Mitsubishi Electric MUZ-GA50VA-E1, MUZ-GA60VA-E1, MUZ-GA60VA-E2, MUZ-GA60VA-E3, MUZ-GA71VA-E1 Service Manual

...
Page 1
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ···································3
2. PART NAMES AND FUNCTIONS ····················· 6
3. SPECIFICATION ················································ 6
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
7. REFRIGERANT SYSTEM DIAGRAM ············· 12
8. PERFORMANCE CURVES ····························· 15
9. ACTUATOR CONTROL ··································· 26
10. SERVICE FUNCTIONS ···································· 27
11. TROUBLESHOOTING ····································· 27
12. DISASSEMBLY INSTRUCTIONS ···················· 46
13. PARTS LIST ····················································· 50
14. RoHS PARTS LIST ·········································· 52
Models
SPLIT-TYPE AIR CONDITIONERS
MUZ-GA50VA -
E1
MUZ-GA60VA -
E1
MUZ-GA60VA -
E2
MUZ-GA60VA -
E3
MUZ-GA71VA -
E1
MUZ-GA71VA -
E2
HFC
utilized
R410A
NOTE:
• RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
• Contents of SERVICE FUNCTIONS (10) have been removed.
No. OB389
REVISED EDITION-H
Indoor unit service manual MSZ-GA•VA Series (OB388)
Please void OB389 REVISED EDITION-G.
OUTDOOR UNIT
Revision H:
Errors in TROUBLESHOOTING have
been corrected.
Page 2
2
Revision A :
• RoHS PARTS LIST has been added.
• Failure mode recall function (11-2.) has been changed.
• Check of HPS (11-6.
) has been corrected.
Revision B:
• Compressor has been changed. (MUZ-GA50/60VA)
Previous New
Model SNB130FLDH SNB130FLDH1
PARTS LIST number E02 851 900 E02 939 900
RoHS PARTS LIST number E12 851 900 E12 939 900
Revision C:
MUZ-GA60/71VA-
E2
have been added.
• Check of outdoor thermistors (11-6. ) has been corrected.
• Contents of SERVICE FUNCTIONS (10) have been removed as these models do not have the functions.
Revision D:
• PARTS LIST and RoHS PARTS LIST have been changed.
Revision E:
• REFRIGERANT SYSTEM DIAGRAM has been changed for MUZ-GA60VA-E2.
Revision F:
MUZ-GA60VA-E3 has been added.
Revision G:
• The fan guard for MUZ-GA50VA-E, MUZ-GA60VA-E and MUZ-GA71VA-E has been changed.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision H:
Errors in TROUBLESHOOTING have been corrected.
Page 3
3
1
TECHNICAL CHANGES
Refrigeration
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%: 50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557
64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non
Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055
1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant
Composition (Ratio)
Refrigerant handling
Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point (°C)
Steam pressure [25°C](Mpa)
Saturated steam density [25°C](kg/m
3
)
Combustibility
ODP 1
GWP 2
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell
1: Ozone Depletion Potential : based on CFC-11 2: Grobal Warming Potential : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air conditioners.
As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
MUZ-A18YV -E1 MUZ-GA50VA -
E1
MUZ-A24YV -E1 MUZ-GA60VA -
E1
MUZ-A26YV -E1 MUZ-GA71VA -
E1
1. Indication of capacity has been changed. (BTU base kW base)
2. Outdoor electronic control P.C. board has been changed.
3. Noise filter P.C. board has been changed.
4. Length of fan motor lead wire has been changed.
5. Shape of relay panel has been changed.
6. Signal of terminal block has been changed.
MUZ-GA60VA -E1 MUZ-GA60VA -
E2
1. Compressor has been changed. (SNB130FLDH1 SNB130FLEH1)
2. Outdoor electronic control P.C. board has been changed.
MUZ-GA71VA -E1 MUZ-GA71VA -
E2
1. Outdoor electronic control P.C. board has been changed.
MUZ-GA60VA -E2 MUZ-GA60VA -
E3
1. Compressor has been changed. (SNB130FLEH1 SNB130FGBH)
2. Outdoor electronic control P.C. board has been changed.
3. Refrigerant circuit has been changed.
Page 4
4
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
NOTE: The unit of pressure has been changed to MPa on the
international system of units (SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/cm2 [Gauge])
R410A tools
Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool). Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps. It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization.
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge Vacuum pump
adapter Electronic scale for
refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm and 15.88mm
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/cm
2
[Gauge])
New Specification Current Specification
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigeration oil are compatible, refrigeration oil goes back to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
Compressor
Page 5
55
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe
Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter
mm
6.35
9.52
12.7
15.88
17
22
26
29
Dimension of flare nut
R22
17
22
24
27
Flaring work and flare nut Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to installation manual “FLARING WORK”.
3. Refrigeration oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
• Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, capacity of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
2. Refrigerant piping
Specifications Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88). Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is insufficient.
Wall thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
15.88
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Heat resisting foam plastic
Specific gravity 0.045 Thickness 8 mm
Insulation material
Page 6
6
PART NAMES AND FUNCTIONS
2
Air inlet
Piping
Air outlet
(back and side)
Drain hose
Drain outlet
ACCESSORIES
Drain socket
Drain cap Ø33
1
2
E1
E2
E3
Single phase
230V,50Hz
20
7.46
0.30
SNB130FLDH or SNB130FLDH1
850
U-V 0.45 W-U 0.45
V-W 0.4 5
RC0J60-AA
BLK-WHT 15.2
WHT-RED 15.2 RED-BLK15.2
840x850x330
53
2
1.8
NEO22
Cooling
5.0(0.9-5.9)
2.5
2,940/1,650
6.23
1,410
98.4
5.93
3.42
53/51
800/480
Heating
5.9(0.9-7.8) —
2,940/2,210
7.01
1,580
98.0
6.71
3.62
55/53
800/620
Outdoor model
Function
Power supply
Capacity Rated frequency (Min.-Max.) Dehumidification Air flow (High/Low) Breaker capacity Running current Power input Power factor Starting current 1 Compressor motor current 1 Fan motor current
Model
Output Winding resistance(at 20°C) Model Winding resistance (at 20°C) Dimensions WxHxD Weight Sound level (High/Low) Fan speed (High/Low) Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
/h
m
3
/h A A
W %
A A A
W
Ω
Ω
mm
kg dB
rpm
kg
Compressor
Fan
motor
Special
remarks
Coefficient of performance(C.O.P) 1
Capacity
Electrical
data
Single phase
230V,50Hz
20
11. 2
0.30
TNB220FMCH
1,300
U-V 1.41 W-U 1.41
V-W 1.4 1
RC0J60-AA
BLK-WHT 15.2
WHT-RED 15.2 RED-BLK15.2
840x850x330
58
2
2.0
NEO22
Heating
8.1(0.9-9.6) —
2,940/2,210
10.6
2,390
98.0
10.3
3.31
55/53
800/620
MUZ-GA71VA
Single phase
230V,50Hz
20
8.93
0.30
SNB130FLDH or SNB130FLDH1
SNB130FLEH1
SNB130FGBH
850
U-V 0.45 W-U 0.45
V-W 0.4 5
RC0J60-AA
BLK-WHT 15.2
WHT-RED 15.2 RED-BLK15.2
840x850x330
53
2
1.8
NEO22
Cooling
6.0(0.9-6.7)
3.0
2,940/1,650
8.23
1,870
98.8
7.93
3.11
53/51
800/480
Heating
6.8(0.9-8.1) —
2,940/2,210
8.33
1,880
98.1
8.03
3.51
55/53
800/620
MUZ-GA60VA
MUZ-GA50VA
Cooling
7.1(0.9-8.3)
3.8
2,940/1,650
10.4
2,360
98.7
10.1
2.93
53/51
800/480
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry bulb temperature 27
Wet bulb temperature 19
Outdoor Dry bulb temperature 35 Wet bulb temperature (24
) Heating: Indoor Dry bulb temperature 20 Wet bulb temperature 15 Outdoor Dry bulb temperature 7 Wet bulb temperature 6 Refrigerant piping length (one way): 5m 1 Measured under rated operating frequency.
3
SPECIFICATION
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
Page 7
7
NOISE CRITERIA CURVES
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
OUTDOOR UNIT
MICROPHONE
1m
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
53
55
Test conditions Cooling: Dry-bulb temperature 35°C
Wet-bulb temperature (24°C) Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Model
Item
Smoothing capacitor
Current transformer
Current transformer
Fuse
Fuse
Fuse
Intelligent power module
High pressure switch
Intelligent power module
Reactor
Expansion valve coil
Power factor controller
Resistor
Resistor
Resistor
Solenoid coil relay
Terminal block
Terminal block
Relay
R.V. coil
MUZ-GA50VA
(CB1,2,3)
(CT1,2)
(CT61)
(F64)
(F801)
(F911)
(HC930)
(HPS)
(IPM)
(L)
(LEV)
(PFC)
(R64A,B)
(R937A,B)
(RS1~4)
(SSR61)
(TB1)
(TB2)
(X64)
(21S4)
MUZ-GA60VA MUZ-GA71VA
560μF 450V
ETQ19Z68AY
ETQ19Z53AY
250V 2A
250V 3.15A
250V 1A
PS21661-RZ
ACB-DB156 (for )
PS21244-A
340μH 20A
DC 12 V
PS51259-A
10Ω 10W
1.1Ω 2W 2%
0.04Ω 7W
TLP3506
3P
3P
G4A
AC 220 ~ 240 V
ACB-DB156
E3
Specifications and rated conditions of main electric parts
Page 8
8
5
OUTLINES AND DIMENSIONS
Unit: mm
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
30°
35°
155
90
198
40
515
299
66
34
51
330
360
850
430
500
80
121
840
Open as a rule 500 mm or more if the front and both sides are open
100 mm or more 200 mm or more if there are obstacles to both sides
Open as a rule 500 mm or more if the back, both sides and top are open
350 mm or more
100 mm or more
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) Ø12.7 (MUZ-GA50) Ø15.88 (MUZ-GA60/71)
Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø6.35 (MUZ-GA50/60) Ø9.52 (MUZ-GA71)
REQUIRED SPACE
Page 9
9
WIRING DIAGRAM
6
R64B
YLW
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
RED
WHT
RS2
RS1
R64A
RS3
RS4
F801
CN901
NR64
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
L
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
W
CN4
TB2
S1
1
CN601
3
S2
1 567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
231 34512
MF
CN932
3X64
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
4
1
RED
YLW
3
2
RED
S
R
21
CN903
21
CN902
21
CN5
6543 1
CN2
27
TAB4
V
MC
W
U
V
WHT
RT61 RT62 RT68
LEV
:Terminal block :Connector
3.Symbols below indicate.
2.Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1.About the indoor side electric wiringNOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGENT POWER MODULE
CT61
FUSE (T2AL 250V)
F64
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
SMOOTHING CAPACITOR
CB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B
RESISTOR
PFC
NF
NR64
VAR ISTOR
AMBIENT TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
R.V. COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT65
FIN TEMPERATURE THERMISTOR
RT64
T801
TRANSFORMER
SSR61
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
MUZ-GA50VA MUZ-GA60VA -
E1
MUZ-GA60VA -
E2
Page 10
10
MUZ-GA60VA -
E3
Page 11
11
MUZ-GA71VA
BLK
CN902
12
CN903
12
TAB4
X64 3
R64A R64B
RED
2
3
1
4
L
YLW
YLW
RED
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
HPS
RED
RED
RED
WHT
RS2
RS1 RS3
RS4
F801
CN901
NR64
CN681
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
12
W
CN4
TB2
S1
1
CN601
3
S2
1567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
23134512
MF
CN932
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
S
R
21
CN5
6543 1
CN2
27
V
MC
W
U
V
WHT
RT61 RT62 RT68
LEV
:Terminal block :Connector
3.Symbols below indicate.
2.Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1.About the indoor side electric wiringNOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGENT POWER MODULE
HPS
HIGH PRESSURE SWITCH
CT61
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
F64
FUSE (T2AL 250V)
SMOOTHING CAPACITORCB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B RESISTOR
PFC
NF
NR64
VAR ISTOR
FIN TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
R.V. COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT64
T801
TRANSFORMER
SSR61
AMBIENT TEMPERATURE THERMISTOR
RT65
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
Page 12
12
REFRIGERANT SYSTEM DIAGRAM
7
MUZ-GA50VA MUZ-GA60VA -
E1
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube Ø3.6 x Ø2.4 x 50
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe Ø12.7 (MUZ-GA50VA) (with heat insulator) Ø15.88 (MUZ-GA60VA)
Refrigerant pipe Ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
MUZ-GA60VA -
E2
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor
RT61 Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube Ø3.6 x Ø2.4 x 50
Capillary tube Ø1.8 x Ø0.6 x 1000
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe Ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Oil separator
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Strainer
#100
Strainer
#100
Ambient temperature thermistor RT65
Refrigerant pipe Ø15.88 (with heat insulator)
Page 13
13
MUZ-GA71VA
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube Ø3.6 x Ø2.4 x 50
Capillary tube Ø1.8 x Ø0.6 x 1000
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe Ø15.88 (with heat insulator)
Refrigerant pipe Ø9.52 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Oil separator
High-pressure switch
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Strainer
#100
Strainer
#100
Ambient temperature thermistor RT65
MUZ-GA60VA -
E3
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube Ø3.6 x Ø2.4 x 50
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe Ø15.88 (with heat insulator)
Refrigerant pipe Ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
High-pressure switch
Page 14
14
Refrigerant Piping Max. length A
Max. Height difference B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : m
Max. length
A
Max. Height
difference
B
1530
Gas
12.7
15.88
Liquid
6.35
9.52
MUZ-GA50VA
MUZ-GA60VA
MUZ-GA71VA
Model
Piping size O.D : mm
Model
MUZ-GA50VA MUZ-GA60VA
Refrigerant piping length (one way)
Outdoor unit
precharged
1,800
15m
160
20m
260
25m
360
30m
460
7m
0
10m
60
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Calculation: Xg = 20 g/m x (Refrigerant piping length (m) -7)
Outdoor unit
precharged
2,000
0 165 440 715 990 1,265
Refrigerant piping length (one way)
15m10m7m
Model
MUZ-GA71VA
20m
25m 30m
Calculation: Xg = 55 g/m x (Refrigerant piping length (m) -7)
NOTE: Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.
