SPLIT-TYPE, AIR CONDITIONERS
SPLIT-TYPE, HEAT PUMP AIR CONDITION
NOTE: • This service Manual covers only change points.
SERVICE MANUAL
Wireless type
Models
MSC-07RV MSC-09RV MSC-12RV -
MSC-07RV MSC-09RV MSC-12RV -
MSC-07RV MSC-09RV MSC-12RV -
MSC-07RV MSC-09RV MSC-12RV -
MSC-07RV MSC-09RV MSC-12RV -
MSC-07RV MSC-09RV MSC-12RV -
Multi system type
MSC-07RV MSC-09RV MSC-12RV -
Inverter controlled multi system type
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
· MU-07RV -
· MU-09RV -
· MU-12RV -
· MU-07RV -
· MU-09RV -
· MU-12RV -
· MU-07RV -
· MU-09RV -
· MU-12RV -
· MUH-07RV -
· MUH-09RV -
· MUH-12RV -
· MUH-07RV -
· MUH-09RV -
· MUH-12RV -
· MUH-07RV -
· MUH-09RV -
· MUH-12RV -
· MUX-10RV -
· MUX-18RV -
· MUX-24RV -
· MXZ-18RV -
Please refer to the Service Manual OB227 REVISED
EDITION-B for unchanged contents.
• Please refer to the following service manual when the
outdoor unit is the under mentioned model.
MXZ-32SV-: OB254
MXZ-18TV-: OB280
MUX-19/20/25TV-: OB284
The specifications of Indoor and Outdoor fan motor.
The data of Med. and Low speed are added to Indoor fan motor
specification
✼
✼The data value of indoor fan motor does not change if the indoor
unit is connected to a multi-type outdoor unit.
Remote controllers of COOL ONLY or COOL & HEAT
type are outdoor unit accessory.
Remote controller is included as an indoor unit accessory.
Two-way common remote controller
Two-way (using dip switch) remote controller
The specification of electronic control P.C. board is
compatible with remote controllers of COOL ONLY
and COOL & HEAT type.
Indoor electronic control P.C. board has changed
for two-way remote controller.
Indoor electronic control P.C. board has changed
for two-way remote controller.
Microprocessor programing flow has changed.
Electronic control P.C. board for E3 is interchangeable
with the one for E2 (except for MSC-12RV).
(New P.C. board) Indoor electronic control P.C. board has
changed.
Earth wire from the board is fixed to the electrical box with screw.
The shape of connector CN211 has changed. Indoor electronic
control P.C. board has been connected with
Power monitor, receiver P.C. board using connector.
When fan speed is set to"Auto", initial temperature difference
specitying changing fan speed has been improved in order to
reach the set temperature faster than E1, E2, and E3.
The mark of terminal block has changed. Terminal block for E4 is
interchangeable with the ones for E1, E2 and E3.
Winding resistance and shape of fan motor have changed.
Fan motor for E4 is not interchangeable with the ones for E1,
E2 and E3 except for MSC-12RV.
Fan motor rubber mount has changed because the shape of
fan motor was changed.
Circle shows the change point of the model.
Change point
No.
MSC-07RV-
E1
E2
E3
MSC-09RV-
E1
E2
E3
MSC-12RV-
E1
E2
E3
E4
E4
E4
TECHNICAL CHANGES
3
1
2
3
4
5
6
7
8
9
10
11
12
13
Remote controller of COOL ONLY type is outdoor unit accessory.
Remote controller is included as an indoor unit accessory.
Compressor contactor (52C) has changed. Compressor
contactor for E2,E3,E4 are interchangeable with the ones for E1.
Compressor has changed. Compressors for E3 and E4 are not
interchangeable with the ones for E1 and E2.
Compressor capacitor has changed. Due to different shape,
compressor capacitor for E4 is not interchangeable with the
ones for E1, E2 and E3.
Fuse has been removed.
Wiring diagram has changed because fuse was removed.
