Mitsubishi MUX-2A28VB, MUX-2A59VB, MUX-3A60VB, MUX-3A63VB, MUX-2A70VB Service Manual

...
SERVICE MANUAL
HFC
utilized
R410A
SPLIT-TYPE, AIR CONDITIONER
Multi system type Models
No. OB384
MUX-2A28VB ­MUX-2A59VB ­MUX-3A60VB ­MUX-3A63VB ­MUX-2A70VB ­MUX-4A73VB -
MUX-2A59VB ­MUX-3A60VB ­MUX-3A63VB ­MUX-2A70VB -
Indication of model name
NOTE:
•As for indoor unit MSC-CA20VB - , MSC-CA25VB ­or MSC-CA35VB - , refer to the service manual OB393.
•This manual describes technical data of outdoor unit.
•As for indoor unit MSC-GA20VB - , MSC-GA25VB ­or MSC-GA35VB - , refer to the service manual OB385.
E1
E1
E1 E1 E1 E1
E1
E1
E1
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················6
3. INDOOR / OUTDOOR CORRESPONDENCE TABLE ···························6
4. SPECIFICATION·················································7
5. NOISE CRITERIA CURVES·····························12
6. OUTLINES AND DIMENSIONS······················ 13
7. WIRING DIAGRAM ··········································16
9. PERFORMANCE CURVES······························32
10. ACTUA TOR CONTROL····································55
11. TROUBLESHOOTING······································56
12. DISASSEMBLY INSTRUCTIONS ·····················63
E1E1
13. PARTS LIST······················································68
E1E1
1
TECHNICAL CHANGES
MUX-A10WV- ➔MUX-2A28VB-
MUX-A20WV- MUX-3A60VB-
1. Indication of capacity has been changed. (BTUkW)
MUX-A19WV- MUX-2A59VB­MUX-A22WV- MUX-3A63VB­MUX-A25WV- MUX-2A70VB­MUX-A26WV- MUX-4A73VB-
1. Indication of capacity has been changed. (BTUkW)
2. Size of stop valve (Gas) has been changed. (
E1E1
E1E1
E1E1
E1E1
E1E1
E1E1
[12.7[9.52)
2
Refrigeration
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
New Specification Current Specification
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigeration oil are compatible each, refrigeration oil goes back to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
Compressor
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/
ff
[Gauge])
3
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
NOTE : The unit of pressure has been changed to MPa on the
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench Flare tool
Flare gauge Vacuum pump
adapter Electronic scale for
refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
Wall thickness
Outside diameter
Pipe
mm For liquid For gas
6.35
9.52
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
4
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter
mm
6.35
9.52
Dimension of flare nut
R410A
17 22
R22
17 22
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Refrigerant gas cylinder operating valve
Liquid pipe
Gas pipe
Service port
Outdoor unit
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
5
2
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
(back and side)
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MUX-2A28VB-
E1
MUX-2A59VB- MUX-3A63VB­MUX-3A60VB- MUX-2A70VB-
(Back and side)
Air outlet
E1E1
E1E1
Air inlet
Piping
Drainage hose
MUX-4A73VB-
E1
Air inlet
(Back and side)
Air outlet
Piping
Drainage hose
Drain outlet
INDOOR / OUTDOOR CORRESPONDENCE TABLE3
MUX-2A28VB - MUX-2A59VB - MUX-3A60VB - MUX-3A63VB ­MUX-2A70VB - MUX-4A73VB -
MUX-2A59VB-
E1
A:
MSC-CA35VB-
