5-1. COOL OPERATION·············································································55
5-2. DRY OPERATION ···············································································56
5-3. HEAT OPERATION·············································································56
5-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION······················58
5-5. INDOOR FAN MOTOR CONTROL·····················································59
5-6. OUTDOOR FAN MOTOR CONTROL·················································59
5-7. AUTO VANE OPERATION··································································59
5-8. i-see CONTROL OPERATION····························································61
5-9. AREA SETTING ··················································································62
5-10. PLASMA DUO OPERATION ······························································64
. AUTO FRONT PANEL ········································································65
6-1. COOL OPERATION·············································································73
6-2. DRY OPERATION ···············································································74
6-3. HEAT OPERATION·············································································74
6-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION······················76
6-5. INDOOR FAN MOTOR CONTROL·····················································77
6-6. OUTDOOR FAN MOTOR CONTROL·················································77
6-7. AUTO VANE OPERATION··································································77
6-8. TIMER OPERATION············································································79
6-9. EMERGENCY / TEST OPERATION···················································80
6-10.
INVERTER SYSTEM CONTROL·······················································81
11.
OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT ·····83
66-
12.
EXPANSION VALVE CONTROL (LEV CONTROL) ···························84
As for outdoor units SUZ-KA25/35/50VA.TH and SUZKA25/35VAH.TH, refer to service manual OC322.
(
MFZ-KA50VA
9-1. COOL OPERATION···········································································117
9-2. DRY OPERATION··············································································117
9-3. HEAT OPERATION············································································117
9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION ····················119
9-5. INDOOR FAN MOTOR CONTROL···················································120
9-6. OUTDOOR FAN MOTOR CONTROL···············································120
9-7. AUTO VANE OPERATION································································120
9-8. i-save OPERATION···········································································124
9-9. TIMER OPERATION··········································································125
9-
10.
EMERGENCY / TEST OPERATION·················································126
11-1. COOL OPERATION·········································································138
11-2. DRY OPERATION············································································139
11-3. HEAT OPERATION··········································································139
11-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION··················141
11-5. INDOOR FAN MOTOR CONTROL ·················································141
11-6. OUTDOOR FAN MOTOR CONTROL ·············································142
11-7. AUT O VANE OPERATION······························································142
11-8. TIMER OPERATION········································································144
11-9. EMERGENCY / TEST OPERATION················································145
11-10.
INVERTER SYSTEM CONTROL ···················································145
11-
11.
OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT
11-
12.
EXPANSION VALVE CONTROL (LEV CONTROL)·······················148
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for
3 minutes.
WIRELESS REMOTE CONTROLLER
1-1. COOL () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature
Room temperature minus set temperature : 0.3 : or more················································ON
Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless
of thermostat’s OFF-ON.
In Auto the fan speed is as follows.
Room temperature minus set temperature : 1.7 : or more·······························High
Room temperature minus set temperature : Between 1 and 1.7 :···················Med.
Room temperature minus set temperature : less than 1 :·································Low
Initial temperature difference Thermostat
Initial temperature difference
Fan speed
6
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 :
0.3 :
Difference between room
temperature and set temperature during operation
3 :
1.7 :
1 :
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and
initial room temperature in dry mode
:
3. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads 4°C or below(MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C or
below(MSC-CA35/CB35/GA35VB) for 5 minutes, the coil frost prevention mode starts.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 4°C (MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C (MSC-CA35/CB35/GA35VB),
this mode is prolonged until RT12 reads over 4°C (MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C (MSCCA35/CB35/GA35VB).
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes.
The indoor fan operates at the set speed.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts
from the beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed.
Operation chart
Example
ON
ON
Compressor
OFF
Outdoor fan
ON
Indoor fan
( continuously at set speed)
1-2. DRY () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION SELECT button.
(3) The microprocessor reads the room temperature and determines the set tem-
perature. Set temperature is as shown on the right chart.
DRY operation will not function when the room temperature is 13°C or below.
(4) When DRY operation functions the fan speed is lower than COOL operation
except at (fan speed) Low.
The system for dry operation uses the same refrigerant circuit as the cooling
circuit.
The compressor and the indoor fan are controlled by the room temperature.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature : 0.3 : or more················································ON
Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto fan speed becomes Low.
3. The operation of the compressor and indoor / outdoor fan
<MU-GA20/GA25/GA35VB, MUH-GA20/GA25/GA35VB, MUX-2A28/2A59/3A60/3A63/2A70/4A73VB>
Compressor operates by room temperature control and time control.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
Initial temperature difference Thermostat
7
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 :
0.3 :
Operation time chart
Released
Cold Air Prevention
18: 22:
Fan speed
Set speed
Very Low or stop
Example
Thermostat
OFF
ON
ON
OFF
Indoor fan
Outdoor fan
Compressor
ON
ON
OFF
8 minutes
OFFOFF
OFF
ON
ON
3 minutes
OFF
OFF
4 minutes
ON
ON
1 minute
4. Coil frost prevention
The operation is as same as coil frost prevention during COOL operation.(Refer to 1-1.3.)