The shape of propeller fan has changed. The number of
propeller fan has changed from four to three. Propeller fan for E4
is not interchangeable with the ones for E1, E2 and E3.
The shape, diameter of axis and fan speed of fan motor have
changed. Fan motor for E4 is not interchangeable with the ones
for E1, E2 and E3.
Fan motor capacitor has changed. 1.5+➔ 2.0+
Fan motor capacitor for E4 is not interchangeable with the
ones for E1, E2 and E3(MU-12RV only).
Refrigerant filing capacity has changed. 0.85kg➔ 0.80kg
The method of troubleshooting for outdoor unit has changed.
The repairing procedure when outdoor unit does not stop
has been added to troubleshooting.
Circle shows that change points apply to the models.
Change point
No.
MU-07RV-
E1
E2
E3
MU-09RV-
E1
E2
E3
MU-12RV-
E1
E2
E3
E4
E4
E4
4
No.
Remote controller of COOL & HEAT type is outdoor unit
1
accessory.
Remote controller is included as an indoor unit accessory.
2
Accumulator has been removed.
3
Compressor has changed.
4
Compressor capacitor has changed. Due to different
shape, compressor capacitor for E4 is not interchangeable
5
with the ones for E1,E2 and E3.
The mark of terminal block has changed. Terminal block
6
for E4 is interchangeable with the ones for E1, E2 and E3.
Deicer P.C. board has changed. Jumper wire of compulsory
defrosting mode has changed.
Jumper wire for defrost setting has changed.
(JPC-JPE➔JRF-JRG) (Refer to page 26.)
7
The defrosting intervals which are changed by setting a short
circuit are the same as E1, E2, and E3.
Deicer P.C. board for E4 is not interchangeable with the
ones for E1, E2 and E3.
Wiring diagram has changed according to the following
reasons; the shape of connectors CN711 and CN661 has
8
changed and R.V. coil relay (X62) has changed into SSR (SR62).
X62 has changed into SR62 in Example of Operation
time chart in HEAT operation.
9
Compared to E1, E2, and E3, no change has been made about
the operational condition for defrosting and tne control system of
R.V. coil (timing of switching on/off).
The shape of propeller fan has changed. The number of
propeller fan has changed from four to three. Propeller
10
fan for E4 is not interchangeable with the ones for E1,E2, and E3.
The shape and diameter of axis of fan motor have changed.
The shape of connector has changed.
11
Fan motor and connector for E4 are not interchangeable
with those for E1, E2 and E3.
Refrigerant filling capacity has changed. 0.80kg➔ 0.85kg
12
The method of checking serial signal error for E4 has been added.
13
The method of troubleshooting for outdoor unit has changed.
14
The method for checking thermistor has been added to
15
troubleshooting.
The method for checking 4-way valve has been added to
16
troubleshooting.
The repairing procedure when outdoor unit does not stop has
17
been added to troubleshooting.
Change point
(JP607-R853➔JPDS-JPSG)
Circle shows that change points apply to the models.
MUH-07RV-
E1
E2
E3
E4
MUH-09RV-
E1
E2
E3
E4
MUH-12RV-
E1
E2
E3
E4
MUX-10RV MUX-18RV MUX-24RV MXZ-18RV -
E1
E1
E1
E1
MUX-10RV MUX-18RV MUX-24RV MXZ-18RV -
E2
E2
E2
E2
1. Remote controller is unprovided as the outdoor unit accessory.
5
COOL ONLY
COOL
& HEAT
TWO-WAY
REMOTE CONTROLLER
Model
MS-07/09/12RV-
E1
MSH-07/09/12RV-
E1
MS-07/09/12RV-
E2
MSH-07/09/12RV-
E2
✕
✕
✕
✕
w
w When HEAT mode is selected
by the remote controller of
COOL & HEAT type, the unit
will operate in FAN mode.
