
E2
11
Page 12
9
a
b
c
d
Outdoor unit
Indoor units
H
H
H
Indoor unit
D
Ball valve with
service port
Ball valve with
service port
Distributor
Strainer
Strainer
LEV
Oil
separator
Compressor
High pressure switch 1
Accumulator
Capillary tube
Reversing valve
Discharge temperature thermistor
Evaporation temperature thermistor (RT67)
Defrost thermistor
Strainer
Distributor
Outdoor heat exchanger
High pressure switch 2
Unit D gas pipe temperature thermistor
[9.52
Indoor unit
C
Unit C gas pipe temperature thermistor
[9.52
[6
Indoor unit
B
Unit B gas pipe temperature thermistor
[12
Indoor unit
A
Indoor unit
A
Strainer
LEV
[6
Indoor unit
B
Strainer
LEV
[6
Indoor unit
C
Strainer
LEV
[6
Indoor unit
D
Unit A gas pipe temperature thermistor
[12
[16
[16
[9.52
[16
Capillary tube
[2.0[0.6 750
[2.5 [0.61000
Capillary tube
[4.0[2.4 400
Capillary tube
Capillary tube
Capillary tube
Capillary tube
[3.0[2.0 200
[3.0[2.0 200
[3.0[2.0 200
[3.0[2.0 200
Refrigerant flow in cooling Refrigerant flow in heating
Reversing valve coil heating ON cooling OFF
REFRIGERANT SYSTEM DIAGRAM
MXZ-32SV ­MXZ-32SV -
E1 E2
Unit:mm
Piping length each indoor unit (a, b, c, d) 25m Total piping length (a+b+c+d) 60m Height difference between units (H) 10m Bending point for each unit 25 Total bending point 60
It does not matter which unit is higher.
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
tables below.
For further information on Different-diameter pipe,see page BACK COVER.
Indoor unit
class Pipe diameter
07/09
12(13)
18
Liquid 6.35(1/4) Liquid 6.35(1/4)
Gas 9.52(3/8) Gas 9.52(3/8)
Liquid 6.35(1/4) Liquid 6.35(1/4)
Gas 12.7(1/2) Gas 12.7(1/2)
Liquid 6.35(1/4) Liquid 6.35(1/4)
Gas 15.88(5/8) Gas 15.88(5/8)
Extension pipe diameter
12
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
Liquid 6.35(1/4)
Gas 12.7(1/2)
Liquid 6.35(1/4)
Gas 12.7(1/2)
Liquid 6.35(1/4)
Gas 9.52(3/8)
Liquid 6.35(1/4)
Gas 9.52(3/8)
Unit : mm (inch)
Page 13
10
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
07 class
7.5
7.0
6.4
5.9
5.3
4.8
8.7
8.1
7.4
6.8
6.2
5.6
10.8
10.1
9.3
8.5
7.7
7.0
6.7
6.2
5.8
5.3
4.8
4.3
18 class
12 class
09 class
32.3
29.8
27.3
24.9
22.4
19.9
17.4
14.9
38.2
35.3
32.4
29.4
26.5
23.5
20.6
17.6
25.9
23.9
21.9
19.9
17.9
15.9
13.9
11.9
27.7
25.6
23.4
21.3
19.2
17.0
14.9
12.8
07 class
09 class
12 class
18 class
PERFORMANCE CURVES
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB
}
Cooling
(4) Total input: W (5) Indoor intake air dry-bulb temperature : °CDB (6) Outdoor intake air wet-bulb temperature : °CWB (7) Total input : W
}
Heating
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT OUTDOOR UNIT
10-1-1.CAPACITY AND THE INPUT CURVES
13
Page 14
10-3-.2.Capacity and input correction by inverter output frequency
0 50 100 150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<HEAT>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<HEAT>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<HEAT>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
2.0
Frequency
<COOL>Total input
Hz
0 50 100 150
0.5
1.0
1.5
<HEAT>Capacity
Frequency
Hz
0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
1. 07-class unit in single operation
2. 09-class unit in single operation
3. 12-class unit in single operation
4. 18-class unit in single operation
(OUTDOOR UNIT:MXZ-32SV)
The dotted line on graphs connects the frequency range in normal operation shown by the full line and the frequency in test run shown by the point.
14
Page 15
0 5 10 15 20 25
4
5
6
7
8
9
10
Ambient temperature(:)
45Hz
Outdoor unit current (A)
Ambient temperature(:)/ Ambient humidity(%)
Ambient temperature(:)/ Ambient humidity(%)
Outdoor low pressure
(MPa•Gauge)
(kgf/F•Gauge)
Outdoor unit current (A)
15
20 25
30
35
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(;) (%)
33Hz
15 20 25 30
35
3
4
5
6
7
8
9
(;) (%)
33Hz
8
7
6
5
4
3
2
10-3-4.Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/
(1) COOL operation
1Both indoor and outdoor units are under the same temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 33Hz
ff
• G)
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation, press emergency run ON/OFF button or any button on remote controller.
(2) HEAT operation
➁ ➂
Indoor Outdoor
Set air flow to Hi speed. Inverter output frequency is 45Hz.
