Mitsubishi Electric MSH09TW, MUH09TW, MSH12TN, MUH12TN, MSH15TN Service Manual

...
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
L
I
S
T
E
D
CUS
SERVICE MANUAL
Wireless type Models
MSH09TW · MUH09TW MSH12TN · MUH12TN MSH15TN · MUH15TN MSH17TN · MUH17TN MSH09TW MSH12TN
MSH15TN MSH17TN
-
-
-
-
· MUH09TW
· MUH12TN
· MUH12TN
· MUH15TN
· MUH15TN
· MUH17TN
Revision:
MUH12TN- has been added.
MUH15TN- has been added.
REFRIGERANT SYSTEM DIAGRAM of
MXZ30TN and MXZ30TN2 has partly been changed.
PARTS LIST of MXZ30TN and MXZ30TN2 has partly been changed
Please void OB275 Revised edition-C.
U2 U2
No. OB275
REVISED EDITION-D
U1U1
-
U1U1
-
U2
-
U1U1
-
U2
-
U1U1
-
Inverter-controlled multi system Model
Indication of
MSH12TN MSH15TN MSH17TN INDOOR UNIT
MUH15TN OUTDOOR UNIT
MSH12TN - MSH15TN - MSH17TN -
MUH15TN - MUH15TN -
U1 U1 U1
model name
Remote controller
Indication of model name
U2U1
· MXZ30TN
· MXZ30TN2
CONTENTS
1. FEATURES·························································2
2. TECHNICAL CHANGES····································5
3. PART NAMES AND FUNCTIONS······················7
4. INDOOR UNIT COMBINATION························10
5. SPECIFICATION···············································11
7. OUTLINES AND DIMENSIONS·······················39
8. WIRING DIAGRAM ··········································43
9. REFRIGERANT SYSTEM DIAGRAM··············51
10. MICROPROCESSOR CONTROL ····················54
11. SERVICE FUNCTIONS·····································72
12. TROUBLESHOOTING ······································75
13. DISASSEMBLY INSTRUCTIONS···················101
14. PARTS LIST····················································114
15. OPTIONAL PARTS·········································126
The Slim Line. From Mitsubishi Electric.
TM
Page 2
1
MSH12TN ­MSH15TN ­MSH17TN -
U1
U1
U1
MSH12TN MSH15TN MSH17TN
MSH09TW
MSH09TW -
U1
MUH09TW
MUH09TW -
U1
MUH15TN -
U1
MUH15TN -
U2
U1
MUH15TN
MUH17TN -
U1
MUH17TN
MXZ30TN MXZ30TN2
LCD wireless remote controller
MUH12TN
MUH12TN-
U2
MUH12TN-
USA Remark
MSH09TW MSH12TN MSH15TN MSH17TN
No
40min.
27˚F
38˚F
CANADA
RT63(Outdoor): for protection in low ambient temperature
Refer to
U1 U1 U1 U1
DIFFERENT POINTS between models for USA and CANADA
AMBIENT TEMPERATURE THERMISTOR
INTERVAL TIME
START TEMPERATURE
FINISH TEMPERATURE
DEFROSTING
Have
15min.
32˚F
50˚F
8. WIRING DIAGRAM
10. MICRO PROCESSOR CONTROL 10-1. -HEAT mode of "I FEEL CONTROL"-
5. Outdoor temperature control(P. 60)
10. MICRO PROCESSOR CONTROL 10-1. -HEAT mode of "I FEEL CONTROL"-
3. Defrosting (P.59)
11. SERVICE FUNCTIONS 11-2. CHANGE IN DEFROST SETTING(P.72)
for protection in low ambient temperature
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
Model
FEATURES
2
Page 3
SWING
Model Cooling capacity Heating capacity SEER HSPF(44/55)
MSH09TW MSH09TW - 8,800Btu/h 10,500Btu/h 10.0 6.8/5.9 MSH12TN MSH12TN - 12,600/12,900Btu/h 13,000/13,500Btu/h 10.2 6.8/5.9 MSH15TN MSH15TN - 14,300/14,600Btu/h 14,500/14,800Btu/h 10.7 6.8/5.9 MSH17TN MSH17TN - 16,000/16,200Btu/h 16,800/17,200Btu/h 10.4 6.8/5.9
U1
U1
U1
U1
“I FEEL CONTROL” IN OUR LCD WIRELESS REMOTE CONTROLLER WITH ON/OFF PROGRAM TIMER
Mitsubishi Electric’s new wireless remote controller incorporates a number of advanced features that provide even greater con-
trol and ease-to-use. It has a liquid crystal display which indicates such information as mode, fan speed and temperature selected as well as the programmed ON/OFF timer. It is also equipped with “I Feel Control”, a unique Mitsubishi Electric fea­ture that allows the user to adjust the temperature to exactly the level he or she wants simply by tapping the button that describes present conditions : “Too Cool” or “Too Warm”. The optimum temperature set this way is then memorized for immedi­ate recall whenever the air conditioner is used again.
Select desired air flow direction. REMOTE-CONTROL OPERATION MODE
Using the remote controller, you can select from five airflow set­tings to match room layout and the location of people. Also, you can set the vane to swing automatically.
AUTO-RESTART FUNCTION
The auto-restart function restarts the equipment when power is
restored following an outage automatically. Operation resumes in the mode in which the equipment was running immediately before the outage.
HIGH PERFORMANCE ROTARY COMPRESSOR
The advanced design of Mitsubishi Electric’s powerful and energy
efficient rotary compressor results in lower operating costs and longer service life.
3
Page 4
Time
Set Temperature
Conventional model
Inverter model
MXZ30TN MXZ30TN2
Time
Set Temperature
Conventional Model:
Temperature are adjusted by switching the compressor off and on.
Inverter Model:
Uniform temperatures are maintained by finely tuned control of compressor speed.
Optimum Comfort in Any Situation
Model Cooling capacity Heating capacity SEER HSPF(44)
MXZ30TN MXZ30TN2
28,400Btu/h
(4,160 - 30,500)
28,600Btu/h
(5,790 - 38,000)
11.0 7.5
Inverter Technology
Outdoor unit uses inverter compressor technology (Variable Frequency Drive) to provide exceptional indoor high-speed cooling and heating. By responding to indoor temperature changes, the system reduces power consumption by varying the compressor speed for extra energy savings and performs only to the levels needed to maintain a constant and comfortable indoor environment.
Extra Energy Savings
For optimum performance inverter technology controls the electrical current to the compressor, delivering only the energy needed to match the cooling and heat load of a room. This feature reduces energy consumption.
High-Speed Heating and Cooling
Compressor rotation is controlled to maximize efficiency, changing speeds according to the cooling and heating load of a room. This application means the desired temperature is reached much faster.
Optimum Comfort Year-Round
Unlike conventional units that start and stop repetitively, inverter units are able to detect subtle changes in room temperature and adjust airflow automatically. This adaptation means less temperature variation and more comfortable rooms.
4
Page 5
2
TECHNICAL CHANGES
MSH09NW2 ➔ MSH09TW
1. Indoor unit has changed.
2. Remote controller has changed.
MSH12NN2 MSH12TN
1. Remote controller has changed.
2. Union size of connect pipe for gas has changed.
MSH15NN2 MSH15TN MSH17NN2 MSH17TN
1. Remote controller has changed.
MUH09NW2 MUH09TW
1. Outdoor unit has changed.
MUH12NN2 MUH12TN
1. Outdoor unit has changed.
MUH15NN2 MUH15TN
1. Only model name has changed.
MUH17NN2 MUH17TN
1. Valve type has changed (Size for connecting pipe is the same).
MSH09NW2 - MSH09TW -
1. Indoor unit has changed.
2. Remote controller has changed.
MSH12NN2 - MSH12TN -
1. Remote controller has changed.
2. Union size of connect pipe for gas has changed.
MSH15NN2 - MSH15TN ­MSH17NN2 - MSH17TN -
1. Remote controller has changed.
MUH09NW2 - MUH09TW -
1. Outdoor unit has changed.
MUH12NN2 - MUH12TN -
1. Outdoor unit has changed.
MUH15NN2 - MUH15TN -
1. Only model name has changed.
U1U1
U1U1
U1U1
U1U1
U1U1
U1U1
U1U1
MUH17NN2 - MUH17TN -
1. Valve type has changed (Size for connecting pipe is the same).
MXZ30TN
1. New model.
U1U1
5
Page 6
MXZ30TN MXZ30TN2
1. Noise filter P.C. board has changed to improve the capacity for protecting the inverter-controlled circuit when the voltage higher than the rated one is aupplied with the inverter-controlled circuit.
2. Noise filter P.C. board for “MXZ30TN” and “MXZ30TN2” are not interchangeable.
3. Service parts have been changed as follows according to above change;
•The value of R(resistor)has changed. 10➔ 20
•TB5(terminal block) has been removed.
MUH12TN - MUH12TN ­MUH15TN - MUH15TN -
U2U1
U2U1
1. Outdoor haet exchanger has changed.
Outdoor haet exchanger for “TN - ” and “TN - ” are not interchangeable.
U2U1
6
Page 7
3
Installation plate Installation plate fixing screw 4 x 25 mm(0.16 x 0.98 in.) Remote controller mounting hardware Fixing screw for 3 3.5 x 16 mm(0.14 x 0.63 in.) (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 5 1 2 2 1 1
1 2 3 4 5 6 7
MSH12TN MSH15TN MSH17TN
MSH09TW MSH09TW -
U1
1 6 1 2 2 1 1
MSH12TN
-
MSH15TN
-
MSH17TN
-
U1
U1
U1
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSH09TW MSH09TW -
Deodorizing filter(option) (gray sponge type)
Air cleaning filter(option) (white bellows type)
Front panel
Air filter
Vertical vanes
Operation section
(When the grille is opened)
MSH09TW MSH09TW -
U1
U1
Grille
MSH12TN MSH15TN MSH17TN
MSH12TN ­MSH15TN ­MSH17TN -
U1 U1 U1
Air inlet
Remote control receiving section
Model indication
Model indication
Horizontal vane
Remote controller
MSH09TW MSH09TW -
U1
Emergency operation switch
MSH12TN MSH12TN ­MSH15TN MSH15TN ­MSH17TN MSH17TN -
U1 U1 U1
Emergency operation switch
ACCESSORIES
MSH12TN MSH12TN ­MSH15TN MSH15TN ­MSH17TN MSH17TN -
7
U1 U1 U1
Operation indicator lamp
Receiving section
Page 8
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
(back and side)
OUTDOOR UNIT
Air inlet
Air outlet
(back and side)
Model indication
MUH09TW MUH09TW ­MUH12TN MUH12TN -
MUH12TN -
MXZ30TN MXZ30TN2
U1
U1
U2
MUH15TN
MUH15TN ­MUH15TN -
U1
MUH17TN MUH17TN -
U2
U1
8
Page 9
REMOTE CONTROLLER
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
STOP
START
HR.
MIN.
I FEEL
COOL
HEAT
DRY
PM
CLOCK
AM
RESET CLOCK
Open the front lid.
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
VANE CONTROL button
CLOCK SET button
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
U1 U1 U1
U1
9
Page 10
4
09
12
15
17
09+09
09+12
09+15
09+17
12+12
09+09+09
09+09+12
90
90
90
90
90
90
90
90
90
90
90
4.0
4.9
4.9
8.6
8.6
8.9
8.9
10.5
10.6
13.6
14.9
4.5
5.4
5.4
9.5
9.5
9.9
9.9
11.6
11.7
15.1
16.4
8,800
13,660
8,800
(4,160~9,210)
12,900
(5,600~15,350)
14,600
(5,600~17,010)
16,200
(6,470~18,720)
17,600
(5,470~18,680)
21,700
(6,240~22,760)
23,400
(6,240~24,030)
25,000
(6,220~27,170)
25,800
(6,300~27,900)
26,400
(9,740~29,150)
28,400
(9,940~30,500)
1,030
(510~1,280)
1,250
(510~1,680)
1,250
(510~1,780)
2,200
(500~2,620)
2,200
(550~3,230)
2,280
(540~3,270)
2,280
(540~3,430)
2,680
(550~4,000)
2,700
(540~4,100)
3,500
(700~4,500)
3,800
(810~4,610)
8,800
12,900
14,600
16,200
12,900
8,800
7,370
8,800
12,900
14,600
16,200
8,800
8,800
8,800
8,800
12,900
8,800
7,370
Indoor units combination
Unit A Unit B Unit C
Cooling capacity (BTU/h)
Total
Outdoor unit
power consumption
(W)
Current
(A)
Power
factor
(%)
208V 230V
NOTE: Electrical data is for outdoor unit only.
MXZ30TN MXZ30TN2
09
12
15
17
09+09
09+12
09+15
09+17
12+12
09+09+09
09+09+12
90
90
90
90
90
90
90
90
90
90
90
4.3
4.7
5.5
6.3
7.6
8.6
9.4
10.6
9.9
10.6
11.0
4.8
5.2
6.1
6.9
8.4
9.6
10.4
11.7
10.9
11.8
12.1
9,530
12,960
10,500
(5,790~16,950)
13,500
(6,420~22,400)
14,800
(6,470~23,180)
17,200
(6,520~23,550)
21,000
(6,520~26,900)
24,000
(6,730~30,000)
25,300
(7,490~32,240)
27,700
(8,140~37,100)
27,000
(7,660~36,890)
28,590
(8,900~37,500)
28,600
(9,040~38,000)
1,100
(560~1,990)
1,200
(560~2,340)
1,400
(570~2,480)
1,600
(600~2,710)
1,950
(620~2,900)
2,210
(640~3,130)
2,400
(640~3,360)
2,700
(690~3,900)
2,520
(650~3,850)
2,720
(710~3,920)
2,800
(710~3,970)
10,500
13,500
14,800
17,200
13,500
9,530
7,820
10,500
13,500
14,800
17,200
10,500
10,500
10,500
10,500
13,500
9,530
7,820
Indoor units combination
Unit A Unit B Unit C
Heating capacity (BTU/h)
Total
Outdoor unit
power consumption
(W)
Current
(A)
Power
factor
(%)
208V 230V
INDOOR UNITS COMBINATION
10
Page 11
5
Item
Model
MSH09TW -
Capacity
Power consumption
EER [SEER] HSPF IV(V) COP INDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor Auxiliary heater
Airflow Low—Med.—High Moisture removal
Sound level Low-Med.-High Cond. drain connection O.D.
Dimensions Weight
OUTDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor
Compressor
Refrigerant control Sound level Defrost method
Dimensions Weight
REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING Pipe size (Min. wall thickness)
Connection method Between the indoor
& outdoor units Refrigerant charge (R22) Refrigerating oil (Model)
Btu/h Btu/h Btu/h
W W
V, phase, Hz
A A
F.L.A
A(kW)
CFM CFM
pt./h
dB(A)
in. in. in. in. Ib.
V, phase, Hz
A A
F.L.A
R.L.A L.R.A
dB(A)
in. in. in. Ib.
in. in.
ft. ft.
lb.
oz.
8,800
10,500
5,300
890 890 820
9.9 [10.0]
6.8 (5.9)
3.46
White
115, 1, 60
15
0.5
0.37 –
198-244-297
173(145)-226(187)-279(233)
2.3
26-31-36
5/8
33-1/2
7-1/2
10-15/16
20
Munsell 5Y 7/1
115, 1, 60
20 16
0.60
RH140WGJT
C-R 0.83 C-S 1.48
12.0
42.0
Capillary tube
47
Reverse cycle
30-23/32
10-1/32
21-1/4
82
Wireless type
12V DC
Not supplied (optional parts)
1/4 (0.0265) 3/8 (0.0285)
Flared
Flared Max. 25 Max. 49
2 Ib. 3 oz.
9.3 (MS56)
1 3
1
12
1
12
Cooling Heating 47 Heating 17 Cooling Heating 47 Heating 17 Cooling Heating Heating
MSH09TW
MSH09TW - MSH09TW
U1
U1
MUH09TW - MUH09TW
U1
HEAT Dry COOL Dry(Wet)
W D H
Model Winding resistance (at 68˚F)
W D H
Liquid Gas Indoor Outdoor Height difference Piping length
1
Cooling Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
SPECIFICATIONS
NOTE : Test conditions are based on ARI 210/240.
1 : Rating conditions(cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, (75˚FWB)2 : (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
3 : (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 82˚FDB, 65˚FWB
Operating Range
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
11
Page 12
Item
Model
MSH12TN
MSH15TN
Capacity
Power consumption
EER [SEER] HSPF IV (V) COP INDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor Auxiliary heater
Airflow Low—Med.—High Moisture removal
Sound level Low-Med.-High Cond. drain connection O.D.
Dimensions Weight
OUTDOOR UNIT MODEL External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor
Compressor
Refrigerant control Sound level Defrost method
Dimensions Weight
REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING Pipe size (Min. wall thickness)
Connection method Between the indoor
& outdoor units Refrigerant charge (R22) Refrigerating oil (Model)
Btu/h Btu/h Btu/h
W W
V, phase, Hz
A A
F.L.A
A(kW)
CFM CFM
pt./h
dB(A)
in. in. in. in. Ib.
V, phase, Hz
A A
F.L.A
R.L.A L.R.A
dB(A)
in. in. in. Ib.
in. in.
ft. ft.
lb.
oz.
12,600/12,900 13,000/13,500
6,800/7,000 1,280/1,310 1,180/1,250 1,110/1,140
9.8/9.8[10.2/10.2]
3.23/3.17
311-339-388
3.3
15
0.42
RH189NHDT
49
30-23/32
10-1/32
21-1/4
86
1/2 (0.0285)
2 Ib. 12 oz.
6.8/6.8 (5.9/5.9)
White
115, 1, 60
15
0.6
0.43 –
360-395-452
36-39-42
5/8
39-15/16
7-1/2
12-5/8
31
Munsell 5Y7/1 208/230, 1, 60
14
C-R 1.68 C-S 2.78
10.0
35.0
Capillary tube Reverse cycle
Wireless type
12V DC
Not supplied (optional parts)
1/4 (0.0265)
Flared
Flared Max. 25 Max. 50
16.1 (MS56)
14,300/14,600 14,500/14,800
8,700/8,900 1,350/1,380 1,250/1,300 1,210/1,240
10.6/10.6 [10.7/10.7]
3.40/3.34
293-321-367
4.7
20
0.52
RH207NHDT
53
33-7/16 11-7/16
23-13/16
99
5/8 (0.0315)
3 lb. 3 oz.
1 3
1
12
1
12
Cooling Heating 47 Heating 17 Cooling Heating 47 Heating 17 Cooling Heating Heating
(208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V)
MSH12TN -
MSH15TN -
MSH12TN
MSH12TN -
U1
MSH15TN
MSH15TN -
U1
U1
MUH12TN
MUH12TN -
U1 U2
MUH15TN
MUH15TN -
U1 U2
U1
Dry Wet
W D H
Model Winding resistance (at 68˚F)
W D H
Liquid Gas Indoor Outdoor Height difference Piping length
Cooling Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
NOTE : Test conditions are based on ARI 210/240.
1 : Rating conditions(cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, (75˚FWB)2 : (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
3 : (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 82˚FDB, 65˚FWB
Operating Range
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
12
Page 13
Item Model
1
Capacity
Power consumption
1 3
EER [SEER] HSPF IV (V) COP
Cooling Heating 47 Heating 17 Cooling
1
Heating 47 Heating 17 Cooling Heating Heating
(208/230V)
1
(208/230V)
2
(208/230V) (208/230V)
1
(208/230V)
2
(208/230V) (208/230V) (208/230V) (208/230V)
Btu/h Btu/h Btu/h
INDOOR UNIT MODEL
W W
MSH17TN
MSH17TN MSH17TN ­External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor Auxiliary heater
Airflow Low—Med.—High
Dry
Wet Moisture removal Sound level Low-Med.-High Cond. drain connection O.D.
W Dimensions
D
H Weight OUTDOOR UNIT MODEL
V, phase, Hz
A A
F.L.A
A(kW)
CFM CFM
pt./h
dB(A)
in. in. in. in. lb.
MUH17TN MUH17TN ­External finish Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor
V, phase, Hz
A A
F.L.A
Model
Compressor
Winding resistance (at 68˚F)
R.L.A
L.R.A Refrigerant control Sound level
dB(A)
Defrost method
in. in. in. lb.
Dimensions Weight
W D H
REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING Pipe size (Min. wall thickness)
Connection method Between the indoor
& outdoor units
Liquid Gas Indoor Outdoor Height difference
Piping length Refrigerant charge (R22) Refrigerating oil (Model)
NOTE : Test conditions are based on ARI 210/240.
1 : Rating conditions (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, (75˚FWB)2 : (heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
3 : (cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 82˚FDB, 65˚FWB
(heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
Operating Range
Cooling Heating
Maximum
Minimum
Maximum
Minimum
in. in.
ft. ft.
lb.
oz.