1. Both of COOL ONLY and COOL & HEAT remote controller are unified into a two-way remote controller.
2. FAN mode operation is available in COOL ONLY unit. In this case the set room temperature
will be displayed on the remote controller, however, the room temperature can not be controlled by remote controller button.
HEAT operation is available in only HEAT & COOL type unit.
• The way of remodelling individual operation of P.C Board of remote controller has changed.
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries and press the
OPERATE/STOP(ON/OFF)button
twice or 3 times at first.
After finish remodelling, put back
the batteries then press the
RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown
in Table 1. After modification, press the RESET button.
Table 1
REMOTE CONTROLLER (How to set the type)
This remote controller setting needs to be switched according to the type of air conditioner (COOL & HEAT or COOL
ONLY).
If the setting is incorrect, the air conditioner does not operate normally. Therefore, check if the setting corresponds to
the type of air conditioner. If it does not, correct the setting as shown below.
Slide switch
Type
The position
of the slide
switch
COOL ONLYCOOL & HEAT
7
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller mounting hardware
Fixing screw for 3 3.5 o 16 mm
Battery (AAA) for remote controller
Felt tape (Used for left or left-rear piping)
Deodorizing filter
Air cleaning filter
Wireless remote controller
Drain socket: MUH type
Drain cap: MUH type
1
1
2
1
5
1
2
2
1
1
1
<Indoor unit>
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller mounting hardware
Fixing screw for 3 3.5 o 16 mm
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
Deodorizing filter
Air cleaning filter
Drain socket
Drain cap
1
2
1
5
1
2
2
1
1
1
1
<Indoor unit>
<Outdoor unit: MUH type><Outdoor unit>
9
0
1
1
2
3
4
5
6
7
8
0
1
1
2
3
4
5
6
7
8
9
• How to replace batteries
Insert the negative pole
of the batteries first.
Check if the polarity of
the batteries are correct.
HEAT
/FAN
/
RESET button
HEAT
/FAN
/
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
2 Press the RESET button.
Then re-attach the front lid.
NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med. /Low )
Fan speed (High/Med. /Low )
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R22)
Refrigerating oil (Model)
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med. /Low )
Fan speed(High/Med. /Low )
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R22)
Refrigerating oil (Model)
Thermistor RT61(at0:)
Room temperature minus set temperature : 2 degrees or more································High
Room temperature minus set temperature : Between 1 and 2 degrees····················Med.
Room temperature minus set temperature : less than 1 degree································Low
MSC-07RV MSC-09RV MSC-12RV -
E4
E4
E4
Initial temperature difference
Fan speed
Room temperature minus set temperature : 1.7 degrees or more·····························High
Room temperature minus set temperature : Between 1 and 1.7 degrees·················Med.
Room temperature minus set temperature : less than 1 degree································Low
Difference between room
temperature and set temperature during operation
4 deg.
1 deg.
2 deg.
1.7 deg.
Difference between room
temperature and set temperature during operation
3 deg.
1.7 deg.
1 deg.
7
TROUBLESHOOTING
7-1. Trouble criterion of main parts
E4
MSC-07RV MSC-09RV MSC-12RV -
Part name
Indoor fan
motor(MF)
INNER FUSE
136I3 CUT OFF
Outdoor fan
motor(MF)
INNER FUSE
163I3 CUT OFF
MU-07RV -
E4
MU-09RV -
E4
MU-12RV -
Motor part
WHT-BLK
BLK-RED
WHT-BLK
BLK-RED
E4
MUH-07RV -
E4
MUH-09RV -
E4
MUH-12RV -
E4
E4
E4
Check method and criterionFigure
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Color of
lead wire
WHT-BLK
BLK-RED
MSC-07/09RV-
396 ~ 430Ω
320 ~ 348Ω
Normal
E4
MSC-12RV-
396 ~ 430Ω
320 ~ 348Ω
E4
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
Color of
lead wire
Color of
lead wire
MU-07/09RV-
311 ~ 381
283 ~ 347
MUH-07/09RV-
311 ~ 381
283 ~ 347
Normal
E4
Ω
Ω
Normal
E4
Ω
Ω
MU-12RV-
265 ~ 325
292 ~ 359
MUH-12RV-
265 ~ 325
292 ~ 359
E4
Ω
Ω
E4
Ω
Ω
Abnormal
Open or short-circuit
Abnormal
Open or short-circuit
Abnormal
Open or
short-circuit
16
When OPERATION INDICATOR lamp flashes 3-time.