E1
MSC-GA35VB-
B:
MSC-CA20VB-
- E1 MSC-GA20VB-
Combination of
the connectable
indoor units
MUX-2A28VB-
A:
MSC-CA20VB-
B:
or
MSC-GA20VB
E1E1
OUTDOOR UNIT
E1
MUX-3A60VB-
E1
or
or
E1 E1
E1
A:
MSC-CA25VB
B:
or
C:
MSC-GA25VB
E1
A: or
-
E1
B:
-
E1
C:
MUX-3A63VB-
MSC-CA35V
MSC-GA35VB MSC-CA20VB
or
MSC-GA20VB
E1
B- E1
- E1
- E1
- E1
MUX-2A70VB-
A:
MSC-CA35VB or B:
MSC-GA35VB
E1E1E1E1
E1
- E1
- E1
Drain outlet
MUX-4A73VB-
A:
MSC-CA35VB or B:
MSC-GA35VB
C:
MSC-CA25VB
or
D:
MSC-GA25VB
- E1
- E1
- E1
- E1
E1
6
4
Outdoor model Function
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
MUX-2A28VB -
E1
Cooling
Single phase
230V,50Hz
1,914
10
21
0.29
RN092VHSHT
600
C-R 3.87
C-S 6.14
RA6V33-FC
WHT-BLK 223
BLK-RED 221 780O540O255
35 49
825
1
0.90 (Room A+B) 350 (NEO22)
Single
A or B
2.4
0.9
3.20 725
98.5
2.91
3.16
Single
A
3.5
1.4
5.73
1,280
97.1
5.16
2.65
Double
A+B
3.5+2.4
1.4+0.9
8.96
2,005
97.3
8.39
2.84
Double
A+B
1.4O2
0.2O2
3.25 730
97.7
2.96
3.50
MUX-2A59VB -
E1
Cooling
Single phase
230V,50Hz
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Indoor unit No.
Single
B
2.4
0.9
2,460
20
3.51 785
97.2
48
2.94
0.57
2.93
MC1 : RN145VHSHT, MC2 : RN092VHSHT
MC1 : 1,000, MC2 : 600
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
66 52
730
1
1.00 (Room A)
0.80 (Room B)
MC1 : 620 (NEO22), MC2 : 350 (NEO22)
C-R 2.43 C-S 3.80
MC1 : , MC2 :
C-R 3.87 C-S 6.14
SPECIFICATION
NOTE: As for specification of the indoor units, refer to service manual OB393 (MSC-CA20/25/35VA- ) or
OB385 (MSC-GA20/25/35VA- ).
E1
E1
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Indoor-Outdoor piping length : 5m
Outdoor DB35°C WB24°C
7
Outdoor model Function
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
Single phase
230V,50Hz
Double
A+B or A+C
2.6+2.8
0.9+1.1 2,460
20
8.18
1,850
98.3 47
7.61
0.57
2.81
MC1 : RN099VHSHT, MC2 : RN125VHSHT
MC1 : 650, MC2 : 800
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
65 52
730
1
0.80 (Room A)
1.00 (Room B+C)
MC1 : 350 (NEO22), MC2 : 350 (NEO22)
MUX-3A60VB -
E1
Cooling
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Indoor unit No.
Single
A
2.6
0.9
3.64 815
97.3
3.07
3.06
Single B or C
2.9
1.2
4.86
1,075
96.2
4.29
2.61
Double
B+C
1.75O2
0.3O2
4.86
1,090
97.5
4.29
3.02
Triple
A+B+C
2.5+1.75O2
0.8+0.3O2
8.41
1,885
97.5
7.84
3.02
C-R 3.40 C-S 4.56
MC1 : , MC2 :
C-R 2.86
C-S 5.72
NOTE: As for specification of the indoor units, refer to service manual OB393 (MSC-CA20/25/35VA- ) or
OB385 (MSC-GA20/25/35VA- ).
E1
E1
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length : 5m
8
E1
Double
B+C
1.45O2
0.4
3.69 830
97.8
2.99
3.22
NOTE: As for specification of the indoor units, refer to service manual OB393 (MSC-CA20/25/35VA- ) or
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
E1
MUX-3A63VB -
E1
Cooling
Single phase
230V,50Hz
Single
A
3.5
1.4
Single B or C
2.4
0.9
Double
A+B or A+C
3.5+2.4
1.4+0.9 2,460
20
5.73
1,280
3.64 815
8.92
1,975
97.1
97.3
96.3 48
5.02
2.99
8.01
0.57
2.65
2.82
2.88
MC1 : RN145VHSHT, MC2 : RN092VHSHT
MC1 : 1,000, MC2 : 600
C-R 2.43
MC1 : , MC2 :
C-S 3.80
C-R 3.87 C-S 0.14
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
67 52
730
1
0.85 (Room A)
0.85 (Room B+C)
MC1 : 620 (NEO22), MC2 : 350 (NEO22)
OB385 (MSC-GA20/25/35VA- ).
