Mitsubishi MSZ-A09YV-E1, MSZ-A12YV-E1 Service Manual

Page 1
SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
E1
E1
(WH)
(WH)
MSZ-A09YV ­MSZ-A12YV -
No. OB327
Indication of model name
MSZ-A09YV ­MSZ-A12YV -
NOTE:
This service manual describes technical data of the indoor units.
•Refer to the service manual OB328 when MSZ-A09YV- or MSZ-A12YV- is connected with MUZ-A09YV- , MUZ-A12YV- , MUZ-A09YVH- or MUZ-A12YVH- .
•Refer to the service manual OB319 when MSZ-A09YV- or MSZ-A12YV- is connected with MXZ-A18WV- , MXZ-A26WV- or MXZ-A32WV- as multi system units.
E1
E1
CONTENTS
1. PART NAMES AND FUNCTIONS······················2
2. SPECIFICATION·················································4
3. NOISE CRITERIA CURVES·······························5
4. OUTLINES AND DIMENSIONS·························6
5. WIRING DIAGRAM ············································7
6. REFRIGERANT SYSTEM DIAGRAM················7
7. SERVICE FUNCTIONS ······································8
8. TROUBLESHOOTING······································10
9. DISASSEMBLY INSTRUCTIONS ····················19
E1E1
E1E1E1E1
E1E1
E1E1E1
Page 2
1
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
MSZ-A09YV -
E1
MSZ-A12YV -
E1
1 5 1 2 2 1 1
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSZ-A09YV ­MSZ-A12YV -
Air cleaning filter (white bellows type)
Heat exchanger
Catechin air filter (With deodorizer)
Air outlet
Vertical vanes Line flow fan
Horizontal vane
Operation section
(When the front panel is opened)
E1
E1
Panel
Front panel Air inlet
to Breaker
Power supply cord
Remote control receiving section
Remote controller
Display section
ACCESSORIES
INDOOR UNIT
Emergency operation switch
Operation indicator lamp
Remote control receiving section
2
Page 3
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
AMPM
CLOCK
˚C
AM
RESET CLOCK
I FEEL
COOL
DRY
AUTO
HEAT
Open the front lid.
Signal transmitting section
Operation display section
OPERATE /STOP (ON /OFF) button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE CONTROL button
CLOCK SET button
Indication of remote controller model
MSZ-A09YV ­MSZ-A12YV -
E1
E1
3
Page 4
1.5+ 440V 250V 3.15A
93:5A 250V
MSBPC20 12V 250"
ERZV10D471
S201DH1Y
5P
JM1aN-ZTMP-DC12V
136:i3: 2A
INDOOR UNIT
Item
Model
Indoor fan capacitor Fuse Thermal fuse Vane motor Varistor Solid state relay Terminal block Contactor Indoor fan motor thermal fuse
MSZ-A09YV -
E1
MSZ-A12YV -
E1
(C11)
(F11)
(F12)
(MV)
(NR11)
(SR141)
(TB)
(52C)
2
MSZ-A09YV -
E1
MSZ-A12YV -
E1
Indoor model
Function
Power supply
Single phase
230V,50Hz
10
0.17 35 —
0.17
RC4V19-LA
WHT-BLK 413 BLK-RED 334 815O278O244
9 5
3 10 10 10
KG04A
Cooling
504/360
W
/222
W
88
37/29W/21
W
1,010/770W/540
W
Heating
564/402
W
/246
W
94
38/30W/21
W
1,110/840W/580
W
Single phase
230V,50Hz
10
0.19 40 —
0.19
RC4V19-KA
WHT-BLK 316 BLK-RED 299 815O278O244
10
5
3 10 10 10
KG04A
Cooling
630/462
W
/288
W
95
39/31W/22
W
1,030/800W/570
W
Heating
642/474W/312
W
94
38/30
W
/22
W
1,050/820W/600
W
Air flow
(High/Med.W/LowW) Power outlet Running current 1 Power input Rated frequency Auxiliary heater Power factor 1 Fan motor current 1 Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level
(High/Med.W/LowW) Fan speed(High/Med.W/LowW) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Thermistor RT13(at25:) Remote controller model
K /h
A A
W
A(kW)
%
A
"
mm
kg
dB(A)
rpm
k" k" k"
Electrical
data
Fan
motor
Special
remarks
Capacity
SPECIFICATION
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor DB27: WB19:
