Refrigerant
Composition (Ratio)
Refrigerant handling
Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point (:)
Steam pressure [25:](Mpa)
Saturated steam density [25:](Kg/K)
Combustibility
ODP w1
GWP w2
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell
w1:Ozone Destruction Parameter : based on CFC-11
w2 :Global Warmth Parameter : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
New SpecificationCurrent Specification
The incompatible refrigerating oil easily separates from
refrigerant and is in the upper layer inside the suction muffler.
Raising position of the oil back hole enables to back the
refrigerating oil of the upper layer to flow back to the
compressor.
Since refrigerant and refrigerating oil are compatible each,
refrigerating oil backs to the compressor through the lower
position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
3
-30 -20 -10010 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
NOTE : The unit of pressure has been changed to MPa on the
R410A toolsCan R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing
gauges. Port diameters have been changed to prevent any other refrigerant
from being charged into the unit.
Hose material and cap size have been changed to improve the pressure
resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge
Vacuum pump
adapter
Electronic scale for
refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No12.7 mm
Wall
thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
0.8 mm
0.8 mm
0.8 mm
Heat resisting foam plastic
Specific gravity 0.045 Thickness 8 mm
Insulation material
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being
charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less
than 0.8mm, as the pressure resistance is insufficient.
4
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter
mm
6.35
9.52
12.7
Dimension of flare nut
R410A
17
22
26
R22
17
22
24
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller holder
Fixing screw for 3 3.5 o 16 mm
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
Deodorizing filter
Air cleaning filter
Refrigerant oil
1
5
1
2
2
1
1
1
1
1
<Indoor unit>
1
2
3
4
5
6
7
8
9
0
Drain socket
Drain cap
1
2
<Outdoor unit: MUH type>
1
2
Air outlet
Drain outlet
Air inlet
(Back and side)
MUX-A19WV-MUX-A25WVMUX-A20WV-
E1
E1E1
MUX-A26WV-
E1
MXZ-A18WV-
Air inlet
(Back and side)
Air outlet
Piping
Drainage hose
Drain outlet
E1
Air inlet
(Back and side)
Air outlet
Piping
Drainage hose
Drain outlet
ACCESSORIES
MSC-A07WVMSC-A09WVMSC-A12WV-
E1
E1
E1
MUH-A07WVMUH-A09WVMUH-A12WV-
MXZ-A18WV-
1
Drain socket
2
Drain cap
7
E1
E1
E1
E1
1
2
MUX-A19WV-
E1
MUX-A25WV-
E1
MUX-A20WV-
E1
MUX-A10WV-
E1
MUX-A26WV-
E1
Combination of
the connectable
indoor units
OUTDOOR UNIT
A: MSC-A12WV- E1
B: MSC-A07WV-
E1
A:
B:
MSC-A09WV- E1
C:
A:
MSC-A07WV- E1
B:
A:
MSC-A12WV- E1
B:
C:
MSC-A09WV- E1
D:
A:
MSC-A12WV- E1
B:
REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
Open the front lid.
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
ON/OFF
ON/OFF
I FEEL
COOL
VANE
HEAT
DRY
/FAN
/
MODE
ECONO COOL
RESET
TOO
WARM
TOO
WARM
FAN
CLOCK
CLOCK
PM
AM
TOO
COOL
PM
AM
TOO
COOL
STOP
START
HR.
MIN.
TEMPERATURE buttons
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
VANE CONTROL button
INDOOR/ OUTDOOR CORRESPONDENCE TABLE3
MSC-A07WV -MSC-A09WV -MSC-A12WV -
E1E1E1
8
07
09
12
07+07
07+09
07+12
09+09
09+12
12+12
90
90
90
90
90
90
90
90
90
3.62
3.91
5.70
7.15
7.73
7.78
8.60
8.84
8.99
2.3
(0.9-2.95)
2.5
(0.9-3.30)
3.4
(0.9-4.00)
4.6
(1.49-5.30)
4.8
(1.49-5.40)
5.0
(1.51-5.60)
5.0
(1.51-5.55)
5.3
(1.53-5.80)
5.4
(1.55-6.00)
0.750
(0.225-1.000)
0.810
(0.225-1.070)
1.180
(0.220-1.450)
1.480
(0.370-2.060)
1.600
(0.370-2.070)
1.610
(0.365-2.100)
1.780
(0.370-2.105)
1.830
(0.365-2.110)
1.860
(0.370-2.130)
–
–
–
2.3
2.5
2.98
2.5
3.1
2.65
2.3
2.5
3.4
2.3
2.3
2.02
2.5
2.2
2.65
Indoor units
combination
Unit AUnit B
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
NOTE: Electrical data is for outdoor unit only.
MXZ-A18WV -
E1
NOTE: Electrical data is for outdoor unit only.
07
09
12
07+07
07+09
07+12
09+09
09+12
12+12
90
90
90
90
90
90
90
90
90
4.73
5.14
6.76
9.32
9.37
9.03
9.28
8.91
8.55
3.3
(0.9-4.0)
3.6
(0.9-4.5)
4.0
(0.9-4.8)
6.1
(1.53-6.70)
6.2
(1.53-6.80)
6.5
(1.55-7.00)
6.5
(1.55-7.0)
6.55
(1.56-7.1)
6.6
(1.58-7.2)
0.980
(0.225-1.115)
1.065
(0.225-1.195)
1.400
(0.220-1.680)
1.930
(0.300-2.070)
1.940
(0.300-2.040)
1.870
(0.295-1.980)
1.920
(0.295-2.010)
1.845
(0.295-1.950)
1.770
(0.290-1.850)
–
–
–
3.05
3.23
3.88
3.25
3.77
3.30
3.3
3.6
4.0
3.05
2.97
2.62
3.25
2.78
3.30
Indoor units
combination
Unit AUnit B
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
MXZ-A18WV -
E1
OUTDOOR UNIT
MXZ-A18WV-
Combination of the
connectable indoor units
07+07
07+09
07+12
09+09
09+12
12+12
E1
❈There is no combination other than this table.
