Capacity Rated frequency(Min.-Max.)
Dehumidification
Air flow ✽1
Power outlet
Running current ✽1
(Total)
Power input ✽1
(Total)
Power factor ✽1
(Total)
Starting current ✽1
(Total)
Compressor motor current ✽1
Fan motor current ✽1
Model
Output
Fan motor Model
Dimensions WOHOD
Weight
Sound level ✽1
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R410A)
Refrigeration oil (Model)
kW
r/h
K /h
A
A
W
%
A
A
A
✽1
(Total)
W
mm
kg
dB(A)
rpm
kg
cc
Compressor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
Electrical
data
MUZ-GC35VA
MUZ-GC25VAH
MUZ-GC35VAH
Single phase
230V,50Hz
10
320 (NEO22)
SPECIFICATION
NOTE : Test conditions are based on ISO 5151
Cooling : IndoorDry-bulb temperature 27:Wet-bulb temperature 19:
Heating : IndoorDry-bulb temperature 20:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency
Outdoor Dry-bulb temperature 35:
Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6:
3
Page 4
Model
Item
Current
transformer
Smoothing
capacitor
Diode module
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
12
Page 13
8PERFORMANCE CURVES
MUZ-GC25VAMUZ-GC35VA
MUZ-GC25VAHMUZ-GC35VAH
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°C WB
(2) Indoor outlet air wet-bulb temperature :°C WB
(3) Outdoor intake air dry-bulb temperature :°C DB
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°C DB
(6) Outdoor intake air wet-bulb temperature :°C WB
(7) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating
INDOOR UNIT
Wet and dry-bulb
thermometers
8-1. Capacity and input curves
1.5
12.7
8.1
1.4
11.6
7.5
10.6
6.8
6.3
5.7
5.1
difference (degree)
4.5
Indoor air Wet-bulb temperature
1.3
9.6
1.2
8.7
1.1
7.8
1.0
6.9
0.9
Capacity correction factor
18 202530354046
Indoor intake air Wet-bulb temperature (:)
OUTDOOR UNIT
Wet and dry-bulb
thermometers
Cooling capacity
26
24
22
20
18
at Rated frequency
MUZ-GC35VA
MUZ-GC25VAH
MUZ-GC25VA
MUZ-GC35VAH
13
Page 14
Indoor air Wet-bulb temperature
difference (degree)
MUZ-GC25VAH
6.8
6.3
5.7
5.1
4.5
4.0
10.6
9.6
8.7
7.8
6.9
6.0
MUZ-GC35VAH
MUZ-GC25VA
MUZ-GC35VA
at Rated frequency
at Rated frequency
input correction factor
Outdoor intake air Dry-bulb temperature (:)
18 202530354046
0.8
0.9
1.0
1.1
1.2
1.3
Total input (cooling)
22
20
18
Indoor intake air Wet-bulb temperature (
:)
26
24
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
27.5
25.4
23.3
21.2
19.1
16.9
14.8
12.7
10.6
8.5
Indoor air Dry-bulb temperature
difference (degree)
at Rated frequency
at Rated frequency
MUZ-GC35VAH
MUZ-GC25VAH
MUZ-GC35VA
MUZ-GC25VA
Outdoor intake air Wet-bulb temperature (:)
-20-15-10-5051015
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity
Capacity correction factor
15
20
26
Indoor intake air Dry-bulb tem
perature (
:
)
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
27.5
25.4
23.3
21.2
19.1
16.9
14.8
12.7
10.6
8.5
Indoor air Dry-bulb temperature
difference (degree)
at Rated frequency
at Rated frequency
MUZ-GC35VAH
MUZ-GC25VAH
MUZ-GC35VA
MUZ-GC25VA
Outdoor intake air Wet-bulb temperature (:)
-20-15-10-5051015
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input(heating)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature (
:)
NOTE:The above broken lines are for the heating operation without any frost and
defrost operation.
14
Page 15
8-2. Capacity and input correction by operational frequency of compressor
MUZ-GC25VA
MUZ-GC25VAH
Correction of Cooling capacity
1.5
Correction of Cooling total input
1.5
Correction of Heating capacity
2.0
Correction of Heating total input
2.0
1.0
0.5
Capacity correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
MUZ-GC35VA
MUZ-GC35VAH
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
1.0
0.5
Input correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
1.5
1.0
0.5
Capacity correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100 150(Hz)
The operational frequency of compressor
8-3. Test run operation (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor
varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
15
Page 16
kgf/F [Gauge]
MPa [Gauge]
18
32152050256030
70 (%)
35(˚C)
3230
70 (%)
35(˚C)
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14
1.4
Ambient temperature(˚C)
Ambient humidity(%)
Outdoor low pressure
MUZ-GC25VAH
Ambient temperature(˚C)
Ambient humidity(%)
15205025
60
2
3
4
5
6
18
MUZ-GC25VAH
MUZ-GC25VA
MUZ-GC25VA
MUZ-GC35VAH
MUZ-GC35VAH
MUZ-GC35VA
MUZ-GC35VA
kgf/F [Gauge]
MPa [Gauge]
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14
1.4
15205025
60
2
2.5
3
3.5
4
18
(A)(A)
Outdoor unit current
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
18
32152050256030
70 (%)
35(˚C)
3230
70 (%)
35(˚C)
(A)(A)
Ambient temperature(˚C)
Ambient temperature(˚C)
MUZ-GC25VAH
MUZ-GC25VA
MUZ-GC35VAH
MUZ-GC35VA
Outdoor unit current
3.0
2.5
2.0
1.5
1.0
0.5
0.0
2
5101520 25(:)
3.0
2.5
2.0
1.5
1.0
0.5
0.0
2
5101520 25(:)
8-4. Outdoor low pressure and outdoor unit current
Dry bulb temperature (°C)
Indoor
20.0
14.521
Outdoor
7
6
151220.0
14.5
Wet bulb temperature (°C)
COOL operation
1 Both indoor and outdoor unit are under the
same temperature/humidity condition.