Outdoor DB35: WB 24:
Heating : Indoor DB 20: WB15:
Outdoor DB 7: WB 6:
Refrigerant piping length (one way): 5m w Reference value
1 Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
4
Page 5
3
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
37 38
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-A09YV -
E1
MSZ-A12YV -
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
E1
FAN SPEED
High
FUNCTION
COOLING HEATING
SPL(dB(A))
39 38
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
INDOORUNIT
WALL
1m
0.8m
MICROPHONE
NC-20
5
Page 6
4
OUTLINES AND DIMENSIONS
MSZ-A09YV -
INDOOR UNIT
278
60
58
162
Wireless remote controller
E1
81.5
606
783
815
149
19
Power supply cord Lead to right 1.0m Lead to left 0.3m
Installation plate
Indoor unit
81.5
41
30
Air out
242 5
Air in
7 or more
244
326326
Installation plate
Liquid line Gas line
{
Insulation
90
110
Drain hose (Connected part O,D)
Insulation
Unit : mm
133.5
231.5
42
2.5
81.5
Wall hole
[6.35-0.5m
[9.52-0.43m
[37 O.D
[21 I.D
[16
[28
4.5
271
[65
MSZ-A12YV -
INDOOR UNIT
278
60
58
162
Wireless remote controller
E1
783
815
606
19
Installation plate
Indoor unit
41
149
Power supply cord Lead to right 1.0m Lead to left 0.3m
30
Air out
242 Air in
7 or more
244
326326
5
Installation plate
Liquid line Gas line
{
Insulation
90
110
Drain hose (Connected part O,D)
Insulation
Unit : mm
161.5161.5
218.5
42
2.5
81.581.5 Wall hole [65
[6.35-0.5m
[9.52-0.43m
[37 O.D
[21 I.D
[16
[28
17.5
258
6
Page 7
5
SYMBOL
C11
F11 F12
MF
MV
SYMBOL
NR11
RT11 RT12 RT13
SR141
SYMBOL
SR142
T11
TB
52C
NAME INDOOR FAN CAPACITOR FUSE (3.15A) THERMAL FUSE (93:) INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR
NAME VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) SOLID STATE RELAY
NAME SOLID STATE RELAY TRANSFORMER TERMINAL BLOCK CONTACTOR
GRN/YLW
BLK GRY YLW BRN WHT RED
MF
1 2 3 4 5 6
3
SR141 SR142
5
3
1
C11
RT13 RT12
CN
112
CN 111
CN 121
151
CN
109CN125
CN
1R1
CN
MV
52
32
5
RT11
CN211
NR11
ELECTRONIC CONTROL P.C. BOARD
F11
T11
230V~
BRN
TB
L
3
N
2
RED
WHT
BLU
F12
BLU
BLU
1 2
BLU
1
2
3
CN201
3
4
52C
12V
TO OUTDOOR UNIT CONNECTING
L 3 N 2
12V
TO OUTDOOR
FOR MXZ type
UNIT CONNECTING
REMOTE CONTROLLER
POWER MONITOR RECEIVER
SAFETY DEVICE (FAN)
P.C. BOARD
LD103
GRN
CIRCUIT BREAKER
POWER SUPPLY CORD ~/N 230V 50Hz
PE
WIRING DIAGRAM
MSZ-A09YV ­MSZ-A12YV -
INDOOR UNIT
E1
E1
MODELS WIRING DIAGRAM
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
6
MSZ-A09YV -
INDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
E1
Refrigerant pipe [9.52 (with heat insulator)
MSZ-A12YV -
INDOOR UNIT
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
Refrigerant flow in cooling Refrigerant flow in heating
thermistor RT12(main)
Indoor coil thermistor RT13(sub)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Indoor heat exchanger
Room temperature thermistor RT11
7
Indoor coil thermistor RT13(sub)
E1
Refrigerant pipe [9.52 (with heat insulator)
Indoor coil thermistor RT12(main)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Unit:mm
Page 8
7
SERVICE FUNCTIONS
MSZ-A09YV ­MSZ-A12YV -
E1
E1
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to page 18.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
Remote controller model : KG04A
J2
NOTE : For remodelling, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table
1. After modification, press the RESET button.
Table 1
1 unit operation No. 1 unit No. 2 unit No. 3 unit No. 4 unit
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.
