Mitsubishi MUH09NW, MSH12NN, MUH12NN, MUH15NN, MUH17NN Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
L
I
S
T
E
D
R
SERVICE MANUAL
Wireless type Models
No. OB198
MSH09NW MSH12NN MSH15NN MSH17NN
MSH12NN MSH15NN MSH17NN INDOOR UNIT
(WH)
(WH)
(WH)
(WH)
Remote controller
· MUH09NW
· MUH12NN
· MUH15NN
· MUH17NN
CONTENTS
1. FEATURES·························································3
2. TECHNICAL CHANGE·······································4
3. PART NAMES AND FUNCTIONS······················4
4. SPECIFICATIONS ··············································6
5. DATA·································································10
6. OUTLINES AND DIMENSIONS·······················23
8. REFRIGERANT SYSTEM DIAGRAM··············28
9. MICROPROCESSOR CONTROL ····················30
10. SERVICE FUNCTIONS·····································41
11. TROUBLESHOOTING ······································43
12. DISASSEMBLY INSTRUCTIONS·····················55
13. PARTS LIST······················································65
14. OPTIONAL PARTS···········································74
MUH12NN MUH15NN OUTDOOR UNIT
The Slim Line. From Mitsubishi Electric.
1
SWING
1013/16
FEATURES
LCD wireless
MSH12NN, MSH15NN MUH12NN, MUH15NN
remote controller
Models Cooling capacity Heating Capacity SEER HSPF
MSH09NW 8,800Btu/h 10,500Btu/h 10.0 6.8 MSH12NN 12,900Btu/h 13,500Btu/h 10.2 6.8 MSH15NN 14,600Btu/h 14,800Btu/h 10.7 6.8 MSH17NN 16,200tu/h 17,200tu/h 10.3 6.8
NEW “I FEEL CONTROL” IN OUR LCD WIRELESS REMOTE CONTROLLER WITH ON/OFF PROGRAM TIMER
Mitsubishi Electric’s new wireless remote controller incorporates a number of advanced features that provide even greater con-
trol and ease-to- use. It has a liquid crystal display which indicates such infomation as mode, fan speed and temperature selected as well as the programmed ON/OFF time. It is also equipped with “I Feel Control”, a unique Mitsubishi Electric feature that allows the user to adjust the temperature to exactly the level he or she wants simply by tapping the button that describes present conditions : “Too Cool” or “Too Warm”. The optimum temperature set this way is then memorized for immediate recall whenever the air conditioner is used again. And what’s more, the new controller has been made more better design and easier to handle than even before.
Select desired air flow direction. REMOTE-CONTROL OPERATION MODE
Using the remote controller, you can select from five airflow set-
tings to match room layout and the location of people. Also, you can set the vane to swing automatically.
Small in size, big on cooling. COMPACT INDOOR UNIT
The sleek design of the NW/NN Series matches virtually any room
layout. For instance, MSH09NW is 10 (HWD), which used to be 143/
16
311/8✕ 53/8.
16
/
321/16✕ 73/
16
13
AUTO-RESTART FUNCTION
The auto-restart function restarts the equipment when power is
restored following an outage automatically. Operation resumes in the mode in which the equipment was running immediately before the outage.
HIGH PERFORMANCE ROTARY COMPRESSOR
The advanced design of Mitsubishi Electric’s powerful and energy-
efficient rotary compressor results in lower operating costs and longer service life.
MSH09NW
3
2
TECHNICAL CHANGES
MSH09EW MSH09NW
1. Indoor unit has changed. (Outline dimension changes. 31-1/8”o5-3/8”o14-3/16”(WoDoH)32-1/16”o7-3/16”o10-13/16”(WoDoH))
2. Outdoor unit has changed. (Capillary tube and refrigerant had changed.)
3. Remote controller has changed. (The timer function was changed to the clock timer function.)
4. Indoor auto vane has been adopted.
MSH12EN, MSH15EN MSH12NN, MSH15NN
1. Indoor unit has changed. (Outline dimension changes. 39-3/8”o7”o14-3/16”(WoDoH)39-15/16”o7-1/2”o12-5/8”(WoDoH))
2. Outdoor unit has changed. (Outline dimension changes. 33-1/2”o11-7/16”o23-7/8”(WoDoH)33-7/16”o11-7/16”o23-13/16”(WoDoH)) (Capillary tube, refrigerant and pipe had changed.)
3. Remote controller has changed. (The timer function was changed to the clock timer function.)
4. The swing mode was addedd to indoor auto vane.
MSH17NN
1. New Model
3
PART NAMES AND FUNCTIONS
MSH09NW, MSH12NN, MSH15NN, MSH17NN
REMOTE CONTROLLER
4
INDOOR UNIT
MSH09NW
(When the front panel is opened)
MSH09NW
MSH12NN MSH15NN MSH17NN
MSH09NW
MSH12NN, MSH15NN,MSH17NN
OUTDOOR UNIT
MUH09NW
MSH12NN, MSH15NN,MSH17NN
MUH12NN
MUH17NN
MUH15NN
5
4
ITEM MODELS MSH09NW
Capacity
Power consumption
EER [SEER] HSPF COP INDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. ampacity Fan motor Auxiliary heater
Airflow Lo—Me—Hi Moisture removal
Sound level Lo-Me-Hi Cond. drain connection O.D.
Dimensions Weight
OUTDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. ampacity Fan motor
Compressor
Refrigerant control Defrost method
Dimensions Weight
REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING
Pipe size Connection method
Between the indoor & outdoor units
47 [17˚]
Dry Wet
W D H
Model Winding resistance (at 68˚F) ½
W D H
Liquid Gas Indoor Outdoor Height difference Piping length
Btu/h Btu/h Btu/h
W W
V, phase, Hz
A A
F.L.A
A(kW)
CFM CFM
Pints/h
dB(A)
in. in. in. in.
lbs.
V, phase, Hz
A A
F.L.A
R.L.A L.R.A
in. in. in.
lbs.
in. in.
ft ft
8,800
10,500
5,300
890 890 820
9.9 [10.0]
6.8
3.5
MSH09NW
White
115, 1, 60
15
0.5
0.37 –
208-265-328 177-226-279
2.3
31-37-42
5/8
32-1/16
7-3/16
10-13/16
18
MUH09NW
Munsell 5Y 7/1
115, 1, 60
20 16
0.7
RH-140WGJT
C-R 0.83 C-S 1.48
12 42
Capillary tube
Reverse cycle
30-11/16
10-1/16
21-1/4
80
Wireless type
12V DC (peak voltage)
Not supplied (optional parts)
1/4
3/8 Flared Flared
Max. 25 Max. 49
1
1
12
1
1
12
2
Cooling Heating 47 Heating 17 Cooling Heating 47 Heating 17
Cooling Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
90˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
SPECIFICATIONS
Notes 1 : Rating conditions (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, 75˚FWB
2 : Rating conditions (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
Operating Range
6
ITEM MODELS MSH12NN MSH15NN
1
1
12
1
12
2
Capacity
Power consumption
1
EER [SEER] HSPF
Cooling Heating 47 Heating 17 Cooling Heating 47 Heating 17
47 [17˚] COP INDOOR UNIT MODEL External finish Power supply
V, phase, Hz Max. fuse size (time delay) Min. ampacity Fan motor Auxiliary heater
Airflow Lo—Me—Hi
Dry
Wet Moisture removal Sound level Lo-Me-Hi Cond. drain connection O.D.
W Dimensions
D
H Weight OUTDOOR UNIT MODEL External finish Power supply
V, phase, Hz Max. fuse size (time delay) Min. ampacity Fan motor
Model
Compressor
Winding resistance (at 68˚F) ½
Refrigerant control Defrost method
W
Dimensions
D
H Weight REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING
Pipe size Connection method
Between the indoor & outdoor units
Notes 1 : Rating conditions (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, 75˚FWB
2 : Rating conditions (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB3 : include auxiliary electric heater operation at 115V
Liquid
Gas
Indoor
Outdoor
Height difference
Piping length
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
Btu/h Btu/h Btu/h
W W
F.L.A
A(kW)
CFM CFM
Pints/h
dB(A)
in. in. in. in.
lbs.
F.L.A
R.L.A L.R.A
in. in. in.
lbs.
in. in.
12,600/12,900 13,000/13,500
6,800/7,000 1,280/1,310 1,180/1,250 1,110/1,140
9.8/9.8[10.2/10.2]
14,300/14,600 14,500/14,800
8,700/8,900 1,350/1,380 1,250/1,300 1,210/1,240
10.6/10.6 [10.7/10.7]
6.8/6.8
3.2/3.2
MSH12NN
3.4/3.3
MSH15NN
White
115, 1, 60 A A
15
0.6
0.43 –
360-395-452
311-339-388
3.3
293-321-367
4.7
36-39-42
5/8
39-15/16
7-1/2
12-5/8
31
MUH12NN
MUH15NN Munsell 5Y7/1 208/230, 1, 60
A A
15
20
14
0.52
RH-185NHDT
RH-207NHDT
C-R 1.68 C-S 2.78
10 35
Capillary tube
Reverse cycle
33-7/16 11-7/16
23-13/16
99
Wireless type
12V DC (peak voltage)
Not supplied (optional parts)
1/4
5/8 Flared Flared
ft ft
Max. 25 Max. 49
Operating Range
Indoor intake air temperature
Cooling Heating
Maximum
Minimum
Maximum
Minimum
90˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
7
ITEM MODELS MSH17NN
Capacity
Power consumption
EER [SEER] HSPF COP INDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. ampacity Fan motor Auxiliary heater
Airflow Lo—Me—Hi Moisture removal
Sound level Lo-Me-Hi Cond. drain connection O.D.
Dimensions Weight
OUTDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. ampacity Fan motor
Compressor
Refrigerant control Defrost method
Dimensions Weight
REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING
Pipe size Connection method
Between the indoor & outdoor units
47 [17˚]
Dry Wet
W D H
Model Winding resistance (at 68˚F) ½
W D H
Liquid Gas Indoor Outdoor Height difference Piping length
Btu/h Btu/h Btu/h
W W
V, phase, Hz
A A
F.L.A
A(kW)
CFM CFM
Pints/h
dB(A)
in. in. in. in.
lbs.
V, phase, Hz
A A
F.L.A
R.L.A L.R.A
in. in. in.
lbs.
in. in.
ft ft
16,000/16,200 16,800/17,200 10,100/10,300
1,560/1,580 1,500/1,570 1,410/1,510
10.3/10.3 (10.4/10.4)
6.8/6.8
3.3/3.2
MSH17NN
White
115, 1, 60
15
0.7
0.51 –
406-441-491 342-371-413
5.1
40-43-45
5/8
39-15/16
7-1/2
12-5/8
31
MUH17NN
Munsell 5Y 7/1
208/230, 1, 60
20 15
0.75
RH-231NHDT
C-R 1.65 C-S2.67
11 38
Capillary tube
Reverse cycle
34-1/4 11-5/8 33-1/2
128
Wireless type
12V DC (peak voltage)
Not supplied (optional parts)
1/4
5/8 Flared Flared
Max. 25 Max. 49
1
1
12
1
1
12
2
Cooling Heating 47 Heating 17 Cooling Heating 47 Heating 17
Cooling Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
90˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
Notes 1 : Rating conditions (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, 75˚FWB
2 : Rating conditions (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
Operating Range
8
Model
MSH09NW
MSH12NN MSH15NN MSH17NN
Additional piping
Max. length : ft
A
49
Gas
[ 3/8
[ 5/8
Piping size O.D. : in. Length of connecting pipe : in.
