Mitsubishi MSZ-FH35VE, MSZ-FH35VE - E1, MSZ-FH25VE - ER1, MSZ-FH35VE - ER1, MSZ-FH50VE - ER1 Service Manual

...
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVE ································ 6
5. OUTLINES AND DIMENSIONS ························ 7
6. WIRING DIAGRAM ············································ 8
8. SERVICE FUNCTIONS ··································· 10
9. MICROPROCESSOR CONTROL ···················12
10. TROUBLESHOOTING ····································· 20
11. DISASSEMBLY INSTRUCTIONS ···················· 36
SPLIT-TYPE AIR CONDITIONERS
SERVICE MANUAL
INDOOR UNIT
PARTS CATALOG (OBB623)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Outdoor unit service manual MUZ-FH·VEHZ Series (OBH625) MUZ-FH·VE Series MXZ-D·VA Series
No. OBH623
REVISED EDITION-A
Models
MSZ-FH25VE
-
E1
MSZ-FH35VE
-
E1
MSZ-FH50VE
-
E1
Please void OBH623.
Revision A:
MSZ-FH50VE- E1 has been added.
Outdoor unit service manual MUZ-FH·VEHZ Series (OBH625) MUZ-FH·VE Series (OBH624) MXZ-D·VA Series (OBH626)
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
MSZ-FH50VE-
E1
has been added.
OBH623A
3
TECHNICAL CHANGES
1
MSZ-FH25VE -
E1
MSZ-FH35VE -
E1
MSZ-FH50VE -
E1
1. New model
These models are compatible with the outdoor units with low standby power control.
Connecting these models to the MUZ-FH·VE(HZ)-series outdoor units enables the low standby power control. Refer to the technical guide (OBT17) about the low standby power control.
These models may be connected to the MUZ-FH·VE(HZ) series after once connected to the MXZ series and operated, for example because of relocation. In that case, the MUZ-FH·VE(HZ) series outdoor units will not operate without taking a step. Follow the procedure "Deleting the memorized abnormal condition" described in 10-2.1.
OBH623A
4
ACCESSORIES
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
PART NAMES AND FUNCTIONS
2
Model
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
Installation plate 1 Installation plate fi xing screw 4 × 25 mm 5 Remote controller holder 1 Fixing screw for
3.5 × 16 mm (Black) 2 Battery (AAA) for remote controller 2 Wireless remote controller 1 Felt tape (For left or left-rear piping) 1 Air cleaning fi lter
(Electrostatic anti-allergy enzyme fi lter)
1
Air cleaning fi lter (Deodorizing fi lter) 1 Air purifying device 1
Operation indicator lamp
Remote control receiving section
Emergency operation switch
Horizontal vane
Air inlet
Air lter
Air cleaning filter (Electrostatic anti-allergy enzyme lter and deodorizing lter)
Front panel
Air outlet
Air purifying device
i-see SENSOR
(AIR PURIFYING) (POWER)
Remote controller
OBH623A
5
Indoor model MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
Power supply Single phase 230 V, 50 Hz
Electrical
data
Power input 1
Cooling
W
29 31
Heating 29 31
Running current
1
Cooling
A
0.28 0.29
Heating 0.28 0.29
Fan
motor
Model RC0J30-MD Current 1
Cooling
A
0.28 0.29
Heating 0.28 0.29 Dimensions W × H × D mm 925 × 305(+17) × 234 Weight kg 13.5
Special remarks
Air direction 5
Airfl ow
Cooling
Super High
m
3
/h
696 744 High 516 606 Med. 378 516 Low 282 444 Silent 234 384
Heating
Super High
m
3
/h
792 876 High 552 672 Med. 384 540 Low 282 432 Silent 240 342
Sound level
Cooling
Super High
dB(A)
42 44 High 36 39 Med. 29 35 Low 23 24 31 Silent 20 21 27
Heating
Super High
dB(A)
44 46 High 36 39 Med. 29 34 Low 24 29 Silent 20 21 25
Fan speed
Cooling
Super High
rpm
1,220 1,280 High 970 1,090 Med. 770 970 Low 630 870 Silent 550 780
Heating
Super High
rpm
1,350 1,460 High 1,020 1,180 Med. 780 1,000 Low 630 850 Silent 560 720
Fan speed regulator 5
Remote controller model SG13A
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C 1 Measured under rated operating frequency.