Indoor intake air temperature
95˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
13
MSH17TN -
16,000/16,200 16,800/17,200 10,100/10,300
1,560/1,580 1,500/1,570 1,410/1,510
10.3/10.3 (10.4/10.4)
6.8/6.8 (5.9/5.9)
3.28/3.21 White
115, 1, 60
15
0.7
0.51 –
406-441-491 342-371-413
5.1
40-43-45
5/8
39-15/16
7-1/2
12-5/8
31
Munsell 5Y 7/1
208/230, 1, 60
20 15
0.75
RH231NHDT
C-R 1.65 C-S2.67
11.0
38.0
Capillary tube
53
Reverse cycle
34-1/4 11-5/8 33-1/2
128
Wireless type
12V DC
Not supplied (optional parts)
1/4 (0.0265) 5/8 (0.0315)
Flared
Flared Max. 25 Max. 50
4lb. 14oz.
16.1 (MS56)
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
U1
U1
U1
Page 14
Indoor unit
w Max. Height difference 25ft.
Outdoor unit
Refrigerant Piping
Max.length
A
w Height difference should be within 25ft. regardless of which unit, indoor or outdoor position is high.
Outside
diameter
Minimum
Wall
thickness
Outside
diameter
Minimum
Wall
thickness
MSH09TW MUH09TW
MSH12TN MUH12TN
MSH15TN MUH15TN
MSH17TN MUH17TN
MSH09TW­MUH09TW-
MSH12TN­MUH12TN­MUH12TN-
MSH15TN­MUH15TN­MUH15TN-
MSH17TN­MUH17TN-
Additional piping
Max. length : ft.
A
50
Gas
Piping size : in. Length of connecting pipe : in.
Liquid
Indoor unit
Outdoor unit
Model
U1 U1
U1 U1 U2
U1 U1 U2
U1 U1
Gas :
Liquid :00
Gas :
Liquid :
16-15/16 19-11/16
[ 3/8
[ 1/2
 
 
[ 5/8
[ 1/4
0.0285
0.0315
0.0265
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
14
Page 15
Item Model
Cooling
Heating
Mode
1: "A" Cooling Steady State at rated compressor Speed3: "B-2" Cooling Steady State at rated compressor Speed
"B-1" Cooling Steady State at minimum compressor Speed Low ambient Cooling Steady State at minimum compressor Speed Intermediate Cooling Steady State At Intermediate compressor Speed
w
1: Standard Rating-Heating at rated compressor Speed 2: Low temperature Heating at rated compressor Speed
Max temperature Heating at minimum compressor Speed High temperature Heating at minimum compressor Speed Frost Accumulation at rated compressor Speed Frost Accumulation at Intermediate compressor Speed
w
Test
Indoor air condition Outdoor air condition Dry bulb
Wet bulb
Dry bulb
Wet bulb
80 80 80 80 80 70 70 70 70 70 70
67 67 67 67 67 60 60 60 60 60 60
95 82 82 67 87 47 17 62 47 35 35
(75) (65) (65)
(53.5)
(69)
43 15
56.5 43 33 33
w
At Intermediate compressor Speed
=("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
Unit: ˚F
Capacity
Power consumption
1 3
EER [SEER] HSPF IV (V) COP
Cooling
1
Heating 47 Heating 17 Cooling
1
Heating 47 Heating 17 Cooling Heating Heating
12
12
Btu/h Btu/h Btu/h
OUTDOOR UNIT MODEL External finish Power supply
V, phase, Hz Max. fuse size (time delay) Min. circuit ampacity Fan motor
F.L.A
Model
Compressor
Winding resistance (at 68˚F)
R.L.A
L.R.A Refrigerant control Sound level
dB(A) Defrost method
W
Dimensions
D
H Weight REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING Pipe size (Min. wall thickness)
Connection method Between the indoor
& outdoor units
Liquid
Gas
Indoor
Outdoor
Height difference
Piping length (a+b+c) Refrigerant charge (R22) Refrigerating oil (Model)
W W
in. in. in. lb.
in. in.
ft. ft.
lb.
oz.
Triple-Unit Double-Unit Single-Unit
28,400/(9,940~30,500) 28,600/(9,040~38,000)
(18,100) 3,800/(810~4,610) 2,800/(710~3,970)
(2,310)
11.0
7.5
3.08
MXZ30TN MXZ30TN2
Munsell 5Y 8/1
208/230, 1, 60 A A
30 25
1.0
THV-247FBA
U-V 0.61 V-W 0.61 W-U 0.61
15 72
LEV
47
Reverse cycle
35-7/16
12-19/32 (+1+3/8)
35-7/16
176
Wireless type
12V DC
Not supplied (optional parts)
1/4 (0.0265)
A:1/2(0.0285), B,C:3/8(0.0285)
Flared Flared
Max. 33
Max. 200
8lb. 10oz.
26.7 (MS56)
NOTE : Test conditions are based on ARI 210/240.
15
Page 16
a
b
c
Outdoor unit
Indoor units
H
H
H
Liquid {1/4 Gas {3/8 Liquid {1/4 Gas {1/2 Liquid {1/4 Gas {5/8 Liquid {1/4 Gas {3/8 Liquid {1/4 Gas {1/2 Liquid {1/4 Gas {5/8
Use a different-diameter pipe of the option MAC-455JP ({1/2 {3/8)
Use a different-diameter pipe of the option MAC-456JP ({1/2 {5/8)
Indoor unit can be connected directly
Indoor unit can be connected directly
Use a different-diameter pipe of the option MAC-454JP ({3/8 {1/2)
It is not possible to connect
09
12
15/17
09
12
15/17
Outdoor unit
A
Liquid {1/4
Gas {1/2
B, C
Liquid {1/4
Gas {3/8
Indoor unit Connection method
Cooling Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95˚FDB, 71˚FWB 67˚FDB, 57˚FWB 80˚FDB, 67˚FWB 70˚FDB, 60˚FWB
Outdoor intake air temperature
115˚FDB
67˚FDB 75˚FDB, 65˚FWB 17˚FDB, 15˚FWB
Operating Range MXZ30TN MXZ30TN2
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ30TN MXZ30TN2
Piping length each indoor unit (a, b, c) 82ft. MAX. Total piping length (a+b+c) 200ft. MAX. Height difference between units (H) 33ft. MAX. Bending point for each unit 25 MAX. Total bending point 60 MAX.
It does not matter which unit is higher.
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe. For further information on Different-diameter pipe,see page 128.
Indoor unit
class Pipe diameter
09
12
15/17
Liquid 1/4 Liquid 1/4
Gas 3/8 Gas 3/8
Liquid 1/4 Liquid 1/4
Gas 1/2 Gas 1/2
Liquid 1/4 Liquid 1/4
Gas 5/8 Gas 5/8
Extension pipe diameter
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Indoor unit C
Liquid 1/4
Gas 1/2
Liquid 1/4
Gas 3/8
Liquid 1/4
Gas 3/8
Unit : inch
Please connect the indoor unit and the outdoor unit as shown in the table below.
16
Page 17
6
Model
Indoor air Outdoor intake air DB temperature(˚F
)
71 67 63 71 67 63 71 67 63
TC
15.8
15.0
14.1
17.9
16.9
15.9
19.8
18.8
17.7
SHC
9.1
10.6
11.9
9.2
11.0
12.5
10.1
12.0
13.7
TPC
1.17
1.10
1.05
1.23
1.16
1.10
1.41
1.33
1.26
TC
14.8
13.9
13.0
16.7
15.8
14.7
18.5
17.5
16.4
SHC
8.5
9.9
11.0
8.6
10.2
11.6
9.4
11.2
12.7
TPC
1.28
1.21
1.16
1.35
1.28
1.22
1.54
1.46
1.40
TC
13.9
12.9
12.1
15.7
14.6
13.7
17.4
16.2
15.2
SHC
8.0
9.2
10.2
8.1
9.5
10.8
8.8
10.4
11.8
TPC
1.38
1.31
1.25
1.45
1.38
1.32
1.66
1.58
1.51
TC
12.9
12.0
11.0
14.6
13.6
12.5
16.2
15.1
13.9
SHC
7.4
8.5
9.3
7.5
8.8
9.8
8.2
9.6
10.7
TPC
1.45
1.39
1.34
1.52
1.46
1.41
1.75
1.67
1.61
TC
11.9
11.0
10.1
13.4
12.5
11.4
14.9
13.9
12.6
SHC
6.8
7.8
8.5
6.9
8.1
8.9
7.6
8.9
9.8
TPC
1.51
1.45
1.39
1.59
1.53
1.46
1.82
1.75
1.67
IWB
(˚F)
75 85 95 105 115
MSH12TN MSH12TN -
MSH15TN MSH15TN -
MSH17TN MSH17TN -
NOTE 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
3
Btu/h), SHC : Sensible Heat Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor intake air DB temperature.
U1
U1
U1
(230V)
DATA
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
6-1. PERFORMANCE DATA
1) COOLING CAPACITY
(115V)
Indoor air Outdoor intake air DB temperature(˚F
MSH09TW MSH09TW -
(208V)
MSH12TN MSH12TN -
MSH15TN MSH15TN -
MSH17TN MSH17TN -
Model
U1
Model
U1
U1
U1
IWB
(˚F)
71 67 63
Indoor air Outdoor intake air DB temperature(˚F
IWB
(˚F)
71 67 63 71 67 63 71 67 63
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
75 85 95 105 115
TC
SHC
TPC
10.8
6.1
0.79
10.2
7.1
0.75
9.6
8.0
0.71
75 85 95 105 115
TC
SHC
TPC
15.4
8.9
1.14
14.6
10.4
1.08
13.7
11.6
1.02
17.5
9.1
1.20
16.6
10.8
1.13
15.6
12.2
1.08
19.6
9.9
1.39
18.6
11.9
1.31
17.4
13.5
1.25
MUH09TW ­MUH12TN - MUH12TN ­MUH15TN - MUH15TN ­MUH17TN -
TC
SHC
10.1
5.7
9.5
6.7
8.9
7.4
TC
SHC
14.4
8.3
13.6
9.7
12.7
10.7
16.4
8.5
15.4
10.0
14.4
11.3
18.3
9.3
17.3
11.1
16.2
12.5
TPC
0.87
0.82
0.79
TPC
1.25
1.18
1.13
1.32
1.25
1.19
1.52
1.44
1.38
U1
U1
TC
9.5
8.8
8.3
TC
13.5
12.6
11.8
15.4
14.3
13.4
17.2
16.0
15.0
SHC
5.4
6.2
6.9
SHC
7.8
8.9
10.0
7.9
9.3
10.5
8.7
10.2
11.6
TPC
0.93
0.89
0.85
TPC
1.34
1.28
1.22
1.42
1.35
1.29
1.64
1.56
1.49
TC
8.8
8.2
7.5
TC
12.6
11.7
10.8
14.3
13.3
12.2
16.0
14.9
13.7
U2U1
U2U1
)
SHC
5.0
5.7
6.3
)
SHC
7.3
8.3
9.1
7.4
8.6
9.6
8.1
9.5
10.6
TPC
0.98
0.94
0.91
TPC
1.41
1.36
1.31
1.49
1.43
1.38
1.72
1.65
1.59
TC
8.1
7.5
6.9
TC
11.6
10.8
9.8
13.2
12.2
11.2
14.7
13.7
12.5
SHC
4.6
5.3
5.7
SHC
6.7
7.6
8.3
6.8
7.9
8.7
7.5
8.8
9.7
TPC
1.02
0.99
0.94
TPC
1.47
1.42
1.36
1.55
1.50
1.43
1.79
1.73
1.65
17
Page 18
Model
Refrigerant piping length (one way : ft.)
1.0
25 (std.)
0.954
40
0.927
49
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW­MSH12TN­MSH15TN­MSH17TN-
U1
U1
U1
U1
2) COOLING CAPACITY CORRECTIONS
(230V)
Model
Indoor air Outdoor intake air WB temperature(˚F
)
75 70 65 75 70 65 75 70 65
TC
7.8
8.3
8.5
8.6
9.1
9.3
10.0
10.6
10.8
TPC
0.93
0.90
0.86
0.97
0.94
0.90
1.17
1.13
1.08
TC
9.8
10.1
10.6
10.7
11.1
11.6
12.5
12.9
13.5
TPC
1.09
1.07
1.03
1.14
1.11
1.07
1.37
1.34
1.30
TC
11.7
11.9
12.4
12.8
13.1
13.5
14.9
15.2
15.7
TPC
1.22
1.19
1.16
1.27
1.24
1.20
1.53
1.49
1.45
TC
13.2
13.5
13.9
14.4
14.8
15.2
16.8
17.2
17.7
TPC
1.28
1.25
1.22
1.33
1.30
1.27
1.61
1.57
1.53
TC
13.6
13.9
14.3
14.9
15.2
15.7
17.3
17.7
18.2
TPC
1.30
1.28
1.24
1.35
1.33
1.29
1.63
1.60
1.55
TC
15.4
15.7
16.1
16.9
17.2
17.6
19.6
20.0
20.5
TPC
1.35
1.33
1.30
1.40
1.38
1.35
1.70
1.66
1.63
IDB (˚F)
15 25 35 43 45 55
MSH12TN MSH12TN -
U1
MSH15TN MSH15TN -
U1
MSH17TN MSH17TN -
U1
NOTE: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
(208V)
Model
Indoor air Outdoor intake air WB temperature(˚F
)
75 70 65 75 70 65 75 70 65
TC
7.5
8.0
8.2
8.4
8.9
9.1
9.7
10.3
10.6
TPC
0.88
0.85
0.81
0.93
0.90
0.86
1.12
1.08
1.04
TC
9.4
9.8
10.2
10.5
10.9
11.4
12.2
12.6
13.2
TPC
1.03
1.01
0.97
1.09
1.07
1.03
1.31
1.28
1.24
TC
11.2
11.5
11.9
12.5
12.8
13.3
14.5
14.9
15.4
TPC
1.15
1.12
1.09
1.22
1.19
1.16
1.46
1.43
1.39
TC
12.7
13.0
13.4
4.1
14.5
14.9
16.4
16.8
17.3
TPC
1.21
1.18
1.15
1.28
1.25
1.22
1.54
1.50
1.46
TC
13.1
13.4
13.8
14.6
14.9
15.4
16.9
17.3
17.8
TPC
1.23
1.20
1.17
1.30
1.28
1.24
1.56
1.53
1.49
TC
14.8
15.1
15.5
16.5
16.9
17.3
19.2
19.6
20.0
TPC
1.27
1.25
1.23
1.35
1.33
1.30
1.62
1.59
1.56
IDB (˚F)
15 25 35 43 45 55
MSH12TN MSH12TN -
U1
MSH12TN - U2
MSH15TN MSH15TN -
U1
MSH15TN - U2
MSH17TN MSH17TN -
U1
(115V)
Model
Indoor air Outdoor intake air WB temperature(˚F
)
75 70 65
TC
6.1
6.5
6.6
TPC
0.66
0.64
0.61
TC
7.6
7.9
8.2
TPC
0.78
0.76
0.73
TC
9.1
9.3
9.6
TPC
0.87
0.85
0.82
TC
10.2
10.5
10.8
TPC
0.91
0.89
0.87
TC
10.6
10.8
11.1
TPC
0.93
0.91
0.88
TC
12.0
12.2
12.5
TPC
0.96
0.94
0.93
IDB (˚F)
15 25 35 43 45 55
MSH09TW MSH09TW -
U1
3) HEATING CAPACITY
18
Page 19
6-2. PERFORMANCE CURVE
71 67 63
71 67 63
65 70 75
75 70 65
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air DB temperature (°F)
Indoor intake air WB temperature (
°F)
Indoor intake air WB temperature (
°F)
Cooling
SHF at rating condition = 0.70
= 233CFM = 0.23
Airflow
Bypass Factor
12
10
8
6
1.2
65 75 85 95 105 115
0.8
0.6
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Indoor intake air DB temperature (
°F)
Heating
= 297CFM
Airflow
12
14
10
8
6
1.1
1.0
15 25 35 45 55
0.8
0.6
0.7
0.9
1.0
NOTE : The curves shows peformance under 230V AC.
As for under 208V AC, refer to PERFORMANCE DATAon page 17 and 18.
MSH09TW MUH09TW
MSH09TW ­MUH09TW -
U1
U1
19
Page 20
MSH12TN
71
67
63
71 67 63
16
14
10
12
2
1
Indoor intake air WB temperature (
°
F)
Indoor intake air WB temperature (
°
F)
65 70 75
75 70 65
20
16
8
12
1.6
0.6
Cooling
SHF at rating condition = 0.71
= 388CFM = 0.15
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air DB temperature (°F)
Indoor intake air DB temperature (
°
F)
Heating
= 452CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
Outdoor intake air WB temperature (°F)
0.8
1.0
1.2
1.4
Indoor intake air DB temperature (
°
F)
MUH12TN
MSH12TN ­MUH12TN ­MUH12TN -
U1 U1 U2
20
Page 21
MSH15TN
71 67 63
71 67 63
65 70 75
75 70 65
Indoor intake air WB temperature (
°
F)
Cooling
SHF at rating condition = 0.65
= 367CFM = 0.22
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
22
18
14
10
2
Outdoor intake air DB temperature (°F)
Indoor intake air DB temperature (
°
F)
Heating
= 452CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
20
16
8
1.4
0.8
Outdoor intake air WB temperature (°F)
1
12
1.0
1.2
0.6
Indoor intake air DB temperature (
°
F)
Indoor intake air WB temperature (
°
F)
MUH15TN
MSH15TN ­MUH15TN ­MUH15TN -
U1 U1 U2
21
Page 22
MSH17TN
71 67
63
71 67 63
65 70 75
75 70 65
Indoor intake air WB temperature (
°
F)
Indoor intake air WB temperature (
°
F)
Cooling
SHF at rating condition = 0.64
= 413CFM = 0.24
Airflow
Bypass Factor
65 75 85 95 105 115
Total power consumption (kW) Total capacity ( 10 Btu/h)
24
20
16
12
2
1
Outdoor intake air DB temperature (°F)
Indoor intake air DB temperature (
°
F)
Indoor intake air DB temperature (
°
F)
Heating
= 491CFM
Airflow
15 25 35 45 55
Total power consumption (kW) Total capacity ( 10 Btu/h)
20
16
12
8
2.0
1.0
Outdoor intake air WB temperature (°F)
1.2
1.6
1.4
1.8
MUH17TN
MSH17TN ­MUH17TN -
U1 U1
22
Page 23
6-3. Condensing pressure MSH09TW MSH09TW -
U1
(Cooling)
(PSIG)
300
Data is based on the condition of indoor humidity 50%. Air flow should be set to High speed.
280
260
240
220
200
Condensing pressure
180
160
140
68 70 75 80 85 90 95 100 104(°F)
MSH09TW MSH09TW-
Indoor DB temperature (
Outdoor ambient temperature
U1
(Heating)
°F)
Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost.
86
(PSIG)
80 75
100
70
90
80
70
60
Suction pressure
50
40
68 70 75 80 85 90 95 100 104(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80
75 70
(PSIG)
310 300 290 280 270 260 250 240 230 220 210 200
Condensing pressure
190 180 170 160 150
5 10152025303540455055606570(°F)
Indoor DB temperature(
Outdoor ambient temperature
°F)
75 70
65
23
(PSIG)
80
70
60
50
40
30
Suction pressure
20
10
5 10152025303540455055606570(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
75 70 65
Page 24
MSH12TN MSH12TN­(Cooling)
(PSIG)
320
U1
Data is based on the condition of indoor humidity 50%. Air flow should be set to High speed.
300
280
260
240
220
Condensing pressure
200
180
160
140
68 70 75 80 85 90 95 100 104(°F)
MSH12TN MSH12TN -
Indoor DB temperature (
Outdoor ambient temperature
U1
(Heating)
°F)
Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost.
86 80 75 70
(PSIG)
100
90
80
70
Suction pressure
60
50
40
Indoor DB temperature (°F)
68 70 75 80 85 90 95 100 104(°F)
Outdoor ambient temperature
86 80
75 70
(PSIG)
310 300 290 280 270 260 250 240 230 220 210 200
Condensing pressure
190 180 170 160 150
5 10152025303540455055606570(°F)
Indoor DB temperature(°F)
Outdoor ambient temperature
(PSIG)
(PSIG)
80
70
60
75
50
70
40
65
30
Suction pressure
Suction pressure
20
10
24
75 70 65
Indoor DB temperature (°F)
Indoor DB temperature (°F)
10 15 20 25 30 35 40 45 50 55 60 65 70(°F)
5
Outdoor ambient temperature
Page 25
MSH15TN MSH15TN­(Cooling)
(PSIG)
320
U1
Data is based on the condition of indoor humidity 50%. Air flow should be set to High speed.
300
280
260
240
220
200
Condensing pressure
180
160
140
68 70 75 80 85 90 95 100 104( F)
MSH15TN MSH15TN­(Heating)
Indoor DB temperature (°F)
Outdoor ambient temperature
U1
Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost.