Outdoor model
Function
Outdoor unit power supply
Indoor unit No.
Capacity Dehumidification Outdoor air flow
Capacity
Power outlet Running current Power input Auxiliary heater Power factor
Electrical
data
Starting current Compressor motor current Fan motor current
Coefficient of performance (C.O.P)
Model Output Winding
Compressor
resistance (at 20:) Model Winding
Fan
motor
resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling
Special
remarks
capacity (R410A) Refrigeration oil (Model)
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length 5m
Triple
A+B+C
3.4+1.45O2
1.4+0.4
8.84
1,980
97.4
8.01
3.01
9
Outdoor model Function
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Indoor unit No.
MUX-2A70VB -
E1
Cooling
Single phase 230V,50Hz
2,460
20
54
0.57
MC1 : RN145VHSHT, MC2 : RN145VHSHT
MC1 : 1,000, MC2 : 1,000
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
68 52
730
1
0.95 (Room A)
0.95 (Room B)
MC1 : 620 (NEO22), MC2 : 620 (NEO22)
Single A or B
3.5
1.4
5.88
1,300
96.1
5.31
2.61
Double
A+B
3.5O2
1.4O2
11.49
2,540
96.1
10.92
2.67
C-R 2.43 C-S 3.80
MC1 : , MC2 :
C-R 2.43
C-S 3.80
NOTE: As for specification of the indoor units, refer to service manual OB393 (MSC-CA20/25/35VA- ) or
OB385 (MSC-GA20/25/35VA- ).
E1
E1
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Indoor-Outdoor piping length : 5m
Outdoor DB35°C WB24°C
10
NOTE: As for specification of the indoor units, refer to service manual OB393 (MSC-CA20/25/35VA- ) or
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
E1
Single A or B
3.4
1.2
5.28
1,180
97.2
4.75
2.79
Single C or D
2.75
1.1
4.54
1,015
97.2
4.01
2.62
E1
MUX-4A73VB -
Cooling
Single phase 230V,50Hz
Double
A+B
1.95O2
0.2O2
Double
A+C or A+D
or
B+C or B+D
3.4+2.7
1.2+1.1
Double
C+D
1.7O2
0.3O2
2,760
20
5.46
1,210
9.57
2,095
4.78
1,060
96.4
95.2
96.4
52
4.93
9.04
4.25
0.53
3.02
2.81
3.01
MC1 : RN145VHSHT, MC2 : RN125VHSHT
MC1 : 1,000, MC2 : 800
C-R 2.43
MC1 : , MC2 :
C-S 3.80
C-R 2.86 C-S 5.72
RA6V60-FA WHT-BLK 79 BLK-RED 80
840O850O330
76 52
730
1
1.05 (Room A+B)
1.05 (Room C+D)
MC1 : 620 (NEO22), MC2 : 350 (NEO22)
OB385 (MSC-GA20/25/35VA- ).
Outdoor model Function
Outdoor unit power supply
Indoor unit No.