2 Operation : TEST RUN OPERATION (refer to 8-3.)
Dry-bulb temperature(:)
20
25
3070
NOTE :
The unit of pressure has been
changed to MPa on the international system of units (SI unit system).
The conversion factor is:
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-2. R.V. coil control
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
ON
OFF
OFF
9-3. Relation between main sensor and actuator
22
Page 23
10
Housing point
SERVICE FUNCTIONS
MUZ-GC25VAMUZ-GC35VA
MUZ-GC25VAHMUZ-GC35VAH
10-1. CHANGE IN DEFROST SETTING
<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.
(Refer to 11-6-1.)
Jumper wire
(Initial setting)
JS
soldered
none
(cut)
Defrost finish temperature (:)
MUZ-GC25VA
MUZ-GC35VA
5
8
MUZ-GC25VAH
MUZ-GC35VAH
8
15
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°C
or below. When pre-heat control is turned ON, compressor is energized. (about 50 W)
MUZ-GC25 <JK> When the JK wire of the inverter P.C. board is cut, pre-heat control is activated.(Refer to 11-6.1)
MUZ-GC35 Inverter P.C.board needs to changed.
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
11
TROUBLESHOOTING
MUZ-GC25VAMUZ-GC35VA
MUZ-GC25VAHMUZ-GC35VAH
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
4) Refer to 11-2. and 11-3.
23
Page 24
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycleRepeated cycle
ON
OFF
No beepBeeps
Repeated cycle
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF3-second ON
Blinking at 0.5second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5second interval
No beepBeeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5second interval
Repeated cycle
Beeps
Does upper lamp of OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5
seconds?
Blinks: Either indoor or outdoor unit is abnormal.
Beep are emitted at the same timing
as the blinking of upper lamp of
OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does upper lamp of
OPERATION INDICATOR lamp stay ON for 3
seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the indoor unit
failure mode table (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply.
<
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time, press
RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some
abnormalities that can't be recalled with this way.
Confirm if outdoor unit is abnormal according to the detailed outdoor
unit failure mode recall function.(Refer to 11-2.2)
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table (Refer to 11-2.3).
Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short
beep is emitted once the signal is received.
11-2. Failure mode recall function
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-4.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
24
Page 25
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5second interval
No beepBeeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5-
second interval
Repeated cycle
W1. Regardless of normal or abnormal condition,
2 short beeps are emitted as the signal is received.
Does upper lamp of OPERATION INDICATOR lamp
on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal.
Beep are emitted at the same
timing as the blinking of upper lamp of
OPERATION INDICATOR lamp. W2
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 25:. W1
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table (Refer to 11-2.3.).
Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according
to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall
function.
The outdoor unit might be abnormal.
Confirm if outdoor unit is abnormal according to the following procedures.
25
Page 26
3. Outdoor unit failure mode table
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
6-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF
9-time flash
2.5 seconds OFF
10-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF
12-time flash
2.5 seconds OFF
14-time flash
2.5 seconds OFF
None (Normal)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent
DC voltage
Each phase current of compressor
Overcurrent
Compressor open-phase
Stop valve
(Closed valve)
Abnormal point
(Failure mode / protection)
Over current protection stop is
continuously performed three times
within 1 minute after the compressor
gets started.
Thermistor shorts or opens during
compressor running.
14 A (MUZ-GC25)/24 A (MUZ-GC35)
current flow into intelligent power
module.
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 116:, compressor
stops.
Compressor can restart if discharge
temperature thermistor reads 100: or
less 3 minutes later.
Temperature indoor coil thermistor
exceeds 70: in HEAT mode.
Temperature defrost thermistor exceeds
70: in COOL mode.
Temperature of fin temperature
thermistor on the inverter P.C. board
exceeds 82 : (MUZ-GC25)/83: (MUZ
-GC35), or temperature of P.C. board
temperature thermistor on the inverter
P.C. board exceeds 81: (MUZ-GC25)
/85: (MUZ-GC35).
Outdoor fan has stopped 3 times
in a row within 30 seconds after outdoor
fan start-up.
Nonvolatile memory data cannot be
read properly.
Temperature of discharge temperature
thermistor has been 50: or less for
20 minutes.
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
14 A (MUZ-GC25) / 24 A (MUZ-GC35)
current flow into intelligent power
module (IPM).
The open-phase operation of
compressor is detected.
The interphase short out occurs in the
output of the intelligent power
module (IPM).