Liquid
[ 1/4
Indoor unit
16-15/16
Outdoor unit
0
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
9
5
MODEL
Refrigerant piping length (one way)
MSH09NW MSH12NN MSH15NN MSH17NN
1.0
1.0
1.0
1.0
25ft (std)
0.954
0.954
0.954
0.954
40ft
0.927
0.927
0.927
0.927
49ft
Models
Indoor air Outdoor intake air DB temperature(˚F
)
MSH09NW
71 67 63 71 67 63 71 67 63 71 67 63
TC
10.8
10.2
9.6
15.8
15.0
14.1
17.9
16.9
15.9
19.8
18.8
17.7
SHC
6.1
7.1
8.0
9.1
10.6
11.9
9.2
11.0
12.5
10.1
12.0
13.7
TPC
0.79
0.75
0.71
1.17
1.10
1.05
1.23
1.16
1.10
1.41
1.33
1.26
TC
10.1
9.5
8.9
14.8
13.9
13.0
16.7
15.8
14.7
18.5
17.5
16.4
SHC
5.7
6.7
7.4
8.5
9.9
11.0
8.6
10.2
11.6
9.4
11.2
12.7
TPC
0.87
0.82
0.79
1.28
1.21
1.16
1.35
1.28
1.22
1.54
1.46
1.40
TC
9.5
8.8
8.3
13.9
12.9
12.1
15.7
14.6
13.7
17.4
16.2
15.2
SHC
5.4
6.2
6.9
8.0
9.2
10.2
8.1
9.5
10.8
8.8
10.4
11.8
TPC
0.94
0.89
0.85
1.38
1.31
1.25
1.45
1.38
1.31
1.66
1.58
1.51
TC
8.8
8.2
7.5
12.9
12.0
11.0
14.6
13.6
12.5
16.2
15.1
13.9
SHC
5.0
5.7
6.3
7.4
8.5
9.3
7.5
8.8
9.8
8.2
9.6
10.7
TPC
0.98
0.94
0.91
1.45
1.39
1.34
1.53
1.46
1.41
1.75
1.68
1.61
TC
8.1
7.5
6.9
11.9
11.0
10.1
13.4
12.5
11.4
14.9
13.9
12.6
SHC
4.6
5.3
5.7
6.8
7.8
8.5
6.9
8.1
8.9
7.6
8.9
9.8
TPC
1.02
0.99
0.94
1.51
1.45
1.39
1.59
1.53
1.46
1.82
1.75
1.68
IWB
(˚F)
75 85 95 105 115
MSH12NN
MSH15NN
MSH17NN
Notes 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
3
Btu/h), SHC : Sensible Heat Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor intake air DB temperature.
Models
Models Outdoor intake air WB temperature(˚F
)
MSH09NW
75 70 65 75 70 65 75 70 65 75 70 65
TC
6.1
6.5
6.6
7.8
8.3
8.5
8.6
9.1
9.3
10.0
10.6
10.8
TPC
0.66
0.64
0.61
0.93
0.90
0.86
0.97
0.94
0.90
1.17
1.13
1.08
TC
7.6
7.9
8.2
9.8
10.1
10.6
10.7
11.1
11.6
12.5
12.9
13.5
TPC
0.78
0.76
0.73
1.09
1.07
1.03
1.14
1.11
1.07
1.37
1.34
1.30
TC
9.1
9.3
9.6
11.7
11.9
12.4
12.8
13.1
13.5
14.9
15.2
15.7
TPC
0.87
0.85
0.82
1.22
1.19
1.16
1.27
1.24
1.20
1.53
1.49
1.45
TC
10.2
10.5
10.8
13.2
13.5
13.9
14.4
14.8
15.2
16.8
17.2
17.7
TPC
0.91
0.89
0.87
1.28
1.25
1.22
1.33
1.30
1.27
1.61
1.57
1.53
TC
10.6
10.8
11.1
13.6
13.9
14.3
14.9
15.2
15.7
17.3
17.7
18.2
TPC
0.93
0.91
0.88
1.30
1.28
1.24
1.35
1.33
1.29
1.63
1.60
1.55
TC
12.0
12.2
12.5
15.4
15.7
16.1
16.9
17.2
17.6
19.6
20.0
20.5
TPC
0.96
0.94
0.93
1.35
1.33
1.30
1.40
1.38
1.35
1.70
1.66
1.63
IWB
(˚F)
15 25 35 43 45 55
MSH12NN
MSH15NNMSH15NNMSH15NNMSH15NNMSH15NN
MSH17NN
Notes 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
3
Btu/h), SHC : Sensible Heat Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. Heating capacity correction factors.
DATA
MSH09NW, MSH12NN, MSH15NN, MSH17NN
1. PERFORMANCE DATA
1) COOLING CAPACITY
2) COOLING CAPACITY CORRECTIONS
3) HEATING CAPACITY
10
2. PERFORMANCE CURVE
71 67 63
71 67 63
65 70 75
75 70 65
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air DB temperature (¡F)
Indoor intake air WB temperature (
¡F)
Indoor intake air WB temperature (
¡F)
Cooling capacity
SHF at rating condition = 0.7
= 279CFM = 0.23
Airflow
Bypass Factor
12
10
8
6
1.2
65 75 85 95 105 115
0.8
0.6
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air WB temperature (¡F)
Indoor intake air DB temperature (¡F)
Indoor intake air DB temperature (
¡F)
Heating capacity
= 328CFM
Airflow
12
14
10
8
6
1.1
1.0
15 25 35 45 55
0.8
0.6
0.7
0.9
NOTE : Apoint on the curve shows the reference point.
MSH09NW MUH09NW
11
NOTE : Apoint on the curve shows the reference point.
71 67 63
71 67 63
16
14
10
12
2
1
Indoor intake air DB temperature (
¡
F)
Indoor intake air DB temperature (
¡
F)
65 70 75
65 70 75
20
16
8
12
1.6
0.6
Cooling capacity
SHF at rating condition = 0.71
= 388CFM = 0.15
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air DB temperature (¡F)
Indoor intake air DB temperature (
¡
F)
Heating capacity
= 452CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air WB temperature (¡F)
0.8
1.0
1.2
1.4
Indoor intake air DB temperature (
¡
F)
MSH12NN MUH12NN
12
NOTE : Apoint on the curve shows the reference point.
71 67 63
71 67 63
65 70 75
75 70 65
Indoor intake air WB temperature (
¡
F)
Cooling capacity
SHF at rating condition = 0.65
= 367CFM = 0.22
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
22
18
14
10
2
Outdoor intake air DB temperature (¡F)
Indoor intake air DB temperature (
¡
F)
Heating capacity
= 452CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
20
16
8
1.4
0.8
Outdoor intake air WB temperature (¡F)
1
12
1.0
1.2
0.6
Indoor intake air DB temperature (
¡
F)
Indoor intake air WB temperature (
¡
F)
MSH15NN MUH15NN
13
NOTE : Apoint on the curve shows the reference point.
71 67
63
71 67 63
65 70 75
75 70 65
Indoor intake air WB temperature (
¡
F)
Indoor intake air WB temperature (
¡
F)
Cooling capacity
SHF at rating condition = 0.64
= 413CFM = 0.24
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
24
20
16
12
2
1
Outdoor intake air DB temperature (¡F)
Indoor intake air DB temperature (
¡
F)
Indoor intake air DB temperature (
¡
F)
Heating capacity
= 491CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
20
16
12
8
2.0
1.0
Outdoor intake air WB temperature (¡F)
1.2
1.6
1.4
1.8
MSH17NN MUH17NN
14
3. Condensing presure
86 F 80 75 70
(Psi.G)
300
280
260
240
220
200
180
160
140
68 70 75 80 85 90 95 100 104 F
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature (
¡F)
86 F
80 75
70
Intdoor DB temperature (
¡F)
(psi.G)
40
50
60
70
80
90
100
68 70 75 80 85 90 95 100 104 F
Suction pressure
Outdoor ambient temperature
75 F 70
65
(psi.G)
310 300
290 280 270 260 250
230
240
220 210 200 190
170
180
150
160
5 10 15 20 25 30 35 40 45 50 55 60 65 70 F
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature(¡F)
75 F 70 65
(psi.G)
80
70
60
50
40
30
20
10
5 10 15 20 25 30 35 40 45 50 55 60 65 70 F
Suction pressure
Outdoor ambient temperature
Intdoor DB temperature (
¡F)
MSH09NW(Cooling)
Data is bassed on the condition of indoor humidity 50%. Air flow should be set at Hi. A point on the curve shows the reference point.
MSH09NW(Heating)
Data is bassed on the condition of outdoor humidity 75%. Air flow should be set at Hi. A point on the curve shows the reference point.
15
MSH12NN(Cooling)
86 F 80 75 70
(Psi.G)
300
320
280
260
240
220
200
180
160
140
68 70 75 80 85 90 95 100 104( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature (¡F)
86 F
80 75
70
Intdoor DB temperature (
¡F)
(psi.G)
40
50
60
70
80
90
100
68 70 75 80 85 90 95 100 104( F)
Suction pressure
Outdoor ambient temperature
75 F 70
65
(psi.G)
310 300
290 280 270 260 250
230
240
220 210 200 190
170
180
150
160
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature(¡F)
75 F 70 65
(psi.G)
80
70
60
50
40
30
20
10
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Suction pressure
Outdoor ambient temperature
Intdoor DB temperature (
¡F)
Data is bassed on the condition of indoor humidity 50%. Air flow should be set at Hi. A point on the curve shows the reference point.
MSH12NN(Heating)
Data is bassed on the condition of outdoor humidity 75%. Air flow should be set at Hi. A point on the curve shows the reference point.
16
MSH15NN(Cooling)
86 F 80 75 70
(Psi.G)
300
320
280
260
240
220
200
180
160
140
68 70 75 80 85 90 95 100 104( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature (¡F)
86 F
80 75
70
Intdoor DB temperature (
¡F)
(psi.G)
40
50
60
70
80
90
100
68 70 75 80 85 90 95 100 104( F)
Suction pressure
Outdoor ambient temperature
75 F 70
65
(psi.G)
290 280 270 260 250
230
240
220 210 200 190
170
180
150
160
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature(¡F)
75 F 70 65
(psi.G)
80
70
60
50
40
30
20
10
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Section pressure
Outdoor ambient temperature
Intdoor DB temperature (¡F)
Data is bassed on the condition of indoor humidity 50%. Air flow should be set at Hi. A point on the curve shows the reference point.
MSH15NN(Heating)
Data is bassed on the condition of outdoor humidity 75%. Air flow should be set at Hi. A point on the curve shows the reference point.
17
MSH17NN(Cooling)
86 F 80 75 70
(Psi.G)
300
320
280
260
240
220
200
180
160
140
68 70 75 80 85 90 95 100 104( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature (¡F)
86 F 80 75
70
Intdoor DB temperature (
¡F)
(psi.G)
40
50
60
70
80
90
100
68 70 75 80 85 90 95 100 104( F)
Suction pressure
Outdoor ambient temperature
75 F 70
65
(psi.G)
290 280 270 260 250
230
240
220 210 200 190
170
180
150
160
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Condensing pressure
Outdoor ambient temperature
Intdoor DB temperature(¡F)
75 F 70 65
(psi.G)
80
70
60
50
40
30
20
10
5 10 15 20 25 30 35 40 45 50 55 60 65 70( F)
Section pressure
Outdoor ambient temperature
Intdoor DB temperature (¡F)
Data is bassed on the condition of indoor humidity 50%. Air flow should be set at Hi. A point on the curve shows the reference point.
