Mitsubishi MXZ-2HA50VF, MXZ-2HA40VF, MXZ-3HA50VF User guide

OUTDOOR UNIT
SERVICE MANUAL
Models
E1
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
-
-
-
ET1
,
E1, ET1
E1, ET1
HFC
R32
Indoor unit service manual MSZ-HR•VF Series (OBH822)
No. OBH828
MXZ-2HA40VF MXZ-2HA50VF
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. SAFETY PRECAUTION ···································· 3
3. PART NAMES AND FUNCTIONS ··················· 13
4. SPECIFICATION ·············································· 14
5. NOISE CRITERIA CURVES ···························· 17
6. OUTLINES AND DIMENSIONS ······················ 18
7. WIRING DIAGRAM ·········································· 20
8. REFRIGERANT SYSTEM DIAGRAM ············· 24
9. PERFORMANCE CURVES ····························· 27
10. ACTUATOR CONTROL ··································· 36
11. SERVICE FUNCTIONS ···································· 37
12. TROUBLESHOOTING ····································· 41
13. DISASSEMBLY INSTRUCTIONS ···················· 66
PARTS CATALOG (OBB828)
Use the specied refrigerant only
OBH828
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
2
1
OBH828
MXZ-2HA40VF -
TECHNICAL CHANGES
E1
MXZ-2HA50VF -E1, MXZ-3HA50VF -E1,
1. New model
ET1
,
ET1
ET1
2
SAFETY PRECAUTION
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
WARNING
Read the OPERATION MANUAL carefully before operation.
Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.
Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.
This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R32
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply breaker.
• Discharge the condenser before the work involving the electric parts.
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the following.
· Be sure to clean the pipes and make sure that the insides of the pipes are clean.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution
not to touch the live parts.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
3
Make sure that the inside and outside of refrige-
OBH828
rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazard to refrigerant cycle. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil, etc.
Use the following tools specifically designed for use with R32 refrigerant.
The following tools are necessary to use R32 refrigerant.
Tools for R32 Gauge manifold Charge hose Gas leak detector
Torque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil, etc.
Do not use refrigerant other than R32.
If other refrigerant (R22, etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil, etc.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
4
[1] Warning for service
OBH828
(1) Do not alter the unit. (2) For installation and relocation work, follow the instructions in the Installation Manual and use tools and pipe components
specifically made for use with refrigerant specified in the outdoor unit installation manual. (3) Ask a dealer or an authorized technician to install, relocate and repair the unit. For appliances not accessible to the general public. (4) Refrigerant pipes connection shall be accessible for maintenance purposes. (5)
If the air conditioner is installed in a small room or closed room, measures must be taken to prevent the refrigerant concentra-
tion in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the
concentration limit to be exceeded, hazards due to lack of oxygen in the room may result. (6) Keep gas-burning appliances, electric heaters, and other fire sources (ignition sources) away from the location where
installation, repair, and other air conditioner work will be performed. If refrigerant comes into contact with a flame, poisonous gases will be released. (7) When installing or relocating, or servicing the air conditioner, use only the specified refrigerant (R32) to charge the refrig-
erant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may
result in an explosion and other hazards. (8) After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact
with the flame of a heater or portable cooking range, poisonous gases will be released. (9) Do not use low temperature solder alloy in case of brazing the refrigerant pipes. (10)
When performing brazing work, be sure to ventilate the room sufficiently. Make sure that there are no hazardous or flam-
mable materials nearby. When performing the work in a closed room, small room, or similar location, make sure that there are no refrigerant leaks
before performing the work. If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released. (11) Do not install the unit in places where refrigerant may build-up or places with poor ventilation such as a semi-basement or a
sunken place in outdoor: Refrigerant is heavier than air, and inclined to fall away from the leak source. (12)
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
(13)
The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an
operating gas appliance or an operating electric heater). (14)
Do not pierce or burn.
(15)
Be aware that refrigerants may not contain an odour.
(16)
Pipe-work shall be protected from physical damage.
(17)
The installation of pipe-work shall be kept to a minimum.
(18)
Compliance with national gas regulations shall be observed.
(19)
Keep any required ventilation openings clear of obstruction.
(20)
Servicing shall be performed only as recommended by the manufacturer.
(21)
The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified
for operation. (22) Maintenance, service and repair operations shall be performed by authorized technician with required qualification. (23)
Be sure to have appropriate ventilation in order to prevent ignition. Furthermore, be sure to carry out fire prevention
measures that there are no dangerous or flammable objects in the surrounding area.
[2] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[3] Additional refrigerant charge
When charging directly from cylinder
R32 is a single refrigerant and its composition does not change. Therefore, both liquid charging and gas charging are
possible. Liquid charging of refrigerant all at once from the low-pressure side may cause the compressor malfunction.
Accordingly, make sure that charging is gradual.
< Cylinder with a siphon tube >
Cylinder
Charging gas refrigerant
Valve
Liquid
Charging liquid refrigerant
5
< Cylinder without a siphon tube >
Cylinder
Liquid
Valve
[4] Cautions for unit using R32 refrigerant
OBH828
Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful
attention to the following points.
(1) Information on servicing (1-1) Checks on the Area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating systems, (1-3) to (1-7) shall be completed prior to conducting work on the systems.
(1-2) Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.
(1-3) General Work Area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the con­ditions within the area have been made safe by control of flammable material.
(1-4) Checking for Presence of Refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
(1-5) Presence of Fire Extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
(1-6) No Ignition Sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, includ­ing cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
(1-7) Ventilated Area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
(1-8) Checks on the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing parts are installed.
• The ventilation machinery and outlets are operating adequately and are not obstructed.
• Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
• Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance
• which may corrode refrigerant containing components, unless the components are constructed of materials which are
inherently resistant to being corroded or are suitably protected against being corroded.
(1-9) Checks on Electrical Devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection proce­dures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an ade­quate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include that:
capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• no live electrical components and wiring are exposed while charging, recovering or purging the system;
• there is continuity of earth bonding
(2) Repairs to Sealed Components (2-1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked
upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
(2-2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not
altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of prevent­ing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
6
(3) Repair to intrinsically Safe Components
OBH828
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmos­phere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
(4) Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
(5) Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
(6) Leak Detection Methods
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equip­ment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable refrigerants, oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing pro­cess.
(7) Removal and Evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a considera­tion. The following procedure shall be adhered to:
• remove refrigerant
• purge the circuit with inert gas
• evacuate
• purge again with inert gas
• open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrig­erants, the system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.
(8) Charging Procedures
In addition to conventional charging procedures, the following requirements shall be followed:
Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines
shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
• Prior to recharging
tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
(9) Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-
7
b) Isolate system electrically.
OBH828
c)
Before attempting the procedure, ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
d)
Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer’s instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i)
Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equip-
ment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
(10)
Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stat­ing the equipment contains flammable refrigerant.
(11)
Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrig­erant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refriger­ants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be com­plete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this pro­cess. When oil is drained from a system, it shall be carried out safely.
8
[5] Service tools
OBH828
Use the below service tools as exclusive tools for R32 refrigerant.
No. Tool name Specifications
Gauge manifold · Only for R32
· Use the existing fitting
specifications
. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
Charge hose · Only for R32
· Use pressure performance of 5.09MPa·G or over.
Electronic scale
Gas leak detector
Adaptor for reverse flow check
Refrigerant charge base
· Use the detector for R134a, R407C, R410a or R32.
· Attach on vacuum pump.
Refrigerant cylinder · Only for R32
· Cylinder with syphon
Refrigerant recovery equipment
2-3. PRECAUTIONS WHEN REUSING EXISTING R22/R410a REFRIGERANT PIPES
(1) Flowchart
• Refer to the owchart below to determine if the existing pipes can be used and if it is necessary to use a lter dryer.
• If the diameter of the existing pipes is different from the specied diameter, refer to technical data materials to conrm if the
pipes can be used.
The existing pipe thickness meets specica­tions and the pipes are not damaged.
Check if the existing air conditioner can operate.
After operating the cooling system for about 30 minutes, perform pump down work.
Disconnect the existing air conditioner from the pipes.
Connect the new air conditioner.
Perform the airtight test, vacuum air purging, additional refrigerant charging (if necessary), and gas leak check.
Test run
Measure the existing pipe thickness and check for damage.
Note: If the existing air conditioner cannot operate, use a refrigerant recovery device to collect the refrigerant.
The existing pipes cannot be reused. Use new pipes.
The existing pipe thickness does not meet
specications or the pipes are damaged.
9
(2) Cautions for refrigerant piping work
3/4
19.05
1.0
OBH828
New refrigerant R32 is adopted for replacement inverter series. Although the refrigerant piping work for R32 is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R32 is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes
Because the working pressure of R32 is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7 mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions(inch)
1/4 3/8 1/2 5/8
Outside
diameter
6.35
9.52
12.70
15.88
(mm)
Thickness
R32/R410a R22
0.8
0.8
0.8
1.0
(mm)
0.8
0.8
0.8
1.0
Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R32 is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and strength, flare cutting dimension of copper pipe for R32 has been specified sepa­rately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R32 also has partly been changed to increase strength as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R32 below. For 1/2 and 5/8 inch pipes, the dimension B changes. Use torque wrench corresponding to each dimension.
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
Outside
diameter(mm) 1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
+0
( )
Dimension A
(mm)
-0.4
R32/R410a R22
9.1
13.2
16.6
19.7
9.0
13.0
16.2
19.4
23.3
Flare nut dimensions
Nominal
dimensions(inch)
1/4 3/8 1/2 5/8 3/4
Outside
diameter(mm)
6.35
9.52
12.70
15.88
19.05
R32/R410a
Tools for R32 (The following table shows whether conventional tools can be used or not.)
Tools and materials Use R32 tools Can R22 tools be used? Gauge manifold Air purge, refrigerant Charge hose
Gas leak detector Gas leak check Tool for HFC refrigerant Refrigerant recovery
equipment Refrigerant cylinder Refrigerant charge Tool exclusive for R32 Safety charger
Charge valve
Vacuum pump
Flare tool
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and vacuum valve
Charging cylinder Refrigerant charge Tool exclusive for R32
: Prepare a new tool. (Use the new tool as the tool exclusive for R32.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
charge and operation check
Refrigerant recovery Tool exclusive for R32
Prevent compressor malfunction when charging refrigerant by spraying liquid refrigerant
Prevent gas from blowing out when detaching charge hose
Vacuum drying and air purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum valve prevents back
ow of oil and refrigerant to
thermistor vacuum gauge)
Tool exclusive for R32
Tool exclusive for R32
Tool exclusive for R32
Tool exclusive for R32
Tools for other refrigerants can be used if equipped with adapter for reverse
ow check
Tools for other refrigerants can be used by adjusting
aring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
(Usable if equipped with
adapter for reverse
ow)
(Usable by adjusting
aring dimension)
Can R407C tools be used?
(Usable if equipped with
adapter for reverse
ow)
(Usable by adjusting
aring dimension)
10
Dimension B
Dimension B
17.0
22.0
26.0
29.0 *
(mm)
R22
17.0
22.0
24.0
27.0
36.0
Can R410a tools be used?
* 36.0mm for indoor unit of RP100, 125 and 140
(Usable if equipped with
adapter for reverse
ow)
(Usable by adjusting
aring dimension)
2-4. CHOOSING THE OUTDOOR UNIT INSTALLATION LOCATION
OBH828
OK OK
OK NG
R32 is heavier than air—as well as other refrigerants— so tends to accumulate at the base (in the vicinity of the floor). If R32 accumulates around base, it may reach a flammable concentration in case room is small. To avoid ignition, maintaining a safe work environment is required by ensuring appropriate ventilation. If a refrigerant leak is confirmed in a room or an area where there is insufficient ventilation, refrain from using of flames until the work environment can be improved by ensuring appropriate ventilation. Install outdoor units in a place where at least one of the four sides is open, and in a sufficiently large space with­out depressions.
2-5. MINIMUM INSTALLATION AREA
If you unavoidably install a unit in a space where all four sides are blocked or there are depressions, confirm that one of these situations (A, B or C) is satisfied.
Note: These countermeasures are for keeping safety not for specification guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to refrigerant quantity M (factory-charged refrigerant + locally added refrigerant).
M [kg] Amin [m²]
1.0 12
1.5 17
2.0 23
2.5 28
3.0 34
3.5 39
4.0 45
4.5 50
5.0 56
5.5 62
6.0 67
6.5 73
7.0 78
7.5 84
Amin
B) Install in a space with a depression height of 0.125 [m] or less.
Height from the bottom of
0.125 [m] or less
Height from the bottom of
0.125 [m] or less
11
C) Create an appropriate ventilation open area.
OBH828
Make sure that the width of the open area is 0.9 [m] or more and the height of the open area is 0.15 [m] or more. However, the height from the bottom of the installation space to the bottom edge of the open area should be 0.125 [m] or less. Open area should be 75% or more opening.
