Mitsubishi Electric MSZ-A09RV-WH, MSZ-A12RV-WH, MUZ-A12RV-E1, MUZ-A09RV-E1, MSZ-A12RV-E1 Service Manual

Page 1
SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
No. OB230
CONTENTS
1. TECHINICAL CHANGES ··································2
3. SPECIFICATION·················································6
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM··············12
8. PERFORMANCE CURVES······························13
9. MICROPROCESSOR CONTROL ····················23
10. SERVICE FUNCTIONS·····································38
11. TROUBLESHOOTING······································40
12. DISASSEMBLY INSTRUCTIONS·····················57
13. PARTS LIST······················································61
14. OPTIONAL PARTS···········································65
MSZ-A09RV -
(WH)
MUZ-A09RV -
MSZ-A12RV -
(WH)
MUZ-A12RV -
E1E1
E1E1
1999
Page 2
1 TECHNICAL CHANGES
2
INFORMATION FOR THE AIR CONDITIONER WITH R-410A REFRIGERANT
• This room air conditioner adopts R-410A of HFC refrigerant which never destroys the ozone layer. Pay attention following points.
1 As R-410A working pressure is 1.6 times higher than that of R-22 of previous refrigerant, dedicated tools and piping are
required.
2 R-410A is more affected by water and contaminations than R-22. Keep R-410Aaway from water and contaminations during
storage and while installing.
3 Use clean dedicated piping materiales for R-410A only which are strong enough against R-410Apressure. Never use any
current pipes designed for R-22.
4 Composition change may occur in R-410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
Lubricant
Refrigerant
New refrigerant
R-410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R-22
R-22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
New Specification Current Specification
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
The incompatible lubricant easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the lubricant of the upper layer to the compressor.
Since refrigerant and lubricant are compatible each, lubricant backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Lubricant
Refrigerant
Compressor
Suction muffler
Oil back hole
Lubricant /Refrigerant
Compressor
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
Page 3
3
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa.G)
R-410A R-22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(;)
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
1.Tools dedicated for the air conditioner with R-410A refrigerant
The following tools are required for R-410A refrigerant. Some R-22 tools can be substituted for R-410Atools. The diameter of the service port on the outdoor unit operation valve has been changed to prevent improper refrigerant charging. Cap size has also been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a coppor-alloy seamless pipe with a thickness of 0.7 mm or less, as the pressure resistance is in sufficient.
2 Flaring work and flare nut
Flaring work for R-410A pipes differs from that for the existing refrigerant pipes. for details of flaring work, refer to Installation manual “6-1 FLARING WORK”.
R-410A tools
Can R-22 tools be used?
Gas leak detector
R-410A pressures beyonds the measurement range of R-22 gauges. Port diameters have been changed to prevent other kinds of refrigerant from being charged into the units.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant. 1/4 and 3/8 wrenches can be used for both R-22 and R-410A units.
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R-22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps. It is difficult to measure R-410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes Yes
Newly required
Newly required
Newly required
Gauge manifold
Charge hose
Torque wrench Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R-410A Yes : Substitutable for R-410A
Wall thickness
Outside diameter
Pipe
mm inch For liquid For gas
6.35
9.52
1/4 3/8
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
Page 4
4
2
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSZ-A09RV­MSZ-A12RV-
E1
E1
Emergency operation switch
Display section
Operation Indicator
Receiving section
Grille
Air cleaning filter(white bellows type)
Deodorizing filter (gray sponge type)
Air filter
Vertical vanes
Air inlet
to Breaker
Remote control receiving section
Horizontal vane
Remote controller
Operation section
(When the grille is open)
Power supply cord
Front panel
Electronic scale for refrigerant charging
Outdoor unit
Gas cylinder
Valve
Refrigerant gas cylinder for R-410A with siphon
Liquid
2 Optional extension pipe for R-410A
3.Refrigerant oil
Apply the special refrigeration oil (accessories) to the flare and the union seat surfaces.
4.Air purge
Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition chang may occur in the refrigerant inside the cylinder and the outdoor unit. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
3m 5m
7m 10m 12m
([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52)
MAC-A00PI MAC-A01PI MAC-A02PI MAC-A03PI MAC-A04PI
Page 5
5
REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIME SET button)
TEMPERATURE buttons
VANE CONTROL button
OFF-TIMER button
RESET button
ON/OFF TOO
WARM
TOO
COOL
HR. MIN.
CLOCK
RESET
CLOCK
MODE
FAN
VANE
START
STOP
ECONO COOL button
ECONO COOL
I FEEL
COOL DRY HEAT
6 00
1 1 00
AM
PM
SWING
SWING button
MUZ-A09RV­MUZ-A12RV-
E1
E1
OUTDOOR UNIT
Air inlet
Air outlet
Drain outlet
Piping
Drain hose
MSZ-A09RV­MSZ-A12RV-
E1
E1
Page 6
6
3
SPECIFICATION
Indoor model
Function
Power supply
Capacity Air flow(Hi) Dehumidification Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (Hi) Fan speed (Hi) Fan speed regulator RT11(at25:) Thermistor RT12(at25:) RT13(at25:) Outdoor model Outdoor air flow Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity(R-410A) Refrigerating oil (Model)
RT61(at100:)
Thermistor RT62(at0:) RT64(at50:)
kW
K /h
R/h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k" k"
K /h
A A
W
"
  
"
mm
kg
dB
rpm
kg
cc k" k" k"
MSZ-A09RV -
E1
Single phase
220-240V,50Hz
10
99
4.55 - 4.17
0.17
RA4V19-BA
WHT-BLK 292.4
BLK-RED 324.6
850O278O191
10
5
3 10 10 10
MUZ-A09RV -
E1
0.27-0.25
SNB-092FBA
700
U-V 0.93 U-W 0.93
V-W 0.93
RA6V28-CA
WHT-BLK 197
BLK-RED 315 YLW-BLK 13
710(+69)o540o255
34
2
1.10
450 (NEO22)
13.4
32.6 17
Cooling
2.6 (0.9-3.3) 516
1.2
3.67-3.37
800 (250-1180)
36
920
1440
6.9
3.25
45
670
Heating
3.6 (0.9-4.8) 540
4.55-4.17
990 (250-1650)
35
950
1530
7.4
3.64
47
700
MSZ-A12RV -
E1
Single phase
220-240V,50Hz
10
— 99
7.25 - 6.65
0.19
RA4V19-BA WHT-BLK 292.4 BLK-RED 324.6
850O278O191
10
5
3 10 10 10
MUZ-A12RV -
E1
0.27-0.25
SNB-092FBA
900
U-V 0.93 U-W 0.93
V-W 0.93
RA6V28-CA
WHT-BLK 197
BLK-RED 315 YLW-BLK 13
710(+69)o540o255
34
2
1.10
450 (NEO22)
13.4
32.6 17
Cooling
3.4 (0.9-3.8) 588
1.6
5.60 - 5.13
1220 (250 - 1580)
39
1020
1440
7.4
2.79
46
670
Heating
`4.8 (0.9-6.1)
642
7.25 - 6.65
1580 (250 - 2050)
39
1100
1530
8.1
3.04
48
700
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical data
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
Capacity
NOTE : Test conditions.
Cooling : Indoor DB27: WB19:
Outdoor DB35: WB24:
Heating : Indoor DB 20: WB -:
Ondoor DB 7: WB 6:
Page 7
7
1.5+ 440V
MP24GA 12V 300"
ERZV10D471
S201DH1Y
4P
JM1aN-ZTMP-DC12V
93.5:5A 250V 136:i3: 2A
250V 3.15A
500+ 450V
1.8+ 440V RR-18
250V 2A
13A 1.0mH
EM43240 50m" 5W
100" 20W
4P
PS21101-AL / PS21204-A
G4U-1-E G4U-1-E
LB6 250V AC
PMA10001
G4A-1A-P-PS
INDOOR UNIT
OUTDOOR UNIT
Item
Model
Model
Item
Indoor fan capacitor Vane motor Varistor (NR11) Semiconductor relay Terminal block Relay (compressor) (52C) Terminal block thermal Fuse Indoor fan motor thermal fuse Fuse (F11)
Smoothing capacitor (C61,C62) Outdoor fan capacitor (C65) Current transformer (CT61) Fuse (F801, F901) Reactor (L64) Noise filter Current detecting resistor (R61, 62, 64) Current limiting resistor (R65) Terminal block Intelligent power module Relay (X61) Relay (X62) Reversing valve coil Power factor controll module Rush current limiting relay
MSZ-A09RV MSZ-A12RV
MUZ-A09RV MUZ-A12RV
Specifications and rating conditions of main electric parts
Page 8
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19: Heating : DB20: WB -:
MSZ-A09RV- E1
HEATING
NOTCH
35
COOLING 36
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35
:
WB24
:
Heating :DB 7
:
WB 6
:
MUZ-A09RV- E1
HEATING
NOTCH
47
COOLING 45
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27
:
WB19
:
Heating : DB20
:
WB -
:
MSZ-A12RV- E1
HEATING COOLING
NOTCH
39
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35
:
WB24
:
Heating :DB 7
:
WB 6
:
MUZ-A12RV- E1
HEATING
NOTCH
48
COOLING 46
SPL(dB(A)) LINE
4
NOISE CRITERIA CURVES
8
Page 9
9
116.581.5
818
278
850
16562956
or more
100
41
2.5
42
271 4.5
231.5
82
169
326 326
5
189
56
160
17.5
Air in
Air out
Insulation [28
Drain hose [16 (Connected part O.D)
Installation plate
Wall hole [65
Indoor unit
Installation plate
Power supply cord Lead to right 1.0m Lead to left 0.3m
Wireless remote controller
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D
[21 I.D
78
67
7
{
OUTLINES AND DIMENSIONS5
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
Service port
Bolt pitch for installation
Handle
Air out
Air in
Drainage holes [28
4 holes 10o21
18
500 710
265
105
69
138
20
40
If both sides or back side is vacant. only to be free 50 cm in front of a unit
Air in
265
REQUIRED SPACE
If a front side or both sides is vacant. an upper side of a unit has only to be vacant 10cm.