4
INDOOR UNITS COMBINATION
9
5
Indoor model
Function
Indoor unit power supply
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med. /Low )
Fan speed (High/Med. /Low )
Fan speed regulator
Thermistor RT11(at 25:)
Thermistor RT12(at 25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at 20:)
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigerating oil (Model)
K /h
A
A
W
%
A
A
"
mm
kg
dB
rpm
k"
k"
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
MSC-A07WV -
E1
Single phase
230V,50Hz
10
0.17
35
90
—
0.17
WHT-BLK 413
BLK-RED 334
815O278O217
9
5
3
10
10
MU-A07WV -
E1
Single phase
230V,50Hz
10
—
2.76
0.22
RN092VHSHT
600
C-R 3.87
C-S 6.14
RA6V23-FC
WHT-BLK 353
BLK-RED 321
780o540o255
34
45
735
1
0.75
350 (NEO22 )
Cooling
474/372 /276
RC4V19-LA
36/31 /25
900/750 /600
2.3
0.9
1,686
2.98
675
98
23
3.24
MSC-A09WV - E1
Single phase
230V,50Hz
10
0.17
35
RC4V19-LA
WHT-BLK 413
BLK-RED 334
815O278O217
9
5
3
10
10
MU-A09WV -
E1
Single phase
230V,50Hz
10
—
RN099VHSHT
700
C-R 3.40
C-S 4.56
RA6V23-FC
WHT-BLK 353
BLK-RED 321
780o540o255
34
45
735
1
0.80
350 (NEO22 )
Cooling
474/384 /306
90
—
0.17
36/31 /25
900/770 /650
2.55
1.1
1,686
3.26
745
99
24
3.04
0.22
3.27
MSC-A12WV - E1
Single phase
230V,50Hz
582/444 /324
10
0.19
40
RC4V19-KA
WHT-BLK 316
BLK-RED 299
815O278O217
10
5
3
10
10
MU-A12WV -
E1
Single phase
230V,50Hz
1.6
1,914
10
4.91
—
97
29
RN135VHSHT
900
C-R 2.79
C-S 3.36
RA6V33-DC
WHT-BLK 301
BLK-RED 332
780o540o255
36
49
825
1
0.83
620 (NEO22)
Cooling
92
—
0.19
40/33 /26
930/760 /600
3.45
1,100
4.60
0.31
3.03
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Capacity
ww
ww
w
w
w
w
w
w
w
w
w
w
ww
w
w
ww
ww
w
w
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : IndoorDB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length 5m
w Reference value
10
Indoor model
Cooling
474/372 /276
Indoor unit power supply
Capacity
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Electrical
data
Starting current
Fan motor current
Function
w
w
K /h
A
A
W
%
A
A
Model
Winding
Fan
motor
resistance(at 20:)
Dimensions WOHOD
Weight
"
mm
kg
Air direction
Sound level(High/Med. /Low )
Fan speed(High/Med. /Low )
ww
ww
dB
rpm
36/31 /25
900/750 /600
Fan speed regulator
Thermistor RT11(at 25:)
Special
remarks
Thermistor RT12(at 25:)
k"
k"
Outdoor model
Outdoor unit power supply
Capacity
Dehumidification
Outdoor air flow
Capacity
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Electrical
data
Starting current
Compressor motor current
Fan motor current
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
Coefficient of performance (C.O.P)
Model
Output
Winding
Compressor
resistance (at 20:)
Model
Winding
Fan
motor
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Air flow (High/Med./Low)
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Air direction
Sound level
(High/Med./Low)
Fan speed
(High/Med./Low)
Fan speed regulator
Thermistor RT11 (at 25:)
Thermistor RT12 (at 25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20:)
Model
Winding
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigerating oil (Model)
Air flow (High/Med./Low)
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level
(High/Med./Low)
Fan speed
(High/Med./Low)
Fan speed regulator
Thermistor RT11 (at 25:)
Thermistor RT12 (at 25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20:)
Model
Winding
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigerating oil (Model)
Indoor units number
Indoor units total capacity (Connectable)
indoor units total capacity (Simultaneous operation)
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Crankcase heater
Power factor
Starting current
Compressor motor current
Fan motor current
Gas refrigerant
pipe joint
Refrigerant pipe
(flared) {9.52
Gas refrigerant
pipe joint
Refrigerant pipe
(flared) {12.7
Open as a rule
500mm or more if
the front and both
sides are open
100mm or more
200mm or more if
there are obstacles
to both sides
Open as a rule
500mm or more if the back,
both sides and top are open
350mm or more
100mm or more
OUTDOOR UNIT
Unit: mm
MUX-A26WV-
E1
OUTDOOR UNIT
MXZ-A18WV -
Drainage
3 holes
([33)
50
Air in
320
E1
500
587
273
65
Air in
Air out
840
121
34
REQUIRED SPACE
More than
330
360
40
69
640
100mm
Open as a rule
More than 200mm if the back,
both sides and top are open
Note:
*
The dimensions given along the arrrows above are required to guarantee
the air conditioner's performance. Install the unit in as wide a place as
possible for later service or repairs.
Service panel
Liquid refrigerant valve
(flared [6.35)
B UNIT
}
195
}
A UNIT
90 65 65 65
Gas refrigerant valve
(flared [9.52)
24
Open as a rule
More than100mm
if the front and both
sides are open
*
More than 100mm
200mm or more if
there are obstacles
to both sides
More than 350mm
8
SYMBOL
NR11
RT11
RT12
SR141
NAME
NAMENAME
INDOOR FAN CAPACITOR
FUSE(3.15A)
INDOOR FAN MOTOR (INNER FUSE)
VANE MOTOR
VARISTOR
ROOM TEMPERATURE THERMIST OR
INDOOR COIL THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
SYMBOL
C11
F11
MF
MV
SYMBOL
TB
T11
TRANSFORMER
CIRCUIT BREAKER
SR141
C11
RED
WHT
3
6
5
BRN
YLW
GRY
BLK
4
3
2
1
MF
121
CN
1
3
5
111
CN
112
CN
RT12
RT11
NR11
F11
ELECTRONIC CONTROL P.C. BOARD
CN211
TAB12
CN201
3
2
1
CN202
2
1
151
CN
5
5
BRN
RED
BLU
WHT
BLK
BLU
BRN
TB
L
3
N
2
1
12V
TO OUTDOOR
UNIT
CONNECTING
POWER
SUPPLY
CORD
~/N 230V
50Hz
GRN/YLW
POWER MONITOR,
RECEIVER
P.C.BOARD
REMOTE
CONTROLLER
MV
FOR
MUH OR
MXZ TYPE
FOR
MU OR
MUX TYPE
12V
PE
101
CN
T11
GRN
LD103
WIRING DIAGRAM
MSC-A07WV MSC-A09WV MSC-A12WV -
INDOOR UNIT
E1
E1
E1
MODELS WIRING DIAGRAM
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
Refrigerant flow in cooling
Refrigerant flow in heating
Muffler
Outdoor
heat
exchanger
Muffler
LEV (A)
Evaporation
temperature
thermistor
LEV (B)
Strainer
Strainer
Strainer
Defrost
thermistor
Capillary tube
{3.0✕{1.8✕600
Capillary tube
{1.8✕{0.6✕750
Capillary tube
{3.0✕{2.0✕400
Capillary tube
{3.0✕{2.0✕400
Stop valve
(with service port)
Gas pipe temperature
B thermistor
Gas pipe temperature
A thermistor
Stop valve
Stop valve
Indoor
Unit B
Indoor
Unit B
Indoor
Unit A
Indoor
Unit A
Stop valve
(with service port)
4-way valve
{8
{6
{6
{12
{12
a
Outdoor
unit
b
H
H
H
E1
Unit:mm
MAX REFRIGERANT PIPING LENGTH
-
MXY-A18WV
Piping length each indoor unit (a, b)20m
Total piping length (a+b)30m
Height difference between units (H)10m
Bending point for each unit15
Total bending point 30
❋It does not matter which unit is higher.