86 80 75 70
(PSIG)
100
90
80
70
60
Suction pressure
50
40
68 70 75 80 85 90 95 100 104( F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80
75 70
(PSIG)
290 280 270 260 250 240 230
220 210 200
Condensing pressure
190 180 170
160 150
510152025303540455055606570( F)
Indoor DB temperature(
Outdoor ambient temperature
°F)
75 70
65
(PSIG)
25
80
70
60
50
40
30
Suction pressure
20
10
510152025303540455055606570( F)
Indoor DB temperature (
Outdoor ambient temperature
°F)
75 70 65
Page 26
MSH17TN MSH17TN­(Cooling)
(PSIG)
320
U1
Data is based on the condition of indoor humidity 50%. Air flow should be set to High speed.
300
280
260
240
220
Indoor DB temperature (°F)
200
Condensing pressure
180
160
140
68 70 75 80 85 90 95 100 104( F)
MSH17TN MSH17TN­(Heating)
Outdoor ambient temperature
U1
Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost.
86 80 75 70
(PSIG)
100
90
80
70
60
Suction pressure
50
40
68 70 75 80 85 90 95 100 104( F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75
70
(PSIG)
300 290 280 270 260 250 240 230
220 210 200
Condensing pressure
190 180 170 160 150
510152025303540455055606570( F)
Indoor DB temperature(
Outdoor ambient temperature
°F)
75 70
65
(PSIG)
26
80
70
60
50
40
30
Section pressure
20
10
510152025303540455055606570( F)
Indoor DB temperature (
Outdoor ambient temperature
°F)
75 70 65
Page 27
6-4. STANDARD OPERATION DATA
MSH09TW MSH09TW - U1
INDOOR UNIT
115V 60Hz 1[, 2 wires
•Both wirings can be applied to all MODELS.
OUTDOOR UNIT
115V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
115V 60Hz 1[, 2 wires
Disconnect switch
Model
Item
Capacity
Total
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor unit
SHF Input Indoor unit Power supply (V, phase, Hz) Input Fan motor current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input Comp. current Fan motor current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge (R22)
Intake air temperature
Discharge air temperature
Fan speed (High) Airflow (High)
Intake air temperature
Fan speed Airflow
DB
WB
DB
WB
DB
WB
Unit
Btu / h
kW
kW
A A
kW
A
A PSIG PSIG
˚F ˚F ˚F ˚F
ft. — ˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
8,800
0.70
235
70 179 113
52 157
80
67
59
57 950
233(Wet)
95
MSH09TW MSH09TW -
0.89
MSH09TW MSH09TW -
115,1,60
0.035
0.34 –
MUH09TW MUH09TW -
115, 1, 60
0.855
6.91
0.59
25
2 lb. 3 oz.
640 985
U1
Heating
10,500
U1
U1
223
60 171 110
35 146
70
60 100
1,000
297(Dry)
47
43
POWER SUPPLY
27
Control voltage
Power supply voltage to serial signal circuit is 12V DC.
11
Peak voltage between
­and 33+ on in-out terminal block is 12V DC .
Page 28
Cooling
12,600/12,900
0.71
1.28/1.31
1.233/1.263
5.74/5.21
259
84 194 120
67 177
80
67
57
56
388[Wet]
95
Capacity (208/230V) SHF Input (208/230V) Indoor unit Power supply (V, phase, Hz) Input Fan motor current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input (208/230V) Comp. current (208/230V) Fan motor current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge (R22)
Intake air temperature
Discharge air temperature
Fan speed (High) Airflow (High)
Intake air temperature
Fan speed (208/230V) Airflow (208/230V)
Unit
Btu / h
kW
kW
A A
kW
A
A PSIG PSIG
˚F ˚F ˚F ˚F ft. — ˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
14,300/14,600
0.65
1.35/1.38
1.303/1.333
5.91/5.41
246
80 146 112
58 161
80
67
57
54
367[Wet]
95
Heating
14,500/14,800
1.25/1.30
1.203/1.253
5.41/5.11
230
57 158 108
33 143
70
60 107
452[Dry]
47
43
Heating
13,000/13,500
1.18/1.25
1.133/1.203
5.24/5.01
203
58 158 103
36 144
70
60 100
452[Dry]
47
43
DB
WB
DB
WB
DB
WB
Item
Model
Total
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor unit
MSH12TN MSH12TN -
U1
MSH12TN MSH12TN -
U1
115, 1, 60
0.047
0.41 –
MUH12TN MUH12TN -
U1 U2
208/230, 1, 60
0.36/0.39
25
2 Ib. 12 oz.
1,200
700/740
974/1,034
MSH15TN MSH15TN -
U1
MSH15TN MSH15TN -
U1
115, 1, 60
0.047
0.41 –
MUH15TN MUH15TN -
U1 U2
208/230, 1, 60
0.49
25
3 Ib. 3 oz.
1,200
830/900
1,288/1,394
MSH12/15TN MSH12/15TN - U1
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz 1[, 2wires
208/230V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
INDOOR UNIT
OUTDOOR UNIT
208/230V 60Hz 1[, 3 wires
115V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
•Both wirings can be applied to all MODELS.
115V
•Outline of MUH12TN( ) is same as one of MUH09TW.
- U1 , - U2
Disconnect switch
POWER SUPPLY
28
Control voltage
Power supply voltage to serial signal circuit is 12V DC. Peak voltage between 11­and 33+ on in-out terminal block is 12V DC .
Page 29
Model
MSH17TN MSH17TN - U1
INDOOR UNIT
OUTDOOR UNIT
115V 60Hz 1[, 2 wires
208/230V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
INDOOR UNIT
OUTDOOR UNIT
208/230V 60Hz 1[, 3 wires
115V 60Hz 1[, 2wires
SIGNAL WIRE 2 wires 12V DC
•Both wirings can be applied to all MODELS.
115V
Disconnect switch
Item
Capacity (208/230V)
Total
Electrical circuit
Refrigerant circuit
SHF Input (208/230V) Indoor unit Power supply (V, phase, Hz) Input Fan motor current Aux. heater current Outdoor unit Power supply (V, phase, Hz) Input (208/230V) Comp. current (208/230V) Fan motor current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp Ref. pipe length Refrigerant charge (R22)
Intake air temperature
Indoor unit
Outdoor unit
Discharge air temperature
Fan speed (High) Airflow (High)
Intake air temperature
Fan speed (208/230V) Airflow (208/230V)
POWER SUPPLY
Unit
Btu / h
kW
kW
A A
kW
A
A PSIG PSIG
˚F ˚F ˚F ˚F ft. —
DB
WB
DB
WB
DB
WB
˚F ˚F ˚F ˚F
rpm
CFM
˚F ˚F
rpm
CFM
Cooling
16,000/16,200
0.64
1.56/1.58
1.506/1.526
6.69/6.19
243
77 165 113
48 150
80
67
56
54
413[Wet]
95
MSH17TN MSH17TN -
MSH17TN MSH17TN -
115,1,60
0.054
0.47 –
MUH17TN MUH17TN -
208/230, 1, 60
0.61
25
4 lb. 14 oz.
1,290
740/800
1,606/1,730
Control voltage
Power supply voltage to serial signal circuit is 12V DC. Peak voltage between 11­and 33+ on in-out terminal block is 12V DC .
U1
Heating
16,800/17,200
1.50/1.57
U1
U1
1.446/1.516
6.39/6.09
242
63 162 112
35 144
70
60 109
491[Dry]
47
43
29
Page 30
Capacity SHF Input Outdoor unit Power supply (V, phase, Hz) Input Comp. current Fan motor current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp. shell bottom temp
Ref. pipe length [Total pipe length for multi-system]
Refrigerant charge (R22)
Intake air temperature
Fan speed (208/230V) Airflow (208/230V)
Unit
Btu / h
kW
kW
A
A PSIG PSIG
˚F ˚F ˚F ˚F
ft.
— ˚F ˚F
rpm
CFM
Heating
28,600
2.8
2.8
12.3
219
47
169
26
144
47 43
DB WB
Item
Model
Total
Electrical circuit
Refrigerant circuit
Outdoor unit
Cooling
28,400
3.8
3.8
17.1
300
65
194
41
150
95
MXZ30TN MXZ30TN2
208/230, 1, 60
0.60
127
82 [197]
8 lb. 10 oz.
630/675
1,764/1,906
MXZ30TN MXZ30TN2
INDOOR UNIT
MXZ30TN MXZ30TN2
115V 60Hz 1[, 2 wires
208/230V 60Hz 1[, 2 wires
SIGNAL WIRE 2 wires 12V DC
INDOOR UNIT
INDOOR UNIT
115V 60Hz 1[, 2 wires
115V 60Hz 1[, 2 wires
POWER SUPPLY
30
Control voltage
Power supply voltage to serial signal circuit is 12V DC. Peak voltage between 11­and 33+ on in-out terminal block is 12V DC .
Page 31
6-5. OPERATING RANGE
MUH09TW MUH12TN
MUH15TN MUH17TN MXZ30TN MXZ30TN2
Indoor unit
Outdoor unit
Rating
115V 60Hz 1[
208/230V 60Hz 1[
Guaranteed Voltage
MSH09TW MSH12TN MSH15TN MSH17TN
Model
MUH09TW­MUH12TN-
MUH12TN­MUH15TN­MUH15TN­MUH17TN-
MSH09TW­MSH12TN­MSH15TN­MSH17TN-
U1
U1
U1
U1
U1
U1
U2
U1
U2
U1
Min. 103V
Max. 127V
115V
Min. 198V Max. 253V
208V
230V
78%
w
At Intermediate compressor Speed
=("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
Function
Cooling
Heating
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Standard temperature
Maximum temperature
Minimum temperature
DB (˚F)
80 95 67
70 80 70
WB (˚F)
67 71 57
60 67 60
Indoor
DB (˚F)
95
115
67
47 75 17
WB (˚F)
— — —
43 65 15
Outdoor
Condition
Intake air temperature
Function
Cooling
Heating
"A" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
"B-1" Cooling Steady State at minimum compressor Speed
Low ambient Cooling Steady State at minimum compressor Speed
Intermediate Cooling Steady State At Intermediate compressor Speedw
Standard Rating-Heating at rated compressor Speed
Low temperature Heating at rated compressor Speed
Max temperature Heating at minimum compressor Speed
High temperature Heating at minimum compressor Speed
Frost Accumulation at rated compressor Speed
Frost Accumulation at Intermediate compressor Speedw
DB (˚F)
80 80 80 80 80 70 70 70 70 70 70
WB (˚F)
67 67 67 67 67 60 60 60 60 60 60
Indoor
DB (˚F)
95 82 82 67 87 47 17 62 47 35 35
WB (˚F)
(75) (65) (65)
(53.5)
(69)
43 15
56.5 43 33 33
Outdoor
Condition
Intake air temperature
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW­MSH12TN­MSH15TN­MSH17TN-
U1 U1 U1 U1
MXZ30TN MXZ30TN2
(1) POWER SUPPLY
(2) OPERATION
31
Page 32
6-6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
MSH09TW MSH09TW-
MSH12TN MSH12TN-
MSH15TN MSH15TN-
MSH17TN MSH17TN-
U1
U1
U1
U1
Mode
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
297 279 233 452 452 388 452 452 367 491 491 413
15.8
14.9
12.4
18.2
18.2
15.6
18.2
18.2
14.8
19.7
19.7
16.6
22.3
21.0
17.6
29.2
29.2
25.2
29.2
29.2
23.9
31.7
31.7
26.8
Air flow
(CFM)
Air speed
(ft./sec.)
Coverage range (ft.)
Function
Dry Dry
Wet
Dry Dry
Wet
Dry Dry
Wet
Dry Dry
Wet
MSH09TW MSH09TW­MUH09TW MUH09TW­MSH12TN MSH12TN­MUH12TN MUH12TN-
MUH12TN­MSH15TN MSH15TN­MUH15TN MUH15TN-
MUH15TN­MSH17TN MSH17TN­MUH17TN MUH17TN-
Outdoor unit
precharged
(up to 25ft.)
2 lb. 3 oz.
2 lb. 12 oz.
3 lb. 3 oz.
4 lb. 14 oz.
25ft.
0
30ft.
2.68
35ft.
5.36
Refrigerant piping length (one way)
40ft.
8.04
45ft.
10.72
49ft.
12.86
Model
U1 U1
U1
U1
U2
U1
U1
U2 U1 U1
6-7. ADDITIONAL REFRIGERANT CHARGE (R22(oz.))
The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizontally from the unit properly at the High speed position. The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture arranged inside the room.
W MXZ30TN and MXZ30TN2 do not have the necessity of additional refrigerant.
32
Page 33
MXZ30TN MXZ30TN2
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
09 class
(32Hz)
51.4
49.8
48.2
46.6
45.0
43.5
49.8
48.4
46.8
45.3
44.1
42.6
51.4
49.6
48.0
46.6
45.0
43.5
47.3
46.0
44.8
43.7 424
41.4
18 class
(73Hz)
15 class
(73Hz)
12 class
(46Hz)
80 85 90 95 100 105 110
80 85 90 95 100 105 110
79
75
72 68 64
79
75
72 68
64
Indoor unit class
(Inverter output
frequency)
Indoor air WB temperature
difference (degree)
72.0
68.7
65.7
62.6
59.5
56.5
53.4
50.4
74.7
71.4
68.2
64.8
61.5
58.3
55.0
51.6
86.2
82.0
77.9
73.8
69.6
65.3
61.2
57.8
68.4
65.7
62.8
59.9
57.2
54.3
51.6
48.7
09 class
(36Hz)
12 class
(65Hz)
15 class
(80Hz)
17 class
(80Hz)
14
20
30
40
50
59 68 79
60
14
20
30
40
50
60
59
68
79
Indoor unit class
(Inverter output
frequency)
Indoor air DB temperature
difference (degree)
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °FWB (2) Indoor outlet air wet-bulb temperature : °FWB (3) Outdoor intake air dry-bulb temperature : °FDB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °FDB (6) Outdoor intake air wet-bulb temperature : °FWB (7) Total input : W Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
Cooling
}
Heating
}
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. Compressor starts running at 33Hz (COOL) or 45Hz (HEAT). The frequency at each operation mode is fixed.
7. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
8. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT OUTDOOR UNIT
6-8. CAPACITY AND THE INPUT CURVES
33
Page 34
6-9. Capacity and input correction by means of inverter output frequency
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Frequency
<HEAT>Total input
Hz
1. 09-class unit in single operation
2. 12-class unit in single operation
3. 15-class unit in single operation
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Frequency
<HEAT>Total input
Hz
4. 17-class unit in single operation
(OUTDOOR UNIT:MXZ30TN MXZ30TN2)
34
Page 35
6-10. Outdoor low pressure and outdoor unit current
65 70 75 80 85 90 95 100 105 110 115
50
60
70
80
90
100
Ambient temperature(°F)
(°F)
86 80
75 70
Indoor DB temperature(°F)
65 70 75 80 85 90 95 100 105 110 115
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Ambient temperature(°F)
(°F)
15 20 25 30 35 40 45 50 55 60 65 70 75
4.0
5.0
6.0
7.0
8.0
9.0
Outdoor ambient temperature(°F)
Outdoor low pressure
Outdoor unit current (A)
Outdoor unit current (A)
45Hz
(PSIG)
33Hz
33Hz
65
75
70
86 80 75 70
Indoor DB temperature(°F)
Indoor DB temperature(°F)
1. 09-class unit in single operation (OUTDOOR UNIT : MXZ30TN MXZ30TN2)
(1) COOL operation
1Data is based on the condition of indoor
humidity 50%
2Air flow speed : High 3Inverter output frequency : 33Hz
(2) HEAT operation
Data is based on the condition of outdoor humidity 75%.
Set air flow to High speed.
Inverter output frequency is 45Hz.
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at High speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
35
Page 36
2. 12-class unit in single operation (OUTDOOR UNIT : MXZ30TN MXZ30TN2)
65 70 75 80 85 90 95 100 105 110 115
65
70
75
80
85
90
95
100
Ambient temperature(°F)
(°F)
86
80
75
70
86 80 75 70
15 20 25 30 35 40 45 50 55 60 65 70 75
4.0
5.0
6.0
7.0
8.0
9.0
Outdoor ambient temperature(°F)
65 70 75 80 85 90 95 100 105 110 115
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Ambient temperature(°F)
(°F)
(PSIG)
Outdoor low pressure
Outdoor unit current (A)
Outdoor unit current (A)
45Hz
33Hz
33Hz
65
70
75
Indoor DB temperature(°F)
Indoor DB temperature(°F)
Indoor DB temperature(°F)
(1) COOL operation
1Data is based on the condition of indoor
humidity 50%
2Air flow speed : High 3Inverter output frequency : 33Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at High speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
(2) HEAT operation
Data is based on the condition of outdoor humidity 75%.
Set air flow to High speed.
Inverter output frequency is 45Hz.
36
Page 37
4. 15-class unit in single operation (OUTDOOR UNIT : MXZ30TN MXZ30TN2)
65 70 75 80 85 90 95 100 105 110 115
65
70
75
80
85
90
95
100
Ambient temperature(°F)
(°F)
86
80
75
70
86 80 75 70
15 20 25 30 35 40 45 50 55 60 65 70 75
4.0
5.0
6.0
7.0
8.0
9.0
Outdoor ambient temperature(°F)
65 70 75 80 85 90 95 100 105 110 115
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Ambient temperature(°F)
(°F)
(PSIG)
Outdoor low pressure
Outdoor unit current (A)
Outdoor unit current (A)
45Hz
33Hz
33Hz
65
70
75
Indoor DB temperature(°F)
Indoor DB temperature(°F)
Indoor DB temperature(°F)
(1) COOL operation
1Data is based on the condition of indoor
humidity 50%
Air flow speed : High
Inverter output frequency : 33Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at High speed.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
(2) HEAT operation
Data is based on the condition of outdoor humidity 75%
Set air flow to High speed.
Inverter output frequency is 45Hz.
37
Page 38
5. 17-class unit in single operation (OUTDOOR UNIT : MXZ30TN MXZ30TN2)
65 70 75 80 85 90 95 100 105 110 115
65
70
75
80
85
90
95
100
Ambient temperature(°F)
(°F)
15 20 25 30 35 40 45 50 55 60 65 70 75
4.0
5.0
6.0
7.0
8.0
9.0
Outdoor ambient temperature(°F)
65 70 75 80 85 90 95 100 105 110 115
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Ambient temperature(°F)
(°F)
(PSIG)
Outdoor low pressure
Outdoor unit current (A)
Outdoor unit current (A)
45Hz
33Hz
33Hz
86 80 75 70
75 70 65
Indoor DB temperature(°F)
Indoor DB temperature(
°F)
Indoor DB temperature(°F)
(1) COOL operation
1Data is based on the condition of indoor
humidity 50%
Air flow speed : High
Inverter output frequency : 33Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 33Hz (COOL) or 45Hz (HEAT).
4.Indoor fan runs at High speed.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
(2) HEAT operation
Data is based on the condition of outdoor humidity 75%
Set air flow to High speed.
Inverter output frequency is 45Hz.
38
Page 39
7
OUTLINES AND DIMENSIONS
MSH09TW MSH09TW -
INDOOR UNIT
10-15/16
2-5/16
6-3/8
Wireless remote controller
U1
Installation plate
Indoor unit
32-3/16
33-1/2
6-1/224-3/42-1/4
3/4
MUH09TW MUH12TN MUH09TW ­MUH12TN - MUH12TN -
U2U1
3-5/16
1-5/8
3-1/4
Air in
U1
12-13/16 12-13/16
3/16
7-7/16
1/4 or more
2-5/8
3-15/16
Air out
3-1/16
REQUIRED SPACE
4 in. or more
6-5/8
1/8
4-5/8
Wall hole [2-9/16
Installation plate
Liquid line [1/4 19-11/16 Gas line [3/8 16-15/16
{
Insulation [1-7/16 O.D
[13/16 I.D
Drain hose [5/8 (Connected part O.D)
Insulation [1-1/8
Outdoor
unit
3/16
9-1/8
10-11/16
1-5/8
4 in. or more
Unit: inch
4 in.or more
OUTDOOR UNIT
Air in
12-19/32
1-1/4
4-9/32
Air in
Drainage 3holes [1-5/16
21-1/4
10-1/4
1-9/16
13/32
5-25/32
4-13/16
4-11/32
Airout
19-22/32
30-23/32
10-1/32
11-7/32
31/32
6-3/32
2-29/32
12-19/32
3-17/32
4-3/32
39
Service panel
Grounding
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [1/4
35-
43-
Gas refrigerant pipe joint Refrigerant pipe (flared) [3/8 (MUH09TW [1/2 (MUH12TN
terminal
16 in. or more
Lock nut
NOTE: Do not wire 12V DC and 115V AC
in same conduit hole.