DB(°C) 20.0
WB(°C) 14.5
DB(°C) 2 7 15 20.0 WB(°C) 1 6 12 14.5
15
Page 16
2. 09-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 33Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(kgf/F•Gauge)
8
7
6
5
4
(MPa•Gauge)
0.8
0.7
0.6
0.5
0.4
Outdoor low pressure
3
0.3
2
0.2 15
Ambient temperature(:)/ Ambient humidity(%)
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
DB(°C) 20.0
WB(°C) 14.5
20 25
WB(°C) 1 6 12 14.5
33Hz
Outdoor unit current (A)
(;)
35
30
DB(°C) 2 7 15 20.0
(%)
9
8
7
6
33Hz
5
4
3
15 20 25 30
Ambient temperature(:)/ Ambient humidity(%)
35
(;) (%)
16
10
9
45Hz
8
7
6
Outdoor unit current (A)
5
4
0 5 10 15 20 25
Ambient temperature(:)
Page 17
3. 12-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 33Hz
(kgf/F•Gauge)
8
(MPa•Gauge)
0.8
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation, press emergency run ON/OFF button or any button on remote controller.
9
0.7
7
0.6
6
0.5
5
0.4
4
Outdoor low pressure
3
0.3
2
0.2 15
Ambient temperature(:)/ Ambient humidity(%)
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
DB(°C) 20.0
WB(°C) 14.5
20 25
DB(°C) 2 7 15 20.0 WB(°C) 1 6 12 14.5
33Hz
30
35
(;)
(%)
8
7
6
5
33Hz
Outdoor unit current (A)
4
3
15 20 25 30
Ambient temperature(:)/ Ambient humidity(%)
35
10
(;) (%)
17
9
45Hz
8
7
6
Outdoor unit current (A)
5
4
0 5 10 15 20 25
Ambient temperature(:)
Page 18
4. 18-class unit in single operation
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
Both indoor and outdoor units are under the same temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
Air flow speed : HI
Inverter output frequency : 33Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at rated frequency.
4.Indoor fan runs at HI speed.
5.To cancel this operation, press emergency run ON/OFF button or any button on remote controller.
(kgf/F•Gauge)
(MPa•Gauge)
0.8
8
0.7
7
0.6
6
0.5
5
0.4
4
Outdoor low pressure
3
0.3
2
0.2 15
Ambient temperature(:)/ Ambient humidity(%)
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 45Hz.
DB(°C) 20.0
WB(°C) 14.5
20 25
DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
33Hz
30
35
(;) (%)
9
8
7
6
5
33Hz
Outdoor unit current (A)
4
3
15 20 25 30
Ambient temperature(:)/ Ambient humidity(%)
35
10
(;) (%)
18
9
8
45Hz
7
6
Outdoor unit current (A)
5
4
0 5 10 15 20 25
Ambient temperature(:)
Page 19
11
Compressor power factor
Indoor unit microprocessor
SSR61
Drive
circuit
Transistor
module
Indoor Unit
A
Indoor Unit
D
Indoor Unit
C
Indoor Unit
B
Gas pipe temperature thermistor RT66, 67, 68, 69
Accumulator
Comp.
H.P.S 63H2
Discharge temperature thermistor RT61
Indoor Unit
A
Evaporation temperature thermistor RT63
Outdoor fan motor MF61
x 61 x 62 x 63
Defrost thermistor RT62
LEV1
LEV2
LEV3
LEV4
Indoor Unit
B
Indoor Unit
C
Indoor Unit
D
Outdoor unit control microprocessor
Compressor primary current
Compressor secondary current
Fin temperature thermistor RT65
R. V. coil 21S4
H.P.S 63H1
Input signal
Output signal
MICROPROCESSOR CONTROL
INVERTER MULTI SYSTEM CONTROL MXZ-32SV -
MXZ-32SV -
E1 E2
19
Page 20
11-1.LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
Indoor unit status Stop of all indoor unit
Opening before stop 500 pulse in 15 minutes
When outdoor unit is operating, some indoor unit stops and some operates.
Thermostat OFF in
COOL or DRY mode
When the outdoor unit operation (When the other indoor unit operates): 5 pulse. When outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency: Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205
Thermostat ON in
COOL or DRY mode
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, adjustment in accordance with intake superheat, discharge temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are different. See 11-2 Operational frequency range (As far as the indoor unit velocity control goes, refer to DRY operation in MICROPROCESSOR CONTROL in the indoor unit service manual.)
• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
Thermostat OFF in HEAT mode
• When the outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes.
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based
Thermostat ON in HEAT mode
on the operation frequency: Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, opening becomes the one that adjustment in accordance with discharge temperature was added to basic opening. w1
w1 LEV opening when the outdoor is unit operating: Upper limit 500, Lower limit 59
LEV opening
COOL : 5 pulse (fully closed) HEAT : 59 pulse (slightly opened)
Determination of LEV standard opening in each indoor unit
• The standard opening is on the straight line, which connects each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below. (LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
• Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.
• Add opening provided in Difference in Operation number in the table below to determined LEV opening for each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse. < Calculation example of LEV opening > Cool operation: Compressor frequency 70Hz: 2 unit ON: 18class (170-150)p(80-60)o(70-60)+150+75-30=205 pulse
Standard opening
1 2 3 4 5 6 7 8
220 210 200 190 180 170 160 150 140
LEV opening (Pulse)
130 120
7 20 40 60 80 100 120 140
COOL
HEAT
Operation frequency of compressor (Hz) : F
20
Page 21
(1) LEV opening correction by suction superheat (COOL, DRY)
1 Suction superheat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)
w 1 Perform this, when number of operation units is 2 units or more w 2 When the correction opening of suction superheat is 0, correct the LEV opening by discharge temperature.
3 Discharge temperature
COOL DRY HEAT
-
w 2
w 2
<Correction>
(Suction superheat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY, correct the LEV openings corrected from the table below
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units or more) (a) Correction by the separate superheat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator temperature thermistor. 1 Calculate each superheat of the unit from the expression below;
(Superheat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)
2 Select minimum superheat from among them. 3 Each LEV opening is corrected by difference between each superheat and minimum superheat.