MSH17NN(Heating)
Data is bassed on the condition of outdoor humidity 75%. Air flow should be set at Hi. A point on the curve shows the reference point.
18
4. STANDARD OPERATION
Model
Item
Capacity
Total
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor unit
SHF Input Indoor unit Power supply (V, phase, Hz) Input Fan current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input Comp. current Fan current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge
Intake air temperature
Discharge air temperature
Fan speed Airflow (Hi)
Intake air temperature
Fan speed Airflow
DB
WB
DB
WB
DB
WB
Unit
Btu / h
kW
kW
A A
kW
A
A psi.G psi.G
˚F ˚F ˚F ˚F
ft
— ˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
8,800
0.70
237
73 162 110
47 147
80
67
59
57
1,230
279
95
MSH09NW
Heating
10,500
0.89
MSH09NW
115,1,60
0.035
0.34 –
MUH09NW
115, 1, 60
0.855
6.8
0.7 233
60 160 108
37 142
25
2 lbs 5 oz
70
60 104
1,430
328
47
43
850
1,059
POWER SUPPLY
MSH09NW
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz, 1[
SIGNAL WIRE 2 wire 12V DC
Field installed 115V 60Hz, 1[
Control voltage
MSH09NW / MUH09NW
Power supply voltage to serial signal circuit is 12V DC. Between
11
and 33on in-out terminal block will
be 12V DC peak voltage.
19
Cooling
12,600/12,900
0.71
1.28/1.31
1.233/1.263
5.61/5.11
246
82 167 114
51 156
80
67
57
56
388
95
Capacity SHF Input Indoor unit Power supply (V, phase, Hz) Input Fan current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input Comp. current Fan current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge
Intake air temperature
Discharge air temperature
Fan speed Airflow (Hi)
Intake air temperature
Fan speed Airflow
Unit
Btu / h
kW
kW
A A
kW
A
A psi.G psi.G
˚F ˚F ˚F ˚F
ft
— ˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
14,300/14,600
0.65
1.35/1.38
1.303/1.333
5.91/5.41
246
80 146 112
58 161
80
67
55
54
367
95
Heating
14,500/14,800
1.25/1.30
1.203/1.253
5.41/5.11
230
57 158 108
33 143
70
60 107
452
47
43
Heating
13,000/13,500
1.18/1.25
1.133/1.203
5.11/4.91
220
58 159 106
31 146
70
60 104
452
47
43
DB WB DB WB
DB WB
Item
Model
Total
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor unit
MSH12NN
MSH12NN
115, 1, 60
0.047
0.41 –
MUH12NN
208/230, 1, 60
0.49
25
3bs 1oz
1,200
830/900
1,288/1,394
MSH15NN
MSH15NN
115, 1, 60
0.047
0.41 –
MUH15NN
208/230, 1, 60
0.49
25
3bs 1oz
1,200
830/900
1,288/1,394
MSH12NN / MSH15NN
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz, 1[
Field installed 208/230V 60Hz, 1[
SIGNAL WIRE 2 wire 12V DC
POWER SUPPLY
20
Control voltage
MSH12NN / MUH12NN MSH15NN / MUH15NN
Power supply voltage to serial signal circuit is 12V DC. Between 11and 33on in-out terminal block will be 12V DC pesk voltage.
Total
MSH17NN
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz, 1[
Field installed 208/230V 60Hz,
SIGNAL WIRE 2 wire 12V DC
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor unit
Model
Item Capacity SHF Input Indoor unit Power supply (V, phase, Hz) Input Fan current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input Comp. current Fan current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge
Intake air temperature
Discharge air temperature
Fan speed Airflow (Hi)
Intake air temperature
Fan speed Airflow
DB
WB
DB
WB
DB
WB
Unit
Btu / h
kW
kW
A A
kW
A
A psi.G psi.G
˚F ˚F ˚F ˚F
ft
˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
16,000/16,200
0.64
1.56/1.58
1,506/1,526
6.69/6.19
243
77 165 113
48 150
80
67
56
54
413
95
MSH17NN
MSH17NN
115,1,60
0.054
0.47 –
MUH17NN
208/230, 1, 60
0.61
25
4 lbs 14 oz
1,290
740/800
1,606/1,730
Heating
16,800/17,200
1.50/1.57
1,446/1,516
6.39/6.09
242
63 162 112
35 144
70
60 109
491
47
43
POWER SUPPLY
Control voltage
MSH17NN / MUH17NN
Power supply voltage to serial signal circuit is 12V DC. Between 11and 33on in-out terminal block will be 12V DC pesk voltage.
21
5. OPERATING RANGE
MUH09NW MUH12NN
MUH15NN MUH17NN
Indoor unit
Outdoor unit
Rating
115V 60Hz 1[
208/230V 60Hz 1[
Guaranteed Voltage
Min. 103V — Max. 127V
Min. 198V — Max. 253V
MSH09NW MSH12NN MSH15NN MSH17NN
Models
Model
MSH09NW
MSH12NN
MSH15NN
MSH17NN
Function
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
328 279 452 388 452 367 491 413
19.0
16.1
18.2
15.6
18.2
14.8
19.7
16.6
25.6
21.8
29.2
25.2
29.2
23.9
31.7
26.8
Air flow
(CFM)
Air speed
(ft/sec.)
Coverage
range (ft)
MSH09NW MUH09NW MSH12NN MUH12NN MSH15NN MUH15NN MSH17NN MUH17NN
Outdoor unit
precharged
(up to 25ft)
2 lbs 5 oz 3 lbs 1 oz 3 lbs 3 oz
4 lbs 14 oz
25ft
0
30ft
3
35ft
5
Refrigerant piping length (one way)
40ft
8
45ft
11
49ft
13
Model
Function
Cooling
Heating
Standard temperature
Maximum temperature
Minimum temperature Standard temperature
Maximum temperature
Minimum temperature
DB (˚F)
80 95 67 70 80 70
WB (˚F)
67 71 57 60
60
Indoor
DB (˚F)
95
115
67 47 75 17
WB (˚F)
— —
— 43 65 15
Outdoor
Condition
Intake air temperature
(1) POWER SUPPLY
(2) OPERATION
6. OUTLET AIR SPEED AND COVERAGE RANGE
7. ADDITIONAL REFRIGERANT CHARGE (R-22(oz))
22
The air coverage range is the value up to the position where the air speed is 1 ft/sec, when air is blown out horizontally from the unit properly at the High speed position. The coverage range should be used only as a gen­eral guideline since it varies according to the size of the room and furniture installed inside the room.
6
OUTLINES AND DIMENSIONS
MSH09NW
INDOOR UNIT
10-13/16
2-3/8
2-3/16
30-13/16
32-1/16
24-5/8
11/16
5-1/8
3-5/16
3-5/16
7-3/8
1-5/8
1/4
3-15/16
8-7/8
12-11/16
7-3/16
3-9/16
8-7/8
12-3/8
3/16
2-13/16
5-1/4
3-11/16
1/4-19-11/16
3/8-16-15/16
1-3/8 O.D.
3/4 I.D
7-3/16
1/8
5/8
1-1/8
Unit: inch
8-11/16
10-3/8 3/8
1-13/16
2-9/16
6-5/16
MUH09NW
OUTDOOR UNIT
7/8
10-1/16
21-1/4
11-1/4
12-5/8
10-5/16
3/8
12-5/8
11/16
4-13/16
9-13/16
3-9/16
1-11/16
19-5/8
30-11/16
4-3/8 13/16
12-5/16
1-15/16
1-1/16
16-11/16
3/4
2-13/16
1-1/4
12-5/8
11-1/4
9/16 9/16
(5/16 7/8)
2-3/8
13-1/2
2-9/16
3-9/16
2-9/16
20 in
5/8
7/16
4
4-3/16
4 in.
16
16 in.
1/4
3/8
4 in.
4 in.
14 in.
23
MSH12NN, MSH15NN, MSH17NN
INDOOR UNIT
5-15/16
7/16 13/16
25-1/2
Unit: inch
8-9/16
2-3/8
1-9/16
17-11/16
17-11/16
17-1/4
12-5/8
1-15/16
2-3/16
6-5/16
MUH12NN, MUH15NN
OUTDOOR UNIT
39-15/16
30-1/2
13-7/8
11/16
7-1/2
11-3/16
10-13/16
13/161/8
11-11/16
2-15/16
7-1/2
installation plate
3/16
5/16-19-11/16
1/2-16-15/16
1-15/16 O.D. 1-1/8 O.D.
5/8 1-1/8
1-3/8
9-3/4
23-13/16
11-1/2
13/16
13-12/16
5/8
7-3/16
19-11/16 33-7/16
13/16
1-15/16
11-7/16
1-3/16
6-3/16
2-15/16
12-3/16
3-15/16
13-9/16
6-5/16
4 in.
20 in.
1/4
5/8
4 in.
4 in.
14 in.
24
MUH17NN
OUTDOOR UNIT
Unit: mm
8
upper clearance.
Note:Allow adequate
11/169/16
Air intake
19-11/16
7-9/32 7-9/32
4
1/2
Front opening
1/2
14-1/4
13
Air intake
36
1/2
1-9/161-1/16
Air outlet
(for N.E.C)
Service space
36
1-3/4
Refrigerant pipe
Refrigerant pipe
(Flared) 5/8
33-9/16
21-3/4
Terminal block for indoor and outdoor unit connection
Terminal block for power line
34-1/4
11-7/8
Handie for moving
Service panel
Ground
terminal
15-7/8
20-5/18
17-3/18
2-1/16
2-3/8
(Flared) 1/4
Knock out hole
13-7/8
13-7/4
2-3/820-5/81-9/16
7-1/18
Knock out holes for
power line 1-1/16
4-3/4
for front piping
(refrigerant. drainage
and wiring)
Knock out hole for
right piping
1-3/4 1-5/8
1/5/16
4-1/8
1/2x7/8 Oval hoies
(standard bolt W3/8(M10)
1 max.
3-1/8
R13/16
R13/16
(refrigerant. drainage
and wiring)
Bottom piping hole
Drain hole
Standard bolt length
2-9/16
Front right piping holes-
detail figures
11/16
R1/4
1/2
2-U-shaped
notched
holes
Drain hole
8
40
The upper side must be open.
For 10 units or less
(Concentrated installation)
Outdoor Unit-Necessary surrouding clearance
1/2
4
1
11-5/8
Outlet guide
installation hole
Handle for
moving
Handle for moving
Rear fresh
air intake
Side air intake
2
1
Rear piping hole
3-3/4
5-7/16
25
7
WIRING DIAGRAM
MSH09NW
MODEL WIRING DIAGRAM
INDOOR UNIT
TB
TO OUTDOOR UNIT CONNECTING WIRES DC12V
POWER SUPPLY 115V 1 phase 60Hz
GROUND
3 1
N
L1
RECEIVER P.C.BOARD
ORN
VLT
BLK RED
5 5
REMOTE CONTROLLER
LD101
AUTO RESTART ASSY
104
CN201
1 2 3 4
TAB12
HIC1
TRANS
F11
CN
CN
151
ELECTRONIC CONTROL P.C BOARD
5
MV
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C11 INDOOR FAN CAPACITOR NR11 VARISTOR TB TERMINAL BLOCK
HIC1 DC/DC CONVERTER RT11
F11 FUSE(3.0A) RT12
ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR
MF INDOOR FAN MOTOR
NOTE:1. For the outdoor electric wiring, refer to the outdoor unit electric wiring diagram .