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
● When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see page BACK COVER.
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
E1E1E1E1E1
E1E1E1E1E1
E1E1E1E1E1
(1) GUARANTEED VOLTAGE
198~264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor outlet air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°CDB
(6) Outdoor intake air wet-bulb temperature :°CWB
(7) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 41,42 and 45 shows the difference
between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
Cooling
}
Heating
}
<MUH-A07/A09/A12WV>
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL
(HEAT
<MUH-A07/A09/A12WV>) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
10-1.CAPACITY AND THE INPUT CURVES
45
OUTDOOR UNIT
10
12
9
8
7
1520
50
25
60
30
70(%)
35(:)
0.7
0.8
0.9
1.0
1.2
11
1.1
230V
1520
50
25
603070(%)
35(:)
2.0
2.5
3.0
3.5
4.0
230V
MSC-A07WV - E1
(MUH-A07WV - E1 )
(MUH-A12WV - E1 )
MSC-A12WV - E1
(MUH-A09WV - E1 )
MSC-A09WV - E1
8.5
7.8
7.1
6.4
5.8
5.1
9.6
8.8
8.0
7.2
6.5
5.1
10.6
9.7
8.8
7.9
7.1
6.3
20.4
18.8
17.2
15.7
14.1
12.5
11.0
9.4
19.2
17.8
16.3
14.8
13.3
11.8
10.4
8.9
MSC-A07WV - E1
(MUH-A07WV - E1 )
(MUH-A09WV - E1 )
MSC-A09WV -
E1
(MUH-A12WV - E1 )
MSC-A12WV - E1
25.2
23.3
21.4
19.4
17.5
15.5
13.6
11.7
NOTE:The above curves are for the heating operation without any frost.
10-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
① Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
Relative humidity(%)
20
25
3070
➁ Air flow should be set at MAX.
③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/
10-4.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
① Both indoor and outdoor unit are under same temperature/humidity condition.
Dry-bulb temperatureRelative humidity (%)
20
25
30
➁ Air flow should be set at MAX.
③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge] )
50
60
70
MUX-A10WV-
(kgf/F[Gauge])(MPa[Gauge])
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
Outdoor low pressure (kgf/F[Gauge])
0.7
7
20
50
Ambient temperature(˚C)
Ambient humidity(%)
MUX-A19WV-
(kgf/F[Gauge])(MPa[Gauge])
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
Outdoor low pressure (kgf/F[Gauge])
0.6
6
20
50
Ambient temperature(˚C)
Ambient humidity(%)
E1
Single operation (Unit A or B)
230V
25603070 (˚C)
E1
Single operation (Unit A)Single operation (Unit B)
230V
2560 30
70
4.0
3.5
3.0
2.5
Outdoor unit current (A)
2.0
(%)
(˚C)
(%)
20
50
Ambient temperature(˚C)
Ambient humidity(%)
7.0
6.0
5.0
4.0
Outdoor unit current (A)
3.0
20
50
Ambient temperature(˚C)
Ambient humidity(%)
230V
2560 30
230V
2560 30
(˚C)
70
(%)
˚C)
(%)
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure (kgf/F[Gauge])
(˚C)
70
(%)
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
230V
2560 30
20
50
Ambient temperature(˚C)
Ambient humidity(%)
4.0
3.5
3.0
2.5
Outdoor unit current (A)
2.0
(˚C)
70
(%)
20
50
Ambient temperature(˚C)
Ambient humidity(%)
230V
2560 30
(˚C)
70
(%)
49
07 class
7.5
6.9
6.3
5.7
5.1
4.6
7.7
7.1
6.4
5.8
5.3
4.7
6.0
5.5
5.1
4.6
4.1
3.7
12 class
09 class
1.2
1.0
0.9
0.8
0.7
0.6
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure (kgf/F[Gauge])
10
9
8
7
6
12
1.1
11
Outdoor unit current (A)
Single operation (Unit A)
2.0
3.0
4.0
5.0
230V
230V
Ambient temperature(˚C)
Ambient humidity(%)
20
50
25603070 (˚C)
(%)
Ambient temperature(˚C)
Ambient humidity(%)
20
50
2560 30
70
(˚C)
(%)
0.9
0.8
0.7
0.6
0.5
0.4
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure (kgf/F[Gauge])
8
7
6
5
4
9
Outdoor unit current (A)
Single operation (Unit B or C)
3.0
4.0
5.0
6.0
230V
230V
Ambient temperature(˚C)
Ambient humidity(%)
20
50
25603070 (˚C)
(%)
Ambient temperature(˚C)
Ambient humidity(%)
20
50
25603070 (˚C)
(%)
MUX-A20WV-
E1
MUX-A25WV-
(kgf/F[Gauge])(MPa[Gauge])
1.2
12
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
Outdoor low pressure (kgf/F[Gauge])
0.6
6
20
50
Ambient temperature(˚C)
Ambient humidity(%)
MUX-A26WV-
(kgf/F[Gauge])(MPa[Gauge])
1.1
11
1.0
10
0.9
9
0.8
8
0.7
7
Outdoor low pressure (kgf/F[Gauge])
0.6
6
20
50
Ambient temperature(˚C)
Ambient humidity(%)
E1
Single operation (Unit A or B)
230V
7.0
6.0
5.0
Outdoor unit current (A)
2560 30
70
E1
Single operation (Unit A or B)
230V
(˚C)
(%)
4.0
6.0
5.0
4.0
Outdoor unit current (A)
2560 30
70
(˚C)
(%)
3.0
230V
20
50
Ambient temperature(˚C)
20
50
Ambient temperature(˚C)
2560 30
Ambient humidity(%)
230V
25603070 (˚C)
Ambient humidity(%)
(˚C)
70
(%)
(kgf/F[Gauge])(MPa[Gauge])
11
10
9
8
7
Outdoor low pressure (kgf/F[Gauge])
6
(%)
1.1
1.0
0.9
0.8
0.7
0.6
20
50
Ambient temperature(˚C)
Ambient humidity(%)
Single operation (Unit C or D)
230V
2560 30
(˚C)
70
(%)
5.0
4.0
3.0
230V
Outdoor unit current (A)
2.0
20
50
Ambient temperature(˚C)
2560 30
Ambient humidity(%)
(˚C)
70
(%)
MXZ-A18WV-
E1
10-5. CAPACITY AND THE INPUT CURVES
50
10-6. Capacity and input correction by inverter output frequency
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
HzHz
<HEAT>Capacity
Frequency
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
050100150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Hz
Frequency
<HEAT>Total input
Hz
1. 07-class unit in single operation
2. 09-class unit in single operation
3. 12-class unit in single operation
22.9
21.2
19.4
17.6
15.9
14.1
12.4
10.6
23.7
21.9
20.1
18.2
16.4
14.6
12.8
10.9
22.6
20.9
19.2
17.4
15.7
13.9
12.2
10.4
07 class
09 class
12 class
(OUTDOOR UNIT : MXZ-A18WV)
NOTE 1 : Compressor running frequency at 33Hz (COOL) or 45Hz (HEAT).