75% or more opening
Width W 0.9 [m] or more
Height from the bottom
0.125 [m] or less
Height H 0.15 [m] or more
■ Indoor units
Install in a room with a floor area of Amin or more, corresponding to refrigerant quantity M (factory-charged refrig­erant + locally added refrigerant). * For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual. For the amount to be added locally, refer to the installation manual. Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0; for wall mounted: 1.8 m or more; for ceiling suspended, cassette and ceiling concealed: 2.2 m or more. * There are restrictions in installation height for each model, so read the installation manual for the particular unit.
M [kg] Amin [m²]
1.0 3
1.5 4.5
2.0 6
2.5 7.5
3.0 9
3.5 12
4.0 15.5
4.5 20
5.0 24
5.5 29
6.0 35
6.5 41
7.0 47
7.5 54
h0
Wall mounted
1.8 [m]
h0 2.2 [m]h0 2.2 [m]h0 2.2 [m]
Ceiling concealedCassetteCeiling suspended
12
3
OBH828
PART NAMES AND FUNCTIONS
MXZ-2HA40VF MXZ-2HA50VF
MXZ-3HA50VF
Air inlet
(Back and side)
Piping
Drain hose
Air outlet
Drain outlet
Air inlet
(Back and side)
Air outlet
Drain outlet
ACCESSORIES
Model
Drain socket 1 1
Drain cap - 2
MXZ-2HA40VF MXZ-2HA50VF
MXZ-3HA50VF
13
4
OBH828
System
Electrical
Coefcient of performance (C.O.P) (Total)
Compressor
Fan
Special
1 Measured under rated operating frequency.
2 When connected with indoor units below. MSZ-HR25VF + MSZ-HR25VF NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m) COOLING INDOOR Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C HEATING INDOOR Dry-bulb temperature 20.0 °C OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
SPECIFICATION
Outdoor model MXZ-2HA40VF
Outdoor unit power supply
Indoor units number 2
Piping total length m Max. 30
Connecting pipe length m Max. 20
Height difference (Indoor ~ Outdoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function Cooling Heating
Capacity Rated frequency (Min.-Max.)
Breaker capacity A 15
Power input (Total) 1, 2 W 1,050 910
Running current (Total)
data
Power factor (Total) 1, 2 % 94 87
Starting current (Total)
Model SVB130FBBMT
Output W 1,100
Current
Refrigeration oil (Model) L 0.35 (FW68S)
Model RC0J50-NA
Current
motor
Dimensions W x H x D mm 800 x 550 x 285
Weight kg 37
Air ow (Rated) m3 /h 1,704 2,010
Sound level (Rated) dB(A) 44 50
Fan speed (Rated) rpm 780 910
remarks
Pre-charged refrigerant quantity (R32) kg 0.9
Max refrigerant quantity (R32) kg 0.9
1, 2 A 4.15
1, 2 A 0.35
1, 2 A
1, 2 A 7.6
2 kW 4.0 (1.1 - 4.3) 4.3 (1.0 - 4.7)
5.1 - 4.9 - 4.7 (220V - 230V - 240V) 4.8 - 4.6 - 4.4 (220V - 230V - 240V)
1, 2 3.81 4.73
Single phase
220 - 230 - 240 V, 50 Hz
14
Outdoor model MXZ-2HA50VF
OBH828
Outdoor unit power supply
Indoor units number 2
Piping total length m Max. 30
Connecting pipe length m Max. 20
System
Height difference (Indoor ~ Outdoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function Cooling Heating
Capacity Rated frequency (Min.-Max.)
Breaker capacity A 15
Power input (Total) 1, 2 W 1,520 1,540
Running current (Total)
data
Power factor (Total) 1, 2 % 97
Electrical
Starting current (Total)
Coefcient of performance (C.O.P) (Total)
Model SVB130FBBMT
Output W 1,300
Current
Refrigeration oil (Model) L 0.35 (FW68S)
Compressor
Model RC0J50-NA
Current
Fan
motor
Dimensions W x H x D mm 800 x 550 x 285
Weight kg 37
Air ow (Rated) m3 /h 1,962 2,082
Sound level (Rated) dB(A) 47 51
Fan speed (Rated) rpm 890 940
Special
remarks
Pre-charged refrigerant quantity (R32) kg 0.9
Max refrigerant quantity (R32) kg 0.9
1 Measured under rated operating frequency.
2 When connected with indoor units below. MSZ-HR25VF + MSZ-HR25VF NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m) COOLING INDOOR Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C HEATING INDOOR Dry-bulb temperature 20.0 °C OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
1, 2 A 6.75
1, 2 A 0.35
1, 2 A
1, 2 A 7.6
2 kW 5.0 (1.1 - 5.4) 6.0 (1.0 - 6.4)
7.1 - 6.8 - 6.5 (220V - 230V - 240V) 7.2 - 6.9 - 6.6 (220V - 230V - 240V)
1, 2 3.29 3.90
Single phase
220 - 230 - 240 V, 50 Hz
15
Outdoor model MXZ-3HA50VF
OBH828
Outdoor unit power supply
Indoor units number 2 to 3
Piping total length m Max. 50
Connecting pipe length m Max. 25
System
Height difference (Indoor ~ Outdoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor) m Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function Cooling Heating
Capacity Rated frequency (Min.-Max.)
Breaker capacity A 25
Power input (Total) 1, 2 W 1,260 1,300
Running current (Total)
data
Power factor (Total) 1, 2 % 97
Electrical
Starting current (Total)
Coefcient of performance (C.O.P) (Total)
Model SVB130FBBM1T
Output W 1,300
Current
Refrigeration oil (Model) L 0.6 (FW68S)
Compressor
Model SIC-82FX-F764-1
Current
Fan
motor
Dimensions W x H x D mm 840 x 710 x 330
Weight kg 57
Air ow (Rated) m3 /h 1,860 1,746
Sound level (Rated) dB(A) 46 50
Fan speed (Rated) rpm 600 580
Special
remarks
Pre-charged refrigerant quantity (R32) kg 1.4
Max refrigerant quantity (R32) kg 1.6
1 Measured under rated operating frequency.
2 When connected with indoor units below. MSZ-HR25VF + MSZ-HR25VF + MSZ-HR25VF NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m) COOLING INDOOR Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C HEATING INDOOR Dry-bulb temperature 20.0 °C OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
1, 2 A 5.30
1, 2 A 0.5
1, 2 A
1, 2 A 6.7
2 kW 5.0 (2.9 - 6.5) 6.0 (2.6 - 7.5)
5.9 - 5.6 - 5.4 (220V - 230V - 240V) 6.1 - 5.8 - 5.6 (220V - 230V - 240V)
1, 2 3.97 4.62
Single phase
220 - 230 - 240 V, 50 Hz
16
5
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
OUTDOOR UNIT
OBH828
NOISE CRITERIA CURVES
FAN SPEED
FUNCTION
SPL(dB(A))
CoolingHigh
HeatingHigh
LINE
44
50
MXZ-2HA50VFMXZ-2HA40VF
FAN SPEED
FUNCTION
SPL(dB(A))
CoolingHigh
HeatingHigh
LINE
47
51
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MXZ-3HA50VF
FAN SPEED
FUNCTION
CoolingHigh
HeatingHigh
SPL(dB(A))
46
50
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Test conditions Cooling :Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°C Heating :Dry-bulb temperature 7.0°C Wet-bulb temperature 6.0°C
17
6
OBH828
MXZ-2HA40VF MXZ-2HA50VF
OUTLINES AND DIMENSIONS
Unit: mm (inch)
18
500 or more
MXZ-3HA50VF
OBH828
Unit: mm (inch)
1.Installation space
Note : Leave front and both sides free of obstruction.
Note : Leave front and overhead free of obstruction.
100 or more
Note : Leave rear, overhead and both sides free of obstruction.
100 or more
500 or more
200 or more
350 or more
2.Service space
100 or more
350 or more
100 or more
500 or more
Service space
350 or more
19
7
ACL, ACL2
F701, 801, 901
IC700, 820, 932
SYMBOL
NOTES:
:Terminal block
About the indoor side electric wiring refer to the
indoor unit electric wiring diagram for the service.
Use copper conductors only.
(For field wiring).
Symbols below indicate.
FUSE (T3.15AL250V)
FUSE (T3.15AL250V)
OBH828
WIRING DIAGRAM
MXZ-2HA40VF -
E1
MXZ-2HA50VF -
POWER SUPPLY
~/N
220-230-240V
50Hz
L
N
TB1
BU
GNYE
LD66B
3
CN722
1 2
21S4
1
CN721
4
X64
BNOG
ACL
E1
TO INDOOR
UNIT No. B
BREAKER
CIRCUIT
BK
ACL2
BKBUBKBNBKBURD
LD-E1
LD62
LD-E2
X66
X63
PTC65
PTC64
IC802
T801
F801
220-230-240V~
12-24V
S3S2S1
TB3
BURDOG
F1
1
CN601
LD61
F61
F701
CN935
INVERTER P.C. BOARD
2
CN642
1
TO INDOOR
UNIT No. A
220-230-240V~
12-24V
S3S1S2
TB2
BK
7
OG
5
1
CN602
CN724
CN725
7
1
CN644
CN641
CN643
OUTDOOR
7
1
3
5
1
5
1
3
1 4
1 2
1
5
BK
BU
DISPLAY
P.C. BOARD
CN936
LED1 LED2
5
M
5
M
RT68RT62
RT61
RT65RT64
LEV A
LEV B
NAME
SYMBOLNAME
FIN TEMP. THERMISTOR
RT64
AMBIENT TEMP. THERMISTOR
RT65
OUTDOOR HEAT EXCHANGER
TERMINAL BLOCK
TRANSFORMER
TEMP. THERMISTOR
T801
RT68
TB1~3
RELAY
REVERSING VALVE COIL
21S4
X63, 64, 66
+
C61C63
+
C62
+
LD66A
~
-
+
LD70
~
DB61
IC820
MS
F62
F901
RD
3
P
W
MC
U
3~
W
WH
V
BK
V
WH
RD
BK
1
CN932
N
U
CNMC
313
P
UWV
IC932
LDU
BKWHRD
1
LDV
20
CN931
N
LDW
1
IC700
MF
5
3
MS
1.
2.
3~
3.
POWER DEVICE
IC802
SYMBOLNAME
:Connector
REACTOR
/
LED
EXPANSION VALVE COIL
COMPRESSOR
FAN MOTOR
MF
MC
LED1, 2
LEV A, B
SMOOTHING CAPACITOR
DIODE MODULE
F1
DB61
C61~63
CIRCUIT PROTECTOR
DISCHARGE TEMP. THERMISTOR
DEFROST THERMISTOR
RT61
RT62
PTC64, 65
FUSE (25A 250V)
FUSE (15A 250V)
POWER MODULE
F61
F62
MXZ-2HA40VF -
ACL, ACL2
F701, 801, 901
IC700, 820, 932
SEMBOL
NOTLAR:
:Terminal bloğu
İç ünite elektrik devresiyle ilgili bakım için iç ünite elektri
devre şemasını referans alınız.
Sadece bakır kablolar kullanınız.
(Saha elektrik devresi için).
Sembollerin anlamı.
OBH828
ET1
MXZ-2HA50VF -
GÜÇ KAYNAĞI
ET1
İÇ ÜNİTE
~/N
230V
50Hz
No. B
İÇ ÜNİTE
No. A
TB1
21S4
ACL
TB3
2
CN642
1
230V~
12-24V
S3S2S1
BURDOG
F1
1
CN601
LD61
F61
F701
CN935
İNVERTÖR BASKILI
DEVRE KARTI
BK
1
5
7
1
DEVRE KESİCİ
L
N
BK
BU
GNYE
BNOG
ACL2
BKBUBKBNBKBURD
LD-E1
LD62
LD66B
CN722
CN721
X64
3
1 2
1
4
LD-E2
X66
X63
PTC65
PTC64
IC802
T801
F801
TB2
7
CN602
CN724
CN725
CN644
CN641
CN643
OG
5
1
5
1
3
1 4
1 2
1
5
S3S1S2
3
12-24V
BU
DIŞ GÖSTERGE
7
1
5
5
230V~
CN936
BK
BASKILI DEVRE
KARTI
LED1 LED2
M
LEV A
M
LEV B
RT68RT62
PARÇA ADI
FIN SICAKLIK TERMİSTÖRÜ
DIŞ ÜNİTE EŞANJÖR
SICAKLIK TERMİSTÖRÜ
RT61
RT65RT64
ORTAM SICAKLIK TERMİSTÖRÜ
RT64
RT65
SEMBOLPARÇA ADI
RT68
TRANSFORMATÖR
RÖLE
İKİ YÖNLÜ VANA SARGISI
TERMİNAL BLOĞU
T801
21S4
TB1~3
X63, 64, 66
C61C63
C62
LD66A
-
LD70
DB61
+
F62
+
+
F901
WH
BK
RD 3
~
+
~
IC820
MS
1
P
U
W
V
MC
BK
U
V
WH
3~
W
RD
313
CN932
N
CNMC
P
UWV
IC932
LDU
BKWHRD
1
LDV
CN931
N
LDW
1
IC700
MF
5
3
MS
k
1.