Capacity Dehumidification Outdoor air flow
Capacity
Power outlet Running current Power input Auxiliary heater Power factor
Electrical
data
Starting current Compressor motor current Fan motor current
Coefficient of performance (C.O.P)
Model Output Winding
Compressor
resistance (at 20:) Model Winding
Fan
motor
resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling
Special
remarks
capacity (R410A) Refrigeration oil (Model)
E1
Triple
A+B+C
or
A+B+D
1.95O2+2.8
0.2O2+1.1
9.61
2,105
95.2
9.08
3.02
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length : 5m
Triple
A+C+D
or
B+C+D
3.4+1.7O2
1.2+0.3O2
9.66
2,140
96.3
9.13
3.02
Four
A+B+C+D
1.95O2+1.7O2
0.2O2+0.3O2
9.75
2,210
98.6
9.22
3.09
11
NOISE CRITERIA CURVES5
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19:
MUX-2A28VB- E1
COOL
FUNCTION
49
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35: WB24:
COOL
FUNCTION
52
SPL(dB
(A)) LINE
MUX-2A59VB - E1 MUX-3A60VB - E1 MUX-3A63VB - E1 MUX-2A70VB - E1
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35: WB24:
COOL
FUNCTION
52
SPL(dB
(A)) LINE
MUX-4A73VB - E1
12
6
320
25
10-
126
76
120
56
260
10
780
500
122
40
540
320
285
255
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Air out
Air in
Air in
176
226
109
32
110
147
Drainage 3holes [33
100mm or more
100mm or more
100mm or more
350mm or more
REQUIRED SPACE
400mm or more
500
840 61
264
10°
10°
Service panel
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
Open as a rule 500mm or more if the back, both sides and top are open
350mm or more
100mm or more
B UNIT A UNIT
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
65
80
121
40
438
Air in
Air out
Air in
273
100
125
320
30
330
640
360
76
505050
Drainage 3holes {33
} }
34
OUTLINES AND DIMENSIONS
OUTDOOR UNIT
MUX-2A28VB-
Unit: mm
E1
MUX-2A59VB-
E1
13
OUTDOOR UNIT
MUX-3A60VB­MUX-3A63VB-
Drainage 3 holes {33
125
Air in
273
34
100
320
E1
E1
500
438
Air in
30
Air out
840 61
121
Unit: mm
Open as a rule 500mm or more if the front and both sides are open
100mm or more
100mm or more
330
360
Open as a rule 500mm or more if the back,
40
640
65
both sides and top are open
10°
10°
264
Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
C UNIT
}
B UNIT
}
A UNIT
}
5050505050
76
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
200mm or more if there are obstacles on both sides
350mm or more
MUX-2A70VB-
Drainage 3 holes {33
125 Air in
273
34
100
320
E1
500
438
Air in
30
Air out
840 61
121
Open as a rule 500mm or more if the front and both sides are open
100mm or more
100mm or more
330
360
Open as a rule 500mm or more if the back,
40
640
80
both sides and top are open
10°
10°
264
} }
B UNIT A UNIT
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
505050 76
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
200mm or more if there are obstacles on both sides
350mm or more
14
OUTDOOR UNIT
MUX-4A73VB-
Drainage 3 holes {33
125
330
Air in
850
430
Open as a rule 500mm or more if
E1
100
273
438
Air in
Air out
121
40
34
30
500
840
100mm or more
360
Open as a rule
65
500mm or more if the back,
61
both sides and top are open
10°
10°
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
80
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
260
the front and both sides are open