21
Page 22
(3) LEV opening correction by discharge temperature
DRY
Min. Max. Rated Min. Max.
Defrost
Rated
Note: When the fan speed of indoor unit is totally Lo notch, restrict the maximum frequency is restricted in 6/7 of the rated frequency.
DRY COOL
COOL
HEAT
Number of
operating
unit
1 2 3 4 2 3 4 5 6 7 8 3 4 5 6 7 8 9 4 5 6 7 8 9
10
18
20
30
40
40 52 68 85
80
105
110
120
120
24 33 46 82
70 80
90
93
101
25
40
58
58
18
20
30
40
62 70 80 86
90 90
110
120
120
62 70 80 86
95
100
100
100
100
36 49 65 80
80 88
100
108
108
1
2
3
4
1 2 1 1 2 3
1 2 2 3 1 1
8/10 of maximum frequency 9/10 of maximum frequency 7/10 of maximum frequency
Maximum frequency
capacity
cord
When LEV correction output is 0 pulse by the suction superheat at cool or dry operation, or dry operating, correct LEV is cor­rected according to the following table.
The target discharge temperature is determined according to frequency zone and number of operation unit of the compressor.
Correct the LEV opening according to difference between the target discharge temperature and discharge temperature.
11-2.Operational frequency range
22
Page 23
11-3.Heat defrosting control
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is -3; or less.
2.When specified non-defrosting time is counted in the control P.C.board.
(Total time of compressor operating) Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds. Indoor fan is off. Defrosting lamp lights.
2.4-way valve reverses flow. Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 8; or more.
2. When it has spent 10 minutes for defrosting. Defrosting finishes at condition of 1 or 2.
11-4.High or low pressure protection
(1) High pressure protection control on heat mode
Temperature of the main pipe temp. thermistor in the indoor unit controls the operation frequency. When temperature of the main pipe temp. thermistor is approx. 49;, the operation frequency is set at the current level. When temperature of the main pipe temp. thermistor is approx. 52; the protection control decreases the frequency at the
speed of 3Hz a minutes. When temperature of the main pipe temp. thermistor is approx. 57; the protection decreases the frequency at the speed of
4Hz a minute and changes the outdoor fan to Low.
Note: Temperature of the pipe temp. thermistor is different depending on the indoor unit.
Temperature of the pipe temp. thermistor is 45; or less, the protection control is released.
(2) High pressure protection control by high pressure switch (H.P.S)
High-pressure switch controls the operation frequency and outdoor fan motor. <Control status> When high-pressure switch is ON. (When discharge pipe pressure is 2.75 MPa or more.) <Control details> (a) When cooling or drying
The protection control decreases the compressor frequency at the speed of 10Hz a minute. (The compressor operates continuously in min. frequency according to a command to decrease more than the min. level.)
(b) When heating
The protection control decreases the compressor frequency at the speed of 10Hz a minute.
The protection control changes the outdoor fan to Low. <Release status> When high-pressure switch is OFF. (When discharge pipe pressure is 2.35 MPa or more.) Or, the compressor stops.
11-5.Discharge temperature protection control
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp. thermistor.
(1) Compressor ON/OFF When temperature of the discharge temp. thermistor exceeds 116;, the control stops the compressor.
When temperature of the discharge temp. thermistor is 80; or less, the controls starts the compressor. (2) Compressor operation frequency
When temperature of the discharge temp. thermistor is expected to be higher than 116;, the control decreases 12Hz from the
current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 111; and less than 116;, the control
decreases 6Hz from the current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 104; and less than 111;, the control is set
at the current frequency.
23
Page 24
11-6.Refrigerant recovery control on heating
<Control status>
The control performs when the following status are satisfied everything;
• When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF)
• When discharge temperature becomes 107; or more.
• When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.
<Control details>
LEV opening, which adjusts to not operating indoor unit, is considered to be 80 pulse.
<Control finish status>
The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.
• When it passed 60 seconds since the control has started.
• When the discharge temperature is 90; or less.
11-7.Outdoor fan control
Fan speed is switched according to a number of operating indoor unit and the compressor frequency.
Note
•When operation, fan speed of Hi/ Low mode changes to VHi/ Hi mode by promoting those fan speeds respectively by 1 step after defrosting is operated. This control is cleared, when the compressor off.
•When overheat protection of P.C. board temperature or fin temperature operates, the outdoor fan speed is fixed to VHi mode regardless of compressor frequency. Also, when the overheat protection is cleared, the fan speed is back to normal
•When the indoor coil thermistor is 57; or more on HEAT operation, fan speed is fixed to Low notch . Or, the indoor coil thermistor is 45; or less on HEAT operation, fan speed is back to normal.
11-8.Relation between main sensor and actuator
Relation between main sensor and actuator.
24
Page 25
12 TROUBLESHOOTING
Lead wiring
Housing point
Operation start
Check the outdoor unit LED indicator
A Check of power supply on page 29.
• Indoor unit serial signal error B Check of serial signal on page 29.
• Cool or HEAT operation only C Check of R.V.coil on page 30.
• When cooling, room does not cool. E Check of inverter, compressor on page 31.
• When cooling, heat exchanger of non-operating indoor unit frosts.
•When heating, non operating indoor unit gets warm. D Check of LEV on page 31.
• When cooling, dew drops in the non-operating indoor unit Check of mis­piping.
• When heating, room does not get warm. E Check of inverter, compressor on page 31. Check mis-piping. Shortage of capacity
Refer to indicator list on page 26 and 27.