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MUH09NW
MODEL WIRING DIAGRAM
SR11
NR11
C11
CN
112
CN
111
CN
121
3 2 1
CN211
RT12 RT11
BLK
3
GRY YLW BRN
WHT
RED
MV VANE MOTOR
SR11 SOLID STATE RELAY
1 2 3
MF
4 5 6
21S4
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING WIRES DC12V
POWER SUPPLY 115V 1 phase 60Hz
GROUND
TB
3
1
N
L
1
ORN
VLT
BLK
RED
BLK
CN730
1 3
TAB20
DSAR
RED
F61
IC881
TRANS
52C
NR61
3❈4
RT61
CN721
X62
SR61
X62
DEICER P.C. BOARD
CN661
C65
C1
1 2 3 4
CN711
RED BLK
RED
WHT
BLK
WHT
MF
S
MC
C
R
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C1
C65
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR
MF MC
OUTDOOR FAN MOTOR(INNER THERMOSTAT) COMPRESSOR
(INNER THERMOSTAT)
TB TERMINAL BLOCK
IC881 DC/DC CONVERTER
21S4 SOLENOID COIL 52C COMPRESSOR CONTACTOR NR61 VARISTOR
DSAR SURGE ABSORBER F61 FUSE (2.0A) RT61
DEFROST THERMISTOR
SR61 SOLID STATE RELAY X62 REVERSING VALVE RELAY
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they can not be removed when you pull
the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate. : Terminal block, : Connector
1.Slide the sleeve.
2.Pull the wire while
26
pushing the locking lever.
MSH12NN, MSH15NN, MSH17NN
MODEL WIRING DIAGRAM
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING WIRES DC12V
POWER SUPPLY 115V 1 phase 60Hz
RECEIVER P.C.BOARD
TB
3 1
N
L1
GROUND
REMOTE CONTROLLER
ORN
VLT
BLK RED
BRN
DISPLAY P.C.BOARD
DSAR
GRN/YLW
AUTO RESTART ASSY
SR144 SR142 SR143 SR141
112
111
LDCOM
LDC11
LDC12
LDFH LDFL LDFM LDFVL
CN
CN
WHT ORN RED
BLK YLW BLU BRN
RT12 RT11
1 2 3 4 5 6 7 8
WHT ORN RED BLK YLW BLU BRN
GRN/YLW
MF
CN201
1 2 3 4
TAB12
CN
CN
CN
101
104
102
33
F11
CN
ELECTRONIC CONTROL P.C BOARD
151
5
5
HIC1
TRANS
C11
NR11
MV
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C11 INDOOR FAN CAPACITOR NR11 VARISTOR TB TERMINAL BLOCK
HIC1 DC/DC CONVERTER RT11
F11 FUSE(3.0A) RT12
MF INDOOR FAN MOTOR
SR142~SR144
ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR SOLID STATE RELAY
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MV VANE MOTOR
DSAR SURGE ABSORBER
MUH12NN, MUH15NN, MUH17NN
OUTDOOR UNIT
GROUND
TO INDOOR UNIT CONNECTING WIRES DC12V
POWER SUPPLY 208/230V 1 phase 60Hz
TB
3
VLT
1
1
L
2
L
ORN
RED RED
RED
BLU
DSAR
MODEL WIRING DIAGRAM
RT61
CN730
CN661
1 3
F61
TAB21
TAB20
NO COM
BLU
IC881
TRANS
52C
X62
21S4
CN721
NR61
DEICER P.C. BOARD
C1
RED
BLK
X62
SR61
WHT
52C
CN720
CN711
C65
MC
1
WHT
2 3
BLK
4
C
RS
MF
REDRED
1
ORN
2
WHT
3
BLK
4
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C1
C65
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR
DSAR SURGE ABSORBER NR61 VARISTOR X62
MF
MC
OUTDOOR FAN MOTOR(INNER THERMOSTAT) COMPRESSOR(INNER THERMOSTAT)
TB TERMINAL BLOCK
52C
COMPRESSOR CONTACTOR REVERSING VALVE RELAY
F61 FUSE (2.0A) RT61 DEFROST THERMISTOR 21S4 SOLENOID COIL
IC881 DC/DC CONVERTER SR61 SOLID STATE RELAY
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate. : Terminal block, : Connector
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
27
8
REFRIGERNT SYSTEM DIAGRAM
Unit:inch
MSH09NW
INDOOR UNIT
Indoor heat
exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Refrigerant pipe [3/8 (Option)
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (Option) (with heat insulator)
Stop valve (with service
port)
Service port
Fusible plug
Accumulator
Strainer
Stop valve
Muffler
Reversing
Muffler
Capillary tube O.D. 0.12I.D.
35-7/16
0.063
Check valve
valve
Compressor
Capillary tube O.D. 0.12I.D.
0.063
Strainer
Service port
Defrost thermisor RT61
19-11/16
MUH09NW
OUTDOOR UNIT
Outdoor heat exchanger
Capillary tube O.D. 0.12I.D. 0.055 11-13/16
Solenoid coil heating ON cooling OFF
Flow of refrigerant (cooling) Flow of refrigerant (heating)
Unit:inch
MSH12NN MSH15NN
INDOOR UNIT OUTDOOR UNIT
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
thermistor RT12
Distributor
Refrigerant pipe [5/8 (Option) (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (Option)
(with heat insulator)
Muffler
Stop valve (with service port)
Service port
Accumulator
Stop valve
Reversing
valve
Fusible plug
Muffler
Compressor
Capillary tube MSH12:O.D. 0.12I.D 0.07119-11/16 MSH15:O.D. 0.12I.D 0.07923-5/8
Strainer
Check valve
Service port
Defrost thermisor RT61
MUH12NN MUH15NN
Strainer
Outdoor heat exchanger
Capillary tube O.D. 0.12I.D.
0.05511-13/16
Capillary tube O.D. 0.12I.D.0.0797-7/8
Solenoid coil heating ON cooling OFF
Flow of refrigerant (cooling) Flow of refrigerant (heating)
28
Unit:inch
MSH17NN
MUH17NN
INDOOR UNIT OUTDOOR UNIT
Refrigerant pipe [5/8
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
thermistor RT12
Distributor
(Option) (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (Option) (with heat insulator)
Ball valve
Ball valve (with service port)
Service port
Fusible plug
Accumulator
Strainer
Reversing
valve
Muffler
Compressor
Capillary tube O.D. 0.12I.D. 0.0799-13/16
Check valve
StrainerStrainer
Muffler
Service port
Defrost thermisor (RT61)
Outdoor heat exchanger
Distributor
Solenoid coil heating ON cooling OFF
Capillary tube O.D. 0.12I.D. 0.07927-9/16
Flow of refrigerant (cooling) Flow of refrigerant (heating)
29
9
Operation Indicator
MICROPROCESSOR CONTROL
Wireless remote controller
INDOOR UNIT DISPLAY SECTION
MSH09NW, MSH12NN MSH15NN, MSH17NN
Once the controls are set, the same operation mode can be repeated by simply turning the OPERATE/STOP button ON. Indoor unit receives the signal with a beep tone. When the system turned off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
9-1. “I FEEL CONTROL” OPERATION
(1) Press OPERATE/STOP button on the remote con-
troller. OPERATION INDICATOR LAMP of the indoor unit will turn on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL
CONTROL.” Then a beep tone is heard.
(3) The operation mode is determined by the initial
room temperature at start-up of the operation.
Initial room tempreature
more than 77˚F
73˚F to 77˚F
less than 73˚F
“I FEEL CONTROL” “I FEEL CONTROL”
“I FEEL CONTROL”
Once the mode is fixed, the mode will not change by room temperature afterwards.
Under the ON-TIMER ( START) operation, mode is determined according to the room temperature when the operation starts.
When the system is stopped with the OPERATE/STOP button on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” mode, the system operates in previous mode auto­matically regardless of the room temperature.
Example
mode
COOL mode of
DRY mode of
HEAT mode of
30
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
When the system is restarted after 2 hours, the operation mode is determined by the initial room temperature at start-up of the operation.
Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
Restart
COOL mode of “I FEEL CONTROL”
Restart
COOL or DRY or HEAT mode of “I FEEL CON­TROL” that determined by initital room tempera­ture at start-up of the operation.
(4) The initial set temperature is decided by the initial room temperature.
Model Initial room temperature Initial set temperature
COOL mode of
“I FEEL CONTROL”
DRY mode of
“I FEEL CONTROL”
HEAT mode of
“I FEEL CONTROL”
1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless of
the initial set temperature. The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone,
79˚F or more
79˚F or less
73˚F to 77˚F
73˚F or less
Initial room temperature minus 4˚F Initial room temperature minus 4˚F
75˚F
79˚F
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
1
TOO
COOL… To raise the set temperature 2~4 degrees(°F)
TOO WARM … To lower the set temperature 2~4 degrees(°F)
31
— COOL mode of “I FEEL CONTROL” —
ON
Compressor and
OFF
ON
OFF
outdoor fan motor
Indoor fan motor
ON
Run continuously in cooling mode
NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”
There are two types of controls in coil frost prevention.
Temperature control <MSH09> When the indoor coil thermistor RT12 reads 39˚F or below for 5 minutes, the coil frost prevention mode starts. <MSH12/15/17>When the indoor coil thermistor RT12 reads 37˚F or below, the coil frost prevention mode starts immediately.
However the coil frost prevention only works after 5 minutes from the compressor starts. The compressor stops and the indoor fan operates at the set speed for 5 minutes. After that, if RT12 still reads below 39˚F (MSH09) or below 37˚F (MSH12/15/17) this mode prolonged until the RT12 reads
over 39˚F (MSH09) or 37˚F (MSH12/15/17).
Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Lo or Me. c. Room temperature is below 79˚F. When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds 79°F. However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
Indoor fan operates at the set speed by FAN SPEED CONTROLbutton. Followings are the fan speed in AUTO.
Initial temperature difference Room temperature minus set temperature : 4 degrees or more···········································Hi Room temperature minus set temperature : 2 degree or more and less than 4 degrees·····Me Room temperature minus set temperature : less than 2 degree···········································Lo
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the temperature and the microprocessor. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. The operation of the compressor and indoor fan is as follows.
1. When the room temperature is 73˚F or over:
Compressor operates by temperature control and time control.
Set temperature is controlled to fall 4˚F as initial set temperature.When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON. Indoor fan and outdoor fan operate in the same cycle as the compressor.
Fan speed
2 deg.
3 deg.
4 deg.
7 deg.
2. When the room temperature is under 73˚F.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
32
Operation time chart
Example
Thermostat
1st ON
ON
OFF
ON
OFF
ON
OFF
1 min.
Indoor fan
Outdoor fan compressor
ON
ON
8 min.
ON
OFF
ON
OFF
3 min.
4 min.
NOTE
Coil frost prevention during DRY mode of “I FEEL CONTROL” The operation is as same as that of coil frost prevention during COOL mode of “I FEEL CONTROL”. However the indoor fan speed becomes the set speed or Lo.
— HEAT mode of “I FEEL CONTROL” —
1. Indoor fan speed control
(1) Followings are the fan speed in AUTO.