However when coil frost prevention works while the indoor fan is OFF, its speed becomes set speed.
1-3. FAN () OPERATION <MU-GA20/GA25/GA35VB, MUX-2A28/2A59/3A60/3A63/2A70/4A73VB>
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
1-4. HEAT () OPERATION <MUH-GA20/GA25/GA35VB>
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Initial temperature difference Thermostat
Room temperature minus set temperature : less than -0.3 :··············································ON
Room temperature minus set temperature : 0.3 : or more·················································OFF
Difference between room
temperature and set temperature during operation
Set temperature
-0.3 :
0.3 :
2. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto the fan speed is as follows.
Set temperature minus room temperature: 1.7 :or more······················································· High
Set temperature minus room temperature: Between 1 and 1.7 :··········································· Med.
Set temperature minus room temperature: less than 1
(2) Cold air prevention control
1 When the compressor is not operating,
(1) if the temperature of indoor coil thermistor RT12 is 0°C or less, the fan stops.
(2) if the temperature of indoor coil thermistor RT12 is more than 0°C, the fan operates at Very Low.
2 When the compressor is operating,
(1) if the temperature of RT12 is 22°C or more, the fan operates at set speed.
(2) if the temperature of RT12 is less than 22°C and
(1) if the temperature of room temperature thermistor RT11 is 15°C or less, the fan stops.
(2) if the temperature of room temperature thermistor RT11 is more than 15°C, the fan operates at Very Low.
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner stating and also after defrosting,
Difference between room
temperature and set temperature during operation
3 :
1.7 :
1:
(3) Warm air control
<Time condition>
<Indoor fan speed>
less than 2 minutes Low
2 minutes to 4 minutes Med.
more than 4 minutes High
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
MUH type
25: or more
23:or more,
less than 25:
less than 23:
MU & MUX type
25: or more
more than13:,
less than 25:
When the following any conditions of 1 (a. ~ c.) and the condition of 2 are satisfied at the same time, warm air control
works.
1 a.) When outdoor unit starts operating in HEAT mode.
b.) When cold air prevention has been released.
c.) When defrosting has been finished
2 When the temperature of indoor coil thermistor RT12 is less than 37°C.
When warm air control works, the fan speed changes as follows to blow out warm air gradually.
Gradation of fan speed in initial
The upper limit of the fan speed in MANUAL is the set speed.
The upper limit of the fan speed in AUTO is the speed decided by indoor fan speed control.(Refer to 1-4.2.(1).)
When the temperature of RT12 has been 37°C or more, or when the set speed has been changed, this control is
released and the fan speed is the set speed.
NOTE: As for high pressure protection, defrosting and R.V. coil control, refer to service manual for outdoor unit.
1-5. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on
with a beep tone.
(2) Select “I FEEL CONTROL”() mode with the OPERA-
TION SELECT button.
(3) The operation mode is determined by the initial room tem-
perature at start-up of the operation, as shown on the
right table.
• Once the mode is fixed, the mode does not change by room temperature afterwards.
• Under the ON-TIMER () operation, mode is determined as follows.
When the system is stopped on the remote controller and restarted within 2 hours in “I FEEL CONTROL” () mode,
the system operates in previous mode automatically regardless of the room temperature.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at
start-up of the operation.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL mode of
“I FEEL CONTROL”
Restart
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that determined by room temperature at start-up of
the operation.
9
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
Initial set temperature
26:
26: or more
25: or more,
less than 26:
23: or more,
less than25:
24:
Initial room temperature
minus 2:
Initial room temperature
minus 2:
❈1
more than 13:,
less than 25:
26: or more
25: or more,
less than 26:
less than 23:
MU & MUX type
MUH type
(4) The initial set temperature is decided by the initial room temperature.
TOO
COOL
TOO
WARM
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” () mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too
warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep
tone.
•Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…
To raise the set temperature 1~2 degrees(°C)
…
To lower the set temperature 1~2 degrees(°C)
1-5-1. COOL mode of “I FEEL CONTROL”
1. Thermostat control
Thermostat control is as same as COOL OPERATION.(1-1.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as COOL OPERATION.(1-1.2.)
3. Coil frost prevention
Coil frost prevention is as same as COOL OPERATION.(1-1.3.)
1-5-2. DRY mode of “I FEEL CONTROL”
1. Thermostat control
Thermostat control is as same as DRY OPERATION.(1-2.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as DRY OPERATION.(1-2.2.)
3. The operation of the compressor and indoor/outdoor fan
The operation of the compressor and indoor/outdoor fan is as same as DRY OPERATION.(1-2.3.)