OFF
"00"
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit. Then, check the outdoor unit with referring to this page.
Display other than "00"
12-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after con­firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the electronic con­trol P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on this page and the check table on page 26 and 27.
12-2. Instruction of troubleshooting
25
Page 26
12-3. Troubleshooting check table
Note . LED indicates "00" in the normal status.
7-segment LED display
00
If there is defect in the following parts(electronic control P.C. board, relay P.C. board, high pressure switches(63H1,63H2),indoor /outdoor fan motor , or indoor coil thermistor), the compressor may stop even with the display remained at “ 00 “.In any case, reset the breaker and check the above-stated parts.
Symptom Outdoor unit does not operate.
Display Detecting method Detecting method Check points
aa44
(A4)
Outdoor power system abnor­mality
When the compressor operation has been interrupted by overcurrent protection continuously three times within 1 minute after start-up, the compressor stops operation.
Error mode
Normal
• Inverter output
• Compressor
aa33
(A3)
(P1)
Symptom Outdoor unit stops and restarts every 3 minutes.
Display Detecting method Detecting method Check points
ee99
(E9)
ee66
(E6)
ff88
(F8)
aa88
Outdoor electronic control P.C. board abnormality
Indoor unit and LEV abnor-
pp11
mality
Evaporation temperature ther­mistor abnormality
Discharge temperature ther­mistor abnormality
Fin temperature thermistor abnormality
Overcurrent protection
(A8)
dd66
(d6)
dd44
(d4)
Discharge temperature over­heat protection
Fin temperature overheat pro­tection
dd77
High pressure protection
(d7)
ff55
(F5)
ff66
(F6)
(F7)
pp99
(P9)
Room-A gas pipe temperature thermistor abnormality
Room-B gas pipe temperature thermistor abnormality
Room-C gas pipe temperature
ff77
thermistor abnormality
Room-D gas pipe temperature thermistor abnormality
When the nonvolatile memory data cannot be read properly on the out­door controller board
When the drain abnormality is detected in the indoor unit and the indoor main coil temperature is too low, or when any abnormality is detected in the components of indoor unit
The compressor stops when a short or open circuit occurs in the evap­oration temperature thermistor during compressor running.
The compressor stops when a short or open circuit occurs in the dis­charge temperature thermistor during compressor running.
The compressor stops when a short or open circuit occurs in the fin tem­perature thermistor during compressor running.
When over current is applied to the power module, the compressor stops and restarts in 3 minutes.
When the discharge temperature thermistor detects 116˚C or above, the compressor stops and restarts operation in 3 minutes. (Protection will be released at 100; or below.)
When the fin temperature thermistor detects 89˚C or above, the com­pressor stops and restarts operation in 3 minutes.
When the compressor starts, primary current or output voltage stops the compressor and restarts in 3 minutes.
When a short or open circuit occurs in the Room-A gas pipe temperature thermistor.
When a short or open circuit occurs in the Room-B gas pipe temperature thermistor.
When a short or open circuit occurs in the Room-C gas pipe temperature thermistor.
When a short or open circuit occurs in the Room-D gas pipe temperature thermistor.
• Outdoor electronic control P.C. board
• Check the abnormality indication on the indoor unit.
• LEV
• Check the characteristic of the evapora­tion temperature thermistor. Refer to
on page 32.
• Check the contact of P.C. board connec­tors.
• Check the characteristic of the discharge temperature thermistor. Refer to FFon page 32.
• Check the contact of P.C. board connec­tors.
• Check the characteristic of the fin temper­ature thermistor. Refer toFFon page 32.
• Check the contact of P.C. board connec­tors.
• Check the inverter and compressor. Refer to EEon page 31.
• Check the amount of gas.
• Check the indoor/outdoor air flow for short cycle.
• Check the indoor unit air filter for clogging.
• Check the amount of gas and the refriger­ant cycle.
• Check the outdoor unit air passage.
• Check the outdoor unit air passage.
• Check the power module.
• Check the outdoor fan motor. Refer to on page 32.
• Amount of gas
• Outdoor unit air passage.
• Check the ball valve.
• Room Agas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
• Room B gas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
• Room C gas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
• Room D gas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
FF
GG
26
Page 27
Symptom Outdoor unit operates. (The compressor operates at reduced frequency.)
Display Detecting method Detecting method Check points
dd88
(d8)
dd99
(d9)
dd77
(d7)
dd66
(d6)
dd33
(d3)
(d1)
Symptom Outdoor unit operates.
Display Detecting method Detecting method Check points
Frequency drop by current protection
Frequency drop by overload protection
Frequency drop by high pres­sure protection
Frequency drop by defrosting in cooling
Frequency drop by discharge temperature protection
Frequency drop by high pres­sure switch protection
Low discharge temperature
dd11
protection
ee77
Defrost thermistor abnormality
(E7)
When the outdoor unit input current exceeds 22.5 A, the compressor operates at reduced frequency.
When the compressor load exceeds the specified value, the compres­sor operates at reduced frequency.
When indoor pipe temperature exceeds 55˚C during heating, the com­pressor operates at reduced frequency.
When the indoor pipe temperature falls to 6˚C or below during cooling, the compressor operates at reduced frequency.
When the discharge temperature exceeds 110˚C, the compressor oper­ates at reduced frequency.
When the high pressure exceeds 2.75MPa (28 kgf/cm2-G), the com­pressor operates at reduced frequency. In addition, the fan speed changes.
When the state with low discharge temperature of which 50˚C in COOL and 48.4 or less in HEATfor 20 minutes, the compressor operates con­tinuously.