Drainage holes [28
127
32.4
92
367
Drainage holes [28
33
32.5
255
285
320
155
90
43-
35-
540
270
10
35cm or more
50cm or more
10cm or more
10cm or more
10cm
or m
ore
MSZ-A09RV­MSZ-A12RV-
E1
E1
MUZ-A09RV­MUZ-A12RV-
E1
E1
INDOOR UNIT
OUTDOOR UNIT
Page 10
10
6 WIRING DIAGRAM
INDOOR UNIT
MSZ-A09RV- MSZ-A12RV- MODELS WIRING DIAGRAM
E1E1
POWER SUPPLY CORD ~/N 220-240V 50Hz
GRN/YLW
BLK GRY YLW BRN WHT RED
MF
1 2 3 4 5 6
3
SR141
3
2
1
CN
121
C11
HIC1
TRANS
MV2
RT13
4 3 2
1
CN112
151
CN
MV1
10
RT12
RT11
111
CN
CN211
NR11
ELECTRONIC CONTROL P.C. BOARD
F11
220-240V~
BRN
TB
L
3
2
N
BLU
BRN
WHT
BLU
F12
RED
BLU
BLU
1 2
BLU
1
2
3
CN201
3
4
52C
PE
CIRCUIT BREAKER
12V
TO OUTDOOR UNIT CONNECTING
GREEN SIGN MONITOR P.C.BOARD
11
CN
1J1
REMOTE CONTROLLER
POWER MONITOR, RECEIVER P.C.BOARD
5
LD101T
SYMBOL C11 F11 F12 HIC1 MF MV1 MV2
SYMBOL NR11
RT11
RT12
RT13
SYMBOL SR141 TB 52C
NAME INDOOR FAN CAPACITOR FUSE (3.15A) THERMAL FUSE (93:) DC/DC CONVERTER INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL)
NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
NAME SOLID STATE RELAY TERMINAL BLOCK CONTACTOR
GRN/YLW
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
Page 11
11
OUTDOOR UNIT
MUZ-A09RV- MUZ-A12RV- MODELS WIRING DIAGRAM
E1E1
C65
BLK
CN771
F901
1
2
CN
911
YLW
X61
RED
WHT
ORG
X62
654321
MF61
5
CN914
BOARD
RELAY
CN912
CN779CN778
CN913
4
4
TRANS
CN601
BLU
WHT
TAB62
SSR61
L61
DSA61
NR61
LD-E
3
L63
TAB68
TAB69
LD62 LD61
LD67
N
P
W
V
U
LD66
LD65
TAB76
TAB75
PFC
R61
R62
C61
C62
R64
CN724
-
+
LEV
6
CN726
1
2
3
L64
12
LDNF1
LDNF2
TAB72
TAB71
TAB61
231
21S4
ELECTRONIC CONTROL P.C BOARD
CN641
1 2
CN642
6 5 4 3 2 1
IPM
V
W
21
3
GRN
GRY
GRY
BLK
BLK
F801
IC950
RT64
RT62
RT61
BLK
WHT
RED
BLK
WHT
RED
P.C
NOISE FILTER P.C BOARD
1 2
TB2
WHT
BLU
R65
X64
CT61
~
~
MC
GRN/YLW
BLU
12V
3 2 N
TB1
220-240V ~
FROM INDOOR UNIT CONNECTING
SYMBOL CT61 C61,C62 C65 DSA61 F801 F901 IC950 IPM LEV L61
SYMBOL L63 L64 MC MF61 NR61 PFC RT61 RT62 RT64 R61,62
SYMBOL R64 R65 SSR61 TB1, TB2 X61, X62 X64
21S4
NAME CURRENT TRANSFORMER SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (2A) FUSE (2A) DC/DC CONVERTER
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL CMC COIL
NAME COIL REACTOR COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) VARISTOR POWER FACTOR CONTROL MODULE DISCHARGE TEMPERATURE THERMIST OR DEFROST THERMISTOR FIN TEMPERATURE THERMIST OR CURRENT-DETECTING RESISTOR
NAME CURRENT-DETECTING RESISTOR CURRENT-LIMITING RESISTOR SOLID STATE RELAY TERMINAL BLOCK RELAY RELAY REVERSING VALVE COIL (COOLING TURN ON)
BLU
RED
WHT
+ +
U
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
Page 12
12
MUZ-A09RV ­MUZ-A12RV -
E1
E1
OUTDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
7
MSZ-A09RV ­MSZ-A12RV -
E1
E1
INDOOR UNIT
Unit : mm
MAX. REFRIGERANT PIPING LENGTH
Model
MSZ-A09RV­MSZ-A12RV-
E1
E1
Additional piping
Max. length :mm
A
12
Piping size O.D : mm
Gas Liquid Indoor unit Outdoor unit
9.52 6.35 0.43 0
Length of connecting pipe : m
Refrigerant Piping Max. length A
Height difference should be within 5m regardless of which unit, indoor or outdoor position is high.
w Max. Height
difference 8m
Indoor unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE (R-410A:g)
Model
MSZ-A09RV­MSZ-A12RV-
E1
E1
Outdoor unit precharged
1100
Refrigerant piping length (one way)
9m8m
60
30
Calculation : Xg=30g /m(A-7)m
Indoor heat exchanger
Outdoor heat exchanger
Distributor
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Defrost thermistor RT62
Discharge thermistor RT61
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
Capillary tube (2 pcs)
Refrigerant flow in cooling
Compressor
Accumulator
Maffler
Muffler
Reversing valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (Option)
Refrigerant pipe [6.35 (Option)
Indoor coil thermistor RT12(main)
Expansion valve
[3.0o[2.0o200
[3.0o[2.0o300
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant inside the cylinder and the outdoor unit. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
11m10m
12090
12m
150
7m
0
Page 13
13
PERFORMANCE CURVES8
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 242V ),50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature ::WB (2) Indoor discharge air wet-bulb temperature ::WB (3) Outdoor intake air dry-bulb temperature ::DB (4) Total input :W (5) Indoor intake air dry-bulb temperature ::DB (6) Outdoor intake air wet-bulb temperature ::WB (7) Total input :W
Indoor air wet-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet-bulb temperature and the indoor discharge air wet-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
E1
INDOOR UNIT
OUTDOOR UNIT
}
Cooling
}
Heating
Page 14
14
7.4
6.9
6.3
5.8
5.3
4.8
MSZ-A09RV- E1
8.5
7.9
7.3
6.7
6.1
5.5
MSZ-A12RV- E1
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Cooling capacity
MUZ-A09RV -
E1
MUZ-A12RV -
E1
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
2.0
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
2.0
MUZ-A09RV -
E1
MUZ-A12RV -
E1
Page 15
15
27.1
25.1
23.0
20.9
18.8
16.7
14.6
12.5
30.4
28.1
25.8
23.4
21.1
18.7
16.4
14.1
MSZ-A12RV- E1
MSZ-A09RV- E1
NOTE:The above curves are for the heating operation without any frost.
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Heating capacity
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
MUZ-A09RV -
E1
MUZ-A12RV -
E1
MUZ-A09RV -
E1
MUZ-A12RV -
E1
Page 16
16
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
Dry-bulb temperature
Relative humidity(%)
20
50
25
60
30
70
(MPa • G)
(kgf/F • G)
(reference)
18 32
62Hz
15 20
50
25 60
30 70(%)
35(:)
0.6
0.7
0.8
0.9
1.0
1.1
62Hz
6
7
8
9
10
11
12
1.2
MUZ-A12RV -
E1
Outdoor low pressure
Ambient temperature(:) Ambient humidity(%)
220V
240V
15 20
50
25 60
30
70(%)
35(:)
3
4
5
6
7
83Hz
32
18
MUZ-A12RV -
E1
Outdoor unit current (A)
Ambient temperature(:) Ambient humidity(%)
2 Air flow should be set at Hi. 3 Operational frequency : 83Hz
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit , and select either the COOLmode or the HEAT mode before starting to operate the air conditioner.
2. The compressor starts up. The operational frequency of the compressor is 83Hz in the COOL mode and 58Hz in the HEAT mode.
3. The fan speed of the indoor unit is Hi.
4. This operation continues for 30minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch again, press any button on the remote
controller.