) )
14 in. or more
Connector
Conduit cover
Page 40
MSH12TN MSH15TN MSH17TN MSH12TN - MSH15TN - MSH17TN -
INDOOR UNIT
39-3/16
4holes 7/16 O 13/16
5-7/8 25-1/2 8-9/16
1-9/16
2-3/8
Indoor unit
U1U1U1
Unit: inch
13/16
39-15/16
12-5/8
7-1/230-1/21-15/16
2-5/16
6-3/8
Wireless remote controller
3/4
MUH15TN MUH15TN - MUH15TN -
OUTDOOR UNIT
Drainage hole [5/8
1-3/8
13-31/32
13-3/4
Air in
13/16
Installation plate
Air in
U2U1
Air out
17-11/16
17-11/16
13-7/817-1/4
3/167-1/2
Installation plate
Liquid line [ 5/16 19-11/16 Gas line [1/2 16-15/16
{
Insulation [ 1-15/16 O.D
Drain hose [ Insulation [ 1-1/8
4 in.
10
10-13/16
Wall hole [2-15/16
[ 1-1/8 I.D
5/8
4 in.
1/8 11-11/16
4 in.
3-17/32
9-3/4
Air in
Drainage
3holes [1-5/16
23-13/16
11-1/2
13/16
Air out
7-3/16
19-11/16
33-7/16
1-15/16
11-7/16
1-3/16
6-3/16
2-15/16
12-3/16
3-15/16
40
13-9/16
6-5/16
20 in.
Service panel
Liquid refrigerant pipe joint
Refrigerant pipe (flared) [1/4
35-
30-
Gas refrigerant pipe joint Rfrigerant pipe (flared) [5/8
NOTE: Do not wire12V DC and
14 in.
Lock nut
Connector
Conduit cover
115V AC in same conduit hole.
Page 41
MUH17TN MUH17TN -
OUTDOOR UNIT
U1
Unit: inch
8
upper clearance.
Note:Allow adequate
1/2
1/2
11/169/16
Air intake
19-11/16
7-9/32 7-9/32
4
Front opening
14-1/4
13
1-9/161-1/16
Air intake
36
1/2
Air outlet
(for N.E.C)
Service space
36
1-3/4
Refrigerant pipe
(Flared) 1/4
Refrigerant pipe
(Flared) 5/8
33-1/2
21-3/4
11-7/8
Handie for moving
Service panel
Ground
terminal
Terminal block for indoor and outdoor unit connection
Terminal block for power line
34-1/4
20-5/18
13-7/8
13-7/4
15-7/8
7-1/18
17-3/18
2-1/16
Knock out holes for
power line 1-1/16
4-3/4
2-3/8
Knock out hole
for front piping
(refrigerant. drainage
and wiring)
Knock out hole for
right piping
2-3/820-5/81-9/16
1/5/16
4-1/8
1/2x7/8 Oval hoies
(standard bolt W3/8(M10)
1 max.
3-1/8
R13/16
R13/16
(refrigerant. drainage
and wiring)
1-3/4 1-5/8
Bottom piping hole
Drain hole
Standard bolt length
2-9/16
Front right piping holes-
detail figures
11/16
R1/4
1/2
2-U-shaped
notched
holes
Drain hole
8
40
The upper side must be open.
For 10 units or less
1/2
(Concentrated installation)
Outdoor Unit-Necessary surrouding clearance
4
1
11-5/8
Outlet guide
installation hole
Handle for
moving
41
Handle for moving
Rear fresh
air intake
Side air intake
2
Conduit hole
1
NOTE: Do not wire12V DC and 115V AC in same conduit hole.
Rear piping hole
3-3/4
5-7/16
Page 42
MXZ30TN MXZ30TN2
Lock nut
Conduit cover
Connector
OUTDOOR UNIT
Base bolt length
Less than
1
Veranda
Base
Rubber cushion
13/32 1-3/812-19/32
19-11/16
7-7/8 7-7/8
Air in
Air out
35-7/16
2-U-shape notched holes
(Base bolt M10)
1-1/16
Air in
13-31/32
1-9/16
2-15/32 1-13/32 Oval hole
(Base bolt M10)
Unit: inch
15-1/4
[
9.52 (flared) 3/8 (B, C unit)
12.7 (flared) 1/2 (A unit)
[
Handle for moving
1.Installation space
Note : Leave front and both sides clearance fully.
Note : Leave front and overhead clearance fully.
Air in
19-11/16
Air in
29/32
More than
1-5/16
More than 3-15/16
More than
7-7/8
18-1/8
12-15/32
3-15/32
35-7/16
29/32
Note : Obstacle on front and rear side only.
The unit can be used by attaching an optional outdoor outlet guide (MAC-855SG) (but both sides and the top are opend.)
Liquid pipe
[
6.35 (flared) 1/4
2.Service space
C unit connection B unit connection A unit connection
More than
3-15/16
More than
3-15/16
Note : Leave front, overhead and both clearance fully.
More than 13-25/32
More than
19-11/16
42
More than
3-15/16
More than
13-25/32
More than 13-25/32
Service space
More than
1911/16
Page 43
8
WIRING DIAGRAM
MSH09TW
MODEL WIRING DIAGRAM
INDOOR UNIT
TB
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
FROM OUTDOOR UNIT CONNECTING WIRES
POWER
(
)
SUPPLY 115V 1 phase 60Hz
TO OUTDOOR UNIT CONNECTING WIRE
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
POWER SUPPLY 115V 1 phase 60Hz
SYMBOL
C11
F11
HIC1
MF
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(3A) DC/DC CONVERTER INDOOR FAN MOTOR(INNER FUSE)
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate; : Terminal block, : Connector
w
FOR MULTI SYSTEM
NAME
MUH09TW
OUTDOOR UNIT
ORN
3+ 1-
N
L1
VLT
BLK
RED
CN
151
CN201
TAB12
LD101T
5
3+
1-
N
L1
w A disconnect may be required by local code.
MV
POWER MONITOR, RECEIVER P.C.BOARD
SYMBOL
MV
NR11
RT11
RT12
VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR
MODEL WIRING DIAGRAM
FROM INDOOR UNIT CONNECTING WIRE
TB2
+
1
ORN
VLT
-
BLK
RED
GRN/YLW
RED
RED BLK
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING WIRES 115V 1 phase 60Hz
POWER SUPPLY 115V 1 phase 60Hz
GROUND
3
1
N
L
TB1
L1
N
1 2 3 4
ELECTRONIC CONTROL P.C. BOARD
5
REMOTE CONTROLLER
NAME NAME
CN730
1 3
TAB20
DSAR
RT61
F61
IC881
TRANS
52C
43
21S4
CN721CN661
X62
NR61
DEICER P.C.BOARD
BLK
HIC1
TRANS
F11
SYMBOL
X62
SR61
C1
NR11
SR141
SR141
TB
CN711
C65
WHT
RED BLK
CN
112
CN
111
3
CN 121
1
C11
2 3
CN211
SOLID STATE RELAY TERMINAL BLOCK
MF
RED
1
WHT
2 3
BLK
4
C
MC
R
S
RT12 RT11
BLK
1
GRY
2
YLW
3
BRN
WHT
RED
MF
4 5 6
SG79J022H01
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate; : Terminal block, : Connector
NAME
SYMBOL
MC
MF NR61 RT61 SR61
NAME NAME COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY
43
SYMBOL
TB1 TB2
X62
21S4
52C
TERMINAL BLOCK TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
VG79B007H01
Page 44
RED
ORN
BLK
L1
N
TB
1-
3+
VLT
5
REMOTE CONTROLLER
POWER MONITOR, RECEIVER P.C.BOARD
LD101T
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
FROM OUTDOOR UNIT CONNECTING WIRES POWER SUPPLY
TO OUTDOOR UNIT CONNECTING WIRE
115V 1 phase
60Hz
MV
ELECTRONIC CONTROL P.C. BOARD
C11
F11
SR141
RT12 RT11
MF
HIC1
TRANS
NR11
TAB12
3
2
1
1
6
2 3 4 5
4
3
2
1
5
CN 121
112
CN
CN 111
CN211
CN201
CN 151
3
BLK GRY YLW BRN WHT RED
(
)
w A disconnect may be required by local code.
W
MSH09TW -
INDOOR UNIT
U1
MODEL WIRING DIAGRAM
SYMBOL
C11
F11
HIC1
MF
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(3A) DC/DC CONVERTER INDOOR FAN MOTOR(INNER FUSE)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate;
/: Terminal block, : Connector
MUH09TW -
OUTDOOR UNIT
SYMBOL
C1
C65
DSAR
F61
IC881
MC
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER COMPRESSOR(INNER PROTECTOR)
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
U1
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING WIRES 115V 1 phase 60Hz
POWER SUPPLY 115V 1 phase 60Hz
NAME
GROUND
SYMBOL
MV NR11 RT11 RT12
VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR
NAME NAME
MODEL WIRING DIAGRAM
RT61
TB2
3
1
N
1
L
TB1
L1
N
SYMBOL
MF
NR61
RT61 RT63 SR61
TB1,TB2
+
ORN
VLT
-
BLK
RED
GRN/YLW
OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY TERMINAL BLOCK
CN730
1 3
F61
TAB20
RED
DSAR
RED BLK
NAME NAME
44
RT63
CN662
IC881
TRANS
52C
43
SYMBOL
SR141
21S4
CN721CN661
X62
BLK
X62
SR61
NR61
DEICER P.C.BOARD
C1
SYMBOL
21S4
TB
WHT
RED BLK
X62
52C
SOLID STATE RELAY TERMINAL BLOCK
SG79J023H01
MF
CN711
C65
S
RED
1
WHT
2 3
BLK
4
C
MC
R
R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
VG79B041H01
Page 45
MSH12TN MSH15TN MSH17TN
MODELS WIRING DIAGRAM
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
FROM OUTDOOR UNIT CONNECTING WIRES POWER
( )
SUPPLY 115V 1 phase 60Hz
TO OUTDOOR UNIT CONNECTING WIRE
FOR MULTI SYSTEM
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
POWER SUPPLY 115V 1 phase 60Hz
SYMBOL
C11
DSAR
F11
HIC1
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR SURGE ABSORVER FUSE(3A) DC/DC CONVERTER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
w
MUH12TN
OUTDOOR UNIT
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING WIRES 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
TB
3+
ORN
1-
VLT
N
BLK
L1
RED
BRN
DSAR
3+
1-
N
L1
GRN/YLW
DISPLAY P.C.BOARD
w A disconnect may be required by local code.
SYMBOL
MF
MV NR11 RT11
CN201
1 2 3 4
TAB12
CN
102CN151CN104CN101
3
MV
F11
ELECTRONIC CONTROL P.C. BOARD
5
53
AUTO RESTART ASSY
NAME NAME INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR
MODEL WIRING DIAGRAM
RT61
GROUND
TB2
3
1
N
1
L
TB1
L1
N
L2
+
ORN
VLT
-
BLK
RED
RED
BLU
GRN/YLW
RED
CN730
1 3
TAB20
DSAR
CN661
F61
HIC1
HIC1
TRANS
IC881
TRANS
52C
4
RECEIVER P.C.BOARD
CN721
X62
3
BLU
CN
112
CN
111
LDCOM LDC11
C11
NR11
LDC12 LDFH
SR144
LDFL
SR142
LDFM
SR143
LDFVL
SR141
REMOTE CONTROLLER
SYMBOL
RT12
SR141~SR144
TB
21S4
X62
CN711
SR61
NR61
DEICER P.C.BOARD
C1
WHT
RED BLK
C65
1 2 3 4
MC
S
RT12 RT11
WHT
WHT
1
ORN
ORN
2
RED
RED
3
BLK
BLK YLW BLU BRN
4 5 6 7 8
YLW BLU BRN
GRN/YLW
MF
INDOOR COIL THERMISTOR SOLID STATE RELAY TERMINAL BLOCK
VG79B016H01
MF
RED WHT
BLK
C
R
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
SYMBOL
MC
MF NR61 RT61 SR61
NAME NAME COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY
45
SYMBOL
TB1 TB2
X62
21S4
52C
TERMINAL BLOCK TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
VG79B008H01
Page 46
MUH15TN MUH17TN
OUTDOOR UNIT
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
WIRES
GROUND
TB2
N
L
TB1
L
N
L
MODELS WIRING DIAGRAM
RT61
RED
RED
CN730
1 3
TAB21
TAB20
RED
DSAR
CN661
F61
IC881
TRANCE
DEICER P.C. BOARD
NO
3
1
1
1
2
+
ORN
VLT
BLK
RED
BLU
GRN/YLW
X62
BLU
21S4
CN721
NR61
52C
COM
C1
X62
SR61
52C
CN720
CN711
C65
2 3
WHT
RED
SR
BLK
RED WHT
BLK
MC
MF
RED
11
ORN
2
WHT
3
BLK
44
C
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
MSH12TN - MSH15TN - MSH17TN -
INDOOR UNIT
NAME
TO OUTDOOR UNIT CONNECTING WIRES 12V DC
FROM OUTDOOR UNIT CONNECTING WIRES POWER
( )
SUPPLY 115V 1 phase 60Hz
TO OUTDOOR UNIT CONNECTING WIRE
SYMBOL
NR61
RT61 SR61
w
MC MF
3+
1-
N
L1
BRN
NAME NAME COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY
TB
ORN VLT
BLK RED
DISPLAY P.C.BOARD
U1U1U1
CN
102CN151CN104CN101
DSAR
GRN/YLW
MODELS WIRING DIAGRAM
CN201
1 2 3 4
TAB12
F11
5
533
AUTO RESTART
MV
ASSY
HIC1
TRANS
ELECTRONIC CONTROL P.C. BOARD
w A disconnect may be required by local code.
SYMBOL
TB1 TB2
X62
21S4
52C
C11
NR11
RECEIVER P.C.BOARD
TERMINAL BLOCK TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
SG79J000H01
CN 112
CN 111
LDCOM LDC11 LDC12 LDFH
SR144
LDFL
SR142
LDFM
SR143
LDFVL
SR141
REMOTE CONTROLLER
WHT ORN RED BLK YLW BLU BRN
RT12 RT11
WHT
1
ORN
2
RED
3
BLK
4
YLW
5
BLU
6
BRN
7 8
GRN/YLW
MF
SYMBOL
C11
DSAR
F11
HIC1
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR SURGE ABSORVER FUSE(3A) DC/DC CONVERTER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
SYMBOL
MF
MV NR11 RT11
NAME
SYMBOL INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR
SR141~SR144 VARISTOR ROOM TEMPERATURE THERMIST OR
46
RT12
TB
NAME INDOOR COIL THERMISTOR SOLID STATE RELAY TERMINAL BLOCK
VG79B017H01
Page 47
MUH12TN -
U1
OUTDOOR UNIT
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING WIRES 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
GROUND
TB2
3
1
N
L
TB1
L1
N
L2
1
MODEL WIRING DIAGRAM
+
ORN
VLT
-
BLK
RED
GRN/YLW
RED
BLU
RED
CN730
1 3
TAB20
DSAR
RT61 RT63
F61
IC881
TRANS
52C
4
21S4
CN721CN661
CN662
X62
NR61
3
DEICER P.C.BOARD
BLU
C1
X62
SR61
WHT
RED BLK
CN711
C65
S
MF
RED
1
WHT
2 3
BLK
4
C
MC
R
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
MUH15TN - MUH17TN -
OUTDOOR UNIT
NAME
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING
WIRES 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
GROUND
U1U1
SYMBOL
MC
MF
NR61
RT61 RT63
TB2
3
1
N
1
L
TB1
1
L
N
2
L
NAME NAME COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERA TURE THERMIST OR
MODELS WIRING DIAGRAM
RT63
RT61
RED
RED
CN730
1 3
TAB21
TAB20
RED
DSAR
CN661
F61
CN662
X62
IC881
TRANCE
DEICER P.C. BOARD
NO
BLU
+
ORN
VLT
BLK
RED
BLU
GRN/YLW
21S4
CN721
NR61
52C
X62
SR61
COM
C1
SYMBOL
SR61
TB1,TB2
X62
21S4
52C
52C
CN720
CN711
C65
2 3
WHT
RED
SR
BLK
SOLID STATE RELAY TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
VG79B042H01
MF
RED
RED
11
ORN
WHT
2
WHT
3
BLK
BLK
44
C
MC
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
MC
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER COMPRESSOR(INNER PROTECTOR)
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
SYMBOL
MF NR61 RT61 RT63 SR61
TB1
NAME NAME OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY TERMINAL BLOCK
47
SYMBOL
TB2 X62
21S4
52C
TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
SG79J001H01
Page 48
MUH12TN -
U2
OUTDOOR UNIT
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING WIRES 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
GROUND
TB2
3
1
N
L
TB1
L1
N
L2
MODEL WIRING DIAGRAM
RT61 RT63
RED
CN730
1 3
TAB20
DSAR
F61
IC881
TRANS
52C
4
CN662
3
1
+
ORN
VLT
BLK
RED
GRN/YLW
RED
BLU
21S4
CN721CN661
X62
X62
SR61
NR61
DEICER P.C.BOARD
C1
BLU
WHT
RED BLK
CN711
C65
S
MF
RED
1
WHT
2 3
BLK
4
C
MC
R
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
MUH15TN -
OUTDOOR UNIT
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTE:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) DC/DC CONVERTER
MC
COMPRESSOR(INNER PROTECTOR)
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate; /: Terminal block, : Connector
NAME
U2
FROM INDOOR UNIT CONNECTING WIRE
FROM INDOOR UNIT CONNECTING WIRES 12V DC
TO INDOOR UNIT CONNECTING
WIRES 115V 1 phase 60Hz
POWER SUPPLY 208/230V 1 phase 60Hz
GROUND
NAME
SYMBOL
MC
MF NR61 RT61 RT63
TB2
3
1
N
1
L
TB1
1
L
N
2
L
SYMBOL
MF
NR61
RT61 RT63 SR61
TB1
COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERA TURE THERMIST OR
MODEL WIRING DIAGRAM
+
ORN
VLT
BLK
RED
BLU
GRN/YLW
OUTDOOR FAN MOTOR(INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY TERMINAL BLOCK
NAME NAME
RT63
RT61
CN730
CN661
RED
RED
1 3
TAB21
TAB20
RED
DSAR
F61
CN662
X62
IC881
TRANCE
DEICER P.C. BOARD
NO
BLU
NAME NAME
21S4
CN721
NR61
52C
SYMBOL
SR61
TB1,TB2
X62
21S4
52C
CN720
X62
SR61
COM
WHT
C1
RED BLK
SYMBOL
TB2 X62
21S4
52C
SOLID STATE RELAY TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
VG79B543H01
52C
MF
CN711
C65
2 3
MC
SR
RED
WHT
BLK
C
11 2 3
44
RED ORN WHT BLK
TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
SG79B542H01
48
Page 49
MXZ30TN
MODELS WIRING DIAGRAM
OUTDOOR UNIT
DS61
C61
ORN
+
+
-
-
YLW
CT
LDB
61
LDB
SSR61
F911
(250V 1A)
CN913
12
RED
RED
21S4
ELECTRONIC CONTROL P.C. BOARD
CN793
BRN
BLU
ORN
YLW
WHT
LEV C
SYMBOL LEV A~C
MC
MF61
R RT61 RT62 RT63 RT65
RT66,67
RT68
GROUND
POWER SUPPLY 208/230V 1 phase 60Hz
INDOOR UNIT (A) INDOOR UNIT (B) INDOOR UNIT (C)
FROM INDOOR UNIT
CONNECTING WIRES
DC 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61 DS62
F801 F911
L61
NAME POWER FACTOR CAPACITOR SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR CURRENT TRANSFORMER DIODE MODULE DIODE STACK FUSE (250V 1A) FUSE (250V 1A) REACTOR
L
COMMON MODE CHOKE COIL
L1 L2
TB1
TB3
TB2
GRN/YLW
RED BLU
TB4
1
3
1
3
1
3
BLU RED
BLU ORN
BLU YLW
RED
X64
CN720
R
BLK
BLK
4
6
X64
0
1
GRY
BRN
12
12
CN601
12
CN602
12
CN603
CN791
123456
RED
BRN
BLU
ORN
LEV A
RED
BLK
GRN
YLW
TB5
LDE
WHT
LD62 LD61
LD63
L61
CN901
64
CN851 CN852
CN792
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV B
WHT
LD64
CN902
123456
RED
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symboles below indicate.
