RoHS compliant products have <G> mark on the spec name plate.
1
TECHNICAL CHANGES
MUH-GD80VB -
1. New model
2
PART NAMES AND FUNCTIONS
MUH-GD80VB
E1
Air inlet
(back and side)
ACCESSORIES
Drain socket
Drain cap 33
Drain cap 16
Air outlet
MUH-GD80VB
1
2
—
2
3
SPECIFICATION
Outdoor modelMUH-GD80VB
FunctionCoolingHeating
Power supply
Single phase
230 V, 50 Hz
CapacitykW8.09.4
Breaker capacityA25
Running current (Total)
Power input (Total)W3,3203,580
data
Power factor (Total)%98
Electrical
Starting current (Total)
Coeffi cient of performance (C.O.P) (Total)
A14.7615.90
A90
2.412.63
ModelNN37VAAHT
OutputW2,500
Compressor
Compressor motor current
A13.8514.62
ModelRA6V75-AD
Fan
Fan motor currentA0.57
motor
Dimensions W H
Dmm840 850 330
Weightkg77
Dehumidifi cation/h4.6
Air fl ow
(High/Low)
Sound level (High/Low)
Fan speed (High/Low)
Fan speed regulator2
Special
remarks
Refrigerant fi lling
capacity (R410A)
/h2,940/1,470
dB55/53
rpm805/435
kg2.40
-
Refrigeration oil (Model)NEO 22
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C
Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Indoor-Outdoor piping length: 5 m
4
MUH-GD80VB
Test conditions,
Cooling : Dry-bulb temperature 35 Wet-bulb temperature 24
Heating : Dry-bulb temperature 7 Wet-bulb temperature 6
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
NOISE CRITERIA CURVES
FAN SPEED
High
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
631252505001000 20004000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))LINE
55
OUTDOOR UNIT
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
3
5
OUTLINES AND DIMENSIONS
MUH-GD80VB
51
34
330
850
430
66
299
515
121
500
840
40
REQUIRED SPACE
100 mm or more
360
Open as a rule
80
500 mm or more if the back,
both sides and top are open
155
90
198
Open as a rule
500 mm or more if
the front and both
sides are open
100 mm or more
200 mm or more if
there are obstacles
to both sides
The standard specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the
operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °CWB
(2) Indoor outlet air wet-bulb temperature: °CWB
(3) Outdoor intake air dry-bulb temperature: °CDB
(4) Total input: W
(5) Indoor intake air dry-bulb temperature: °CDB
(6) Outdoor intake air wet-bulb temperature: °CWB
(7) Total input: W
Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating
INDOOR UNIT
Wet and dry-bulb
thermometers
19.2
17.4
15.6
13.9
12.4
10.8
Indoor air Wet-bulb temperature
OUTDOOR UNIT
Wet and dry-bulb
thermometers
Indoor intake air Wet-bulb temperature (°C)
Indoor intake air Wet-bulb temperature (°C)
Outdoor intake air Dry-bulb temperature (°C)Outdoor intake air Dry-bulb temperature (°C)
MUH-GD80VB
6
38.4
35.5
32.5
29.6
26.6
23.6
20.7
17.7
Indoor air Dry-bulb temperature
Indoor intake air Dry-bulb temperature (°C)
Indoor intake air Dry-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
NOTE: The above curves are for the heating operation without any frost.
MUH-GD80VB
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20
25
30
Air flow should be set at MAX.
The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1(MPa [Gauge]) = 10.2 (kgf/ [Gauge])
(kgf/ [Gauge])(MPa[Gauge])
11
11
10
10
9
9
8
8
7
7
Outdoor low pressure
6
5
6
5
18
1520
Ambient temperature (˚C)
Ambient humidity (%)
Relative humidity(%)
50
60
70
MUH-GD80VB
50
25
60
3035
70 (%)
230 V
32
MUH-GD80VB
16
15
14
13
12
Outdoor unit current(A)
11
10
18
1520
50
Ambient temperature (˚C)
Ambient humidity (%)
25
60
230 V
3035
32
70 (%)
HEAT operation
Condition indoor: Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
Outdoor: Dry bulb temperature 7,15, 20°C
Wet bulb temperature 6,12, 14.5°C
NOTE Q :Total capacity (kW) INPUT :Total power input (W) DB: Dry-bulb temperature
-10-505101520
QINPUTQINPUTQINPUTQINPUTQINPUTQINPUTQINPUT
9
ACTUATOR CONTROL
MUH-GD80VB
9-1. R.V. COIL CONTROL
10
10
SERVICE FUNCTIONS
MUH-GD80VB
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JPG1 and R871 on the outdoor deicer P.C. board, defrosting mode can be accomplished
regardless of the defrost interval restriction. (Refer to 11-4.)