2.
3~
3.
SEMBOLPARÇA ADI
:Konnektör
/
GÜÇ CİHAZI
LED
GENLEŞME VANASI SARGISI
IC802
LED1, 2
LEV A, B
DİYOT MODÜLÜ
REAKTÖR
SÜZME KAPASİTÖR
DB61
C61~63
BASMA SICAKLIK TERMİSTÖRÜ
KOMPRESÖR
FAN MOTORU
DEVRE KORUMASI
DEFROST TERMİSTÖRÜ
MF
MC
RT61
RT62
PTC64, 65
SİGORTA (T3.15AL250V)
SİGORTA (T3.15AL250V)
SİGORTA (25A 250V)
SİGORTA (15A 250V)
GÜÇ MODÜLÜ
F1
F61
F62
21
MXZ-3HA50VF -
OBH828
E1
22
MXZ-3HA50VF -
OBH828
ET1
23
8
OBH828
REFRIGERANT SYSTEM DIAGRAM
MXZ-2HA40VF MXZ-2HA50VF
R.V. coil OFF ON
Refrigerant flow in cooling Refrigerant flow in heating
Compressor
Discharge temperature thermistor RT62
Muffler
UNIT: mm
Indoor unit
A
Indoor unit
B
Indoor unit
A
Indoor unit
B
Stop valve (with service port)
Stop valve (with service port)
Capillary tube
Stop valve
(with strainer #100)
Capillary tube
Stop valve
(with strainer #100)
LEV A
LEV B
Sub muffler
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b) 20 m
Total piping length (a+b) 30 m
Bending point for each unit 30
Total bending point 20
It is irrelevant which unit is higher.
4-way valve
Indoor units
Outdoor heat exchanger temperature thermistor RT68
FAN-OUT
Ambient
HEX-OUT
Strainer #100
Distributor
a
temperature thermistor RT65
Defrost thermistor RT61
Capillary tube
Max. Height difference
Outdoor unit
15 m
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit
precharged
(g)
900 0
Refrigerant piping length (one way, 2 unit total)
30 m
b
Outdoor unit union diameter For
Indoor unit A
Indoor unit B
Liquid 6.35(1/4)
Gas 9.52(3/8)
Liquid 6.35(1/4)
Gas 9.52(3/8)
15 m
10 m
UNIT: mm (inch)
24
MXZ-3HA50VF
OBH828
UNIT: mm
R.V. coil OFF ON
Indoor unit
A
Indoor unit
B
Indoor unit
C
Refrigerant flow in cooling Refrigerant flow in heating
Capillary tube
Indoor unit
A
Indoor unit
B
Indoor unit
C
Strainer #100
Capillary tube
Strainer #100
Capillary tube
Strainer #100
High-pressure switch
Muffler
LEV A
LEV B
LEV C
Oil separator
Stop valve with service port
Strainer #100
Compressor
4-way valve
Stop valve
Discharge temperature
thermistor RT62
Capillary tube
Power
receiver
LEV E
Charge pipe
HEX-OUT
Strainer #100
Distributor
Outdoor heat exchanger temperature thermistor RT68
FAN-OUT
Ambient temperature thermistor RT65
Defrost thermistor RT61
Capillary tube
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b, c) 25 m Total piping length (a+b+c) 50 m Bending point for each unit 25 Total bending point 50
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit
precharged
(g)
1,400 0 200
Calculation: Xg = 20 g/m x (Refrigerant piping length (m) - 40)
Refrigerant piping length (one way, 3 unit total)
40 m 50 m
Indoor units
a
b
c
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Indoor unit C
Max. Height difference
Outdoor unit
15 m
10 m
UNIT: mm (inch)
Liquid 6.35(1/4)
Gas 9.52(3/8)
Liquid 6.35(1/4)
Gas 9.52(3/8)
Liquid 6.35(1/4)
Gas 9.52(3/8)
15 m
25
PUMPING DOWN
OBH828
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
1) Turn off the breaker.
2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approximately 0.5 to 0 kgf/cm²), fully close the stop valve on the gas
pipe side of the outdoor unit and stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.) * If too much refrigerant has been added to the air conditioner system, the pressure may not drop to
proximately 0.5 to 0 kgf/cm²) ant circuit. If this occurs, use a refrigerant collecting device to collect all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.
7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
, or the protection function may operate due to the pressure increase in the high pressure refriger-
WARNIG
0.05 to 0 MPa [Gauge] (ap-
26
9
OBH828
PERFORMANCE CURVES
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 - 264 V 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °CWB
(2) Indoor outlet air wet-bulb temperature: °CWB (3) Outdoor intake air dry-bulb temperature: °CDB (4) Total input: W (5) Indoor intake air dry-bulb temperature: °CDB (6) Outdoor intake air wet-bulb temperature: °CWB (7) Total input: W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating
INDOOR UNIT
Wet and dry bulb thermometers
FRONT VIEW
OUTDOOR UNIT
Wet and dry bulb thermometers
BACK VIEW
27
9-1. CAPACITY AND THE INPUT CURVES
OBH828
MXZ-2HA40VF MXZ-2HA50VF
8.7
5.9
8.0
5.5
7.3
5.0
6.6
4.6
5.9
4.1
5.3
3.7
difference (°C)
4.6
3.2
Indoor air Wet-bulb temperature
2.8
4.0
11.1
10.2
9.3
8.3
7.5
6.6
5.8
5.0
1.4
1.3
1.2
1.1
Indoor intake air Wet-bulb temperature (°C)
1.0
0.9
0.8
Capacity correction factors
0.7
Cooling capacity
26
24
22 20 18
35 class
22.2
20.6
19.0
17.4
15.8
14.3
12.7
11.1
9.5
7.9
6.3
35 class
42 class
(MXZ-2HA50VF)
26.6
24.7
22.8
20.9
19.0
17.1
15.2
13.3
11.4
9.5
7.6
42 class
(MXZ-2HA50VF)
25 class
21.3
19.8
18.3
16.7
15.2
13.7
12.2
difference (°C)
10.7
9.1
Indoor air Dry-bulb temperature
7.6
6.1
25 class
-10 0 15 30 45 Outdoor intake air Dry - bulb temperature (ºC)
1.4
Total input (Cooling)
1.3
1.2
1.1
Indoor intake air Wet-bulb temperature (°C)
26
1.0
0.9
Input correction factors
0.8
0.7
-10 0 15 30 45 Outdoor intake air Dry - bulb temperature (ºC)
1.4
Heating capacity
1.3
1.2
1.1
1.0
0.9
0.8
0.7
Indoor intake air Dry-bulb temperature (°C)
0.6
0.5
Capacity correction factors
0.4
-12 0 8 18
-16 -8 -4 4 12 16 Outdoor intake air Wet
Outdoor intake air Wet
1.4
Total input (Heating)
-
-
bulb temperature (
1.3
1.2
1.1
1.0
0.9
0.8
Indoor intake air Dry-bulb temperature (°C)
0.7
Input correction factors
0.6
0.5
0.4
-12 0 8 18
-16 -8 -4 4 12 16 Outdoor intake air Wet
Outdoor intake air Wet
-
-
bulb temperature (
46-5 5 10 20 25 35 40
22
24
20 18
46-5 5 10 20 25 35 40
15
20 26
)
ºC
26
26 20
20
15
15
)
ºC
28
MXZ-3HA50VF
Indoor intake air Dry-bulb temperature (°C)
OBH828
difference (°C)
Indoor air Wet-bulb temperature
5.9
5.5
5.0
4.6
4.1
3.7
3.2
2.8
25 class
8.7
11.1
8.0
10.2
7.3
9.3
6.6
8.3
5.9
7.5
5.3
6.6
4.6
5.8
4.0
5.0
35 class
12.8
11.6
10.5
9.5
8.5
7.5
6.6
5.6
42 class
50 class
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
Capacity correction factors
-10 0 15
Indoor intake air Wet-bulb temperature (°C)
-5 5 10 20 25 35 40
Outdoor intake air Dry
Cooling capacity
- bulb temperature (
30
ºC
)
45 46
26 24 22 20 19 18
16
21.3
22.2
29.9
19.8
20.6
27.8
18.3
19.0
25.7
16.7
17.4
23.5
15.2
15.8
21.4
13.7
14.3
19.2
12.2
12.7
difference (°C)
10.7
9.1
Indoor air Dry-bulb temperature
7.6
6.1
25 class
11.1
9.5
7.9
6.3
35 class
17.1
15.0
12.8
10.7
8.6
42 class
38.4
35.7
32.9
30.2
27.4
24.7
21.9
19.2
16.5
13.7
11.0
50 class
1.4
Total input (Cooling)
1.3
1.2
1.1
Indoor intake air Wet-bulb temperature (°C)
1.0
0.9
0.8
0.7
0.6
0.5
Input correction factors
0.4
-10 0 15
-5 5 10 20 25 35 40
Outdoor intake air Dry
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
Capacity correction factors
0.4
-16 -8 -4 4 12 18
Indoor intake air Dry-bulb temperature (°C)
-12 0 8 16 Outdoor intake air Wet
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Input correction factors
0.5
0.4
Heating capacity
Total input (Heating)
- bulb temperature (
-
bulb temperature (
30
ºC
18 19 20 16 22 24 26
45 46
)
ºC
15 20 26
)
26
20
15
-16 -8 -4 4 12 18-12 0 8 16
Outdoor intake air Wet
-
bulb temperature (
29
)
ºC
9-2. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY (single operation)
OBH828
MXZ-2HA40VF
25-class unit
2.0
<COOL>Capacity
2.0
<COOL>Total input
2.0
<HEAT>Capacity
2.5
<HEAT>Total input
1.5
1.0
0.5
0 50 100 150
Frequency
35-class unit
<COOL>Capacity
2.0
1.5
1.0
0.5
0 50 100 150
Frequency
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<COOL>Total input
2.5
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<HEAT>Capacity
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
2.0
1.5
1.0
0.5
Hz
<HEAT>Total input
0 50 100 150
Frequency
Hz
Hz
30
MXZ-2HA50VF
OBH828
25-class unit
<COOL>Capacity
2.0
1.5
1.0
0.5
0 50 100 150
Frequency
35-class unit
<COOL>Capacity
2.0
1.5
1.0
0.5
0 50 100 150
Frequency
42-class unit
<COOL>Capacity
2.0
<COOL>Total input
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<COOL>Total input
2.5
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<COOL>Total input
2.0
<HEAT>Capacity
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<HEAT>Capacity
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<HEAT>Capacity
1.5
2.5
2.0
1.5
1.0
0.5
Hz
<HEAT>Total input
0 50 100 150
Frequency
2.0
1.5
1.0
0.5
Hz
<HEAT>Total input
0 50 100 150
Frequency
1.5
<HEAT>Total input
Hz
Hz
1.5
1.0
0.5
0 50 100 150
Frequency
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
1.0
0.5
Hz
0 50 100 150
Frequency
1.0
0.5
Hz
0 50 100 150
Frequency
Hz
31
MXZ-3HA50VF
OBH828
25-class unit
<COOL>Capacity
2.0
2.0
<COOL>Total input
2.0
<HEAT>Capacity
2.0
<HEAT>Total input
1.5
1.0
0.5
0 50 100 150
Frequency
35-class unit
<COOL>Capacity
2.0
1.5
1.0
0.5
0 50 100 150
42-class unit
1.5
1.0
0.5
Frequency
<COOL>Capacity
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<COOL>Total input
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<COOL>Total input
2.0
1.5
1.0
0.5
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<HEAT>Capacity
2.0
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
<HEAT>Capacity
1.5
1.0
0.5
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
2.0
1.5
1.0
0.5
Hz
<HEAT>Total input
0 50 100 150
Frequency
1.5
1.0
0.5
<HEAT>Total input
Hz
Hz
0 50 100 150
Frequency
50-class unit
<COOL>Capacity
1.5
1.0
0.5
0 50 100 150
Frequency
Hz
0 50 100 150
Frequency
<COOL>Total input
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
Hz
0 50 100 150
Frequency
<HEAT>Capacity
1.5
1.0
0.5
Hz
0 50 100 150
Frequency
Hz
0 50 100 150
Frequency
1.5
1.0
0.5
Hz
<HEAT>Total input
0 50 100 150
Frequency
Hz
Hz
32
9-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION <Test run operation>
Outdoor low pressure
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
Ambient humidity (%)
Outdoor low pressure
Outdoor unit current (A)
Ambient humidity (%)
Outdoor low pressure
Outdoor unit current (A)
OBH828
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor varies).