NOTE 2 : The dotted line on graphs connects the frequency range in normal operation shown by the full line and the
frequency in test run shown by the point.
51
10-7. Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation (OUTDOOR UNIT : MXZ-A18WV)
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
15
14
13
12
11
10
9
8
7
6
5
(MPa•Gauge)
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
15
2025
5060
Ambient temperature(:)/ Ambient humidity(%)
33Hz
(kgf/F• Gauge)
Outdoor low pressure
30
70
35
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is located
on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.T o cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
5.0
4.5
4.0
3.5
33Hz
3.0
2.5
Outdoor unit current (A)
2.0
1.5
(:)
(%)
1.0
15
202530
506070
Ambient temperature(:)/ Ambient humidity(%)
35
(:)
(%)
(2) HEAT operation
①
IndoorOutdoor
➁
Set air flow to Hi speed.
➂
Inverter output frequency is 80Hz.
DB(°C) 20.0
WB(°C) 14.5
DB(°C) 271520.0
WB(°C) 161214.5
8
7
6
5
4
Outdoor unit current (A)
3
2
0510152025
52
45Hz
Ambient temperature(:)
2. 09-class unit in single operation (OUTDOOR UNIT : MXZ-A18WV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is located
on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.T o cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
15
14
13
12
11
10
9
8
7
6
5
(MPa•Gauge)
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
15
Ambient temperature(:)/ Ambient humidity(%)
kgf/F• Gauge)
Outdoor low pressure
(2) HEAT operation
①
IndoorOutdoor
➁
Set air flow to Hi speed.
➂
Inverter output frequency is 80Hz.
DB(°C) 20.0
WB(°C) 14.5
2025
5060
5.0
4.5
4.0
3.5
33Hz
(:)
35
30
70
DB(°C) 271520.0
WB(°C) 161214.5
(%)
3.0
2.5
Outdoor unit current (A)
2.0
1.5
1.0
Ambient temperature(:)/ Ambient humidity(%)
15
202530
202530
33Hz
35
(:)
(%)
8
7
6
5
4
Outdoor unit current (A)
3
2
53
45Hz
0510152025
Ambient temperature(:)
3. 12-class unit in single operation (OUTDOOR UNIT : MXZ-A18WV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT. The switch is located
on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.T o cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP
(ON/OFF) button ON. Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for
3 minutes.
WIRELESS REMOTE CONTROLLER
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
• The following indication does not
depend on the shape of lamp.
Operation Indicator
lighted
not lighted
Difference
between target
Operation stateIndication
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait until the
target temperature is
obtained.
temperature
and room
temperature
Approx. 2 :
or more
11-1. COOL () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature
Room temperature minus set temperature : 0.3 : or more················································ON
Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless
of thermostat’s OFF-ON.
In Auto the fan speed is as follows.
Room temperature minus set temperature : 1.7 degrees or more·······························High
Room temperature minus set temperature : Between 1 and 1.7 degrees···················Med.
Room temperature minus set temperature : less than 1 degree··································Low
This shows that the
room temperature is
approaching the
target temperature.
Initial temperature difference Thermostat
Initial temperature difference
Fan speed
84
Approx. 2 :
or less
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 :
0.3 :
Difference between room
temperature and set temperature during operation
3 deg.
1.7 deg.
1 deg.
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and
initial room temperature in dry mode
:
3. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads 4°C or below(MSC-A07/A09WV) / 0°C or below(MSC-A12WV) for 5 minutes,
the coil frost prevention mode starts.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 4°C (MSC-A07/A09WV) / 0°C (MSC-A12WV), this mode is prolonged until the RT12
reads over 4°C (MSC-A07/A09WV) / 0°C (MSC-A12WV).
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes.
The indoor fan operates at the set speed.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts
from the beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed.
Operation chart
Example
ON
ON
Compressor
OFF
Outdoor fan
ON
Indoor fan
( continuously at set speed)
11-2. DRY () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION SELECT button.
(3) The microprocessor reads the room temperature and determines the set tem-
perature. Set temperature is as shown on the right chart.
DRY operation will not function when the room temperature is 13°C or below.
(4) When DRY operation functions the fan speed is lower than COOL operation
except at (fan speed) Low.
The system for dry operation uses the same refrigerant circuit as the cooling
circuit.
The compressor and the indoor fan are controlled by the room temperature.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature : 0.3 : or more················································ON
Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto fan speed becomes Low.
3. The operation of the compressor and indoor / outdoor fan <MU-A07/A09/A12WV, MUH-A07/A09/A12WV,
Compressor operates by room temperature control and time control.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
● When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
● When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
Initial temperature difference Thermostat
MUX-A10/A19/A20/A25/A26WV>
85
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 :
0.3 :
Operation time chart
Released
Cold Air Prevention
18: 22:
Fan speed
Set speed
Very Low or stop
Example
Thermostat
OFF
ON
ON
OFF
Indoor fan
Outdoor fan
Compressor
ON
ON
OFF
8 min.1 min.