Defrost thermistor RT61 must read below -3°C.
10-2. CHANGE IN DEFROST SETTING
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed.
<JRG> When the JRG wire of the deicer P.C. board is cut, the defrost temperature will be changed.
(Refer to 11-4.)
ModelChange point
MUH-GD80VB
11
TROUBLESHOOTING
Jumper wire
JRF
JRG
Defrost interval time changes from 40 minutes to 15 minutes.
Defrost start temperature does not change.(-3.0 )
Defrost finish temperature changes from 13 to 15 .
MUH-GD80VB
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after con-
firming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the com-
ponents.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing ON and OFF before starting serv-
ice work.
(2) Before servicing check that the connector and terminal are connected properly.
(3) If the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the compo-
nents for bursting and discoloration.
11
Housing point
11-2. TROUBLE CRITERION OF MAIN PARTS
MUH-GD80VB
Part nameFigureCheck method and criterion
Measure the resistance with a tester.
Defrost thermistor
(RT61)
Discharge temperature
thermistor (RT62)
Ambient temperature
thermistor (RT63)
Compressor (MC)
INNER
PROTECTOR
160± 5°C OPEN
90±10°C CLOSE
(Part temperature –10°C ~ 40°C)
Refer to 11-4. "Test point diagram and voltage", "Outdoor deicer P.C. board",
the chart of thermistor.
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0°C ~ 40°C)
Refer to 11-4. "Test point diagram and voltage", "Outdoor deicer P.C. board",
the chart of thermistor.
Measure the resistance with a tester.
(Part temperature –10°C ~ 40°C)
Refer to 11-4. "Test point diagram and voltage", "Outdoor deicer P.C. board",
the chart of thermistor.
Measure the resistance between the terminals with a tester.
(Part temperature –10°C ~ 40°C)
Terminal
C – R
C – S
Normal
0.56 Ω ~ 0.71 Ω
1.43 Ω ~ 1.76 Ω
S
WHT
AUX.
RED
P
C
~
MAIN
R
BLK
Outdoor fan motor (MF)
INNER
PROTECTOR
135± 5°C OPEN
( 83±15°C CLOSE )
R.V. coil (21S4)
LEV (Expansion valve)
Reference value
Measure the resistance between the terminals with a tester.
(Part temperature –10°C ~ 40°C)
Color of
lead wire
WHT – BLK
BLK – YLW
YLW – RED
Normal
55 Ω ~ 68 Ω
49 Ω ~ 61 Ω
22 Ω ~ 29 Ω
Measure the resistance between the terminals with a tester.
(Part temperature –10°C ~ 40°C)
Normal
2.673 kΩ ~ 3.268 kΩ
Measure the resistance with a tester.
(Part temperature : –10°C ~ 40°C)
Color of lead wire
Normal
WHT – RED
RED – ORN
YLW – BRN
41.0 Ω ~ 49.0 Ω
BRN – BLU
MAIN
AUX.1AUX.2
C
REDORN WHT
BLK
YLW
LEV
P
: INNER PROTECTOR
P
12
11-3. TROUBLESHOOTING FLOW
Compressor and/or outdoor fan motor doesn’t operate.
Check of outdoor unit
Turn ON the power supply.
Is there 230 V AC to
between on the
outdoor terminal block
Yes
No
Check the outdoor power supply
?
Compressor
does not operate.
Is there 5 V DC between
J101 - J401 on the deicer
+
P.C. board?
Operate the unit in
COOL or HEAT mode by
pressing the EMERGENCY
OPERATION switch.
3 minutes after the power
supply turns ON, is there
230 V AC between A1-A2 on
the compressor contactor
(52C)?
Is there 230 V AC between
2/T1 on the compressor
contactor (52C) and on the
outdoor terminal block?
Check the compressor.
Refer to 11-2.
and connection of wiring.
Yes
Yes
Yes
No
Replace the
deicer P.C. board.
No
No
Replace the
deicer P.C. board.
Replace the compressor
contactor (52C).
Yes
Yes
No
Rectify the connecting
wire.
No
Rectify the connecting
wire.
Outdoor fan motor
does not operate.