Page 15
15
PERFORMANCE CURVES8
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-
tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °C WB (2) Indoor outlet air wet-bulb temperature : °C WB (3) Outdoor intake air dry-bulb temperature : °C DB (4) Total input : W (5) Indoor intake air dry-bulb temperature : °C DB (6) Outdoor intake air wet-bulb temperature : °C WB (7) Total input : W
Indoor air wet and dry bulb temperature difference on the left side of the chart on this page and next page shows the dif­ference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
}
}
Cooling
Heating
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
Wet and dry bulb thermometers
Wet and dry bulb thermometers
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
Indoor air Wet-bulb temperature
difference (degree)
MUZ-GA50VA
8.7
8.0
7.3
6.6
5.9
5.3
at Rated frequency
MUZ-GA71VA
at Rated frequency
Outdoor intake air Dry-bulb temperature (°C)
Outdoor intake air Dry-bulb temperature (°C)
10.7
9.8
8.9
8.0
7.2
6.4
8.7
8.0
7.3
6.6
5.9
5.3
MUZ-GA60VA
at Rated frequency
Indoor intake air Wet-bulb temperature (°C)
Indoo
r intake air Wet-bulb temperature (°C)
8-1. CAPACITY AND INPUT CURVES
Page 16
16
MUZ-GA71VA
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
24.1
22.3
20.4
18.5
16.7
14.8
13.0
11.1
23.4
21.6
19.8
18.0
16.2
14.4
12.6
10.8
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-
bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
Indoor intake air Dry-bulb temperature (°
C)
MUZ-GA50VA
at Rated frequency
MUZ-GA60VA
at Rated frequency
MUZ-GA71VA
at Rated frequency
27.9
25.7
23.6
21.4
19.3
17.2
15.0
12.9
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
MUZ-GA50VA
MUZ-GA60VA
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
Page 17
17
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system). The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])
(MPa [Gauge])
(kgf/cm
2
[Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.3
0.4
0.5
0.6
0.7
0.8
3
4
5
6
7
8
9
0.9
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
15 2050256030
70 (%)
35(°C)
4
5
6
7
8
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
MUZ-GA50VA
MUZ-GA50VA
0.3
0.4
0.5
0.6
0.7
0.8
3
4
5
6
7
8
9
0.9
MUZ-GA71VA
15 205025
60
30 70 (%)
35(°C)
5
7
9
11
13
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
MUZ-GA71VA
(MPa [Gauge])
(kgf/cm
2
[Gauge])
18 32
15 2050256030
70 (%)
35(°C)
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
0.3
0.4
0.5
0.6
0.7
0.8
3
4
5
6
7
8
9
0.9
(MPa [Gauge])
(kgf/cm
2
[Gauge])
18 32
15 2050256030
70 (%)
35(°C)
15 205025
60
30 70 (%)
35(°C)
5
6
7
8
9
32
18
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
MUZ-GA60VA
MUZ-GA60VA
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
COOL operation
Both indoor and outdoor unit are under the
same temperature/humidity condition.
Operation: TEST RUN OPERATION (refer to 8-3.)
Dry-bulb temperature( )
Relative humidity(%)
20
50
25
60
30
70
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Page 18
18
Outdoor unit current (A)
Outdoor unit current (A)
Ambient temperature(°C)
Ambient temperature(°C)
Outdoor unit current (A)
Ambient temperature(°C)
MUZ-GA71VA
MUZ-GA50VA
MUZ-GA60VA
10.0
9.0
8.0
7.0
6.0
5.0
4.0
2
5 10 15 20 25(°C)
16.0
15.0
14.0
13.0
12.0
11. 0
10.0 2
5 10 15 20 25(°C)
12.0
11. 0
10.0
9.0
8.0
7.0
6.0 2
5 10 15 20 25(°C)
Condition:
Operation: TEST RUN OPERATION (refer to 8-3.)
HEAT operation
Dry bulb temperature (ºC)
Indoor
20.0
14.521
Outdoor
76151220.0
14.5
Wet bulb temperature (ºC)
Page 19
19
MSZ-GA50VA: MUZ-GA50VA
INDOOR INDOOR
CAPACITY:5.0(kW)
INPUT:1460(W)SHF:0.65
21
OUTDOOR DB(°C)
25 27 30
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 5.88 2.76 0.47 1200 5.63 2.64 0.47 1260 5.40 2.54 0.47 1320 21 20 6.13 2.14 0.35 1260 5.88 2.06 0.35 1335 5.70 2.00 0.35 1365 22 18 5.88 3.00 0.51 1200 5.63 2.87 0.51 1260 5.40 2.75 0.51 1320 22 20 6.13 2.39 0.39 1260 5.88 2.29 0.39 1335 5.70 2.22 0.39 1365 22 22 6.38 1.72 0.27 1305 6.15 1.66 0.27 1388 6.00 1.62 0.27 1425 23 18 5.88 3.23 0.55 1200 5.63 3.09 0.55 1260 5.40 2.97 0.55 1320 23 20 6.13 2.63 0.43 1260 5.88 2.53 0.43 1335 5.70 2.45 0.43 1365 23 22 6.38 1.98 0.31 1305 6.15 1.91 0.31 1388 6.00 1.86 0.31 1425 24 18 5.88 3.47 0.59 1200 5.63 3.32 0.59 1260 5.40 3.19 0.59 1320 24 20 6.13 2.88 0.47 1260 5.88 2.76 0.47 1335 5.70 2.68 0.47 1365 24 22 6.38 2.23 0.35 1305 6.15 2.15 0.35 1388 6.00 2.10 0.35 1425 24 24 6.70 1.54 0.23 1365 6.45 1.48 0.23 1440 6.30 1.45 0.23 1485 25 18 5.88 3.70 0.63 1200 5.63 3.54 0.63 1260 5.40 3.40 0.63 1320 25 20 6.13 3.12 0.51 1260 5.88 3.00 0.51 1335 5.70 2.91 0.51 1365 25 22 6.38 2.49 0.39 1305 6.15 2.40 0.39 1388 6.00 2.34 0.39 1425 25 24 6.70 1.81 0.27 1365 6.45 1.74 0.27 1440 6.30 1.70 0.27 1485 26 18 5.88 3.94 0.67 1200 5.63 3.77 0.67 1260 5.40 3.62 0.67 1320 26 20 6.13 3.37 0.55 1260 5.88 3.23 0.55 1335 5.70 3.14 0.55 1365 26 22 6.38 2.74 0.43 1305 6.15 2.64 0.43 1388 6.00 2.58 0.43 1425 26 24 6.70 2.08 0.31 1365 6.45 2.00 0.31 1440 6.30 1.95 0.31 1485 26 26 6.90 1.31 0.19 1440 6.70 1.27 0.19 1515 6.60 1.25 0.19 1560 27 18 5.88 4.17 0.71 1200 5.63 3.99 0.71 1260 5.40 3.83 0.71 1320 27 20 6.13 3.61 0.59 1260 5.88 3.47 0.59 1335 5.70 3.36 0.59 1365 27 22 6.38 3.00 0.47 1305 6.15 2.89 0.47 1388 6.00 2.82 0.47 1425 27 24 6.70 2.35 0.35 1365 6.45 2.26 0.35 1440 6.30 2.21 0.35 1485 27 26 6.90 1.59 0.23 1440 6.70 1.54 0.23 1515 6.60 1.52 0.23 1560 28 18 5.88 4.41 0.75 1200 5.63 4.22 0.75 1260 5.40 4.05 0.75 1320 28 20 6.13 3.86 0.63 1260 5.88 3.70 0.63 1335 5.70 3.59 0.63 1365 28 22 6.38 3.25 0.51 1305 6.15 3.14 0.51 1388 6.00 3.06 0.51 1425 28 24 6.70 2.61 0.39 1365 6.45 2.52 0.39 1440 6.30 2.46 0.39 1485 28 26 6.90 1.86 0.27 1440 6.70 1.81 0.27 1515 6.60 1.78 0.27 1560 29 18 5.88 4.64 0.79 1200 5.63 4.44 0.79 1260 5.40 4.27 0.79 1320 29 20 6.13 4.10 0.67 1260 5.88 3.94 0.67 1335 5.70 3.82 0.67 1365 29 22 6.38 3.51 0.55 1305 6.15 3.38 0.55 1388 6.00 3.30 0.55 1425 29 24 6.70 2.88 0.43 1365 6.45 2.77 0.43 1440 6.30 2.71 0.43 1485 29 26 6.90 2.14 0.31 1440 6.70 2.08 0.31 1515 6.60 2.05 0.31 1560 30 18 5.88 4.88 0.83 1200 5.63 4.67 0.83 1260 5.40 4.48 0.83 1320 30 20 6.13 4.35 0.71 1260 5.88 4.17 0.71 1335 5.70 4.05 0.71 1365 30 22 6.38 3.76 0.59 1305 6.15 3.63 0.59 1388 6.00 3.54 0.59 1425 30 24 6.70 3.15 0.47 1365 6.45 3.03 0.47 1440 6.30 2.96 0.47 1485 30 26 6.90 2.42 0.35 1440 6.70 2.35 0.35 1515 6.60 2.31 0.35 1560 31 18 5.88 5.11 0.87 1200 5.63 4.89 0.87 1260 5.40 4.70 0.87 1320 31 20 6.13 4.59 0.75 1260 5.88 4.41 0.75 1335 5.70 4.28 0.75 1365 31 22 6.38 4.02 0.63 1305 6.15 3.87 0.63 1388 6.00 3.78 0.63 1425 31 24 6.70 3.42 0.51 1365 6.45 3.29 0.51 1440 6.30 3.21 0.51 1485 31 26 6.90 2.69 0.39 1440 6.70 2.61 0.39 1515 6.60 2.57 0.39 1560 32 18 5.88 5.35 0.91 1200 5.63 5.12 0.91 1260 5.40 4.91 0.91 1320 32 20 6.13 4.84 0.79 1260 5.88 4.64 0.79 1335 5.70 4.50 0.79 1365 32 22 6.38 4.27 0.67 1305 6.15 4.12 0.67 1388 6.00 4.02 0.67 1425 32 24 6.70 3.69 0.55 1365 6.45 3.55 0.55 1440 6.30 3.47 0.55 1485 32 26 6.90 2.97 0.43 1440 6.70 2.88 0.43 1515 6.60 2.84 0.43 1560
5.20
2.44
0.47
1380
5.50
1.93
0.35
1425
5.20
2.65
0.51
1380
5.50
2.15
0.39
1425
5.75
1.55
0.27
1485
5.20
2.86
0.55
1380
5.50
2.37
0.43
1425
5.75
1.78
0.31
1485
5.20
3.07
0.59
1380
5.50
2.59
0.47
1425
5.75
2.01
0.35
1485
6.10
1.40
0.23
1560
5.20
3.28
0.63
1380
5.50
2.81
0.51
1425
5.75
2.24
0.39
1485
6.10 1.65 0.27
1560
5.20
3.48
0.67
1380
5.50
3.03
0.55
1425
5.75
2.47
0.43
1485
6.10
1.89
0.31
1560
6.40
1.22
0.19
1605
5.20
3.69
0.71
1380
5.50
3.25
0.59
1425
5.75
2.70
0.47
1485
6.10
2.14
0.35
1560
6.40
1.47
0.23
1605
5.20
3.90
0.75
1380
5.50
3.47
0.63
1425
5.75
2.93
0.51
1485
6.10
2.38
0.39
1560
6.40
1.73
0.27
1605
5.20
4.11
0.79
1380
5.50
3.69
0.67
1425
5.75
3.16
0.55
1485
6.10
2.62
0.43
1560
6.40
1.98
0.31
1605
5.20
4.32
0.83
1380
5.50
3.91
0.71
1425
5.75
3.39
0.59
1485
6.10
2.87
0.47
1560
6.40
2.24
0.35
1605
5.20
4.52
0.87
1380
5.50
4.13
0.75
1425
5.75
3.62
0.63
1485
6.10
3.11
0.51
1560
6.40
2.50
0.39
1605
5.20
4.73
0.91
1380
5.50
4.35
0.79
1425
5.75
3.85
0.67
1485
6.10
3.36
0.55
1560
6.40
2.75
0.43
1605
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 20
20
INDOOR INDOOR
CAPACITY: 5.0(kW)
INPUT: 1460(W)SHF: 0.65
35
OUTDOOR DB(°C)
40 43 46
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 21 20 22 18 22 20 22 22 23 18 23 20 23 22 24 18 24 20 24 22 24 24 25 18 25 20 25 22 25 24 26 18 26 20 26 22 26 24 26 26 27 18 27 20 27 22 27 24 27 26 28 18 28 20 28 22 28 24 28 26 29 18 29 20 29 22 29 24 29 26 30 18 30 20 30 22 30 24 30 26 31 18 31 20 31 22 31 24 31 26 32 18 32 20 32 22 32 24 32 26
4.90 2.30 0.47 1470 4.50 2.12 0.47 1560
5.15 1.80 0.35 1530 4.80 1.68 0.35 1605
4.90 2.50 0.51 1470 4.50 2.30 0.51 1560
5.15 2.01 0.39 1530 4.80 1.87 0.39 1605