When a short or open circuit occurs in the defrost thermistor during heating * In this case, the compressor continues to operate.
These symptoms do not mean any abnormality of the product, but check the following points.
• Air filter clogging.
• Amount of gas.
• Short cycle of indoor/outdoor air flow.
• Amount of gas.
• Outdoor unit air passage.
Check the amount of gas.
• Replace the outdoor controller board.
• Check the contact of LEV board connec­tors.
• Defrost thermistor characteristic.
• Contact of P. C. board connectors.
hh44
(h4)
Power factor detection abnor­mality
When the compressor power factor cannot be detected * In this case, the compressor keeps running.
• Compressor wiring.
27
Page 28
W
U
V
WHT
RED
BLK
LEV
WHT
RED
YLW
BRN
ORN
BLU
12-4. Trouble criterion of main parts
WHT
Protector specification
Short Open
95I15: 135I5:
BLK
P
ORN BLU
RED YLW
Part name Check method and criterion
Defrost thermistor Evaporation / Gas pipe temperature thermistor
Discharge temperature thermistor
Compressor
Outdoor fan motor
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
Normal abnormal
5k~ 55k Opened or short-circuited
Measure the resistance using a tester, after warming up the thermistor by holding by hand. (Part temperature : 20°C ~40°C)
Normal abnormal
100k~ 250k Opened or short-circuited
Measure the resistance between terminals using a tester. (Winding temperature : -10°C ~ 40°C)
Normal abnormal
1Each phase 0.53~ 0.66 Opened or short-circuited
Measure the resistance between lead wires using a tester. (Part temperature : -10°C ~ 40°C)
WHT - BLK
BLK - YLW
YLW - BLU
RED - BLK
Normal
69.0~ 86.0
23.0~ 30.0
10.0~ 13.0
73.0~ 91.0
abnormal
Opened or short-circuited (Not including
WHT - ORN)
R. V. coil
Linear expansion valve
High pressure switch (HPS)
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
Normal abnormal
1640~ 2310 Opened or short-circuited
Measure the resistance using a tester.(Part temperature -10°C ~ 40°C)
Lead wire color Normal
Abnormal WHT - RED RED - ORN
YLW - BRN
21 ~ 26
Opened or short-circuited
BRN - BLU
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
Pressure Normal abnormal
Operation OFF HPS1 2.35 ± 0.15MPa (24 ± 1.5kg / cm2) HPS2 2.55 ± 0.2MPa (26 ± 2kg / cm2)
0.05
HPS1 2.75 MPa (28 kg / cm2) HPS2 3.43 MPa (35 kg / cm2)
+
0.1
-
0
+
-
0.15
0.5
+
1.0
-
0
+
1.5
-
Short
Other than
those list-
Open
ed at left
P Inner protector
28
Page 29
Outdoor unit does not operate. (LED display: display OFF)
AA
Check of power supply
Start
Check the connecting of main circuit parts and connectors (CN501: I.P.M P. C. board, CN 801: Electronic control P. C. board, CN554: relay P. C. board).
Turn on power supply.
Is there voltage of 220V AC - 240V AC in the power supply terminal block?
Yes
Is there voltage of 310V DC - 340V DC across the smoothing capacity?
Yes
Replace the electronic control P. C. board.
Outdoor unit does not operate. (LED display:
BB
Check of serial signal
Start
1. Check the indoor unit with referring to the indoor unit service manual.
2. Turn off the power supply of the indoor and outdoor unit and return the indoor/ outdoor unit connecting wire to former original.
3. Check the connection of indoor/ outdoor unit connecting wire in the outdoor unit terminal block, and check the connection of the connectors (CN601: unit A, CN 602: unit B, CN603: unit C, CN604: unit D) in the electronic control P. C. board.
4. Disconnect the lead wire to the compressor. Turn on the power supply (indoor/ outdoor unit) 3 minutes later, EMERGENCY OPERATION starts.
No
No
Check the power supply cable.
Is there voltage of 220V AC - 240V AC across the output cables (LD63, LD64) in the noise filter P. C. board?
Yes
Is there voltage of 220V AC - 240V AC across the input terminal part in the diode module (DS61)?
Yes
Check the main circuit parts and replace it.
0000
)
Replace the noise
No
filter P. C. board.
Replace the current
No
limiting resistor.
w When replacing, check the
connection of connector CN720 in the outdoor electronic control P. C. board.
Is there voltage of 5V DC - 10V DC between No. 3 (+) and N (-) in the outdoor terminal block?
No
Recheck a connected circumstance of the indoor/ outdoor unit connecting wire.
Yes
Replace the electronic control P. C. board.
29
Page 30
The cooling operation or heating operation does not operate. (LED display:
CC
Check of R. V. coil
• When heating operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (HEAT operation) starts.
0000
)
Is there voltage of 220V AC - 240V AC between pin1 and pin 2 at connector CN913?
Yes
Turn off power supply of indoor and outdoor unit.
Disconnect the connector CN913 in noise filter P. C. board. Is there normal resistance to R.V. coil?
Yes
Replace the 4-way valve.
• When cooling operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (COOL operation) starts.
No
Replace the R. V. coil.
No
1. Turn off power supply of indoor and outdoor unit, and disconnect the connectors (CN851, CN852) in the electronic control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (HEAT operation) starts.
Is there voltage 12V DC between the connector CN852 pin 1 (+) and pin 5 (-)?
Yes
Replace the noise filter P. C. board.
No
Replace the electronic control P. C. board.
Is there voltage of 220V AC - 240V AC between pin1 and pin 2 at connector CN913?