Is there 5 V DC between
J101 - J401 on the deicer
+
P.C. board?
Yes
Operate the unit in
COOL or HEAT mode by
pressing the EMERGENCY
OPERATION switch.
Yes
Check the outdoor fan
motor. Refer to 11-2.
No
No
Yes
Replace the
deicer P.C. board.
Replace the
deicer P.C. board.
No
Rectify the connecting
wire.
13
Compressor and/or outdoor fan motor doesn’t stop.
Check of outdoor unit
Turn OFF the power supply.
After 30 seconds, turn ON the power supply again.
Operate the unit in COOL or HEAT mode by
pressing the EMERGENCY OPERATION switch.
Operate the unit for 1 minute or more and stop it by
pressing the EMERGENCY OPERATION switch again.
After 30 seconds,
does compressor stop?
After 30 seconds, does
outdoor fan motor stop?
Check of R.V. coil
C
Ok
Ok
Yes
Yes
Is there 230 V AC between
No
A1-A2 on the compressor
contactor (52C)?
Replace the
deicer P.C. board.
No
Replace the
deicer P.C. board.
Yes
Is there 230 V AC between
No
2/T1 on the compressor
contactor (52C) and on the
outdoor terminal block?
Replace the
compressor contactor (52C).
Yes
Unit operates HEAT mode even if it is set to COOL mode.
First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board.
Turn ON the power supply and operate the indoor unit in COOL mode
by pressing the EMERGENCY OPERATION switch.
After 3 minutes, does the unit
operate in HEAT mode?
Yes
Is there 230 V AC between
CN721 – on the deicer
P.C. board?
Yes
Replace the
deicer P.C. board.
No
Ok
No
Replace the R.V. coil.
No
Rectify the connecting
wire.
Unit operates COOL mode even if it is set to HEAT mode.
First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board.
Turn ON the power supply and operate the indoor unit in HEAT mode
by pressing the EMERGENCY OPERATION switch.
After 3 minutes, does the unit
operate in COOL mode?
Yes
Is there 230 V AC between
CN721 – on the deicer
P.C. board?
Yes
Replace the R.V. coil.
No
No
OK
Replace the
deicer P.C. board
14
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit doesn’t operate.
How to check mis-wiring
D
• Turn ON the power supply. (indoor/outdoor unit)
• Press EMERGENCY OPERATION switch once.
After 3 minutes, mis-wiring is indicated
(0.5-second ON, 0.5-second OFF)
on OPERATION INDICATOR
lamp on indoor unit.
Correct them.
1. Turn OFF the power supply (indoor/outdoor unit) and disconnect indoor/outdoor
connecting wire on indoor side.
2. Short-circuit terminal block - by lead wire.
Turn ON the power supply (indoor unit) and press EMERGENCY OPERATION switch once.
3.
Yes
Is this mis-wiring, poor contact,
or wire disconnection?
Is there 20 V DC between both ends of
R132 on the indoor electronic control P.C.
board ?
( By tester, the stylus is between 0 ~ 20 V. )
• Turn OFF the power supply. (indoor unit)
• Connect indoor/outdoor connecting
wire.
Start
No
Yes
Short circuit of JPG and JPS on the indoor electronic control
P.C. board enables self -check to be displayed in 3 seconds.
No
Replace the indoor electronic
control P.C. board.
Turn ON the power supply. (outdoor unit)
Is there 230 V AC between on the outdoor terminal block?
Yes
Is there 5 V DC between J101 + -J401 - on the deicer P.C.
board?(Refer to 11-4.)
Yes
During EMERGENCY OPERATION, is there
10 V DC between both ends of R601 on the
deicer P.C. board? (Refer to 11-4.)
(By tester, the stylus is between 5 ~10 V.)
Yes
Replace the deicer P.C. board.
No
No
Check the outdoor power supply
and connection of wiring.
No
Replace the deicer P.C. board.
Make the wiring between CN730
on the deicer P.C. board and
outdoor terminal block correct.
(Refer to 11-4.)
Refer to indoor unit
service manual.
15
When OPERATION INDICATOR lamp flashes 10-time.
Heating/Cooling doesn't operate.
Check of LEV (Expansion valve)
E
Turn ON the power supply.
During pressing both the OPERATION SELECT
button and the TOO COOL button on the
remote controller at the same time,
press the RESET button.
First, release the RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
With remote controller set toward the indoor unit, press
OPERATE/STOP (ON/OFF) button and confirm one
beep tone.