4. Coil frost prevention
Coil frost prevention is as same as DRY OPERATION.(1-2.4.)
1-5-3. HEAT mode of “I FEEL CONTROL” <MUH-GA20/GA25/GA35VB>
1. Thermostat control
Thermostat control is as same as HEAT OPERATION.(1-4.1.)
2. Indoor fan speed control
Indoor fan speed control is as same as HEAT OPERATION.(1-4.2.)
NOTE: As for high pressure protection, defrosting and R.V. coil control, refer to service manual for outdoor unit.
10
1-6. INDOOR FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to
feedback the rotational frequency. Comparing the current rotational frequency with the target rotational
frequency (High,Med.,Low), the microprocessor controls SR141 and adjusts fan motor electric current to make the
current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched,
the rotational frequency changes smoothly.
HighHigh
Med.
Low
(2) Fan motor lock-up protection
When the rotational frequency feedback signal is not output for 12 seconds, (or when the microprocessor cannot detect
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR lamp flashes on and off to show the fan motor abnormality.
1-7. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing the VANE CONTROL button.
(3) Positioning
The vane presses the vane stopper once to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP(ON/OFF) button is pressed.
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO () mode
The microprocessor automatically determines the vane angle to make the optimum room temperature distribution.
COOL and DRY operation
Vane angle is fixed to Angle 1.
(5) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the cumulative operation time of compressor exceeds 1
hour, the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE ()
By selecting SWING mode with the VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller
displays “”.
When any of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1 automatically to prevent cold air blowing on users.
① Compressor is not operating.
➁ Defrosting is performed.
➂ Indoor coil thermistor RT12 reads 24: or below.
➃ Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor
RT12 temperature
NOTE : If the temperature of RT12 reads from 24°C to 28°C at the air conditioner stating , this control works.
When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher.
Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12).
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air
conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when the ECONO COOL button is pressed once again or VANE CONTROL button is pressed or operation mode is changed.
NOTE : ECONO COOL operation does not work in COOL mode of “I FEEL CONTROL”.
<SWING operation>
In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.
According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is
decided. Then when the downward blow has been finished, next upward blow time is decided.
For initial 10 min. the swing operation is performed in table G~H for quick cooling.
Also, after 10 min. when the difference of set temperature and room temperature is more than 2 degrees, the swing
operation is performed in table D~H for more cooling.
The air conditioner repeats the swing operation in various cycle as follows.
<MUH-GA20/GA25/GA35VB>
Horizontal vane
Temperature of indoor
coil thermistor RT12
A
B
C
D
E
F
G
H
15°C or less
15°C to 17°C
17°C to 18°C
18°C to 20°C
20°C to 21°C
21°C to 22°C
22°C to 24°C
more than 24°C
Downward blow time
(sec.)
2
5
8
11
14
17
20
23
Horizontal blow time
(sec.)
23
20
17
14
11
8
5
2
1-8. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON or OFF TIMER buttons to select the operation.
“” button... AUTO START operation (ON timer)
“” button... AUTO STOP operation (OFF timer)
12
Lighted
Not lighted
PM
AM
PM
PM
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” mark is flashing.
These marks disappear in 1 minute.
After setting ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• Apower failure occurs.
• The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with ON or OFF TIMER buttons. (“” or “”)
To cancel ON timer, press “” button.
To cancel OFF timer, press “” button.
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
• OFF timer and ON timer can be used in combination.
• “” and “ ” display shows the order of OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
1-9. EMERGENCY / TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the
indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL [/ HEAT<MUH-GA20/GA25/GA35VB>]
MODE with a set temperature of 24°C. The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation [, and defrosting<MUH-GA20/GA25/GA35VB> too].
In the test run or emergency operation, the horizontal vane operates in VANE AUTO () mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once again
(MU-GA20/GA25/GA35VB, MUX-2A28/2A59/3A60/3A63/2A70/4A73VB)/once or twice (MUH-GA20/GA25/GA35VB) or the
unit receives any signal from the remote controller.
In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
• The following indication does not depend on the
shape of lamp.
Press once <Cool>
OPERATION INDICATOR lamp
EMERGENCY OPERATION switch
Press again <Heat>
Press once again <Stop>
w Heat is available only in MUH-GA20/GA25/GA35VB.