COOL operation
MUZ-A09RV -
E1
MUZ-A09RV -
E1
(MPa • G)
(kgf/F • G)
(reference)
18 32
62Hz
7
8
9
10
11
12
13
15 20
50
25 60
30 70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
62Hz
Outdoor low pressure
Ambient temperature(:) Ambient humidity(%)
15 20
50
25 6030 70(%)
35(:)
1
2
3
4
5
32
18
220V
240V
53Hz
Outdoor unit current (A)
Ambient temperature(:) Ambient humidity(%)
Page 17
17
6.0
5.5
5.0
4.5
4.0
3.5
3.0 2
5 10152025
240V
220V
58Hz
MUZ-A12RV -
E1
Outdoor unit current (A)
Ambient temperature(:)
HEAT operation
Condition Indoor : Dry bulb temperature 20.0:
Wet bulb temperature 14.5:
Outdoor : Dry bulb temperature 2 7 15 20.0:
Wet bulb temperature 1 6 12 14.5:
58Hz
220V
240V
6.0
5.5
5.0
4.5
4.0
3.5
3.0 2
510152025
MUZ-A09RV -
E1
Outdoor unit current (A)
Ambient temperature(:)
Page 18
18
PERFORMANCE DATA COOL operation
MUZ-A09RV -
E1
21
18
3.06 1.71 0.56 640 2.93 1.64 0.56 672 2.81 1.57 0.56 704 2.70 1.51 0.56 736
21
20
3.19 1.40 0.44 672 3.06 1.34 0.44 712 2.96 1.30 0.44 728 2.86 1.26 0.44 760
22
18
3.06 1.83 0.60 640 2.93 1.76 0.60 672 2.81 1.68 0.60 704 2.70 1.62 0.60 736
22
20
3.19 1.53 0.48 672 3.06 1.47 0.48 712 2.96 1.42 0.48 728 2.86 1.37 0.48 760
22
22
3.32 1.19 0.36 696 3.20 1.15 0.36 740 3.12 1.12 0.36 760 2.99 1.08 0.36 792
23
18
3.06 1.96 0.64 640 2.93 1.87 0.64 672 2.81 1.80 0.64 704 2.70 1.73 0.64 736
23
20
3.19 1.66 0.52 672 3.06 1.59 0.52 712 2.96 1.54 0.52 728 2.86 1.49 0.52 760
23
22
3.32 1.33 0.40 696 3.20 1.28 0.40 740 3.12 1.25 0.40 760 2.99 1.20 0.40 792
24
18
3.06 2.08 0.68 640 2.93 1.99 0.68 672 2.81 1.91 0.68 704 2.70 1.84 0.68 736
24
20
3.19 1.78 0.56 672 3.06 1.71 0.56 712 2.96 1.66 0.56 728 2.86 1.60 0.56 760
24
22
3.32 1.46 0.44 696 3.20 1.41 0.44 740 3.12 1.37 0.44 760 2.99 1.32 0.44 792
24
24
3.48 1.11 0.32 728 3.35 1.07 0.32 768 3.28 1.05 0.32 792 3.17 1.02 0.32 832
25
18
3.06 2.20 0.72 640 2.93 2.11 0.72 672 2.81 2.02 0.72 704 2.70 1.95 0.72 736
25
20
3.19 1.91 0.60 672 3.06 1.83 0.60 712 2.96 1.78 0.60 728 2.86 1.72 0.60 760
25
22
3.32 1.59 0.48 696 3.20 1.54 0.48 740 3.12 1.50 0.48 760 2.99 1.44 0.48 792
25
24
3.48 1.25 0.36 728 3.35 1.21 0.36 768 3.28 1.18 0.36 792 3.17 1.14 0.36 832
26
18
3.06 2.32 0.76 640 2.93 2.22 0.76 672 2.81 2.13 0.76 704 2.70 2.06 0.76 736
26
20
3.19 2.04 0.64 672 3.06 1.96 0.64 712 2.96 1.90 0.64 728 2.86 1.83 0.64 760
26
22
3.32 1.72 0.52 696 3.20 1.66 0.52 740 3.12 1.62 0.52 760 2.99 1.55 0.52 792
26
24
3.48 1.39 0.40 728 3.35 1.34 0.40 768 3.28 1.31 0.40 792 3.17 1.27 0.40 832
26
26
3.59 1.00 0.28 768 3.48 0.98 0.28 808 3.43 0.96 0.28 832 3.33 0.93 0.28 856
27
18
3.06 2.44 0.80 640 2.93 2.34 0.80 672 2.81 2.25 0.80 704 2.70 2.16 0.80 736
27
20
3.19 2.17 0.68 672 3.06 2.08 0.68 712 2.96 2.02 0.68 728 2.86 1.94 0.68 760
27
22
3.32 1.86 0.56 696 3.20 1.79 0.56 740 3.12 1.75 0.56 760 2.99 1.67 0.56 792
27
24
3.48 1.53 0.44 728 3.35 1.48 0.44 768 3.28 1.44 0.44 792 3.17 1.40 0.44 832
27
26
3.59 1.15 0.32 768 3.48 1.11 0.32 808 3.43 1.10 0.32 832 3.33 1.06 0.32 856
28
18
3.06 2.57 0.84 640 2.93 2.46 0.84 672 2.81 2.36 0.84 704 2.70 2.27 0.84 736
28
20
3.19 2.29 0.72 672 3.06 2.20 0.72 712 2.96 2.13 0.72 728 2.86 2.06 0.72 760
28
22
3.32 1.99 0.60 696 3.20 1.92 0.60 740 3.12 1.87 0.60 760 2.99 1.79 0.60 792
28
24
3.48 1.67 0.48 728 3.35 1.61 0.48 768 3.28 1.57 0.48 792 3.17 1.52 0.48 832
28
26
3.59 1.29 0.36 768 3.48 1.25 0.36 808 3.43 1.24 0.36 832 3.33 1.20 0.36 856
29
18
3.06 2.69 0.88 640 2.93 2.57 0.88 672 2.81 2.47 0.88 704 2.70 2.38 0.88 736
29
20
3.19 2.42 0.76 672 3.06 2.32 0.76 712 2.96 2.25 0.76 728 2.86 2.17 0.76 760
29
22
3.32 2.12 0.64 696 3.20 2.05 0.64 740 3.12 2.00 0.64 760 2.99 1.91 0.64 792
29
24
3.48 1.81 0.52 728 3.35 1.74 0.52 768 3.28 1.70 0.52 792 3.17 1.65 0.52 832
29
26
3.59 1.44 0.40 768 3.48 1.39 0.40 808 3.43 1.37 0.40 832 3.33 1.33 0.40 856
30
18
3.06 2.81 0.92 640 2.93 2.69 0.92 672 2.81 2.58 0.92 704 2.70 2.49 0.92 736
30
20
3.19 2.55 0.80 672 3.06 2.44 0.80 712 2.96 2.37 0.80 728 2.86 2.29 0.80 760
30
22
3.32 2.25 0.68 696 3.20 2.17 0.68 740 3.12 2.12 0.68 760 2.99 2.03 0.68 792
30
24
3.48 1.95 0.56 728 3.35 1.88 0.56 768 3.28 1.83 0.56 792 3.17 1.78 0.56 832
30
26
3.59 1.58 0.44 768 3.48 1.53 0.44 808 3.43 1.51 0.44 832 3.33 1.46 0.44 856
31
18
3.06 2.93 0.96 640 2.93 2.81 0.96 672 2.81 2.70 0.96 704 2.70 2.60 0.96 736
31
20
3.19 2.68 0.84 672 3.06 2.57 0.84 712 2.96 2.49 0.84 728 2.86 2.40 0.84 760
31
22
3.32 2.39 0.72 696 3.20 2.30 0.72 740 3.12 2.25 0.72 760 2.99 2.15 0.72 792
31
24
3.48 2.09 0.60 728 3.35 2.01 0.60 768 3.28 1.97 0.60 792 3.17 1.90 0.60 832
31
26
3.59 1.72 0.48 768 3.48 1.67 0.48 808 3.43 1.65 0.48 832 3.33 1.60 0.48 856
32
18
3.06 3.06 1.00 640 2.93 2.93 1.00 672 2.81 2.81 1.00 704 2.70 2.70 1.00 736
32
20
3.19 2.80 0.88 672 3.06 2.69 0.88 712 2.96 2.61 0.88 728 2.86 2.52 0.88 760
32
22
3.32 2.52 0.76 696 3.20 2.43 0.76 740 3.12 2.37 0.76 760 2.99 2.27 0.76 792
32
24
3.48 2.23 0.64 728 3.35 2.15 0.64 768 3.28 2.10 0.64 792 3.17 2.03 0.64 832
32
26
3.59 1.87 0.52 768 3.48 1.81 0.52 808 3.43 1.78 0.52 832 3.33 1.73 0.52 856
OUTDOOR DB(:)
INDOOR INDOOR
21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 2.6 kW INPUT : 800 W SHF : 0.74
Page 19
19