8
Page 9
How to release “AUTO RESTART FUNCTION”
JR07
IC101
CN151
SW1
CN112
CN111
CN201
52C
C11
CN211
CN1V1
CN1R1
CN121
1Turn off the main power for the unit. 2Pull out the indoor electronic control P.C. board and the power monitor receiver P.C.board. (Refer to page 19.) 3Solder the Jumper wire to the JR07 on the indoor electronic control P.C.board. (Refer to page 18.)
Operation
1 If the main power (230V AC) has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 min-
utes for the compressor to start running.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
9
Page 10
8
RESET button
Housing point
TROUBLESHOOTING
MSZ-A09YV ­MSZ-A12YV -
E1
E1
8-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to the flow chart on page 12 and the check table on page 13.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
NOTE : 1. If the RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
2 Press the RESET button with tip end of ball point
pen or the like, and then use the remote controller.
10
Page 11
5. How to install the horizontal vanes
Lighted
Flashing
Operation Indicator
If horizontal vanes are not installed correctly, both of the operation indicator lamps will flash. In this case, install the horizontal vanes correctly by following the procedures 1 to 6.
NOTE: Before installation of the horizontal vanes, disconnect the power supply plug and/ or turn off the breaker.
Upper vane
Insert this end first.
Lower vane
Insert this end first.
Upper right
The holes on the insertion ends of the upper and lower horizontal vanes different shapes.
654
Lock.
Stopper
Lock.
Stopper
In.
321
Insert.
Lower right
Lock.
Lock.
In.
In procedures 2,3,5, and 6, lock the stoppers until they click into place.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units will start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
•When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few min­utes (max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
Insert.
11
Page 12
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage" on page 18.
Refer to "Check of inverter/ compressor".
Refer to B "Check of remote controller and receiver P.C. board" on page 15.
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to C "Check of indoor electronic control P.C. board" on page 15.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Left lamp Flash on and off at
0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring
Left lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Left lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Left lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
Left lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Left lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to D "How to check of mis-wiring (When outdoor unit doesn't work)" on page 16.
Both lamps (Left and right) Flash on and off at 0.5-second intervals Cause: Indoor unit
• The horizontal vanes are not installed correctly.
Refer to E "Check of installation of the horizontal vanes" on page 17.
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage" on page 18.
Refer to A "Check of indoor fan motor" on page 14.
Refer to "Check of inverter/ compressor".
Refer to "Check of outdoor thermistor".
Replace the inverter P.C. board and others.
Left lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
As for outdoor unit, refer to service manual OB328 or OB319.
8-2. Instruction of troubleshooting
12
Page 13
1. Troubleshooting check table
Operation Indicator
· Flashing of the OPERATION INDICATOR lamp (on the left or both) indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left) is lighting during normal operation.
flashing
• The following indication applies regardless of shape of the indicator.
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
Abnormal
No.
1
w2
w3
4
5
6
7
8
point
Attachment of the horizontal vane
Mis-Wiring
Indoor coil thermistor
Room tempera­ture thermistor
Indoor fan motor
Indoor control system
Outdoor power system
Outdoor thermistors
Outdoor control system
MXZ type
Operation mode setting
Both lamps flash at the same time.
0.5-second ON
0.5-second OFF Left lamp flashes.
0.5-second ON
0.5-second OFF
Left lamp flashes. 2-time flash
2.5-second OFF
Left lamp flashes. 3-time flash
2.5-second OFF
Left lamp flashes. 4-time flash
Left lamp flashes. 5-time flash
2.5-second OFF
Left lamp flashes. 6-time flash
2.5-second OFF
Left lamp flashes. 7-time flash
Operation Indicator
Flashing
Both lamp
Lighted
2.5-second OFF
2.5-second OFF
2.5-second OFF
SymptomOperation indicator lamp Detection method
Indoor unit and outdoor unit do not operate.
Outdoor unit does not operate.
Outdoor unit does not operate.
Indoor fan repeats 12 seconds ON and 3 minutes OFF. When the indoor fan breaks, the fan keeps stopping.
Outdoor unit does not operate.
Outdoor unit does not operate.
Outdoor unit does not operate.
Outdoor unit does not operate.
Outdoor unit operates but indoor unit does not operate.
When the electricity is not conducted to the safety device (FAN) of the horizontal vane.
3 minutes after power supply turns ON, when serial signal is not received.
Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation.
When rotational frequency feedback signal is not emit during 12-second indoor fan operation.