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
D Unit
50 50
C Unit
5050
B Unit
50 50
A Unit
50
76
100mm or more 200mm or more if there are obstacles on both sides
350mm or more
Unit: mm
15
7
WIRING DIAGRAM
MUX-2A28VB -
OUTDOOR UNIT
POWER SUPPLY
~ / N 230V 50Hz
CIRCUIT BREAKER
TO INDOOR UNIT No.A CONNECTING
12V
TO INDOOR UNIT No.B CONNECTING
12V
E1
MODEL WIRING DIAGRAM
BLU
2 1
2 1
NO
BRN
2
BLU
BLU
BLU
BLU
52C
52C
1
2
TB3
F61
BLU
COM
BRN
BLU
WHT
5
6
5
6
X1
X1
X2
X2
2
1
F62
1 3
4
3 2 4
WHT
BRN BRN BRN
WHT
1
TB3
WHT
C2
C1
WHT BLU
RED
WHT
BLU
RED
1 2
3
2 1
WHT
BLK
RED
BLU BLU
S
BLK
C
21R
MC
MF
R
2 1
2
1
L
N
TB2
TB1
WHT
PE
BLK YLW
ORN
X1
X2
DSAR
7
8 7
8
BRN
BRN
21R1
21R2
BLU
BLU
BLU BLU
BLU
BLU
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
DSAR
F61,F62
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
SURGE ABSORBER FUSE(2A) COMPRESSOR(INNER PROTECTOR)
MC
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NAME
SYMBOL
OUTDOOR FAN MOTOR(INNER FUSE)
MF
TB1,TB2,TB3
21R
TERMINAL BLOCK RELAY(A)
X1
RELAY(B)
X2
SOLENOID COIL
NAME NAME
SYMBOL
21R1 21R2
52C
SOLENOID COIL(A) SOLENOID COIL(B) COMPRESSOR CONTACTOR
16
MUX-2A59VB ­MUX-2A70VB -
OUTDOOR UNIT
E1
E1
MODELS WIRING DIAGRAM
POWER SUPPLY ~/N 230V 50Hz
L
N
TB1
PE
CIRCUIT BREAKER
GRN/YLW
TO INDOOR UNIT A CONNECTING
2 1
TB2
BLU
YLW
12V TO INDOOR
UNIT B CONNECTING
2 1
BLU
ORN
12V
SYMBOL
C1
COMPRESSOR CAPACITOR(MC1)
C2
COMPRESSOR CAPACITOR(MC2)
C61
DSAR
F61
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
BRN BLU
BRN
TB4
2
1
DSAR
3 2 1
3 2 1
BLU
CN71
CN73
CN91
SYMBOL
MC1
MC2 MF61 NR61
SR861
BRN
123
CN90
OUTDOOR CONTROL P.C. BOARD
F61
NR61
T61
SR861
52 3 41
6
BLK
WHT
RED
MF61
COMPRESSOR(INNER PROTECTOR) COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) SURGE ABSORBER OUTDOOR FAN RELAY
LD1
LD2
RED
RED
C61
NAME NAME
BRN
X522
BRN
X521
3
4
X521X522
SYMBOL
TB1
TB2~TB4
T61 X521 X522
C1
BLU
RED
S
MC1
BLU
BLK
R
C
WHT
3
4
C2
RED
S
MC2
R C
BLK
WHT
TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER COMPRESSOR CONTACTOR(MC1) COMPRESSOR CONTACTOR(MC2)
17
1
2
3
1
2
3
123
213
1 2 31 2 31 2 3
21R421R3
NR61
T61
1
2
43
43
C61
LD1
WHT
WHT
OUTDOOR CONTROL P.C. BOARD
BRN
BLU
BRN
BLU
BRN
BLU
BLU
X522
X521
BLK
SR865
SR866
SR863
SR861
LD2
RED
RED
RED
BLK
WHT
652 3 41
BRN BLU
BLU
TB4
CN86
CN85
CN81
CN91
CN90
TB3
TB2
X521
BLU
BLU
X522
BLU
BLU
21RB
F61
CN74
CN73
CN71
TO INDOOR
UNIT B
CONNECTING
12V
PE
CIRCUIT BREAKER
GRN/YLW
WHT
BLU
ORN
BLU
YLW
BLU
RED
RED
TO INDOOR
UNIT A
CONNECTING
12V
1
2
1
2
C2
C1
R C
S
CR
S
MC2
TO INDOOR
UNIT C
CONNECTING
12V
MF61
MC1
BLK
TB1
POWER SUPPLY
~/N
230V
50Hz
1
2
L
N
DSAR
BRN
MUX-3A60VB -
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
TERMINAL BLOCK
TRANSFORMER
COMPRESSOR CONTACTOR(MC1)
COMPRESSOR CONTACTOR(MC2)
SOLENOID COIL
SOLENOID COIL (B)
SOLENOID COIL (C)
T61
SYMBOL
TB2~TB4
NAME NAME
X521
X522
21RB
21R3
21R4
18
OUTDOOR FAN MOTOR(INNER PROTECTOR)
SURGE ABSORBER
MF61
NR61
SYMBOL
NAME
COMPRESSOR CAPACITOR(MC1)
COMPRESSOR CAPACITOR(MC2)
C1
C2
SYMBOL
OUTDOOR FAN RELAY
RELAY (21RB)
SR861
SR863
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
C61
DSAR
RELAY (C) (21R4)
RELAY (B) (21R3)
TERMINAL BLOCK
TB1
SR865
SR866
FUSE(3.15A)
COMPRESSOR(INNER PROTECTOR)
COMPRESSOR(INNER PROTECTOR)