The compressor winding shorts out.
Closed valve is detected by compressor
current.
Condition
•Reconnect connectors.
•Refer to 11-5. A"How to
check inverter/
compressor".
•Check stop valve.
•Refer to 11-5.G"Check
of outdoor thermistors".
❈Defective outdoor
thermistors can be
identified by checking
the blinking pattern
of LED.
•Reconnect compressor
connector.
•Refer to 11-5.A"How to
check inverter/
compressor".
•Check stop valve.
•Reconnect compressor
connector.
•Refer to 11-5.A"How to
check inverter/
compressor".
•Check refrigerant circuit
and refrigerant amount.
•Refer to 11-5.L"Check
of LEV".
•Check refrigerant circuit
and refrigerant amount.
•Check stop valve.
•Check around outdoor unit.
•Check outdoor unit air
passage.
•Refer to 11-5.I"Check of
outdoor fan motor".
•Refer to 11-5.I"Check of
outdoor fan motor".
Refer to 11-5.M"Check of
inverter P.C. board".
•Replace the inverter P.C.
board.
•Refer to 11-5.L"Check
of LEV".
•Check refrigerant circuit
and refrigerant amount.
•Refer to 11-5.A"How to
check inverter/
compressor".
•Reconnect compressor
connector.
•Refer to 11-5. A"How to
check inverter/
compressor".
•Check stop valve
Correspondence
Indoor/outdoor
unit failure mode
recall function
Outdoor unit
failure mode
recall function
1-time flash every
2.5 seconds
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
2-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF
12-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF
9-time flash
2.5 seconds OFF
10-time flash
2.5 seconds OFF
LED indication
(Outdoor P.C. board)
OFF
The upper lamp of
OPERATION INDICATOR
lamp(Indoor unit)
14-time flash
2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
26
Page 27
Abnormal point/ Condition
Over current protection stop is continuously performed three
times within 1 minute after the compressor gets started, or
failure of restart of compressor has repeated 24 times.
Discharge temperature thermistor, fin temperature thermistor,
defrost thermistor, P.C. board temperature thermistor or
ambient temperature thermistor shorts or opens during
compressor running.
Nonvolatile memory data cannot be read properly.
(When the upper lamp of OPERATION INDICATOR lamp of the
indoor unit lights up or flashes 7-time.)
14 A (MUZ-GC25)/ 24 A (MUZ-GC35) current flows into
intelligent power module, or compressor repeats after 15
seconds when overcurrent protection occures with in 10
seconds after compressor starts. (Repeated 24 times at
Maximum)
Temperature of discharge temperature thermistor exceeds
116:, compressor stops. Compressor can restart if discharge
temperature thermistor reads 100: or less 3 minutes later.
Temperature of fin temperature thermistor on the heat sink
exceeds 82: (MUZ-GC25)/ 83: (MUZ-GC35) or temperature
of P.C. board temperature thermistor on the inverter P.C.board
exceeds 81: (MUZ-GC25)/ 85: (MUZ-GC35).
Indoor coil thermistor exceeds 70: in HEAT mode.
Defrost thermistor exceeds 70: in COOL mode.
Current from power outlet exceeds 5.5 A (MUZ-GC25)/ 5.2 A
(MUZ-GC35 in COOL mode)/6.1 A (MUZ-GC35 in HEAT
mode), compressor frequency lowers.
Temperature of indoor coil thermistor exceeds 55: in HEAT
mode, compressor frequency lowers.
Indoor coil thermistor reads 8: or less in COOL mode,
compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds
111:, compressor frequency lowers.
Temperature of discharge temperature thermistor has been
50: or less for 20 minutes.
No.
1
2
3
7
8
9
10
15
16
17
18
19
Symptom
LED indication
Condition
Correspondence
Outdoor unit
does not
operate.
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated.
Outdoor unit
operates.
Outdoor unit
operates.
1-time flash every
2.5 seconds
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
Outdoor power
system
Outdoor
thermistors
Outdoor control
system
Overcurrent
protection
Discharge
temperature
overheat
protection
Fin temperature
/P.C. board
temperature
thermistor
overheat protection
High pressure
protection
Frequency drop by
current protection
Frequency drop by
high pressure
protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge
temperature
protection
Low discharge
temperature
protection
·
Reconnect connector of compressor.
· Refer to 11-5.A "How to check
inverter/ compressor".
· Check stop valve.
· Refer to 11-5.G "Check of outdoor
thermistors".
·
Reconnect connector of compressor.
· Refer to 11-5.A "How to check
inverter/compressor".
· Check stop valve.
Replace inverter P.C. board.
· Check refrigerant circuit and
refrigerant amount.
· Refer to 11-5.L "Check of LEV".
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to 11-5.I "Check of outdoor
fan motor".
· Check refrigerant circuit and
refrigerant amount.
· Check stop valve.
The unit is normal, but check the
following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to 11-5.L "Check of LEV".
· Check refrigerant circuit and
refrigerant amount.
Inverter P.C. board (Parts side)
LED
Flashing
Refer to 11-5.N "How to check miswiring and serial signal error.
The communication fails between the indoor and outdoor unit
for 3 minutes.