When it cannot properly read data in the nonvolatile memory of indoor electronic control P.C. board.
When compressor has stopped due to over current protection or start-up failure protection 3 times in a row within 5 seconds after start­up.
<Thermistor short> Thermistors are abnormal when they short after compressor start-up. <Thermistor open> Thermistors are abnormal when they open after compressor start-up. However, discharge temperature thermistor is abnormal when open circuit is detected more than 10 minutes after compressor start-up.
When it cannot properly read data in the nonvolatile memory of outdoor electronic control P.C. board.
When the operation mode of each indoor unit is differently set to COOL(includes DRY) and HEAT at same time, the operation mode of indoor unit that has operated at first has the priority.
Check point
• Refer to E "Check of installation of the horizontal vanes" on page 17.
• Refer to D "How to check mis-wiring " on page 16.
• Refer to the characteristics of
indoor coil thermistor, sub indoor coil thermistor, and room temperature thermistor on page 18.
• Refer to A "Check of
indoor fan motor" on page 14.
• Replace the indoor electronic
control P.C. board.
• Refer to "Check of inverter/ compressor".
Refer to service manual OB328 or OB319.
• Shortage of refrigerant
• Replace the outdoor control
P.C. board. Refer to "Check of outdoor
thermistor".
Refer to service manual OB328 or OB319.
• Replace the outdoor
electronic control P.C. board or inverter P.C. bpard. Refer to service manual OB328 or OB319.
• Unify the operation mode.
Refer to service manual OB319.
NOTE : w When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the 52C and the indoor fan motor with the OPERATION INDICATOR lamp lighting. When the 52C and the indoor fan motor are turned ON again 3 minutes later and the same abnormality is detected (a second detection of the above abnormality after the power ON), the indoor electronic control P.C. board turns OFF the 52C and the indoor fan motor with the OPERATION INDICATOR lamp flashing. However, the first detection is cleared in case the power is turned OFF after the first detection.
13
Page 14
2. Trouble criterion of main parts
Part name FigureCheck method and criterion
Indoor fan motor(MF) INNER FUSE
136i 3: CUT OFF
WHT – BLK
BLK – RED
Abnormal
Open or
short-circuit
Normal
MSZ-A09YV 303 " ~ 329 " 287 " ~ 311 "
MSZ-A12YV 396 " ~ 430 " 320 " ~ 348 "
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Normal
8 k" ~ 20 k"
Abnormal
Open or short-circuit
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Vane motor(MV)
Motor part
Sensor part
Measure the resistance between the terminals with a tester. (Part temperature 10˚C ~ 30˚C)
BRN – YLW YLW – GRY
Abnormal
Remain 0V or 5V
Normal
4.5 ~ 5.5V
Measure the voltage power ON.
(When fan revolved one time)
0V5V0V
(Approx.)
Normal
BRN-other one
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
Color of lead wire
Color of lead wire
BLK
RED
WHT
GRY
YLW
BRN
240 " ~ 260 "
Color of lead wire
MAIN AUX.
FUSE
RED
YLW BRN
ORN
GRN
ROTOR
Turn OFF the power supply and check the connector CN 211 visually.
No(others)
Disconnect connector from CN 211 on indoor electronic control P.C. board. Measure resistance between lead wire 1 and 5 and then 3 and 5.
Yes(0 or )
Is resistance 0"(short circuit) or (open circuit)?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
CN211
1 3 5
Fan
motor
Indoor electronic control P.C. board
MSZ-A09YV - MSZ-A12YV -
E1E1
When OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate.
A
Check of indoor fan motor
14
Page 15
Indoor electronic control P.C. board
Varistor (NR11)
Indoor electronic control P.C. board
Fuse (F11)
1 3
CN201
F12
N
2 3
Thermal fuse connector
Terminal
block
Check both “parts side” and “pattern side” of indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse (F11) blown?
Replace the fan motor.
Is winding resistance of fan motor 0 "?
Is winding resistance of vane motor 0 "?
No
Yes
No
Replace the vane motor.
Yes
No
Yes
Is varistor (NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply. Disconnect indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
No
Does the unit operate with the remote controller or does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?
Yes
No
Turn OFF the power supply.
Turn OFF the power supply.
Replace the indoor electronic control P.C. board.
Measure the resistance between CN201
1 on
the indoor electronic control P.C. board and
N
on the terminal block with the tester.