OFFOFF
OFF
ON
ON
3 min.
ON
OFF
ON
OFF
4 min.
4. Coil frost prevention
The operation is as same as coil frost prevention during COOL operation.(Refer to 11-1.3.)
However when coil frost prevention works while the indoor fan is OFF, its speed becomes set speed.
11-3. FAN () OPERATION <MU-A07/A09/A12WV, MUX-A10/A19/A20/A25/A26WV>
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select FAN mode with the OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
11-4. HEAT () OPERATION <MUH-A07/A09/A12WV>
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Initial temperature difference Thermostat
Room temperature minus set temperature : less than -0.3 :··············································ON
Room temperature minus set temperature : 0.3 : or more·················································OFF
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 deg.
0.3 deg.
2. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto the fan speed is as follows.
Set temperature minus room temperature: 1.7 degrees or more·············································· High
Set temperature minus room temperature: Between 1 and 1.7 degrees·································· Med.
Set temperature minus room temperature: less than 1 degree················································· Low
(2) Cold air prevention control
1 When the compressor is not operating,
(1) if the temperature of indoor coil thermistor RT12 is 0°C or less, the fan stops.
(2) if the temperature of indoor coil thermistor RT12 is more than 0°C, the fan operates at Very Low.
2 When the compressor is operating,
(1) if the temperature of RT12 is 22°C or more, the fan operates at set speed.
(2) if the temperature of RT12 is less than 22°C and
(1) if the temperature of room temperature thermistor RT11 is 15°C or less, the fan stops.
(2) if the temperature of room temperature thermistor RT11 is more than 15°C, the fan operates at Very Low.
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner stating and also after defrosting,
this control works.
Initial temperature difference
86
Fan speed
Difference between room
temperature and set temperature during operation
3 deg.
1.7 deg.
1 deg.
(3) Warm air control.
<Time condition>
<Indoor fan speed>
less than 2 minutes Low
2 minutes to 4 minutes Med.
more than 4 minutes High
High pressure protection
Released
48: 52:
Outdoor fan
OFF
ON
When the following any condition of 1 (a. ~ c.) and the condition of 2 are satisfied at the same time, warm air control
works.
1 a.) When outdoor unit starts operating inHEAT mode.
b.) When cold air prevention has been released.
c.) When defrosting has been finished
2 When the temperature of indoor coil thermistor RT12 is less than 37°C.
When warm air control works, the fan speed changes as follows to blow out warm air gradually.
Gradation of fan speed in initial
The upper limit of the fan speed in MANUAL is the set speed.
The upper limit of the fan speed in AUTO is the speed decided by indoor fan speed control.(Refer to 11-4.2.(1).)
When the temperature of RT12 has been 37°C or more, or when the set speed has been changed, this control is
released and the fan speed is the set speed.
3. High pressure protection <MUH-A07/A09/A12WV>
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess
rise protection of compressor discharge pressure.
Outdoor fan OFF: 52:
Outdoor fan ON: 48:
Operation chart
Example
Indoor coil thermistor
RT12 temperature
52˚C
Outdoor fan motor
turn OFF
48˚C
Outdoor fan motor
ON
OFF
ON
OFF
Outdoor fan motor
turn ON
NOTE : During high pressure protection and for 4 min. and 15 sec. after high pressure protection, defrosting of outdoor heat
exchanger is not detected by the defrost thermistor RT61.(Refer to 11-4.4. Defrosting.)
87
4. Defrosting <MUH-A07/A09/A12WV>
Defrosting of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.
(1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) The compressor cumulative operation time exceeds 40 minutes without the defrosting operation working.
b) RT61 reads - 3°C or less.
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops.
d) RT61 reads 3.1°C or more.
e) The defrosting time exceeds 10 minutes.
Operation time chart
Example
Defrost thermistor RT61
3.1: or more
-3: or less
Outdoor 52C
contactor
(Compressor)
ON
OFF
X62
(R.V. coil)
ON
OFF
30 sec.
15 sec.
30 sec.
5 sec.
SR61
Outdoor fan
Defrost
counter
Indoor fan
ON
OFF
ON
OFF
ON
Very Low
❈
Max 10 min.
NOTE
OFF
Indoor
Horizontal
Horizontal vane
Set position
NOTE ● When the indoor coil thermistor RT12 reads above 0°C, indoor fan operates at Very Low for 30 seconds.
● When the indoor coil thermistor RT12 reads 0°C or less, the indoor fan stops.
88
5. R.V. coil control <MUH-A07/A09/A12WV>
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
MUH type
25: or more
23:or more,
less than 25:
less than 23:
MU&MUX type
25: or more
more than13:,
less than 25:
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
When operation starts, the 4-way valve reverses for 5 seconds right before start-up of the compressor.
Operation time chart
(COOL/DRY)
5 sec.
(HEAT)
5 sec.
Compressor
R.V. coil
Outdoor fan
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
11-5. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on
with a beep tone.
(2) Select “I FEEL CONTROL”() mode with the OPERA-
TION SELECT button.
(3) The operation mode is determined by the initial room tem-
perature at start-up of the operation, as shown on the
right table.
● Once the mode is fixed, the mode does not change by room temperature afterwards.
● Under the ON-TIMER () operation, mode is determined according to the room temperature at set time the opera-
tion starts.
● When the system is stopped on the remote controller and restarted within 2 hours in “I FEEL CONTROL” () mode,
the system operates in previous mode automatically regardless of the room temperature.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL mode of
“I FEEL CONTROL”
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at
start-up of the operation.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that determined by room temperature at start-up of
the operation.
89
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
Initial set temperature
26:
26: or more
25: or more,
less than 26:
23: or more,
less than25:
24:
Initial room temperature
minus 2:
Initial room temperature
minus 2:
❈1
more than 13:,
less than 25:
26: or more
25: or more,
less than 26:
less than 23:
MU & MUX type
MUH type
(4) The initial set temperature is decided by the initial room temperature.
TOO
COOL
TOO
WARM
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” () mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too
warm. Each time the TOO WARM or TOO COOLbutton is pressed, the indoor unit receives the signal and emits a beep
tone.
● Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…
To raise the set temperature 1~2 degrees(°C)
…
To lower the set temperature 1~2 degrees(°C)
11-5-1. COOL mode of “I FEEL CONTROL”
1. Thermostat control
Thermostat control is as same as COOL OPERATION.(11-1.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as COOL OPERATION.(11-1.2.)