6. To cancel test run operation or EMERGENCY OPERATION, press EMERGENCY OPERATION switch or any button on remote controller.
9-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT CURVE (single operation)
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is : 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
(1) COOL operation
Both indoor and outdoor units are under the
same temperature/humidity condition.
Operation : TEST RUN OPERATION (Refer to 9-3.)
Dry-bulb temperature (
20
25
30 70
Relative humidity (%)
)
50
60
MXZ-2HA40VF
25-class unit 35-class unit
(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
30Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
Ambient temperature ( )
30Hz
(°C)
70
(%)
Ambient humidity (%)
(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
MXZ-2HA50VF
25-class unit 35-class unit
(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
30Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
Ambient temperature ( )
30Hz
(°C)
70
(%)
(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
30Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
Ambient temperature ( )
30Hz
(°C)
70
(%)
Ambient humidity (%)
6
30Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
Ambient temperature ( )
30Hz
(°C)
70
(%)
42-class unit
(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
(°C)
(%)
5
4
3
2
1
30Hz
70
30Hz
15 20 25 30 35
50 60
70
Ambient temperature ( ) Ambient humidity (%)
(°C)
(%)
33
MXZ-3HA50VF
Outdoor low pressure
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
Outdoor low pressure
Outdoor unit current (A)
OBH828
25-class unit 35-class unit
(MPa[Gauge])
1.4
14
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
40Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
40Hz
(°C)
70
(%)
Ambient temperature ( ) Ambient humidity (%)
(MPa[Gauge])
1.4
14
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
42-class unit 50-class unit
(MPa[Gauge])
1.4
14
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
40Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
40Hz
(°C)
70
(%)
Ambient temperature ( ) Ambient humidity (%)
(MPa[Gauge])
1.4
14
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
15 20 25 30 35
50 60
Ambient temperature ( ) Ambient humidity (%)
6
40Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
40Hz
(°C)
70
(%)
Ambient temperature ( ) Ambient humidity (%)
6
40Hz
70
5
4
3
2
1
(°C)
15 20 25 30 35
(%)
50 60
40Hz
(°C)
70
(%)
Ambient temperature ( ) Ambient humidity (%)
34
(2) HEAT operation
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
Outdoor unit current (A)
OBH828
Condition :
Indoor
Dry bulb temperature (°C)
Wet bulb temperature (°C)
20.0
14.5
Operation : TEST RUN OPERATION (Refer to 9-3.)
MXZ-2HA40VF
25-class unit
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
35-class unit
7
6
5
34Hz
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
MXZ-2HA50VF
25-class unit
7
6
35-class unit 42-class unit
7
6
34Hz
Outdoor
2
1
7
6
151220.0
14.5
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
MXZ-3HA50VF
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
34Hz
48Hz
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
35-class unit
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
34Hz
48Hz
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
42-class unit
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
48Hz
34Hz
50-class unit 25-class unit
7
6
5
4
3
2
0 5 10 15 20 25
Ambient temperature ( )
48Hz
35
10
OBH828
ACTUATOR CONTROL
MXZ-2HA40VF MXZ-2HA50VF
Relation between main sensor and actuator
Sensor Purpose
Discharge temperature thermistor Protection
Indoor coil temperature thermistor
Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Capacity code Control
Cooling: Coil frost prevention Heating: High pressure protection
Control/Protection Heating: Defrosting (Heater)
Cooling: Control/Protection
MXZ-3HA50VF
Relation between main sensor and actuator
Sensor Purpose
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Capacity code Control
Protection
Cooling: Coil frost prevention Heating: High pressure protection
Control/Protection Heating: Defrosting (Heater)
Cooling: Control/Protection
Compressor LEV
Compressor LEV
Actuator
Actuator
fan motor
Outdoor
fan motor
Outdoor
R.V. coil
4-way
valve
36
11
OBH828
SERVICE FUNCTIONS
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
11-1. THE POSITION OF SWITCH <MXZ-2HA40VF/2HA50VF>
SW1 SW2
ON
Outdoor display P.C. board
ON
1 2 3 4 5 6
<MXZ-3HA50VF>
SW871
CN750
CN751
Outdoor control P.C. board
11-2. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
With this function, once the operation mode is locked to either COOL/DRY mode or HEAT mode, the air conditioner operates in that mode only. Changing the setting is required to activate this function. Explain about this function to your customers and ask them whether they want to use it.
SW1
ON
1 2 3 4 5 6
SW2
ON
1 2 3 4 5 6
[How to lock the operation mode] (1) Turn OFF the power supply and make sure that the LED goes off. (2) Set SW1 as shown in the figure below. (3) Turn ON the power supply.
<MXZ-2HA40VF/2HA50VF> <MXZ-3HA50VF>
SW1 on the outdoor display P.C. board
Cool/Dry Heat SW1
ON
SW1
ON
SW1 on the outdoor control P.C. board
Cool/Dry Heat SW1
ON
5
6
SW1
ON
5
6
37
11-3.
SW1
OBH828
LOWERING THE OPERATING NOISE OF THE OUTDOOR UNIT
With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. However, note that the cooling and heating capacity may lower if this function is activated. Changing the setting is required to activate this function. Explain about this function to your customers and ask them whether they want to use it.
[How to lower the operating noise] (1) Turn OFF the power supply and make sure that the LED goes off. (2) Set "3" on SW1 to ON to enable this function. (MXZ-2HA40VF/2HA50VF) Set "5" on SW1 to ON the enable this function. (MXZ-3HA50VF) (3) Turn ON the power supply.
<MXZ-2HA40VF/2HA50VF> <MXZ-3HA50VF>
SW1 on the outdoor display P.C. board
ON
SW1 on the outdoor control P.C. board
SW1
ON
5
6
38
11-4. AUTOMATIC LINE CORRECTING
OBH828
<MXZ-2HA40VF/2HA50VF>
This outdoor unit has an automatic line correcting function which automatically detects and corrects improper wiring or piping.
<MXZ-2HA40VF/2HA50VF>
Improper wiring or piping can be automatically detected when one indoor unit is operated in COOL mode for 30 minutes. When improper wiring or piping is detected, wiring lines are corrected (A to B/ B to A) with the software.
NOTE: This function may not work due to the condition or environment of the unit, such as the following:
- gas leak, closed stop valve
- unit failure such as defective LEV
- indoor/outdoor temperature
NOTE: This function does not work when "2" on SW2 on the outdoor display P.C. board is turned OFF.
<Correct>
Terminal block
Liquid/ Gas pipe
Outdoor unit
<Incorrect wiring>
Terminal block
Liquid/ Gas pipe
Outdoor unit
<Incorrect piping>
Terminal block
Liquid/ Gas pipe
Outdoor unit
The record of automatic line correcting can be checked in the following way: (1) Turn OFF the power supply and make sure that the LED goes off. (2) Turn ON "3" on SW2 on the outdoor display P.C. board. (3) Turn ON the power supply. (4) Check the correction state with the LED lamps on the outdoor display P.C. board. (5) Turn OFF the power supply and make sure that the LED goes off. (6) Turn OFF "3" on SW2 on the outdoor display P.C. board. (7) Turn ON the power supply.
Number of blinks
LED1 (Red) LED2 (Yellow)
Once Once Not corrected
3 times 3 times Corrected
B A
Indoor unit B
B A
Indoor unit A
B A
Indoor unit B
B A
Indoor unit A
B A
Indoor unit B
B A
Indoor unit A
MXZ-2HA40VF/2HA50VF
Wiring line
SW2 on the outdoor display P.C. board
SW2
MXZ-2HA40VF/2HA50VF
SW2 on the outdoor display P.C. board
SW2
Indoor/outdoor connecting wire
Refrigerant pipe
39
<MXZ-3HA50VF>
OBH828
Outdoor unit has an auto line correcting function which automatically detects and corrects improper wiring or piping.
Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871). When improper wiring or piping is detected, wiring lines are corrected. This will be completed in about 10 to 15 minutes.
[How to activate this function]
1. Check that outside temperature is above 0˚C. (This function does not work when the outside temperature is 0˚C or below.)
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Check that the wiring between indoor and outdoor unit is correct. (If the wiring is not correct, this function does not work.)
4. Turn ON the power supply and wait at least 1 minute.
5. Press the piping/wiring correction switch (SW871) on the outdoor control P.C. board. Do not touch energized parts.
LED indication during detection:
LED1 (Red)
Lit
LED indication after detection:
LED1 (Red)
Lit
Once
Make sure that the valves are open and the pipes are not collapsed or clogged.
6. Press the switch to cancel.
LED indication after cancel :
LED1 (Red)
Lit
LED2 (Yellow)
Lit
LED2 (Yellow)
Not lit
Once
Other indications
LED2 (Yellow)
Lit
LED3 (Green)
Once
LED3 (Green)
Lit
Once
LED3 (Green)
Not lit
Result Completed (Problem corrected/ normal) Not completed (Detection failed) Refer to "SAFETY PRECAUTIONS WHEN LED BLINKS"
located behind the top panel.
NOTE: Indoor unit cannot be operated while this function is activated. When this function is activated while indoor unit is operating, the operation will be stopped. Operate indoor unit after the auto line correcting is finished. Pressing the switch during detection cancels this function.
The record of auto line correcting can be confirmed in the following way:
Press the switch for more than 5 seconds. LED will show the record of auto correcting for about 30 seconds as shown in the table below:
Number of blinks
LED1 (Red)
Once
3 times
NOTE: Activate this function to confirm the correct wiring after replacing the outdoor control P.C. board. (Previous records are deleted when the outdoor control P.C. board is replaced.) The record cannot be shown if auto line correcting is not canceled (Refer to "How to activate this function").
LED2 (Yellow)
Once
3 times
LED3 (Green)
Lit Lit
Wiring line
Not corrected Corrected
40
12
OBH828
TROUBLESHOOTING
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
12-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the unit rst with the remote controller, and after conrming
the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
<Incorrect>
Lead wiring
3. Troubleshooting procedure
1)
Check if the OPERATION INDICATOR lamp on the indoor unit is blinking on and off to indicate an abnormality. To
make sure, check how many times the OPERATION INDICATOR lamp is blinking on and off before starting service work
.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) Refer to 12-2, 12-3 and 12-4.
<Correct>
Connector housing
12-2. FAILURE MODE RECALL FUNCTION
This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (12-4.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit Refer to the service manual of indoor unit.
41
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH828
Operational procedure
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
1
With the remote controller headed towards the indoor unit, press the TEMPERATURE buttons to adjust the set temperature to 25°C. 2
Does the OPERATION INDICATOR lamp on the
indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the OPERATION INDICATOR lamp.
Yes (Blinks
The outdoor unit is abnormal. Check the blinking pattern, and make sure that the abnormal point with the table of outdoor unit failure mode recall function (12-2.3.). Make sure to check at least 2 consecutive blinking cycles.
3
)
No (OFF)
3
The outdoor unit is normal.
Release the failure mode recall function. 1
Release the failure mode recall function. 1
Repair the failure parts.
Delete the memorized abnormal condition. 1
Release the failure mode recall function. 1
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
1. Refer to the service manual of indoor unit.
2. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
3. Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
Blinking at 0.5-
second interval
Repeated cycle
42
3. Table of outdoor unit failure mode recall function
OBH828
MXZ-2HA
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit) OFF None (Normal) 2-time blink Outdoor power system Lit Lit Overcurrent protection cut-out operates
3-time blink Discharge temperature
4-time blink Overcurrent Once Not lit The overcurrent ows into intelligent
5-time blink Discharge temperature Lit Lit Discharge temperature exceeds 116ºC
Abnormal point
(Failure mode/protection)
thermistor Defrost thermistor Lit Once
Ambient temperature thermistor
Fin temperature thermistor Lit 3 times
P.C. board temperature thermistor
Outdoor heat exchanger temperature thermistor
Compressor Twice Not lit The overcurrent ows into intelligent
LED indication
(Outdoor P.C. board)
LED 1 LED 2
Not lit Not lit
Lit Once Thermistor shorts or opens during
Lit Twice
Lit 4 times • Replace the inverter P.C. board.
Lit 9 times • Refer to 12-6.
9 times Not lit Waveform of compressor current is dis-
3 consecutive times within 1 minute after the compressor gets started. Compressor protection cut-out operates 24 consecutive times within 10 seconds after the compressor gets started.
compressor running.
power module.
power module within 10 seconds after the compressor gets started. ( The compressor gets restarted in 15 seconds.)
torted.
during operation.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (12-4).
Condition Remedy
• Check the compressor connecting wire.
• Refer to 12-6. inverter/compressor".
• Check the stop valve.
• Refer to 12-6. door thermistors".
door thermistors".
• Check the compressor connecting wire.
• Refer to 12-6. inverter/compressor".
• Check the stop valve.
• Check the compressor connecting wire.
• Refer to 12-6. inverter/compressor".
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 12-6.