13
1-10. OUTDOOR UNIT ACTUATOR CONTROL
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (CLOSE)
OFF (OPEN)
ON (CLOSE)
OFF (OPEN)
SOLENOID
VALVE
MUX-4A73VB
INDOOR UNIT
MC1
MC2
MF61
21R1
21R2
21R3
21R4
21RA
(BALANCE)
21RB
(BALANCE)
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
ON
OFF
OFF
–
–
–
–
OFF
ON
OFF
–
–
–
–
–
–
ON
ON
OFF
OFF
–
–
–
–
B
ON
OFF
ON
OFF
–
–
–
–
ANY UNIT ON
OFF
–
–
ON
OFF
–
–
–
–
ON
OFF
ON
OFF
–
–
–
–
C
–
–
–
–
ON
ON
OFF
OFF
OFF
–
–
–
–
ON
OFF
–
–
–
–
–
–
ON
ON
OFF
OFF
D
–
–
–
–
ON
OFF
ON
OFF
OFF
–
–
–
–
–
–
ON
OFF
–
–
–
–
ON
OFF
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
ON (CLOSE)
OFF (OPEN)
SOLENOID
VALVE
INDOOR UNIT
MC1
MC2
MF61
21R3
21R4
21RB
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
OFF
–
–
–
–
OFF
–
–
–
–
–
–
–
–
B
–
–
ON
ON
OFF
OFF
ANY UNIT ON
OFF
ON
OFF
–
–
ON
ON
OFF
OFF
C
–
–
ON
OFF
ON
OFF
OFF
–
–
ON
OFF
ON
OFF
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON (CLOSE)
OFF (OPEN)
ON (OPEN)
OFF (CLOSE)
ON (OPEN)
OFF (CLOSE)
SOLENOID
VALVE
MUX-2A28VB
INDOOR UNIT
MC
MF
21R
(BALANCE)
21R1
21R2
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
ON
OFF
OFF
ANY UNIT ON
OFF
ON
ON
OFF
OFF
ON
OFF
–
–
B
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
–
–
ON
OFF
ACTUATOR
ON
OFF
ON
OFF
ON
OFF
MUX-2A59VB
MUX-2A70VB
INDOOR UNIT
MC1
MC2
MF61
COMPRESSOR
OUTDOOR
FAN MOTOR
A
ON
OFF
–
–
ANY UNIT ON
OFF
B
–
–
ON
OFF
OFF
MUX-3A60VB MUX-3A63VB
“–” means that the indoor unit is not related to the control of actuator.
14
2
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
WIDE VANE
LONG
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET CLOCK
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE button
(Horizontal vane button)
CLOCK SET button
LONG button
WIDE VANE button
(Vertical vane button)
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
FAN
Signal transmitting section
Operation display section
OPERATE/ STOP
(ON/ OFF) button
TEMPERATURE buttons
Lighted
Not lighted
Approx.
2 : or more
Difference
between target
temperature
and room
temperature
Approx.
2 : or less
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait until the
target temperature is
obtained.
This shows that the
room temperature is
approaching the
target temperature.
Operation state
Indication
Operation Indicator
Operation Indicator lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
INDOOR UNIT DISPLAY SECTION
• The following indication applies regardless of
shape of the indicator.
Once the operation mode is set, the same operation mode can
be repeated by simply turning OPERATE/STOP (ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
2-1. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote
controller. OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select “I FEEL CONTROL” mode with OPERATION
SELECT button.
(3) The operation mode is determined by the room tempera-
ture at start-up of the operation.
Initial room temperature
25: or more
more than 13:,
less than 25:
15
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
• Once the mode is fixed, the mode does not change by room temperature afterwards.
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
Initial room temperatureInitial set temperature
26: or more
25: to 26:
more than 13:, less than 25:
24:
Initial room temperature
minus 2:
Initial room temperature
minus 2:
❈1
TOO
COOL
TOO
WARM
• Under the ON-TIMER () operation, mode is determined as follows.
When the system is stopped on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” () mode,
the system operates in previous mode automatically regardless of the room temperature.
Operation timer chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
Restart
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at
start-up of the operation.
Operation timer chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL or DRY mode
of “I FEEL CONTROL”
that determined by
room temperature at
start-up of the operation.
(4) The initial set temperature is decided by the initial room temperature.
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL” () mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
•Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…
To raise the set temperature 1~2°C
…
To lower the set temperature 1~2°C
16
2-1-1. COOL mode of “I FEEL CONTROL”
Difference between room
temperature and set temperature
during operation
1°C 1.7°C
3°C
Outdoor fan speed
20: 22:
High
Ambient temperature
thermistor RT63 temperature
Low
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In AUTO the fan speed is as follows.
Initial temperature difference Fan Speed
Room temperature minus set temperature : 1.7 °Cor more
Room temperature minus set temperature : Between 1 and 1.7
Room temperature minus set temperature : less than 1
2. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads 3°C or below(MS-GA50VB) /1°C or below(MS-GA60VB)/ RT12 or RT13
reads -1°C or below (MS-GA80VB), the coil frost prevention mode starts immediately.
However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 3°C(MS-GA50VB)/ 1°C(MS-GA60VB)/ RT12 or RT13 still reads below-1°C
(MS-GA80VB) this mode prolonged until the RT12 reads over 3°C(MS-GA50VB)/ 1°C(MS-GA60VB) / RT12 or RT13 still
reads over-1°C(MS-GA80VB).