Is resistance approx. 0"?
Replace the fuse (F12).
No
Yes
()
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
CN302
CN125
CN109
12
12
31
543
Remote controller
Indoor electronic control P.C. board
Power monitor receiver P.C. board
Check of remote controller and receiver P.C. board
B
wCheck if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press the RESET button. (Refer to page 10.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries.(Refer to page 10.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Measure the voltage between receiver P.C. board connector CN302 No.3(-) and No.5(+) when the remote controller button is pressed.
Is the voltage approx. 4V DC?
No(5V or 0V DC)
No
Yes
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
Replace the indoor electronic control P.C. board.
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board
C
Replace the receiver P.C. board.
15
Page 16
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second or flashes once.
Is there voltage approx. 280V DC between LD61A (+) and LD66A (–) on the inverter P.C. board?
Is there approx. 230V AC between outdoor terminal block 2 and N when EMERGENCY OPERATION switch is pressed three minutes after turn OFF the power supply and then turn ON again?
Is mis-wiring indicated when 52C turns ON three minutes later?
w3 Replace the outdoor electronic control P.C.
board.
Does the OPERATION INDICATOR lamp flash quickly when OPERATE/STOP(ON/OFF) button on the remote controller is pressed?
w2 Mis-wiring may damage indoor electronic
control P.C. board during the operation in the left. Be sure to confirm the wiring is correct before the operation starts.
w3 Replace the
indoor electronic control P.C. board.
w3 Be sure to release the failure-mode
recall function after checking.
No
w3 Rectify indoor/ outdoor connecting wire.
Yes
A
B
Turn OFF the power supply and confirm that indoor/ outdoor connecting wire is correct. Short-circuit indoor terminal block N and 3. During pressing the OPERATION SELECT button and TOO COOL button on the remote controller, press the RESET button. (The above procedure allows OPERATION INDICATOR lamp to indicate the failure-mode.) w2
Open-circuit indoor terminal block N and 3, Check if there is amplitude of 5 to 20V DC between outdoor terminal block N and 3(for confirmation of serial signal) and if there is 230V AC between 2 and N.
1. Turn OFF the power supply.
2. Disconnect the connector between the compressor and the transistor module.
3.Turn ON the power supply.
4. Press the EMERGENCY OPERATION switch.
Yes
No
Yes
No
Yes
No
Yes
(light up or OFF)
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press the EMERGENCY OPERATION switch.
A
B
· Reinstall the unit away from light.
· Attach a filter on receiving part.
Procedure of release of failure-mode 1 Press the EMERGENCY
OPERATION switch.
2 Turn OFF the power supply and
then turn ON again.
3 Press the RESET button on the
remote controller.
Start
No
• Turn ON the power supply.
Press once EMERGENCY OPERATION switch.
Is this mis-wiring, poor contact, or wire disconnection?
Make them sure.
Yes
After three minutes, mis-wiring is indicated (0.5-second ON, 0.5-second OFF) on OPERATION INDICATOR lamp on indoor unit.w
w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self -check to be displayed in 3 seconds.
•The following indication applies regardless of shape of the indicator.
Flashing
Operation Indicator
As for outdoor unit, refer to service manual OB328 or OB319.
Outdoor unit doesn’t operate.
D
How to check mis-wiring
16
Page 17
When both OPERATION INDICATOR lamps flash 1-time. Indoor unit and outdoor unit don’t operate.
Check of installation of the horizontal vanes
E
Start
Turn OFF the power supply.
No
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
Relock the stopper of the horizontal vane to the indoor unit. Refer to page 11.
Turn ON the power supply.
To check the continuity of safety device, measure the resistance of connector 1 - 3 connected to CN1R1 on the indoor electronic control P.C. board.
Is there resistance 0 "?
Yes
Replace the indoor electronic control P.C. board.
F
Check of thermal fuse
Turn OFF the power supply.
No
OK
No()
Is the OPERATION INDICATOR lamp flashing?
Yes
Turn OFF the power supply.
Replace the safety device.
Is resistance between the connector CN 201 1 on indoor electronic control P.C. board and the terminal block N?
No
Ok
Yes
Replace the thermal fuse (F12).