Yes
1. Turn off power supply of indoor and outdoor unit, and disconnect the connectors (CN851, CN852) in the electronic control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (COOL operation) starts.
Is there voltage 12V DC between the connector CN852 pin 1 (+) and CN851 pin 5 (-)? W1
Yes
Replace the electronic control P. C. board.
No
Replace the noise filter P. C. board.
W1If the connector CN913 is not connected or R. V. coil is open, voltage
occurs between terminals even when the control is OFF.
No
Replace the 4-way valve.
30
Page 31
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit get warm.
Start
0000, pp11
)
(LED display:
DD
Check of LEV
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
No
Disconnect the connectors (CN791: unit A, CN792: unit B, CN793: unit C, CN794: unit D). Is there normal resistance to LEV coil?
No
Replace the LEV coil.
Yes
Normal
Yes
Replace the electronic control P. C. board.
• When heating, room does not get warm.
• When cooling, room does not get cool. (LED display:
EE
Check of inverter/ compressor
0000, aa88
)
Start
Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
W1 • After the outdoor fan starts running, wait for 1 minutes or more before Measure the voltage between each leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Output voltage COOL: 100V(58Hz) HEAT: 100V(58Hz) Is there voltage output? W1
Yes
Is output balanced?
No
Yes
measuring the voltage.
•The output voltage values have the tolerance of i20%.
No
Is the overcurrent protection error shown on the LED monitor?
Yes
1.Turn off power supply of the indoor
No
and outdoor unit, and disconnect the connector CN 551 in the relay P. C. board.
2.Turn on power supply to the outdoor
Replace the electronic control P. C. board with the I.P.M P. C. board.
unit, and after 1 minutes or more passed, check the resistance between the connector CN551 pin 1 and pin 2.
Turn off power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals.
No
Is there resistance of 0.27" to 0.34" between the each terminals?
Yes
Return the lead wire of compressor to former, and turn on power supply to indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Replace the compressor.
0"
Check the resistance between each terminal.
After 1 minute has passed since the power supply of outdoor unit was turned off, disconnect the connector CN 553 in the relay P. C. board.
Infinite
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short 10 to 60 seconds: compressor lock 60 seconds to 5minutes: refrigerant circuit defective 5 minutes or more: normal
Replace the relay P. C. board.
31
0"
Check the resistance HPS (63H2).
Replace the HPS (63H2).
Infinite
Page 32
• When thermistor is abnormal.
FF
Check of thermistor
Start
Disconnect the connector in the electronic control P. C. board (see below table), and measure the resistance of thermistor to check whether the thermistor is normal or not.
Normal
Reconnect the connectors (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Does thermistor operate 10 minutes or more though the thermistor abnormality is not displayed?
Yes
Normal
Thermistor Defrost thermistor Discharge temperature thermistor Evaporation temperature thermistor Gas pipe temperature thermistor (Unit A) Gas pipe temperature thermistor (Unit B) Gas pipe temperature thermistor (Unit C) Gas pipe temperature thermistor (Unit D) Fin temperature thermistor
• Fan motor does not operate. Or, fan motor stops at once’after fan motor operates.
GG
Check of fan motor
Symbol
RT62 RT61 RT63 RT66 RT67 RT68 RT69 RT65
No
Replace the electronic control P. C. board.
Connector, Pin No. Between CN661 pin1 and pin2 Between CN661 pin3 and pin4 Between CN661 pin5 and pin6 Between CN662 pin1 and pin2 Between CN662 pin3 and pin4 Between CN662 pin5 and pin6 Between CN662 pin7 and pin8 Between CN663 pin1 and pin2
Abnormal
Replace the thermistor.
Start
Check the connection of fan motor connector, connectors (CN851, CN852) on electronic control P. C. board, and connectors (CN901, CN902) on noise filter P. C. board.
Disconnect the fan motor connector, and measure the resistance of the fan motor winding to check the winding characteristic.
Normal
1. Disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
2. Check the voltage between pin 2 and pin 3, pin 2 and pin 5, pin 2 and pin 6 at the fan motor connector.
Is there voltage of 220V AC - 240V AC?
No
1. Turn off power supply of the indoor and outdoor unit, and disconnect the connector (CN851, CN852).
2. Is the voltage 0V, when the voltage between CN852 pin1 (+) and CN851 pin1 (-), pin2 (-), or pin3 (-) are measured after the power supply is turned on the outdoor unit?
Yes
Is there voltage of 12V DC between CN852 pin1 (+) and pin3 (-), when power supply turns on the indoor unit and EMERGENCY OPERATION starts in three minutes?
Yes
Replace the noise filter P. C. board.
Yes
32
Abnormal
No
No
Replace the fan motor.
Replace the electronic control P. C. board.
Page 33
Infinity
0"
Yes
No
Start
1. Disconnect the connector CN722 in the electronic control P. C. board.
2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned off.
Check the resistance between each terminal?
Reconnect CN722. Turn on power supply to the indoor and outdoor unit. 3 minutes lator, EMERGENCY OPERATION starts.
Is HPS protection displayed immediately after compressor starts?
Replace HPS (63H1).
Replace the electronic control P. C. board.
Normal
• When the operation frequency does not go up from lowest frequency.
HH
Check of HPS
II
The other cases
In the case that the indoor fan and outdoor fan operate but the compressor does not operate, it causes that the high pressure switch can be operated once. First of all, check the high pressure switch can be shorted, turn OFF the power and turn ON again 1 minute later. Indoor unit dose not operate. (difference modes)
• When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in the figure below.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.