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the
beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again. Time accumulation is resumed.
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63.
Outdoor fan Low operation : When the outside temperature decreases to 20°C or less.
Until the outside temperature goes to 22°C.
Outdoor fan High operation : Until the outside temperature decreases to 20°C or less.
When the outside temperature goes to 22°C.
NOTE : When indoor fan speed is Low except FAN operation mode and the outside temperature is 30: or less, the
outdoor fan operates at Low.
Outdoor fan Low operation is cancelled according to the following conditions(1 or 2):
1 When the operation is not changed and the outside temperature goes to 33: or more.
2 When the operation is changed. (Change to FAN operation mode / Change of the indoor fan speed)
4. Discharge temperature protection <MU-GA80VB>
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess rise protection of
compressor discharge pressure.
• Compressor
When the temperature of discharge temperature thermistor RT62 goes to 120: or more, the compressor is turned OFF.
After 3 minutes since the compressor has been turned OFF, if the temperature of discharge temperature thermistor RT62
becomes 100: or less, the compressor is turned ON.
17
2-1-2. DRY mode of “I FEEL CONTROL”
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
•When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
•When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example
ON
ON
Thermostat
Indoor fan
Outdoor fan
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
Compressor
8 minutes
3 minutes
4 minutes
1 minute
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, its speed becomes Low.
4. Outdoor fan speed control <MU-GA80VB>
Outdoor fan speed control is as same as one of COOL mode of “I FEEL CONTROL”.
2-2. COOL () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
✻ Indoor fan continues to operate regardless of thermostat’s OFF-ON at set speed.
✻ Coil frost prevention is as same as COOL mode of “I FEEL CONTROL”.
18
AUTO
Horizontal
12
34 5
MiddleDownwardSwing
2-3. DRY () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT
button.
(3) The microprocessor reads the room tempera-
ture and determines the set temperature. Set
temperature is as shown on the right chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY mode of
“I FEEL CONTROL”.
(4) DRY operation will not function when the room
temperature is 13°C or below.
2-4. FAN () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns ON with a beep tone.
(2) Select FAN mode with OPERATION
SELECT button.
(3) Select the desired fan speed. When AUTO, it
becomes Low.
Only indoor fan operates. Outdoor unit does not
operate.
2-5. INDOOR FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to
feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency
(High, Med., Low), the microprocessor controls SR141 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational
frequency changes smoothly.
Rotational frequency
High
High
Med.
Low
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot
detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut
off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION
INDICATOR Indicator lamp flashes on and off to show the fan motor abnormality.
2-6. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing the VANE button.
time
19
(3) Positioning
The vane presses the vane stopper once to confirm the standard position and then moves to the set angle.
Confirming of standard position is performed in case of follows.
(a) When the power supply turns ON.
(b) When the operation starts or finishes (including timer operation).
(c) When the test run starts.
(d) When the vane control is changed AUTO to MANUAL(except SWING).
(e) When the SWING is finished (including ECONO COOL).
(4) VANE AUTO () mode
The microprocessor automatically determines the horizontal vane angle and operation to make the optimum room temperature distribution.
COOL and DRY operation
Vane angle is fixed to Angle 1.
FAN operation
Vane angle is fixed to Angle 4.
(5) STOP (operation OFF) and ON-TIMER standby
When the following cases occur, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the compressor cumulative operation time of compressor
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE ()
By selecting SWING mode with VANE button, the horizontal vane swings vertically. The remote controller displays “”.
SWING mode is cancelled when VANE button is pressed once again.
20
COOL / DRYFAN
Fan speed : Faster
Solid arrow : When LONG mode is used.
Dotted arrow : When LONG mode is not used.
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher.
Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(Tp
(w 1)).
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air
conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE button is pressed or
LONG button is pressed or change to other operation mode.
NOTE : ECONO COOL operation does not work in COOL mode of “I FEEL CONTROL”.
<SWING operation>
w 1 Tp : • Value of RT12 (MS-GA50/GA60VB)
• Minimum value of indoor coil thermistor (main) RT12 and indoor coil thermistor (sub) RT13 (MS-GA80VB)
In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.
According to the temperature of indoor coil thermistor Tp
(w 1) at starting of this operation, next downward blow time is
decided. Then when the downward blow has been finished, next horizontal blow time is decided.
For initial 10 minutes the swing operation is performed in table G~H for quick cooling.
Also, after 10 minutes when the difference of set temperature and room temperature is more than 2:, the swing operation is performed in table D~H for more cooling.
The air conditioner repeats the swing operation in various cycle as follows.