"How to check
"Check of out-
"Check of out-
"How to check
"How to check
"Check of LEV".
Indoor/
outdoor
unit failure
mode recall
function
○ ○ ○ ○ ○ ○
6-time blink High pressure Lit Lit The outdoor heat exchanger temperature
7-time blink Fin temperature 3 times Not lit The n temperature exceeds 90ºC
P.C. board temperature 4 times Not lit The P.C. board temperature exceeds
8-time blink Outdoor fan motor Lit Lit Failure occurs 3 consecutive times
9-time blink Nonvolatile memory data Lit 5 times Nonvolatile memory data cannot be read
Power module 7 times Not lit The output of the power module that
10-time blink Discharge temperature Lit Lit The discharge temperature is kept
11-time blink Current sensor 8 times Not lit The sensor circuit of current of
Bus-bar voltage 6 times Not lit The bus-bar voltage exceeds 430 V or
14-time blink Stop valve Lit 12 times The current of compressor is power
17 time blink Outdoor refrigerant system
abnormality
Lit 17 times A closed valve and air trapped in the
exceeds 70ºC during cooling or the indoor gas pipe temperature exceeds 70ºC during heating.
during operation.
80ºC during operation.
within 30 seconds after the fan gets started.
properly.
drove the compressor was shorted or the winding of the compressor was shorted.
under 50ºC (COOL mode)/40ºC (HEAT mode) for more than 40 minutes.
compressor shorts or opens during compressor operate.
falls to 50 V or below during compres­sor operating.
module is out of order.
refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
• Check the refrigerant circuit and the refrigerant amount.
• Check the stop valve.
Check the around outdoor unit.
• Check the outdoor unit air pas-
sage.
• Refer to 12-6.
door fan motor".
• Refer to 12-6.
door fan motor".
• Replace the inverter P.C. board.
• Refer to 12-6.
inverter/compressor".
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 12-6.
• Replace the inverter P.C. board.
• Check the power supply.
• Replace the inverter P.C. board.
• Check the stop valve.
• Check the refrigerant circuit and
the refrigerant amount.
Check for a gas leak in a connecting
piping etc.
• Check the stop valve.
• Refer to 12-6.
door refrigerant circuit".
"Check of out-
"Check of out-
"How to check
"Check of LEV".
"Check of out-
43
NOTE: Blinking patterns of this mode differ from the ones of
OBH828
MXZ-3HA
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
OFF None (Normal) Lit Lit 2-time blink Outdoor power system Lit Lit
3-time blink
4-time blink Overcurrent Once Not lit
5-time blink Discharge temperature Lit Lit
6-time blink High pressure Lit Lit
7-time blink Fin temperature 3 times Not lit
8-time blink Outdoor fan motor Lit Lit
9-time blink Outdoor control system Lit 5 times
10-time blink Low discharge temperature
11-time blink Communication error
15-time blink LEV and drain pump Lit Lit The indoor unit detects an abnormality in
Abnormal point
(Failure mode/protection)
Discharge temperature thermistor Defrost thermistor Ambient temperature thermistor Fin temperature thermistor P.C. board temperature thermis-
tor Outdoor heat exchanger tem-
perature thermistor
P.C. board temperature 4 times Not lit
protection
between P.C. boards
Current sensor Lit 7 times
Zero cross detecting circuit 5 times Not lit
Converter 5 times Not lit
Bus-bar voltage 5 times Not lit
LED indication
(Outdoor P.C.
board)
LED1 LED2
Overcurrent protection cut-out operates 3 con­secutive times within 1 minute after the com­pressor gets started, or converter protection cut-out or bus-bar voltage protection cut-out operates 3 consecutive times within 3 minutes
Lit Once Lit Once Lit Twice Lit 3 times Lit 4 times • Replace the outdoor control P.C.
Lit 9 times • Refer to 12-6.
Lit Lit
Lit 6 times
after startup. A thermistor shorts or opens during
compressor running.
21 A current ows into power module.
The discharge temperature exceeds 115°C during operation. Compressor can restart if discharge tempera­ture thermistor reads 80°C or less 3 minutes
.
later The outdoor heat exchanger temperature ex-
ceeds 70°C during cooling or the indoor gas pipe temperature exceeds 70°C during heating.
The n temperature exceeds 88°C during op­eration.
The P.C. board temperature exceeds 67°C during operation.
A failure occurs 3 consecutive times within 30 seconds after the fan gets started.
Nonvolatile memory data cannot be read prop­erly.
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes.
Communication error occurs between the out­door control P.C. board and outdoor power P.C. board for more than 10 seconds.
The communication between boards protec­tion cut-out operates 2 consecutive times.
A short or open circuit is detected in the cur­rent sensor during compressor operating.
Current sensor protection cut-out operates 2 consecutive times.
Zero cross signal cannot be detected while the compressor is operating.
The protection cut-out of the zero cross detecting circuit operates 10 consecutive times.
A failure is detected in the operation of the converter during operation.
The bus-bar voltage exceeds 400 V or falls to low level during compressor operating.
the LEV and drain pump.
Troubleshooting check table (12-4.).
Condition Remedy
• Check the connection of the com­pressor connecting wire.
• Refer to 12-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
• Refer to 12-6. "Check of outdoor thermistors".
board.
thermistors".
• Reconnect compressor connector.
• Refer to 12-6. verter/compressor".
• Check the stop valve.
• Check refrigerant circuit and refrig­erant amount.
• Refer to 12-6.
• Check refrigerant circuit and refrig­erant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 12-6. fan motor".
• Refer to 12-6. "Check of outdoor fan motor".
• Replace the outdoor control P
• Check refrigerant circuit and refrig­erant amount.
• Refer to 12-6.
• Check the connecting wire between outdoor control P.C. board and out­door power P.C. board.
• Check the connecting wire among outdoor control P.C. board and out­door power P.C. board.
• Check the voltage of power supply.
• Replace the outdoor power P.C. board.
• Check the voltage of power supply.
• Replace the outdoor control P.C. board.
• Refer to 12-6.
• Check the drain pump of the indoor unit.
"Check of outdoor
"How to check in-
"Check of LEV".
"Check of outdoor
.C. board.
"Check of LEV".
"Check of LEV".
Indoor/
outdoor unit
failure mode
recall function
44
12-3. INSTRUCTION OF TROUBLESHOOTING
OBH828
• Check the indoor unit referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit. Then, check the outdoor unit with referring to this page.
Operation start
Check the outdoor unit LED indicator.
Both LED1 and LED2 are OFF.
Both LED1 and LED2 are lighting.
LED1 or LED2 has blinked.
Refer to 12-6. "Check of power supply".
• Indoor unit
serial signal error Refer to 12-6. "How to check miswiring and serial signal error".
• COOL or
HEAT operation only Refer to 12-6. "Check of R.V. coil".
• When cooling, heat
exchanger of non-operating indoor unit frosts.
• When heating, non-
operating indoor unit gets warm. Refer to 12-6. "Check of LEV".
• When cooling
dew drops in the non-operating indoor unit. Check of mispiping.
Refer to 12-4. "Troubleshooting check table".
• When heating,
room does not get warm. Refer to 12-6. "How to check inverter/compressor".
Check mispiping,
shortage of capacity.
• When cooling,
room does not cool. Refer to 12-6. "How to check inverter/ compressor".
45
12-4. TROUBLESHOOTING CHECK TABLE
OBH828
MXZ-2HA
Symptom
No.
Outdoor unit
1
does not operate.
2
3
4
5
6
7
'Outdoor unit stops and restarts
8
3 minutes later' is repeated.
9
10
11
12
13
14
15
Outdoor unit operates.
16
17
18
Indication
LED1(Red) LED2(Yellow)
Lit Once
Lit Twice
Lit 3 times
Lit 4 times
5 timesLit
Lit 7 times
Lit 17 times
Twice Not lit
3 times Not lit
4 times Not lit
5 times Not lit
9 times Not lit
13 times
8 times Not lit
10 times
Once
Twice Lit
3 times
Not lit
Not lit
Lit
Lit
Abnormal point / Condition Remedy
LEV and drain pump
Outdoor power system
Discharge temperature thermistor
Fin temperature thermistor
P.C board temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Defrost thermistor
Nonvolatile memory data
Outdoor refrigerant system abnormality
Overcurrent
Discharge temperature protection
Fin temperature protection P.C. board temperature protection
High pressure protection
Bus-bar voltage protection
Outdoor fan motor
Current sensor protection
Compressor
Primary current protection
Secondary current protection
High pressure protection
Defrosting in cooling
Discharge temperature protection
The indoor unit detects an abnormality in the LEV and drain pump.
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
A short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 10 minutes of compressor startup.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
A short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor startup.
A short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes of compressor startup.
The nonvolatile memory data cannot be read properly.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
18 A current flows into intelligent power module.
Discharge temperature exceeds 116°C during operation. Compressor restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
The fin temperature exceeds 90°C during operation.
The P.C. board temperature exceeds 78°C during operation.
The outdoor heat exchanger temperature exceeds 70°C during cooling or indoor gas pipe temperature exceeds 70°C during heating.
The bus-bar voltage exceeds 430 V or falls to 50 V or below during compressor operating.
Failure occurs 3 consecutive times within 30 seconds after the fan gets started.
A short or open circuit is detected in the current sensor during compressor operating.
The compressor does not synchronize with the operating power.
The input current exceeds 10 A.
The current of the compressor exceeds 17 A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
The discharge temperature exceeds 100°C during operation.
Condition
• Refer to 12-6.
• Check the drain pump of the indoor unit.
• Check the connection of the compressor connecting wire.
• Refer to 12-6.
• Check the stop valve.
• Refer to 12-6.
• Refer to 12-6.
• Replace the inverter P.C. board.
• Refer to 12-6.
• Replace the inverter P.C. board.
• Check for a gas leak in a connecting piping etc.
• Check the stop valve.
• Refer to 12-6.
• Reconnect compressor connector.
• Refer to 12-6.
• Check the stop valve.
• Check the amount of gas and the refrigerant circuit.
can
• Refer to 12-6.
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 12-6.
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Replace the inverter P.C. board.
• Refer to 12-6.
• Replace the inverter P.C. board.
• Reconnect compressor connector.
• Refer to 12-6.
• Check the stop valve.
These symptoms do not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 12-6.
• Refer to 12-6.
"Check of LEV".
"How to check inverter/compressor".
"Check of outdoor thermistors".
"Check of outdoor thermistors".
"Check of outdoor thermistors".
"Check of outdoor refrigerant circuit".
"How to check inverter/compressor".
"Check of LEV".
"Check of outdoor fan motor".
"Check of outdoor fan motor".
"How to check inverter/compressor".
"Check of LEV".
"Check of outdoor thermistors".
19
4 times
Low discharge
Lit
temperature protection
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 50°C (COOL mode)/40°C (HEAT mode) for more than 40 minutes.
• Refer to 12-6.
• Check the refrigerant circuit and the refrigerant amount.
46
"Check of LEV".
Symptom
OBH828
No.
Outdoor unit operates.
20
Indication
LED1(Red) LED2(Yellow)
5 times
Lit
Abnormal point / Condition Remedy
Cooling high pressure protection
The outdoor heat exchanger temperature exceeds 58°C during operation.
Condition
This symptom does not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
21
Outdoor unit
22
operates normally.
23
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 12-7.4.
2. LED is lighted during normal operation. The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) The blinking frequency is “2”.
8 times
9 times
Lit
ON
2.5-second OFF 2.5-second OFF
OFF
Converter protection
Lit
Inverter check mode
Lit
Normal
Lit
A failure is detected in the operation of the converter during operation.
The connector of compressor is disconnected. Inverter check mode starts.
-
0.5-second ON
0.5-second ON
• Check the voltage of power supply.
• Replace the inverter P.C. board.
-
-
Outdoor display P.C. board (Parts side)
Lit
LED1
LED2
47
MXZ-3HA
OBH828
No. Symptom
1 Outdoor
unit does not operate.
2
3
4
5
6
7
8
9
10
11
12
13 Lit 15 times Relay operation No relay operation is detected during operation. • Replace the outdoor power P.C. board.
14 'Outdoor unit
stops and restarts 3 minutes later' is repeated.
15
16
17
18
19
20
21
Indication
LED1(Red) LED2(Yellow)
Lit Once LEV and drain pump
Lit Twice
Lit 3 times
Lit 4 times
Lit 5 times
Lit 6 times
Lit 7 times Outdoor control system
Lit 8 times Current sensor
Lit 11 times
Lit 12 times
Lit 13 times Current sensor
Lit 14 times Voltage sensor
Twice Not lit
3 times Not lit
4 times Not lit
5 times Not lit
6 times Not lit Pre-heating protection Overcurrent is detected during pre-heating.