Indoor fan motor doesn’t operate.
A
Check of indoor fan motor
Turn OFF the power supply.
Check connector CN211 visually.
No
Re-connect the lead wires.
Are lead wires connected?
Disconnect lead wires from connector CN211 on indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.5 and then No.3 and No.5.
Yes
Is resistance 0 (short circuit) or ∞ (open circuit)?
Yes ( 0 or ∞ )
Repair or replace the indoor fan motor.
Is soldered point of the connector
correctly soldered?
Turn ON the power supply. Stop it if the unit oper-
ate. Insert screwdriver into air outlet to rotate
indoor fan motor slowly for 1 revolution or over, and
No
(others)
measure voltage No.2(+) and No.3(-) on CN121.
No
Does voltage repeat 0V DC and 5V DC?
Replace the indoor electronic control P.C. board.
Yes
No
Re-solder it.
Yes
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.
Check of remote controller and receiver P.C. board
B
wCheck the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the remote controller displayed?
Yes
Remove batteries, then set them back and
press the RESET button. Check if the unit
operates with the remote controller.
Does the unit operate with the
remote controller?
Yes
Ok
Measure the voltage between receiver P.C. board connector CN302
No.3
No
(not clear)
No
(–)
and No.5
Replace the batteries.
Turn on a radio to AM and press switch on
the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
No
MSC-07/09/12RV-, ,
MSC-07/09/12RV-
(+)
when the remote controller button is pressed.
Is the voltage approx. 4V DC?
Replace the receiver P.C. board.
E4
No(5V or 0V DC)
No
Yes
Yes
Replace the remote controller.
• Re-install the unit away from lights.
• Attach a filter on receiving part.
E3E2E1
Replace the indoor electronic control
P.C. board.
17
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board
C
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller?
Does the OPERATION INDICATOR lamp light up
by pressing the EMERGENCY OPERATION switch?
Yes
Turn OFF the
power supply.
Be sure to check both resistances.
Replace the vane
motor.
Yes
Is winding
resistance of
vane motor 0 "?
Is winding
resistance of
fan motor 0 "?
Yes
Replace the fan
motor.
No
No
No
Turn OFF the
power supply.
Be sure to check both fuse
and varistor in any case.
Replace the fuse.
Yes
Is fuse(F11) blown?
Is varistor(NR11) burnt?
Yes
Replace the varistor.
No
Replace the indoor
electronic control
P.C. board.
No
18
Compressor and / or outdoor fan motor doesn’t operate.
Yes
Is there 220-240V AC
between 1–2 on the outdoor
terminal block (TB2)?
Compressor
doesn't operate.
Operate the unit in COOL mode by pressing the
EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Outdoor fan motor
doesn't operate.
Check the power supply, and
rectify the connecting wire.
Check the indoor electronic
control P.C. board, and rectify
the indoor and outdoor
connecting wire.
Start
No
No
Yes
Is there 220-240V AC between L–N
on the outdoor terminal block (TB1)?
Is the switch SW2-2 on the
indoor electronic control
P.C. board set to MU type?
No
Change the switch SW-2-2
on the indoor electronic control
P.C. board to MU type.
Yes
Is there 220-240V AC between L–N
on the outdoor terminal block (TB1)?
Is there 12V DC between
1–2 on the outdoor
terminal block (TB2)?
No
Check the indoor electronic
control P.C. board, and rectify
the indoor and outdoor
connecting wire.