Indoor electronic control P.C. board
17
CN201
Page 18
TEST POINT DIAGRAM AND VOLTAGE MSZ-A09YV - MSZ-A12YV -
E1E1
Indoor electronic control P.C. board
Fuse F11 250V AC 3.15A
Power supply input 230V AC
}
R132
Indoor fan motor 230V AC
}
Safety device of fan by horizontal vane CN1R1
Varistor (NR11)
J12
12V
{
DC
J33
+
Power monitor receiver P.C. board
J33
+
}
5V DC
J23
Room temperature thermistor RT11
Indoor coil thermistor RT12(MAIN) RT13(SUB)
Timer short mode point JPG, JPS
}
(Refer to page 8.)
Emergency operation switch
Release of Auto restart function Solder the Jumper wire to the JR07. (Refer to page 9.)
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
CN302
Resistance (k")
Temperature (:)
18
Page 19
9
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
9-1. MSZ-A09YV - MSZ-A12YV -
E1E1
INDOOR UNIT
OPERATING PROCEDURE
1. Removing the panel
(1) Remove the screw caps of the panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board and the power monitor receiver P.C. board
NOTE : In case of removing only indoor electronic control
P.C. board work (3) is not necessary. (1) Remove the panel. (Refer to 1.) (2) Remove the power monitor receiver P.C. board holder from
the bottom of electrical box.
(3) Open the power monitor receiver P.C. board holder and
remove the power monitor receiver P.C. board.
(4) Remove the screw of the electrical cover and the electrical
cover. (5) Remove the screw of the V.A. clamp and the V.A. clamp. (6) Remove the screw of the cord clamp and the cord clamp. (7) Remove the screw of the terminal block. (8) Remove the screw of the ground wire. (9) Pull out indoor electronic control P.C. board slightly. (10)
Disconnect all (except CN109, CN125) the connectors on
the electronic control P.C. board. (11)
Remove the electronic control P.C. board.
(12)
Disconnect the connector of power monitor receiver P.C.
board (CN109, CN125) on the electronic control P.C.
board.
19
Photo 1
Photo 2
Screw of the ground wire
Power monitor receiver P.C. board holder
PHOTOS
Screws of the panel
Terminal block fixing screw
Indoor electronic control P.C. board
Cord clamp fixing screw
Screw of the V.A. clamp
Screw of the electrical cover
Page 20
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
(1) Remove the panel. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) (3) Remove the V.A. clamp. (Refer to 2.) (4) Remove the cord clamp. (Refer to 2.) (5) Remove the terminal block. (Refer to 2.) (6) Remove the screw of ground wire. (Refer to 2.) (7) Disconnect the connector of the indoor coil thermistor
(CN112), the fan motor connector (CN211 and CN121), the vane motor connector (CN151) and the connector of the safety device (CN1R1) on the electronic control P.C. board.
(8) Remove the fan motor lead wire and indoor coil thermistor
from the electrical box.
(9) Remove the lead wire of vane motor and safety device from
the bottom of electrical box.
(10)
Remove the screw fixing the electrical box, remove the
electrical box.
4. Removing the nozzle assembly and the vane motor
(1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(4) Remove the screws of the vane motor, disconnect the
vane motor connector.
(5) Remove the vane motor.
Photo 3
Photo 4
Indoor coil thermistor connector
Fan motor connector
Screws of the vane motor
Vane motor connector
Screw of the electrical box
5. Removing the indoor fan motor and the line flow fan
(1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly. (Refer to 4.) (4) Remove the screw of the lead cover and the lead cover. (5) Remove the lead wire of the fan motor. (6) Release the hooks of the motor band and open it slightly. (7) Loosen the hexagon socket set screw of the line flow fan. (8) Remove the screws fixing the motor bed, remove the fan
motor with motor band and the motor bed. (9) Remove the screws fixing the left side of the heat
exchanger. (10)
Lift the left side of the heat exchanger.
(11)
Remove the line flow fan.
Photo 6
Hexagon socket set screw
Drain hose
Photo 5
Screws of the left side of the heat exchanger
Photo 7
Screw of the lead cover
Hooks of the motor band
Screws of the motor bed
20
Page 21
PARTS LIST10
MSZ-A09YV - (WH) MSZ-A12YV - (WH)
E1
E1
10-1. INDOOR UNIT STRUCTURAL PARTS
1 (w)
2
3 4
5
6
10-2. ACCESSORY AND REMOTE
9 (w)
8 7 (See page 23.)
(w) These figures show about MSZ-A12YV.
CONTROLLER
10
11
10-1. INDOOR UNIT STRUCTURAL PARTS
Symbol
No.