5.45 1.47 0.27 1590 5.10 1.38 0.27 1680
4.90 2.70 0.55 1470 4.50 2.48 0.55 1560
5.15 2.21 0.43 1530 4.80 2.06 0.43 1605
5.45 1.69 0.31 1590 5.10 1.58 0.31 1680
4.90 2.89 0.59 1470 4.50 2.66 0.59 1560
5.15 2.42 0.47 1530 4.80 2.26 0.47 1605
5.45 1.91 0.35 1590 5.10 1.79 0.35 1680
5.75 1.32 0.23 1650 5.40 1.24 0.23 1725
4.90 3.09 0.63 1470 4.50 2.84 0.63 1560
5.15 2.63 0.51 1530 4.80 2.45 0.51 1605
5.45 2.13 0.39 1590 5.10 1.99 0.39 1680
5.75 1.55 0.27 1650 5.40 1.46 0.27 1725
4.90 3.28 0.67 1470 4.50 3.02 0.67 1560
5.15 2.83 0.55 1530 4.80 2.64 0.55 1605
5.45 2.34 0.43 1590 5.10 2.19 0.43 1680
5.75 1.78 0.31 1650 5.40 1.67 0.31 1725
6.05 1.15 0.19 1710 5.70 1.08 0.19 1785
4.90 3.48 0.71 1470 4.50 3.20 0.71 1560
5.15 3.04 0.59 1530 4.80 2.83 0.59 1605
5.45 2.56 0.47 1590 5.10 2.40 0.47 1680
5.75 2.01 0.35 1650 5.40 1.89 0.35 1725
6.05 1.39 0.23 1710 5.70 1.31 0.23 1785
4.90 3.68 0.75 1470 4.50 3.38 0.75 1560
5.15 3.24
0.63
1530 4.80 3.02 0.63 1605
5.45 2.78 0.51 1590 5.10 2.60 0.51 1680
5.75 2.24 0.39 1650 5.40 2.11 0.39 1725
6.05 1.63 0.27 1710 5.70 1.54 0.27 1785
4.90 3.87 0.79 1470 4.50 3.56 0.79 1560
5.15 3.45 0.67 1530 4.80 3.22 0.67 1605
5.45 3.00 0.55 1590 5.10 2.81 0.55 1680
5.75 2.47 0.43 1650 5.40 2.32 0.43 1725
6.05 1.88 0.31 1710 5.70 1.77 0.31 1785
4.90 4.07 0.83 1470 4.50 3.74 0.83 1560
5.15 3.66 0.71 1530 4.80 3.41 0.71 1605
5.45 3.22 0.59 1590 5.10 3.01 0.59 1680
5.75 2.70 0.47 1650 5.40 2.54 0.47 1725
6.05 2.12 0.35 1710 5.70 2.00 0.35 1785
4.90 4.26 0.87 1470 4.50 3.92 0.87 1560
5.15 3.86 0.75 1530 4.80 3.60 0.75 1605
5.45 3.43 0.63 1590 5.10 3.21 0.63 1680
5.75 2.93 0.51 1650 5.40 2.75 0.51 1725
6.05 2.36 0.39 1710 5.70 2.22 0.39 1785
4.90 4.46 0.91 1470 4.50 4.10 0.91 1560
5.15 4.07 0.79 1530 4.80 3.79 0.79 1605
5.45 3.65 0.67 1590 5.10 3.42 0.67 1680
5.75 3.16 0.55 1650 5.40 2.97 0.55 1725
6.05 2.60 0.43 1710 5.70 2.45 0.43 1785
4.33 2.03 0.47 1590 4.15 1.95 0.47 1620
4.63 1.62 0.35 1650 4.45 1.56 0.35 1695
4.33 2.21 0.51 1590 4.15 2.12 0.51 1620
4.63 1.80 0.39 1650 4.45 1.74 0.39 1695
4.93 1.33 0.27 1710 4.75 1.28 0.27 1740
4.33 2.38 0.55 1590 4.15 2.28 0.55 1620
4.63 1.99 0.43 1650 4.45 1.91 0.43 1695
4.93 1.53 0.31 1710 4.75 1.47 0.31 1740
4.33 2.55 0.59 1590 4.15 2.45 0.59 1620
4.63 2.17 0.47 1650 4.45 2.09 0.47 1695
4.93 1.72 0.35 1710 4.75 1.66 0.35 1740
5.25 1.21 0.23 1763 5.10 1.17 0.23 1800
4.33 2.72 0.63 1590 4.15 2.61 0.63 1620
4.63 2.36 0.51 1650 4.45 2.27 0.51 1695
4.93 1.92 0.39 1710 4.75 1.85 0.39 1740
5.25 1.42 0.27 1763 5.10 1.38 0.27 1800
4.33 2.90 0.67 1590 4.15 2.78 0.67 1620
4.63 2.54 0.55 1650 4.45 2.45 0.55 1695
4.93 2.12 0.43 1710 4.75 2.04 0.43 1740
5.25 1.63 0.31 1763 5.10 1.58 0.31 1800
5.53 1.05 0.19 1823 5.35 1.02 0.19 1860
4.33 3.07 0.71 1590 4.15 2.95 0.71 1620
4.63 2.73 0.59 1650 4.45 2.63 0.59 1695
4.93 2.31 0.47 1710 4.75 2.23 0.47 1740
5.25 1.84 0.35 1763 5.10 1.79 0.35 1800
5.53 1.27 0.23 1823 5.35 1.23 0.23 1860
4.33 3.24 0.75 1590 4.15 3.11 0.75 1620
4.63 2.91 0.63 1650 4.45 2.80 0.63 1695
4.93 2.51 0.51 1710 4.75 2.42 0.51 1740
5.25 2.05 0.39 1763 5.10 1.99 0.39 1800
5.53 1.49 0.27 1823 5.35 1.44 0.27 1860
4.33 3.42 0.79 1590 4.15 3.28 0.79 1620
4.63 3.10 0.67 1650 4.45 2.98 0.67 1695
4.93 2.71 0.55 1710 4.75 2.61 0.55 1740
5.25 2.26 0.43 1763 5.10 2.19 0.43 1800
5.53 1.71 0.31 1823 5.35 1.66 0.31 1860
4.33 3.59 0.83 1590 4.15 3.44 0.83 1620
4.63 3.28 0.71 1650 4.45 3.16 0.71 1695
4.93 2.91 0.59 1710 4.75 2.80 0.59 1740
5.25 2.47 0.47 1763 5.10 2.40 0.47 1800
5.53 1.93 0.35 1823 5.35 1.87 0.35 1860
4.33 3.76 0.87 1590 4.15 3.61 0.87 1620
4.63 3.47 0.75 1650 4.45 3.34 0.75 1695
4.93 3.10 0.63 1710 4.75 2.99 0.63 1740
5.25 2.68 0.51 1763 5.10 2.60 0.51 1800
5.53 2.15 0.39 1823 5.35 2.09 0.39 1860
4.33 3.94 0.91 1590 4.15 3.78 0.91 1620
4.63 3.65 0.79 1650 4.45 3.52 0.79 1695
4.93 3.30 0.67 1710 4.75 3.18 0.67 1740
5.25 2.89 0.55 1763 5.10 2.81 0.55 1800
5.53 2.38 0.43 1823 5.35 2.30 0.43 1860
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MSZ-GA50VA: MUZ-GA50VA
Page 21
21
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MSZ-GA60VA: MUZ-GA60VA
INDOOR INDOOR
CAPACITY: 6.0(kW)
INPUT: 1930(W)SHF: 0.64
21
OUTDOOR DB(°C)
25 27 30
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 21 20 22 18 22 20 22 22 23 18 23 20 23 22 24 18 24 20 24 22 24 24 25 18 25 20 25 22 25 24 26 18 26 20 26 22 26 24 26 26 27 18 27 20 27 22 27 24 27 26 28 18 28 20 28 22 28 24 28 26 29 18 29 20 29 22 29 24 29 26 30 18 30 20 30 22 30 24 30 26 31 18 31 20 31 22 31 24 31 26 32 18 32 20 32 22 32 24 32 26
7.057.05 3.24 0.46 1560 6.75 3.11 0.46 1638 6.48 2.98 0.46 1716
7.35 2.50 0.34 1638 7.05 2.40 0.34 1736 6.84 2.33 0.34 1775
7.05 3.53 0.50 1560 6.75 3.38 0.50 1638 6.48 3.24 0.50 1716
7.35 2.79 0.38 1638 7.05 2.68 0.38 1736 6.84 2.60 0.38 1775
7.65 1.99 0.26 1697 7.38 1.92 0.26 1804 7.20 1.87 0.26 1853
7.05 3.81 0.54 1560 6.75 3.65 0.54 1638 6.48 3.50 0.54 1716
7.35 3.09 0.42 1638 7.05 2.96 0.42 1736 6.84 2.87 0.42 1775
7.65 2.30 0.30 1697 7.38 2.21 0.30 1804 7.20 2.16 0.30 1853
7.05 4.09 0.58 1560 6.75 3.92 0.58 1638 6.48 3.76 0.58 1716
7.35 3.38 0.46 1638 7.05 3.24 0.46 1736 6.84 3.15 0.46 1775
7.65 2.60 0.34 1697 7.38 2.51 0.34 1804 7.20 2.45 0.34 1853
8.04 1.77 0.22 1775 7.74 1.70 0.22 1872 7.56 1.66 0.22 1931
7.05 4.37 0.62 1560 6.75 4.19 0.62 1638 6.48 4.02 0.62 1716
7.35 3.68 0.50 1638 7.05 3.53 0.50 1736 6.84 3.42 0.50 1775
7.65 2.91 0.38 1697 7.38 2.80 0.38 1804 7.20 2.74 0.38 1853
8.04 2.09 0.26 1775 7.74 2.01 0.26 1872 7.56 1.97 0.26 1931
7.05 4.65 0.66 1560 6.75 4.46 0.66 1638 6.48 4.28 0.66 1716
7.35 3.97 0.54 1638 7.05 3.81 0.54 1736 6.84 3.69 0.54 1775
7.65 3.21 0.42 1697 7.38 3.10 0.42 1804 7.20 3.02 0.42 1853
8.04 2.41 0.30 1775 7.74 2.32 0.30 1872 7.56 2.27 0.30 1931
8.28 1.49 0.18 1872 8.04 1.45 0.18 1970 7.92 1.43 0.18 2028
7.05 4.94 0.70 1560 6.75 4.73 0.70 1638 6.48 4.54 0.70 1716
7.35 4.26 0.58 1638 7.05 4.09 0.58 1736 6.84 3.97 0.58 1775
7.65 3.52 0.46 1697 7.38 3.39 0.46 1804 7.20 3.31 0.46 1853
8.04 2.73 0.34 1775 7.74 2.63 0.34 1872 7.56 2.57 0.34 1931
8.28 1.82 0.22 1872 8.04 1.77 0.22 1970 7.92 1.74 0.22 2028
7.05 5.22 0.74 1560 6.75 5.00 0.74 1638 6.48 4.80 0.74 1716
7.35 4.56 0.62 1638 7.05 4.37 0.62 1736 6.84 4.24 0.62 1775
7.65 3.83 0.50 1697 7.38 3.69 0.50 1804 7.20 3.60 0.50 1853
8.04 3.06 0.38 1775 7.74 2.94 0.38 1872 7.56 2.87 0.38 1931
8.28 2.15 0.26 1872 8.04 2.09 0.26 1970 7.92 2.06 0.26 2028
7.05 5.50 0.78 1560 6.75 5.27 0.78 1638 6.48 5.05 0.78 1716
7.35 4.85 0.66 1638 7.05 4.65 0.66 1736 6.84 4.51 0.66 1775
7.65 4.13 0.54 1697 7.38 3.99 0.54 1804 7.20 3.89 0.54 1853
8.04 3.38 0.42 1775 7.74 3.25 0.42 1872 7.56 3.18 0.42 1931
8.28 2.48 0.30 1872 8.04 2.41 0.30 1970 7.92 2.38 0.30 2028
7.05 5.78 0.82 1560 6.75 5.54 0.82 1638 6.48 5.31 0.82 1716
7.35 5.15 0.70 1638 7.05 4.94 0.70 1736 6.84 4.79 0.70 1775
7.65 4.44 0.58 1697 7.38 4.28 0.58 1804 7.20 4.18 0.58 1853
8.04 3.70 0.46 1775 7.74 3.56 0.46 1872 7.56 3.48 0.46 1931
8.28 2.82 0.34 1872 8.04 2.73 0.34 1970 7.92 2.69 0.34 2028
7.05 6.06 0.86 1560 6.75 5.81 0.86 1638 6.48 5.57 0.86 1716
7.35 5.44 0.74 1638 7.05 5.22 0.74 1736 6.84 5.06 0.74 1775
7.65 4.74 0.62 1697 7.38 4.58 0.62 1804 7.20 4.46 0.62 1853
8.04 4.02 0.50 1775 7.74 3.87 0.50 1872 7.56 3.78 0.50 1931
8.28 3.15 0.38 1872 8.04 3.06 0.38 1970 7.92 3.01 0.38 2028
7.05 6.35 0.90 1560 6.75 6.08 0.90 1638 6.48 5.83 0.90 1716
7.35 5.73 0.78 1638 7.05 5.50 0.78 1736 6.84 5.34 0.78 1775
7.65 5.05 0.66 1697 7.38 4.87 0.66 1804 7.20 4.75 0.66 1853
8.04 4.34 0.54 1775 7.74 4.18 0.54 1872 7.56 4.08 0.54 1931
8.28 3.48 0.42 1872 8.04 3.38 0.42 1970 7.92 3.33 0.42 2028
6.24 2.87 0.46 1794
6.60 2.24 0.34 1853
6.24 3.12 0.50 1794
6.60 2.51 0.38 1853
6.90 1.79 0.26 1931
6.24 3.37 0.54 1794
6.60 2.77 0.42 1853
6.90 2.07 0.30 1931
6.24 3.62 0.58 1794
6.60 3.04 0.46 1853
6.90 2.35 0.34 1931
7.32 1.61 0.22 2028
6.24 3.87 0.62 1794
6.60 3.30 0.50 1853
6.90 2.62 0.38 1931
7.32 1.90 0.26 2028
6.24 4.12 0.66 1794
6.60 3.56 0.54 1853
6.90 2.90 0.42 1931
7.32 2.20 0.30 2028
7.68 1.38 0.18 2087
6.24 4.37 0.70 1794
6.60 3.83 0.58 1853
6.90 3.17 0.46 1931
7.32 2.49 0.34 2028
7.68 1.69 0.22 2087
6.24 4.62 0.74 1794
6.60 4.09 0.62 1853
6.90 3.45 0.50 1931
7.32 2.78 0.38 2028
7.68 2.00 0.26 2087
6.24 4.87 0.78 1794
6.60 4.36 0.66 1853
6.90 3.73 0.54 1931
7.32 3.07 0.42 2028
7.68 2.30 0.30 2087
6.24 5.12 0.82 1794
6.60 4.62 0.70 1853
6.90 4.00 0.58 1931
7.32 3.37 0.46 2028
7.68 2.61 0.34 2087
6.24 5.37 0.86 1794
6.60 4.88 0.74 1853
6.90 4.28 0.62 1931
7.32 3.66 0.50 2028
7.68 2.92 0.38 2087
6.24 5.62 0.90 1794
6.60 5.15 0.78 1853
6.90 4.55 0.66 1931
7.32 3.95 0.54 2028
7.68 3.23 0.42 2087
Page 22
22
INDOOR INDOOR
CAPACITY:6.0(kW)
INPUT:1930(W)SHF:0.64
35
OUTDOOR DB(°C)
40 43 46