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.55 1.43 0.56 784 2.34 1.31 0.56 832 2.25 1.26 0.56 848 21 20 2.68 1.18 0.44 816 2.50 1.10 0.44 856 2.41 1.06 0.44 880 22 18 2.55 1.53 0.60 784 2.34 1.40 0.60 832 2.25 1.35 0.60 848 22 20 2.68 1.29 0.48 816 2.50 1.20 0.48 856 2.41 1.15 0.48 880 22 22 2.83 1.02 0.36 848 2.65 0.95 0.36 896 2.56 0.92 0.36 912 23 18 2.55 1.63 0.64 784 2.34 1.50 0.64 832 2.25 1.44 0.64 848 23 20 2.68 1.39 0.52 816 2.50 1.30 0.52 856 2.41 1.25 0.52 880 23 22 2.83 1.13 0.40 848 2.65 1.06 0.40 896 2.56 1.02 0.40 912 24 18 2.55 1.73 0.68 784 2.34 1.59 0.68 832 2.25 1.53 0.68 848 24 20 2.68 1.50 0.56 816 2.50 1.40 0.56 856 2.41 1.35 0.56 880 24 22 2.83 1.25 0.44 848 2.65 1.17 0.44 896 2.56 1.13 0.44 912 24 24 2.99 0.96 0.32 880 2.81 0.90 0.32 920 2.73 0.87 0.32 940 25 18 2.55 1.83 0.72 784 2.34 1.68 0.72 832 2.25 1.62 0.72 848 25 20 2.68 1.61 0.60 816 2.50 1.50 0.60 856 2.41 1.44 0.60 880 25 22 2.83 1.36 0.48 848 2.65 1.27 0.48 896 2.56 1.23 0.48 912 25 24 2.99 1.08 0.36 880 2.81 1.01 0.36 920 2.73 0.98 0.36 940 26 18 2.55 1.94 0.76 784 2.34 1.78 0.76 832 2.25 1.71 0.76 848 26 20 2.68 1.71 0.64 816 2.50 1.60 0.64 856 2.41 1.54 0.64 880 26 22 2.83 1.47 0.52 848 2.65 1.38 0.52 896 2.56 1.33 0.52 912 26 24 2.99 1.20 0.40 880 2.81 1.12 0.40 920 2.73 1.09 0.40 940 26 26 3.15 0.88 0.28 912 2.96 0.83 0.28 952 2.87 0.80 0.28 972 27 18 2.55 2.04 0.80 784 2.34 1.87 0.80 832 2.25 1.80 0.80 848 27 20 2.68 1.82 0.68 816 2.50 1.70 0.68 856 2.41 1.64 0.68 880 27 22 2.83 1.59 0.56 848 2.65 1.49 0.56 896 2.56 1.43 0.56 912 27 24 2.99 1.32 0.44 880 2.81 1.24 0.44 920 2.73 1.20 0.44 940 27 26 3.15 1.01 0.32 912 2.96 0.95 0.32 952 2.87 0.92 0.32 972 28 18 2.55 2.14 0.84 784 2.34 1.97 0.84 832 2.25 1.89 0.84 848 28 20 2.68 1.93 0.72 816 2.50 1.80 0.72 856 2.41 1.73 0.72 880 28 22 2.83 1.70 0.60 848 2.65 1.59 0.60 896 2.56 1.54 0.60 912 28 24 2.99 1.44 0.48 880 2.81 1.35 0.48 920 2.73 1.31 0.48 940 28 26 3.15 1.13 0.36 912 2.96 1.07 0.36 952 2.87 1.03 0.36 972 29 18 2.55 2.24 0.88 784 2.34 2.06 0.88 832 2.25 1.98 0.88 848 29 20 2.68 2.04 0.76 816 2.50 1.90 0.76 856 2.41 1.83 0.76 880 29 22 2.83 1.81 0.64 848 2.65 1.70 0.64 896 2.56 1.64 0.64 912 29 24 2.99 1.55 0.52 880 2.81 1.46 0.52 920 2.73 1.42 0.52 940 29 26 3.15 1.26 0.40 912 2.96 1.19 0.40 952 2.87 1.15 0.40 972 30 18 2.55 2.34 0.92 784 2.34 2.15 0.92 832 2.25 2.07 0.92 848 30 20 2.68 2.14 0.80 816 2.50 2.00 0.80 856 2.41 1.92 0.80 880 30 22 2.83 1.93 0.68 848 2.65 1.80 0.68 896 2.56 1.74 0.68 912 30 24 2.99 1.67 0.56 880 2.81 1.57 0.56 920 2.73 1.53 0.56 940 30 26 3.15 1.38 0.44 912 2.96 1.30 0.44 952 2.87 1.26 0.44 972 31 18 2.55 2.45 0.96 784 2.34 2.25 0.96 832 2.25 2.16 0.96 848 31 20 2.68 2.25 0.84 816 2.50 2.10 0.84 856 2.41 2.02 0.84 880 31 22 2.83 2.04 0.72 848 2.65 1.91 0.72 896 2.56 1.84 0.72 912 31 24 2.99 1.79 0.60 880 2.81 1.68 0.60 920 2.73 1.64 0.60 940 31 26 3.15 1.51 0.48 912 2.96 1.42 0.48 952 2.87 1.38 0.48 972 32 18 2.55 2.55 1.00 784 2.34 2.34 1.00 832 2.25 2.25 1.00 848 32 20 2.68 2.36 0.88 816 2.50 2.20 0.88 856 2.41 2.12 0.88 880 32 22 2.83 2.15 0.76 848 2.65 2.02 0.76 896 2.56 1.95 0.76 912 32 24 2.99 1.91 0.64 880 2.81 1.80 0.64 920 2.73 1.75 0.64 940 32 26 3.15 1.64 0.52 912 2.96 1.54 0.52 952 2.87 1.49 0.52 972
CAPACITY : 2.6 kW INPUT : 800 W SHF : 0.74
PERFORMANCE DATA COOL operation
MUZ-A09RV -
E1
Page 20
20
MUZ-A12RV -
E1
OUTDOOR DB(:)
INDOOR INDOOR
21 25 27 30
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.00 2.04 0.51 976 3.83 1.95 0.51 1025 3.67 1.87 0.51 1074 3.54 1.80 0.51 1122 21 20 4.17 1.62 0.39 1025 4.00 1.56 0.39 1086 3.88 1.51 0.39 1110 3.74 1.46 0.39 1159 22 18 4.00 2.20 0.55 976 3.83 2.10 0.55 1025 3.67 2.02 0.55 1074 3.54 1.94 0.55 1122 22 20 4.17 1.79 0.43 1025 4.00 1.72 0.43 1086 3.88 1.67 0.43 1110 3.74 1.61 0.43 1159 22 22 4.34 1.34 0.31 1061 4.18 1.30 0.31 1129 4.08 1.26 0.31 1159 3.91 1.21 0.31 1208 23 18 4.00 2.36 0.59 976 3.83 2.26 0.59 1025 3.67 2.17 0.59 1074 3.54 2.09 0.59 1122 23 20 4.17 1.96 0.47 1025 4.00 1.88 0.47 1086 3.88 1.82 0.47 1110 3.74 1.76 0.47 1159 23 22 4.34 1.52 0.35 1061 4.18 1.46 0.35 1129 4.08 1.43 0.35 1159 3.91 1.37 0.35 1208 24 18 4.00 2.52 0.63 976 3.83 2.41 0.63 1025 3.67 2.31 0.63 1074 3.54 2.23 0.63 1122 24 20 4.17 2.12 0.51 1025 4.00 2.04 0.51 1086 3.88 1.98 0.51 1110 3.74 1.91 0.51 1159 24 22 4.34 1.69 0.39 1061 4.18 1.63 0.39 1129 4.08 1.59 0.39 1159 3.91 1.52 0.39 1208 24 24 4.56 1.23 0.27 1110 4.39 1.18 0.27 1171 4.28 1.16 0.27 1208 4.15 1.12 0.27 1269 25 18 4.00 2.68 0.67 976 3.83 2.56 0.67 1025 3.67 2.46 0.67 1074 3.54 2.37 0.67 1122 25 20 4.17 2.29 0.55 1025 4.00 2.20 0.55 1086 3.88 2.13 0.55 1110 3.74 2.06 0.55 1159 25 22 4.34 1.86 0.43 1061 4.18 1.80 0.43 1129 4.08 1.75 0.43 1159 3.91 1.68 0.43 1208 25 24 4.56 1.41 0.31 1110 4.39 1.36 0.31 1171 4.28 1.33 0.31 1208 4.15 1.29 0.31 1269 26 18 4.00 2.84 0.71 976 3.83 2.72 0.71 1025 3.67 2.61 0.71 1074 3.54 2.51 0.71 1122 26 20 4.17 2.46 0.59 1025 4.00 2.36 0.59 1086 3.88 2.29 0.59 1110 3.74 2.21 0.59 1159 26 22 4.34 2.04 0.47 1061 4.18 1.97 0.47 1129 4.08 1.92 0.47 1159 3.91 1.84 0.47 1208 26 24 4.56 1.59 0.35 1110 4.39 1.54 0.35 1171 4.28 1.50 0.35 1208 4.15 1.45 0.35 1269 26 26 4.69 1.08 0.23 1171 4.56 1.05 0.23 1232 4.49 1.03 0.23 1269 4.35 1.00 0.23 1305 27 18 4.00 3.00 0.75 976 3.83 2.87 0.75 1025 3.67 2.75 0.75 1074 3.54 2.65 0.75 1122 27 20 4.17 2.62 0.63 1025 4.00 2.52 0.63 1086 3.88 2.44 0.63 1110 3.74 2.36 0.63 1159 27 22 4.34 2.21 0.51 1061 4.18 2.13 0.51 1129 4.08 2.08 0.51 1159 3.91 1.99 0.51 1208 27 24 4.56 1.78 0.39 1110 4.39 1.71 0.39 1171 4.28 1.67 0.39 1208 4.15 1.62 0.39 1269 27 26 4.69 1.27 0.27 1171 4.56 1.23 0.27 1232 4.49 1.21 0.27 1269 4.35 1.18 0.27 1305 28 18 4.00 3.16 0.79 976 3.83 3.02 0.79 1025 3.67 2.90 0.79 1074 3.54 2.79 0.79 1122 28 20 4.17 2.79 0.67 1025 4.00 2.68 0.67 1086 3.88 2.60 0.67 1110 3.74 2.51 0.67 1159 28 22 4.34 2.38 0.55 1061 4.18 2.30 0.55 1129 4.08 2.24 0.55 1159 3.91 2.15 0.55 1208 28 24 4.56 1.96 0.43 1110 4.39 1.89 0.43 1171 4.28 1.84 0.43 1208 4.15 1.78 0.43 1269 28 26 4.69 1.45 0.31 1171 4.56 1.41 0.31 1232 4.49 1.39 0.31 1269 4.35 1.35 0.31 1305 29 18 4.00 3.32 0.83 976 3.83 3.17 0.83 1025 3.67 3.05 0.83 1074 3.54 2.93 0.83 1122 29 20 4.17 2.96 0.71 1025 4.00 2.84 0.71 1086 3.88 2.75 0.71 1110 3.74 2.66 0.71 1159 29 22 4.34 2.56 0.59 1061 4.18 2.47 0.59 1129 4.08 2.41 0.59 1159 3.91 2.31 0.59 1208 29 24 4.56 2.14 0.47 1110 4.39 2.06 0.47 1171 4.28 2.01 0.47 1208 4.15 1.95 0.47 1269 29 26 4.69 1.64 0.35 1171 4.56 1.59 0.35 1232 4.49 