Yes
Is there 220-240V AC between COM
on the compressor contactor (52C) and
N on the outdoor terminal block (TB1)?
Yes
Check the compressor and
compressor contactor, and
rectify the connecting wire.
Replace the compressor
contactor (52C).
No
Yes
Is there 220-240V AC between COM
on the compressor contactor (52C) and
N on the outdoor terminal block(TB1)?
Yes
Check the outdoor fan motor
and outdoor fan capacitor,
and rectify the connecting wire.
No
Check the power supply, and
rectify the connecting wire.
Replace the compressor
contactor (52C).
No
E1
E2
E3
MU-07/09/12RV- , ,
Is fuse "F" (2A) blown?
No
Replace the fuse "F" (2A).
Yes
D
Check of outdoor unit
<MU-07/09/12RV>
19
Compressor and / or outdoor fan motor doesn’t operate.
Yes
Compressor
doesn't operate.
Yes
Yes
Is there 220-240V AC between
3 on the compressor contactor
(52C) and N on the outdoor
terminal block (TB1)?
Operate the unit in COOL or HEAT mode by pressing the
EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Outdoor fan motor
doesn't operate.
No
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor
capacitor, and rectify the connecting wire.
Start
Yes
Is there 220-240V AC between 4
on the compressor contactor (52C) and
TAB20 on the deicer P.C. board?
Is there 220-240V AC between L–N
on the outdoor terminal block (TB1)?
Replace the
deicer P.C. board.
Replace the
deicer P.C. board.
No
No
Yes
Yes
No
Check the outdoor fan motor
and rectify the connecting
wire.
Is there 220-240V AC between 4 on
the compressor contactor (52C) and
TAB 20 on the deicer P.C. board?
Replace the
deicer P.C. board.
No
Yes
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Is there 220-240V AC between L–N
on the outdoor terminal block (TB1)?
No
No
Is the switch SW2-2 on the
indoor electronic control
P.C. board set to MUH type?
No
Change the switch SW-2-2
on the indoor electronic control
P.C. board to MUH type.
Yes
+
–
Is there 5V DC between J8 –J9
(MUH-07/09/12RV- , , )/
J205 –J101 (MUH-07/09/12RV- )
on the deicer P.C. board?
+
–
E1
E2
E3
E4
+
–
Is there 5V DC between J8 –J9
(MUH-07/09/12RV- , , )/
J205 –J101 (MUH-07/09/12RV- )
on the deicer P.C. board?
+
–
E1
E2
E3
E4
D
Check of outdoor unit
<MUH-07/09/12RV>
20
E
How to check mis-wiring and serial signal error
Outdoor unit does not work.
Start
Turn OFF the power supply(indoor/outdoor unit).
w 1 Set the switch(SW2-2) on indoor electronic control P.C. board to
MU or MUX type, when the outdoor unit is MU or MUX type.
If the setting is MUH or MXZ type, the unit does not work.
w 2 Short circuit of JPG and JPS on the indoor electronic control
P.C. board enables self -check to be displayed in 3 seconds.
Is the outdoor unit "MUH or MXZ" type?
Yes
•Turn ON the power supply(indoor/outdoor unit).
•Press once EMERGENCY OPERATION switch.
3 min. later, what self-check result is
displayed on OPERATION INDICATOR
lamp on indoor unit?
w 2
Mis-wiring is indicated.
No
Serial signal error is indicated.
(0.5-sec. ON, 2.5-sec. OFF)
Set the switch(SW2-2) on the indoor electronic
control P.C. board to MU or MUX type.
Does the unit operate?
Refer to the
"Instruction of
troubleshooting."
(0.5-sec. ON, 0.5-sec. OFF)
Make them sure.
Yes
Is this mis-wiring, poor contact,
or disconnection of wire?
No
1. Turn OFF the power supply(indoor/outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.
2. Short-circuit between indoor terminal block N and 3.
3. Turn ON the power supply(indoor unit) and press once EMERGENCY OPERATION switch.
Is there 20V DC between both ends of
R132 on indoor electronic control P.C.
board ?