Serial signal
8-time flash
2.5 seconds OFF
Compressor
synchronous
abnormality
The waveform of compressor current is distorted.
·
Reconnect connector of compressor.
· Refer to 11-5.A "How to check
inverter/compressor".
8-time flash
2.5 seconds OFF
PAM protection
PAM:
Pulse
Amplitude
Modulation
The overcurrent flows into IGBT(Insulated Gate Bipolar
transistor : TR821) or when the bus-bar voltage reaches 320 V
or more, PAM stops and restarts.
This is not malfunction.
PAM protection will be activated in
the following cases;
1Instantaneous power voltage drop
(Short time power failure)
2When the power supply voltage is
high.
9-time flash
2.5 seconds OFF
Inverter check
mode
The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the
compressor is correctly connected.
Refer to 11-5.A "How to check
inverter/ compressor".
4
11
20
10-time flash
2.5 seconds OFF
Outdoor fan motor
6-time flash
2.5 seconds OFF
· Check stop valve.
Closed valve is detected by compressor current.
Stop valve/
Closed valve
5
11-time flash
2.5 seconds OFF
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
· Refer to 11-5.I "Check of outdoor
fan motor.
· Refer to 11-5.M "Check of inverter
P.C. board.
12
13
14
12-time flash
2.5 seconds OFF
Each phase
current of
compressor
Each phase current of compressor cannot be detected
normally
· Refer to 11-5.A "How to check
inverter/compressor".
13-time flash
2.5 seconds OFF
DC voltage
DC voltage of inverter cannot be detected normally.
· Refer to 11-5.A "How to check
inverter/compressor".
· Check refrigerant circuit and
refrigerant amount.
· Refer to 11-5.L "Check of LEV".
· Refer to 11-5.G "Check of
outdoor thermistors".
Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
Outdoor unit is defective.
Outdoor unit
(Other abnormality)
6
14-time flash
2.5 seconds OFF
11-3. Troubleshooting check table
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
2.5-second OFF
OFF
0.5-second ON
2.5-second OFF
0.5-second ON
27
Page 28
11-4. Trouble criterion of main parts
Part nameFigureCheck method and criterion
Outdoor fan motor (MF)
INNER FUSE
(Only MUZ-GC25)
RA6V21-AB
152 : CUT OFF
RA6V21-BB
126i2 : CUT OFF
+0
-5
R.V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
WHT – BLK
BLK – RED
RED – WHT
Normal
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Normal
1.26 k" ~ 1.62 k"1.21 k" ~ 1.56 k"
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
Normal
38 " ~ 50 "
Measure the resistance with a tester.
(Part temperature –20˚C ~ 40˚C)
Measure the resistance with a tester.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board",
the chart of thermistor.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board",
the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Defrost thermistor
(RT61)
Fin temperature
thermistor (RT64)
Ambient temperature
thermistor (RT65)
31 " ~ 41 "
31 " ~ 41 "
31 " ~ 41 "
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Compressor (MC)
MUZ-GC25
U-V
U-W
V-W
Normal
1.43 " ~ 1.84 "
1.58 " ~ 2.03"
MUZ-GC35
MUZ-GC25
MUZ-GC35MUZ-GC25
Measure the resistance with a tester.
(Part temperature –20˚C ~ 40˚C)
MUZ-GC35
MUZ-GC25
23
W
U
V
1
WHT
RED BLK
23
W
U
V
1
WHT
RED BLK
WHT
RED
BLK
FUSE
MUZ-GC35
Defrost heater (H)
Normal
313 " ~ 402 "333 " ~ 428 "
MUZ-GC35MUZ-GC25
RA6V21-BB
RA6V21-AB
292 " ~ 374 "
236 " ~ 304 "
212 " ~ 272 "
234 " ~ 300 "
LEV
WHT6
RED1
ORN4
YLW5
BRN2
BLU3
MUZ-GC25VAMUZ-GC35VA
MUZ-GC25VAHMUZ-GC35VAH
28
Page 29
11-5. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 5-times.
Outdoor unit does not operate.
A
How to check inverter/ compressor
Disconnect the connector (CN61)
between compressor and the
intelligent power module (IPM).
Check the voltage
between terminals.
Are the voltages
balanced?
Yes
Check the
compressor.
B
Check of open phase
●With the connector between the compressor and the intelligent
power module disconnected, activate the inverter and check if the
inverter is normal by measuring the balance of voltage between the
terminals.
Output voltage 115V
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on
the indoor unit. (Test run operation : refer to 8-3.)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times. (Refer to 11-6.1.)
See 11-5.B “Check of open phase” .
No
Replace the inverter P.C. board.
See 11-5.C “Check of compressor” .
w Measure AC voltage between
the lead wires at 3 points.
9-time flash
2.5-second OFF
C
Check of compressor
Refer to 11-5.D "Check of
compressor winding".
Is the compressor normal?
Refer to 11-5.E "Check of
compressor operation time".
Does the compressor
operate continuously?
OK
Yes
Yes
No
(MUZ-GC25)
No
(MUZ-GC35)
Replace the compressor.
Refer to 11-5.F "Check of compressor start failure".
Is the compressor
operation time more than
10 seconds?
Yes
Check the refrigerant circuit.
Check stop valve.