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 21 20 22 18 22 20 22 22 23 18 23 20 23 22 24 18 24 20 24 22 24 24 25 18 25 20 25 22 25 24 26 18 26 20 26 22 26 24 26 26 27 18 27 20 27 22 27 24 27 26 28 18 28 20 28 22 28 24 28 26 29 18 29 20 29 22 29 24 29 26 30 18 30 20 30 22 30 24 30 26 31 18 31 20 31 22 31 24 31 26 32 18 32 20 32 22 32 24 32 26
5.19 2.39 0.46 2067 4.98 2.29 0.46 2106
5.55 1.89 0.34 2145 5.34 1.82 0.34 2204
5.19 2.60 0.50 2067 4.98 2.49 0.50 2106
5.55 2.11 0.38 2145 5.34 2.03 0.38 2204
5.91 1.54 0.26 2223 5.70 1.48 0.26 2262
5.19 2.80 0.54 2067 4.98 2.69 0.54 2106
5.55 2.33 0.42 2145 5.34 2.24 0.42 2204
5.91 1.77 0.30 2223 5.70 1.71 0.30 2262
5.19 3.01 0.58 2067 4.98 2.89 0.58 2106
5.55 2.55 0.46 2145 5.34 2.46 0.46 2204
5.91 2.01 0.34 2223 5.70 1.94 0.34 2262
6.30 1.39 0.22 2291 6.12 1.35 0.22 2340
5.19 3.22 0.62 2067 4.98 3.09 0.62 2106
5.55 2.78 0.50 2145 5.34 2.67 0.50 2204
5.91 2.25 0.38 2223 5.70 2.17 0.38 2262
6.30 1.64 0.26 2291 6.12 1.59 0.26 2340
5.19 3.43 0.66 2067 4.98 3.29 0.66 2106
5.55 3.00 0.54 2145 5.34 2.88 0.54 2204
5.91 2.48 0.42 2223 5.70 2.39 0.42 2262
6.30 1.89 0.30 2291 6.12 1.84 0.30 2340
6.63 1.19 0.18 2369 6.42 1.16 0.18 2418
5.19 3.63 0.70 2067 4.98 3.49 0.70 2106
5.55 3.22 0.58 2145 5.34 3.10 0.58 2204
5.91 2.72 0.46 2223 5.70 2.62 0.46 2262
6.30 2.14 0.34 2291 6.12 2.08 0.34 2340
6.63 1.46 0.22 2369 6.42 1.41 0.22 2418
5.19 3.84 0.74 2067 4.98 3.69 0.74 2106
5.55 3.44 0.62 2145 5.34 3.31 0.62 2204
5.91 2.96 0.50 2223 5.70 2.85 0.50 2262
6.30 2.39 0.38 2291 6.12 2.33 0.38 2340
6.63 1.72 0.26 2369 6.42 1.67 0.26 2418
5.19 4.05 0.78 2067 4.98 3.88 0.78 2106
5.55 3.66 0.66 2145 5.34 3.52 0.66 2204
5.91 3.19 0.54 2223 5.70 3.08 0.54 2262
6.30 2.65 0.42 2291 6.12 2.57 0.42 2340
6.63 1.99 0.30 2369 6.42 1.93 0.30 2418
5.19 4.26 0.82 2067 4.98 4.08 0.82 2106
5.55 3.89 0.70 2145 5.34 3.74 0.70 2204
5.91 3.43 0.58 2223 5.70 3.31 0.58 2262
6.30 2.90 0.46 2291 6.12 2.82 0.46 2340
6.63 2.25 0.34 2369 6.42 2.18 0.34 2418
5.19 4.46 0.86 2067 4.98 4.28 0.86 2106
5.55 4.11 0.74 2145 5.34 3.95 0.74 2204
5.91 3.66 0.62 2223 5.70 3.53 0.62 2262
6.30 3.15 0.50 2291 6.12 3.06 0.50 2340
6.63 2.52 0.38 2369 6.42 2.44 0.38 2418
5.19 4.67 0.90 2067 4.98 4.48 0.90 2106
5.55 4.33 0.78 2145 5.34 4.17 0.78 2204
5.91 3.90 0.66 2223 5.70 3.76 0.66 2262
6.30 3.40 0.54 2291 6.12 3.30 0.54 2340
6.63 2.78 0.42 2369 6.42 2.70 0.42 2418
5.88 2.70 0.46 1911 5.40 2.48 0.46 2028
6.18 2.10 0.34 1989 5.76 1.96 0.34 2087
5.88 2.94 0.50 1911 5.40 2.70 0.50 2028
6.18 2.35 0.38 1989 5.76 2.19 0.38 2087
6.54 1.70 0.26 2067 6.12 1.59 0.26 2184
5.88 3.18 0.54 1911 5.40 2.92 0.54 2028
6.18 2.60 0.42 1989 5.76 2.42 0.42 2087
6.54 1.96 0.30 2067 6.12 1.84 0.30 2184
5.88 3.41 0.58 1911 5.40 3.13 0.58 2028
6.18 2.84 0.46 1989 5.76 2.65 0.46 2087
6.54 2.22 0.34 2067 6.12 2.08 0.34 2184
6.90 1.52 0.22 2145 6.48 1.43 0.22 2243
5.88 3.65 0.62 1911 5.40 3.35 0.62 2028
6.18 3.09 0.50 1989 5.76 2.88 0.50 2087
6.54 2.49 0.38 2067 6.12 2.33 0.38 2184
6.90 1.79 0.26 2145 6.48 1.68 0.26 2243
5.88 3.88 0.66 1911 5.40 3.56 0.66 2028
6.18 3.34 0.54 1989 5.76 3.11 0.54 2087
6.54 2.75 0.42 2067 6.12 2.57 0.42 2184
6.90 2.07 0.30 2145 6.48 1.94 0.30 2243
7.26 1.31 0.18 2223 6.84 1.23 0.18 2321
5.88 4.12 0.70 1911 5.40 3.78 0.70 2028
6.18 3.58 0.58 1989 5.76 3.34 0.58 2087
6.54 3.01 0.46 2067 6.12 2.82 0.46 2184
6.90 2.35 0.34 2145 6.48 2.20 0.34 2243
7.26 1.60 0.22 2223 6.84 1.50 0.22 2321
5.88 4.35 0.74 1911 5.40 4.00 0.74 2028
6.18 3.83 0.62 1989 5.76 3.57 0.62 2087
6.54 3.27 0.50 2067 6.12 3.06 0.50 2184
6.90 2.62 0.38 2145 6.48 2.46 0.38 2243
7.26 1.89 0.26 2223 6.84 1.78 0.26 2321
5.88 4.59 0.78 1911 5.40 4.21 0.78 2028
6.18 4.08 0.66 1989 5.76 3.80 0.66 2087
6.54 3.53 0.54 2067 6.12 3.30 0.54 2184
6.90 2.90 0.42 2145 6.48 2.72 0.42 2243
7.26 2.18 0.30 2223 6.84 2.05 0.30 2321
5.88 4.82 0.82 1911 5.40 4.43 0.82 2028
6.18 4.33 0.70 1989 5.76 4.03 0.70 2087
6.54 3.79 0.58 2067 6.12 3.55 0.58 2184
6.90 3.17 0.46 2145 6.48 2.98 0.46 2243
7.26 2.47 0.34 2223 6.84 2.33 0.34 2321
5.88 5.06 0.86 1911 5.40 4.64 0.86 2028
6.18 4.57 0.74 1989 5.76 4.26 0.74
2087
6.54 4.05 0.62 2067 6.12 3.79 0.62 2184
6.90 3.45 0.50 2145 6.48 3.24 0.50 2243
7.26 2.76 0.38 2223 6.84 2.60 0.38 2321
5.88 5.29 0.90 1911 5.40 4.86 0.90 2028
6.18 4.82 0.78 1989 5.76 4.49 0.78 2087
6.54 4.32 0.66 2067 6.12 4.04 0.66 2184
6.90 3.73 0.54 2145 6.48 3.50 0.54 2243
7.26 3.05 0.42 2223 6.84 2.87 0.42 2321
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MSZ-GA60VA: MUZ-GA60VA
Page 23
23
INDOOR INDOOR
CAPACITY:7.1(kW)
INPUT:2420(W)SHF:0.63
21
OUTDOOR DB(°C)
25 27 30
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 21 20 22 18 22 20 22 22 23 18 23 20 23 22 24 18 24 20 24 22 24 24 25 18 25 20 25 22 25 24 26 18 26 20 26 22 26 24 26 26 27 18 27 20 27 22 27 24 27 26 28 18 28 20 28 22 28 24 28 26 29 18 29 20 29 22 29 24 29 26 30 18 30 20 30 22 30 24 30 26 31 18 31 20 31 22 31 24 31 26 32 18 32 20 32 22 32 24 32 26
8.34 3.75 0.45 1952 7.99 3.59 0.45 2050 7.67 3.45 0.45 2147
8.70 2.87 0.33 2050 8.34 2.75 0.33 2172 8.09 2.67 0.33 2220
8.34 4.09 0.49 1952 7.99 3.91 0.49 2050 7.67 3.76 0.49 2147
8.70 3.22 0.37 2050 8.34 3.09 0.37 2172 8.09 2.99 0.37 2220
9.05 2.26 0.25 2123 8.73 2.18 0.25 2257 8.52 2.13 0.25 2318
8.34 4.42 0.53 1952 7.99 4.23 0.53 2050 7.67 4.06 0.53 2147
8.70 3.57 0.41 2050 8.34 3.42 0.41 2172 8.09 3.32 0.41 2220
9.05 2.63 0.29 2123 8.73 2.53 0.29 2257 8.52 2.47 0.29 2318
8.34 4.76 0.57 1952 7.99 4.55 0.57 2050 7.67 4.37 0.57 2147
8.70 3.91 0.45 2050 8.34 3.75 0.45 2172 8.09 3.64 0.45 2220
9.05 2.99 0.33 2123 8.73 2.88 0.33 2257 8.52 2.81 0.33 2318
9.51 2.00 0.21 2220 9.16 1.92 0.21 2342 8.95 1.88 0.21 2416
8.34 5.09 0.61 1952 7.99 4.87 0.61 2050 7.67 4.68 0.61 2147
8.70 4.26 0.49 2050 8.34 4.09 0.49 2172 8.09 3.97 0.49 2220
9.05 3.35 0.37 2123 8.73 3.23 0.37 2257 8.52 3.15 0.37 2318
9.51 2.38 0.25 2220 9.16 2.29 0.25 2342 8.95 2.24 0.25 2416
8.34 5.42 0.65 1952 7.99 5.19 0.65 2050 7.67 4.98 0.65 2147
8.70 4.61 0.53 2050 8.34 4.42 0.53 2172 8.09 4.29 0.53 2220
9.05 3.71 0.41 2123 8.73 3.58 0.41 2257 8.52 3.49 0.41 2318
9.51 2.76 0.29 2220 9.16 2.66 0.29 2342 8.95 2.59 0.29 2416
9.80 1.67 0.17 2342 9.51 1.62 0.17 2464 9.37 1.59 0.17 2538
8.34 5.76 0.69 1952 7.99 5.51 0.69 2050 7.67 5.29 0.69 2147
8.70 4.96 0.57 2050 8.34 4.76 0.57 2172 8.09 4.61 0.57 2220
9.05 4.07 0.45 2123 8.73 3.93 0.45 2257 8.52 3.83 0.45 2318
9.51 3.14 0.33 2220 9.16 3.02 0.33 2342 8.95 2.95 0.33 2416
9.80 2.06 0.21 2342 9.51 2.00 0.21 2464 9.37 1.97 0.21 2538
8.34 6.09 0.73 1952 7.99 5.83 0.73 2050 7.67 5.60 0.73 2147
8.70 5.31 0.61 2050 8.34 5.09 0.61 2172 8.09 4.94 0.61 2220
9.05 4.44 0.49 2123 8.73 4.28 0.49 2257 8.52 4.17 0.49 2318
9.51 3.52 0.37 2220 9.16 3.39 0.37 2342 8.95 3.31 0.37 2416
9.80 2.45 0.25 2342 9.51 2.38 0.25 2464 9.37 2.34 0.25 2538
8.34 6.42 0.77 1952 7.99 6.15 0.77 2050 7.67 5.90 0.77 2147
8.70 5.65 0.65 2050 8.34 5.42 0.65 2172 8.09 5.26 0.65 2220
9.05 4.80 0.53 2123 8.73 4.63 0.53 2257 8.52 4.52 0.53 2318
9.51 3.90 0.41 2220 9.16 3.76 0.41 2342 8.95 3.67 0.41 2416
9.80 2.84 0.29 2342 9.51 2.76 0.29 2464 9.37 2.72 0.29 2538
8.34 6.76 0.81 1952 7.99 6.47 0.81 2050 7.67 6.21 0.81 2147
8.70 6.00 0.69 2050 8.34 5.76 0.69 2172 8.09 5.58 0.69 2220
9.05 5.16 0.57 2123 8.73 4.98 0.57 2257 8.52 4.86 0.57 2318
9.51 4.28 0.45 2220 9.16 4.12 0.45 2342 8.95 4.03 0.45 2416
9.80 3.23 0.33 2342 9.51 3.14 0.33 2464 9.37 3.09 0.33 2538
8.34 7.09 0.85 1952 7.99 6.79 0.85 2050 7.67 6.52 0.85 2147
8.70 6.35 0.73 2050 8.34 6.09 0.73 2172 8.09 5.91 0.73 2220
9.05 5.52 0.61 2123 8.73 5.33 0.61 2257 8.52 5.20 0.61 2318
9.51 4.66 0.49 2220 9.16 4.49 0.49 2342 8.95 4.38 0.49 2416
9.80 3.63 0.37 2342 9.51 3.52 0.37 2464 9.37 3.47 0.37 2538
8.34 7.42 0.89 1952 7.99 7.11 0.89 2050 7.67 6.82 0.89 2147
8.70 6.70 0.77 2050 8.34 6.42 0.77 2172 8.09 6.23 0.77 2220
9.05 5.88 0.65 2123 8.73 5.68 0.65 2257 8.52 5.54 0.65 2318
9.51 5.04 0.53 2220 9.16 4.85 0.53 2342 8.95 4.74 0.53 2416
9.80 4.02 0.41 2342 9.51 3.90 0.41 2464 9.37 3.84 0.41 2538
7.38 3.32 0.45 2245
7.81 2.58 0.33 2318
7.38 3.62 0.49 2245
7.81 2.89 0.37 2318
8.17 2.04 0.25 2416
7.38 3.91 0.53 2245
7.81 3.20 0.41 2318
8.17 2.37 0.29 2416
7.38 4.21 0.57 2245
7.81 3.51 0.45 2318
8.17 2.69 0.33 2416
8.66 1.82 0.21 2538
7.38 4.50 0.61 2245
7.81 3.83 0.49 2318
8.17 3.02 0.37 2416
8.66 2.17 0.25 2538
7.38 4.80 0.65 2245
7.81 4.14 0.53 2318
8.17 3.35 0.41 2416
8.66 2.51 0.29 2538
9.09 1.54 0.17 2611
7.38 5.09 0.69 2245
7.81 4.45 0.57 2318
8.17 3.67 0.45 2416
8.66 2.86 0.33 2538
9.09 1.91 0.21 2611
7.38 5.39 0.73 2245
7.81 4.76 0.61 2318
8.17 4.00 0.49 2416
8.66 3.20 0.37 2538
9.09 2.27 0.25 2611
7.38 5.69 0.77 2245
7.81 5.08 0.65 2318
8.17 4.33 0.53 2416
8.66 3.55 0.41 2538
9.09 2.64 0.29 2611
7.38 5.98 0.81 2245