( By tester, the stylus is between 0 ~ 20V. )
Yes
•Turn OFF the power supply(indoor unit).
•Connect ON indoor and outdoor connecting wire.
Turn ON the power supply(outdoor unit).
No
Replace the indoor electronic
control P.C. board.
No
Yes
w1
Ok
Is the outdoor unit "MUH" type?
Yes
Is there 220-240V AC between outdoor
terminal block L-N (TB1)?
Is there 5V DC between J8 - –J9 + (MUH-07/09/12RV- , , )/
J205 + –J101 - (MUH-07/09/12RV- ) on the deicer P.C. board?
Turn ON the power supply(indoor unit).
During EMERGENCY OPERATION,
is there 10V DC between both ends
of R601?
(By tester, the stylus is between 5 ~10V)
Replace the deicer P.C. board.
Yes
E4
Yes
Yes
No
No
E2
E1
E3
No
Refer to T Check of mis-wiring
or mis-piping.
Check the outdoor power supply,
power supply cord and
connection.
No
Replace the deicer P.C. board.
Make the wiring between CN730
on the deicer P.C. board and
outdoor terminal block correct.
21
Compressor and / or outdoor fan motor doesn’t stop.
V
Check of outdoor unit
Start
Turn OFF the power supply.
After 1 minute, turn ON
power supply again.
Does compressor or
outdoor fan motor stop?
Yes
Ok
No
<MU-07/09/12RV>
Is there 12V DC between
1–2 on the outdoor
terminal block (TB2)?
Yes
Replace the indoor
electoronic control
P.C. board.
Compressor and / or outdoor fan motor doesn’t stop.
V
Check of outdoor unit
Start
Turn OFF the power supply.
After 1 minute, turn ON
power supply again.
<MUH-07/09/12RV>
Is there 220-240V AC between COM on
No
the compressor contactor (52C) and N on
the outdoor terminal block (TB1)?
Rectify the connecting wire.
No
Yes
Replace the compressor
contactor(52C).
Does compressor stop?
Yes
Ok
Does outdoor fan motor stop?
Yes
Ok
Is there 220-240V AC between 3 on
No
the compressor contactor (52C) and N on
the outdoor terminal block (TB1)?
Yes
Replace the
deicer P.C. board.
No
Replace the
deicer P.C. board.
No
Rectify the connecting wire.
22
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.
W
Check of outdoor thermistor
Start
Defrost thermistor (RT61)
Measure
Turn OFF the
power supply.
resistance
between CN 661
1 and 2.
<MUH-07/09/12RV>
Does the resistance
of thermistor have
the characteristics ?
No
Replace the
thermistor.
Re-connect CN661.
Turn ON the power
Yes
supply and press
the EMERGENCY
OPERATION
switch.
Replace the deicer P.C.
Does the unit operate
10 minutes or more?
❈ Defective contact of the connector is considered.
Unit operates COOL mode even if it is set to HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Check of R.V. coil
X
<MUH-07/09/12RV>
Turn ON the power supply and operate
the indoor unit in HEAT mode by pressing
the EMERGENCY OPERATION switch.
board.
No
Yes
Ok ❈
After 3 minutes, does the unit
operate in COOL mode?
Yes
Is there 220-240V AC
between CN7211 – 2 on the
deicer P.C. board?
Yes
Replace the R.V. coil.
No
Ok
No
Replace the
deicer P.C. board
23
After 3 minutes, does the unit
operate in HEAT mode?
Ok
No
Is there 220-240V AC
between CN7211 – 2 on the
deicer P.C. board?
Replace the
deicer P.C. board.
Yes
Yes
Yes
No
Replace the R.V. coil.
Turn ON the power supply and operate
the indoor unit in COOL mode by pressing
the EMERGENCY OPERATION switch.