Set temperature minus room temperature: 4 degrees or more···················································Hi Set temperature minus room temperature: 2 degrees or more and less than 4 degrees ···········Me Set temperature minus room temperature: less than 2 degree···················································Lo
(2) Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 72˚F. The fan operates at VLo when the temperature is below 64˚F. But the fan stops when the indoor fan operates at VLo and the temperature is below 59˚F or less.
Released
Cold Air Prevention
64˚F
NOTE : At intial in hysteresis this control works.
(3) New warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther­mistor RT12 temperature to blow out warm air. After releasing of cold air prevention, when the indoor coil temperature is 99˚F or above, the fan speed shifts to the set speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed. When the indoor coil temperature is less than 99˚F, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed> less than 2 minutes························Lo 2 minutes to 4 minutes···················Me 4 minutes or more··························Hi The upper limit of the fan speed is the set speed. If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at VLo. NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start until the indoor coil thermistor RT12 reads above 72˚F or more.
temperature difference Fan speed
2 deg.
72˚F
4 deg.
3 deg.
7 deg.
33
2. High pressure protection
During heating operation, the outdoor fan motor is controlled by the indoor coil thermistor RT12 temperature for excess rise protection of compressor discharge pressure. Outdoor fan OFF: 126˚F (MSH09), 122˚F (MSH12/15/17) Outdoor fan ON : 118.4˚F (MSH09),115˚F (MSH12/15/17)
High pressure protection time chart Indoor coil temperrature thermistor
RT12
126˚F(MSH09) 122˚F(MSH12/15/17)
118˚F(MSH09) 115˚C(MSH12/15/17)
Outdoor fan motor turn OFF
Outdoor fan motor turn ON
Outdoor fan motor
NOTE: When the outdoor fan is OFF in heating, the defrosting of outdoor heat exchanger is not detected by the defrost ther-
mistor RT61.
3. Defrosting
Defrosting of outdoor heat exchanger is controlled by deicer P.C. board, with detection by the defrost thermistor RT61.
(1) Defrost starting conditions
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds for 40 minutes without the defrosting
operation working. b) The defrost thermistor RT61 reads 27˚F. c) After releasing the high pressure protection, 4 minutes and 15 seconds have elapsed.
(2) Defrost terminating conditions
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 38˚F or more. e) The defrosting time exceeds 10 minutes.
ON
OFF
OFF
34
(3) Defrost time chart
Defrost thermistor 38˚F or more
RT61 27˚F or less
Outdoor 52C relay(Compressor)
ON OFF
X62 (Solenoid coil)
SR61 Outdoor fan
Defrost counter
Indoor fan
Indoor vane
ON OFF
ON OFF
ON OFF
ON OFF
Horizontal set position
30 sec.
VLo
15 sec.
30 sec.
15 sec.
Max 10 min.
NOTE When the indoor coil thermistor reads above 64˚F, indoor fan operates at VLo for 30 seconds.
When the indoor coil thermistor reads 64˚F or less, the indoor fan stops.
35
4. Reversing valve control
50
50
59
68
77
86
95
59 68 77 86 95¡F
¡F
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
NOTE: The Reversing valve reverses for 5 seconds right before start-up of the compressor.
(COOL / DRY)
(HEAT)
Compressor
Reversing valve
Outdoor fan
ON
OFF ON
OFF
ON
OFF
9-2. COOL OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit turns on with a beep tone.
(2) Select COOL mode. (3) Set the TEMPERATURE button.
(TOO WARM or TOO COOL button)
The setting range is 59 ~ 89˚F
Indoor fan continues to operate regardless of
thermostat’s OFF-ON
Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”
9-3. DRY OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone. (2) Select DRY mode. (3) The microprocessor reads the room tempera-
ture and determines the set temperature. Set
temperature is as shown in the right chart.
Thermostat (SET TEMP.)is not work.
The other operations are same as DRY mode of
“I FEEL CONTROL”. (4) DRY operation will not functions when the room
temperature is 55˚F or below. (5) When DRY operation functions, the fan speed
is lower than cool operation.
5 sec.
5 sec.
ON OFF ON
OFF
ON
OFF
9-4. HEAT OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR on the indoor unit turns on with a beep tone. (2) Select HEAT mode. (3) Press TEMPERATURES button (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 59 ~ 89˚F. (4) Indoor fan speed control, high pressure protection, defrosting, heater control are the same as HEAT mode of “I FEEL
CONTROL”.
36
9-5. FAN MOTOR CONTROL (MSH09 only)
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback
the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo) the microprocessor controls SR11 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 min­utes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the operation indicator flash­es to show the fan motor abnormality. (See page 45.)
9-6. AUTO VANE OPERATION
(1) Vane motor drive
MSH-N series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by plus signals (approx. 12V) transmitted from indoor microprocessor.)
(2) The auto vane angle changes as follows by pressing the VANE CONTROL ( ) button.
VANE
37
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. The positioning is decided as follows. (a) When the OPERATE/STOP button is pressed. (POWER ON/OFF) (b) When the vane control change AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
(4) VANE AUTO mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
In COOL and DRY operation
Vane angle is fixed to Angle 1.
In HEAT operation
Vane angle is fixed to Angle 4.
(5) Dew prevention
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE
By pressing the SWING button vane swings vertically. The remote controller displays “ ” SWING mode is cancelled when the SWING button is pressed or the operation stops or changes to other mode.
(7) Cold air prevention in HEAT mode.
When either of the following conditions occurs in HEAT mode, the horizontal vane angle changes to Angle 1 automatically
to prevent cold air blowing on users.
Compressor is not operating.Defrosting is performed.Indoor coil thermistor RT12 reads 75˚F or below.Indoor coil thermistor RT12 temperature is raising from 75˚F or below, but it does not exceed 82°F.
Indoor coil thermistor RT12 temperature
NOTE : At initial in hysteresis this control works.
38
Angle 1
75˚F
Set position
82˚F
9-7. TIMER OPERATION
START STOP
START STOP
1. How to set the timer.
(1) Press OPERATE/STOP button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIMER MONITOR so set the current time, correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
START” button... AUTO START operation (ON timer)
STOP” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN, button will work when “ These marks disappear in 1 minute. When setting the ON timer, check that OPERATION INDICATOR of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
A power failure occurs.
The circuit breaker functions.
2. CANCEL
Timer setting can be cancelled with the TIMER CONTROLbuttons. (“
To cancel the ON timer, press the “ To cancel the OFF timer, press the “
Timer is cancelled and the display of set time disappears.
START” or “ STOP” mark is flashing.
START” or “ STOP”)
START” button.
STOP” button.
PROGRAM TIMER
The OFF timer and ON timer can be used in combination.
” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
39
Emergency operation switch
Emergency operation switch
9-8. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION switch on the front of the indoor unit. The unit will start and the POWER MONITOR lamp will light. The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of 75˚F. The fan shifts to Me speed. This operation continues until the EMERGENCY OPERATION switch is pressed or a button on the remote controller is pressed, then normal operation will start. The coil frost prevention circuit operates in this operation, and defrosting operates too. In the test run or emergency operation, the horizontal vane operates in AUTO mode a the set temperature of 75˚F. Defrosting of outdoor heat exchanger works in EMERGENCY HEAT MODE.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
MSH09NW
Press once
<Cool>
Press again
<Heat>
Press once again
<Stop>
MSH12NN MSH15NN MSH17NN
40
10
SERVICE FUNCTIONS
MSH09NW, MSH12NN, MSH15NN, MSH17NN
1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. See Page 53. Defrost thermistor RT61 must read below 27°F
2. DEFROST TERMINATION CHANGE
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. <JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed.
Model
MSH09NW
MSH12NN MSH15NN MSH17NN
3. AUTO RESTART FUNCTION
When the indoor unit is operated with the remote controller, the signals of the operation mode, the set temperature, and the
fan speed are sent from the indoor electronic control P.C.board and memorized in the auto restart assy.
When the main power is turned off and then turned on back again, the unit restarts automatically in the memorized set con-
ditions approximately after 3 seconds.
NOTE:
a) When the unit operation is stopped with the Emergency Operation Switch, the unit does not restart after the power is
restored, since the signal of “Operation Stop” is memorized in the auto restart assy.
b) Operation details may not be memorized in case the signal is transmitted by the remote controller to turn the main
power OFF within 10 seconds after the power ON. .
c) When the unit operation is stopped with the remote controller before power failure, the unit does not restart until the
OPERATE/STOP (ON/OFF) button on the remote controller is pressed.
4. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronics control P.C. board. The time will be shortened as follows. 3-minute delay : 3-minute 3-second. AUTO START : 1 hour 1-minutes AUTO STOP : 1 hour 1-minutes
Junper wire Change point
JPC
JPE
Short the connector during the timer mode.
}
Defrost interval time changes from 40 minutes to 15minutes.
Defrost start temperature changes from 27˚F to 32˚F.
Defrost finish temperature changes from 38˚F to 50˚F.
41
5. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the indoor unit number.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For remodeling, take out the
batteries at first. After finish remodeling, put back the batteries then push the RESET-button.
The P.C.board has the print “J1” and “J2”. Jumper wires are mounted to each “J1” and “J2”. Cut “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, push the RESET button near the MIN-button on the remote controller.
Table.1
1 unit operation
No,1 unit No,2 unit No,3 unit No,4 unit
Note : At power supply failure or installation, indoor unit deletes the memory about remote controller. When the
No modification
– – –
2 unit operation
Same as at left
Cut J1
– –
3 unit operation
Same as at left Same as at left
Cut J2
4 unit operation Same as at left Same as at left Same as at left
Cut both J1 and J2
power supply is turned on and indoor unit receives the first signals from the remote controller, the remote controller number is designated as the indoor unit number. Therefore at and after the second time indoor unit accepts the remote controller of the initial setting number. At setting-error, turn the power supply off to cancel the individual operation, and then turn the power supply on to restart the setting.
42
11
Lead wiring
Reset button
Housing point
TROUBLESHOOTING
MSH09NW, MSH12NN, MSH15NN, MSH17NN
11-1 Cautions on troubleshooting
11-1-1 Before troubleshooting, check the followings:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
11-1-2 Take care the followings during servicing.
1) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the P.C. boards.
2) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
11-1-3 Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing to indicate an abnormality. To make sure, check the how many times abnormality indication is flashing on and off before starting service work.
2) If the P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 44 and the check table on page 45.
11-1-4 How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote con-
troller normally, discharge the remote controller in the following order.
The remote controller has a reset button. After installing new batteries, press the reset button with tip end of ball point
pen or the like, and then use the remote controller.
43
11-2 Instruction of troubleshooting
Start
Indoor unit oper­ates. Outdoor unit doesn’t operate.
Outdoor unit operates in only Test Run opera­tion.
Check room temperature thermistor.
MSH12NN MSH15NN MSH17NN When the
remote controller is pressed or when the Emergency operation switch is pressed,the fan does not rotate,with Operation indi­cator lamp on.
Outdoor unit doesn’t oper­ate even in Test Run operation.
Refer to “Check of outdoor unit” on page 49.
D
Indoor unit dosen’t receive the signal from remote controller.
Refer to ”Check of receiver P.C. board” on page 48.
1-time flash
Cause:indoor/outdoor unit connecting
Trouble of mis-wiring
(
Trouble of the serial signal
Refer to “How to check mis-wiring and sig­nal error (when outdoor unit doesn’t work)” on page 50.1
B
E
Refer to “Check of indoor fan motor” on page 47.