OPERATION INDICATOR
Lighting Flashing
33
Page 34
TEST POINT DIAGRAM AND VOLTAGE MXZ-32SV
-
MXZ-32SV -
,
E2E1
Electronic control P.C.board
Discharge temperature thermistor
Resistance (k)
Temperature(;)
Gas pipe temperature thermistor Evaporation temperature thermistor Defrost temperature thermistor
Resistance (k)
Discharge temperature thermistor
0.3~0.6V DC
Evaporation temperature thermistor
2.5~4.0V DC
Fin temperature thermistor
1.0~4.0V DC
Temperature(;)
12V DC
0~5V DC
{
+
-
-
-
-
-
-
-
Defrost temperature thermistor
2.5~4.0V DC
Outdoor fan ON 12V DC
Outdoor fan Lo 12V DC
R.V. coil 12V DC
-
Outdoor fan Me 12V DC
{
Serial signal Room D 5~10V DC
Resistance (k)
Temperature(;)
{
Serial signal Room C 5~10V DC
{
Serial signal Room B
5~10V DC
{
Serial signal Room A 5~10V DC
{
Relay 12V DC
{
5V DC
LED monitor indication
Room D
Room C
Room B
Room A
Gas pipe temperature thermistor 2.5~4.0V DC
34
{
High pressure switch
Liner expansion valve(LEV) 12V DC pulse wave
Page 35
Noise filter P.C.board
E1
MXZ-32SV
-
OUTDOOR FAN 220V-240V AC
{
{
220V-240V AC OUTPUT
{
220V-240V AC INPUT
REVERSING VALVE
MXZ-32SV
220V-240V AC
E2
-
OUTDOOR FAN 230V AC
{
{
{
230V AC OUTPUT
FUSE 3.15A VARISTOR
REVERSING VALVE
230V AC
{
230V AC INPUT
{
35
Page 36
I.P.M P.C.board MXZ-32SV
MXZ-32SV -
E1
-
E2
12V DC
{
12V DC
{
{
320V DC
Relay P.C.board
E1
MXZ-32SV
MXZ-32SV -
-
E2
High pressure switch
12V DC
12V DC
{
{
{
{
Short
36
Page 37
13
DISASSEMBLY INSTRUCTIONS
13-1. MXZ-32SV - , MXZ-32SV -
E2E1
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1.Removing the compressor
(1)Remove the screws of the service panel, and remove it.
Release refrigerant gas. (2)Remove the screws of the top panel, and remove it. (3)Remove the screws of the front panel, and remove it. (4)Disconnect the compressor lead wire. (TAB64,TAB65,TAB66) (5)Disconnect the ourdoor electronic control P.C. board
connectors CN791, CN792, CN793, CN794, CN662,
CN722 and CN661. Disconnect the noise filter P.C. board con-
nectors CN913.
Disconnect the fan motor connector. (6)Remove the four screws of the electrical parts, and remove
them. (7)Remove the propeller. (8)Remove the screws of the separator, and remove it. (9)Detach the brazed joints of the compressor suction and dis-
charge pipes. (See Photo 3.) (10)Remove the three compressor nuts and remove the com-
pressor.
Photo 1
Top panel
Service panel
Front panel
Photo 2
Control P.C.board
Photo 3
Electrical parts
Sepatator
Terminal
Discharge pipe brazed part
37
Suction pipe braxed part
Page 38
OPERATING PROCEDURE PHOTOS
2.Removing the fan motor
(1)Remove the top panel (five screws),the service panel (four
screws), and the front panel (two screws).
(See Photo 1.) (2)Disconnect the fan motor connector. (3)Remove the propeller. (4)Remove the fan motor.
3.Removing the 4-way valve
(1)Remove the screws of the top panel, and remove it.
(See Photo 1.)
(2)Remove the service panel, rear panel, and connect cover
panel.Recover refrigerant gas. (3)Remove the electrical parts. (See Photo 2.) (4)Detach the brazed joint of 4-way valve and pipe.
(See Photo 4.)
4.Removing the linear expansion valve
(1)Remove the service panel. (See Photo 1.)
(Gas recovery is not required if the unit is pumped down.) (2)Remove the coil of linear expansion valve. (3)Detach the brazed joint of linear expansion valve and pipe.
Photo 4
4 way valve
R. V. coil
Brazing Points
Photo 5
38
LEV coils
Linear expansion valves
Page 39
OPERATING PROCEDURE PHOTOS
5.Removing the reactor
(1)Remove the screws of the top panel, and remove it.
(See Photo 1.) (2)Disconnect the reactor lead wire. (3)Remove the screws of the reactor, and take it out.
Photo 6
Reactor
39
Page 40
14
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15
16
17 18 19 20 21 22
M21 17A 501 T2W E40 301 T2W E40 452
M21 17A 447
M21 17A 443
M21 17E 337 T2W E40 357 T2W E40 356 T2W E70 451 T2W E79 424 T2W G01 424 T2W E58 376 T2W E65 375
M21 42A 340 T2W E70 307
M21 42A 308
M21 17A 362 T2W G01 362 T2W E70 308 T2W E70 398 T2W E40 441 T2W E66 382 T2W E89 313
M21 370 378
PROPELLER FAN OUTDOOR FAN MOTOR I.P.M P.C. BOARD DIODE STACK DIODE MODULE REACTOR POWER FACTOR CAPACITOR SMOOTHING CAPACITOR ELECTRONIC CONTROL P.C. BOARD NOISE FILTER P.C. BOARD NOISE FILTER P.C. BOARD TERMINAL BLOCK TERMINAL BLOCK RELAY GAS PIPE TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR RESISTOR RESISTOR THERMISTOR SET R. V. COIL RELAY P.C. BOARD FUSE FUSE & VARISTOR SET TERMINAL BLOCK
MF61
DS62 DS61
L
C61
C62,C63
X64
RT66,67,68,69
RT65
R
RT61, 62, 63
21S4
F801, F911
F912, NR63
TB4
1 1 1 1 1 1 1 2 1 1
4 1 1 1 1 1
1 1 1 2
1
No. Parts Name
Symbol
in Wiring
Diagram
Parts No.