LEV operates in full-opening
direction.
CLOCK
°C
AMPM
AMPM
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it?
No
Is LEV properly fixed to
the expansion valve?
Yes
Does the resistance of LEV have
the characteristics on 11-2?
No
Replace the
LEV.
Yes
No
Yes
OK
Properly fix the LEV to the
expansion valve.
Replace the
deicer P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON again.
2. Press the RESET button on the remote controller.
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.
F
Check of outdoor thermistor
Disconnect the connectors CN661 and/or CN662 from the deicer P.C. board.
(Check the characteristics of each thermistor.)
Defrost thermistor(RT61)
Measure
resistance
between CN661
and .
Turn OFF the
power supply.
Discharge temperature
thermistor(RT62)
Measure
resistance
between CN662
and .
Ambient temperature
thermistor(RT63)
Measure
resistance
between CN662
and .
Does the resistance
of thermistor have the
characteristics
on 11-4?
No
Replace the
thermistor.
16
Connect CN661 and
CN662.
Turn ON the power
Yes
supply and press
the EMERGENCY
OPERATION
switch.
Replace the deicer P.C.
board.
No
Does the unit operate
10 minutes or more?
Yes
OK .
It probably had contact failure of the connectors.
11-4. TEST POINT DIAGRAM AND VOLTAGE
MUH-GD80VB
Outdoor deicer P.C. board
Defrost thermistor (RT61)
Ambient temperature thermistor (RT63)
100
90
80
70
60
50
Resistance (kΩ)
40
30
20
10
0
-20 -10 010 20 30 40
Temperature (°C)
Discharge temperature thermistor (RT62)
900
800
700
600
500
400
300
Resistance (kΩ)
200
100
0
0 102030405060708090100110120
Temperature (°C)
Defrost
interval
time short
pin(JPG1,
R871)
(Refer to
10-1.)
J101
5 V
DC
J401
(Refer to
11-3. or
11-3. .)
CN661 Defrost thermistor (RT61)
(Refer to
11-3. )
+
}
CN662 Discharge temperature thermistor
(RT62)
(Refer to 11-3. )
CN662 Ambient temperature
thermistor (RT63)
(Refer to 11-3.
)
LEV
connector
(CN724)
Fan motor
connector
(CN711)
Varistor
(NR62)
R.V. coil
}
(CN721)
+
12 V DC
}
Fuse
T3.15AL250V
Varistor
(NR61)
CN730 -
}
230 V AC
(Refer to
11-3.
11-3.
or
.)
Jumper wire for
change in defrost
setting (JRF, JRG)
(Refer to 10-2.)
17
+
}
R601 10 V DC
(Refer to 11-3. .)
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Locking lever
MUH-GD80VB
OPERATING PROCEDURE
1.Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Remove the screws of the cabinet.
(8) Remove the cabinet.
(9) Remove the screws of the back panel.
(10)
Remove the back panel.
Slide the sleeve.
Pull the terminal while
pushing the locking
lever.
(2) The terminal with this connector has the
locking mechanism.
Hold the sleeve, and
pull out the terminal
slowly.
Connector
PHOTOS
Photo 1
Screws
of the
cabinet
Screw of the top panel
Photo 3
Screws
of the
back
panel
Screw of the motor support
Screws of the back panel
Screws of the cabinet
Photo 2
Screw of the service panel
Screws
of the
top
panel
Screws
of the
cabinet
Screw
of the
valve
cover
18
OPERATING PROCEDURE
PHOTOS
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller nut and the propeller.
NOTE: Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the
propeller and the motor shaft cut section.
Set the propeller fan in position by using the cut on
the shaft and the mark on the propeller.
(3) Remove the clamp of outdoor fan motor lead wire and
disconnect the outdoor fan motor connector.
(4) Remove the screws fixing the outdoor fan motor.
(5) Remove the outdoor fan motor.
Photo 4
Screws
of the
relay
panel
Photo 5
Propeller
nut
Propeller
Deicer P.C. board
Screws of the
relay panel
Screws of the outdoor fan motor
Terminal
blocks
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the compressor.
(6) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge shows
0 kg/cm
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
(10)
2
(0 MPa).
Remove the compressor.
Screws of the outdoor fan motor
Photo 6
Discharge pipe
Suction
pipe
Terminal cover
Compressor nuts
19
HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Apr. 2008. No.OBH514 6
Made in Japan
New publication, effective Apr. 2008
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.