SPECIFICATION
3
Specifications and rating conditions of main electric parts
Fuse (F11)
T3.15AL250V Horizontal vane motor (MV1) 12 VDC Vertical vane motor (MV2) 12 VDC i-see SENSOR MOTOR (MT) 12 VDC Varistor (NR11) S10K300E2K1 Terminal block (TB)
3P
OBH623A
6
MSZ-FH25VE MSZ-FH35VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
42 44
NC-10
NOISE CRITERIA CURVE
4
Test conditions
Cooling: Dry-bulb temperature 27 °C
Wet-bulb temperature 19 °C
Heating: Dry-bulb temperature 20 °C
INDOOR UNIT
WALL
MICROPHONE
0.8m
1m
MSZ-FH50VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
44 46
NC-10
OBH623A
7
Unit: mm
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
MSZ-FH25VE MSZ-FH35VE
Piping
Insulation ø37 O.D Liquid line ø6.35 - 0.39 m (Flared connection ø6.35) Gas line ø9.52 - 0.34 m (Flared connection ø9.52)
Drain hose Insulation ø28 O.D Connected part ø16 O.D
OUTLINES AND DIMENSIONS
5
MSZ-FH50VE
Piping
Insulation ø37 O.D Liquid line ø6.35 - 0.39 m (Flared connection ø6.35) Gas line ø9.52 - 0.34 m (Flared connection ø12.7)
Drain hose Insulation ø28 O.D Connected part ø16 O.D
OBH623A
8
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
WIRING DIAGRAM
6
OBH623A
9
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Flared connection
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
Indoor coil thermistor RT12 (main)
Indoor coil thermistor RT13 (sub)
Refrigerant flow in cooling Refrigerant flow in heating
Unit: mm
REFRIGERANT SYSTEM DIAGRAM
7
MSZ-FH25VE MSZ-FH35VE
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Flared connection
Refrigerant pipe ø12.7 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
Indoor coil thermistor RT12 (main)
Indoor coil thermistor RT13 (sub)
Refrigerant flow in cooling Refrigerant flow in heating
MSZ-FH50VE
OBH623A
10
8-1. TIMER SHORT MODE
For service, the following set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. (Refer to 10-7.) Set time: 3 minutes 3 seconds (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit-of JPG and JPS.)
8-2. HOW TO SET REMOTE CONTROLLER EXCLUSIVELY FOR A PARTICULAR INDOOR UNIT
A maximum of 4 indoor units with wireless remote controllers can be used in a room. To operate the indoor units individually with each remote controller, assign a number to each remote controller according to the number of the indoor unit.
This setting can be set only when all the following conditions are met:
• The remote controller is powered OFF.
• Weekly timer is not set.
• Weekly timer is not being edited. (1) Hold down
button on the remote controller for 2 seconds to enter the pairing mode.
(2) Press
button again and assign a number to each remote controller.
Each press of
button advances the number in the following order: 1 2 3 4.
(3) Press
button to complete the pairing setting.
After you turn the breaker ON, the remote controller that first sends a signal to an indoor unit will be regarded as the remote controller for the indoor unit. Once they are set, the indoor unit will only receive the signal from the assigned remote controller afterwards.
SERVICE FUNCTIONS
8
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
8-3. SETTING THE INSTALLATION POSITION
Be sure to set the remote controller according to the installed position of the indoor unit.
Installation position:
Left: Distance to objects (wall, cabinet, etc.) is less than 50 cm to the left Center: Distance to objects (wall, cabinet, etc.) is more than 50 cm to the left and right Right: Distance to objects (wall, cabinet, etc.) is less than 50 cm to the right
The installation position can be set only when all the following conditions are met:
• The remote controller is powered OFF.
• Weekly timer is not set.
• Weekly timer is not being edited.
(1) Hold down
button on the remote controller for 2 seconds to enter the position setting mode.
(2) Select the target installation position by pressing
button. (Each press of the button displays the
positions in order: center right left.) (3) Press
button to complete the position setting.
Installation position Left Center Right Remote controller
display
(Left)(Center)(Right)
OBH623A
11
8-4. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in the same mode just before the shutoff of the main power.
Operation
If the main power has been cut, the operation settings remain. After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to disable “AUTO RESTART FUNCTION”
Turn off the main power for the unit. Cut the jumper wire to JR77 on the indoor electronic control P.C. board. (Refer to 10-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is OFF.
To prevent breaker OFF due to the rush of starting current, systematize other home appliance not to turn ON at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
JR77
CN110CN151
BZ
Indoor electronic control P.C. board
OBH623A
12
WIRELESS REMOTE CONTROLLER
MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE
MICROPROCESSOR CONTROL
9
NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receive the signal of the
remote controller with beeps.
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
Indication of remote controller model is on back
Distance of signal : About 6 m
Beep(s) is (are) heard from the indoor unit when the signal is received.
FAN SPEED CONTROL button
PURIFIER button INDIRECT/DIRECT button
OPERATION SELECT button
ECONO COOL button POWERFUL button
CLOCK button
Lid Slide the lid down to open the remote controller. Slide it down further to get to the weekly timer buttons.
WEEKLY TIMER set buttons
TIME, TIMER set buttons FORWARD button BACKWARD button
RESET button
i-save button
NATURAL FLOW button
SENSOR (i-see) button
VANE CONTROL button
WIDE VANE button
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
•The following indication applies regardless of shape of the indication. Indication Operation state Room temperature
Standby mode (Only during multi system operation)
-
Lighted Blinking
Not lighted
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons TEMP
or button to select the desired temperature. The setting range is 16 - 31°C.
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
3. Indoor fan speed control
When the thermostat turns OFF, the indoor fan operates very Low to reduce power consumption. When the room temperature rises and the thermostat is ON, the indoor fan operates according to the settings on the
remote controller.
OBH623A
Loading...
+ 28 hidden pages