: Terminal block : Connector
DS62
A
ORN
K
WHT
NOISE FILTER P.C.BOARD
X63
X62
C65
34
RED
ORN
WHT
BLK
123456
MF61
CN722 CN663
RED
RED
BLK
63H1 RT63
RT65
L
X61
BLU
YLW
12345612 1234
BLK
GRY
RT66 RT68
GRY
CN662
GRY
RT67
C63 C62
RED
+-+
YLW
1234
CN801
CN704
1234567
CN705
GRY
GRY
GRY
NAME EXPANSION VALVE COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) RESISTOR DISCHARGE TEMPERATURE THERMISTOR DEFROST TEMPERATURE THERMIST OR EVAPORATION TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR GUS PIPE TEMPERATURE THERMISTOR GUS PIPE TEMPERATURE THERMISTOR
RED
-
CN501
4321
2
CN514
CN515
7654321
I.P.M P.C. BOARD
CN661
12345678
GRY
GRY
BLK
BLK
GRY
RT62
RT61
YLW
TAB62
F801
(250V 1A)
T801
CT62
GRY
SYMBOL
SSR61
T801
TB1~5
X61,62,63
X64,65 X66,67
21S4 63H1 63H2
TAB63
V
MC
UW
RED
WHT
BLK
TAB64
TAB65
TAB66
NAME SOLENOID COIL RELAY TRANSFORMER TERMINAL BLOCK FAN MOTOR RELAY RELAY RELAY R.V. COIL HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH
BRN GRY
21
X65
CN552
BLK
BLK
CN554CN551
X66
ORN ORN
RELAY
P.C. BOARD
SG79A481H02
CN553
21
X67
63H2
WHT
WHT
49
Page 50
POWER SUPPLY 208/230V 1 phase 60Hz
INDOOR UNIT (A)
TB1
TB4
BLU RED
X64
GRN/YLW
GRN
CN720
CN601
0
LD62
CN913
CN791
CN901
64
2
CN902
CN851 CN852
MF61
21S4
12
21
21
12
12
34
123456
1234567
123456
C65
LD64
LDB
LDB
LD61
LDE
L61
F911
SSR61
X63
X62
X61
1
L1 L2
3
1
INDOOR UNIT (B)
BLU ORN
CN602
12
3
3
1
INDOOR UNIT (C)
BLU YLW
CN603
12
1
RED
BRN
GRY
WHT
YLW
RED
RED
RED
BRN
BLU
ORN
YLW
WHT
ORN
WHT
BLK
BLU
YLW
RED
ORN
ORN
RED
RED
YLW
YLW
BLK
BLK
ORN ORN
BRN GRY
X65
X66
X67
63H2
CN552
CN553
BLK
RELAY
P.C. BOARD
WHT
WHT
RED
WHT
V
UW
A
K
L
WHT
NOISE FILTER P.C.BOARD
RED
DS61
DS62
C61
CT 61
C63 C62
+
+
-
+-+
-
-
BLU
LEV A
CN792
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV B
CN793
123456
RED
BRN
BLU
ORN
YLW
WHT
LEV C
CN722 CN663
63H1 RT63
CN662
12345612 1234
RED
RED
BLK
BLK
RT66 RT68
RT67
GRY
GRY
GRY
GRY
GRY
GRY
CN661
CN705
7654321
CN515
1234
4321
CN801
CN501
TAB62
TAB63
T801
CT62
TAB66
TAB65
TAB64
I.P.M P.C. BOARD
F801
(250V 1A)
CN704
CN514
CN554CN551
12345678
RT62
RT61
RT65
GRY
GRY
BLK
BLK
GRY
GRY
ELECTRONIC CONTROL P.C. BOARD
MC
(250V 1A)
GROUND
TB3
TB2
FROM INDOOR UNIT
CONNECTING WIRES
DC 12V
SYMBOL
C61
C62,63
C65
CT61,62
DS61 DS62
F801 F911 F912
L
L61
SYMBOL LEV A~C
MC MF61 NR63
R RT61 RT62 RT63 RT65
RT66,67
RT68
NAME POWER FACTOR CAPACITOR SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR CURRENT TRANSFORMER DIODE MODULE DIODE STACK FUSE (250V 1A) FUSE (250V 1A) FUSE (3.15A) REACTOR COMMON MODE CHOKE COIL
NAME EXPANSION VALVE COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) VARISTOR RESISTOR DISCHARGE TEMPERATURE THERMISTOR DEFROST TEMPERATURE THERMIST OR EVAPORATION TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR GUS PIPE TEMPERATURE THERMISTOR GUS PIPE TEMPERATURE THERMISTOR
SYMBOL
SSR61
T801
TB1~4
X61,62,63
X64,65 X66,67
21S4 63H1 63H2
NAME SOLENOID COIL RELAY TRANSFORMER TERMINAL BLOCK FAN MOTOR RELAY RELAY RELAY R.V. COIL HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH
NOTE: 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symboles below indicate.
: Terminal block : Connector
4
LD63
6 BLK
BLK
BLK
RED
R
(3.15A)
LD65
F912
NR63
N
MXZ30TN2
OUTDOOR UNIT
MODELS WIRING DIAGRAM
SG79Y087H01
50
Page 51
9
REFRIGERANT SYSTEM DIAGRAM
MSH09TW MSH09TW -
Unit:inch
U1
MUH09TW MUH09TW -
U1
INDOOR UNIT
Indoor coil
Indoor heat
exchanger
Room temperature thermistor RT11
thermistor RT12
Refrigerant pipe [3/8 (Option)
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (Option) (with heat insulator)
Stop valve (with service
port)
Service port
Fusible plug
Strainer
Stop valve
Muffler
4-way valve
Muffler
Compressor
Capillary tube CT3 O.D. 0.12I.D.
31-1/2
0.063
Check valve
Service port
Strainer
Defrost thermistor RT61
Capillary tube CT2 O.D. 0.12I.D.
17-11/16
0.063
Flow of refrigerant (cooling) Flow of refrigerant (heating)
OUTDOOR UNIT
Outdoor heat exchanger
Capillary tube CT1 O.D. 0.12I.D. 0.055 19-11/16
R.V. coil heating ON cooling OFF
Unit:inch
MUH12TN
MSH12TN
MSH12TN -
INDOOR UNIT OUTDOOR UNIT
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
thermistor RT12
Distributor
U1
Refrigerant pipe [1/2 (Option) (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (Option)
(with heat insulator)
Muffler
Stop valve (with service port)
Service port
Stop valve
Strainer
4-way valve
Fusible plug
Muffler
Strainer
Compressor
Service port
Defrost thermistor RT61
Flow of refrigerant (cooling) Flow of refrigerant (heating)
MUH12TN ­MUH12TN -
Outdoor heat exchanger
Capillary tube CT1 O.D. 0.12✕I.D.
0.05519-11/16
Capillary tube CT1 O.D. 0.12✕I.D.0.071✕11-13/16
R.V. coil
heating ON cooling OFF
51
U1
U2
Page 52
Indoor heat exchanger
Outdoor heat exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
Refrigerant pipe [5/8 (Option) (with heat insulator)
Flared connection
Distributor
Refrigerant pipe [1/4 (Option) (with heat insulator)
Flared connection
Stop valve (with service port)
Strainer #100
Strainer #100
Stop valve
4-way
valve
Flow of refrigerant (cooling) Flow of refrigerant (heating)
Accumulator
Muffler
Compressor
Muffler
Service port
Service port
Fusible plug
Defrost thermistor (RT61)
Check valve
Capillary tube CT3 O.D. 0.12I.D. 0.0799-13/16
Capillary tube CT2 O.D. 0.12I.D. 0.07927-9/16
R.V. coil heating ON cooling OFF
Distributor
Unit:inch
MSH15TN
MSH15TN -
INDOOR UNIT OUTDOOR UNIT
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
thermistor RT12
Distributor
U1
Refrigerant pipe [5/8 (Option) (with heat insulator)
Flared connection
Muffler
Stop valve (with service port)
Service port
Accumulator
4-way valve
Fusible plug
Muffler
Strainer
Compressor
MUH15TN
Service port
#100
Defrost thermistor RT61
MUH15TN ­MUH15TN -
Outdoor heat exchanger
Capillary tube CT1 O.D. 0.12✕I.D.
0.05511-13/16
U1 U2
Flared connection
Refrigerant pipe [1/4 (Option)
(with heat insulator)
Strainer #100
Stop valve
Capillary tube CT3 O.D. 0.12✕I.D.0.079✕23-5/8
Check valve
Capillary tube CT2 O.D. 0.12✕I.D.0.079✕7-7/8
R.V. coil
heating ON cooling OFF
Flow of refrigerant (cooling) Flow of refrigerant (heating)
Unit:inch
MSH17TN MSH17TN -
U1
MUH17TN MUH17TN -
INDOOR UNIT OUTDOOR UNIT
U1
52
Page 53
Ball valve with
service port
Ball valve with
service port
Distributor
Strainer
#100
Strainer #100
LEV
Oil separator
Compressor
High pressure switch 1
Accumulator
Capillary tube CT2
Reversing valve
Discharge temperature thermistor
Evaporation temperature thermistor
Defrost thermistor
Strainer #100
Distributor #50
Outdoor heat exchanger
High pressure switch 2
Indoor unit
C
Unit C gas pipe temperature thermistor
Indoor unit
B
Unit B gas pipe temperature thermistor
Indoor unit
A
Indoor unit
A
Strainer
#100
LEV
Indoor unit
B
Strainer
#100
LEV
Indoor unit
C
Unit A gas pipe temperature thermistor
Capillary tube CT1
O.D. 0.0985 I.D. 0.024 29.53
O.D. 0.0985 I.D. 0.024 39.37
Capillary tubeCT3,4,5
O.D. 0.157 I.D. 0.094
15.75
Capillary tube CT6
Capillary tube CT7
Capillary tube CT8
O.D. 0.12 I.D. 0.079 7.87
O.D. 0.12 I.D. 0.079 7.87
O.D. 0.12 I.D. 0.079 7.87
Muffler
Refrigerant flow in cooling Refrigerant flow in heating
R.V. coil heating ON cooling OFF
Fusible
plug Service port
Service port
MXZ30TN MXZ30TN2
Unit: inch
53
Page 54
10
lighted not lighted
Approx. 4 ˚F or more
Difference between target temperature and room temperature
Approx. 4 ˚F or less
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature.
Operation stateIndication
Operation Indicator
Operation Indicator lamp
The operation indicator located at the right side of the indoor unit indicates the operation state.
• The following indication applies regardless of shape of the indicatior.
INDOOR UNIT DISPLAY SECTION
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
STOP
START
HR.
MIN.
I FEEL
COOL
HEAT
DRY
RESET CLOCK
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
VANE CONTROL button
CLOCK SET button
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
MICROPROCESSOR CONTROL
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
U1
MUH12TN -
U1
MUH15TN -
U1
MXZ30TN
U2
MZX30TN2
U2
Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP(ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
WIRELESS REMOTE CONTROLLER
54
Page 55
10-1. “I FEEL CONTROL” OPERATION
(1) Press OPERATE/STOP(ON/OFF) button on the remote controller.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL CONTROL”.
Then a beep tone is heard.
(3) The operation mode is determined by the room temperature at
start-up of the operation.
Once the mode is fixed, the mode does not change by room temperature afterwards.
Under the ON-TIMER ( START) operation, mode is determined according to the room temperature as the operation
starts.
When the system is stopped with the OPERATE/STOP(ON/OFF) button on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” mode, the system operates in previous mode automatically regardless of the room tem­perature.
Operation time chart Example
Initial room temperature
77˚F or more 73˚F to 77˚F
less than 73˚F
“I FEEL CONTROL”
“I FEEL CONTROL”
“I FEEL CONTROL”
mode
COOL mode of
DRY mode of
HEAT mode of
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at start-up of the operation.
Operation time chart Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
(4) The initial set temperature is decided by the initial room temperature.
Restart
COOL mode of “I FEEL CONTROL”
Restart
COOL or DRY or HEAT mode of “I FEEL CON­TROL” that determined by room temperature at start-up of the operation.
Mode Initial room temperature Initial set temperature
COOL mode of
“I FEEL CONTROL”
DRY mode of
“I FEEL CONTROL”
HEAT mode of
“I FEEL CONTROL”
1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart. The set temperature is calculated by the previous set temperature.
79˚F or more
77˚F to 79˚F
73˚F to 77˚F
less than 73˚F
55
75˚F
Initial room temperature minus 4˚F Initial room temperature minus 4˚F
79˚F
1
Page 56
Difference between room temperature and set temperature during operation
(5) TEMPERATURE buttons
TOO
COOL
TOO
WARM
In “I FEEL CONTROL” mode, set temperature is decided by the microprocessor based on the room temperature. In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, consider­ing the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
To raise the set temperature 2~4 degrees(°F)
To lower the set temperature 2~4 degrees(°F)
— COOL mode of “I FEEL CONTROL” —
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. In AUTO the fan speed is as follows.
Initial temperature difference
Fan speed Room temperature minus set temperature : 2 degrees or more········································High Room temperature minus set temperature : Between 1 and 2 degrees····························Med. Room temperature minus set temperature : less than 1 degrees······································Low
2 deg.
4 deg.
3 deg.
2. Coil frost prevention
Temperature control
<MSH09> When the indoor coil thermistor RT12 reads 39˚F or below for 5 minutes, the coil frost prevention mode starts. <MSH12/15/17> When the indoor coil thermistor RT12 reads 37˚F or below, the coil frost prevention mode starts
immediately. However the coil frost prevention doesn’t work for 5 minutes since the compressor has
started. The indoor fan operates at the set speed the compressor stops for 5 minutes. After that, if RT12 still reads below 39˚F (MSH09) or below 37˚F (MSH12/15/17) this mode is prolonged until the RT12 reads over 39˚F (MSH09) or 37˚F (MSH12/15/17).
Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med.. c. Room temperature is below 79˚F. When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 79°F. However, when two of the above conditions (b.and c.) are satisfied again. Time accumulation is resumed.
ON
ON
7 deg.
Compressor and
OFF
Outdoor fan motor
Indoor fan motor
ON (continuously at set speed)
OFF
56
Page 57
Difference between room temperature and set temperature during operation
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the temperature. By such controls, amount of air flow of indoor unit will be reduced in order to lower humidity without much room tempera­ture drop.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. In AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan (Refer to page 65 for MXZ30TN) Compressor operates by room temperature control and time control. Set temperature is controlled to fall 4˚F as initial set temperature. Indoor fan and outdoor fan operate in the same cycle as the compressor.
When the room temperature is 73˚F or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
When the room temperature is under 73˚F.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example: When the room temperature is 73˚F or over
ON
ON
Thermostat
OFF
ON
Indoor fan
OFF
ON
Outdoor fan Compressor
OFF
8 min.
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost
prevention) has the priority. However, when coil frost prevention works while the compressor is not operating, the speed becomes Low.
— HEAT mode of “I FEEL CONTROL” —
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more··········································High Set temperature minus room temperature: Between 1 and 2 degrees· ·····························Med. Set temperature minus room temperature: less than 1 degree ··········································Low
(2) Cold air prevention control
<MSH09>
1 When the compressor is not operating,
(1) if the temperature of indoor coil thermistor RT12 is 64°F or less, the indoor fan stops. (2) if the temperature of indoor coil thermistor RT12 is more than 64°F, the indoor fan operates at Very Low.
2 When the compressor is operating,
(1) if the temperature of RT12 is 72°F or more, the indoor fan operates at set speed. (2) if the temperature of RT12 is less than 72°F and
(1) if the temperature of room temperature thermistor RT11 is 59°F or less, the indoor fan stops. (2) if the temperature of room temperature thermistor RT11 is more than 59°F, the indoor fan operates at Very
Low.
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4 min.
3 min.
1 min.
Initial temperature difference Fan speed
57
2 deg.
4 deg.
3 deg.
7 deg.
Page 58
<MSH12/15/17>
Released
Cold Air Prevention
64°F72°F
Indoor fan speed
Set speed Very Low or stop
Indoor coil thermistor RT12 temperature
<Time condition>
<Indoor fan speed>
less than 2 minutes Low 2 minutes to 4 minutes Med. more than 4 minutes High
High pressure protection
Released
118˚F
(MSH09)
115˚F(MSH12/15/17)
126˚F(MSH09) 122˚F(MSH12/15/17)
ON
Outdoor fan
OFF
When the compressor is operating,
(1) if the temperature of indoor coil thermistor RT12 is less than 64°F or, the indoor fan operates at Very Low.
But if the temperature of room temperature thermistor RT11 is 59°F or less, the fan stops.
(2) if the temperature of indoor coil thermistor RT12 is more than 72°F, the indoor fan operates at set speed.
NOTE : If the temperature of RT12 reads from 64°F to 72°F at the air conditioner starting and also after defrosting,
this control works.
(3) Warm air control.
When any condition of 1(a. ~ d.) and the condition of 2 as follows are satisfied at the same time, warm air control works.
1 a.) when the operation mode has been changed to HEAT mode
b.) when cold air prevention has been released c.) when defrosting has been finished d.) when the compressor starts in HEAT mode
2 When the temperature of indoor coil thermistor RT12 is less than 99°F.
When warm air control works, the indoor fan speed changes as follows to blow out warm air gradually.
Gradation of indoor fan speed in initial
The upper limit of the indoor fan speed in MANUAL is the set speed. The upper limit of the indoor fan speed in AUTO is the speed decided by indoor fan speed control. When the temperature of RT12 has been 99°F or more, or when the set speed has been changed, this control is released and the indoor fan speed is the set speed.
(4) Flow soft control
When the thermostat (compressor) is off, the indoor fan operates as follows.
< RT12 > < Indoor fan speed >
<MSH09> less than 64°F off
64°F or more Very Low
<MSH12/15/17> — Very Low
NOTE : When the thermostat(compressor) turns on, the indoor
fan operates at set speed. But until cold air prevention and warm air control is released, the indoor fan follows them.
2. High pressure protection (Refer to page 70 for MXZ30TN MXZ30TN2) During heating operation, the outdoor fan motor is controlled by the indoor coil thermistor RT12 temperature for excess rise protection of compressor discharge pressure. Outdoor fan OFF : 126˚F (MSH09), 122˚F (MSH12/15/17) Outdoor fan ON : 118˚F (MSH09), 115˚F (MSH12/15/17)
High pressure protection time chart Example
Indoor coil thermistor RT12 temperature
126˚F(MSH09) 122˚F(MSH12/15/17)
118˚F(MSH09) 115˚F(MSH12/15/17)
Outdoor fan motor turn OFF
Outdoor fan motor turn ON
Outdoor fan motor
ON
NOTE: During high pressure protection and for 4 minutes and 15 seconds after high pressure protection, defrosting of
outdoor heat exchanger is not detected by the defrost thermistor RT61.
OFF
ON
58
OFF
Page 59
3. Defrosting (Refer to page 70 for MXZ30TN MXZ30TN2) Defrosting of outdoor heat exchanger is controlled by deicer P.C. board, which detection by the defrost thermistor RT61. (1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts. a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes (MSH09TW, MSH12/15/
17TN) /15 minutes (MSH09TW - , MSH12/15/17TN- , MSH12/15TN- ) without the defrosting operation
U2U1U1
working.
b) The defrost thermistor RT61 reads 27˚F or less (MSH09TW, MSH12/15/17TN) / 32°F or less (MSH09TW - ,
MSH12/15/17TN- , MSH12/15TN- ).
U2U1
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops. d) The defrost thermistor RT61 reads 38˚F or more (MSH09TW, MSH12/15/17TN) / 50°F or more (MSH09TW - ,
MSH12/15/17TN- , MSH12/15TN- ).
U2U1
e) The defrosting time exceeds 10 minutes.
(3) Defrosting time chart
Defrost thermistor RT61
U1
U1
50°F or more (MSH09TW - , MSH12/15/17TN- , MSH12/15TN- ) 38˚F or more
(MSH09TW, MSH12/15/17TN) 32°F or less
(MSH09TW - , MSH12/15/17TN- , MSH12/15TN- ) 27°F or less
(MSH09TW, MSH12/15/17TN)
U2
U2
Outdoor 52C contactor(Compressor)
X62 (R.V. coil)
SR61 Outdoor fan
Defrost counter
U1U1
U1U1
ON OFF
ON
OFF
ON OFF
ON OFF
30 sec.
15 sec.
30 sec.
5~15 sec.
Max 10 min.
Indoor fan
ON
OFF
Indoor vane
Horizontal
Set position
NOTE: When the indoor coil thermistor RT12 reads above 64˚F, indoor fan operates at Very Low for 30 seconds since
RT61 has read the working temperature of defrosting.
When the indoor coil thermistor RT12 reads 64˚F or less, the indoor fan stops.
NOTE
59
Page 60
4. R.V. coil control
50
50
59
68
77
86
95
59 68 77 86 95°F
°F
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
(COOL / DRY)
5 sec.
(HEAT)
5 sec.
Compressor
ON OFF
R.V. coil
ON OFF
Outdoor fan
ON
OFF
5. Outdoor temperature control <MSH09TW - , MSH12/15/17TN- , MSH12/15TN- >
When the temperature of the ambient temperature thermistor RT63 falls below 19°F, the compressor stops for protecting the unit.
COMPRESSOR
ON OFF
19°F 29°F
NOTE: If the temperature of RT63 reads from 19°F to 29°F at the air conditioner starting, compressor operates.
10-2. COOL OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with the OPERATION SELECT button. (3) Press the TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 59 ~ 89˚F
Indoor fan continues to operate regardless of thermostat’s OFF-ON at set speed.Coil frost prevention is as same as COOL mode of “I FEEL CONTROL”.