7.81 5.39 0.69 2318
8.17 4.65 0.57 2416
8.66 3.90 0.45 2538
9.09 3.00 0.33 2611
7.38 6.28 0.85 2245
7.81 5.70 0.73 2318
8.17 4.98 0.61 2416
8.66 4.24 0.49 2538
9.09 3.36 0.37 2611
7.38 6.57 0.89 2245
7.81 6.01 0.77 2318
8.17 5.31 0.65 2416
8.66 4.59 0.53 2538
9.09 3.73 0.41 2611
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MSZ-GA71VA: MUZ-GA71VA
Page 24
24
INDOOR INDOOR
CAPACITY:7.1(kW)
INPUT:2420(W)SHF:0.63
35
OUTDOOR DB(°C)
40 43 46
WB(°C)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(°C)
21 18 21 20 22 18 22 20 22 22 23 18 23 20 23 22 24 18 24 20 24 22 24 24 25 18 25 20 25 22 25 24 26 18 26 20 26 22 26 24 26 26 27 18 27 20 27 22 27 24 27 26 28 18 28 20 28 22 28 24 28 26 29 18 29 20 29 22 29 24 29 26 30 18 30 20 30 22 30 24 30 26 31 18 31 20 31 22 31 24 31 26 32 18 32 20 32 22 32 24 32 26
6.14 2.76 0.45 2586 5.89 2.65 0.45 2635
6.57 2.17 0.33 2684 6.32 2.09 0.33 2757
6.14 3.01 0.49 2586 5.89 2.89 0.49 2635
6.57 2.43 0.37 2684 6.32 2.34 0.37 2757
6.99 1.75 0.25 2782 6.75 1.69 0.25 2830
6.14 3.25 0.53 2586 5.89 3.12 0.53 2635
6.57 2.69 0.41 2684 6.32 2.59 0.41 2757
6.99 2.03 0.29 2782 6.75 1.96 0.29 2830
6.14 3.50 0.57 2586 5.89 3.36 0.57 2635
6.57 2.96 0.45 2684 6.32 2.84 0.45 2757
6.99 2.31 0.33 2782 6.75 2.23 0.33 2830
7.46 1.57 0.21 2867 7.24 1.52 0.21 2928
6.14 3.75 0.61 2586 5.89 3.59 0.61 2635
6.57 3.22 0.49 2684 6.32 3.10 0.49 2757
6.99 2.59 0.37 2782 6.75 2.50 0.37 2830
7.46 1.86 0.25 2867 7.24 1.81 0.25 2928
6.14 3.99 0.65 2586 5.89 3.83 0.65 2635
6.57 3.48 0.53 2684 6.32 3.35 0.53 2757
6.99 2.87 0.41 2782 6.75 2.77 0.41 2830
7.46 2.16 0.29 2867 7.24 2.10 0.29 2928
7.85 1.33 0.17 2965 7.60 1.29 0.17 3026
6.14 4.24 0.69 2586 5.89 4.07 0.69 2635
6.57 3.74 0.57 2684 6.32 3.60 0.57 2757
6.99 3.15 0.45 2782 6.75 3.04 0.45 2830
7.46 2.46 0.33 2867 7.24 2.39 0.33 2928
7.85 1.65 0.21 2965 7.60 1.60 0.21 3026
6.14 4.48 0.73 2586 5.89 4.30 0.73 2635
6.57 4.01 0.61 2684 6.32 3.85 0.61 2757
6.99 3.43 0.49 2782 6.75 3.31 0.49 2830
7.46 2.76 0.37 2867 7.24 2.68 0.37 2928
7.85 1.96 0.25 2965 7.60 1.90 0.25 3026
6.14 4.73 0.77 2586 5.89 4.54 0.77 2635
6.57 4.27 0.65 2684 6.32 4.11 0.65 2757
6.99 3.71 0.53 2782 6.75 3.57 0.53 2830
7.46 3.06 0.41 2867 7.24 2.97 0.41 2928
7.85 2.28 0.29 2965 7.60 2.20 0.29 3026
6.14 4.97 0.81 2586 5.89 4.77 0.81 2635
6.57 4.53 0.69 2684 6.32 4.36 0.69 2757
6.99 3.99 0.57 2782 6.75 3.84 0.57 2830
7.46 3.35 0.45 2867 7.24 3.26 0.45 2928
7.85 2.59 0.33 2965 7.60 2.51 0.33 3026
6.14 5.22 0.85 2586 5.89 5.01 0.85 2635
6.57 4.79 0.73 2684 6.32 4.61 0.73 2757
6.99 4.27 0.61 2782 6.75 4.11 0.61 2830
7.46 3.65 0.49 2867 7.24 3.55 0.49 2928
7.85 2.90 0.37 2965 7.60 2.81 0.37 3026
6.14 5.47 0.89 2586 5.89 5.24 0.89 2635
6.57 5.06 0.77 2684 6.32 4.87 0.77 2757
6.99 4.55 0.65 2782 6.75 4.38 0.65 2830
7.46 3.95 0.53 2867 7.24 3.84 0.53 2928
7.85 3.22 0.41 2965 7.60 3.11 0.41 3026
6.96 3.13 0.45 2391 6.39 2.88 0.45 2538
7.31 2.41 0.33 2489 6.82 2.25 0.33 2611
6.96 3.41 0.49 2391 6.39 3.13 0.49 2538
7.31 2.71 0.37 2489 6.82 2.52 0.37 2611
7.74 1.93 0.25 2586 7.24 1.81 0.25 2733
6.96 3.69 0.53 2391 6.39 3.39 0.53 2538
7.31 3.00 0.41 2489 6.82 2.79 0.41 2611
7.74 2.24 0.29 2586 7.24 2.10 0.29 2733
6.96 3.97 0.57 2391 6.39 3.64 0.57 2538
7.31 3.29 0.45 2489 6.82 3.07 0.45 2611
7.74 2.55 0.33 2586 7.24 2.39 0.33 2733
8.17 1.71 0.21 2684 7.67 1.61 0.21 2806
6.96 4.24 0.61 2391 6.39 3.90 0.61 2538
7.31 3.58 0.49 2489 6.82 3.34 0.49 2611
7.74 2.86 0.37 2586 7.24 2.68 0.37 2733
8.17 2.04 0.25 2684 7.67 1.92 0.25 2806
6.96 4.52 0.65 2391 6.39 4.15 0.65 2538
7.31 3.88 0.53 2489 6.82 3.61 0.53 2611
7.74 3.17 0.41 2586 7.24 2.97 0.41 2733
8.17 2.37 0.29 2684 7.67 2.22 0.29 2806
8.59 1.46 0.17 2782 8.09 1.38 0.17 2904
6.96 4.80 0.69 2391 6.39 4.41 0.69 2538
7.31 4.17 0.57 2489 6.82 3.89 0.57 2611
7.74 3.48 0.45 2586 7.24 3.26 0.45 2733
8.17 2.69 0.33 2684 7.67 2.53 0.33 2806
8.59 1.80 0.21 2782 8.09 1.70 0.21 2904
6.96 5.08 0.73 2391 6.39 4.66 0.73 2538
7.31 4.46 0.61 2489 6.82 4.16 0.61 2611
7.74 3.79 0.49 2586 7.24 3.55 0.49 2733
8.17 3.02 0.37 2684 7.67 2.84 0.37 2806
8.59 2.15 0.25 2782 8.09 2.02 0.25 2904
6.96 5.36 0.77 2391 6.39 4.92 0.77 2538
7.31 4.75 0.65 2489 6.82 4.43 0.65 2611
7.74 4.10 0.53 2586 7.24 3.84 0.53 2733
8.17 3.35 0.41 2684 7.67 3.14 0.41 2806
8.59 2.49 0.29 2782 8.09 2.35 0.29 2904
6.96 5.64 0.81 2391 6.39 5.18 0.81 2538
7.31 5.05 0.69 2489 6.82 4.70 0.69 2611
7.74 4.41 0.57 2586 7.24 4.13 0.57 2733
8.17 3.67 0.45 2684 7.67 3.45 0.45 2806
8.59 2.84 0.33 2782 8.09 2.67 0.33 2904
6.96 5.91 0.85 2391 6.39 5.43 0.85 2538
7.31 5.34 0.73 2489 6.82 4.98 0.73 2611
7.74 4.72 0.61 2586 7.24 4.42 0.61 2733
8.17 4.00 0.49 2684 7.67 3.76 0.49 2806
8.59 3.18 0.37 2782 8.09 2.99 0.37 2904
6.96 6.19 0.89 2391 6.39 5.69 0.89 2538
7.31 5.63 0.77 2489 6.82 5.25 0.77 2611
7.74 5.03 0.65 2586 7.24 4.71 0.65 2733
8.17 4.33 0.53 2684 7.67 4.06 0.53 2806
8.59 3.52 0.41 2782 8.09 3.32 0.41 2904
PERFORMANCE DATA COOL operation at Rated frequency
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MSZ-GA71VA: MUZ-GA71VA
Page 25
25
CAPACITY:5.9(kW)
INPUT:1630(W)
OUTDOOR WB(°C)
3.72 1099 4.48 1318 5.25 1487 6.02 1606 6.79 1707 7.49 1758 8.26 1791
3.54 1183 4.25 1403 5.02 1555 5.72 1673 6.49 1758 7.20 1808 7.94 1876
3.19 1268 3.95 1487 4.66 1639 5.43 1758 6.20 1842 6.90 1893 7.67 1944
INDOOR
-10-5 0 5 101520
DB(°C)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 21 26
CAPACITY:6.8(kW)
INPUT:1940(W)
OUTDOOR WB(°C)
4.28 1294 5.17 1552
6.05
1751 6.94 1891 7.82 2010 8.64 2070 9.52 2109
4.08 1393 4.90 1652
5.78
1831 6.60 1970 7.48 2070 8.30 2129 9.15 2209
3.67 1493 4.56 1751
5.37
1930 6.26 2070 7.14 2169 7.96 2229 8.84 2289
INDOOR
-10-5 0 5 101520
DB(°C)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 21 26
CAPACITY:8.1(kW)
INPUT:2450(W)
OUTDOOR WB(°C)
INDOOR
-10-5 0 5 101520
DB(°C)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 21 26
5.10 1625 6.16 1950 7.21 2200 8.26 2375 9.32 2525 10.29 2600 11.34 2650
4.86 1750 5.83 2075 6.89 2300 7.86 2475 8.91 2600 9.88 2675 10.89 2775
4.37 1875 5.43 2200 6.40 2425 7.45 2600 8.51 2725 9.48 2800 10.53 2875
PERFORMANCE DATA HEAT operation at Rated frequency
NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
MSZ-GA50VA : MUZ-GA50VA
MSZ-GA60VA : MUZ-GA60VA
MSZ-GA71VA : MUZ-GA71VA
Page 26
26
9
ACTUATOR CONTROL
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
Relation between main sensor and actuator.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Outdoor heat exchanger temperature
Ambient temperature thermistor
Purpose
Protection
Defrosting Protection
Defrosting
Protection
Protection
Protection
Compressor LEV
Outdoor fan motor
R.V. coil
Sensor
Actuator
Page 27
27
SERVICE FUNCTIONS
10
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting serv­ice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to 11-2, 11-3 and 11-4.
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
Contents of “SERVICE FUNCTIONS” have been removed.
Lead wiring
Housing point
Incorrect
Correct
Page 28
28
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of the indoor/outdoor unit failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
NOTE1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnorma l.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2
Turn ON the power supply. <
Preparation of the remote controller
>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.
First, release RESET button. Hold down the other two buttons for another 3 seconds. Confirm that the indicators on the LCD screen shown in the right figures are all displayed. Then release the buttons.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.(Refer to 11-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to 11-2.3). Make sure to check at least two consecutive blinking cycles. 3
1. Regardless of normal or abnormal condition, a short
beep is emitted once the signal is received.
Page 29
29
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
NOTE1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
Does left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks°C The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 25°C. 1
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to 11-2.3.). Make sure to check at least two consecutive blinking cycles. 2
Release the failure mode recall function according to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall function.
The outdoor unit might be abnormal. Confirm if outdoor unit is abnormal according to the following procedures.
Page 30
30
3. Outdoor failure mode table
OFF None (Normal) 2-time flash
3-time flash
4-time flash
5-time flash
6-time flash
7-time flash
8-time flash
Lighting Lighting
Lighting Once
Lighting Once Lighting Twice
Lighting 3 times Lighting 4 times
Lighting 9 times