Temperature of Tp
A
B
C
D
E
F
G
H
15°C or less
15°C to 17°C
17°C to 18°C
18°C to 20°C
20°C to 21°C
21°C to 22°C
22°C to 24°C
more than 24°C
(w 1)
Downward blow time
(second)
2
5
8
11
14
17
20
23
Horizontal blow time
(second)
23
20
17
14
11
8
5
2
(9) LONG MODE ()
By pressing LONG button indoor fan speed becomes faster than setting fan speed on the remote controller, and the horizontal vane moves to the position for LONG mode. The remote controller displays “”. LONG mode is cancelled
when LONG button is pressed once again or VANE button is pressed or ECONO COOLbutton is pressed in COOL
mode.
• In the following example, the vertical vane is set to (front.).
21
About 100-
Horizontal AIR FLOW blowing range
61
23
45SWING
2. Vertical vane
(1) Vane motor drive
These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the
motor are controlled by pulse signals (approx. 12V) transmitted from microprocessor.
(2) The vertical vane angle and mode change as follows by pressing WIDE VANE button.
(3) Positioning
The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When OPERATE/STOP(ON/OFF) button is pressed (POWER ON/OFF).
(b) When SWING is started or finished.
(c) When the power supply turns ON.
(4) SWING MODE ()
By selecting SWING mode with WIDE VANE button, the vertical vane swings horizontally. The remote controller displays
“”. The vane moves right and left in the width of Angle 4 repeatedly.
(5) WIDE MODE ()
By selecting WIDE mode with WIDE VANE button, indoor fan speed becomes faster than setting fan speed on the
remote controller (W). The remote controller displays “”.
W Indoor fan speed becomes faster than setting fan speed on the remote controller even when or is
selected.
2-7. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON/OFF TIMER buttons to select the operation.
“ON-TIMER” button... AUTO START operation (ON timer)
“OFF-TIMER” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” mark is flashing.
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• Apower failure occurs.
•The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with ON/OFF TIMER buttons.
To cancel ON timer, press “ON-TIMER” button.
To cancel OFF timer, press “OFF-TIMER” button.
TIMER is cancelled and the display of set time disappears.
22
PROGRAM TIMER
PM
AM
PM
PM
• OFF timer and ON timer can be used in combination.
• “” and “” display shows the order of OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
2-8. EMERGENCY / TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL MODE with a set temperature of 24°C.
The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO () mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed again or the unit receives any
signal from the remote controller. In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
• The following indication applies regardless of
shape of the indicator.
OPERATION INDICATOR lamp
Press once <Cool>
Press again <Stop>
EMERGENCY OPERATION switch
23
Lighted
Not Lighted
Rank
Ta (:)
more than Tb+10
Tb+5 to Tb+10
Tb+2 to Tb+5
Tb-2 to Tb+2
Tb-5 to Tb-2
Tb-10 to Tb-5
less than Tb-10
100 pulse or less
Cooling
5
2
1
0
-1
-2
-5
NOTE : Discharge temperature : Ta, Target discharge temperature : Tb
100 pulse or more
Cooling
20
10
2
0
-2
-5
-10
Opening immediately before having stopped last time
2-9. EXPANSION VALVE CONTROL (LEV CONTROL) <MU-GA80VB>
Controlled range
Basic specification
Minimum : 54 pulse, Maximum : 500 pulse
Drive speed
30 ~ 90 pulse / second
Opening set
The setting is always in opening direction.
(To close the LEV, it is closed to the pulse smaller than the one which is
set finally. Then the LEV is opened to the final setting pulse.)
Stop of indoor unit
Opening in stop : 150 pulse ➔ LEV opening is set to becomes 500 pulse
after 3 minutes passed.
Remote controller ON
LEV positioning (LEV is closed completely at once)
Power ON (Breaker ON)
LEV is positioned. However, afterwards, LEV is not positioned at the first
remote controller ON.
Approximate for 2 minutes since
compressor has started.
Opening is set by the initial opening.
(Initial opening is set according to each operation modes and
outer temperature conditions.)
From approximate 2 minutes to
approximate 13 minutes
(for 11 minutes) since compressor
has started.
Opening is set by standard opening.
(Standard opening is set according to each operation modes and
outer temperature conditions.)
After 13 minutes passed since
compressor has started.
LEV opening is corrected to be once every 2 minutes so that discharge
temperature becomes the target discharge temperature.
(When the discharge temperature is lower than target : LEV is corrected in
closed direction, when the discharge temperature is higher than target :
LEV is corrected in opening direction.)
At thermostat OFF
Opening in stop : 150 pulse ➔ LEV is set to the initial opening after about
3 minutes passed.
At thermostat ON
Same as the starting of compressor operation
At remote controller OFF
Opening in stop : 150 pulse ➔ LEV is set so that the opening is opened
completely at the speed of 4 pulse every 5 seconds in opening after about
3 minutes passed.
General operation
LEV (Expansion valve) is controlled by “Thermostat ON” commands given from the unit.
(1) LEV opening correction by discharge temperature
The LEV opening is corrected according to the temperature difference between target discharge temperature (Tb) and
actual discharge temperature (Ta).