Indoor unit operation monitor lamp is flashing.
2-time flash
2.5-second OFF
MSH09NW only 3-time flash
2.5-second OFF
Cause:Indoor unit 2-time-Room tempera-
ture/Indoor coil thermistor trouble.
MSH09NW only 3-time-Indoor fan motor
trouble
Check indoor coil thermistor. Refer
A
to“Test point dia­gram and voltage” on page 51 and
52.
Indoor unit doesn’t receive the signal from remote controller. Also, operation monitor lamp doesn’t flash, when the emergency operation switch is pressed.
Refer to “Check of indoor electric control P.C. board” on page 49.
6-time flash
Cause:outdoor unit 6-time-Replace the out-
Check room temperature thermistor. Refer to“Test point diagram and volt­age” on page 51 and 52.
C
2.5-second OFF
door thermistor
44
1<The case of the trouble of the serial signal>
when turn off the power and then turn on the power again, the indication shows “the trouble of mis-wiring.”
11-2-1 troubleshooting check table
Look at the left lamp flash for the self check table.
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table
NO.
Abnormal
point
Indication
Symptom
Detect method
Check point
Mis-wiring
1
2
Room tempera­ture ther­mistor
3
Serial sig­nal
Indoor coil thermistor
Indoor fan motor
1-second ON
1-second OFF
1-second ON
2.5-second OFF
2-time flash
2.5-second OFF
MSH09NW only
3-time flash
2.5-second OFF
Outdoor unit
does not run.
Outdoor unit does not run.
Indoor fan
repeats 12 sec­onds ON and 3 minutes OFF.
When the indoor
fan breaks, the fan keeps stop­ping.
When serial signal stops for 4 to 5 seconds after 1st on of 52C relay by POWER turning on.
When serial signal from out­door unit stops for 4 to 5 sec­onds.
Detects Indoor coil/room tem­perature thermistor short or open circuit every 2 seconds during operation.
When rotational frequency feedback signal is not emit during 12-second indoor fan operation.
Check wiring (visual sheck and conductiv­ity check).
Check indoor electronic control P.C. board.
Check outdoor DEICER P.C. board.
Check electrical parts.
Check thermistor calibretion.
Reconnect connector.
Check indoor borad.
Disconnect connector CN211 and then
check connector CN121 - to make sure rotational frequency feedback signal of 1.5V or over exists.
Check indoor electronic control P.C.
board.
Check indoor fan motor.
Reconnect conector.
2
3
6-time flash
Outdoor
4
thermistor
2.5-second OFF
Outdoor unit
does not run
When the outdoor thermistor shorts or opens after the com­pressor start-up.
Check outdoor DEICER P.C. board.
Check thermistor calibretion.
45
MSH09NW, MSH12NN, MSH15NN, MSH17NN
1 2 3
09NW
RED
BLK
YLW GRY BRN
WHITE
1 2 3
12/15/17 NN
RED
ORN
BLU
BLK
WHT
YLW
BRN
F
09NW
RED
BLK
WHT
P
12/15/17 NN
RED ORN
BLK
WHT
P
11-2-2 Trouble criterion of main parts
Part name
Room temperature thermistor
Indoor coil thermistor
Defrost thermistor
Compressor
Measure the resistance with a tester. (Part temperature 50°F ~ 86°F)
8k~ 20k
Measure the resistance with a tester. (Part temperature 14°F ~ 104°F)
5k~ 55k
Measure the resistance between the terminals with a tester. (Coil wiring temperature14°F ~ 104°F)
C-R C-S
Measure the resistance between the terminals with a tester. (Coil wiring temperature 50°F ~ 86°F)
Motor part
WHT-BLK BLK-RED
Check method and criterion
Normal
Normal
09NW
0.86~1.06
1.9~2.4
Opened or short-circuited
Opened or short-circuited
Normal
12NN
1.9~2.41.4~1.9
2.7~3.4
15NN
2.4~3.0
Normal
09NW
76~83
70~76
Abnormal
Abnormal
17NN
1.4~1.8
2.3~2.9
Figure
Abnormal
Opened or
short-circuited
Abnormal
Opened or
short-circuited
Measure the voltage Power ON.
Indoor fan motor
Sensor partMotor part
BRN-YLW YLW-GRY
WHT-BLK BLK-YLW YLW-BLU BLU-BRN
BRN-RED
Measure the resistance between the terminals with a tester. (Coil wiring temperature14°F ~ 104°F)
Outdoor fan motor
WHT-BLK BLK-RED
Vane motor
46
Measure the resistance between the terminals with a tester. (Part temperature 50°F ~ 86°F)
Normal
09NW
282 ~ 305
Normal
09NW
4.5 ~ 5.5V
(When fan revolved one time)
0V5V0V (Approx.)
Normal
12/15NN
67~73
9~9.8
4.9~5.5
5.8~6.4
28~32
Normal
09NW
42~53 74~92
12/15/17NN 358 ~ 387
12/15NN
102~126
97~120
Opened or short-circuited
Abnormal
Remain 0V or 5V
17NN
53~59 10~12
4.6~5.0
5.4~6.0
36~40
17NN
55~68
82~101
Abnormal
Abnormal
Opened or
short-circuited
Abnormal
Opened or
short-circuited
A
Check of indoor fan motor
Inodoor fan does not operate.
Turn OFF power supply. Check connector (Fan motor) visually.
No
Are lead wires connected?
Reconnect the lead wires.
Yes
Disconnect lead wires from connector (Fan motor) on indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.3 and then No.2 and No.3 (09NW).
Is resistance 0 (short circuit) or (open circuit)?
Yes ( 0 or )
Repair indoor fan motor.
{
No.1 and No.4 and then No.3 and No.4 (12/15/17NN).
12/15/17NN
No
(others)
No
Is soldered point normal?
Insert screwdriver into air outlet to
09NW
rotate indoor fan motor slowly for 1 revolution or over, and measure voltage between YLW and GRY of CN 121 .
Does voltage repeat 0V DC and more than 5V?
Replace the indoor electronic con­trol P.C. board.
No
Yes
Resolder it.
}
Yes
47
Check of receiver P.C. board
B
Indoor unit operates by pressing the emergency ON/OFF switch, but does not operate with the remote controller.
Check the model name of remote controller.
Is LCD display on remote con­troller visible?
Yes
Remove batteries and then set them back. Check if the unit operates with remote controller.
Does the unit operate with remote controller?
Yes
OK
Connect properly.
No (not clear)
No
No
Replace batteries.(see page 43.)
Turn a radio to AM and press switch on remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 3.28ft?
No
MSH12/15/17NN
The connector connecting Receiver P.C. board and Micom P.C. board is properly fixed.
Yes
Replace Receiver P.C. board.
No
Yes
Replace remote controller.
Re-install the unit away from lights.
Attach a filter on receiving part.
MSH09NW
48
Connect properly.
Replace Auto Restart Assy.
Reolace Micom P.C. board.
No
No
No
No
The unit receives signal of Operate ON/OFF with remote controller, and emits a beep tone.
Yes
END
The connecer of Auto Restart Assy is properly fixed.
Yes
Replace Auto Restart Assy.
The unit receives signal of Operate ON/OFF with remote controller, and emits a beep tone.
Yes
END
The unit receives signal of Operate ON/OFF with remote controller, and emits a beep tone.
Yes
END
Check of indoor electronic control P.C. board
C
The unit doesn’t operate with the remote controller.
Replace the fuse.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Is fuse(F11)blown?
Check both “parts side”and “pattern side of indoor electronic control P.C. board visually.
Be sure to check both fuse and varistor in any case.
Yes
No
1.Pull out power supply cord.
2.Measure resistance between CN201
1
on electronic con­trol P.C. board and on the terminal block with a tester.
Trouble of indoor electronic con­trol P.C. board.
Yes
Is ther resistance? (Approx.0)
N
No
Trouble of fuse(F12)
Check of outdoor unit
D
Is varistor(NR11)burnt?
Yes
Replace varistor.
No
09NW
12/15/17NN
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
Start
Press EMERGENCY ON/OFF button. 3-minute time delay works. Test mode operates for 30 minutes.
Check voltage to terminal block of outdoor unit. Is there AC115V(MSH09),208/230V(MSH12/15/17) to terminal block between - (MSH09), ­(MSH12/15/17)?
Check voltage to terminal block of indoor unit. Is there DC12V to terminal block between - ?
NL1 L2L1
No
31
Yes
Check the outdoor DEICER P.C. board at first, then check
Yes
CN201
1144
L1
Terminal
CN201
11
44
the outdoor fan motor and the compressor.
N
L1
L N
N
block
Terminal
Terminal block
block
No
Replace indoor electronic control P.C. board.
Check continuity of indoor and outdoor unit connection.
49
How to check mis-wiring and serial signal error (when outdoor unit does not work)
E
Start
Turn off power supply. (indoor/outdoor units)
Turn on power supply. (indoor/outdoor units)
Rectify voltage. When 230V is available for MSH09NW outdoor unit,replace the outdoor P.C. board.
Correct mis-wiring.
No
Power voltage of terminal blocks of indoor/outdoor units is normal.
Yes
Turn on Emergency operation switch.
Normal operation starts 3 minutes after power supply is turned on.
No
No
Terminal blocks11and33on indoor unit is properly connected to their counter parts on outdoor unit.
Yes
Check by using Checking Mode.
11
Disconnect indoor/outdoor wiring (at indoor ter­minal blocks 11and 33)
22
Short curcuit between indoor terminal blocks and 33.
33
While pressing Mode button on remote con-
troller,press Reset button. Do this where the unit can recieve the signal. (LCD on remote controller displays all signs.)
Press OPERATE ON/OFF button on remote controller to send signal.
Yes
11
Check if connecting or con­tacting part has no problem.
Replace indoor P.C. board.
No
50
Make sure the unit emits a beep tone.
Operation Indicator lamp on the unit flashes.
Yes
Replace outdoor P.C.board.
Before the unit resumes normal operation.
•Release the checking mode on remote con­troller by pressing Reset button, and then send the unit signal to stop operation.
•Turn off power supply to indoor/outdoor units.
•Get indoor terminal blocks of 11and open,and reconnect in-out wiring.
Be sure to turn off power supply to indoor/out-
[ ]
door units in replacing P.C.board.
33
In checking mode,Operation Indicator
[ ]
lamp does not indicate its actual state.
END
TEST POINT DIAGRAM AND VOLTAGE
32F50 68 86 104 122 140
MSH09NW Indoor electronic control P.C. board
CN201 No.1
Power supply input AC115V
}
CN201 No.1
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
Varistor(NR11)
Fuse AC250V 3.0A
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12)
JPS
Timer short mode point
JPG
51
TEST POINT DIAGRAM AND VOLTAGE
32F50 68 86 104 122140
MSH12NN, MSH15NN, MSH17NN Indoor electronic control P.C. board
Fan motor power supply
VLo Me Lo Hi
8 7 5 6 4 3 2 1
Varistor(NR11)
Fuse AC250V 3.0A
Power supply input AC115V
}
JP17
+
JP16
--
DC12V
}
CN201
JP11
+
DC5V
JP24
JPS JPG
CN112 CN111
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
}
--
Time short mode point
Indoor coil thermistor (RT12)
Room temperature thermistor (RT11)
52
MUH09NW
˚F
-4 14 32 50 68 86 104
MUH12NN MUH15NN MUH17NN
Outdoor fan motor
AC115V(MUH09) AC208/230V(MUH12/15/17)
Solenoid coil
AC115V(MUH09) AC208/230V(MUH12/15/17)
}
}
R601 DC5~10V
}
INPUT
+
--
DEICER P.C. BOARD
AC115V(MUH09) AC208/230V(MUH12/15/17)
Defrost thermistor(RT61)
}
}
--
}
DC12V
Fuse 2A/250V
Defrost interval time short pin
+
J8
DC5V
}
J7
--
+
+
}
52C
DC12V
--
Defrost termination temperature change. Jumper wire JPC and JPE.