No
Replace the compressor.
29
Page 30
Check of compressor winding
D
● Disconnect the connector (CN61) between the compressor and
intelligent power module, and measure the resistance between the
compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 11-4.
0["] ···············Abnormal [short]
Infinite["] ·······Abnormal [open]
NOTE: 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20:.
Refer to 3.SPECIFICATION.
E
Check of compressor operation time
●Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(Test run operation : Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of compressor
due to over current.
w Measure the resistance between the
lead wires at 3 points.
<<Judgement>>
For refrence
0 second
1 second
2 seconds
Compressor starts
Abnormal
(IPM failure)
(Compressor winding short)
Abnormal
(Compressor lock out)
(Starting defect)
F
Check of compressor start failure
Confirm that 1~5 is normal.
•Electrical circuit check
1Contact of the compressor connector (including CN61)
2Output voltage of inverter P.C.board and balance of them (See 11-5.B)
3Direct current voltage between DB61(+) and (-) on inverter P.C.board
4Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds
or more after it starts?
No
Yes
Check the refrigerant circuit.
Check the stop valve.
After the compressor is heated with a drier,
does the compressor start? w1
Yes
Compressor start failure. Activate pre-heat control.
(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
No
Replace the compressor
30
w1
Heat with a drier for about
20 minutes.
Do not recover refrigerant
gas while heating
compressor with a drier.
Heating part
Page 31
When OPERATION INDICATOR lamp flashes 6-time.
Measure the
resistance
between CN641
1 and 2.
Measure the
resistance
between CN642
1 and 2.
No
Yes
Replace the
thermistor
except RT64.
In case that
RT64 is
abnormal,
replace the
inverter P.C.
board, since
RT64 is
combined with
the inverter P.C.
board.
Replace the inverter
P.C. board.
Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
(Check the characteristics of each thermistor.)
Defrost thermistor RT61
Measure the
resistance
between CN641
3 and 4.
Reconnect the
connectors
CN641, CN642
and CN643.
Turn ON the
power supply and
press
EMERGENCY
OPERATION
switch.
Discharge
temperature
thermistor RT62
Fin temperature
thermistor RT64
Is the resistance of
thermistor normal?
(Refer to 11-6.1.)
No
Yes
Does the unit operate
10 minutes or more?
OK.
(Cause is poor
contact.)
Measure the
resistance
between CN643
1 and 2.
Ambient
temperature
thermistor RT65
Disconnect connector (CN61) between
the compressor and intelligent power
module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Is there 230V AC between CN7211 and
2 on the inverter P.C.board(GC25) or
power P.C. board(GC35) 3 minutes after
the power supply is turned ON?
Yes
No
Replace the inverter
P.C.board(GC25) or
power P.C.board(GC35).
Replace the 4-way valve.
Replace the 4-way valve.
Disconnect connector (CN61) between
the compressor and the intelligent power
module.
Turn ON the power supply and press
EMERGENCY OPERATION switch once
(COOL mode).
Is there 230V AC between CN7211 and
2 on the inverter P.C.board(GC25) or
power P.C.board(GC35) 3 minutes after
the power supply is turned ON?
No
Yes
w First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.
w In case CN721 is not connected or R.V. coil is open, voltage is generated between the
terminal pins of the connector although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
CN721
Inverter P.C.board
(Soldered side)
MUZ-GC25
CN721
Power P.C.board
(Soldered side)
MUZ-GC35
Replace the inverter
P.C.board(GC25) or
power P.C.board(GC35).
The thermistors in the outdoor unit are abnormal.
G
Check of outdoor thermistors
Check of R.V. coil
H
Unit operates COOL mode even if it is set to HEAT mode.
Unit operates HEAT mode even if it is set to COOL mode.
31
Page 32
Outdoor fan motor does not operate.
Replace the
outdoor fan motor.
Does upper lamp of
OPERATION INDICATOR
lamp on the indoor unit
light up?
Is the resistance of fan
motor normal?
3 minutes after, is there
voltage 230V AC
between CN771 2 and
3 on the inverter P.C.
board?
Disconnect the connector CN771 on inverter P.C.
board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Yes
Yes
No
Check the resistance of fan motor. (Refer to 11-4.)
Replace the inverter
P.C. board.
No
Replace the outdoor
fan motor.
Does the voltage between
each terminal repeat 5V
and 0V DC by turns?
Does the outdoor fan
rotate smoothly?
Check the inverter P.C. board.
(Refer to 11-5. M)
No
Yes
Yes
( Fixed to either 5V or 0V DC)
Yes
No
No
Rotate the outdoor fan slowly
by hand, and measure the
voltage of CN931 (Measurement
of feedback output).
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Is the resistance
between each terminal of
outdoor fan motor normal?
(Refer to 11-4.)
Disconnect CN932
from the inverter
P.C. board.
Replace the outdoor fan
motor.
CN931
CN932
Inverter P.C. board
(Solder side)
Turn ON the
power supply.
I
Check of outdoor fan motor
MUZ-GC25VAMUZ-GC25VAH
MUZ-GC35VAMUZ-GC35VAH
32
Page 33
● Check other electric parts in the main circuit together in the case that the current-limiting resistor is defective.