F61
MC1
MC2
2. Use copper conductors only. (For field wiring)
/: Terminal block, : Connector
3. Symbols below indicate.
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
MUX-3A63VB -
E1
OUTDOOR UNIT
S
RED
C1
BLU
BRN
BRN
CR
MC1
BLK
BLU
MODEL WIRING DIAGRAM
S
MC2
WHT
X521
RED
C2
43
43
X522
R C
BLK
X521
X522
T61
WHT
SR865
SR866
SR863
CN86
1 2 31 2 31 2 3
CN85
CN81
BLU BLU
BLU BLU
BLU BLU
21R421R3
21RB
TERMINAL BLOCK
TRANSFORMER
T61
SYMBOL
TB2~TB4
COMPRESSOR CONTACTOR(MC1)
COMPRESSOR CONTACTOR(MC2)
SOLENOID COIL
X521
X522
21RB
SOLENOID COIL (B)
21R3
SOLENOID COIL (C)
21R4
TB4
TB1
2
BRN
L
1
BLU
N
BRN
PE
OUTDOOR CONTROL P.C. BOARD
CN90
BRN
123
BLU
DSAR
GRN/YLW
CIRCUIT BREAKER
BLU
TB2
2
F61
213
YLW
1
CN71
NR61
3
BLU
2
2
ORN
1
CN73
1
SR861
3
BLU
TB3
2
CN74
2
WHT
1
LD1 LD2
652 3 41
CN91
1
RED RED
RED
BLK
WHT
C61
MF61
NAME NAME
OUTDOOR FAN MOTOR(INNER PROTECTOR)
SURGE ABSORBER
MF61
NR61
SYMBOL
NAME
COMPRESSOR CAPACITOR(MC1)
COMPRESSOR CAPACITOR(MC2)
C1
C2
SYMBOL
OUTDOOR FAN RELAY
RELAY (21RB)
SR861
SR863
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
C61
DSAR
RELAY (C) (21R4)
RELAY (B) (21R3)
TERMINAL BLOCK
TB1
SR865
SR866
FUSE(3.15A)
COMPRESSOR(INNER PROTECTOR)
COMPRESSOR(INNER PROTECTOR)
F61
MC1
MC2
2. Use copper conductors only. (For field wiring)
/: Terminal block, : Connector
3. Symbols below indicate.
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
POWER SUPPLY
~/N
230V
50Hz
TO INDOOR
TO INDOOR
UNIT A
UNIT B
CONNECTING
12V
CONNECTING
12V
TO INDOOR
UNIT C
CONNECTING
12V
19
DSAR
CIRCUIT BREAKER
L
N
2
1
2
112
1
2
BLK
RED
MF61
21R1
BLU
BLU
RED RED
OUTDOOR CONTROL P.C. BOARD
T61
3 4
43
X521
X522
MC1
S
R C
MC2
S
R C
C1
C2
BLK
RED
WHT
RED
BLK
WHT
X522 X521
13
3
1
3
113
1
3
621
CONNECTING
TO INDOOR
POWER SUPPLY
WHT
BLU
ORN
BLU
BRN
BLU
YLW
CN74CN73CN72CN71
TB1
TB3
TB2
2
2
2
2
2
BRN
BLU
TB4
2
1
BLU
F61
BRN
BLU
SR861
CN91
43 5
SR868
BLU
BLU
BRN
BRN
LD1
LD2
C61
NR61
CN90
WHT
1 2 3 1 2 3
21R2
BLU
BLU
SR867
21R3
BLU
BLU
SR866
1 2 3
BLU
BLU
21R4
1 2 3
SR865
BLU
BLU
21RA
1 2 3
SR864
BLU
BLU
21RB
1 2 3
SR863
CN83 CN84 CN85 CN86 CN81CN82
~/N
12V
230V
50Hz
UNIT C
TO INDOOR
CONNECTING
12V
UNIT A
PE
GRN/YLW
TO INDOOR
CONNECTING
UNIT D
12V
CONNECTING
TO INDOOR
12V
UNIT B
BRN
SYMBOL
SR861
SR863
SR864
SR865
SR866
SR867
SR868
TB1~TB4
T61
SYMBOL
C1
C2
C61
DSAR
F61
MC1
MC2
MF61
NR61
NAME
NAME NAME
COMPRESSOR CAPACITOR(MC1)
COMPRESSOR CAPACITOR(MC2)
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
FUSE(3.15A)
COMPRESSOR(INNER PROTECTOR)
COMPRESSOR(INNER PROTECTOR)
OUTDOOR FAN MOTOR(INNER PROTECTOR)
SURGE ABSORBER
OUTDOOR FAN RELAY
RELAY (21RB)
RELAY (21RA)
RELAY (D) (21R4)
RELAY (C) (21R3)
RELAY (B) (21R2)
RELAY (A) (21R1)
TERMINAL BLOCK
TRANSFORMER
COMPRESSOR CONTACTOR(MC1)