10-3. DRY OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on
with a beep tone. (2) Select DRY mode with the OPERATION SELECT button. (3) The microprocessor reads the room temperature and
determines the set temperature. Set temperature is as
shown on the right chart.
Thermostat (SET TEMP.) does not work.
The other operations are same as DRY mode of “I FEEL
CONTROL”. (4) DRY operation will not function when the room tempera-
ture is 55˚F or below.
10-4. HEAT OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on
with a beep tone. (2) Select HEAT mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO
COOL button) to select the desired temperature.
The setting range is 59 ~ 89˚F. (4) Indoor fan speed control, high pressure protection, defrost-
ing, 4-way valve control are the same as HEAT mode of “I FEEL CONTROL”.
ON
OFF ON
OFF
ON OFF
U2U1U1
60
Page 61
10-5. FAN MOTOR CONTROL<MSH09>
Rotational frequency
High High
time
Med.
Low
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed­back the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (High, Med., Low) the microprocessor controls SR141 and adjusts fan motor electric current to make the current rotational fre­quency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequen­cy changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR lamp flashes on and off to show the fan motor abnormality. (Refer to page 72.)
10-6. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL button.
(3) Positioning
(4) VANE AUTO mode
(5) STOP (operation OFF) and ON-TIMER standby
(6) Dew prevention
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in case of follows. (a) When the OPERATE/STOP(ON/OFF) button is pressed. (POWER ON/OFF) (b) When the vane control is changed AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
In COOL and DRY operation
Vane angle is fixed to Angle 1.
In HEAT operation
Vane angle is fixed to Angle 4.
When the following cases occur, the vane returns to the closed position. (a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When the ON-TIMER is in standby.
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
61
Page 62
(7) SWING MODE
Released
Cold Air Prevention
75˚F 82˚F
Angle 1
Horizontal vane
Set position
PM
AM
PM
PM
By selecting SWING mode with the VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller
displays “ ”.
(8) Cold air prevention in HEAT operation.
When any of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1 automati-
cally to prevent cold air blowing on users.
Compressor is not operating.
Defrosting is performed.
Indoor coil thermistor RT12 reads 75˚F or below.
Indoor coil thermistor RT12 temperature is raising from 75˚F or below, but it does not exceed 82°F.
Indoor coil thermistor RT12 temperature
NOTE : If the temperature of RT12 reads from 75˚F to 82 ˚F at the air conditioner starting, this control works.
10-7. TIMER OPERATION
1. How to set the timer.
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIMER MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON/OFF TIMER buttons to select the operation.
“ON-TIMER” button... AUTO START operation (ON timer) “OFF-TIMER” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button (TIME SET button) to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “ ” or “ ” mark is flashing. These marks disappear in 1 minute. After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
A power failure occurs.
The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the ON/OFF TIMER buttons.
To cancel the ON timer, press the “ON-TIMER” button.
To cancel the OFF timer, press the “OFF-TIMER” button.
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
The OFF timer and ON timer can be used in combination.
“ ” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
62
Page 63
EMERGENCY OPERATION switch
10-8. EMERGENCY-TEST OPERATION
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote controller run down. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at High speed and the system is in continuous operation. (The thermostat is ON.) After 30 minutes of test run operation the system shifts to EMERGENCY COOL 75˚F. The fan speed shifts to Med. speed. The coil frost prevention works even in emergency operation, and defrosting cycle as well.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until the EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
• The following indication applies regardless of shape of the indicator.
MSH09TW MSH09TW -
MSH12TN MSH12TN ­MSH15TN MSH15TN ­MSH17TN MSH17TN -
U1
U1 U1 U1
/HEAT
MODE with a set temperature of
OPERATION INDICATOR lamp
Press once
<Cool>
Press again
<Heat>
Press once again
<Stop>
EMERGENCY OPERATION switch
63
Page 64
Compressor power factor
Indoor unit microprocessor
SSR61
Drive
circuit
Transistor
module
Indoor Unit
A
Indoor Unit
C
Indoor Unit
B
Gas pipe temperature thermistor RT66, 67, 68
Accumulator
Comp.
H.P.S 63H2
Discharge temperature thermistor RT61
Indoor Unit
A
Evaporation temperature thermistor RT63
Outdoor fan motor MF61
x 61 x 62 x 63
Defrost thermistor RT62
LEV1
LEV2
LEV3
Indoor Unit
B
Indoor Unit
C
Outdoor unit control microprocessor
Compressor primary current
Compressor secondary current
Fin temperature thermistor RT65
R. V. coil 21S4
H.P.S 63H1
Input signal
Output signal
IPM
Muffler
10-9. INVERTER MULTI SYSTEM CONTROL
MXZ30TN MXZ30TN2
64
Page 65
10-10-2. Outline of main power supply circuit
1. At the start of operation Rush current is generated the instant the electricity is turned on to the main power supply circuit to operate the compressor. To prevent the rush current from running into the main power supply circuit, R(Current-limiting resistor) absorbs the rush current. After the rush current is absorbed, X64(Relay) is ON and the circuit to R is short-circuited, then the electricity to R is bypassed. When X64 is ON, the system starts the operation of compressor.
2. At normal operation The noise of alternating current of power supply is eliminated by L61(Common mode choke coil). Then DS61(Diode stack) performs full-wave rectification of alternating current and the alternating current is converted to direct current. C62, C63(Smoothing capacitor) stabilizes the power supply converted to direct current from alternating current and supplies it to IPM(Intelligent power module). Direct current rectified by DS61 is converted to three-phase alternating current by IPM. Microcomputer installed in the electronic control P.C. board controls frequency and voltage of three-phase alternating current converted by IPM. Three-phase alternating current is supplied from IPM to the compressor with frequency and voltage decided by microcomputer based on various kinds of information. CT61,CT62(Current transformer) measures the current of main power supply circuit.
3. Power factor improvement of power supply Unlike inverter-less alternating current circuit, the power factor of this inverter circuit is improved by extending the period of the current running in the circuit.
C63 is used in this circuit to supply stable direct current voltage. However, in case only SMOOTHING CAPACITOR is used for stable supply of direct current, the power factor of power supply is lowered because the period of direct current running in the circuit is short. Therefore, for improvement of power factor, the circuit also uses C61(Power factor capacitor), L61(Reactor) and DS62(Diode stack) to prepare the direct current circuit to extend the period of the current running in the circuit.
10-10-1. Outline drawing of main power supply circuit
POWER SUPPLY
X64
L61
L1
L2
V
UW
A
K
L
NOISE FILTER P.C.BOARD
DS61
DS62
C61
CT
61
C63
C62
+
+
-
+
-
+
-
-
R
CT62
I.P.M P.C. BOARD
ELECTRONIC CONTROL P.C. BOARD
MC
10-10. INVERTER MAIN POWER SUPPLY CIRCUIT
MXZ30TN MXZ30TN2
65
Page 66
SYMBOL C61 C62, C63 CT61, CT62 DS61 DS62 IPM L L61 R
X64
NAME POWER FACTOR CAPACITOR SMOOTHING CAPACITOR CURRENT TRANSFORMER DIODE STACK DIODE STACK INTELLIGENT POWER MODULE REACTOR COMMON MODE CHOKE COIL
CURRENT-LIMITING RESISTOR
RELAY
FUNCTION It improves the power factor of power supply. It stabilizes the direct current voltage. It measures the current of main power supply circuit. It converts the alternating current voltage to direct current voltage. It is combined with L61 to improve the power factor of power supply. It generates three-phase alternating current and operates compressor. It is combined with DS62 to improve the power factor of power supply. It eliminates and absorbs the electrical noise. It absorbs the rush current so not to run into the main power supply circuit when the electricity is turned on.
It short-circuits the circuit to current-limiting resistor when the compressor operates.
4. Elimination of electrical noise Noise filter circuit is formed by L61, and the condenser installed on the noise filter P.C. board. It eliminates the electrical noise (both common mode and normal mode noise) of alternating current power supply supplied to main power supply circuit. Noise filter circuit also absorbs electrical noise that is generated in the inverter circuit and prevents it from reaching outside of the unit.
5. IPM Six power transistors that outputs the direct current waveform as three-phase alternating current waveform, the driving circuit which operates the power transistors, and the overcurrent detecting circuit which protects the power transistors are built into the IPM. It can simplify and miniaturize the control circuit.
10-10-3. Function of main parts
10-11. Optimal voltage control
Target power factor minus detected power factor (Calculated value is supposed to be "A".)
Calculation of voltage
correction value (%)
A[-2%
-2%<A<+2% A]+2%
Previous voltage correction value minus 1 Same as previous voltage correction value Previous voltage correction value plus 1
1 slip 0
Power factor
efficiency
The purpose of optimal voltage control is to operate the compressor at optimal voltage that meets the load detected by the power factor of the compressor.
1. Optimal
As shown on the right the efficiency (ratio of output against input) of the motor in the compressor becomes optimal when the sliding (ratio of differ­ence between the actual number of rotation and the number of synchronous rotation of motor) is one fixed value. The value of sliding can be calculated from the power factor since the sliding and the power factor are mutually related as shown in the table on the right. To make the value of sliding so that the efficiency of motor is optimal, the power factor of the compressor is detected. Then the detected power factor is controlled so that its efficiency can be high. As a result, it is possible to operate the compressor at optimal voltage.
2. How to determine the optimal voltage
Compare the detected power factor with the target power factor so that the efficiency of motor is optimal, the voltage correction value is changed and the optimal output voltage is determined. Optimal output voltage[V]= Standard voltage at certain frequency [V]x voltage correction value(%)
66
Page 67
When outdoor unit is operating, some indoor units stop and some operate.
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency: Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 units operation)
• After starting operation, adjustment in accordance with intake super heat, discharge temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are different. See 10-10 Operational frequency range. (As far as the indoor unit velocity control goes, refer to DRY operation in MICROPROCESSOR CONTROL in the indoor unit service manual.)
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency: Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 units operation)
• After starting operation, opening becomes the one that adjustment in accordance with discharge temperature was added to basic opening. w1
Thermostat ON in HEAT mode
LEV opening
Thermostat OFF in
COOL or DRY mode
Thermostat OFF in HEAT mode
Stop of all indoor unit
Indoor unit status
COOL : 5 pulse (full closed) HEAT : 59 pulse (slightly opened)
Thermostat ON in
COOL or DRY mode
Opening before stop 500 pulse in 15 minutes
When the outdoor unit operates (When the other indoor unit operate): 5 pulse. When outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes
• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
• When the outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes.
w1 LEV opening when the outdoor unit is operating: Upper limit 500, Lower limit 59
10-12. LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
Determination of LEV standard opening in each indoor unit
• The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below. (LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
• Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.
• Add opening provided in Difference in Operation number in the table below to determined LEV opening for each indoor unit, when 2 or 3 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse. < Calculation example of LEV opening > Cool operation: Compressor frequency 70Hz: 2 units ON: 18 class (170-150)p(80-60)o(70-60)+150+75-30=205 pulse
67
Page 68
7 20 40 60 80 100 120 140
Operation frequency of compressor (Hz) : F
120
130
140
150
160
170
180
190
200
210
220
LEV opening (Pulse)
Standard opening
12345678
COOL
HEAT
(1) Simultaneous correction of LEV openings by suction super heat (COOL, DRY)
Suction superheat (S.H.)
LEV opening correction (pulse)
more than 53.6
50 to53.6
46.4 to 50
42.8 to 46.4
42.8 or less
6 4 3 2 0
1 Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
w 1 Perform this, when number of operation units is 2units or more w 2 When the correction opening of suction super heat is 0, correct the LEV opening by Discharge temperature.
3 Discharge temperature
COOL DRY HEAT
••
-
w 2
w 2
<Correction>
432
Code4Code3Code2
Standard opening (pulse)
Difference in capacity
Difference in operation number
12345678
COOL
HEAT
130 120
130 130
130 140
150 155
Capacity code
Indoor unit
2
09312415/17
170 170
180 185
180 200
190 215251550307545
-30
-10
-40
-40
-50
-50
(Correction is performed only for operating unit.)
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
Correct the LEV openings simultaneusly as the table below
68
Page 69
(2) Separate correction (COOL, DRY)
Difference of superheat
LEV opening correction (pulse)
more than 48.2
42.8 to 48.2
37.4 to 42.8
37.4 or less
8 6 2 0
Operation frequency of compressor
Minimum ~ 20
21 ~ 30 31 ~ 40 41 ~ 55 56 ~ 70 71 ~ 90
91 ~ maximum
Single
123.8
134.6
149.0
152.6
158.0
161.6
165.2
Double
140.0
147.2
154.4
161.6
170.6
181.4
183.2
Triple
143.6
150.8
163.4
174.2
186.8
194.0
194.0
Single
131.0
136.4
145.4
158.0
176.0
185.0
185.0
Double
120.2
125.6
131.0
136.4
145.4
156.2
165.2
Triple
118.4
123.8
129.2
134.6
143.6
154.4
163.4
Number of operating unit. Number of operating unit.
COOL, DRY HEAT
Discharge temperature (°F)
LEV correction opening (pulse)
more than Target discharge temperature+19.8 Target discharge temperature+19.8 to Target discharge temperature+14.4 Target discharge temperature+14.4 to Target discharge temperature+9 Target discharge temperature+9 to Target discharge temperature+3.6 Target discharge temperature+3.6 to Target discharge temperature-3.6 Target discharge temperature-3.6 to Target discharge temperature-9 Target discharge temperature-9 to Target discharge temperature-14.4 Target discharge temperature-14.4 to Target discharge temperature-19.8 Target discharge temperature-19.8 or less
COOL
10
4 2 1 0
-1
-2
-5
-8
HEAT
7 6 3 2 0
-1
-1
-3
-7
(Correction is performed only for operating unit.) (When 2 or more units are operating.)
Correction by the separate super heat. Correct the LEV separately by the difference between gas pipe temperature and minimum gas pipe temperature.
1 Calculate super heat using the expression below.
(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)
2 Separate correction is performed according to each super heat in the table below.
(3) LEV opening correction by discharge temperature
When LEV correction output is 0 pulse by the suction super heat at COOL, DRY or HEAT operation, correct LEV is corrected according to the following table.
The target discharge temperature is determined according to frequency zone and number of operation unit of the compressor.
Correct the LEV opening according to difference between the target discharge temperature and discharge temperature.
69
Page 70
10-13. Operational frequency range
2 3 4 4 5 6 7 8 6 7 8 9
18
20
30
52 68 85
105
110
120
33 46 73
80
90
104
25
40
58
18
22
26
70 80 86
90
110
120
70 80 86
100
100
100
49 65 80
88
100
98
1
2
3
1 1 2
1 2 1
8/10 of maximum frequency 9/10 of maximum frequency 7/10 of maximum frequency
Maximum frequency
capacity
code
DRY
(Hz)
Min. Max. Rated Min. Max.
Defrost
Rated
COOL (Hz)
HEAT (Hz)
Number of
operating
unit
Note
Limit the maximum frequency by means
of fan speed
When all the indoor units in their operation are running in the same operation mode and when their fan speed is set to "Low," the maximum frequency is limited to 6/7 the rated frequency in the mode.
•Limit the maximum frequency by means of operation mode
When some indoor units are operating in cool mode while others are in dry mode, the maximum frequency, which has the highest frequency of all the operation mode, is limited as the table below:
DRY COOL
10-14. Heat defrosting control
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is 26.6°F or less.
2.When specified non-defrosting time, is counted in the control p.c.board is satisfied.
(Total time of compressor operating) Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights
2.4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 46.4°F or more.
2. When it has spent 10 minutes for defrosting. Defrosting finishes at condition of 1 or 2.
10-15. High pressure protection
(1) High pressure protection control on heat mode
Temperature of the main pipe temp. thermistor in the indoor unit controls the operation frequency. When temperature of the main pipe temp. thermistor is approx. 120.0°F, the operation frequency is set at the current level. When temperature of the main pipe temp. thermistor is approx. 125.6°F the protection control decreases the frequency at the speed of 3Hz a minutes. When temperature of the main pipe temp. thermistor is approx. 134.6°F the protection decreases the frequency at the speed of 4Hz a minute and changes the outdoor fan to Low.
Note:Temperature of the pipe temp. thermistor is different depending on the indoor unit.
Temperature of the pipe temp. thermistor is 113°F or less, the protection control is Released.
(2) High pressure protection control by high pressure switch (H.P.S 63H1)
High-pressure switch controls the operation frequency and outdoor fan motor. <Control status> When high-pressure switch is ON. (When discharge pipe pressure is 398.8 PSIG or more.) <Control details> (a) When cooling or drying
The protection control decreases the compressor frequency at the speed of 10Hz a minute. (The compressor operates continuously in min. frequency according to a command to decrease more than the min. level.)
(b) When heating
The protection control decreases the compressor frequency at the speed of 10Hz a minute. The protection control changes the outdoor fan to Low.
70
Page 71
<Release status>
COOL
Fan speed
Up
Down
Up
Down
Single Double Triple
Mode
HEAT
Indoor unit operation
<Relation between compressor frequency and fan speed.>
55 Hz 45 Hz 60 Hz 50 Hz
50Hz 45 Hz 45 Hz 40 Hz
50 Hz 45 Hz 40 Hz 35 Hz
Up
Down
Fan speed
Hi
Low
Compressor frequencyMin. Max.
When high-pressure switch is OFF. (When discharge pipe pressure is 340.8 PSIG or more.) Or, the compressor stops.
10-16. Discharge temperature protection control
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp. thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temp. thermistor exceeds 240.8°F, the control stops the compressor. When temperature of the discharge temp. thermistor is 212°F or less, the controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temp. thermistor is expected to be higher than 240.8°F, the control decreases 12Hz from the current frequency. When temperature of the discharge temp. thermistor is expected to be higher than 231.8°F and less than 240.8°F, the con­trol decreases 6Hz from the current frequency. When temperature of the discharge temp. thermistor is expected to be higher than 219.2°F and less than 231.8°F, the con­trol is set at the current frequency.
10-17. Refrigerant recovery control on heating
<Control status>
The control performs when the all following status are satisfied;
• When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF)
• When discharge temperature becomes 224.6°F or more.
• When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.
<Control details>
LEV opening, which adjusts to not operating indoor unit, is considered to be 80 pulse.
<Control finish status>
The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.
• When it passed 60 seconds since the control has started.
• When the discharge temperature is 194°F or less.
10-18. Outdoor fan control
Fan speed is switched according to a number of operating indoor unit and the compressor frequency.
Note
• When operation, fan speed of High/ Low mode changes to Very High/ High mode by promoting those fan speeds respec­tively by 1 step after defrosting is operated. This control is cleared, when the compressor off.
•When overheat protection of P.C. board temperature or fin temperature operates, the outdoor fan speed is fixed to Very High mode regardless of compressor frequency. Also, when the overheat protection is cleared, the fan speed is back to normal
•When the indoor coil thermistor is 134.6°F or more on HEAT operation, fan speed is fixed to Low notch . Or, the indoor coil thermistor is 113°F or less on HEAT operation, fan speed is back to normal.
71
Page 72
Discharge temperature thermistor
Purpose
Protection Defrosting
Protection Defrosting
Control
Control Protection Protection
Control
Compressor LEV
Outdoor fan motor
4-way
valve
Sensor
Defrost thermistor
Fin temperature thermistor
Indoor pipe temperature thermistor
Capacity code
Evaporation temperature thermistor Gas pipe temperature thermistor High pressure switch
Actuator
10-19. Relation between main sensor and actuator
Relation between main sensor and actuator.
11
MSH09TW MSH12TN MSH15TN MSH17TN
SERVICE FUNCTIONS
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
11-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accom­plished regardless of the defrost interval restriction. (Refer to page 96.)
Defrost thermistor RT61 must read below 27°F(MSH09TW,MSH12/15/17TN)/ 32°F(MSH09TW
U1
). (Refer to page 73.)
11-2. CHANGE IN DEFROST SETTING MXZ30TN and MXZ30TN2 is not equipped with this function.
<MSH09TW, MSH12/15/17TN>
<JPC> When the JPC wire of the deicer P.C. board is cut, the defrost interval time is changed.
<JPE> When the JPE wire of the deicer P.C. board is cut, the defrost temperature is changed. (Refer to page 96.)
Model
MUH09TW MUH12TN MUH15TN
MUH17TN
Jumper wire Change point
JPC
JPE
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
MUH12TN -
U1
MUH15TN -
U1
U1
U2
MXZ30TN
U2
MXZ30TN2
U1
- ,MSH12/15/17TN-
Defrost interval time changes from 40 minutes to 15minutes.
Defrost start temperature changes from 27˚F to 32˚F. Defrost finish temperature changes from 38˚F to 50˚F.
72
Page 73
<MUH09TW- , MUH12/15/17TN- , MUH12/15TN- >
U2U1U1
<JPC> When the JPC wire of the deicer P.C. board is soldered, the defrost interval time is changed. <JPE> When the JPE wire of the deicer P.C. board is soldered, the defrost temperature is changed. (Refer to page 96.)