3. Coil frost prevention
Coil frost prevention is as same as COOL OPERATION.(11-1.3.)
11-5-2. DRY mode of “I FEEL CONTROL”
1. Thermostat control
Thermostat control is as same as DRY OPERATION.(11-2.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as DRY OPERATION.(11-2.2.)
3. The operation of the compressor and indoor/outdoor fan
The operation of the compressor and indoor/outdoor fan is as same as DRY OPERATION.(11-2.3.)
4. Coil frost prevention
Coil frost prevention is as same as DRY OPERATION.(11-2.4.)
11-5-3. HEAT mode of “I FEEL CONTROL” <MUH-A07/A09/A12WV>
1. Thermostat control
Thermostat control is as same as HEAT OPERATION.(11-4.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as HEAT OPERATION.(11-4.2.)
3. High pressure protection
High pressure protection is as same as HEAT OPERATION.(11-4.3.)
4. Defrosting
Defrosting is as same as HEAT OPERATION.(11-4.4.)
5. R.V. coil control
R.V. coil control is as same as HEAT OPERATION.(11-4.5.)
90
11-6. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to
feedback the rotational frequency. Comparing the current rotational frequency with the target rotational
frequency (High,Med.,Low), the microprocessor controls SR141 and adjusts fan motor electric current to make the
current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched,
the rotational frequency changes smoothly.
HighHigh
Med.
Low
(2) Fan motor lock-up protection
When the rotational frequency feedback signal is not output for 12 seconds, (or when the microprocessor cannot detect
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR lamp flashes on and off to show the fan motor abnormality. (Refer to page 109.)
11-7. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL button.
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP(ON/OFF) button is pressed.
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO () mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room-temperature distribution.
1 In COOL and DRY operation
Vane angle is fixed to Angle 1.
2 In FAN operation <MU-A07/A09/A12WV>
2 In HEAT operation
(5) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the cumulative operation time of compressor exceeds 1
hour, the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE ()
By selecting SWING mode with the VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller
displays “”.
<MUH-A07/A09/A12WV>
Vane angle is fixed to Angle 4.
91
(7) Cold air prevention in HEAT operation
Set position
Angle 1
Released
Cold air prevention
24:
28:
When any of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1 automatically to prevent cold air blowing on users.
① Compressor is not operating.
➁ Defrosting is performed.
➂ Indoor coil thermistor RT12 reads 24: or below.
➃ Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor
RT12 temperature
NOTE : If the temperature of RT12 reads from 24°C to 28°C at the air conditioner stating , this control works.
When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher than that in
COOL mode.
Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12).
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that
in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when the ECONO COOL button is pressed once again or VANE CONTROL button is pressed or operation mode is changed.
NOTE : ECONO COOL operation does not work in COOL mode of “I FEEL CONTROL”.
SWING operation
In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.
According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is
decided. Then when the downward blow has been finished, next upward blow time is decided.
For initial 10 min. the swing operation is performed in table G~H for quick cooling.
Also, after 10 min. when the difference of set temperature and room temperature is more than 2 degrees, the swing
operation is performed in table D~H for more cooling.
The air conditioner repeats the swing operation in various cycle as follows.
<MUH-A07/A09/A12WV>
Horizontal vane
Temperature of indoor
coil thermistor RT12
A
B
C
D
E
F
G
H
15°C or less
15°C to 17°C
17°C to 18°C
18°C to 20°C
20°C to 21°C
21°C to 22°C
22°C to 24°C
more than 24°C
Downward blow time
(sec.)
2
5
8
11
14
17
20
23
Horizontal blow time
(sec.)
23
20
17
14
11
8
5
2
11-8. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON or OFF TIMER buttons to select the operation.
“” button... AUTO START operation (ON timer)
“” button... AUTO STOP operation (OFF timer)
92
PM
AM
PM
PM
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” mark is flashing.
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
● A power failure occurs.
● The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the ON or OFF TIMER buttons. (“” or “”)
To cancel the ON timer, press the “” button.
To cancel the OFF timer, press the “” button.
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
● The OFF timer and ON timer can be used in combination.
● “” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
11-9. EMERGENCY-TEST OPERATION
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the
indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote
controller run down. The unit will start and the OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation the system shifts to EMERGENCY COOL [/HEAT <MUH-A07/A09/A12WV,
MXZ-A18WV>] MODE with a set temperature of 24°C. The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation [, and defrosting <MUH-A07/A09/A12WV, MXZ-A18WV>
too].
In the test run or emergency operation, the horizontal vane operates in VANE AUTO () mode.
Emergency operation continues until the EMERGENCY OPERATION switch is pressed once again (MU-A07/A09/A12WV,
MUX-A10/A19/A20/A25/A26WV)/once or twice (MUH-A07/A09/A12WV, MXZ-A18WV) or the unit receives any signal
from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
EMERGENCY OPERATION switch
93
• The following indication does not depend on the
shape of lamp.
OPERATION INDICATOR lamp
Press once <Cool>
Press again <Heat>
Press once again <Stop>
w Heat is available only in MUH-A07/A09/A12WV and
MXZ-A18WV.
11-10. OUTDOOR UNIT ACTUATOR CONTROL
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (CLOSE)
OFF (OPEN)
ON (CLOSE)
OFF (OPEN)
SOLENOID
VALVE
MUX-A26WV -
E1
INDOOR UNIT
MC1
MC2
MF61
21R1
21R2
21R3
21R4
21RA
(BALANCE)
21RB
(BALANCE)
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
ON
OFF
OFF
–
–
–
–
OFF
ON
OFF
–
–
–
–
–
–
ON
ON
OFF
OFF
–
–
–
–
B
ON
OFF
ON
OFF
–
–
–
–
ANY UNIT ON
OFF
–
–
ON
OFF
–
–
–
–
ON
OFF
ON
OFF
–
–
–
–
C
–
–
–
–
ON
ON
OFF
OFF
OFF
–
–
–
–
ON
OFF
–
–
–
–
–
–
ON
ON
OFF
OFF
D
–
–
–
–
ON
OFF
ON
OFF
OFF
–
–
–
–
–
–
ON
OFF
–
–
–
–
ON
OFF
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (CLOSE)
OFF (OPEN)
SOLENOID
VALVE
MUX-A20WV -
E1
INDOOR UNIT
MC1
MC2
MF61
21R3
21R4
21RB
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
OFF
–
–
–
–
OFF
–
–
–
–
–
–
–
–
B
–
–
ON
ON
OFF
OFF
ANY UNIT ON
OFF
ON
OFF
–
–
ON
ON
OFF
OFF
C
–
–
ON
OFF
ON
OFF
OFF
–
–
ON
OFF
ON
OFF
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON (CLOSE)
OFF (OPEN)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
SOLENOID
VALVE
MUX-A10WV - E1
INDOOR UNIT
MC
MF61
21R
(BALANCE)
21R1
21R2
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
ON
OFF
OFF
ANY UNIT ON
OFF
ON
ON
OFF
OFF
ON
OFF
–
–
B
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
–
–
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
MUX-A19WV -
E1 MUX-A25WV - E1
INDOOR UNIT
MC1
MC2
MF61
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
OFF
–
–
ANY UNIT ON
OFF
B
–
–
ON
OFF
OFF
“–” means that the indoor unit is not related to the control of actuator.