1.57 0.35 1269 4.35 1.52 0.35 1305 30 18 4.00 3.48 0.87 976 3.83 3.33 0.87 1025 3.67 3.19 0.87 1074 3.54 3.08 0.87 1122 30 20 4.17 3.12 0.75 1025 4.00 3.00 0.75 1086 3.88 2.91 0.75 1110 3.74 2.81 0.75 1159 30 22 4.34 2.73 0.63 1061 4.18 2.63 0.63 1129 4.08 2.57 0.63 1159 3.91 2.46 0.63 1208 30 24 4.56 2.32 0.51 1110 4.39 2.24 0.51 1171 4.28 2.18 0.51 1208 4.15 2.12 0.51 1269 30 26 4.69 1.83 0.39 1171 4.56 1.78 0.39 1232 4.49 1.75 0.39 1269 4.35 1.70 0.39 1305 31 18 4.00 3.64 0.91 976 3.83 3.48 0.91 1025 3.67 3.34 0.91 1074 3.54 3.22 0.91 1122 31 20 4.17 3.29 0.79 1025 4.00 3.16 0.79 1086 3.88 3.06 0.79 1110 3.74 2.95 0.79 1159 31 22 4.34 2.90 0.67 1061 4.18 2.80 0.67 1129 4.08 2.73 0.67 1159 3.91 2.62 0.67 1208 31 24 4.56 2.51 0.55 1110 4.39 2.41 0.55 1171 4.28 2.36 0.55 1208 4.15 2.28 0.55 1269 31 26 4.69 2.02 0.43 1171 4.56 1.96 0.43 1232 4.49 1.93 0.43 1269 4.35 1.87 0.43 1305 32 18 4.00 3.80 0.95 976 3.83 3.63 0.95 1025 3.67 3.49 0.95 1074 3.54 3.36 0.95 1122 32 20 4.17 3.46 0.83 1025 4.00 3.32 0.83 1086 3.88 3.22 0.83 1110 3.74 3.10 0.83 1159 32 22 4.34 3.08 0.71 1061 4.18 2.97 0.71 1129 4.08 2.90 0.71 1159 3.91 2.78 0.71 1208 32 24 4.56 2.69 0.59 1110 4.39 2.59 0.59 1171 4.28 2.53 0.59 1208 4.15 2.45 0.59 1269 32 26 4.69 2.21 0.47 1171 4.56 2.14 0.47 1232 4.49 2.11 0.47 1269 4.35 2.05 0.47 1305
CAPACITY : 3.4 kW INPUT : 1220 W SHF : 0.69
PERFORMANCE DATA COOL operation
Page 21
21
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.33 1.70 0.51 1196 3.06 1.56 0.51 1269 2.94 1.50 0.51 1293 21 20 3.50 1.37 0.39 1244 3.26 1.27 0.39 1305 3.15 1.23 0.39 1342 22 18 3.33 1.83 0.55 1196 3.06 1.68 0.55 1269 2.94 1.62 0.55 1293 22 20 3.50 1.51 0.43 1244 3.26 1.40 0.43 1305 3.15 1.35 0.43 1342 22 22 3.71 1.15 0.31 1293 3.47 1.08 0.31 1366 3.35 1.04 0.31 1391 23 18 3.33 1.97 0.59 1196 3.06 1.81 0.59 1269 2.94 1.74 0.59 1293 23 20 3.50 1.65 0.47 1244 3.26 1.53 0.47 1305 3.15 1.48 0.47 1342 23 22 3.71 1.30 0.35 1293 3.47 1.21 0.35 1366 3.35 1.17 0.35 1391 24 18 3.33 2.10 0.63 1196 3.06 1.93 0.63 1269 2.94 1.85 0.63 1293 24 20 3.50 1.79 0.51 1244 3.26 1.66 0.51 1305 3.15 1.60 0.51 1342 24 22 3.71 1.45 0.39 1293 3.47 1.35 0.39 1366 3.35 1.31 0.39 1391 24 24 3.91 1.06 0.27 1342 3.67 0.99 0.27 1403 3.57 0.96 0.27 1434 25 18 3.33 2.23 0.67 1196 3.06 2.05 0.67 1269 2.94 1.97 0.67 1293 25 20 3.50 1.93 0.55 1244 3.26 1.80 0.55 1305 3.15 1.73 0.55 1342 25 22 3.71 1.59 0.43 1293 3.47 1.49 0.43 1366 3.35 1.44 0.43 1391 25 24 3.91 1.21 0.31 1342 3.67 1.14 0.31 1403 3.57 1.11 0.31 1434 26 18 3.33 2.37 0.71 1196 3.06 2.17 0.71 1269 2.94 2.09 0.71 1293 26 20 3.50 2.07 0.59 1244 3.26 1.93 0.59 1305 3.15 1.86 0.59 1342 26 22 3.71 1.74 0.47 1293 3.47 1.63 0.47 1366 3.35 1.57 0.47 1391 26 24 3.91 1.37 0.35 1342 3.67 1.29 0.35 1403 3.57 1.25 0.35 1434 26 26 4.11 0.95 0.23 1391 3.88 0.89 0.23 1452 3.76 0.86 0.23 1482 27 18 3.33 2.50 0.75 1196 3.06 2.30 0.75 1269 2.94 2.21 0.75 1293 27 20 3.50 2.21 0.63 1244 3.26 2.06 0.63 1305 3.15 1.98 0.63 1342 27 22 3.71 1.89 0.51 1293 3.47 1.77 0.51 1366 3.35 1.71 0.51 1391 27 24 3.91 1.52 0.39 1342 3.67 1.43 0.39 1403 3.57 1.39 0.39 1434 27 26 4.11 1.11 0.27 1391 3.88 1.05 0.27 1452 3.76 1.01 0.27 1482 28 18 3.33 2.63 0.79 1196 3.06 2.42 0.79 1269 2.94 2.32 0.79 1293 28 20 3.50 2.35 0.67 1244 3.26 2.19 0.67 1305 3.15 2.11 0.67 1342 28 22 3.71 2.04 0.55 1293 3.47 1.91 0.55 1366 3.35 1.84 0.55 1391 28 24 3.91 1.68 0.43 1342 3.67 1.58 0.43 1403 3.57 1.54 0.43 1434 28 26 4.11 1.28 0.31 1391 3.88 1.20 0.31 1452 3.76 1.16 0.31 1482 29 18 3.33 2.77 0.83 1196 3.06 2.54 0.83 1269 2.94 2.44 0.83 1293 29 20 3.50 2.49 0.71 1244 3.26 2.32 0.71 1305 3.15 2.23 0.71 1342 29 22 3.71 2.19 0.59 1293 3.47 2.05 0.59 1366 3.35 1.98 0.59 1391 29 24 3.91 1.84 0.47 1342 3.67 1.73 0.47 1403 3.57 1.68 0.47 1434 29 26 4.11 1.44 0.35 1391 3.88 1.36 0.35 1452 3.76 1.31 0.35 1482 30 18 3.33 2.90 0.87 1196 3.06 2.66 0.87 1269 2.94 2.56 0.87 1293 30 20 3.50 2.63 0.75 1244 3.26 2.45 0.75 1305 3.15 2.36 0.75 1342 30 22 3.71 2.33 0.63 1293 3.47 2.18 0.63 1366 3.35 2.11 0.63 1391 30 24 3.91 1.99 0.51 1342 3.67 1.87 0.51 1403 3.57 1.82 0.51 1434 30 26 4.11 1.60 0.39 1391 3.88 1.51 0.39 1452 3.76 1.47 0.39 1482 31 18 3.33 3.03 0.91 1196 3.06 2.78 0.91 1269 2.94 2.68 0.91 1293 31 20 3.50 2.77 0.79 1244 3.26 2.58 0.79 1305 3.15 2.48 0.79 1342 31 22 3.71 2.48 0.67 1293 3.47 2.32 0.67 1366 3.35 2.24 0.67 1391 31 24 3.91 2.15 0.55 1342 3.67 2.02 0.55 1403 3.57 1.96 0.55 1434 31 26 4.11 1.77 0.43 1391 3.88 1.67 0.43 1452 3.76 1.62 0.43 1482 32 18 3.33 3.17 0.95 1196 3.06 2.91 0.95 1269 2.94 2.79 0.95 1293 32 20 3.50 2.91 0.83 1244 3.26 2.71 0.83 1305 3.15 2.61 0.83 1342 32 22 3.71 2.63 0.71 1293 3.47 2.46 0.71 1366 3.35 2.38 0.71 1391 32 24 3.91 2.31 0.59 1342 3.67 2.17 0.59 1403 3.57 2.11 0.59 1434 32 26 4.11 1.93 0.47 1391 3.88 1.82 0.47 1452 3.76 1.77 0.47 1482
CAPACITY : 3.4 kW INPUT : 1220 W SHF : 0.69
MUZ-A12RV -
E1
PERFORMANCE DATA COOL operation
Page 22
22
OUTDOOR DB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.02 1027 3.65 1232 4.27 1390 4.90 1501 5.52 1596 6.10 1643 6.72 1675 21 2.88 1106 3.46 1311 4.08 1454 4.66 1564 5.28 1643 5.86 1691 6.46 1754 26 2.59 1185 3.22 1390 3.79 1533 4.42 1643 5.04 1722 5.62 1770 6.24 1817
CAPACITY : 4.8 kW INPUT : 1580 W
MUZ-A09RV -
E1
MUZ-A12RV -
E1
PERFORMANCE DATA HEAT operation
PERFORMANCE DATA HEAT operation
OUTDOOR DB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.27 644 2.74 772 3.20 871 3.67 941 4.14 1000 4.57 1030 5.04 1049 21 2.16 693 2.59 822 3.06 911 3.49 980 3.96 1030 4.39 1059 4.84 1099 26 1.94 743 2.41 871 2.84 960 3.31 1030 3.78 1079 4.21 1109 4.68 1139
CAPACITY : 3.6 kW INPUT : 990 W
Page 23
23
MICROPROCESSOR CONTROL9
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIME SET button)
TEMPERATURE buttons
VANE CONTROL button
OFF-TIMER button
RESET button
ON/OFF TOO
WARM
TOO
COOL
HR. MIN.