Model
MUH09TW - MUH12TN ­MUH12TN - MUH15TN ­MUH15TN ­MUH17TN -
U1 U1
Jumper wire Change point
U2U1 U2U1
JPC
JPE
Defrost interval time changes from 15 minutes to 40 minutes.
Defrost start temperature changes from 32˚F to 27˚F. Defrost finish temperature changes from 50˚F to 38˚F.
11-3. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to page 94 or 95.)
Set time : 1 minute 1-second Set time : 3 minutes 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time
is shortened by short circuit of JPG and JPS.)
11-4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the indoor unit number.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries and press the OPERATE/STOP(ON/OFF)button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
73
Page 74
C111
CN201
C11
CN211
IC152
CN151
SW1
CN112
CN121
IC101
CN111
JR07
Table 1
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
CN104
JHA
CN102
CN112
CN113
CN151
CN101
BZ
SW
IC101
RA102
CN201
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
11-5. AUTO RESTART FUNCTION
When the indoor unit is operated with the remote controller, the signals of the operation mode, the set temperature, and the fan speed are sent from the indoor electronic control P.C. board and memorized in the auto restart assembly. When the main power is turned off and then turned back on, the unit restarts automatically in the memorized set conditions approximately after 3 minutes.
How to release “AUTO RESTART FUNCTION”
1 Turn off the main power for the unit. 2 Pull out the indoor electronic control P.C. board and the display P.C.board. (Refer to page 102 or 104.) 3<MSH09>
Solder the Jumper wire or the Resistor 220to the JR07 on the indoor electronic control P.C.board. (Refer to page 94.)
<MSH12/15/17>
Disconnect the AUTO RESTART ASSY from CN104, and solder the Jumper wire to JHA on the indoor electronic control P.C. board.(Refer to page 95.)
Operation
1 If the main power (115V AC) has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 minutes
for the compressor to start running.)
MSH09
MSH12/15/17
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding system that allows the units to start one by one.
74
Page 75
12
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
RESET button
Lead wiring
Housing point
TROUBLESHOOTING
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW -
MSH12TN -
MSH15TN -
MSH17TN -
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
MUH12TN -
U1
MUH15TN -
U1
U1
MXZ30TN
U2
MXZ30TN2
U2
12-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, first be sure to turn off the remote controller to stop the unit, and then after con­firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to the flow chart on page 76, 77 and the check table on page 78, 79, 80.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, the remote controller can be repaired only by the battery replacement. To operate the remote controller nor­mally, replace the batteries in the following order. This remote controller has the RESET button. After refilling new batteries, press the RESET button with tip end of ball point pen or the like, and then use the remote controller.
1 Remove the front lid and replace batteries.
Then re-attach the front lid.
NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.
2 Press the RESET button.
75
Page 76
12-2. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage" on page 94, 95.
Refer to D "Check of outdoor unit" on page 86.
Refer to B "Check of remote controller and receiver P.C. board" on page 84.
Flash on and off at
0.5-second interval Cause: Indoor/ Outdoor unit
• Mis-wiring
2-time flash Cause: Indoor unit
• Trouble of room temperature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Refer to F "How to check mis-wiring and sirial singal error (When outdoor unit doesn't operate)" on page 87. 1
Check room temperature thermistor and indoor coil thermistor. Refer to "Test point diagram and voltage" on page 94, 95.
1-time flash Cause: Indoor/Outdoor unit
• Trouble of serial signal
Refer to A "Check of indoor fan motor" on page 83.
1. Check indoor / outdoor connecting wire.
2. Refer to C "Check of indoor electronic control P.C. board" on page 85.
Outdoor unit doesn't stop even if indoor unit stops.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to E "Check of outdoor unit" on page 86.
Refer to H "Check of R.V. coil" on page 88.
Refer to G "Check of outdoor thermistor" on page 88.
Indoor unit operates. Outdoor unit doesn't operate normally.
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
MUH09TW
U1
MUH12TN
U1 U1
MUH15TN
U1
MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
MUH12TN -
U1
MUH15TN -
U1 U1
U2 U2
1<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the indication shows “the trouble of mis-wiring.”
76
Page 77
MXZ30TN MXZ30TN2 only
Operation start
Check the outdoor unit LED indicator
I Check of power supply See page 89.
• Indoor unit serial signal error J Check of serial signal See page 89.
• COOL or HEAT operation only K Check of R.V.coil See page 90.
• When cooling, room does not cool. M Check of inverter, compressor See page 91.
• When cooling, heat exchanger of non-operating indoor unit frosts.
•When heating, non operating indoor unit gets warm. L Check of LEV See page 91.
• When cooling, dew drops in the non-operating indoor unit Check of mis­piping.
• When heating, room does not get warm. M Check of inverter,compressor See page 91. Check mis-piping Shortage of capacity
Refer to indicator list See page 79, 80.
OFF
"00"
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit. Then, check the outdoor unit with referring to this page.
Display other than "00"
77
Page 78
1. Troubleshooting check table
Operation Indicator
flashing
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighted during normal operation.
• The following indication applies regardless of shape of the indicatior.
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
MUH12TN -
U1
MUH15TN -
U1 U1
U2 U2
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table
NO.
Abnormal
point
Indication
Symptom
Detect method
Check point
Mis-wiring
1
Serial sig­nal
Indoor coil thermistor
2
Room tempera­ture ther­mistor
Indoor fan
3
motor
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
2-time flash
2.5-second OFF
<MSH09>
3-time flash
2.5-second OFF
Outdoor unit does not run.
Outdoor unit does not run.
Indoor fan repeats 12 sec­onds ON and 3 minutes OFF. When the indoor fan breaks, the fan keeps stop­ping.
When the unit operates by the remote controller or emer­gency operation switch at 3 minutes after the main power supply is turned on.
When serial signal from out­door unit stops for 4 to 5 sec­onds.
Detects Indoor coil/ room tem­perature thermistor short or open circuit every 8 seconds during operation.
When rotational frequency feedback signal is not emit during 12-second indoor fan operation.
Check wiring (visual check and conductiv­ity check).
Check indoor electronic control P.C. board.
Check outdoor DEICER P.C. board.
Check electrical parts.
Check resistance of thermistor.
Re-connect connector.
Check indoor electronic control P.C.
board.
Disconnect connector CN211 and then
check connector CN121 - to make sure rotational frequency feedback signal of 1.5V or over exists.
Check indoor electronic control P.C.
board.
Check indoor fan motor.
Re-connect connector.
2
3
6-time flash
Outdoor
4
thermistor
2.5-second OFF
Outdoor unit does not run
When the outdoor thermistor shorts or opens after the com­pressor start-up.
78
Check deicer P.C. board.
Check resistance of thermistor.
Page 79
MXZ30TN MXZ30TN2
Note . LED indicates "00" in the normal status.
7-segment LED display
00
If there is defect in the following parts(electronic control P.C. board, relay P.C. board, high pressure switches(63H1,63H2),indoor /outdoor fan motor , or indoor coil thermistor), the compressor may stop even with the display remained at “ 00 “.In any case, reset the breaker and check the above-stated parts.
Symptom Outdoor unit does not operate.
Display Abnormal Detecting method Check points
aa44
(A4)
Outdoor power system abnor­mality
When the compressor operation has been interrupted by overcurrent protection continuously three times within 1 minute after start-up, the compressor stops operation.
Error mode
Normal
• Inverter output
• Compressor
aa33
(A3)
Symptom Outdoor unit stops and restarts every 3 minutes.
Display Abnormal Detecting method Check points
ee99
(E9)
ee66
(E6)
ff88
(F8)
aa88
Outdoor electronic control P.C. board abnormality
Evaporation temperature ther­mistor abnormality
Discharge temperature ther­mistor abnormality
Fin temperature thermistor abnormality
Overcurrent protection
(A8)
dd66
(d6)
dd44
(d4)
dd77
Discharge temperature over­heat protection
Fin temperature overheat pro­tection
High pressure protection
(d7)
ff55
(F5)
ff66
(F6)
ff77
(F7)
Room-A gas pipe temperature thermistor abnormality
Room-B gas pipe temperature thermistor abnormality
Room-C gas pipe temperature thermistor abnormality
When the nonvolatile memory data cannot be read properly on the out­door controller board
The compressor stops when a short or open circuit occurs in the evap­oration temperature thermistor during compressor running.
The compressor stops when a short or open circuit occurs in the dis­charge temperature thermistor during compressor running.
The compressor stops when a short or open circuit occurs in the fin tem­perature thermistor during compressor running.
When over current is applied to the power module, the compressor stops and restarts in 3 minutes.
When the discharge temperature thermistor detects 240.8°F or above, the compressor stops and restarts operation in 3 minutes. (Protection will be released at 212°F or below.)
When the fin temperature thermistor detects 192.2°F or above, the com­pressor stops and restarts operation in 3 minutes.
When the compressor starts, primary current or output voltage stops the compressor and restarts in 3 minutes.
When a short or open circuit occurs in the Room-A gas pipe temperature thermistor.
When a short or open circuit occurs in the Room-B gas pipe temperature thermistor.
When a short or open circuit occurs in the Room-C gas pipe temperature thermistor.
• Outdoor electronic control P.C. board
• Check the characteristic of the evapora­tion temperature thermistor. Refer to
on page 90.
• Check the contact of P. C. board con­nectors.
• Check the characteristic of the discharge temperature thermistor. Refer to KKon page 90.
• Check the contact of P. C. board con­nectors.
• Check the characteristic of the fin temper­ature thermistor. Refer toKKon page 90.
• Check the contact of P.C. board connec­tors.
• Check the inverter and compressor. Refer to JJon page 89.
• Check the amount of gas.
• Check the indoor/outdoor air flow for short cycle.
• Check the indoor unit air filter for clogging.
• Check the amount of gas and the refriger­ant cycle.
• Check the outdoor unit air passage.
• Check the outdoor unit air passage.
• Check the power module.
• Check the outdoor fan motor. Refer to on page 91.
• Amount of gas
• Outdoor unit air passage.
• Check the ball valve.
• Room Agas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
• Room B gas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
• Room C gas pipe temperature thermistor characteristic.
• Contact of P.C. board connectors.
KK
LL
79
Page 80
Symptom Outdoor unit operates. (The compressor operates at reduced frequency.)
P
RED BLK
WHT
Display Abnormal Detecting method Check points
dd88
(d8)
dd99
(d9)
dd77
(d7)
dd66
(d6)
Frequency drop by current protection
Frequency drop by overload protection
Frequency drop by high pres­sure protection
Frequency drop by defrosting in cooling
Frequency drop by discharge temperature protection
When the outdoor unit input current exceeds 22.5 A, the compressor operates at reduced frequency.
When the compressor load exceeds the specified value, the compres­sor operates at reduced frequency.
When indoor pipe temperature exceeds 131°F during heating, the com­pressor operates at reduced frequency.
When the indoor pipe temperature falls to 42.8°F or below during cool­ing, the compressor operates at reduced frequency.
When the discharge temperature exceeds 230°F, the compressor oper­ates at reduced frequency.
These symptoms do not mean any abnormality of the product, but check the
following points.
• Air filter clogging.
• Amount of gas.
• Short cycle of indoor/outdoor air flow.
dd33
(d3)
(d1)
Symptom Outdoor unit operates.
Display Abnormal Detecting method Check points
Frequency drop by high pres­sure switch (63H1) protection
Low discharge temperature
dd11
protection
ee77
Defrost thermistor abnormality
(E7)
hh44
(h4)
Power factor detection abnor­mality
When the high pressure exceeds 398 PSIG, the compressor operates at reduced frequency. In addition, the fan speed changes.
When the state with low discharge temperature of which 122°F in COOL and 119.3°F or less in HEAT for 20 minutes, the compressor operates continuously.
When a short or open circuit occurs in the defrost thermistor during heating * In this case, the compressor continues to operate.
When the compressor power factor cannot be detected * In this case, the compressor keeps running.
• Amount of gas.
• Outdoor unit air passage.
Check the amount of gas.
• Replace the outdoor controller board.
• Check the contact of LEV board connec­tors.
• Defrost thermistor characteristic.
• Contact of P. C. board connectors.
• Compressor wiring.
2. Trouble criterion of main parts
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
Part name
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Defrost thermistor(RT61)
U1
MUH09TW
U1
MUH12TN
U1
MUH15TN
U1
MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
Check method and criterion
Measure the resistance with a tester. (Part temperature 50°F ~ 86°F)
Normal
8k~ 20k
Measure the resistance with a tester. (Part temperature 14°F ~ 104°F)
U1
MUH12TN -
U1
MUH15TN -
U1 U1
Abnormal
Open or short-circuit
U2 U2
Figure
Ambient temper-
ature thermistor
(RT63)
MSH09TW ­MSH12/15/17TN -
only
Compressor(MC)
MUH09TW MUH12/15/17TN
OPEN 302 CLOSE
203
U1
°F i 9°F
°F i 18°F
U1
Measure the resistance between the terminals with a tester. (Part temperature14°F ~ 104°F)
C-R C-S
5k~ 60k
0.7~0.9
1.3~1.6
Normal
MUH12/15
1.4~1.9
2.4~3.0
Abnormal
Open or short-circuit
Normal
MUH17MUH09
1.4~1.8
2.3~2.9
80
Abnormal
Open or
short-circuit
Page 81
1 2 3
RED
YLW GRY BRN
WHT
MAIN
AUX.
1 2 3
BLK
FUSE
RED
ORN
BLU
BLK
MAIN
WHT
YLW
AUX.1
BRN
AUX.2 AUX.3
AUX.4
FUSE
RED
AUX.
MAIN
BLK
WHT
P
RED ORN
BLK
WHT
P
AUX.
MAIN
RED
YLW
BRN
ORN
GRN
ROTOR
YLW
RED
BLU
ORN
PNK
ROTOR
MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
U1 U1 U1 U1
MUH09TW MUH12TN MUH15TN MUH17TN
MUH09TW ­MUH12TN ­MUH15TN ­MUH17TN -
U1
MUH12TN -
U1
MUH15TN -
U1 U1
U2 U2
Part name
Indoor fan motor(MF)
MSH09TW
MSH09TW -
U1
CUT OFF 262°F
MSH12/15/17TN MSH12/15/17
U1
-
TN
CUT OFF 293°F
Outdoor fan motor(MF)
OPEN
302
°F i 9°F CLOSE 203
°F i 18°F
Check method and criterion
Measure the resistance between the terminals with a tester. (Part temperature 50°F ~ 86°F)
Normal MSH09
Motor partSensor partMotor part
WHT-BLK BLK-RED
76~83 70~76
Measure the voltage Power ON.
BRN-YLW YLW-GRY
Normal
MSH09
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V (Approx.)
Abnormal
Remain 0V or 5V
Normal
WHT-BLK BLK-YLW YLW-BLU BLU-BRN
MSH12/15
65~72
8~10
4~6
5~7
28~31
MSH17
52~57 10~12
4~5 5~6
35~39
BRN-RED
Measure the resistance between the terminals with a tester. (Part temperature14°F ~ 104°F)
Normal
WHT-BLK BLK-RED
MUH09
54~67 58~72
MUH12
116~143 215~264
MUH15
102~126
97~120
MUH17
60~75 77~96
Measure the resistance between the terminals with a tester. (Part temperature 50°F ~ 86°F)
Abnormal
Open or
short-circuit
Abnormal
Open or
short-circuit
Abnormal
Open or
short-circuit
Figure
MSH09
MSH12/15/17
MUH09/12
MUH15/17
MSH09
MSH09
Vane motor(MV)
BRN-other one
282 ~ 306
Normal
MSH12/15/17
RED-other one
358 ~ 388
81
Abnormal
Open or
short-circuit
MSH12/15/17
PP
:INNER PROTECTOR
Page 82
W
U
V
WHT
RED
BLK
WHT
BLK
P
ORN BLU
RED YLW
LEV
WHT
RED
YLW
BRN
ORN
BLU
MXZ30TN MXZ30TN2
Part name
Defrost thermistor Evaporation/ Gas pipe temperature thermistor
Discharge temperature thermistor
Compressor
Measure the resistance using a tester. (Part temperature 14°F ~ 104°F)
Measure the resistance using a tester, after warming up the thermistor by holding by hand. (Part temperature : 68°F ~ 104°F)
Measure the resistance between terminals using a tester. (Winding temperature : 14°F ~ 104°F)
Check method and criterion
Normal
abnormal
5k~ 55k Open or short-circuit
Normal
abnormal
100k~ 250k Open or short-circuit
Normal abnormal
1Each phase 0.53~ 0.66 Open or short-circuit
Figure
Outdoor fan motor OPEN
275
°F i 9°F
CLOSE 187
°F i 27°F
R. V. coil
Linear expansion valve
Measure the resistance between lead wires using a tester. (Part temperature : 14°F ~ 104°F)
WHT - BLK
BLK - YLW YLW - BLU RED - BLK
Normal
69.0~ 86.0
23.0~ 30.0
10.0~ 13.0
73.0~ 91.0
abnormal
Open or
short-circuit
(Not including
WHT - ORN)
Measure the resistance using a tester. (Part temperature 14°F ~ 104°F)
Normal abnormal
1640~ 2310 Open or short-circuit
Measure the resistance using a tester.(Part temperature 14°F ~ 104°F)
Lead wire color Normal
Abnormal WHT - RED RED - ORN
YLW - BRN
37.4 ~ 53.9
Open or short-circuit
BRN - BLU
Measure the resistance using a tester. (Part temperature 14°F ~ 104°F)
High pressure switch (HPS)
HPS1 340.8 ± 21.8PSIG HPS2 369.8 ± 29 PSIG HPS1 398.8 PSIG HPS2 497.5 PSIG
Pressure
Operation OFF
+
­+
-
7.3
14.5 0
21.8
82
Normal abnormal
Short
Other than
those
listed at
Open
left
P Inner protector
Page 83
Indoor fan does not operate.
AA
Check of indoor fan motor
Turn OFF the power supply. Check connector (Fan motor) visually.
No
Are lead wires connected?
Re-connect the lead wires.
Yes
Disconnect lead wires from connector (Fan motor). Measure resistance between lead wires No.1 and No.3 and then No.2 and No.3 (MSH09).
Is resistance 0 (short circuit) or (open circuit)?
Yes ( 0 or ∞ )
Repair or replace the indoor fan motor.
{
No.1 and No.4 and then No.3 and No.4 (MSH12/15/17).
No
(others)
No
Is soldered point of the connector
correctly soldered?
MSH12/15/17
MSH09
Replace the indoor electronic con­trol P.C. board.
Insert screwdriver into air outlet and rotate indoor fan (motor) slowly for 1 revolution or more, and measure voltage between CN 121 1-2 .
Does voltage repeat 0V DC and more than 5V?
Yes
No
Re-solder it.
}
Yes
83
Page 84
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
w Check if the remote controller is exclusive for this air conditioner.
w
In case of replacing the receiver P.C. board of MSH09, replace the indoor electronic control P.C. board with it because they are unified.
BB
Check of remote controller and receiver P.C. board
Switch on the remote controller.
Is LCD display on the remote con­troller displayed?
Yes
Remove the batteries, then set them back and press the RESET button. Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
Connect properly.
No (not clear)
No
No
No
Replace the batteries.(Refer to page 75.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 3.28ft.?
No
MSH12/15/17
Is the connector connecting receiver P.C. board and indoor electronic con­trol P.C. board properly connected?
Yes
Replace the receiver P.C. board.
Does the unit receive signal of ON/OFF with the remote controller and emit a beep tone?
Yes
OK
No
Yes
Replace the remote controller.
Re-install the unit away from lights.
Attach a filter on receiving part.
MSH09
Replace the power monitor, receiver P.C. board with the indoor electronic
control P.C. board.
Connect properly.
Replace the indoor electronic control P.C. board.
No
No
No
Is auto restart assembly properly connected ?
Yes
Replace the auto restart assembly.
Does the unit receive signal of ON/OFF with the remote controller and emit a beep tone?
Yes
OK
Does the unit receive signal of ON/OFF with the remote controller and emit a beep tone?
Yes
OK
84
Page 85
Check the both “parts side” and “pattern side” of indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse (F11) blown?
Be sure to check both fuse and varistor in any case.
Replace the fan motor.
Replace the indoor electronic control P.C. board.
Is winding resistance of fan motor 0 "?
Is winding resistance of vane motor 0 "?
No
Yes
Replace the vane motor.
No
Yes
Yes
Is varistor (NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply. Disconnect indoor fan motor connector CN211(MSH09 only) and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
No
No
Does the unit operate with the remote controller or the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?
Yes
No
Be sure to check both resistances.
Turn OFF the power supply.
Turn OFF the power supply.
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
CC
Check of indoor electronic control P.C. board
85
Page 86
After 30 seconds, does compressor stop?
No
Yes
Replace the deicer P.C. board.
Yes
1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL or HEAT mode by
pressing the EMERGENCY OPERATION switch for 1 minute or more. 4 Stop it by pressing the EMERGENCY OPERATION switch twice or once.