Once Goes
out
Lighting
Lighting
Lighting
Lighting
3 times
Goes
out
4 times Goes
out
Lighting
Lighting
Lighting
Lighting
Lighting
5 times
9-time flash
10-time flash
• Check the connection of the compressor connecting wire.
• Refer to 11-4. "How to check inverter/compressor".
• Check the stop valve.
• Replace the outdoor electronic control P.C. board.
•Check refrigerant circuit and refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Refer to 11-6. "Check of outdoor fan motor".
• Replace the outdoor electronic control P.C. board.
•Check refrigerant circuit and refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Reconnect compressor connector.
• Refer to 11-6. "How to check inverter/ compressor."
• Check the stop valve.
•Check refrigerant circuit and refrigerant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoot unit air passage.
• Refer to 11-6. "Check of outdoor fan motor".
• Refer to 11-6. "Check of outdoor thermistors".
• Refer to 11-6. "Check of outdoor thermistors".
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or when converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
Thermistor shorts or opens during compressor running.
28A current flows into intelligent power module.
High-pressure is detected with the high-pressure switch (HPS) during operation.
The outdoor heat exchanger temperature exceeds 70°Cduring cooling or the indoor gas pipe temperature exceeds 70°C during heating.
The fin temperature exceeds 87°C during operation.
The P.C. board temperature exceeds 70°C during operation.
Failure occurs continuously 3 times within 30 seconds after the fan gets started.
Nonvolatile memory data cannot be read properly.
The frequency of the compressor is kept 80Hz or more and the discharge temperature is kept under 39°C for more than 20
minutes.
Outdoor power system
Discharge temperature thermistor
Defrost thermistor Ambient temperature thermistor
Fin temperature thermistor P.C. board temperature
thermistor
Outdoor heat exchanger temperature thermistor
Overcurrent
Discharge temperature
High pressure
Fin temperature
P.C. board temperature
Outdoor fan motor
Nonvolatile memory data
Discharge temperature
--
Abnormal point
(Failure mode/protection)
Condition
Remedy
Indoor/outdoor
unit failure mode
recall function
LED indication
(Outdoor P.C. board)
LED 1 LED 2
Discharge temperature exceeds 116 °C during operation. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
The left lamp of
OPERATION INDICAOR
lamp(Indoor unit)
Page 31
31
11-time flash
• Check the connecting wire between outdoor electronic control P.C. board and power board.
• Replace the power board.
• Check the connecting wire among electronic control P.C. board, noise filter P.C. board and power board.
• Check the voltage of power supply.
• Replace the power board.
• Check the voltage of power supply.
• Replace the outdoor electronic control P.C. board.
The communication between boards protection stop is continuously performed twice.
Communication error occurs between the electronic control P.C. board and power board for more than 10 seconds.
Current sensor protection stop is continuously performed twice.
A short or open circuit is detected in the current sensor during compressor operating.
The protection stop of the zero cross detecting circuit is continuously performed 10 times.
Zero cross signal cannot be detected while the compressor is operating.
A failure is detected in the operation of the converter during operation.
The bus-bar voltage exceeds 400V or falls to 200V or below during compressor operating.
The bus-bar voltage exceeds 400V or falls to 50V or below during compressor operating.
Communication error between P.C. boards
Current sensor
Zero cross detecting circuit
Converter
Bus-bar voltage (1)
Bus-bar voltage (2)
Even if this protection stop is performed continuously 3 times, it does not mean the abnormality in outdoor power system.
Lighting 6 times
Lighting 7 times
5 times Goes
out
5 times
Goes
out
5 times
6 times
Goes
out
Goes
out
Abnormal point
(Failure mode/protection)
Condition
Remedy
Indoor/outdoor
unit failure mode
recall function
LED indication
(Outdoor P.C. board)
LED 1 LED 2
The left lamp of
OPERATION INDICATOR
lamp(Indoor unit)
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4.).
Page 32
32
11-3. INSTRUCTION OF TROUBLESHOOTING
Start
Indoor unit Operates. Outdoor unit does not operate.
Indoor unit does not receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates only in Test Run operation. (Refer to 8-3.)
Outdoor unit does not operate even in Test Run operation. (Refer to 8-3.)
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit does not operate, when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage".
Refer to 11-6. "How to check inverter/ compressor".
Refer to "Check of remote controller and receiver P.C. board".
1. Check indoor/outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to "Check of indoor electronic control P.C. board and indoor fan motor".
Unit does not operate normal operation in COOL or HEAT mode.
Refer to 11-6. "Check of R.V. coil".
Left lamp Flash on and off at
0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal.
Left lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Left lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Left
lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
Left lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Left lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to 11-6. "How to check of mis-wiring and serial signal error".
“Test Run Operation” means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage".
Refer to "Check of indoor fan motor".
Refer to 11-6. "How to check inverter/ compressor".
Refer to 11-6. "Check of outdoor thermistors".
Replace inverter P.C. board or outdoor electronic control P.C. board.
Left lamp 14-time flash Cause: Outdoor unit
• Other abnormality
Check 11-2.2. "Flow chart of the detailed outdoor unit failure mode recall function."
Left lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
Refer to indoor unit service manual.
Indoor unit operates. Outdoor unit does not operate normally.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
Page 33
33
11-4. TROUBLESHOOTING CHECK TABLE
LED1(Red) LED2(Yellow)
Lightning Twice Outdoor power system
• Check the connection of the compressor connecting wire.
• Refer to 11-6. "How to check inverter/compressor".
• Check the stop valve.
Lightning 3 times
Discharge temperature thermistor
• Refer to 11-6. "Check of outdoor thermistors".
• Refer to 11-6. "Check of outdoor thermistors".
Outdoor heat exchanger temperature thermistor
Defrost thermistor
Lightning 7 times Nonvolatile memory data • Replace the outdoor electronic control P.C. board.
Lightning 8 times Current sensor • Replace the power board.
Lightning 11 times
Communication error between P.C. boards
• Check the connecting wire between outdoor electronic control P.C. board and power board.
Lightning 12 times
Zero cross detecting circuit • Check the connecting wire among outdoor electronic control
P.C. board, noise filter P.C. board and power board.
Abnormal point/Condition
Remedy
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor start-up.
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 5 minutes of compressor start-up.
• Refer to 11-6. "Check of outdoor thermistors".
• Replace the outdoor electronic control P.C. board.
Indication
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or when converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 10 minutes of compressor start-up.
Condition
The nonvolatile memory data cannot be read properly.
Lightning 6 times Serial signal
Fin temperature thermistor
P.C board temperature thermistor
Lightning 4 times
Ambient temperature thermistor
Current sensor protection stop is continuously performed twice.
The communication protection stop between boards is continuously performed twice.
The protection stop of the zero cross detecting circuit is continuously performed 10 times.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
5 timesLightning
Outdoor electronic control P.C. board (Parts side)
IPM protection
Lock protection
3 times Goes out
Discharge temperature protection
• Check the amount of gas and refrigerant circuit.
• Refer to 11-6. "Check of LEV".
Fin temperature protection
P.C. board temperature protection
High-pressure protection
8 times Goes out
Converter protection
• Replace the power board.
Bus-bar voltage protection (1)
• Check the voltage of power supply.
• Replace the power board or the outdoor electronic control P.C. board.
• Refer to 11-6. "Check of bus-bar voltage".
Bus-bar voltage protection (2)
13 times Goes out Outdoor fan motor • Refer to 11-6. "Check of outdoor fan motor".