94
11-11 INVERTER MULTI SYSTEM CONTROL
MXZ-18WV -
Indoor unit
microprocessor
E1
Outdoor unit control microprocessor
SSR61
Compressor
power
factor
Drive
circuit
Transistor
module
Fin temperature
thermistor RT65
Comp.
Discharge
temperature
thermistor
RT61
Compressor
primary
current
Output signal
Input signal
Compressor
secondary
current
x 61
x 62
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Gas pipe
temperature
thermistor RT6B
R. V. coil
21S4
B
Highpressure protect
Gas pipe
A
temperature
thermistor RT6A
Evaporation
temperature
thermistor
RT63
thermistor RT68
Outdoor
fan motor
MF61
LEV (A)
A
LEV (B)
Defrost
thermistor
RT62
B
95
11-11-2. Outline of main power supply circuit
1. At the start of operation
Rush current is generated the instant the electricity is turned on to the main power
supply circuit to operate the compressor.
To prevent the rush current from running into the main power supply circuit, R64A, R64B (Current-limiting resistor) absorbs
the rush current.
After the rush current is absorbed, X64 (Relay) is ON and the circuit to R is
short-circuited, then the electricity to R is bypassed.
When X64 is ON, the system starts the operation of compressor.
2. At normal operation
The noise of alternating current of power supply is eliminated by L61, L62 (Common mode choke coil).
Then DS61, DS62 (Diode stack) performs full-wave rectification of alternating current and the
alternating current is converted to direct current.
C61, C62 and C63 (Smoothing capacitor) stabilizes the power supply converted to direct current from alternating current
and supplies it to IPM (Intelligent power module).
Direct current rectified by DS61, DS62 is converted to three-phase alternating current by IPM.
Microcomputer installed in the electronic control P.C. board controls frequency and voltage of three-phase alternating
current converted by IPM.
Three-phase alternating current is supplied from IPM to the compressor with frequency and voltage decided by
microcomputer based on various kinds of information.
CT61, CT761 (Current transformer) measures the current of main power supply circuit.
3. Power-factor improvement of power supply and harmonics control
Although C61, C62, and C63 [smoothing capacitor] are used in this inverter circuit in order to supply direct-current stably,
since the charge current to a capacitor turns into intermittent current in the stable circuit with only a capacitor, power factor
of power supply gets worse and harmonics ingredient also becomes large.
Then, AFM [active filter module] and L [reactor] have been arranged on direct-current circuit, and the improvement of
power factor and generating of harmonics are controlled by bringing the intermittent current waveform of alternating
power supply close to sine wave synchronized with the power supply voltage waveform. (Note 1)
Note 1: When short-circuited between plus and minus pole of direct-current circuit,
alternating power supply current flows. By controlling time of short-circuiting to flow proper amount of current in the
intermittent portion of alternating power supply current constantly, the current waveform of alternating power supply is
brought close to sine wave.
4. Removal of electric noise
Because of the noise filter circuit formed by L61 and L62 [CMC coil] and the capacitor on the noise filter board, the electric
noise of the alternating power supply supplied to the main power supply circuit is removed.
Moreover, common mode noise is absorbed with the above-mentioned noise filter, and the normal mode noise is
absorbed in the noise filter circuit formed by L63 [NMC coil] and the capacitors [C650A, C650B, and C650C] on the
control board so that the electric noise generated in the inverter circuit may not leak out.
POWER
SUPPLY
X64
R64A/R64B
DS61/DS62AFM
L
L61/L62
L
N
U
U
V
V
W
W
P
N
NOISE FILTER
P.C.BOARD
ELECTRONIC CONTROL P.C. BOARD
CT61L63
CT761
+
+
-
MC
IPM
11-11-1. INVERTER MAIN POWER SUPPLY CIRCUIT
96
5. IPM
Target power factor minus detected power factor
(Calculated value is supposed to be "A".)
Calculation of voltage
correction value (%)
A[-2%
-2%<A<+2%
A]+2%
Previous voltage correction value minus 1
Same as previous voltage correction value
Previous voltage correction value plus 1
1slip0
Power factor
efficiency
Six power transistors that outputs the direct current waveform as three-phase alternating current waveform, the driving
circuit which operates the power transistors, and the overcurrent detecting circuit which protects the power transistors are
built into the IPM. It can simplify and miniaturize the control circuit.
6.AFM [Active Filter Module]
The circuit that detects power supply voltage waveform, the circuit that detects the current flowing in module, the switching
element that short-circuits between plus and minus pole of direct-current circuit, and the switching element driving current
are built into AFM.
The current waveform is automatically adjusted by controlling the interval of short-circuit between plus and minus pole of
direct-current circuit so that the waveform of actual current flowing to service power supply is synchronized with the phase
of power supply voltage waveform detected by AFM.
11-11-3. Function of main parts
SYMBOL
C61,C62, C63
CT61, CT761
DS61, DS62
IPM
L
L61, L62
L63
R
X64
NAME
SMOOTHING CAPACITOR
CURRENT TRANSFORMER
DIODE STACK
INTELLIGENT POWER MODULE
REACTOR
COMMON MODE CHOKE COIL
NORMAL MODE CH6KE COIL
CURRENT-LIMITING RESISTOR
RELAY
FUNCTION
It stabilizes the direct current voltage.
It measures the current of main power supply circuit.
It converts the alternating current voltage to direct current voltage.
It generates three-phase alternating current and operates compressor.
It is combined with DS62 to improve the power factor of power supply.
It eliminates and absorbs the electrical noise.
It absorbs the rush current not to run into the main power supply
when the electricity is turned on.