53
RELAY OPERATION MSH09NW MSH12NN MSH15NN MSH17NN
MODE
COOL & COOL mode of I FEEL CONTROL
DRY & DRY mode of I FEEL CONTROL
HEAT & HEAT mode of I FEEL CONTROL
NOTE : When the compressor is OFF, “3-minute time delay circuit” operates.
THERMOSTAT
ON
OFF
ON
OFF
ON ON
OFF
52C CONTACTOR
ON
OFF
OFF for 2 min.after system
Repeats 8 min. ON/3min. OFF operation or 2 min. ON/3 min. OFF operation
Repeates 4 min. OFF/1 min. ON operation
OFF
COIL FROST PREVENTION mode are as follows
MODE
THERMOSTAT
52C CONTACTOR
INDOOR FAN RELAY
AUTO or set speed
AUTO or set
AUTO or set speed links with 52C con­tactor.
AUTO or set speed
VLo speed
INDOOR FAN RELAY
COOL & COOL mode of I FEEL CONTROL
ON
DRY & DRY mode of I FEEL CONTROL
Off for 5 min. After that, OFF is pro­longed until indoor coil thermistor reads termination temper­ature.
Indoor fan relay mode (MSH12NN,MSH15NN)
Indoor fan speed
Hi
Me
Lo
VLo
OFF
Relay turning ON
SR144 SR143 SR142 SR141
All fan relays are off
AUTO or set speed
VLo speed
54
12
DISASSEMBLY INSTRUCTIONS
NOTE:
On the wiring diagram shows the terminals with a lock mechanism, so it
cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger.
12-1 MSH09NW
INDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws caps of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
Slide the sleeve.Pull the wire while pushing
the locking lever.
Photo 1
Front panel
2. Removing the electronic control P.C. board and the display P.C. board.
(1) Remove the front panel. (Refer to 1) (2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the terminal cover.
Remove the screw of the terminal block. (4) Remove the cord clamp. (5) Disconnect the room temperature thermistor and the con-
nector from the indoor coil thermistor. (6) Remove the screw of the ground wire. (7) Remove the electronic control P.C. board and the display
P.C. board.
Photo 2
Screw
Room temperature thermistor connector
Ground wire screw
Cord clamp
Terminal block cover
Indoor electronic
control P.C.board
Terminal block cover screw
55
OPERATING PROCEDURE PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Remove the electronic control P.C. board and the display
P.C. board.(Refer to 2) (4) Remove the ground wire of the indoor heat exchanger. (5) Unhook the catches (both upper and lower), remove the
electrical box.
4. Removing the vane motor
(1) Remove the front panel. (2) Remove the screw of the vane motor, disconnect the con-
nector. (3) Remove the vane motor.
5. Removing the line flow fan and the indoor fan motor
(1) Remove the front panel. (Refer to 1) (2) Disconnect the connector from the vane motor. (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly. (4) Lifting the left side of the heat exchanger, remove the elec-
trical box. (5) Remove the fixture of the fan motor. (6) Remove the hexagon socket set screws. (7) Remove the line flow fan and the fan motor.
Photo 3
Photo 4
Vane motor screw
Drain hose
Vane motor
56
Fan motor catches
Fan motor fixture
Indoor coil thermistor
12-2 MSH12NN , MSH15NN, MSH17NN
INDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws caps of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board
(1) Remove the front panel. (Refer to 1) (2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the terminal cover.
Remove the screw of the terminal block. (4) Unhook the catch of the lamp holder. (5) Remove the receiver holder. (6) Disconnect the connectors on the electronic control
P.C. board and remove the ground and the indoor coil ther-
mistor. (7) Remove the electronic P.C. board.
Photo 1
Photo 2
Ground
Front panel
Screws
Indoor coil thermistor
Screw
Terminal block screw
Electronic control P.C. board
57
OPERATING PROCEDURE PHOTOS
3. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel.(Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con trol P.C. board. Remove the ground wire of the indoor heat exchanger.
(5) Unhook the catches (both upper and lower), remove the
electrical box.
(6) Unhook the catch on the both sides of the nozzle
assembly. (7) Remove the nozzle assembly. (8) Remove the screws of the bearing support. (9) Remove the screw of the heat exchanger and unhook the
catch.
(10) Lifting the heat exchanger, remove the bearing support. (11) Remove the motor support. (12) Loose the screw securing the line flow fan, remove the
line flow fan.
(13) Remove the screws of the side cover, remove the fan
motor.
Photo 3
Catch
Heat exchanger
screw
Bearing support screws
Photo 4
Heat exchanger
Indoor fan motor
Line flow fan Motor band
Fan motor screws
58
12-3 MUH09NW
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove screws securing the top panel. (2) Remove the screw securing the service panel. (3) Remove screws securing the cabinet. (4) Remove the service panel,and remove the screw from the
insides. (5) Remove the top panel. (6) Remove the cabinet.
Photo 1
Screw for service panel
Service panel
Screw for top plate
Screws for cabinet
2. Removing the propeller fan and the outdoor fan motor
(1) Remove the cabinet.(Refer to 1) (2) Remove the propeller fan nuts. (3) Remove the propeller fan.
NOTE:Loose the propeller fan in the rotating direction for
removal. When attaching the propeller fan,align the mark on the propeller fan and the motor shaft cut section. Set the fan in position by using the cut on the shaft and
the mark on the fan.
(4) Remove lead clamps and disconnect the outdoor fan motor
lead wires. (5) Remove screws securing the fan motor. (6) Remove the outdoor fan motor.
Photo 2
Screw for cabinet
Photo 3
propeller fan
Outdoor fan motor
Set screws for outdoor fan motor
Propeller fan nut
Screw for top plate
Lead clamps
59
OPERATING PROCEDURE PHOTOS
3. Removing the compressor
(1) Remove the lead clamps. (2) Remove the screws securing the relay panel. (3) Remove the screw securing the service port. (4) Remove the terminal cover. (5) Pull out the lead from the compressor terminal. (6) Remove the overcurrent relay. (7) Remove the compressor nuts. (8) Detach the suction pipe welded section and discharge pipe
welded section with a burner.
NOTE
Before using a torch, rechin gas from the pipes until the pres­sure gauge shows 0 PSIG.
Use the burner under the condition that gas can be released even when the inner pressure rises by heat.
Reclain all refrigerant in an environmentally acceptable man­ner.
Photo 4
Terminal cover
compressor Suction pipe
Discharge pipe
60
12-4 MUH12NN , MUH15NN
OUTDOOR UNIT
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
Photo 1
Screws
Service panel
Photo 2
Screw
Screws
2. Removing the electrical parts
(1) Remove the service panel and the cabinet. (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan connector
•Terminal block
Photo 3
Connector
Compressor capacitor
Terminal block
Screw
61
OPERATING PROCEDURE
PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector and remove the clamp of fan
motor lead wire. (3) Remove the propeller fan nut and remove the propeller fan. (4) Remove screws securing the fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the terminal cover on the compressor (3) Disconnect lead wires from the glass terminal of the com-
pressor.(Refer to 2) (4) Release gas from the refrigerant circuit. (5) Disconnect the welded part of the discharge pipe. (6) Disconnect the welded part of the suction pipe. (7) Remove nuts securing the compressor. (8) Remove the compressor.
Photo 4
Propeller fan
Photo 5
Propeller fan nut
Discharge pipe
Clamp
Connector
Set screw for outdoor fan motor
NOTE
Reclaim all refrigerant in an environmentally acceptable man­ner.
Terminal cover
Compressor fan
Suction pipe
Compressor nuts
62
12-5 MUH17NN
Outdoor controller board
Transformer
Capacitor
Contactor
Terminal block
Screws
Propeller fan
Motor support
Separator support plate
High-pressure switch
Lead connectors
Valve bed
Crankcase heater
Propeller nut
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet and electrical parts
(1) Remove the top panel (3 screws in front, 2 screws in rear) (2) Remove the cover panel (1 screw).
The panel is anchored by clicks to the side panel. Remove by pulling towards you.
(3) Remove the cover panel (1 screw).
The panel is anchored by clicks on the right and left sides. After removing the screw, pull the panel down and remove it by pulling towards you.
Photo 1
Photo 2
Screws
Front panel
Top panel
Service panel
Cover panel
2. Removing the outdoor fan motor
(1) Remove the front panel (3 screws).
Open the panel to a 45 degree angle and lift to remove. The
panel is clasped at three points on the left side. (2) Remove the propeller fan (1 set nut). (3) Remove the fan motor (3 screws).
Remove the lead connectors.
Photo 3
63
OPERATING PROCEDURE PHOTOS
Heat exchanger
Accumulator
Charge plug
Ball valve
Compressor
3. Removing the heat exchanger and compressor
(1) Remove the rear panel (2 screws in front, 1 screw on the
side, 3 screws in the rear). Remove the valve bed, and open the rear panel to the rear to remove.
NOTE :
All panels are clasped, and must be removed by shifting up and down.
(2) Remove the right side panel (4 screws). (3) Remove the rear guard (3 screws). (4) Remove the separator support plate (4 screws). (5) Remove the motor support (2 screws). (6) Remove the valve bed (5 screws). The valve bed is
clasped on the right and left sides. Lift to remove.
(7) Remove the electrical parts box.
Remove the respective connectors from highpressure switch, crank case heater, shell thermo, and fan motor
lead. (8) Remove the separator (2 screws). (9) Remove the heat exchanger (2 screws).
Disconnect the welded section of pipe.
(10) Remove the compressor (3 set nuts).
Remove the weldment of the compressor suction pipe and
discharge pipe.
Photo 4
Screws
Photo 5
Screws
64
Photo 6
13
1 2 3 4 5 6
FRONT PANEL(WH) GRILL(WH) AIR FILTER BOX(WH) INSTALLATION PLATE SCREW CAP(WH)
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 2 1 1 2
1PC/SET
2PCS/SET
RemarksPart No.
NO.
Part Name
MSH09NW
(WH) E02 289 000 E02 151 010 E02 164 100 E02 166 234 E02 151 970 E02 166 067
1 2 3
INDOOR HEAT EXCHANGER UNION(GAS) UNION(LIQUID)
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1
{ 3/8 { 1/4
RemarksPart No.
NO.
Part Name
MSH09NW
(WH) E02 155 620 E02 155 666 E02 151 667
PARTS LIST
INDOOR UNIT STRUCTURAL PARTS MSH09NW (WH)
1
5
6
2
3
4
Optional parts (See page 74.)