1 The LEV correction is used properly for two kinds according to the LEV opening status at operation off.
24
2 When the temperature difference RT between indoor coil thermistor (main) RT12 and indoor coil thermistor (sub)
Ta (:)
more than Tb+10
Tb+5 to Tb+10
Tb+2 to Tb+5
Tb-2 to Tb+2
Tb-5 to Tb-2
Tb-10 to Tb-5
less than Tb-10
less than 2:
20
10
2
0
-2
-5
-10
NOTE : Discharge temperature : Ta, Target discharge temperature : Tb
3: or more
60
20
2
0
-2
-5
-10
RT
2: or more and less than 3:
60
20
2
0
-2
-5
-10
Tb (:)
COOL (Normal)
COOL ( RT is less than 2:, or RT is 2:or more and less than 3:.)
COOL ( RT is 3 :or more.)
NOTE : Target discharge temperature : Tb
80
70
65
Operation mode
NOTE : Opening increases and decreases to be in the target discharge temperature during operation.
Opening
completely
Positioning
Power ON
Initial opening
Standard opening
Remote
controller
ON
➔
Operation
Thermostat
OFF
Standard opening
Thermostat
ON
Opening in stop
Operation
Opening in stop
Remote
controller
OFF
Opening
completely
Remote
controller
ON
➔
Positioning
Standard opening
Operation
Time
LEV opening
Initial opening
Initial opening
Open
Close
(Second)
(A)
WITH SOFT START RELAY
WITHOUT SOFT START RELAY
RT13 in the indoor unit is 2: or more for a fixed time at cool or dry operation, the target discharge temperature is
changed. After the temperature is changed, when temperature difference RT is 3: or more, the target temperature
is changed again. The LEV opening is controlled based on the changed target discharge temperature and the temperature difference RT.
The target discharge temperature (Tb) is set according to the operation mode or the unit status as follows.
NOTE : When the discharge temperature (Ta) is 50: or less on the cool operation LEV opening is set in 54 pulse.
When this state continues for 20 minutes, the compressor is stopped and restarts in 3 minutes.
When the compressor is stopped, the indoor unit indicates the abnormality of refrigerant system and stops.
(OPERATION INDICATOR lamp is 10-time flashing on and off.)
(2) LEV time chart
2-10. FUNCTION OF SOFT START RELAY
Soft start relay will chop some starting current.
Starting current is reduced as shown in the following figures.
25
3
Lighted
Not lighted
Approx.
2 :
or more
Difference
between target
temperature
and room
temperature
Approx.
2 :
or less
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait until the
target temperature is
obtained.
This shows that the
room temperature is
approaching the
target temperature.
Operation state
Indication
Operation Indicator
Operation Indicator lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
INDOOR UNIT DISPLAY SECTION
• The following indication applies regardless of
shape of the indicator.
Once the operation mode is set, the same operation mode can
be repeated by simply turning OPERATE/STOP (ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
3-1. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote
controller. OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select “I FEEL CONTROL” mode with OPERATION
SELECT button.
(3) The operation mode is determined by the room tempera-
ture at start-up of the operation.
Initial room temperature
25: or more
23:to 25:
less than 23:
26
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
• Once the mode is fixed, the mode does not change by room temperature afterwards.
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperatureInitial set temperature
26:
26: or more
25: to 26:
less than 23:
23: to 25:
24:
Initial room temperature
minus 2:
Initial room temperature
minus 2:
❈1
TOO
COOL
TOO
WARM
• Under ON-TIMER () operation, mode is determined as follows.
When the system is stopped on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” () mode,
the system operates in previous mode automatically regardless of the room temperature.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
Restart
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at
start-up of the operation.
Operation time chart
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that determined by room temperature at start-up of
the operation.
(4) The initial set temperature is decided by the initial room temperature.
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL” () mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Each time TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
•Fuzzy control
When TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the
room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…
To raise the set temperature 1~2°C
…
To lower the set temperature 1~2°C
27
3-1-1. COOL mode of “I FEEL CONTROL”
Difference between room
temperature and set temperature
during operation
1°C 1.7°C
3°C
Outdoor fan speed
20: 22:
High
Ambient temperature
thermistor RT63 temperature
Low
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In AUTO the fan speed is as follows.
Initial temperature difference Fan Speed
Room temperature minus set temperature : 1.7 : or more
Room temperature minus set temperature : Between 1 and 1.7 :
Room temperature minus set temperature : less than 1 :
2. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads 1°C or below(MSH-CA50/CB50/GA50VB) /–1°C or below(MSH-GA60VB)/
RT12 or RT13 reads 1°C or below (MSH-GA80VB), the coil frost prevention mode starts immediately.