8 times Not lit Converter protection
9 times Not lit
11 times Not lit
Abnormal point / Con-
dition
Outdoor power system
Discharge temperature thermistor
Fin temperature thermistor
P. C. board tempera­ture thermistor
Ambient temperature thermistor
Outdoor heat ex­changer temperature thermistor
Defrost thermistor
Zero cross detecting circuit (Outdoor control
.C. board)
P
Communication error between P.C. boards
communication
M-NET error
Zero cross detecting circuit (Outdoor power P.C. board)
IPM protection
Lock protection
Discharge temperature protection
Fin temperature protection
P.C. board temperature protection
High pressure protection
Bus-bar voltage protection
Low outside tempera­ture protection(cooling)
Condition Remedy
The indoor unit detects an abnormality in the LEV and drain pump.
Overcurrent protection cut-out operates 3 consecu tive times within 1 minute after the compressor gets started, or converter protection cut-out or bus­bar voltage protection cut-out operates 3 consecu­tive times within 3 minutes after startup.
short circuit is detected in the thermistor during
A operation, or an open circuit is detected in the ther mistor after 10 minutes of compressor startup.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
short circuit is detected in the thermistor during
A operation, or an open circuit is detected in the ther­mistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor startup.
short circuit is detected in the thermistor during
A operation, or an open circuit is detected in the ther­mistor after 5 minutes of compressor startup.
Zero cross signal cannot be detected. • Replace the outdoor control P.C. board.
The nonvolatile memory data cannot be read properly.
Current sensor protection cut-out operates 2 con secutive times.
The communication protection cut-out between boards operates 2 consecutive times.
M-NET adapter P.C. board detects an abnormality in the communication error.
The protection cut-out of the zero cross detecting circuit operates 10 consecutive times.
A short or open circuit is detected in the input cur rent detection circuit during operation.
A short or open circuit is detected in the input volt­age detection circuit during operation.
Overcurrent is detected after 30 seconds of com pressor startup.
Overcurrent is detected within 30 seconds of com pressor startup.
The discharge temperature exceeds 115°C during operation. Compressor can restart if discharge temperature thermistor reads 80°C or less 3 minutes later.
The n temperature exceeds during operation.
The P.C. board temperature exceeds during opera­tion.
High pressure is detected with the high pressure switch (HPS) during operation.
The outdoor heat exchanger temperature exceeds 70°C during cooling or the indoor gas pipe tem perature exceeds 70°C during heating.
A failure is detected in the operation of the convert­er during operation.
The bus-bar voltage exceeds 400 V or falls to low level during compressor operating.
The ambient became -12°C or less.
• Refer to 12-6.
• Check the drain pump of the indoor unit.
-
eck the connection of the compressor connect-
• Ch ing wire.
• Refer to 12-6. sor".
• Check the stop valve.
-
• Refer to 12-6.
• Refer to 12-6.
• Replace the outdoor control P
• Refer to 12-6.
• Replace the outdoor control P.C. board.
-
• Replace the outdoor power P
• Check the connecting wire between outdoor con­trol P.C. board and outdoor power P.C. board.
• Check the connecting wire between M-NET adapter P.C. board and outdoor control P.C. board, or terminal block.
• Replace the outdoor power P.C. board.
-
• Replace the outdoor power P.C. board.
• Replace the outdoor power P.C. board.
• Reconnect compressor connector
-
• Refer to 12-6.
compressor".
-
• Check the stop valve.
• Check the power module (PAM module).
• Check the amount of gas and refrigerant circuit.
• Refer to 12-6.
•Check refrigerant circuit and refrigerant amount.
•Refer to 12-6.
• Check around of gas and the refrigerant circuit.
• Check the stop valve.
-
• Reconnect compressor connector
• Refer to 12-6.
compressor".
• Check the power module.
• Replace the outdoor power P
• Check the voltage of power supply.
• Replace the outdoor power P.C. board or the out­door control P.C. board.
• Refer to 12-6.
"Check of LEV".
"How to check inverter/compres-
"Check of outdoor thermistors".
"Check of outdoor thermistors".
.C. board.
"Check of outdoor thermistors".
.C. board.
"How to check inverter/
"Check of LEV".
"Check of outdoor fan motor".
"How to check inverter/
"Check of bus-bar voltage".
.
.
.C. board.
48
No. Symptom
Outdoor control P.C. board
OBH828
22 'Outdoor unit
stops and restarts
23
3 minutes later' is
24
repeated.
25
26 Outdoor unit
operates.
27
28
29
30
31
32
Outdoor
33
unit operates normally.
34
35 Lit Lit Normal
NOTE 1. The location of LED is illustrated at the right figure. Refer to 12-7.1.
2. LED is lighted during normal operation. The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the blinking frequency is “2”.
ON
2.5-second OFF 2.5-second OFF
OFF
Indication
LED1(Red) LED2(Yellow)
13 times Not lit Outdoor fan motor
Lit 8 times
Lit 11 times
Lit 12 times
Once Lit
Twice Lit
3 times Lit
4 times Lit
5 times Lit
7 times Lit
11 times Lit
8 times Lit
9 times Lit Inverter check mode
Abnormal point / Con-
dition
A failure occurs 3 consecutive times within 30
Current sensor protec­tion
Communication between P.C. boards protection
Zero cross detecting circuit (Outdoor power P
.C. board)
Primary current protec tion
High pressure protec­tion
Defrosting in cooling
Discharge temperature protection
Low discharge temperature protection
Cooling high pressure protection
High Low Pressure bypass valve Cooling evaporating temperature drop prevention control
M-NET communication error
Cooling evaporating temperature protection
0.5-second ON 0.5-second ON
seconds after the fan gets started. A
short or open circuit is detected in the current
sensor during compressor operating. Communication error occurs between the outdoor
control P.C. board and outdoor power P.C. board for more than 10 seconds.
Zero cross signal cannot be detected while the compressor is operating.
­The input current exceeds 13.6 A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 50°C(COOL mode)/40°C(HEAT mode) for more than 40 minutes.
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes.
The outdoor heat exchanger temperature exceeds 58°C during operation.
During cooling operation, the temperature of indoor heat exchanger becomes 3°C or less within 1 hour after the compressor starts running, or it becomes less than 12°C - 16°C* later than that. * It depends on the difference between the set temperature and the room temperature.
M-NET adapter P.C. board detects an abnormality in the communication error.
During cooling operation, the temperature of indoor heat exchanger becomes 7°C - 11°C* or less within 1 hour after the compressor starts running, or it becomes 9°C - 17°C* or less later than that. * It depends on the indoor unit type/model or the
difference between the set temperature and the room temperature.
The unit is operated with emergency operation switch.
Condition Remedy
• Refer to 12-6.
• Replace the outdoor power P.C. board.
• Check the connecting wire between outdoor con trol P.C. board and outdoor power P.C. board.
• Replace the outdoor power P.C. board.
These symptoms do not mean any abnormality of the product, but check the following points.
• Check if indoor lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
• Check refrigerant circuit and refrigerant amount.
• Refer to 12-6.
• Refer to 12-6.
• Refer to 12-6.
• Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality of the product, but check the following points.
• Check if indoor lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
This symptom does not mean any abnormality of the product, but check the following points.
• Check the indoor lters are not clogged.
• Check there is sufcient refrigerant.
• Check the indoor/outdoor unit air circulation is not short cycled.
• Check the connecting wire between M-NET adapter P.C. board and outdoor control P.C. board, or terminal block.
This symptom does not mean any abnormality of the product.
"Check of outdoor fan motor".
-
"Check of LEV". "Check of outdoor thermistors".
"Check of LEV".
(Parts side)
LED2
LED1
Lit
49
12-5. TROUBLE CRITERION OF MAIN PARTS
W
OBH828
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
Part name Check method and criterion
Defrost thermistor (RT61) Fin temperature thermistor (RT64) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
Discharge temperature thermistor (RT62)
Compressor
RED
V
WHT
U
BLK
Outdoor fan motor
WHT
RED BLK
2 3
V
1
W
U
MXZ-2HA40VF/2HA50VF
Outdoor fan motor
MXZ-3HA50VF
Measure the resistance with a tester.
Refer to 12-7. "TEST POINT DIAGRAM AND VOLTAGE" 1. "Inverter P.C. board", 2. "Outdoor control P.C. board " or 3. "Outdoor power P.C. board" for the chart of thermis­tor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 12-7. "TEST POINT DIAGRAM AND VOLTAGE" 1. "Inverter P.C. board", 2. "Outdoor control P.C. board ", for the chart of thermistor.
Measure the resistance between terminals with a tester. (Winding temperature : -10°C - 40°C)
Normal (Each phase)
- 1.06
0.86
Measure the resistance between lead wires with a tester. (Part temperature : -10°C - 40°C)
Normal (Each phase)
32
- 43
Refer to 12-6.
.
R.V. coil
Linear expansion valve
WHT
RED
ORN
YLW
LEV
BLU
High pressure switch (HPS)
MXZ-3HA50VF
Measure the resistance with a tester. (Part temperature : -10°C - 40°C)
Normal
MXZ-2HA40VF MXZ-2HA50VF
1.2 k
- 1.56 k 1.26 k - 1.62 k
MXZ-3HA50VF
Measure the resistance with a tester. (Part temperature : -10°C - 40°C)
Color of lead wire Normal
WHT - RED RED - ORN
YLW - RED
37.4
- 53.9
RED - BLU
Pressure Normal
HPS
3.43 ± 0.15 MPa Close
4.14 ± 0.1 MPa Open
50
12-6. TROUBLESHOOTING FLOW
OBH828
Outdoor unit does not operate.
Check of power supply
MXZ-2HA40VF/2HA50VF
Check the main power supply circuit for proper connections.
Turn ON the power supply.
Is there voltage of 220 - 230 - 240 V AC in the power supply terminal block?
Yes
Is there voltage of 220 - 230 - 240 V AC between LD66B and X64 on the inverter P.C. board?
Yes
Is there voltage of 220 - 230 - 240 V AC between LD66A and LD70 on the inverter P.C. board?
Yes
Is there voltage of 311 - 339 V DC between DB61 and DB61 on the inverter P.C. board?
Is there voltage of 5 V DC between CN936 and CN936 on the outdoor display P.C. board?
Replace the outdoor display P.C. board.
+
Yes
Yes
-
MXZ-3HA50VF
No
No
No
No
No
Check the power supply and correct them.
Replace the inverter P.C. board.
Replace the reactor.
Replace the inverter P.C. board.
Check the connected wire between the inverter P.C. board and outdoor display P.C. board and correct it. Replace the inverter P.C. board.
Check the main power supply circuit for proper connections.
Turn ON the power supply.
Is there voltage of 220 - 230 - 240 V AC in the power supply terminal block?
Yes
Is the output voltage from the outdoor power P.C. board 311 - 339 V DC?
No
Turn OFF the power supply and recconnect the reactor.
Is the reactor short-circuited?
Yes
Replace the outdoor power P.C. board.
No
Check the power supply cable.
Yes
Replace the outdoor control P.C. board.
No
Replace the reactor.
51
replacing the indoor electronic control
• When the indoor unit does not operate, it cannot be operated either with the remote controller or with the
OBH828
EMERGENCY OPERATION switch.
• When the outdoor unit does not operate, the OPERATION INDICATOR lamp on the indoor unit blinks ON and OFF
every 0.5-second.
How to check miswiring and serial signal error (when outdoor unit does not work)
MXZ-2HA40VF/2HA50VF
LED indication for communication status
Communication status is indicated by the LED.
Unit status No
Blinking: normal communication
Lit: abnormal communication or not connected
NOTE: "Lit" and "Not lit" in the table below
does not indicate abnormal.
Outdoor display P.C. board
LED1 LED2
Blinking
LED 1 LED 2 Unit A Unit B status status
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2 ?
seYNot lit: The outdoor P.C. board is abnormal.
Press the EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Yes
Is serial signal error indicated 6 minutes later?
seY
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
No
Turn OFF the power supply.
Remove the indoor/out­door connecting wire from the outdoor terminal block connected with the indoor unit on which miswiring or the serial signal error is indicated. Short-circuit between S2 and S3 of the outdoor terminal block .
Check the power supply and correct the problem.
Replace the indoor electronic control P.C. board. *1
Is there rated voltage between outdoor terminal block S1 and S2?
oN
Check the indoor/outdoor
seY
connecting wire and correct the problem.
*1 Turn OFF the power supply before
P.C. board.
Refer to indoor unit service manual.
Check the indoor/outdoor
oNoN
connecting wire and correct the problem.
If the trouble sometimes occurs, possible causes are as follows:
• Poor connection of the indoor/ outdoor connecting wire Check for intermediate connection of the indoor/outdoor connecting wire, loose connection to the terminal block, and cut wire inside the cable. If any of them is found, correct the problem(s).
• Effects of the inverter lighting on the indoor unit If the trouble occurs or does not occur depending on whether the light is on or off, distance the lighting from the indoor unit or apply the glass filter on the receiving part of the indoor unit.