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Check of R.V. coil
X
<MUH-07/09/12RV>
24
TEST POINT DIAGRAM AND VOLTAGE
MSC-07RV MSC-09RV MSC-12RV -
E4
E4
E4
Indoor electronic control P.C. board
Power supply input
220-240V AC
}
CN201
Fuse(F11) 250V AC 3.15A
Fan motor power supply
}
Varistor (NR11)
CN111
Room temperature
thermistor (RT11)
CN112
Indoor coil
thermistor (RT12)
12V
DC
5V
DC
}
+
}
JPGND
J205
+
CN302
R132
CN121
Timer short mode point
(JPS, JPG)
Emergency operation switch
Vane motor power supply
(CN151)
SW2 (Refer to page 121 of
OB227 REVISED EDITION-B.)
1 sets the Auto restart function
ON/ OFF.
2 switches over MU and MUX
type/ MUH and MXZ type.
P.C.board
0~20V DC
Resistance(k")
25
MUH-07RV MUH-09RV MUH-12RV -
E4
E4
E4
Outdoor deicer P.C. board
CN711
Outdoor fan motor
220-240V AC
}
CN721
R.V. coil
220-240V AC
}
5V DC
J205
J101
Power supply input
220-240V AC
}
NR61
Varistor
F61
Fuse
2A/250V
R601
+
5~10VDC
}
--
Defrost interval
time short pin
(JPDS, JPSG)
(Refer to page 5.)
SLEEVE BEARING
DRAIN HOSE
NOZZLE (WH)
VANE UPPER (WH)
VANE LOWER (WH)
FUSE
VARISTOR
VANE MOTOR SUPPORT SET
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
VANE MOTOR
VANE MOTOR
ROOM TEMPERATURE THERMISTOR
INDOOR FAN MOTOR
INDOOR FAN MOTOR
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR RUBBER MOUNT
FAN MOTOR RUBBER MOUNT
INDOOR COIL THERMISTOR
LINE FLOW FAN
BEARING MOUNT
3.15A
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
AUTO RESTART
Part number that is circled is not shown in the illustration.
Symbol
No.
E02 336 630
1
E02 336 232
2
E02 336 521
3
E02 437 900
E02 589 900
E02 438 900
4
E02 408 900
E02 141 900
E02 594 900
E02 336 506
5
E02 075 506
E02 339 290
6
E02 340 290
E02 339 661
7
E02 340 661
E02 339 662
8
E02 336 245
9
E02 339 233
10
E02 440 233
E02 336 515
11
E02 336 297
12
E02 339 936
13
E02 412 936
Part No.
Part name
OUTDOOR HEAT EXCHANGER
CABINET
GRILLE(OUT)
COMPRESSOR
COMPRESSOR
COMPRESSOR
COMPRESSOR
COMPRESSOR
COMPRESSOR
COMPRESSOR RUBBER SET
COMPRESSOR RUBBER SET
BASE
BASE
STOP VALVE(GAS)
STOP VALVE(GAS)
STOP VALVE(LIQUID)
SERVICE PANEL
BACK PANEL
BACK PANEL
MOTOR SUPPORT
TOP PANEL
CAPILLARY TUBE
CAPILLARY TUBE
PROPELLER FAN
PROPELLER FAN
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
OUTDOOR FAN CAPACITOR
OUTDOOR FAN CAPACITOR
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR
FUSE
SURGE ABSORBER
RA6V23RA6V23RA6V33RA6V33-
1.5+ /440V AC
1.5+ /440V AC
2.0+ /440V AC
25+ /440V AC
25+ /440V AC
30+ /440V AC
30+ /440V AC
3P
3P
2P
PROPELLER FAN
PROPELLER FAN
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