CLOCK
RESET
CLOCK
MODE
FAN
VANE
START
STOP
ECONO COOL button
ECONO COOL
I FEEL
COOL DRY HEAT
6 00
1
1 00
AM
PM
SWING
SWING button
INDOOR UNIT DISPLAY SECTION
Once the controls are set, the same operation mode can be repeated by simply turning the OPERATE/STOP button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for
3 minutes.
MSZ-A09RV­MSZ-A12RV-
E1
E1
GREEN SIGN
GREEN SIGN shows the current room temperature and set temperature. The room temperature indicated on the temperature monitor lamp may not be exactly the same as the actual room temperature.
Available the set temperature range is 16:~31:, however, indication range of temperature monitor lamp is 21:~30:.
The set temperature (lighting) and room temperature (blinking) are displayed.
1.
When the room temperature or set temperature is out of the indication range
If the set temperature is lower than 21:, indicating lamp at 21: is lighting. And if the room temperature is lower than 21:, indicating lamp at 21: is blinking.
If the set temperature is higher than 30:, indicating lamp at 30: is lighting. And if the room temperature is higher than 30:, indicating lamp at 30: is blinking.
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
Blinking lamp shows the room temperature
Lighting lamp shows the set temperature
(Example) When the set temperature is 26:, indicating lamp at 26:
is lighting. When the room temperature is 27.5: or higher and lower than 28.5:, indicating lamp at 28: is blinking.
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
Blinking lamp shows the room temperature
Lighting lamp shows the set temperature
w When the set temperature and room temperature are the same, corresponding indicating lamp is lighting.
NOTE: When the unit is not operating : Both POWER MONITOR lamp and green sign lamps are off. When ON- Timer is set : POWER MONITOR lamp is on. All green sign lamps are off. When OFF- Timer is set : The lamp indication is as same as ordinary operation.
(Example) When the set temperature is 28:, indicating lamp at 28:
is lighting. When the room temperature is 30: or higher, indicating lamp at 30: is blinking.
2.When the room temperature or set temperature is within the indication range
WIRELESS REMOTE CONTROLLER
Page 24
24
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature Initial set temperature
26:
26: or more
26: or less
23: or less
23: to 25:
24:
Initial room temperatureminus 2:
Initial room temperatureminus 2:
1
4. The initial set temperature is decided by the initial room temperature.
9-1. “I FEEL CONTROL” ( ) OPERATION
1. Press OPERATE/STOP button on the remote controller. OPERATION INDICATOR lamp of the indoor unit will turn on with a beep tone.
2. Press OPERATION SELECT button to set “I FEEL CONTROL”( ) Then a beep tone is heard.
3. The operation mode is determined by the initial room temperature at start-up of the operation.
Example
Previous operation COOL mode of “I FEEL CONTROL” or COOL mode
Once the mode is fixed, the mode will not change by room temperature afterwards.
Under the ON-TIMER ( ) operation, mode is determined according to the room temperature as the operation
starts.
When the system is stopped with the OPERATE/STOP button on the remote controller, and restarted within 2 hours in “I
FEEL CONTROL” ( ) mode, the system operates in previous mode automatically regardless of the room temperature.
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
more than 25:
23: to 25:
less than 23:
Example
Previous operation COOL mode of “I FEEL CONTROL” or COOL mode
When the system is restarted after 2 hours, the operation mode is determined by the initial room temperature at start-up
of the operation.
Restart
COOL mode of “I FEEL CONTROL”
Restart
COOL or DRY or HEAT mode of “I FEEL CONTROL” that determined by initial room temperature start-up of the operation.
1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless
of the initial set temperature The set temperature is calculated by the previous set temperature.
Page 25
25
5. TEMPERATURES buttons In “I FEEL CONTROL” (h)mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Pressing the TOO WARM or TOO COOL button emits a beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cold. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
TOO COOL… To raise the set temperature 1 ~ 2 degrees (: )
TOO WARM … To lower the set temperature 1 ~ 2 degrees (:)
— Cool mode of “I FEEL CONTROL” —
1. Followings are the fan speed in AUTO.
Room temperature minus set temperature: 2 degrees or moreover··························Hi Room temperature minus set temperature:
1 degree or more and less than 2 degrees ··········Me
Room temperature minus set temperature: less than 1 degree·································Lo
2. Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. (1).Compressor has been continuously operating. (2).Indoor fan speed is Lo or Me (3).Room temperature is below 26:. When compressor turns off half way,.the accumulated time is cancelled. When compressor turns on again, time counting starts from the beginning. When the indoor fan speed becomes Hi or the room temperature exceeds 26:, timecounting stops temporarily. After, when the above conditions are satisfied again, time counting restarts. The indoor fan operates at set speed.
1.5 deg.
4 deg.
2 deg.
1 deg.
Temperature difference
Difference between room temperature and set temperature during operation.
Fan speed
The operational frequency of the compressor is controlled based on the temperature of the indoor coil thermistor(RT12).
• The indoor fan maintains the actual speed of the moment.
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the temperature and the microprocessor. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. The operation of the compressor and indoor fan is as follows.
Compressor operates by temperature control and time control.
1 Set temperature is controlled to fall 2°C as initial set temperature. 2 Indoor fan and outdoor fan operate in the same cycle as the compressor. 3 Operational frequency control of compressor is fixed 30Hz.
Temperature of indoor coil thermistor:Th
approx. 8°C or above
approx. 6°C to 8°C approx. 3°C to 6°C
approx. 3°C or below
Operation frequency
normal
fixed
lower at the rate of 3Hz/min
lower at the rate of 6Hz/min Compressor is turned OFF for 5 minutes when left temperature continues for 5 minutes or more.
3. Coil frost prevention mode
NOTE Coil frost prevention during DRY mode of “I FEEL CONTROL”
The operation is same as coil frost prevention during COOL mode of “I FEEL CONTROL” .
Page 26
26
— HEAT mode of “I FEEL CONTROL” —
3. Defrosting in DRY mode
The operational frequency of the compressor is controlled based on the temperature of the indoor coil thermistor (RT12).
The indoor fan maintains the actual speed of the moment. However, it changes to Lo speed when the compressor stops.
Temperature of indoor coil thermistor:RT12
approx. 8°C or above
approx. 6°C to 8°C approx. 3°C to 6°C
approx. 3°C or below
Operation frequency
normal
fixed
lower at the rate of 3Hz/min
lower at the rate of 6Hz/min Compressor is turned OFF for 5 minutes when left temperature
continues for 5 minutes or more.
1. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more················································· Hi Set temperature minus room temperature: Between 1 and 2 degrees····································· Me Set temperature minus room temperature: less than 1 degree················································· Lo
1 deg.
1.7 deg.
2 deg.
4 deg.
Initial temperature difference
Fan speed
Difference between room temperature and set temperature during
(2) Cold air prevention control
1 When the compressor is not operating,
(1) if the temperature of indoor coil thermistor RT12 is 18°C or less, the fan stops. (2) if the temperature of indoor coil thermistor RT12 is more than 18°C, the fan operates at VLo.
2 When the compressor is operating,
(1) if the temperature of RT12 is 22°C or more, the fan operates at set speed. (2) if the temperature of RT12 is less than 22°C and
(1) if the temperature of room temperature thermistor RT11 is 15°C or less, the fan stops. (2) if the temperature of room temperature thermistor RT11 is more than 15°C, the fan operates at VLo.