• Noise on the indoor/outdoor connecting wire Pass the indoor/outdoor connecting wire through a different route if the existing wiring is arranged as below:
• The indoor/outdoor connecting wire runs near the other equipment.
• The indoor/outdoor connecting wire is detoured and run long.
power supply cable of
Turn ON the power supply.
Does the LED on the outdoor display P.C. board or the outdoor control P.C. board repeat quick BLINKING and OFF? *2
No (Lighted or not lighted)
Replace the inverter P.C. board or the outdoor control P.C. board. *3 *4
52
*2 The LED indicates the status of serial communication. Check the communication status.
Replace the indoor
Yes
electronic control P.C. board. *1 *4
*1 Turn OFF the power supply before replacing the indoor electronic control P.C. board. Refer to indoor unit service manual. *3 Turn OFF the power supply before replacing the inverter P.C. board. Be careful of residual voltage of smoothing capacitor. *4 Remove the short-circuit between outdoor terminal block S2 and S3. Connect the indoor/outdoor connecting wire.
MXZ-3HA50VF
OBH828
LED indication for communication status
Communication status is indicated by the LED.
Unit status Blinking: normal communication Lit: abnormal communication or not connected
Pattern 1 and 2 is repeatedly displayed alternately. Each pattern is displayed for 10 seconds.
NOTE: "Lit" in the table below does not indicate abnormal communication.
Outdoor control P.C. board
Pattern
1
2
LED 1 LED 3LED 2
Unit A status
Unit C status
LED1 LED2
Blinking
LED3
Unit B status
Unit D status
Not lit
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Lit
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring.
B
Bridge the outdoor terminal block S2 and S3. 1
Yes
Yes
Yes
A
No
No
Check the power supply.
Check the wiring.
No
Is there any miswiring, poor contact, or wire
No
disconnection of the indoor/outdoor connecting wire?
No
1 Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.
Yes
Correct them.
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
Is serial signal error indicated 6 minutes later?
A
· Reinstall either the unit or the light away from each
No
other.
· Attach a filter on remote control receiving
Yes
B
section of the indoor unit.
Turn ON the power supply.
Does the LED on the outdoor control P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Yes
Turn OFF the power supply. Remove the bridge between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
Refer to indoor unit service manual.
Yes
Yes
No
No
No
(Lit or not lit)
Replace the outdoor control P.C. board.
2
2 Be careful of the residual
voltage of smoothing capacitor.
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Yes
Replace the indoor/outdoor connecting wire.
53
The cooling operation or heating operation does not operate.
OBH828
Check of R.V. coil
MXZ-2HA40VF/2HA50VF
• The heating operation does not operate.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in HEAT mode.
Is there voltage of 220 - 230 - 240 V AC between pin1 and pin2 at connector CN721?
Yes
Turn OFF the power supply. Disconnect the connector CN721.
Is there normal resistance to R.V. coil? (Refer to 12-5.)
Yes
Replace the 4-way valve.
• The cooling operation does not operate.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in COOL mode.
No
Replace the R.V. coil.
No
Connector MXZ-2HA
CN721 Inverter P.C. board
Replace the inverter P.C. board.
Is there voltage of 220 - 230 - 240 V AC between pin1 and pin2 at connector CN721?
No
Replace the 4-way valve.
Yes
Replace the inverter P.C. board.
54
MXZ-3HA50VF
OBH828
• When cooling operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in COOL mode.
Connector MXZ-3HA
CNAC CN712
CNAC2
Outdoor control P.C. board
Outdoor power P.C. board
Is there voltage of 220 - 230 - 240 V AC between pin1 and pin2 at connector CN712?
Yes
Turn OFF the power supply. Disconnect the connector CNAC2.
Is there normal resistance to R.V. coil? (Refer to 12-5.)
Yes
Replace the 4-way valve.
• When heating operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in HEAT mode.
Is there voltage of 220 - 230 - 240 V AC between pin1 and pin2 at connector CN712?
Yes
No
Replace the R.V. coil.
No
Is there voltage 220 - 230 - 240 V AC between the pin1 and pin3 at connector CNAC?
Replace the outdoor control P.C. board.
No
Replace the 4-way valve.
Yes
Replace the outdoor
No
power P.C. board.
Replace the outdoor control P.C. board.
55
• When cooling, heat exchanger of non-operating indoor unit frosts.
OBH828
• When heating, non-operating indoor unit gets warm.
Check of LEV
Turn ON the power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard? Or, do you feel vibration of LEV coil with your hand?
No
Disconnect the connectors. CN724: LEV A, CN725: LEV B (MXZ-2HA) CN791: LEV A, CN792: LEV B, CN793: LEV C (MXZ-3HA), CN797: LEV R (MXZ-3HA) Is there normal resistance to LEV coil? (Refer to 12-5.)
No
Replace LEV coil.
Yes
Yes
Replace the outdoor control P.C. board.
Normal
Connector MXZ-2HA MXZ-3HA
Inverter P.C. board
Outdoor control P.C. board
56
• When heating, room does not get warm.
OBH828
• When cooling, room does not get cool.
How to check inverter/compressor
Disconnect the terminal of the compressor or the connector (CNMC) between the compressor and the outdoor power P.C. board.
start EMERGENCY OPERATION.
Measure the voltage between each lead wire leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Output voltage: Is proper output voltage detected? 1, 2
50V-250V
Yes
Is output balanced?
Yes
(Except MXZ-2HA) Is the input voltage to the outdoor control P.C. board 370 V or more?
3 minutes after the power supply is turned ON,
1 • After the outdoor fan starts running, wait for 1 minute or more before measuring the voltage.
• The output voltage values have the tolerance of ± 20%. 2 • The output differs depending on the capacity or the number of indoor units to be operated.
No
No
No
Replace the outdoor power P.C. board.
Yes
Turn OFF the power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is the resistance between each terminal normal? (Refer to 12-5.)
Yes
Reconnect the lead wire of compressor, and turn ON the power supply to indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor layer short 10 to 60 seconds: compressor lock 60 seconds to 5 minutes: refrigerant circuit defective 5 minutes or more: normal
No
Replace the compressor.
57
• When thermistor is abnormal.
OBH828
Check of outdoor thermistors
Disconnect the connector in the following table and measure the resistance of the thermistor to check whether the thermistor is normal or not. (Refer to 12-7.)
Normal
Reconnect the connector in the following table and disconnect the lead wire leading to the compressor. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION.
Does the unit operate 10 minutes or more without showing thermistor abnormality?
Yes
Normal
MXZ-2HA40VF MXZ-2HA50VF
Thermistor Defrost Discharge temperature Fin temperature Ambient temperature Outdoor heat exchanger temperature
MXZ-3HA50VF
Thermistor Defrost Discharge temperature Outdoor heat exchanger temperature Ambient temperature Fin temperature
Symbol
RT61 RT62 RT64 RT65 RT68
Symbol
RT61 RT62 RT68 RT65 RT64
Abnormal
No
Connector, Pin No. CN641 pin1 and pin2 CN641 pin3 and pin4 CN642 pin1 and pin2 CN643 pin1 and pin2 CN644 pin1 and pin3
Connector, Pin No. Between CNTH1 pin1 and pin2 Between CNTH1 pin3 and pin4 Between CNTH1 pin7 and pin8 Between CNTH2 pin1 and pin2 Between CN171 pin1 and pin2
Replace the thermistor except RT64. If RT64 is abnormal, replace the outdoor power P.C. board since RT64 is combined with this board.
Replace the outdoor control P.C. board or the outdoor power P.C. board.
Board
Inverter P.C. board
Board
Outdoor control P.C. board
Outdoor power P.C. board
58
• Fan motor does not operate or stops operating shortly after starting the operation.
Disconnect CN932 and measure the resistance of the outdoor fan motor.
Turn ON the breaker. Rotate the outdoor fan motor manually and measure the voltage of CN931. Between (+) and (-) Between (+) and (-) Between (+) and (-)
Is the resistance of outdoor fan motor normal? (Refer to 12-5.)
Does the outdoor fan motor rotate smoothly?
Does the voltage between each terminal become 5 V DC and 0 V DC repeatedly?
Replace the outdoor fan motor.
Replace the inverter P.C. board or the outdoor control P.C. board.
No
Yes
Yes
No
Yes
No
OBH828
Check of outdoor fan motor
MXZ-2HA40VF/2HA50VF
Connector MXZ-2HA
Inverter P.C. board
59
MXZ-3HA50VF
OBH828
Disconnect CNF1 and measure the resistance of the outdoor fan motor.
Is the resistance of outdoor fan motor normal? (Refer to right table.)
Yes
Does the outdoor fan motor rotate smoothly?
Yes
Turn on the power supply to start operation and measure the voltage of connector CNF1.
Is the voltage of connector CNF1 normal? (Refer to right table.)
Yes
Turn OFF the power supply and connect the connector CNF1. Turn ON the power supply and measure the voltage of connector CNF1 while rotating the motor by the hand.
Connector MXZ-3HA
No
Replace the outdoor fan motor.
No
Replace the outdoor fan motor.
CNF1
pin1 - pin4
pin5 - pin4
pin6 - pin4
* To measure the voltage, connect the negative (-) end of the tester to pin4. * Voltage between pin4 and pin6 should be measured within 1 minute after the operation starts.
No
Replace the outdoor control P.C. board.
Voltage
325 V DC
15 V DC
1 - 5 V DC
Measuring points
pin1 - pin4
pin5 - pin4
pin6 - pin4
pin7 - pin4
* To measure the resistance, connect the negative (-) end of the tester to pin4.
CNF1
Outdoor control
P.C. board
Resistance
60 kΩ
160 kΩ
Does the voltage between pin7 and pin4 of connector CNF1 repeat 0 V and 5 V?
Yes
Start operation.
Does the fan motor operate for about 5 seconds?
Yes
Replace the outdoor control P.C. board.
No
Replace the outdoor fan motor.
No
Replace the outdoor fan motor.
60
• When the operation frequency does not go up from the lowest frequency.
OBH828
Check of HPS
Connector MXZ-3HA
CN63H
MXZ-3HA50VF
1. Disconnect the connector CN63H in the outdoor control P.C. board.
2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned OFF.
Outdoor control P.C. board
Check the resistance between each terminal.
0 Ω
Reconnect CN63H. Turn ON the power supply to the indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed immediately after compressor starts?
No
Normal
Yes
Infinity
Replace the outdoor control P.C. board.
Replace HPS.
The other cases
Indoor unit does not operate. (different operating models in multi system)
• When you try to run 2 indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal to
the outdoor units rst decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas
continuously ows into the indoor unit even while it is not operating.
Check of bus-bar voltage
MXZ-3HA50VF
•Check the voltage of power supply.
Conrm outdoor unit failure mode
recall function. (Refer to 12-2.2.)
Conrm LED1 indication lamp on the outdoor control P.C. board.
Blink 5 times
Replace the outdoor power P.C. board.
Turn ON power supply. Start operation.
Conrm LED1 indication lamp on the outdoor control P.C.
board.
Blink 9 times
Replace the outdoor control P.C. board.
Turn OFF power supply before removing P.C. board.
Lighting Lighting
Normal
Lighting
Replace the outdoor control P.C. board.
Turn ON power supply. Start operation.
Conrm LED1 indication lamp on the outdoor control P.C.
board.
Blink 9 times
Replace the outdoor power P.C. board.
61
Check of outdoor refrigerant circuit
OBH828
MXZ-2HA40VF/2HA50VF
Has the operation stopped during pump down?
Yes
The operation has stopped to pre­vent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the power sup­ply OFF.
CAUTION : Do not start the operation again to prevent hazards.
No
Was the operation started with the stop valve closed, and was it opened during operation?
No
The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from,
and x the leak.
The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and
Yes
start the cooling operation again.