It short-circuits the circuit to current-limiting resistor when the
compressor operates.
circuit
11-12. Optimal voltage control
The purpose of optimal voltage control is to operate the compressor at optimal
voltage that meets the load detected by the power factor of the compressor.
1. Optimal
As shown on the right the efficiency (ratio of output against input) of the
motor in the compressor becomes optimal when the sliding (ratio of difference between the actual number of rotation and the number of synchronous
rotation of motor) is one fixed value. The value of sliding can be calculated
from the power factor since the sliding and the power factor are mutually
related as shown in the table on the right. To make the value of sliding so
that the efficiency of motor is optimal, the power factor of the compressor is
detected. Then the detected power factor is controlled so that its efficiency
can be high. As a result, it is possible to operate the compressor at optimal
voltage.
2. How to determine the optimal voltage
Compare the detected power factor with the target power factor so that the efficiency of motor is optimal, the voltage
correction value is changed and the optimal output voltage is determined.
Optimal output voltage[V]= Standard voltage at certain frequency [V]x voltage correction value(%)
97
11-13 LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
Indoor unit status
Stop of all indoor unit
When outdoor unit is operating,
some indoor units stop and
some operate.
Thermostat OFF in
COOL or DRY mode
When the outdoor unit operates (When the other indoor unit operates): 5 pulse.
When outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop ➝ 500 pulse in 15 minutes
Opening before stop ➝ 500 pulse in 15 minutes
• LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
on the operation frequency:
Ex.) Opening 130 pulse in standard opening 1 ➝ Minimum 80 pulse, Maximum 205
Thermostat ON in
COOL or DRY mode
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 units operation)
• After starting operation, adjustment in accordance with intake super heat, discharge
temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are
different. See 11-2 Operational frequency range
(As far as the indoor unit velocity control goes, refer to DRY operation in
MICROPROCESSOR CONTROL in the indoor unit service manual.)
• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
Thermostat OFF in HEAT mode
• When the outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop ➝ 500 pulse in 15 minutes.
• LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
Thermostat ON in HEAT mode
on the operation frequency:
Ex.) Opening 120 pulse in standard opening 1 ➝ Minimum 70 pulse, Maximum 165
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 units operation)
• After starting operation, opening becomes the one that adjustment in accordance
with discharge temperature was added to basic opening. w1
w1 LEV opening when the outdoor unit is operating: Upper limit 500 pulse, Lower limit 59 pulse.
Determination of LEV standard opening in each indoor unit
• The standard opening is on the straight line, which connects an each standard point in the section where divided
into seven according to the operation frequency of compressor as shown in the figure below.
(LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
• Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8,
when capacity of the indoor unit is excluding code 1.
• Add opening provided in Difference in Operation number in the table below to determined LEV opening for
each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse.
< Calculation example of LEV opening >
Cool operation: Compressor frequency 70Hz: 2 units ON: 18 class
(170-150)p(80-60)o(70-60)+150+75-30=205 pulse
Standard opening
12345678
220
210
200
190
180
170
160
150
140
LEV opening (Pulse)
130
120
720406080100120140
Operation frequency of compressor (Hz) : F
COOL
HEAT
98
(1) LEV opening correction by suction super heat (COOL, DRY)
Suction superheat (S.H.)
LEV opening
correction (pulse)
more than 12
10 to12
8 to 10
6 to 8
6 or less
7
5
4
3
0
Superheat
LEV opening
correction (pulse)
more than 9
6 to9
3to 6
6 or less
10
8
4
0
1 Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
w 1 Perform this, when number of operation units is 2 units or more.
w 2 When the correction opening of suction super heat is 0, correct the LEV opening by discharge temperature.
3 Discharge temperature
COOLDRYHEAT
••
-
•
w 2
•
w 2
•
<Correction>
2
Code3Code2
Standard opening (pulse)
Difference in
capacity
Difference in
operation number
12345678
COOL
HEAT
200
160
210
170
220
180
230
190
Capacity code
Indoor unit
1
07209312418
240
200
240
210
250
210
250
2202520
50
40
-60
-70
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY, correct the LEV openings corrected from the table below.
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units)
(a) Correction by the separate super heat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator
temperature thermistor.
1 Calculate each super heat of the unit from the expression below;
(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)
2 Separate correction is performed according to each super heat in the table below.
99
(3) LEV opening correction by discharge temperature
Operation frequency
of compressor
Minimum ~ 20
21 ~ 33
34 ~ 46
47 ~ 59
60 ~ 72
73 ~ 85
86 ~ 98
97 ~ 111
111 ~ Maximum
Single
40
40
45
52
62
67
72
75
80
Double
40
40
45
52
62
67
72
75
80
Single
45
50
55
60
65
70
70
75
76
Double
45
50
55
60
65
70
70
75
76
Number of operating unitNumber of operating unit
COOL, DRYHEAT
LEV opening correction (pulse)
Discharge temperature (;)
LEV opening
correction (pulse)
More than Target discharge temperature+11
Target discharge temperature+11 to Target discharge temperature+8
Target discharge temperature+8 to Target discharge temperature+5
Target discharge temperature+5 to Target discharge temperature+2
Target discharge temperature+2 to Target discharge temperature-2
Target discharge temperature-2 to Target discharge temperature-5
Target discharge temperature-5 to Target discharge temperature-8
Target discharge temperature-8 to Target discharge temperature-11
Target discharge temperature-11 or less
COOL
10
4
2
1
0
-1
-2
-5
-8
HEAT
8
2
1
1
0
-1
-1
-2
-6
DRY
(Hz)
Min. Max. RatedMin. Max.
Defrost
Rated
Note: When the fan speed of indoor unit is
totally Low notch, the maximum frequency
is rated frequency.
COOL (Hz)
HEAT (Hz)
Number of
operating
unit
1
2
3
2
3
4
5
6
7
25
40
76
90
100
120
55
61
85
110
27
41
53
722543
100
100
122
122
120
120
120
120
72
76
88
120
1
2
capacity
code
When LEV correction output is 0 pulse by the suction super heat at COOL or DRY operation, or HEAT operating, correct
LEV is corrected according to the following table.
The target discharge temperature is determined according to frequency zone and number of operation unit of the
compressor.
Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.
11-14.Operational frequency range
11-15.Heat defrosting control
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is -3; or less.
2.When specified non-defrosting time, is counted in the control p.c.board is satisfied.
(Total time of compressor operating)
Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights.
2.4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 13.2; or more.
2. When it has spent 10 minutes for defrosting.
Defrosting finishes at condition of 1 or 2.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.