NOTE : At initial and after defrosting, when the RT12 is from 18: to 22:, Cold Air Prevention control works.
(3) Warm air control.
When the following any condition of 1(a. ~ d.) and the condition of 2 are satisfied at the same time, warm air control works.
1 a.) when the operation mode has been changed to HEAT mode
b.) when cold air prevention has been released c.) when defrosting has been finished d.) when the compressor starts in HEAT mode
2 When the temperature of indoor coil thermistor RT12 is less than 37°C. When warm air control works, the fan speed changes as follows to blow out warm air gradually.
Gradation of fan speed in initial
The upper limit of the fan speed in MANUAL is the set speed. The upper limit of the fan speed in AUTO is the speed decided by indoor fan speed control.(Refer to 8-4.1.(1).) When the temperature of RT12 has been 37°C or more, or when the set speed has been changed, this control is released and the fan speed is the set speed.
(4) Flow soft control
When the thermostat (compressor) is off, the indoor fan operates as follows.
Released
Cold Air Prevention
18:RT12 22:
Fan speed Set speed
VLo or stop
<Time condition>
<Indoor fan speed>
less than 2 minutes Lo 2 minutes to 4 minutes Me more than 4 minutes Hi
NOTE : When the thermostat(compressor) turns on, the fan will operate
at set speed. But until cold air prevention and warm air control is released, the fan speed follow them.
Compressor
OFF
ON
Fan VLo
Set speed
Page 27
27
2. High pressure protection
In HEAT mode and manually-operated HEAT mode, the indoor coil thermistor detects the temperature at the indoor heat
exchanger and controls the compressor rotational frequency to prevent the condensing pressure from increasing
excessively.
3. Overload starting
When the room temperature thermistor reads 18°C or above, the compressor runs with its maximum frequency regulated for
3 minutes after the start-up.
4. Defrosting in HEAT mode
• conditions to start defrosting:
a) The defrost thermistor attached to the outdoor heat exchanger read -3°C or below.
b) The cumulative operation time of the compressor has reached any of the set values: 30, 40, 45, 55, 65, 75, 85, 95, 105,
115 minutes.
c) More than 5 minutes have passed since the start-up of the compressor.
When the above three conditions, a), b), and c), are satisfied, the defrosting starts.
wSet value of compressor operation time(hereinafter referred to as defrost interval)
The first defrost interval is 40 minutes long, and the second 45 minutes long.The third and subsequent intervals are set to be longer, and less frequent, depending on defrosting time. The third and subsequent defrost intervals follow any of the three patterns …5 or 10 minutes longer, the same, or 5 or 10 minutes shorter compared with the previous defrost interval … with the longest 115 minutes and the shortest 30 minutes.
• Conditions to end defrosting Defrosting is released when any of the following condition is satisfied: a) The defrost thermistor reads 13°C or above. b) Defrosting time has exceeded 10 minutes. c) Some other mode than HEAT mode is set during defrosting.
Time chart of defrost in HEAT mode (reverse type)
normal
indoor fan
Compressor normal
outdoor fan moter
Reversing valve
ON ON
OFF
OFF
100Hz
horizontal
normal
vertical vanes
normal
normal
normal
VLo (temperature of indoor coil thermistor > 18:)
30
second
30
second
30
second1second
5 second
1
second
1
second
STOP
5
second
MAX Hz
MAX Hz
<outdoor unit>
Page 28
28
9-2. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.Operation indicator lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
Indoor fan continues to operate regardless of thermostat’s OFF-ONCoil frost prevention is same as COOL mode of “I FEEL CONTROL”
9-3. DRY ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
Operation indicator lamp of the indoor unit turns on with a beep
tone. (2) Select DRY mode with the OPERATION SELECT button. (3) The microprocessor reads the room temperature and determines
the set temperature. Set temperature is as shown on the right
chart.
DRY operation will not function when the room temperature is
13°C or below. (4) When DRY operation functions the fan speed is lower than cool
operation expect at (fan speed) Lo notch.
9-4. HEAT ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
Operation indicator lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and initial room temperature in dry mode
:
9-5. FAN MOTOR CONTROL
1. Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo) the microprocessor controls SR11 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
2. Fan motor lock-up protection When the rotational frequency feedback signal is not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the operation indicator flashes to show the fan motor abnormality. (See page 45.)
Page 29
29
5. Dew prevention During COOL or DRY operation with the vane angle at Angle 4 or 5 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
6 SWING MODE ( )
By pressing the SWING button,vane swings horizontally. The remote controller displays “ ”. The swing operation will be cancelled if any of the following .operations are performed.
The unit is turned off.
The vertical vanes will return to their positions just before the swing operation was started.
The operation mode(AUTO, COOL, DRY or HEAT)is changed.
The vertical vanes will return to their positions just before the swing operation was started.
The “ ” button is pressed.
The vertical vanes stop at the position when the button is pressed.
3. Positioning The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
The positioning is decided as follows. (a) When the operate button is pushed. (POWER ON) (b) When the stop button is pushed. (POWER OFF) (c) When the vane control change AUTO to MANUAL. (d) When the SWING is finished. (e) When the test run starts. (f) When the power supply is ON.
4. VANE AUTO ( ) mode In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
(1) In COOL and DRY operation
(2) In HEAT operation
Vane angle is fixed to Angle 1.
Vane angle is fixed to Angle 4.
9-6. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL ( ) button.
Page 30
30
COOL and DRY
HEAT
About 100-
About 150-
Horizontal AIR FLOW blowing range
7 Horizontal AIR FLOW ( )
The auto vane angle changes as follows by pressing the VANE CONTROL( ) button.
Press the “ ” button.
The vertical vanes begin moving.
When the vanes move to the desired position, press the “ ” button again.
The vanes stop moving.
NOTE
If the “ ” button is not pressed again within 30 seconds in COOL or DRY mode or within 1 minute in HEAT mode after the vanes start moving, the vanes will automatically return to their original positions.
8. Cold air prevention in HEAT mode. When either of the following conditions occurs in HEAT mode, the auto vane angle changes to Angle 1 automatically to prevent cold air blowing on users.
Compressor is not operating.Defrosting is performed.Indoor coil thermistor RT12 reads 24: or below.Indoor coil temperature is raising from 24°C or below, but it does not exceed 28:.
(8) ECONO COOL ( ) operation
When the ECONO COOL button is pressed in MANUAL COOL mode, the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12). Also SET TEMPERATURE is automatically set 2°C higher than that in MANUAL COOL mode.
•SWING operation In swing operation of ECONO COOL operation air flow is initially blew out upward(levelly). According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided.Then when the downward blow has been finished,next upward blow time is decided. The air conditioner repeats the swing operation in various cycle as follows. However, for initial 10 min. the swing operation is performed in table G~H for quick cooling(but G : RT 12 is 24: or less). Also, after 10 min. when the difference of set temperature and room temperature is more than 2 degrees, the swing operation is performed in table D~H for more cooling(but D: RT12 is 20: or less).
Temperature of indoor
coil thermistor RT12
more than 24°C
5
2
Downward blow time
(sec.)
22°C to 24°C
21°C to 22°C
20°C to 21°C
18°C to 20°C
17°C to 18°C
15°C to 17°C
15°C or less
5
8
11
14
17
20
23
Upward(level) blow time
(sec.)
20
17
14
11
8
2
23
A
H
G
F
E
D
C
B
•ECONOmical operation (SET TEMPERATURE)
When this operation is selected in MANUAL COOL mode, SET TEMPERATURE is automatically set 2°C higher than that in MANUAL COOL mode. By above SWING operation temperature that you feel can decrease by 2°C. So keeping comfort, energy can be saved.
Page 31
31
PROGRAM TIMER
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
The OFF timer and ON timer can be used in combination.
” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
2. Cancel
TIMER setting can be cancelled with the ON or OFF TIMER buttons. (“ ” or “ ”) To cancel the ON timer, press the “ ” button.
To cancel the OFF timer, press the “ ” button. TIMER is cancelled and the display of set time disappears.
9-7. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON or OFF TIMER buttons to select the operation.
” button... AUTO START operation (ON timer) “ ” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “ ” or “ ” mark is flashing. These marks disappear in 1 minute. After setting the ON timer, check that Operation indicator lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
A power failure occurs.
The circuit breaker functions.
Indoor coil temperature
Angle 1
24
:
Normal
28:
Page 32
32
9-8. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY ON/OFF button on the front of the indoor unit. The unit will start and the OPERATION INDICATOR will light. The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. After 30 minutes of test run operation the system shifts to EMERGENCY COOL, HEAT MODE with a set temperature of 24°C. The fan shifts to Me speed. This operation continues until the EMERGENCY OPERATION switch button is pressed or a button on the remote controller is pressed, then normal operation will start. The coil frost prevention circuit operates in this mode, and defrosting operates too. In the test run or emergency operation, the horizontal vane operates in AUTO mode with a set temperature of 24°C. Defrosting of outdoor heat exchanger works in EMERGENCY HEAT MODE. NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
Light up Blinking light
Press once < Cooling >
Press again < Heating >
Press once again < Stop >
EMERGENCY OPERATION switch
Blinking lamp shows the room temperature
Lighting lamp shows the set temperature
9-9. POWER MONITOR LAMP
Color of the lamp
RED
ORANGE
GREEN
Operating condition The unit operates at high power. The unit operates at middle power. The unit operates with energy-saving.