62
12-7. TEST POINT DIAGRAM AND VOLTAGE
OBH828
1. Inverter P.C. board
MXZ-2HA40VF MXZ-2HA50VF
Back side of unit
220-230-240 V AC (LD66A, LD70)
Output to drive outdoor fan
Output to drive compressor
(LDU, LDV, LDW) motor (CN932)
280 - 370 V DC (DB61(+), (-))
Fin temperature thermistor/RT64 (CN642)
FUSE (F901) T3.15AL250V
Signal of outdoor fan motor (CN931)
Ambient temperature thermistor /RT65 (CN643)
Smoothing capacitor (C61, C62, C63)
Outdoor heat exchanger temperature thermistor /RT68 (CN644)
Discharge temperature thermistor/RT62 (CN641)
Defrost thermistor/RT61 (CN641)
FUSE (F801) T3.15AL250V
R.V. coil (CN721)
Heater (CN722)
FUSE (F701) T3.15AL250V
LEV A coil
LEV B coil
(CN724)
(CN725)
220-230-240 V AC (X64 , LD66B)
Connect to outdoor dis­play P.C. board (CN935)
220-230-240 V AC (LD61, LD62)
220-230-240 V AC
(CN601 , ) Serial signal A
(CN601 , ) Serial signal B (CN601
CN602 )
,
Front side of unit
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
Resistance(k )
20
10
0
-20 -10 0 10 20 30 40
Temperature (°C)
Resistance (kΩ)
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
200
100
0
0 10 20 30 40 50 60 70 80 90 100 110 120
63
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
Resistance(k )
40
20
0
0 10 20 30 40 50 60 70 80
Temperature (°C)Temperature (°C)
Discharge temperature thermistor (RT62)
2. Outdoor control P.C. board
OBH828
MXZ-3HA50VF
CN741 Signal translation (
To Communication
adaptor board
VFG (Rotate signal) (Voltage between right pins of PC931, pin 3 and pin 4) (Correspond to
(CNF1 (+)- (−))
VSP (Rotate instruction) (Voltage between pins of C930): 0 V DC (when stopped),
1.8 - 6.5 V DC (when operated) (Same as
(CNF1 (+)- (−))
CNF1
To fan motor Bus-bar voltage 290 - 370 V DC
15 V DC
Rotate instruction (Constant voltage)
Rotate signal (Pulse wave)
CNDC Bus-bar voltage 290 - 370 V DC
220 - 230 - 240 V AC
)
CN601
Serial signal 12 ~ 24 V
Room B
Room A
Input
Room C
)
CN611
Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
100
90
80
70
60
50
Resistance (kΩ)
40
30
20
10
0
-20 -10 0 10 20 30 40 (ºC)
Temperature
Thermistor R25 = 10 k ± 2% B constant = 3950 ± 2%
Rt = 10exp{3950( )}
F711 FUSE T3.15AL250V
CNAC to outdoor power P.C. board
220 - 230 - 240 V AC
Input
CN714 Defrost heater
220 - 230 - 240 V AC
Output
CN713 Valve coil
220 - 230 - 240 V AC
Output
273+t1298
1
CN63H High pressure switch
CN702 Signal transmission (To power board) 5 V DC pulse wave
(+)
15 V
(-) (-)
15 V
(-)
CN701 Signal transmission (To power board) 5 V DC pulse wave
CNTH2 Ambient temperature thermistor (RT65)
CNTH1
Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62)
Defrost thermistor (RT61)
SW1
SW871
SW2
CN793 LEV Room C CN797 LEV Room R
(-)
(+)
CN791 LEV Room A CN792 LEV Room B
LEV: 12 V DC pulse wave
(
800
LED3
LED2
LED1
700
600
500
400
300
Resistance(k )
200
100
0
0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature( )
Thermistor R100 = 13.36 k ± 2% B constant = 4014 ± 2%
Rt = 13.36exp{4014( )}
273+t1373
1
64
3. Outdoor power P.C. board
OBH828
MXZ-3HA50VF
(+)
CN151 Signal transmission (To Outdoor control P.C. board)
15 V (-)
5 V DC pulse wave
(-) 15 V
Output to drive compressor
Connect to reactor (Red line)
Connect to reactor (White line)
CN171 Fin temperature thermistor (RT64)
CNDC Bus-bar voltage 290 - 370 V DC
Connect to earth
-
)
(
CN152 Signal Transmission
(+)
(From Outdoor Control P.C. board) 5 V DC pulse wave
Connect to earth
CNAC2 220-230-240 V AC Output
F1 FUSE T6.3AL250V
220-230-240 V AC Input
F2 FUSE T6.3AL250V
CNAC1 220-230-240 V AC Output
4. Outdoor display P.C. board
MXZ-2HA40VF MXZ-2HA50VF
To inverter P.C. board (CN936)
Fin temperature thermistor (RT64)
200
180
160
140
120
100
80
Resistance (kΩ)
60
40
20
0
0 10 20 30 40 50 60 70 80
Temperature
Thermistor R50 = 17 k ± 2%
)
GND5V
LED2LED1
SW1
SW2
B constant = 4150 ± 3%
Rt = 17exp{4150( )}
273+t1323
(°C)
1
65
13
OBH828
DISASSEMBLY INSTRUCTIONS
<Detaching method of the terminal with locking mechanism>
The terminal which has the locking mechanism can be detached as shown below. There are following 2 types of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with the connector shown below
Sleeve
has the locking mechanism.
Slide the sleeve. Pull the terminal while
Locking lever
pushing the locking lever.
13-1. MXZ-2HA40VF MXZ-2HA50VF
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet and the panels
(1) Remove the screws fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor connect-
ing wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 2
Photo 1
Hold the sleeve, and pull out the terminal slowly.
Connector
: Indicates the visible parts in the photos. : Indicates the invisible parts in the photos.
Screws of the top panel
Direction to remove
Screws of
the cabinet
Screws of the back panel
66
Photo 3
Hooks
Screws of Service panel
Screws of the back panel
OPERATING PROCEDURE PHOTOS
OBH828
2. Removing the inverter assembly and the inverter
P.C. board
(1) Remove the service panel, the top panel and the cabinet
(Refer to 1).
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire and remove the back panel (Refer to section 1).
(3) Disconnect all connectors and lead wires on the inverter
P.C. board. (4) Remove the compressor connector (CNMC). (5) Remove the screws fixing the heat sink support and the
separator. (6) Remove the screws of the terminal block support and the
back panel. (Photo 2) (7) Remove the inverter assembly. (8) Remove the screw of the earth wire and screws of the ter-
minal block support. (9) Remove the hooks of the heat sink support and remove
the heat sink support from the P.C. board support. (
10
) Remove the screw fixing the inverter P.C. board and
remove the inverter P.C. board from the P.C. board sup-
port.
3. Removing the R.V. coil
(1) Remove the service panel, the top panel and the cabinet
(Refer to section 1).
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire and remove the back panel (Refer to section 1).
(3) Remove the inverter assembly (Refer to section 2). (4) Remove the R.V. coil.
Photo 4
Screws of the heat sink support and the separator
Photo 5
Compressor
Reactor (ACL2)
connector
Inverter assembly
Screws of the terminal block support
4. Removing the discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor
(1) Remove the service panel, the top panel and the cabinet (Refer to section 1). (2) Disconnect the power supply and indoor/outdoor connect-
ing wire and remove the back panel (Refer to section 1). (3) Remove the inverter assembly (Refer to section 2). (4) Pull out the discharge temperature thermistor from its
holder. (5) Pull out the defrost thermistor from its holder (Photo 7). (6) Pull out the outdoor heat exchanger temperature thermis-
tor from its holder (Photo 7).
P.C. board support
Hooks of the heat sink support
Photo 6
Discharge temperature thermistor (RT62)
67
Screw of the earth wire
Screw of the inverter
P.C. board
Reactor (ACL)
R.V. coil
OPERATING PROCEDURE PHOTOS
OBH828
5. Removing the outdoor fan motor
(1) Remove the service panel, the top panel and the cabinet
(Refer to section 1).
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire. (3) Disconnect the connectors for outdoor fan motor. (4) Remove the propeller fan nut. (5) Remove the propeller fan. (6) Remove the screws fixing the fan motor. (7) Remove the fan motor.
6. Removing the compressor and the 4-way valve
(1) Remove the service panel, the top panel and the cabinet (Refer to section 1).
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire and remove the back panel (Refer to section 1). (3) Remove the inverter assembly (Refer to section 2). (4) Recover gas from the refrigerant circuit.
Photo 7
Outdoor heat exchanger temperature thermistor (RT68)
Photo 8
Screws of the fan motor
Defrost thermistor (RT61)
Base heater ( only)
NOTE: Recover gas from the pipes until the pressure gauge
2
shows 0 kg/cm
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the nuts of compressor legs. (7) Remove the compressor. (8) Detach the brazed part of pipes connected with 4-way
valve.
(0 MPa).
Photo 10
Discharge pipe brazed part
Suction pipe brazed part
Photo 9
Propeller fan
Propeller fan nut
Compressor nuts
Brazed parts of 4-way valve
68
13-2. MXZ-3HA50VF
OBH828
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet and the panels
(1) Remove the screws of the service panel, and remove the
service panel.
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire.
(3) Remove the screws of the top panel, and remove the top
panel.
(4) Remove the screws of the cabinet, and remove the cabi-
net.
(5) Remove the screws of the back panel, and remove the
back panel (Photo 3).
Photo 3
Screw of the rear guard
Photo 1
Screws of the sub panel
Screws of the cabinet
Photo 2
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screws of the cabinet
Screws of service panel
Screws of the sub panel
Screws of the back panel
Screws of the back panel
Screws of the back panel
Screws of the cabinet
69
OPERATING PROCEDURE PHOTOS
OBH828
2. Removing the outdoor control P.C. board, the out­door power P.C. board and the reactor
(1) Remove the service panel (Photo 1). (2) Disconnect the power supply and indoor/outdoor con-
necting wire.
(3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3).
(4) Disconnect all connectors and lead wires on the outdoor
control P.C. board.
(5) Unhook the catches of the outdoor control P.C. board,
and remove the outdoor control P.C. board.
(6) Remove the screws of the electrical box assembly,
unhook the catches of the electrical box assembly, and remove the electrical box assembly.
(7) Remove the screws of outdoor control P.C. board holder,
and remove the outdoor control P.C. board holder.
(8) Remove the screws of the reactor, and remove the reac-
tor.
(9) Remove the screws of the reactor bed, and remove the
reactor bed.
(
10
) Remove the screws of the heat sink support, and remove
the heat sink support.
(
11
) Remove the screws fixing the outdoor power P.C. board.
(
12
) Disconnect all connectors and lead wires on the outdoor
power P.C. board.
Photo 4
Electrical box assembly
Screws of the electrical box assembly
Catch of the electrical box assembly
Photo 5
Catches of the outdoor control P.C. board
Photo 7
Screws of the outdoor power P.C. board
Screws of the outdoor control P.C. board holder
Photo 6
Screw of the heat sink support
Screw of the reactor bed
Screws of the reactor
Heat sink support
Screws of the outdoor control P.C. board holder
Screws of the reactor bed
70
OPERATING PROCEDURE PHOTOS
OBH828
3. Removing the fan motor
(1) Remove the service panel (Photo 1). (2) Disconnect the power supply and indoor/outdoor connect-
ing wire.
(3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3).
(4) Disconnect connectors CN712, CNF1, CNTH1, CNTH2,
CN63H, CN791, CN792, CN793, CN797 on the outdoor control P.C. board and disconnect the relay connector of the compressor lead wire.
(5) Remove the screws of the electrical box assembly, and
remove the electrical box assembly (Photo 4). (6) Remove the propeller fan. (7) Remove the fan motor.
4. Removing the compressor and the 4-way valve
(1) Remove the service panel (Photo 1). (2) Disconnect the power supply and indoor/outdoor connect-
ing wire. (3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3). (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm (5) Disconnect the outdoor control P.C. board connectors: CN712, CNF1, CNTH1, CNTH2, CN63H, CN791,CN792,
CN793, CN797. (6) Disconnect the compressor lead wire from the terminal of the compressor (U, V, W). (7) Remove the screws of the electrical box assembly, and
remove the electrical box assembly (Photo 4). (8) Remove the propeller fan. (9) Remove the sound proof felt *1, *2.
NOTE: Before removing the sound proof felt, remove
the hook-and-loop fastener of the top felt by the power receiver.
(
10
) Remove the screws of the separator, and remove the
separator. (
11
) Detach the brazed parts of the compressor suction and
discharge pipes. (
12
) Remove the compressor nuts and remove the compres-
sor. (
13
) Detach the brazed parts of the 4-way valve and pipe.
2
(0 MPa).
Photo 8
Propeller fan
Photo 9
Photo 10
R.V. coil
Screws of the outdoor fan motor
Propeller fan nut
4 way valve
Separator
Hook-and-loop fastener
Sound proof felt *1
LEV coil E
Expansion valve E
Discharge pipe brazed part
Suction pipe brazed part
Sound proof felt *2
Power receiver
Discharge temperature thermistor (RT62)
Compressor nuts
71
OPERATING PROCEDURE PHOTOS
5. Removing the expansion valve
(1) Remove the service panel (Photo 1). (2) Remove the top panel, the cabinet, and the back
panel (Photo 1, 2, 3).
(Gas recovery is not required if the unit is pumped
down.)
(3)
Remove the electrical parts for removing LEV R (Photo 4,
8). (4) Remove the LEV coils. (5) Detach the brazed parts of expansion valves and
pipes.
Photo 11
R.V. coil
Photo 12
Outdoor heat exchanger temperature thermistor (RT68)
4-way valve
Brazed parts
Ambient temperature thermistor (RT65)
LEV coils
Defrost thermistor (RT61)
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2018 MITSUBISHI ELECTRIC CORPORATION
Published: Dec. 2018. No.OBH828 Made in Japan Specifications are subject to change without notice.
72
Expansion valves
Loading...