DEICER P.C. BOARD
DEICER P.C. BOARD
DEICER P.C. BOARD
SURGE ABSORBER
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
DEFROST THERMISTOR
DEFROST THERMISTOR
DEFROST THERMISTOR
DEFROST THERMISTOR
R. V. COIL
FUSE
VARISTOR
RA6V23RA6V23RA6V33RA6V3325+ /440V AC
25+ /440V AC
30+ /440V AC
30+ /440V AC
3P
3P
2P
2P
250V 2A
MF
MF
MF
MF
C1
C1
C1
C1
DSAR
TB1
TB1
TB2
TB2
RT61
RT61
RT61
RT61
21S4
F61
NR61
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
E02 430 426
E02 440 704
E02 444 704
E02 440 705
12
13
14
REMOTE CONTROLLER
DRAIN SOCKET
DRAIN SOCKET
DRAIN CAP
CABINET
OUTER NOZZLE
SERVICE PANEL
OVERCURRENT RELAY
COMPRESSOR
CAPILLARY TUBE
([3.0X[1.6X1400)
BASE
CAPILLARY TUBE
([3.0X[1.4X1100)
STOP VALVE(GAS)
STOP VALVE(LIQUID)
STOP VALVE(GAS)
STOP VALVE(LIQUID)
UNION(3/8)
UNION(1/4)
SOLENOID VALVE
SOLENOID VALVE
SOLENOID COIL
SOLENOID COIL(B)
SOLENOID COIL(C)
BACK PANEL
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR RELAY
COMPRESSOR CONTACTOR
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
MOTOR SUPPORT
OUTDOOR FAN MOTOR
PROPELLER FAN
OUTDOOR HEAT EXCHANGER
SIDE PANEL
CAPILLARY TUBE
OUTER NOZZLE
SERVICE PANEL
MOTOR SUPPORT
CAPILLARY TUBE
([3.0O[1.6O1100)
SOLENOID VALVE (A,B)
COMPRESSOR (C,D)
PIPE B S. V
S. V HEADER B
STOP VALVE (GAS)
STOP VALVE (GAS)
BASE
COMPRESSOR (A,B)
STOP VALVE (LIQUID)
S. V HEADER A
PIPE A S. V
SOLENOID VALVE
REAR PANEL
REAR GUARD
TOP PANEL
OUTDOOR HEAT EXCHANGER
FRONT PANEL
SIDE PANEL
CAPILLARY TUBE
([3.0O[1.6O800)
Symbol
in Wiring
Diagram
MC2
MC1
When servicing, cut the tube to the proper length as shown in the REFRIGERANT SYSTEM DIAGRAM.
[3.0O[1.6O1000
RH-174VGH
[9.52
[12.7
RH-231VHA
[6.35
Including Capillary TUBE
([3.0O[1.8O260, [3.0O[1.6O400)
SIDE PANEL
HANDLE
FAN GUARD
FRONT PANEL
PROPELLER FAN
HANDLE
LABEL
SERVICE PANEL
COMPRESSOR
REAR PANEL
EXPANSION VALVE (COIL)
EXPANSION VALVE (COIL)
EXPANSION VALVE
BASE ASSEMBL Y
UNION (1/4F)
UNION (3/8F)
BALL VALVE (3/8)
HIGH PRESSURE SWITCH
REAR GUARD
4-WAY VALVE
ACCUMULATOR
MUFFLER
MOTOR SUPPORT
OUTDOOR HEAT EXCHANGER
OUTDOOR FAN MOTOR
TOP PANEL
CAPILLARY TUBE ([4.0✕[2.4✕2000)
CAPILLARY TUBE ([2.0✕[0.6✕1000)
Part numbers that are circled are not shown in the illustration.
12
11
10
9
8-20. ACCESSORY AND REMOTE CONTROLLER
39
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Mar. 2002. No.OB252 REVISED EDITION C 13
Distributed in Jan. 2002. No.OB252 REVISED EDITION B 273
Distributed in Mar. 2001. No.OB252 REVISED EDITION A 249
Distributed in Mar. 2000. No.OB252 543
Made in Japan
New publication, effective Mar. 2002
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.