Turn ON the power
supply and press
EMERGENCY
OPERATION switch.
Replace the inverter P.C.
board or the compressor.
Replace the power P.C.
board or the inverter P.C.
board.
Does the rush current
limiting relay(X64) work
properly? (Normally it
closes 1 second after
outdoor unit power ON.)
No
Yes
No
No
Yes
Yes
Is the resistance of current-limiting
resistor (R64A or R64B) on the
power P.C. board normal?
(Normal resistance : 5' i5%)
Replace the power P.C.board.
Replace the power P.C. board.
Does LED on the inverter
P.C. board light up?
Inverter does not operate.
Disconnect the connector
(CN61) between compressor and
intelligent power module.
Turn ON power supply and press
EMERGENCY OPERATION
switch.
Check the electric
parts in main circuit.
If light up,ok.
If flash, refer to
11-3.
Is there voltage
280V ~ 370V DC
between DB61 (+) and
DB61 (–) on the
inverter P.C. board?
(Refer to 11-6.1.)
Dose LED on the inverter
P.C. board light up or
flash? (Refer to 11-6.1.)
Yes
Yes
Yes
No
No
Replace the indoor
electronic control
P.C. board.
No
Yes
No
Replace the inverter
P.C. board.
DB61
280V~370V DC
Inverter P.C. board
(Solder side)
Is there voltage 230V AC
between the indoor
terminal block S1 and
S2?
Rectify indoor/ outdoor
connecting wire.
Does the upper lamp of
OPERATION INDICATOR
lamp on the indoor unit
light up?
Check of power supply
J
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check of current-limiting resistor
K
MUZ-GC35VAMUZ-GC35VAH
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
33
Page 34
Heating/Cooling does not work sufficiently.
Replace the LEV.
Expansion valve operates in
full-opening direction.
Is LEV properly fixed to the
expansion valve?
OK
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it ?
Does the resistance of LEV
have the characteristics?
(Refer to 11-4.)
Measure each voltage between connector pins
of CN724 on the inverter P.C. board.
1.Pin3(-) Pin1(+)
2.Pin4(-) Pin1(+)
3.Pin5(-) Pin1(+)
4.Pin6(-) Pin1(+)
Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the
expansion valve.
Yes
No
No
Properly fix the LEV to the
expansion valve.
Replace the
inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
W1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is received.
Turn ON the power supply.
<
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote
controller at the same time, press RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD
except the set temperature in operation display
section of the remote controller is displayed after
3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. W1
Check of LEV (Expansion valve)
L
34
Page 35
Yes
(10-time flash)
Yes
Check the LED indication on
the inverter P.C. board.
Does the LED flash 10-time?
No
No
Is the fuse (F901) blown on
the inverter P.C. board?
Replace the inverter P.C. board.
CN931
CN932
Inverter P.C.board
(Solder side)
Check the corresponding parts
following LED indication.
(Refer to 11-3.)
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the connection of the connectors.
(CN931, CN932) of outdoor fan motor.
If the connection is poor, make it correct.
Check the outdoor fan motor.
(Refer to11-5.I.)
Outdoor fan motor does not operate , or stops immediately after starting up.
Check of inverter P.C. board
M
MUZ-GC35VAMUZ-GC35VAH
35
Page 36
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Is there rated voltage in
the power supply?
Is there any mis-wiring,
poor contact, or wire
disconnection of the
indoor/outdoor
connecting wire?
W1. Mis-wiring may damage indoor P.C. board during the
operation.
Be sure to confirm the wiring is correct before the
operation starts.
W3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when
the inverter P.C.board or the outdoor electronic control
P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or
not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
W2 Be careful to the residual
voltage of smoothing capacitor.
No
No
Yes
No
Yes
Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between
outdoor terminal block S1 and
S2?
Does the upper lamp of OPERATION
INDICATOR lamp light up?
<Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power
supply.
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and
S3.
W1
B
Turn ON the power supply.
Check the wiring.
Correct them.
Turn OFF the power supply.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20V DC
between indoor terminal block S2
and S3? <Confirmation of serial
signal>
Is there rated voltage between
indoor terminal block S1 and S2?
<Confirmation of power voltage>
No
No
No
Yes
Yes
Yes
Replace the inverter P.C. board or
the outdoor electronic control P.C.board.
W2
Is there any error of the
indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
No
Replace the
indoor/outdoor
connecting wire.
Is serial signal
error indicated
6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON again.
· Press EMERGENCY OPERATION
switch.
B
· Reinstall
either the
unit or the
light each
other away.
· Attach a filter
on remote
control
receiving
section of
the indoor
unit.
A
Is serial signal error indicated 6 minutes later?
Is there 2V DC or less between CN10A3(+)
and JPG(GND)(–) on the indoor electronic
control P.C. board?
Is there 2V DC or less between
CN10A4(+) and JPG(GND)(–)
on the indoor electronic control
P.C. board?
Be sure to release the failure-mode recall function after checking.
Is there 2V DC or less between
CN10A4(+) and JPG(GND)(–)
on the indoor electronic control
P.C. board?
Does the LED on the inverter P.C. board
or the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-second-ON
quick blinking"? W3
Replace the indoor power /
terminal P.C. board.
Replace the indoor
electronic control P.C. board.
Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-seconds.
Outdoor unit doesn’t operate.
How to check mis-wiring and serial signal error (when outdoor unit does not work)
N
36
Page 37
O
Replace or repair the antenna.
Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the
antennas and the indoor
unit within 3m, or is the
distance between the
antennas and the outdoor
unit within 3m?
Is the distance between the
TV sets or radios and the
indoor unit within 1m, or is
the distance between the TV
sets or radios and the
outdoor unit within 3m?
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in
the antenna wiring?
Is the indoor/outdoor
connecting wire of the air
conditioner and the wiring of
the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on
the electric field strength or the installation condition (combination of specific conditions such as
antennas or wiring).
Check the followings before asking for service.
1.Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ;
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring
from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for
the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button
on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During
operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the
outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for
the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between
the antennas and the indoor
unit, and/or the antennas and
the outdoor unit.
Extend the distance between
the TV sets and/or radios and
the indoor unit, or the TV sets
or radios and the outdoor unit.
Extend the distance between
the indoor/outdoor connecting
wire of the air conditioner and
the wiring of the antennas.
Electromagnetic noise enters into TV sets or radios
37
Page 38
Replace the inverter P.C. board.
Is there 230V AC between CN722 1 and 3 on the
inverter P.C. board(GC25) or power P.C.
board(GC35)? Refer to 11-6.
Yes
No
No problem of the inverter P.C.
board(GC25) or power P.C.
board(GC35).
Is the voltage between CN726 2(+)-3(-)
on the power P.C. board 0V DC? Refer
to 11-6.
Yes
No
Replace the power
P.C. board.
NOTE: In case both thermistors are more than the above
temperature, cool them with cold water etc...
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5: or below, and let
the defrost thermistor continue to read -1: or below.
3
2
1
230V AC
(MUZ-GC25VAH)
(MUZ-GC35VAH)
1
230V AC
MUZ-GC25VAH
Inverter P.C board
MUZ-GC35VAH
Power P.C board
3
2
Check the following points before checking electric continuity.
1) Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.
2) Is the resistance of defrost heater normal? Refer to 11-4.
3) Does the heater protector remain conducted (not open)?
4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
26H
CN726
CN722
H
2
1
2
1
23
26H
CN722
H
1
2
1
2
Outdoor base gets frozen.
Check of defrost heater
P
MUZ-GC25VAH MUZ-GC35VAH
38
Page 39
11-6. Test point diagram and voltage
1. Inverter P.C. board
MUZ-GC25VA
MUZ-GC25VAH
Back side of unit
DB61
280V ~ 370V
DC
(+)
(-)
230V AC
DB61
Smoothing capacitor
(C62)
Fuse
(F801)
Smoothing capacitor
(C61)
Varistor
(NR63)
Varistor
(NR62)
Varistor
(NR61)
Jumper wire for change
in defrost setting (JS)
Output to
drive
compressor
(LDW,
LDV,
LDU)
LED monitor
lamp
Front side of unit
(CN643)
Fin temperature
thermistor/RT64
(CN642)
Defrost thermistor/RT61
(CN641)
Ambient temperature
thermistor /RT65
Discharge temperature
thermistor/RT62
(CN641)
LEV
connector
(CN724)
R.V.coil
(CN721)
Output to drive
outdoor
fan motor
(CN771)
Fuse
(F701)
Heater
connector
(CN722)
MUZ-
GC25VAH
Jumper wire for pre-heat
control setting (JK)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
100
90
80
70
60
50
40
30
Resistance(k")
20
10
0
-20 -10010203040
Temperature(:)
Discharge temperature thermistor(RT62)
700
600
500
400
300
200
Resistance(k")
100
0
0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature(:)
39
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
Resistance(k")
40
20
0
0 1020304050607080
Temperature(:)
Page 40
1. Inverter P.C. board
-20 -10010203040
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Ambient temperature thermistor(RT65)
Defrost thermistor(RT61)
Temperature(:)
Discharge temperature thermistor(RT62)
010 20 30 40 50 60 70 80 90 100 110 120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor(RT64)
Resistance(k")
Resistance(k")
Resistance(k")
MUZ-GC35VA
MUZ-GC35VAH
Back side of unit
DB61
280V ~ 370V
DC
(+)
(-)
Output to
drive
compressor
(LDW,
LDV,
LDU)
230V AC
DB61
Smoothing capacitor
(C63C)
Smoothing capacitor
(C63B)
Smoothing capacitor
(C63A)
FUSE
(F801)
FUSE
(F901)
LED monitor
lamp
fan motor CN931)
1(+)
2(+)
3(+)
45V
5GND
Rotational frequency
feedback signal of outdoor
Jumper wire for change
in defrost setting (JS)
Front side of unit
Connecting wire with
power P.C. board
(CN725)
LEV
connector
(CN724)
40
(CN641)
Defrost thermistor/RT61
(CN641)
Discharge temperature
thermistor/RT62
Ambient temperature
thermistor /RT65
(CN643)
thermistor/RT64
(CN642)
Fin temperature
Output to drive
outdoor fan motor
(CN932)
Connector for indoor/
outdoor communication
(CN601)
Page 41
2. Power P.C. board
MUZ-GC35VA
MUZ-GC35VAH
Back side of unit
Connecting wire with
inverter P.C.board
(CN726)
FUSE
(F71)
Varistor
(NR63)
230V AC
Heater connector
(CN722)
MUZ-GC35V AH
Varistor
(NR62)
Varistor
(NR64)
Front side of unit
230V AC
R.V.coil(CN721)
230V AC
41
Page 42
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
1Slide the sleeve.