INDOOR UNIT HEAT EXCHANGER MSH09NW (WH)
3
2
1
65
INDOOR UNIT
E02 199 520 E02 166 040 E02 141 702 E02 151 303 E02 268 300 E02 151 505 E02 151 302 E02 151 509 E02 151 308 E02 151 307 E02 289 375 E02 289 450 E02 268 452 E02 268 382 E02 001 504 E02 151 468 E02 268 385
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17
NOZZLE(WH) VANE(WH) DRAIN HOSE VANE MOTOR INDOOR FAN MOTOR RUBBER MOUNT LINE FLOW FAN BEARING MOUNT ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL BLOCK ELECTRONIC CONTROL P.C.BOARD AUTO RESTART FUSE SLEEVE BEARING RECEIVER VARISTOR
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1
FAN GUARD
2PCS/SET
250V3A
RemarksPart No.
NO.
Part Name
MV MF
RT11 RT12
TB
F11
NR11
MSH09NW
(WH)
ELECTRICAL PARTS MSH09NW(WH)
8
15
3
2
7
9
6
5
1
4
10
12
Part number that are circled is not shown in the illustration.
66
OUTDOOR UNIT
E02 096 232 E02 085 297 E02 199 521 E02 085 245 E02 289 630 E02 289 900 E02 047 506 E02 289 290 E02 096 662 E02 096 661 E02 289 515 E02 289 936 E02 290 936 E02 289 937 E02 268 351 E02 289 967
1 2 3 4 5 6 7 8
9 10 11
12
13 14
CABINET TOP PANEL FAN GUARD SERVICE PANEL OUTDOOR HEAT EXCHANGER COMPRESSOR COMPRESSOR RUBBER SET BASE STOP VALVE(LIQUID) STOP VALVE(GAS) MOTOR SUPPORT CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE OUTDOOR FAN CAPACITOR REVERSING VALVE
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1
RH-140WGJT 2RUBBER 3SPRING
{ 1/4 { 3/8
{ 0.12{ 0.06335-7/16 { 0.12{ 0.5511-13/16 { 0.12{ 0.06319-11/16
5.0+/250VAC
RemarksPart No.
NO.
Part Name
MC
MUH09NW
STRUCTURAL PARTS MUH09NW
5
2
1
4
3
11
14
9
10
7
8
6
Part number that are circled is not shown in the illustration.
67
OUTDOOR UNIT
E02 085 501 E02 289 301 E02 289 353 E02 289 374 E02 289 310 E02 289 451 E02 289 490
1 2 3 4 5 6 7
PROPELLER FAN OUTDOOR FAN MOTOR COMPRESSOR CAPACITOR TERMINAL BLOCK DEFROST THERMISTOR DEICER P.C. BOARD SOLENOID COIL
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1 1 1 1
70+/220VAC
Remarks
Part No.
NO.
Part Name
MF
C1
TB
RT61
21S4
MUH09NW
FUNCTIONAL PARTS AND ELECTRICAL PARTS MUH09NW
5
6
1
Part number that are circled is not shown in the illustration.
2
4
3
68
INDOOR UNIT
1
2 3 4 5 6
7
FRONT PANEL(WH) FRONT PANEL(WH) FRONT PANEL(WH) GRILLE(WH) BOX(WH) AIR FILTER INSTALLATION PLATE SCREW CAP(WH) LAMP PANEL(WH)
LAMP PANEL(WH) LAMP PANEL(WH)
Symbol
in Wiring
Diagram
Q'ty/unit
1
1 1 2 1 3 1
1PC/SET
3PCS/SET
RemarksPart No.
NO.
Part Name
MSH12NN
(WH)
1
1 1 2 1 3
1
MSH15NN
(WH) E02 282 000 E02 283 000 E02 284 000 E02 138 010 E02 143 234 E02 141 100 E02 141 970 E02 143 067 E02 282 007 E02 283 007
E02 284 007
MSH17NN
(WH)
1 1 1 2 1 3
1
E02 141 620 E02 138 667 E02 138 666
1 2 3
INDOOR HEAT EXCHANGER UNION(LIQUID) UNION(GAS)
Symbol
in Wiring
Diagram
Q'ty/unit
1
1
1
{1/4 {5/8
RemarksPart No.
NO.
Part Name
MSH12NN,MSH15NN,MSH17NN
(WH)
STRUCTURAL PARTS MSH12NN (WH) MSH15NN (WH)
1
MSH17NN (WH)
2
5
3
Optional parts (See page 74.)
Part number that are circled is not shown in the illustration.
INDOOR UNIT HEAT EXCHANGER PARTS MSH12NN (WH) MSH15NN (WH)
MSH17NN (WH)
6
2
4
1
3
69
INDOOR UNIT
E02 138 520 E02 143 040 E02 141 702 E02 270 300 E02 272 300 E02 001 505 E02 268 452 E02 282 450 E02 283 450 E02 284 450 E02 268 382 E02 141 302 E02 141 303 E02 138 329 E02 141 509 E02 282 375 E02 141 468 E02 001 504 E02 138 307 E02 138 308 E02 268 385
1 2 3
4
5 6
7
8
9 10 11 12 13 14 15 16 17 18
NOZZLE(WH) VANE(WH) DRAIN HOSE INDOOR FAN MOTOR INDOOR FAN MOTOR RUBBER MOUNT AUTO RESTART ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD FUSE LINE FLOW FAN VANE MOTOR DISPLAY P.C. BOARD BEARING MOUNT TERMINAL BLOCK RECEIVER P. C. BOARD SLEEVE BEARING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR VARISTOR
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1
2 1 1
1 1 1 1 1 1 1 1 1 1 1
FAN GUARD
2PCS/SET
250V/3A
RemarksPart No.
NO.
Part Name
MF MF
F11
MV
TB
RT12 RT11 NR11
MSH12NN
(WH)
1 1 1 1
2 1
1
1 1 1 1 1 1 1 1 1 1 1
MSH17NN
(WH)
MSH15NN
(WH)
1 1 1
1 2 1
1 1 1 1 1 1 1 1 1 1 1 1
ELECTRICAL PARTS MSH12NN (WH) MSH15NN (WH) MSH17NN (WH)
15
12
3
11
9
7
5
4
5
16
13
2
Part number that are circled is not shown in the illustration.
70
1
10
17
14
OUTDOOR UNIT STRUCTURAL PARTS MUH12NN MUH15NN
1
17
19
18
12
8
10
4
21
15
2
Part number that are circled is not shown in the illustration.
E02 141 232
1
E02 141 521
2
E02 270 245
3
E02 139 630
4
E02 283 630 E02 139 515
5
E02 271 900
6
E02 282 900 E02 156 290
7
E02 270 301
8
E02 141 501
9
E02 271 353
10
E02 282 340
11
E02 282 374
12
E02 285 936 E02 283 936
13
E02 282 936 E02 282 937 E02 075 506
14
E02 139 662
15
E02 150 661
16
E02 270 233
17
E02 282 451
18
E02 139 310
19
E02 172 490
20
E02 282 961
21
CABINET GRILLE SERVICE PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER MOTOR SUPPORT COMPRESSOR COMPRESSOR BASE OUTDOOR FAN MOTOR PROPELLER FAN COMPRESSOR CAPACITOR COMPRESSOR CONTACTOR TERMINAL BLOCK CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE COMPRESSOR RUBBER SET STOP VALVE(LIQUID) STOP VALVE(GAS) BACK PANEL DEICER P.C. BOARD DEFROST THERMISTOR SOLENOID COIL REVERSING VALVE
9
Symbol
in Wiring
Diagram
MC MC
MF
C1
52C
TB
RT61
21S4
5
14
MUH12NN
6
1 1 1 1
1
1 1 1 1 1 1 1 1
2 1 3 1 1 1 1 1 1 1
7
Q'ty/unit
16
MUH15NN
1 1 1
1 1 1
1 1 1 1 1 1
1 2 1 3 1 1 1 1 1 1 1
3
RemarksPart No.NO. Part Name
RH-207NHDT RH-185NHDT
30+/370VAC
{0.12{0.07119-11/16 {0.12{0.07923-5/8 {0.12{0.05511-13/16 {0.12{0.0797-7/8
3RUBBER
{1/4 {5/8
71
OUTDOOR UNIT STRUCTURAL PARTS MUH17NN
1
3 8 11 4
2
16
19
18 21
5
14
13
2015
17
72
6
10
9
7
OUTDOOR UNIT
E02 214 232
E02 214 297
E02 214 521
E02 214 245
E02 284 630
E02 272 900
E02 075 506
E02 284 290
E02 284 662
E02 010 661
E02 214 515
E02 138 936
E02 257 936
E02 214 501
E02 284 301
E02 272 353
E02 282 374
E02 214 310
E02 282 451
E02 172 490
E02 282 961
E02 282 340
1 2 3 4 5 6 7 8
9 10 11
12 13
14 15 16 17 18 19 20 21
CABINET TOP PANEL FAN GUARD SERVICE PANEL OUTDOOR HEAT EXCHANGER COMPRESSOR COMPRESSOR RUBBER SET BASE STOP VALVE(LIQUID) STOP VALVE(GAS) MOTOR SUPPORT CAPILLARY TUBE CAPILLARY TUBE (
{0.12{0.0799-13/16
) PROPELLER FAN OUTDOOR FAN MOTOR COMPRESSOR CAPACITOR TERMINAL BLOCK DEFROST THERMISTOR DEICER P.C. BOARD SOLENOID COIL REVERSING VALVE COMPRESSOR CONTACTOR
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RH-231NHDT 3RUBBER
 {1/4 {3/8
{0.12{0.07927-9/16 {0.12{0.07919-11/16
35+/370VAC
RemarksPart No.NO. Part Name
MC
MF C1 TB
RT61
21S4
MUH17NN
E02 141 426 E02 141 083
1 2
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
Symbol
in Wiring
Diagram
Q'ty/unit
1 1
RemarksPart No.NO. Part Name
MSH09NW
(WH)
1 1
MSH12/15/17NN
(WH)
STRUCTURAL PARTS MUH17NN
ACCESSORY AND REMOTE CONTROLLER PARTS MSH09NW (WH) MSH12NN (WH) MSH15NN (WH) MSH17NN (WH)
2
1
73
14
MAC - 440PI
MAC - 441PI MAC - 442PI MAC - 443PI MAC - 670PI MAC - 671PI MAC - 672PI MAC - 673PI MAC - 674PI
0
5
0
5
13
C 13/16
D1-1/16
C 1-7/32
D 1-1/16
1/4
3/8
5/8
10ft
16ft 23ft 33ft 10ft 16ft 23ft 33ft 49ft
MSH09NW
Applicable
Model
Part No.
Pipe size O.D
Pipe length
Cross-section A-Gas(in.) B-Liquid(in.) Insulation(in.)
Additional refrigerant
charge
R-22(Oz)
MSH12NN MSH15NN MSH17NN
OPTIONAL PARTS
1. REFRIGERANT PIPES
The air conditioner has flared connections its on indoor and outdoor sides. Please use the optional extension pipe as follows.
2. AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Part No. Model
MAC-1000FT MSH09NW
MAC-1100FT MSH12NN,MSH15NN,MSH17NN
3. DEODORIZING FILTER
DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odors of pets.
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
Part No. Model
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
74
MAC-1500DF MSH09NW
MAC-1600DF
MSH12NN,MSH15NN,MSH17NN
CC
Copyright 1997 MITSUBISHI ELECTRIC ENGINIEERING CO.,LTD
Issued in Jul. 1997. No.OB198 5042
New publication, effective Jul. 1997 Specifications subject to change without notice.
3400 Lawrenceville Suwanee Road Suwanee, Georgia 30024
Toll Free: 800-433-4822 Toll Free Fax: 800-889-9904
Specifications are subject to change without notice.
www.mrslim.com
Loading...