Q'ty / unit
MXZ-32SV-
Remarks
RA6V60-
220+ 400V 2500+ 400V
Indoor unit connecting
Power supply
A,B,C,D
EVAPORATION DISCHARGE, DEFROST
250V/ 3.15A
E1
MXZ-32SV-
E2
1 1 1 1 1 1 1 2 1
1 4 1 1 1 1
1
1 1 2 1
PARTS LIST
14-1. OUTDOOR UNIT FUNCTIONAL PARTS MXZ-32SV ­MXZ-32SV -
E1 E2
Part numbers that are circled are not shown in the illustration.
40
Page 41
14-2. OUTDOOR UNIT STRUCTURAL PARTS
1 2 3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
M21 AS2 232
M21 17A 245 T92 500 800 T2W E70 654 T2W E95 654 T2W E95 655 T2W E70 653 T2W E95 653 T2W E95 655 T2W E70 652 T2W E95 652 T2W E95 655 T2W E70 651 T2W E95 651 T2W E95 655 T2W E79 290
M21 42E 644 T2W E40 247 T2W E70 248
M21 48A 961 T2W E79 646
M21 17A 297 T2W E40 523
M21 42E 630
M21 17A 249 T2W E40 646
M21 986 936
M21 LV0 936 T2W E59 936 T2W E70 936
FRONT PANEL SERVICE PANEL COMPRESSOR EXPANSION VALVE LEV COIL EXPANSION VALVE EXPANSION VALVE LEV COIL EXPANSION VALVE EXPANSION VALVE LEV COIL EXPANSION VALVE EXPANSION VALVE LEV COIL EXPANSION VALVE BASE ASSEMBLY UNION PIPE COVER REAR PANEL 4-WAY VALVE HIGH PRESSURE SWITCH TOP PANEL REAR GUARD HEAT EXCHANGER SIDE PANEL HIGH PRESSURE SWITCH CAPILLARY TUBE([4.0O[2.4O2000) CAPILLARY TUBE SET([3.0O[2.0O200) CAPILLARY TUBE ([2.5O[0.6O1000) CAPILLARY TUBE ([2.0O[0.6O750)
MC
LEV D
LEV C
LEV B
LEV A
63H1
63H2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 4 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 4 1 1
No. Parts Name
Symbol
in Wiring
Diagram
Parts No.
Q'ty / unit
MXZ-32SV-
Remarks
THV-247FBA D room D room D room C room C room C room B room B room B room A room A room A room
1/2,3/8,1/4 SET
2.75MPa(28kg/cm2)
3.43MPa(35kg/cm
2
)
[4.0O[2.4O400
[3.0O[2.0O200 4PCS/SET
[2.5O[0.6O1000 [2.5O[0.6O750
E1
MXZ-32SV-
E2
MXZ-32SV ­MXZ-32SV -
Part numbers that are circled are not shown in the illustration.
E1 E2
17 14
16
1
2
3
4 5
13 1215
11
10
6
8
7
9
When servicing , cut the tube to the proper length as shown in the REFRIGERANT SYSTEM DIAGRAM on page 12.
41
Page 42
1
No. Parts Name
Symbol
in Wiring
Diagram
Parts No.
Q'ty / unit
Remarks
E1
MXZ-32SV
T2W E59 704
DRAIN SOCKET ASSEMBLY
1
DRAIN SOCKET O1 DRAIN CAP O2
E2
1
14-3. ACCESSORY PARTS MXZ-32SV -
MXZ-32SV -
E1
E2
1
42
Page 43
B
A
C
15
OPTIONAL PARTS
15-1. Different-diameter pipe
MXZ-32SV
Model name
Model code
Connected pipes
diameter (mm)
Length
A
Length
B
Length
Unit : mm (inch)
C
MAC-454JP
51H-454
For different­diameter
MAC-455JP
51H-455
pipes
MAC-456JP
516456
15-2. Outlet guide
Changes air discharge direction.
Applied unit Model name Model code
MXZ-32SV MAC-855SG 51H-855
610.4 534 386
5 - [6
Punched hole
416
{9.52 — {12.7
(3/8) (1/2)
{12.7 — {9.52
(1/2) (3/8)
{12.7 — {15.88
(1/2) (5/8)
150
109.4
51.8
6.46.4
29.2760.829.2
{9.52
(3/8)
{12.7
(1/2)
{12.7
(1/2)
{12.7
(1/2)
{9.52
(3/8)
{15.88
(5/8)
69
65
66.5
386 534
832
5 - [6
Punched hole
MAC-855SG
43
Page 44
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Jun. 2006. No.OB254 REVISED EDITION-B 7 Distributed in Jan. 2003. No.OB254 REVISED EDITION-A 7 Reprinted in Feb. 2002. No.OB254 12 Reprinted in Dec. 2001. No.OB254 5 Reprinted in Dec. 2001. No.OB254 50 Reprinted in Feb. 2001. No.OB254 10 Distributed in May 2000. No.OB254 523 Made in Japan
New publication, effective Jun. 2006 Specifications subject to change without notice.
Loading...