However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 1°C(MSH-CA50/CB50/GA50VB)/ –1°C(MSH-GA60VB)/ RT12 or RT13 still reads
below 1°C (MSH-GA80VB) this mode prolonged until RT12 reads over 1°C(MSH-CA50/CB50/GA50VB)/ –1°C(MSHGA60VB) / RT12 or RT13 still reads over 1°C(MSH-GA80VB).
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the
beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again. Time accumulation is resumed.
Operation chart
Example
Compressor
OFF
ON
Outdoor fan
····································High
·························Med.
·····································Low
ON
OFF
(continuously at set speed)
Indoor fan
ON
3. Outdoor fan speed control <MUH-GA80VB>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63.
Outdoor fan Low operation : When the outside temperature decreases to 20°C or less.
Until the outside temperature goes to 22°C.
Outdoor fan High operation : Until the outside temperature decreases to 20°C or less.
When the outside temperature goes to 22°C.
NOTE1 : If the temperature of RT63 reads from 20: to 22: at the air conditioner starting outdoor fan speed is High.
NOTE2 : When indoor fan speed is Low except HEAT operation mode and the outside temperature is 30: or less, the
outdoor fan operates at Low.
Outdoor fan Low operation is cancelled according to the following conditions(1 or 2):
1 When the operation is not changed and the outside temperature goes to 33: or more.
2 When the operation is changed. (Change to HEAT operation mode / Change of the indoor fan speed)
4. Discharge temperature protection <MUH-GA80VB>
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess rise protection of
compressor discharge pressure.
• Compressor
When the temperature of discharge temperature thermistor RT62 goes to 120: or more, the compressor is turned OFF.
After 3 minutes since the compressor has been turned OFF, if the temperature of discharge temperature thermistor RT62
becomes 100: or less, the compressor is turned ON.
28
3-1-2. DRY mode of “I FEEL CONTROL”
Difference between room
temperature and set temperature
during operation
1°C 1.7°C
4°C
2°C
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
•When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
•When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example
ON
ON
Thermostat
Indoor fan
Outdoor fan
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
Compressor
3. Coil frost prevention
8 minutes
3 minutes
4 minutes
1 minute
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, its speed becomes Low.
4. Outdoor fan speed control <MUH-GA80VB>
Outdoor fan speed is as same as one of COOL mode of “I FEEL CONTROL”.
3-1-3. HEAT mode of “I FEEL CONTROL”
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 : or more·························································· High
Set temperature minus room temperature: Between 1 and 2 : ·············································· Med.
Set temperature minus room temperature: less than 1: ························································· Low
Initial temperature differenceFan speed
29
(2) Cold air prevention control
Released
Cold Air Prevention
18: 22:
Fan speed
Set speed
Very Low or stop
High pressure protection
Released
48:52:
ON
Outdoor fan
OFF
55:
(MUH-GA50VB)
(MUH-GA60VB)58:
Outdoor fan speed
13: 18:
High
Ambient temperature
thermistor RT63 temperature
Low
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates Low when
the temperature of indoor coil thermistor RT12 is below 18°C. But the fan stops when the indoor fan operates at Very
Low and the room temperature is 15°C or less.
Indoor coil thermistor
RT12 temperature
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner starting and also after defrosting, this
control works.
(3) Warm air control
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil thermistor RT12 temperature to blow out warm air.
After releasing of cold air prevention, when the indoor coil thermistor RT12 temperature is 37°C or above, the fan speed
shifts to the set speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.
When the indoor coil thermistor RT12 temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed>
less than 2 minutes························Low
2 minutes to 4 minutes···················Med.
4 minutes or more··························High
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at Very Low.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start at set speed until the indoor coil thermistor RT12 reads 22°C or more.
2. Outdoor fan speed control <MUH-GA80VB>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63.
Outdoor fan Low operation : Until the outside temperature decreases to 13°C.
When the outside temperature goes to 18°C or more.
Outdoor fan High operation :When the outside temperature decreases to 13°C or less.
Until the outside temperature goes to 18°C.
3. High pressure protection
<MUH-GA50/60VB>
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess
rise protection of compressor discharge pressure.
(MUH-GA50VB) Outdoor fan OFF: 52°C
Outdoor fan ON: 48°C
(MUH-GA60VB) Outdoor fan OFF: 58°C
Outdoor fan ON: 55°C
High pressure protection chart
Example
Indoor coil thermistor
RT12 temperature
(MUH-GA50VB) 52˚C
(MUH-GA60VB) 58˚C
(MUH-GA50VB) 48˚C
(MUH-GA60VB) 55˚C
Outdoor fan motor
ON
OFF
ON
OFF
Outdoor fan motor
turn OFF
Outdoor fan motor
turn ON
NOTE : During high pressure protection and for 4 minutes and 15 seconds after high pressure protection, defrosting of
outdoor heat exchanger is not detected by the defrost thermistor RT61.
30
Loading...
+ 134 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.