E02 749 234
1
E02 751 234
2
E02 838 000
3
E02 749 067
4
E02 838 010
5
E02 408 142 E02 763 100
6
E02 764 100 7 8
E02 749 975
E02 408 970 9
E02 751 970
Part No.
Part name
BOX (WH) BOX (WH) PANEL ASSEMBLY (WH) SCREW CAP FRONT PANEL (WH) CATCH CATECHIN AIR FIL TER CATECHIN AIR FIL TER AIR CLEANING FILTER CORNER BOX (RIGHT) INSTALLATION PLATE INSTALLATION PLATE
in Wiring
Diagram
10-2. ACCESSORY AND REMOTE CONTROLLER
E02 838 426
10
E02 527 083
11
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
Q'ty/unit
MSZ-A09YV -
(WH)
1
1 2 1 2 2
2 1 1
1 1
E1
MSZ-A12YV -
(WH)
1 1 2 1 2
2 2 1
1
1 1
E1
Including No.3,4,5 2PCS/SET
2PCS/SET
MAC-1300FT
KG04A
Remarks
21
Page 22
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8
9 10 11
12 13
14 15 16
17 18 19
20 21 22
E02 001 504 E02 661 702 E02 838 235 E02 815 316 E02 838 040 E02 838 041 E02 127 382 E02 829 385 E02 749 385 E02 763 034 E02 815 468 E02 838 452 E02 839 452 E02 749 303 E02 151 308 E02 749 300 E02 751 300 E02 749 333 E02 679 375 E02 665 505 E02 151 505 E02 838 307 E02 749 302 E02 408 509 E02 751 509 E02 408 381
MSZ-A09YV-
E1
MSZ-A12YV-
E1
23
24 25
E02 749 620 E02 839 620 E02 815 666 E02 151 666 E02 151 667
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION (GAS) UNION (GAS) UNION (LIQUID)
{9.52 {9.52 {6.35
1
1 1
1 1
1
SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y (WH) SAFETY DEVICE VANE UPPER VANE LOWER FUSE VARISTOR VARISTOR VANE CRANK SET POWER MONITOR RECEIVER P.C. BOARD ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD VANE MOTOR ROOM TEMPERATURE THERMISTOR INDOOR FAN MOTOR INDOOR FAN MOTOR MOTOR BAND TERMINAL BLOCK FAN MOTOR RUBBER MOUNT FAN MOTOR RUBBER MOUNT INDOOR COIL THERMISTOR LINE FLOW FAN BEARING MOUNT BEARING MOUNT THERMAL FUSE
3.15A
AUTO RESTART AUTO RESTART
RC4V19­RC4V19-
2PCS/SET 2PCS/SET
93:
F11 NR11 NR12
MV
RT11
MF MF
TB
RT12, RT13
F12
1 1 1 1 1 1 1 1 1 1 1 1
1 1 1
1 1 2
1 1 1
1
1 1 1 1 1 1 1 1 1 1 1
1 1 1
1 1 1
2 1 1
1 1
(WH)
(WH)
MSZ-A09YV - (WH) MSZ-A12YV - (WH)
E1
E1
10-3. INDOOR UNIT ELECTRICAL PARTS
10-4. INDOOR UNIT HEAT EXCHANGER
AND FUNCTIONAL PARTS
SLEEVE BEARING
1
3
4 5 6
21
20
2
FUSE
VARISTOR
7
19
18
17
15
ROOM TEMPERATURE THERMISTOR
16
14
24
25
13
10
8
9
11
12
(W) This figure shows about MSZ-A12YV.
10-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Part number that is circled is not shown in the illustration.
10-4. INDOOR UNIT HEAT EXCHANGER
23 (W)
22
Page 23
10-5. AIR CLEANING FILTER
MAC-1300FT
Model Part No.
MSZ-A09YV - MSZ-A12YV -
E1 E1
Air cleaning filter (White bellows type)
MAC-093SS-E
Model Part No.
MSZ-A09YV - MSZ-A12YV -
E1 E1
Heat exchanger
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
OPTIONAL PARTS11
QUICK CLEAN KIT
You can sweep the surface of heat exchanger if you install the special-made brush to your vacuum cleaner.
23
Page 24
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Jan. 2004. No. OB327 6 Made in Japan
New publication, effective Jan. 2004 Specifications subject to change without notice.
Loading...