COMPRESSOR CONTACTOR(MC2)
SOLENOID COIL (BALANCE)
SOLENOID COIL (BALANCE)
SOLENOID COIL (A)
SOLENOID COIL (B)
SOLENOID COIL (C)
SOLENOID COIL (D)
SYMBOL
X521
X522
21RA
21RB
21R1
21R2
21R3
21R4
MUX-4A73VB -
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
2. Use copper conductors only. (For field wiring)
/: Terminal block, : Connector
3. Symbols below indicate.
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
20
8
Indoor unit A
Outdoor unit
MUX-2A28VB- E1
Additional piping max. length 15m
Max. length difference 10m
Indoor unit B
UNIT A
Indoor
heat
exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
UNIT B
Indoor
heat
exchanger
Outdoor
heat
exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
(With insulation)
Refrigerant pipe
[9.52
(With insulation)
Refrigerant pipe
[9.52
Flared connection
(With insulation)
Refrigerant pipe
[6.35
(With insulation)
Refrigerant pipe
[6.35
Flared connection
Stop valve with service port
Solenoid valve 21R1
Solenoid valve 21R
Solenoid valve 21R2
Capillary tube
Capillary tube
Capillary tube
Capillary tube
[3.0 x [1.4 x 1000
Compressor
Strainer
#100
Muffler
Refrigerant flow in cooling
Stop valve with service port
Stop valve
Stop valve
[3.0 x [1.6 x 900
[3.0 x [1.4 x 400
[3.0 x [1.4 x 400
Strainer
#100
OUTDOOR UNIT
INDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
Unit : mm
MUX-2A28VB-
E1
MAX. REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
UNIT No.
unit + unit
PIPING PREPARATION
1 Table below shows the specifications of pipes commercially available.
UNIT No. Pipe
and
2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation. 3 Refrigerant bending radius must be 10cm or more.
BA
BA
UNIT
Outdoor unit precharged
900g
For liquid 6.35 8 mm Heat resisting foam plastic
For gas 9.52 8 mm 0.045 specific gravity
Refrigerant piping length (one way)
10m11m12m13m14m15m16m17m18m19m20m21m22m23m24m25m26m27m28m29m30
0 10 20 30 40 50 60
70 80 90 100 110 120 130 140 150 160 170 180 190 200
Outside diameter Insulation
mm thickness
21
Insulation material
m
OUTDOOR UNIT
INDOOR UNIT
UNIT A
Indoor
heat
exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
UNIT B
Indoor
heat
exchanger
Outdoor
heat
exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
Flared connection
Flared connection
Stop valve with service port
Stop valve
Stop valve with service port
Capillary tube
Capillary tube
Muffler
Muffler
Strainer
#100
Compressor(A)
Compressor(B)
Refrigerant flow in cooling
Stop valve
[3.0 x [1.4 x 850
[3.0 x [1.4 x 1100
(With insulation)
Refrigerant pipe
[6.35
(With insulation)
Refrigerant pipe
[6.35
(With insulation)
Refrigerant pipe
[9.52
(With insulation)
Refrigerant pipe
[9.52
Strainer
#100
Unit : mm
MUX-2A59VB-
E1
22