2Pull the terminal while
Locking lever
pushing the locking
lever.
12-1. MUZ-GC25VAMUZ-GC25VAH
OPERATING PROCEDURE
1. Removing cabinet and panels
(1) Remove the screw fixing the service panel. (See Photo 2.)
(2) Pull down the service panel and remove it. (See Photo 2.)
(3)
Disconnect the power supply and indoor/outdoor connecting wire.
(4) Remove the screws fixing the top panel. (See Photo 1.)
(5) Remove the top panel. (See Photo 1.)
(6) Remove the screws fixing the cabinet. (See Photo 1.)
(7) Remove the cabinet.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
(2) The terminal with this connector has the
locking mechanism.
1Hold the sleeve, and
pull out the terminal
slowly.
Connector
NOTE : Turn OFF power supply before disassembling.
PHOTOS
Photo 1
Screws
of the
top panel
Screws of
the top panel
Photo 2
Screw of the
service panel
Direction to
remove
Hooks
42
Screws of
the cabinet
Service
panel
Page 43
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the earth wires (See Photo 3.), the lead wire to
the reactor and the following connectors;
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature
(3) Disconnect the compressor connector (CN61).
(4) Remove the screws fixing the relay panel. (See Photo 3.)
(5) Remove the inverter assembly. (See Photo 4.)
(6) Remove the inverter P.C. board from the inverter assembly.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the R.V. coil. (See Photo 5.)
Photo 3
Screws of the
relay panel
Screw of
the earth
wires
Photo 4 (Inverter assembly)
Inverter
P.C. board
Heat sink
4. Removing the discharge temperature thermistor and
defrost thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Pull out the discharge temperature thermistor from its
holder. (See Photo 6.)
(3) Pull out the defrost thermistor from its holder. (See Photo 5.)
43
Photo 5
R.V. coil
Defrost
thermistor
Page 44
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the connectors for outdoor fan motor.
(3) Remove the propeller nut. (See Photo 7.)
(4) Remove the propeller. (See Photo 7.)
(5) Remove the screws fixing the fan motor. (See Photo 7.)
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm
(4) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
2
(0 MPa).
Photo 6
Discharge temperature thermistor
Photo 7
44
Propeller
Screws of the outdoor fan motor
Photo 8
Welded parts of 4-way valve
Page 45
12-2. MUZ-GC35VAMUZ-GC35VAH
NOTE : Turn OFF power supply before disassembling.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (See Photo 2.)
(2) Pull down the service panel and remove it. (See Photo 2.)
Disconnect the power supply and indoor/outdoor connecting wire.
(3)
(4) Remove the screws fixing the top panel. (See Photo 1.)
(5) Remove the top panel. (See Photo 1.)
(6) Remove the screws fixing the cabinet.
(7) Remove the cabinet.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
Photo 1
Screws
of the
top panel
Screws of
the cabinet
PHOTOS
Screw of
the cabinet
Screws of
the top panel
Back
panel
Service
panel
Photo 2
Screws of
the cabinet
Screw of the
service panel
Direction to
remove
Hooks
45
Page 46
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
and power P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the earth wires (See Photo 3.), the lead wire to
the reactor and the following connectors;
<Power P.C. board>
CN721 (4-way valve)
CN722 (Defrost heater) MUZ-GC35VAH
<Inverter P.C. board>
CN931,CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature
thermistor)
CN643 (Ambient temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the relay panel. (See Photo 3.)
(5) Remove the inverter assembly. (See Photo 4.)
(6) Remove the inverter P.C. board from the inverter assembly.
(7) Remove the screw fixing the power P.C. board. (See Photo
4.)
(8) Remove the power P.C. board from the inverter assembly.
Photo 3
Screws of the
relay panel
Photo 4 (inverter assembly)
Heat sink
Inverter
P.C. board
Screws of
the earth
wires
Power
P.C. board
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the R.V. coil. (See Photo 5.)
4. Removing the discharge temperature thermistor and
defrost thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Pull out the discharge temperature thermistor from its
holder. (See Photo 5.)
(3) Pull out the defrost thermistor from its holder. (See Photo
6.)
Photo 5
Screw of the
power P.C. board
R.V. coil
46
Discharge temperature thermistor
Page 47
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the connectors for outdoor fan motor.
(3) Remove the propeller nut. (See Photo 7.)
(4) Remove the propeller. (See Photo 7.)
(5) Remove the screws fixing the fan motor. (See Photo 7.)
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
2
gauge shows 0kg/cm
(4) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
(0 MPa).
Photo 6
Photo 7
Defrost
thermistor
Screws of the outdoor fan motor
47
Propeller
Photo 8
Welded parts of 4-way valve
Page 48
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Jan. 2007. No. OBH469 6
Made in Japan
New publication, effective Jan. 2007
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.