Ok
No
After 30 seconds, does outdoor fan motor stop?
Replace the deicer P.C. board.
Yes
Ok
No
Rectify the connecting wire.
Is there 115V AC (MSH09),208/230V AC (MSH12/15/17) to terminal block between 3 (MSH09/12), COM (MSH15/17)on the compressor contactor(52C) and N (MSH09) L2 (MSH12/15/17) on the outdoor terminal block?
Is there 115V AC (MSH09), 208/230V AC (MSH12/15/17) between 4 on the compressor contactor (52C) (MSH09/12), TAB21(MSH15/17) and TAB20 on the deicer P.C. board?
Yes
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
No
Yes
Compressor doesn't operate.
Yes
Yes
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Outdoor fan motor doesn't operate.
No
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor capacitor, and rectify the connecting wire.
Start
Yes
Is there 115V AC (MSH09), 208/230V AC (MSH12/15/17) between 4 on the compressor contactor (52C) (MSH09/12), TAB21(MSH15/17) and TAB20 on the deicer P.C. board?
Is there 115V AC(MSH09), 208/230V AC (MSH12/15/17) to terminal block between L1 - N (MSH09), L1 - L2 (MSH12/15/17)?
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Yes
Yes
No
Check the outdoor fan motor and rectify the connecting wire.
Replace the deicer P.C. board.
No
No
Yes
Is there 5V DC between J8 –J9 on the deicer P.C. board?
+
Is there 5V DC between J8 –J9 on the deicer P.C. board?
+
Is there 115V AC (MSH09),208/230V AC (MSH12/15/17) to terminal block between 3 (MSH09/12), COM (MSH15/17)on the compressor contactor(52C) and N (MSH09), L2 (MSH12/15/17)on the outdoor terminal block?
Is there 115V AC(MSH09), 208/230V AC (MSH12/15/17) to terminal block between L1 - N (MSH09), L1 - L2 (MSH12/15/17)?
Compressor and/or outdoor fan does not operate. (Only indoor fan operates.)
DD
Check of outdoor unit
Compressor and/or outdoor fan motor doesn’t stop.
EE
Check of outdoor unit
86
Page 87
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second or flashes once. Outdoor unit doesn’t operate.
FF
How to check mis-wiring and serial signal error
Start
Turn OFF the power supply.
Turn ON the power supply.
Rectify the wiring.
Correct the mis-wiring.
No
Is the power voltage to terminal blocks of indoor/outdoor units normal?
Yes
Turn ON the EMERGENCY OPERATION switch.
After 3 minutes that power supply has been turned on, does the compressor start operating?
(any mode possible)
No
No
Is the terminal blocks11and33on the indoor unit properly connected to their counter parts on outdoor unit?
Yes
Turn OFF the Power supply. Check by using Checking Mode.
11
Disconnect indoor/outdoor wiring (at indoor terminal blocks
and 33)
22
Short circuit between indoor terminal blocks 11and 33.
Turn ON the Power supply.
33
While pressing OPERATION SELECT button on remote
controller, press RESET button on remote controller.
(LCD on remote controller displays all signs.)
Press OPERATE/STOP(ON/OFF) button on the remote controller to send signal.
Yes
11
OK
Replace the indoor electronic
control P.C. board.
Make sure the unit emits a beep tone.
No
Does the OPERATION INDICATOR lamp on the indoor unit flash on?
Yes
Replace the deicer P.C.board.
Before the unit resumes normal operation.
•Release the checking mode by pressing RESET button on the remote controller, and then send the unit signal to stop operation.
•Turn OFF the power supply to indoor/outdoor units.
•Get indoor terminal blocks 11and 33opened, and re-connect indoor/ outdoor wiring.
Be sure to turn OFF the power supply to
[]
indoor/outdoor units in replacing P.C. board.
87
Page 88
When OPERATION INDICATOR lamp flashes 6-time.
Measure resistance between CN 661 1 and 2.
No
Yes
Replace the thermistor.
Defrost thermistor (RT61)
Re-connect CN661. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Does the resistance of thermistor have the characteristics on page 96?
No
Yes
Does the unit operate 10 minutes or more?
Replace the deicer P.C.
board.
Ok 3
3 Defective contact of the connector is considered.
Turn OFF the power supply.
After 3 minutes, does the unit operate in COOL mode?
OK
Yes
Yes
No
After 3 minutes, does the unit operate in HEAT mode?
OK
No
Replace the deicer P.C. board
No
Replace the R.V. coil.
Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.
Is there 115V AC (MUH09), 208/230V AC (MUH12/15/17) between CN72112 on the deicer P.C. board? Refer to page 96.
Replace the deicer P.C. board.
Yes
Yes
No
Replace the R.V. coil.
Turn ON the power supply and operate the indoor unit in COOL mode by pressing the EMERGENCY OPERATION switch.
Is there 115V AC (MUH09), 208/230V AC (MUH12/15/17) between CN72112 on the deicer P.C. board? Refer to page 96.
Thermistors in the outdoor unit are abnormal.
GG
Check of outdoor thermistor
(MUH09/12/15/17)
W Disconnect the connector CN661 from the deicer P.C. board.
(Check the characteristics of thermistor.)
Unit operates COOL mode even if it is set to HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
HH
Check of R.V. coil
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
HH
Check of R.V. coil
(MUH09/12/15/17)
(MUH09/12/15/17)
88
Page 89
Outdoor unit does not operate. (LED display: display OFF)
II
Check of power supply
Start
Check the connecting of main circuit parts and connector (CN501: I.P.M P. C. board, CN 801: Electronic control P. C. board, CN554: relay P. C. board)
Turn on power supply
(MXZ30TN MXZ30TN2)
Is there voltage of 208V AC - 230V AC in the power supply terminal block?
Yes
Is there voltage of 290V DC - 330V DC across the smoothing capacitor?
Yes
Replace the electronic control P. C. board.
No
No
Check the power supply cable.
Is there voltage of 208V AC - 230V AC across the output cable (LD63, LD64) in the noise filter P. C. board?
Is there voltage of 208V AC - 230V AC across the input terminal part in the diode module (DS61)?
Check the main circuit parts and replace it.
Outdoor unit does not operate. (LED display:
JJ
Check of serial signal
Start
(MXZ30TN MXZ30TN2)
0000
Replace the noise
No
filter P. C. board
Yes
Replace the current
No
limiting resistor.
w When replacing, check the
Yes
connection of connector CN720 in the outdoor electronic control P. C. board
)
1. Check the indoor unit with referring to F How to check mis-wiring and serial signal error.
2. Turn off the power supply of the indoor and outdoor unit and connect the indoor/outdoor unit connecting wire correctly.
3. Check the connection of indoor/ outdoor unit connecting wire in the outdoor unit terminal block, and check the connection of the connector (CN601: unit A, CN 602: unit B, CN603: unit C) in the electronic control P. C. board.
4. Disconnect the lead wire to the compressor. 3 minutes after turning on the power suppy, start EMERGENCY OPERATION.
Is there voltage of 5V DC - 10V DC between No. 3 (+) and 1 (-) in the outdoor terminal block.
No
Recheck a connected circumstance of the indoor/ outdoor unit connecting wire.
Yes
Replace the electronic control P. C. board.
89
Page 90
The cooling operation or heating operation does not operate. (LED display:
KK
Check of R. V. coil
• When heating operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power suppy, start EMERGENCY OPERATION in HEAT mode.
(MXZ30TN MXZ30TN2)
0000
)
Is there voltage of 208V AC - 230V AC between pin1 and pin 2 at connector CN913?
Yes
Turn off power supply of indoor and outdoor unit.
Disconnect the connector CN913 in noise filter P. C. board, and measure the resistance of R. V. coil to check the integrity.
Yes
Replace the 4-way valve.
• When cooling operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power suppy, start EMERGENCY OPERATION in COOL mode.
No
Replace the R. V. coil.
No
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector (CN851, CN852) in the electronic control P. C. board.
2. 3 minutes after turning on the power suppy, start EMERGENCY OPERATION in HEAT mode.
Is there voltage 12V DC between the connector CN852 pin 1 (+) and CN851 pin 5 (-)?
Replace the noise filter P. C. board.
Yes
No
Replace the electronic control P. C. board.
Is there voltage of 208V AC - 230V AC between pin1 and pin 2 at connector CN913? W1
Yes
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector (CN851, CN852) in the electronic control P. C. board.
2. 3 minutes after turning on the power suppy, start EMERGENCY OPERATION in COOL mode.
Is there voltage 12V DC between the connector CN852 pin 1 (+) and CN851 pin 5 (-)?
Yes
Replace the electronic control P. C. board.
No
No
Replace the noise filter P. C. board.
Replace the 4-way valve.
W1If the connector CN913 is not connected or R. V. coil is open,
occurs between terminals even when the control is OFF.
90
Page 91
•When cooling, heat exchanger of non-operating unit frosts.
•When heating, non-operating indoor unit get warm. (LED display:
LL
Check of LEV
Start
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
(MXZ30TN MXZ30TN2)
0000, pp11
)
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
Yes
Normal
No
Disconnect the connector (CN791: unit A, CN792: unit B, CN793: unit C), and measure the resistance of LEV coil to check the integrity.
No
Replace the LEV coil.
•When cooling, room does not get cool.
•When heating, room does not get warm. (LED display:
MM
Check of inverter/compressor
Start
Disconnect the lead wire to the compressor at terminals.
power suppy, start EMERGENCY OPERATION.
Measure the voltage between each leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Output voltage COOL: 100V(58Hz) HEAT: 100V(58Hz) Is voltage output? W1
Yes
Is output balanced?
Yes
Turn off power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is there resistance of 0.53" to 0.66" between the each terminals?
Yes
Return the lead wire of compressor to former, and turn on power supply to indoor and outdoor unit. Three minutes later, start EMERGENCY OPERATION.
No
(MXZ30TN MXZ30TN2)
3 minutes after turning on the
W1 • After the outdoor fan starts running, wait for 1 minutes or more before
measuring the voltage.
•The output voltage values in the above table have the tolerance of i20%.
No
LED indicator the inverter stops due to over current?
Replace the electronic control P. C. board with the I.P.M P. C. board.
No
Replace the compressor.
0000, aa88
Yes
Yes
Replace the electronic control P. C. board
)
1.Turn off power supply of the indoor
No
and outdoor unit, and disconnect the connector CN 551 in the relay P. C. board
2.Turn on power supply to the outdoor unit, and after 1 minutes or more passed, check the resistance between the connector CN551 pin 1 and pin 2.
0"
Check the resistance between each terminal
Infinity
After 1 minutes has passed since the power supply of outdoor unit was turned off, disconnect the connector CN 553 in the relay P. C. board.
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor layer short 10 to 60 seconds: compressor lock 60 seconds to 5minutes: refrigerant circuit defective 5 minutes or more: normal
Replace the relay P. C. board.
91
0"
Check the resistance HPS (63H2).
Replace the HPS (63H2).
Infinity
Page 92
•When thermistor is abnormal. (When the LED displayis a table below)
NN
Check of thermistor
Start
(MXZ30TN MXZ30TN2)
Disconnect the connector in the electronic control P. C. board (see below table), and measure the resistance of thermistor to check whether the thermistor is normal or not.
Normal
Reconnect the connector (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor.
3 minutes after turning on the power suppy, start EMERGENCY OPERATION.
Does thermistor operate 10 minutes or more though the thermistor abnormality is not displayed?
Yes
Normal
Thermistor Discharge temperature thermistor Defrost thermistor Evaporation temperature thermistor Fin temperature thermistor Gas pipe temperature thermistor (Unit A) Gas pipe temperature thermistor (Unit B) Gas pipe temperature thermistor (Unit C)
Symbol
RT61 RT62 RT63 RT65 RT66 RT67 RT68
No
Replace the electronic control P. C. board.
Connector, Pin No. Between CN661 pin3 and pin4 Between CN661 pin1 and pin2 Between CN661 pin5 and pin6 Between CN663 pin1 and pin2 Between CN662 pin1 and pin2 Between CN662 pin3 and pin4 Between CN662 pin5 and pin6
Abnormal
Replace the thermistor
•Fan motor does not operate or stops operating shortly after starting the operation.
OO
Check of fan motor
Start
(MXZ30TN MXZ30TN2)
Check the connection of connector (CN851, CN852) in the fan motor relay connector and electronic control P. C. board at the noise filter P. C. board and connector (CN901, CN902) in the noise filter board.
Disconnect the fan motor connector, and measure the resistance of the fan motor winding to check the winding characteristic.
Normal
1. Disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later, start EMERGENCY OPERATION .
2. Check the voltage between pin 2 and pin 3, pin 2 and pin 5, pin 2 and pin 6 at the fan motor connector.
Is there voltage of 208V AC - 230V AC?
No
1. Turn off power supply of the indoor and outdoor unit, and disconnect the connector (CN851, CN852).
2. Is the voltage 0V, when the voltage between CN852 pin1 (+) and CN851 pin1 (-), pin2 (-), or pin3 (-) are measured after the power supply is turned on the outdoor unit?
Yes
Is there voltage of 12V DC between CN852 pin1 (+) and CN851 pin3 (-), when power supply turns on the indoor unit and EMERGENCY OPERATION starts in three minutes.
Yes
Replace the noise filter P. C. board
Yes
92
Abnormal
No
No
Replace the fan motor
Replace the electronic control P. C. board
Page 93
Infinity
0"
Yes
No
Yes
Start
1. Disconnect the connector CN722 in the electronic control P. C. board.
2. Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turnd off.
Check the resistance between each terminal?
Return CN722 to former. Turn on power supply to the indoor and outdoor unit. 3 minutes lator, EMERGENCY OPERATION starts.
Is HPS protection displayed immediately after compressor starts.
Replace HPS (63H1).
Replace the electronic control P. C. board.
Normal
•When the operation frequency does not go up from lowest frequency.
PP
Check of HPS
(MXZ30TN MXZ30TN2)
QQ
The other cases
(MXZ30TN MXZ30TN2)
In the case that the indoor fan and outdoor fan operate but the compressor does not operate, it causes that the high pressure switch can be operated once. First of all, check the high pressure switch can be shorted, turn OFF the power and turn ON again 1 minute later. Indoor unit does not operate. (difference modes)
• When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in the figure below.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.
OPERATION INDICATOR
Lighting Flashing
93
Page 94
TEST POINT DIAGRAM AND VOLTAGE
32F50 68 86 104 122 140
MSH09TW MSH09TW -
U1
Indoor electronic control P.C. board
Varistor(NR11)
Fuse(F11) 250V AC 3A
Fan motor
Power supply input 1 15V AC
--
Timer short mode point (JPS, JPG) (Refer to page 73.)
12V DC
}
+
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Auto restart function Solder the Jumper wire or the Resistor 220to the JR07.(Refer to page 74.)
Emergency operation switch
+
5V DC
}
--
Room temperature thermistor(RT11) Indoor coil thermistor(RT12)
94
Page 95
TEST POINT DIAGRAM AND VOLTAGE
32F50 68 86 104122 140
MSH12TN MSH15TN MSH17TN MSH12TN - MSH15TN - MSH17TN ­Indoor electronic control P.C. board
Fan motor
Very
Med. Low High
Low
C11
}
8 7 5 6 4 3 2 1
Varistor(NR11)
Fuse(F11) 250V AC 3.0A
CN201
Power supply input 115V AC
}
JP17
+
12V DC
JP16
}
--
U1U1U1
JP11
+
5V DC
JP24
CN104
JHA
Emergency operation switch JPS JPG
Indoor coil thermistor(RT12) Room temperature thermistor(RT11)
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
}
--
Auto restart function Disconnect the AUTO RESTART ASSY
}
from CN104, and solder the Jumper wire to JHA.(Refer to page 74.)
Timer short mode point
}
(Refer to page 73.)
95
Page 96
MUH09TW MUH09TW -
Defrost thermistor (RT61)
Ambient temperature thermistor (RT63)
-4 14 32 50 68 86 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Resistance(k")
U1
MUH12TN MUH12TN - MUH12TN ­MUH15TN MUH15TN - MUH15TN ­MUH17TN MUH17TN -
U1
Outdoor deicer P.C. board
U2U1
U2U1
Outdoor fan motor
115V AC(MUH09) 208/230V AC(MUH12/15/17)
}
R.V. coil
115V AC(MUH09) 208/230V AC(MUH12/15/17)
}
R601 5~10V DC
}
+ CN730
Power supply input
115V AC(MUH09) 208/230V AC(MUH12)
}
Power supply
input 208/230V AC
(MUH15/17)
}
Defrost thermistor (RT61)
}
Ambient temperature thermistor(RT63) is only
for MUH09TW -
MUH12/15/17TN -
Ambient temperature thermistor(RT63)
}
Fuse 2A/250V
Defrost interval time short pin (JP607,R853) (Refer to page 72.)
+
J9
}
J8
U1
and
U1
5V DC
.
}
12V DC
+
+
}
52C
12V DC
96
Jumper wire for change in
defrost setting (JPC, JPE)
(Refer to page 72, 73.)
Page 97
TEST POINT DIAGRAM AND VOLTAGE
OFF
0V 0V 0V
Outdoor fan Outdoor fan Outdoor fan
Low 12V 12V
0V
High
12V
0V
12V
Very high
12V
0V 0V
MXZ30TN MXZ30TN2 Electronic control P.C. board
700 600 500 400 300
Resistance (KΩ)
200 100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Discharge temperature thermistor
0.3~0.6V DC
Evaporation temperature thermistor
2.5~4.0V DC
Discharge temperature thermistor
Temperature(°F)
Defrost temperature thermistor
2.5~4.0V DC
Gas pipe temperature thermistor Evaporation temperature thermistor Defrost temperature thermistor
100
90 80 70 60 50 40 30
Resistance (kΩ)
20 10
0
-4 14 32 50 68 86 104
Temperature(°F)
Fin temperature thermistor
1.0~4.0V DC
200 180 160 140 120 100
80 60
Resistance (KΩ)
40 20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
0~5V DC
12V DC
5V DC
R.V. coil 12V DC
-
{
Serial signal Room C 5~10V DC
{
Serial signal Room B
5~10V DC
{
Serial signal Room A 5~10V DC
{
Relay 12V DC
{
+
-
-
-
-
-
-
-
{
LED monitor indication
Room C
Room B
Room A
Gas pipe temperature thermistor 2.5~4.0V DC
97
{
High pressure switch
Liner expansion valve(LEV) 12V DC pulse wave
Page 98
MXZ30TN Noise filter P.C. board
OUTDOOR FAN 208V-230V AC
{
{
208V-230V AC OUTPUT
{
208V-230V AC INPUT
REVERSING VALVE
208-230V AC
MXZ30TN2 Noise filter P.C. board
OUTDOOR FAN 208-230V AC
REVERSING VALVE
208-230V AC
{
{
{
208-230V AC OUTPUT
Replace them at the same time
{
208-230V AC INPUT
{
98
Page 99
I.P.M P.C. board
Relay P.C. board
12V DC
{
12V DC
{
12V DC
{
{
290V-330V DC
High pressure switch
12V DC
{
{
{
Short
99
Page 100
RELAY OPERATION MSH09TW MSH12TN MSH15TN MSH17TN
MSH09TW ­MSH12TN ­MSH15TN ­MSH17TN -
1. COMPRESSOR CONTACTOR
• EACH MODE
U1
U1
U1
U1
MODE
COOL & COOL mode of I FEEL CONTROL
DRY & DRY mode of I FEEL CONTROL
HEAT & HEAT mode
THERMOSTAT
ON
OFF
ON
OFF
ON ON
52C CONTACTOR
ON
OFF
OFF for 2 min. after unit starts operation.
Repeat of 8 min. ON/3min. OFF operation or 2 min. ON/3 min. OFF operation
Repeat of 4 min. OFF/ 1 min. ON operation
AUTO or set speed
AUTO or set speed
AUTO or set speed links with 52C contactor.
AUTO or set speed
of I FEEL CONTROL
NOTE : Once the compressor is OFF, “3-minute time delay circuit” works at next start-up.
• COIL FROST PREVENTION
MODE
OFF
THERMOSTAT
52C CONTACTOR
OFF
OFF or Very Low speed
COOL & COOL mode of I FEEL CONTROL
DRY & DRY mode of I FEEL CONTROL
ON
OFF for 5 min. After that, OFF is pro­longed until indoor coil thermistor reads termination temper­ature.
AUTO or set speed
AUTO or set speed <MSH12/15/17>
Low speed when coil frost prevention starts while COMPRESSOR OFF
INDOOR FAN SPEED
INDOOR FAN SPEED
2. SOLID STATE RELAY (INDOOR FAN MOTOR RELAY)
MSH12TN MSH15TN MSH17TN MSH12TN - MSH15TN - MSH17TN -
Indoor fan speed
High
Med.
Low
Very Low
OFF
Relay turning ON
SR144 SR143 SR142 SR141
All fan relays are OFF.
U1U1U1
100
Loading...