RoHS compliant products have <G> mark on the spec name plate.
Use the specifi ed refrigerant only
OBH683D
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• 3. SPECIFICATION has been modified.
(The value of the disconnect switch for MSZ-FH15NA has been modified.)
• 8. MICROPROCESSOR CONTROL has been modified.
• 9. TROUBLESHOOTING has been modified.
Revision B:
• 4. OUTLINE AND DIMENSIONS has been modified.
(The length of the connect pipes has been modified.)
Maximum temperature9073115—
Minimum temperature675714—
Maximum humidity78%—
Standard temperature70604743
Maximum temperature80677565
Minimum temperature7060-13-14
DBWBDBWB
IndoorOutdoor
3-2. OUTLET AIR SPEED AND COVERAGE
ModelModeFunction
MSZ-FH06NA
MSZ-FH09NA
MSZ-FH12NA
MSZ-FH15NA
MSZ-FH18NA
MSZ-FH18NA2
HEATDry43719.529.8
COOL
HEATDry43719.529.8
COOL
HEATDry45420.331.0
COOL
HEATDry49722.233.8
COOL
HEATDry51423.034.9
COOL
HEATDry51423.034.9
COOL
Airfl ow
(CFM)
Dry38117.026.1
Wet32814.622.5
Dry38117.026.1
Wet32814.622.5
Dry39817.827.3
Wet34215.323.5
Dry41118.328.0
Wet35415.724.1
Dry43719.529.8
Wet37616.725.6
Dry45920.531.2
Wet39517.627.0
Air speed
(ft./s)
Coverage
5
(ft.)
● The air coverage is the figure up to the
position where the air speed is 1 ft./s,
when air is blown out horizontally from
the unit properly at the High speed
position.
The coverage should be used only
as a general guideline since it varies
according to the size of the room and
furniture arranged inside the room.
For service, the following set time can be shortened by bridging JPG and JPS on the electronic control P.C. board.
(Refer to 9-7.)
Set time: 3 minutes → 3 seconds (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by bridging JPG and JPS.)
7-2. HOW TO SET REMOTE CONTROLLER EXCLUSIVELY FOR A PARTICULAR INDOOR UNIT
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
To operate the indoor units individually with each remote controller, assign a number to each remote controller according
to the number of the indoor unit.
This setting can be set only when all the following conditions are met:
• The remote controller is powered OFF.
• Weekly timer is not set.
• Weekly timer is not being edited.
(1) Hold down
(2) Press
Each press of
(3) Press
After you turn the breaker ON, the remote controller that first sends a signal to an indoor unit will be regarded as the
remote controller for the indoor unit.
Once they are set, the indoor unit will only receive the signal from the assigned remote controller afterwards.
button on the remote controller for 2 seconds to enter the pairing mode.
button again and assign a number to each remote controller.
button advances the number in the following order: 1 → 2 → 3 → 4.
button to complete the pairing setting.
7-3. SETTING THE INSTALLATION POSITION
Be sure to set the remote controller according to the installed position of the indoor unit.
Installation position:
Left: Distance to objects (wall, cabinet, etc.) is less than 50 cm to the left
Center: Distance to objects (wall, cabinet, etc.) is more than 50 cm to the left and right
Right: Distance to objects (wall, cabinet, etc.) is less than 50 cm to the right
The installation position can be set only when all the following conditions are met:
• The remote controller is powered OFF.
• Weekly timer is not set.
• Weekly timer is not being edited.
(1) Hold down
(2) Select the target installation position by pressing
positions in order: center → right → left.)
(3) Press
button on the remote controller for 2 seconds to enter the position setting mode.
button. (Each press of the button displays the
button to complete the position setting.
(Left)(Center)(Right)
Installation positionLeftCenterRight
Remote controller
display
9
7-4. AUTO RESTART FUNCTION
OBH683D
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in
the same mode just before the shutoff of the main power.
Operation
If the main power has been cut, the operation settings remain.
After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to disable “AUTO RESTART FUNCTION”
Turn off the main power for the unit.
Cut the jumper wire to JR77 on the indoor electronic control P.C. board. (Refer to 9-7.)
Indoor electronic control
P.C. board
CN110CN151
BZ
JR77
NOTE:
• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
• If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
• If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is OFF.
• To prevent breaker OFF due to the rush of starting current, systematize other home appliance not to turn ON at the same
time.
• When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
Beep(s) is (are) heard from
the indoor unit when the
signal is received.
FAN SPEED CONTROL button
WIDE VANE button
VANE CONTROL button
INDIRECT/DIRECT button
TIME, TIMER set buttons
FORWARD button
BACKWARD button
WEEKLY TIMER
set buttons
RESET button
CLOCK button
Lid
Slide the lid down
to open the remote
controller. Slide it down
further to get to the
weekly timer buttons.
Operation display section
TEMPERATURE buttons
OPERATION SELECT button
ECONO COOL button
POWERFUL button
SMART SET button
NATURAL FLOW button
STOP/OPERATE
(OFF/ON) button
SENSOR (i-see) button
Indication of
remote controller
model is on back
NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the
remote controller with beeps.
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
•The following indication applies regardless of shape of the indication.
IndicationOperation stateRoom temperature
The unit is operating to
reach the set temperature.
The room temperature is
approaching the set temperature.
Standby mode (only during
multisystem operation)
About 4°F (2°C) or more
away from set temperature
About 2 to 4°F (1 to 2°C)
from set temperature
—
Lighted
Blinking
Not lighted
11
8-1. COOL ( ) OPERATION
OBH683D
(1) Press STOP/OPERATE (OFF/ON) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons TEMP
The setting range is 61 - 88°F (16 - 31°C).
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
or button to select the desired temperature.
8-2. DRY ( ) OPERATION
(1) Press STOP/OPERATE (OFF/ON) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention works the same way as that in COOL mode. (8-1.1.)
2. Low outside temperature operation
Low outside temperature operation works the same way as that in COOL mode. (8-1.2.)
8-3. FAN ( ) OPERATION
(1) OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
8-4. HEAT ( ) OPERATION
(1) Press STOP/OPERATE (OFF/ON) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons TEMP
The setting range is 61 - 88°F (16 - 31°C).
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room temperature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the condensing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor
heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
or button to select the desired temperature.
8-5. AUTO CHANGE OVER ··· AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from OFF:
• If the room temperature is higher than the set temperature, operation starts in COOL mode.
• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.
(2) Mode change
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 2°F (1°C) below
the set temperature.
HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 2°F (1°C) above
the set temperature.
12
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.