Lighting 8 times
Current sensor protection
• Replace the power board.
Lighting 11 times
Communication between P.C. boards protection
• Check the connecting wire between outdoor electronic control P.C. board and power board.
Lighting 12 times
Zero cross detecting circuit protection
• Check the connecting wire among outdoor electronic control P.C. board, noise filter P.C. board and power board.
•Check refrigerant circuit and refrigerant amount.
•Refer to 11-6. "Check of outdoor fan motor".
• Check the amount of gas and the refrigerant circuit.
• Check stop valve.
• Reconnect compressor connector.
• Refer to 11-6. "How to check inverter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice Goes out
4 times Goes out
5 times Goes out
9 times Goes out
Overcurrent is detected after 30 seconds of compressor start-up.
Overcurrent is detected within 30 seconds of compressor start-up.
The bus-bar voltage exceeds 400V or falls to 200V or below during compressor operating.
The bus-bar voltage exceeds 400V or falls to 50V or below during compressor operating.
Discharge temperature exceeds 116°C during operation and compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
The fin temperature exceeds 87°C during operation.
The P.C. board temperature exceeds 70°C during operation.
High-pressure is detected with the high-pressure switch (HPS) during operation.
Failure occurs continuously 3 times within 30 seconds after the fan gets started.
A short or open circuit is detected in the current sensor during compressor operating.
Communication error occurs between the outdoor electronic control P.C. board and power board for more than 10 seconds.
Zero cross signal cannot be detected while the compressor is operating.
The outdoor heat exchanger temperature exceeds 70°C during cooling or indoor gas pipe temperature exceeds 70°C during heating.
A failure is detected in the operation of the converter during operation.
Outdoor unit does not operate.
Lighting
• Refer to 11-6. "How to check mis-wiring and serial signal error".
The communication fails between the indoor and outdoor unit for 3 minutes.
LED2
LED1
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit stops and restarts 3 minutes later' is repeated.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED is lighted during normal operation.
Page 34
34
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighting
Discharge temperature protection
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Refer to 11-6. "Check of outdoor thermistors".
4 times
Lighting
Low discharge temperature protection
• Refer to 11-6. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
5 times
Lighting
Cooling high-pressure protection
This symptom does not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
-
-
These symptoms do not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Twice Lighting
Once Lighting
The discharge temperature exceeds 100°C during operation.
The frequency of the compressor is kept 80Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes.
The outdoor heat exchanger temperature exceeds 58°C during operation.
9 times
Lighting
Inverter check mode
Lighting
Lighting
Normal
The unit is operated with emergency operation switch.
-
The input current exceeds 15A.
The current of the compressor exceeds 15A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
LED1(Red) LED2(Yellow)
Abnormal point/Condition Remedy
Indication
Condition
Outdoor unit operates.
Outdoor unit operates
No.
Symptom
20
21
22
23
24
25
26
Page 35
35
Part name Check method and criterion Figure Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor (RT68)
Measure the resistance with a tester.
Refer to 11-7. “Test point diagram and voltage”, 1. “Outdoor electronic control P.C. board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-7. “Test point diagram and voltage”,1. “Outdoor electronic control P.C. board”, for the chart of thermistor.
Fin temperature thermistor (RT64)
Compressor
Measure the resistance between terminals using a tester. (Winding temperature: -10 °C ~ 40 °C)
Normal
GA50 GA60VA-
E1,E2
GA60VA-
E3
GA71VA
0.40 Ω ~ 0.49 Ω 0.86 Ω ~ 1.06 Ω 1.29 Ω ~ 1.49 Ω
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Part temperature: -10 °C ~ 40 °C)
Color of lead wire Normal
RED - BLK
13.4 Ω ~ 16.4 ΩBLK - WHT
WHT - RED
R. V. coil
Measure the resistance using a tester. (Part temperature: -10 °C ~ 40 °C)
Normal
MUZ-GA60VA
-
E3
Other models
1.32 kΩ ~ 1.62 kΩ 2.6 kΩ ~ 3.3 kΩ
Linear expansion valve
Measure the resistance using a tester. (Part temperature: -10 °C ~ 40 °C)
Color of lead wire Normal
WHT - RED
37.4 Ω ~ 53.9 Ω
RED - ORN
YLW - BRN BRN - BLU
High pressure switch (HPS)
MUZ-GA60VA
-
E3
MUZ-GA71VA
Pressure
3.7 ± 0.15 MPa Close
4.8 MPa Open
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
11-5. TROUBLE CRITERION OF MAIN PARTS
W
U
V
WHT
RED
BLK
RED
YLW
BRN
ORN
BL
U
LEV
WHT
U
RED
WHT
BLK
V
W
(W)
(V)
(U)
0.05
0.1
+
-
Page 36
36
Check of power supply
Outdoor unit does not operate.
11-6. TROUBLESHOOTING FLOW
Turn ON power supply.
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
Replace the power board.
Check the connecting of parts of main power supply circuit.
Is there voltage of 230 VAC in the power supply terminal block?
Is the output voltage from the noise filter P.C. board 230 VAC?
Is the input voltage to the outdoor electronic control P.C. board 325 VDC?
Check the power supply cable.
Replace the outdoor electronic control P.C. board.
Replace the noise filter P.C. board.
Is fuse (F64) blown?
Is the input voltage to the power board 230 VAC?
Replace the fuse.
Replace the reactor.
Page 37
37
How to check mis-wiring and serial signal error (when outdoor unit does not work)
B
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second. Outdoor unit does not operate.
Is there rated voltage in the power supply?
Is there any mis-wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
1. Mis-wiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.
3.Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
2 Be careful to the residual
voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Refer to indoor unit service manual.
Lighted Blinking
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power supply.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and S3. 1
B
Turn ON the power supply.
Check the wiring.
Correct them.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. 2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
Is serial signal error indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light away from each other.
· Attach a filter on remote control receiving section of the indoor unit.
A
Is serial signal error indicated 6 minutes later?
No
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
3
Outdoor electronic control P.C. board
(Parts side)
LED2
LED1
Page 38
38
Check of R.V. coil
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in HEAT mode.
Is there voltage of 230 VAC between pin1 and pin 2 at connector CN912?
Turn OFF power supply of indoor and outdoor unit.
1. Turn OFF power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in HEAT mode.
Replace the 4-way valve.
Replace the noise filter P.C. board.
Replace the R.V. coil.
Is there voltage 12 VDC between the connector CN781 pin 5 (+) and pin 3 (-)?
Replace the electronic control P.C. board.
Disconnect the connector CN912 in noise filter P. C. board. Is there normal resistance to R.V. coil?
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in COOL mode.
Is there voltage of 230 VAC between pin1 and pin 2 at connector CN912?
1. Turn OFF power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.
2. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION in COOL mode.
Replace the 4-way valve.
Replace the noise filter P.C. board.
Is there voltage 12 VDC between the connector CN781 pin 5 (+) and pin 3 (-)?
Replace the outdoor electronic control P.C. board.
If the connector CN912 is not connected or R.V. coil is open, voltage occurs between terminals even when the control is OFF.
• When heating operation does not work.
• When cooling operation does not work.
The cooling operation or heating operation does not operate.
Page 39
39
When OPERATION INDICATOR lamp flashes 5-time.
• When heating, room does not get warm.
• When cooling, room does not get cool.
Check of LEV
No
Yes
No
Yes
Turn ON power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with hands?
Disconnect the connector CN795. Is there normal resistance to LEV coil?
Normal
Replace the outdoor electronic control P.C. board.
Replace the LEV coil.
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit gets warm.
How to check inverter/compressor
No
No
Yes
Yes
Yes
No
Yes
No
Disconnect the terminal of the compressor. 3 minutes after turning ON the power supply, start
EMERGENCY OPERATION.
Is output balanced?
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short 10 to 60 seconds: compressor lock 60 seconds to 5minutes: refrigerant circuit defective 5 minutes or more: normal
Measure the voltage between each lead wire leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Is there output voltage?
Turn OFF power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is the resistance between each terminal normal?
Is the input voltage to the outdoor electronic control P.C. board 370V or more?
Reconnect the lead wire of compressor, and turn ON power supply to indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.
Replace the compressor.
Replace the power board.
• After the outdoor fan starts running, wait for 1 minute or more before
measuring the voltage.
• The output voltage values have the tolerance of ± 20%.
Page 40
40
Check of outdoor fan motor
• Fan motor does not operate or stops operating shortly after starting the operation.
Check of outdoor thermistors
• When OPERATION INDICATOR lamp flashes 6-time.
• When thermistor is abnormal.
Disconnect the connector in the outdoor electronic control P.C. board or the outdoor power board (see below table), and measure the resistance of thermistor. Is the thermistor normal? (Refer to 11-7.1.)
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Replace the thermistor.
Normal
Replace the outdoor electronic control P.C. board.
Yes
Yes
No
No
Reconnect the connector CN661, CN663 and CN3. 3 minutes after turning ON the power supply, start EMERGENCY OPERATION.
Defrost Discharge temperature Outdoor heat exchanger temperature Ambient temperature Fin temperature
Symbol
RT61 RT62 RT68 RT65 RT64
Connector, Pin No.Thermistor Board Between CN661 pin1 and pin2 Between CN661 pin3 and pin4 Between CN661 pin7 and pin8 Between CN663 pin1 and pin2 Between CN3 pin1 and pin2
Outdoor electronic control P.C. board
Outdoor power board
When RT64 is abnormal, replace the
outdoor power
board.
Yes
No
No
Yes
Yes
No
(Fixed to either 5V or 0 VDC)
Check the connection between the connector CN931 and CN932.
Disconnect CN932 from outdoor electronic control P.C. board, and turn ON the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between (+) and (-) Between (+) and (-) Between (+) and (-)
Is the resistance between each terminal of outdoor fan motor normal?
Does the outdoor fan motor rotate smoothly?
Does the voltage between each terminal become 5 VDC and 0 VDC repeatedly?
Replace the outdoor DC fan motor.
Replace the outdoor electronic control P.C. board.
Page 41
41
Check of HPS
• When the operation frequency does not go up from lowest frequency.
MUZ-GA60VA
-
E3
MUZ-GA71VA
Infinity
0Ω
No
Yes
1. Disconnect the connector CN681 in the electronic control P.C. board.
2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.
Check the resistance between each terminal.
Reconnect CN681. Turn ON power supply to the indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed immediately after compressor starts?
Replace HPS.
Replace the electronic control P.C. board.
Normal
I Check of bus-bar voltage
•Check the voltage of power supply.
•Confi rm outdoor unit failure mode recall function. (Refer to 11-2.2.)
Blink 5 times
Confi rm LED1 indication lamp on the outdoor electronic control P.C. board.
Replace the power board.
Blink 9 times
Replace the outdoor electronic control P.C. board.
Turn OFF power supply before removing P.C. board.
Confi rm LED1 indication lamp on the outdoor electronic control P.C. board.
Turn ON power supply. Start operation.
Blink 6 times
Replace the outdoor electronic control P.C. board .
Lighting
Replace the outdoor electronic control P.C. board.
Blink 9 times
Replace the power board.
Confi rm LED1 indication lamp on the outdoor electronic control P.C. board.
Turn ON power supply. Start operation.
Normal
Lighting Lighting
Page 42
42
Electromagnetic noise enters into TV sets or radios
J
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
Page 43
43
-20-100 10203040
100
90
80
70
60
50
40
30
20
10
0
0 1020304050607080
200
180
160
140
120
100
80
60
40
20
0
Resistance (kΩ)
Resistance (kΩ)
Temperature (°C)
Temperature (°C)
Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
Fin temperature thermistor (RT64)
0 102030405060708090100110120
700
600
500
400
300
200
100
0
Resistance (kΩ)
Temperature (°C)
Discharge temperature thermistor (RT62)
11-7. TEST POINT DIAGRAM AND VOLTAGE
1. Outdoor electronic control P.C. board
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
LED 1
LED 2
CN801
325 VDC
-
370 VDC
Input
(
(
CN932
20-90 VAC
GND
5 V
5 VDC
pulse wave
(
To fan
motor
Defrost thermistor (RT61)
Discharge temperature
thermistor (RT62)
Outdoor heat exchanger
temperature thermistor (RT68)
(
(
(+)
(–)
(+)
(–)
Rush current relay
(–)R.V. coil
(
12 VDC
15 V
15 V
CN931
(+)
(–)
(
CN661
CN701
Signal transmission
(To power board)
5 VDC pulse wave
(+)
(–)
(
GND
CN702
Signal reception
(From power board)
5 VDC pulse wave
GND (power board)
CN781
CN795
12 VDC
pulse wave
LEV
(
(
(
(
(
F801
FUSE
T3.15AL250V
(
Ambient temperature
thermistor (RT65)
CN663
Serial signal Room A
5 - 10 VDC
CN601
230 VAC Input
CN681 High pressure switch
MUZ-GA60VA-
E3
MUZ-GA71VA
(
(
(
Page 44
44
{
CN912 R.V. coil 230 VAC
230 VAC Input
230 VAC Output
{
CN901 To electronic control P.C. board
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
F64 FUSE T2AL250V
F911 FUSE T1AL250V
2. Noise filter P.C. board
CN902 To power board
{
CN903 To power board
{
230 VAC Output
NR64 VARISTOR
Page 45
45
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
3. Outdoor power board
325-370 VDC Output
(Red)
(White)
Connect to the compressor Voltage among phases: 5 V to 180 V
Connect to the earth
CN5 Primary current detection (Connect to the noise filter)
CN2 Connect to the controller board (+)1-5(–): Signal transmission (To electronic control P.C. board) 5 VDC pulse wave (+)2-5(–): Zero cross signal 3-4 : Not used (+)6-5(–): 15 V (+)7-5(–): 15 V
(+)
(–)
Signal reception (From electronic control P.C. board) 5 VDC pulse wave
)
CN3 Fin temperature thermistor RT64
325-370 VDC Output
(Red)
(White)
Connect to the compressor Voltage among phases: 5V to 180V
Connect to the earth
CN5 Primary current detection (Connect to the noise filter)
CN2 Connect to the controller board (+)1-5(–): Signal transmission (To electronic control P.C. board) 5 VDC pulse wave (+)2-5(–): Zero cross signal 3-4 : Not used (+)6-5(–): 15 V (+)7-5(–): 15 V
(+)
(–)
Signal reception (From electronic control P.C. board) 5 VDC pulse wave
)
CN3 Fin temperature thermistor RT64
1
3
1
3
Page 46
46
12
DISASSEMBLY INSTRUCTIONS
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA
NOTE:
These photos are MUZ-GA71VA. Other models are almost the same as MUZ-GA71VA. Turn OFF power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connecting wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 2
Photo 1
Photo 3
Screw of the top panel
Screws of the cabinet
Screws of the cabinet
Screws of the top panel
Screws of the cabinet
Screw of the service panel
Screw of the valve cover
Screw of the motor support
Set screws of the back panel
Screws of the back panel
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
Page 47
47
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board and power board
(1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel.(Refer to 1.) (3) Disconnect the following connectors; <Electronic control P.C. board> CN931 and CN932 (Fan motor) CN795 (LEV) CN661 (Discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor) CN663 (Ambient temperature thermistor) CN681 (High pressure switch) (GA60VA-
E3
, GA71VA) <Noise filter P.C. board> CN912 (R.V coil) (4) Remove the compressor connector. (5) Remove the screws fixing the relay panel. (6) Remove the inverter assembly. (7) Disconnect all connectors and lead wires on the electronic
control P.C. board.
(8) Remove the electronic control P.C. board from the inverter
assembly. (9) Remove the screws fixing the power board assembly. (10)
Disconnect all connectors and lead wires on the power
board. (11)
Remove the power board from the inverter assembly.
(12)
Disconnect all connectors and lead wires on the noise filter
P.C. board. (13)
Remove the noise filter P.C. board from the inverter
assembly.
Photo 4
3. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors; <Noise filter P.C. board> CN912 (R.V coil) (4) Remove the R.V. coil. (Photo 9)
Screws of the relay panel
Screws of the power board assembly
Page 48
48
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors; <Electronic control P.C. board> CN931 and CN932 (Fan motor) (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 7
Propeller
Screws of the outdoor fan motor
OPERATING PROCEDURE
PHOTOS
4. Removing the defrost thermistor, discharge temper­ature thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors; <Electronic control P.C. board> CN661 (Discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor) CN663 (Ambient temperature thermistor) (4) Pull out the defrost thermistor from its holder. (5) Pull out the discharge temperature thermistor from its holder. (6) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(7) Pull out the ambient temperature thermistor from its holder.
Photo 5
Photo 6
Defrost thermistor
Discharge temperature thermistor
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
Page 49
49
OPERATING PROCEDURE
PHOTOS
Photo 8
Brazed parts of 4-way valve
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm2 (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed part of 4-way valve and pipe.
7. Removing the reactor
(1) Remove the top panel. (Refer to 1.) (2) Disconnect the reactor lead wire. (3) Remove the screws of the reactor, and remove the reactor.
Photo 10
Screws of the reactor
Photo 9
Brazed part of the dis­charge pipe
R.V. coil
Brazed part of the suction pipe
Page 50
50
4
19
9
1
1310 12
2
5
6
7
8
16
14
20
22
23
24
25
293031
3
13
PARTS LIST (non-RoHS compliant)
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA 13-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
11
15
17
18
21
28
27
26
13-2. ACCESSORY
33
34
Page 51
51
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA 13-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No.
No.
Part Name
MUZ-GA50 VA -
E1
MUZ-GA60 VA -
E1
MUZ-GA71 VA -
E1
E02 819 297 E02 851 630 E02 853 630 E02 938 301 E02 851 501 E02 851 290 E02 853 290 E02 819 232 E02 819 009 E02 819 521 E02 853 646 E12 C34 506 E02 853 506 E02 939 900 E02 853 900 E02 851 661 E02 819 661 E02 821 662 E02 822 662 E02 851 640 E02 853 640 E02 851 493 E02 853 299 E02 935 490 E02 891 961 E02 819 650 E02 819 245 E12 D01 450 E12 C96 450 E12 C97 450 E02 935 374 E02 823 375 E02 851 337 E02 935 444 E02 935 309 E02 851 308 E02 935 440 E02 819 233 E02 817 009 E02 851 515 E02 851 936 E02 853 936 E02 861 936
1
2
3 4
5
6 7 8 9
10
11
12
13
14
15 16 17 18 19 20
21
22 23 24 25 26 27 28 29 30 31
32
TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER BASE BASE CABINET HANDLE FAN GUARD HIGH PRESSURE SWITCH COMPRESSOR RUBBER SET COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR STOP VALVE (GAS) STOP VALVE (GAS) STOP VALVE (LIQUID) STOP VALVE (LIQUID) EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE COIL OIL SEPARATOR R.V. COIL 4-WAY VALVE VALVE COVER SERVICE PANEL OUTDOOR ELECTRONIC CONTROL P.C. BOARD OUTDOOR ELECTRONIC CONTROL P.C. BOARD OUTDOOR ELECTRONIC CONTROL P.C. BOARD TERMINAL BLOCK TERMINAL BLOCK REACTOR NOISE FILTER P.C. BOARD AMBIENT TEMPERATURE THERMISTOR THERMISTOR SET POWER BOARD BACK PANEL (OUT) HANDLE MOTOR SUPPORT CAPILLARY TUBE (TAPER PIPE) CAPILLARY TUBE (TAPER PIPE) CAPILLARY TUBE
RC0J60-
3RUBBERS/SET 3RUBBERS/SET SNB130FLDH1 TNB220FMCH Ø12.7 Ø15.88 Ø6.35 Ø9.52
3P 3P
Including heat sink and RT64
Ø3.6xØ2.4x50 Ø3.6xØ2.4x50 Ø1.8xØ0.6x1000
MF
HPS
MC MC
LEV
21S4
TB1 TB2
L
RT65
RT61,RT62,RT68
1 1
1 1 1
1 1 1
3
1
1 1
1
1
1 1 1 1
1
1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1
1 1 1
3
1
1
1
1
1
1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1
1
1 1 1
1 1 1 1 1
3
1
1
1
1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1
1 1
DEFROST, DISCHARGE OUTDOOR HEAT EXCHANGER
Part number that is circled is not shown in the illustration.
PARTS LIST (non-RoHS compliant)
13-2. ACCESSORY
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No.
No.
Part Name
MUZ-GA50 VA -
E1
MUZ-GA60 VA -
E1
MUZ-GA71 VA -
E1
E02 817 704 E02 444 705
33 34
DRAIN SOCKET DRAIN CAP
Ø33
1 2
1 2
1 2
Page 52
52
4
19
9
1
1310 12
2
5
6
7
8
16
14
20
22
23
24
25
293031
3
14
RoHS PARTS LIST (RoHS compliant)
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA 14-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
11
15
17
18
21
28
27
26
Page 53
53
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA 14-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No.
RoHS
No.
Part Name
MUZ-GA50 VA -
E1
MUZ-GA60 VA -
E1 E2 E1 E2
MUZ-GA71 VA -
E12 819 297 E12 851 630 E12 853 630 E12 938 301 E12 851 501 E12 851 290 E12 853 290 E12 819 232 E12 819 009 E12 D84 521 E12 853 646 E12 C34 506 E12 853 506 E12 939 900 E12 C06 900 E12 C37 900 E12 853 900 E12 851 661 E12 819 661 E12 821 662 E12 822 662 E12 851 640 E12 853 640 E12 851 493 E12 853 299 E12 935 490 E12 D02 490 E12 891 961 E12 C18 961 E12 819 650 E12 819 245 E12 D01 450 E12 C96 450 E12 C97 450 E12 D02 450 E12 935 374 E12 823 375 E12 851 337 E12 935 444 E12 935 309 E12 851 308 E12 935 440 E12 B79 440 E12 819 233 E12 817 009 E12 851 515 E12 851 936 E12 853 936 E12 861 936
1
2
3 4
5
6 7 8 9
10
11
12
13
14
15 16
17
18
19 20
21
22 23 24 25 26 27
28
29 30 31
32
G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G
TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER BASE BASE CABINET HANDLE FAN GUARD HIGH PRESSURE SWITCH COMPRESSOR RUBBER SET COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR STOP VALVE (GAS) STOP VALVE (GAS) STOP VALVE (LIQUID) STOP VALVE (LIQUID) EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE COIL OIL SEPARATOR R.V. COIL R.V. COIL 4-WAY VALVE 4-WAY VALVE VALVE COVER SERVICE PANEL OUTDOOR ELECTRONIC CONTROL P.C. BOARD OUTDOOR ELECTRONIC CONTROL P.C. BOARD OUTDOOR ELECTRONIC CONTROL P.C. BOARD OUTDOOR ELECTRONIC CONTROL P.C. BOARD TERMINAL BLOCK TERMINAL BLOCK REACTOR NOISE FILTER P.C. BOARD AMBIENT TEMPERATURE THERMISTOR THERMISTOR SET POWER BOARD POWER BOARD BACK PANEL(OUT) HANDLE MOTOR SUPPORT CAPILLARY TUBE(TAPER PIPE) CAPILLARY TUBE(TAPER PIPE) CAPILLARY TUBE
RC0J60-
Including ice guard
3RUBBERS/SET 3RUBBERS/SET SNB130FLDH1 SNB130FLEH1 SNB130FGBH TNB220FMCH Ø12.7 Ø15.88 Ø6.35 Ø9.52
3P 3P
Including heat sink and RT64
Including heat sink and RT64
Ø3.6xØ2.4x50 Ø3.6xØ2.4x50 Ø1.8xØ0.6x1000
MF
HPS
MC MC MC MC
LEV
21S4 21S4
TB1 TB2
L
RT65
RT61,RT62,RT68
1 1
1 1 1
1 1 1
3
1
1 1
1
1
1
1
1 1
1
1 1 1 1 1 1 1
1 1 1 1
1
1 1 1 1
1 1 1
3
1
1 1
1
1 1 1
1
1 1
1
1 1 1 1 1 1 1
1 1 1 1
1
1 1
1 1 1
1 1 1
3
1
1
1
1
1
1
1
1 1 1
1 1 1 1 1 1 1
1 1 1 1
1
1 1 1
1 1 1 1 1
3
1
1
1
1 1 1 1
1
1 1
1
1 1 1 1 1 1 1
1 1 1
1 1
1
1 1 1
1 1 1 1 1
3
1
1
1
1 1 1 1
1
1 1
1
1 1 1 1 1 1 1
1 1 1
1 1
DEFROST, DISCHARGE OUTDOOR HEAT EXCHANGER
1 1
1 1 1
1 1 1 1 3
1
1 1
1
1
1
1 1 1
1 1 1 1 1 1 1
1 1 1 1 1
E3
Part number that is circled is not shown in the illustration.
RoHS PARTS LIST (RoHS compliant)
Page 54
MUZ-GA50VA MUZ-GA60VA MUZ-GA71VA 14-2. ACCESSORY
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No.
No.
RoHS
Part Name
MUZ-GA50 VA -
E1
MUZ-GA60 VA -
MUZ-GA71 VA -
E12 817 704 E12 444 705
12G
G
DRAIN SOCKET DRAIN CAP
Ø33
1 2
1 2
1 2
121
2
E1 E2 E1 E2
1 2
E3
1
2
RoHS PARTS LIST (RoHS compliant)
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD Distributed in Jun. 2011. No. OB389 REVISED EDITION-H Distributed in Jun. 2010. No. OB389 REVISED EDITION-G 6 Distributed in Sep. 2007. No. OB389 REVISED EDITION-F 6 Distributed in Jul. 2007. No. OB389 REVISED EDITION-E 6 Distributed in Jun. 2007. No. OB389 REVISED EDITION-D 6 Distributed in Apr. 2007. No. OB389 REVISED EDITION-C 6 Distributed in Aug. 2006. No. OB389 REVISED EDITION-B 6 Distributed in Jun. 2006. No. OB389 REVISED EDITION-A 6 Distributed in Jan. 2005. No. OB389 6 Made in Japan
New publication, effective Jun. 2011 Specifications subject to change without notice.
Loading...