The color of POWER MONITOR lamp is GREEN in any of the following cases.
• When ON-timer is standby
• In DRY operation
• In EMERGENCY operation
• When defrosting of the outdoor unit is being done in HEAT operation
Page 33
33
9-10. Operational frequency control of outdoor unit
1. Outline The operational frequency is decided by following the procedures below:
First, set the target operational frequency based on the difference between the room temperature and the set temperature. Second, regulate the target operational frequency by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.
(1) maximum/ minimum frequency in each operation mode.
w The maximum frequency in COOL mode is limited according to operation hours, as shown below.
(2) Frequency change speed
During increasing frequency
During decreasing frequency
Operational frequency MUZ-A09RV- E1 MUZ-A12RV- E1
10Hz to 14Hz 0.5 sec./Hz 15Hz to 79Hz 5 sec./Hz
80Hz to 150Hz 0.5 sec./Hz
Operational frequency MUZ-A09RV- E1 MUZ-A12RV- E1
10Hz to 42Hz 1 sec./Hz
43Hz to 150Hz 0.5 sec./Hz
Minimum
frequency
15 15
Model
MSZ-A09RV MSZ-A12RV
COOL (indoor fan speed : Hi)
Rating
frequency
53 82
Maximum frequency
80 88
Minimum
frequency
16 16
HEAT
Rating
frequency
67 98
Maximum frequency
98
115
DRY
22/27 22/27
1Hr
Time
Maximum frequency
frequency
Rating or under-rating frequency
Page 34
34
9-11 .Electronic expansion valve control (LEV control)
(1)Outline of LEV control
The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each operational frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temperature (Shell temperature) of the compressor, developing the unit’s performance.
(2)Specification of LEV control
Control range from min. 33 pulse to max. 500 pulse. Actuating speed LEV opens 40 pulse/sec. and close 90 pulse/sec. Opening degree adjustment LEV opening degree is always adjusted in opening direction.
(When reducing the opening degree, LEV is once over­closed, and then adjusted to the proper degree by opening.
Unit OFF LEV remains at max. opening degree (reaches max. opening
degree approx. 15 minutes after compressor stops)
Remote controller ON LEV is positioned. (first full-closed at zero pulse and then
positioned.)
During 2 to 15 minutes after compressor starts Opening degree is adjusted according to standard opening
degree. (Standard opening degree is set for each rotational frequency of compressor)
More than 15 minutes have passed since compressor
start-up
LEV opening degree is corrected to get target discharge temperature of compressor. (For discharge temperature lower than target temperature, LEV is corrected in closing direction.) (For discharge temperature higher than target temperature, LEV is corrected in opening direction.) wIt may take more than 30 minutes to reach target temperature, depending on operating conditions.
Thermostat OFF LEV starts to open every 3 pulse/sec.
from the same opening degree as that when the Unit turned IFF (and becomes full-opened after approx. 15 minutes.)
Thermostat ON LEV is controlled in the same way as that is after the
compressor has started up.
Defrosting in HEAT mode LEV is adjusted to open 350 pulse.
general operation
standard
specification
Page 35
35
In COOL mode, the two indoor coil thermistor (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger, And when teperature difference have developed, the indoor coil thermistors adjust LEV opening to get approxiimate 10 degrees lower temperature than the target temperature in the table above, thus diminishing super heat.
(3) Time chart
OFF Time
Time
ON
The operational frequency of the compressor
Commanded to open
Standard opening degree
opening degree is corrected according to discharge temperature
positioning
air conditioner ON
Air conditioner OFF (thirmostat off)
LEV opening degree
15 min.
(4) Control data
06 05 04 03 02
01
LEV opening degree
A(target discharge temperature)
B
C
D
E
F
30 50 70
The operational frequency of the compressor
90 110 130
(Hz)
A
58/49B60/58C68/67D70/70E72/72F72/72
(a) Reference value of target discharge temperature
(Cooling :/Heating :)
01
110/8002150/10003200/12004200/13005200/13006200/130
(b) Reference value of LEV standard degreeperature
(COOL/HEAT pulse)
Page 36
36
9-13. Reversing valve control
COOL&DRY mode
. . . . . . . . .
ON(voltage applied)
The Reversing valve turns ON as soon as thermostat turns ON. The Reversing valve turns OFF 15 minutes after the thermostat turns OFF.
HEAT mode
. . . . . . . . . . . . . . .
OFF(voltage not applied)
During normal HEAT operation the Reversing valve is OFF.
w The Reversing valve does not turn ON before the compressor starts up.
ON
OFF
ON
OFF
Outdoor fan
Compressor
5.0 sec. 15 sec.
ON OFF
Compressor
Outdoor fan
Reversing valve
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-12.Outdoor fan motor control
The AC fan motor turns ON/OFF, interlocking with the compressor. [ON] The AC fan motor turns on 5.0 seconds before the compressor starts up. [OFF] The AC fan motor turns off 15 seconds after the compressor stops running.
Page 37
37
9-14. Indoor fan motor control
The detected rotational frequency of the fan motor is feed backed to the microprocessor and then the microprocessor works to keep the rotational frequency at a fixed value against load fluctuation.
(1) Circuit block diagram
(2) Control system
The microprocessor adjusts rotational frequency. If feed backed pulses are not detected for 12 seconds, fan motor becomes abnormal and indoor operation indicator lamp flashes to show abnormality.
Controlled voltage is applied to AC fan motor.
The microprocessor outputs pulse every 100Hz (every 50Hz in half wave). (Fan speed varies according to the time span between a Zero-cross point on the commercial wave and a pulse out put point.)
The microprocessor drives SSR on relay p.c. board.
The microprocessor detects rotational frequency of AC fan motor, using Hall element in AC fan motor.
<Input side>
microprocessor
controller board
220~240V AC
SSR output
rotational frequency
every 100Hz pulse output
AC motor
actuator (SSR)
AC motor
rotational frequency sensor part
output input
<Output side>
Page 38
38
1. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the indoor unit number.
How to modify the remote controller P.C. board
The P.C. board has the print “J1” and “J2”. Jumper wires are mounted to each “J1” and “J2”.Cut “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, push the RESET. button near the MIN-button on the remote controller.
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When
the power supply is turned on and indoor unit receives the first signals from the remote controller, the remote controller number is designated as the indoor unit number. Therefore at and after the second time indoor unit accepts the remote controller of the initial setting number. At setting - error, turn the power supply off to cancel the individual operation and then turn the power supply on to restart the setting.
Remove batteries before modification. The board has a print as shown below;
NOTE : Fore remodeling, take out the batteries at first.
After finish remodeling, put back the batteries then push the RESET-button.
No.1 unit No.2 unit No.3 unit No.4 unit
1 unit operation No modification
2 unit operation
Same as at left
Cut J1
3 unit operation Same as at left Same as at left
Cut J2
4 unit operation
Same as at left Same as at left Same as at left
Cut both J1 and J2
Table1.
2. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPS on and the electronic control P.C. board. The time will be shortened as follows. 3-minute delay : 3-minute 3-second. AUTO START : 1 hour 1-minutes AUTO STOP : 1 hour 1-minutes
Short the connector during the timer mode.
}
10 SERVICE FUNCTIONS
Page 39
39
3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment the power has restored after power failure, then, the unit will restart automatically. If the unit is operated in “I FEEL CONTROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided by the initial room temperature at (re)start.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Remove the indoor electronic control P.C. board and the display P.C.board.(See page 57,58.) 3Pull the indoor electronic control P.C. board forward and cut the RESISTOR JR07 on it.
C11
52C
CN201
CN112
CN121SW
CN111
IC101
CN211
CN151
JR07
Operation
1If the main power (220-240V AC) has been cut, the operation settings remain. 2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
Page 40
40
TROUBLESHOOTING11
11-1 Cautions on troubleshooting
1. Before troubleshooting, check the followings:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the followings during servicing.
1) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the P.C. boards.
2) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
3) When connecting or disconnecting the connectors, hold the housing of the connector, DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the POWER LAMP on the indoor unit is flashing to indicate an abnormality. To make sure, check the abnormality indication for 2 or 3 times before starting service work.
2) If the P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart and the check table on page 38.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote controller normally, replace the batteries in the following order. This remote controller has the reset button. After refilling new batteries, press the reset button with tip end of ball point pen or the like, and then use the remote controller.
Housing point
RESET BUTTON
Lead wiring
3. Caution for the outdoor unit repair service
1) Do not load on the P.C.board cover.
2) Since every P.C.board circuit links directly with power supply 220~240V AC, do not short the P.C.board and metal section on servicing. Also if touch the parts on the P.C.board, it may cause an electric shock.
3) When closing the P.C.board cover, prevent a foreign matter or dust from coming inside the P.C.board.
Be careful at voltage measurement
Cover
Relay P.C. board
Electronic control P.C. board
MSZ-A09RV ­MSZ-A12RV -
E1
E1
Page 41
41
11-2 Troubleshooting procedure
The following procedure facilitates identifying defective points. The abnormalities in
can be located in the Troubleshooting check table on page 42~43.
Indoor unit dose not respond to remote controller.
Refer to G ‘Check of indoor electronic control P.C. board’ on page 49.
Power monitor lamp flashes.
Indoor unit does not respond to remote controller. In addition, operation Power monitor lamp dose not light up, with emergency operation switch ON.
Indoor fan motor dose not run.
Refer to F ‘Check of indoor fan motor’ on
page 49.
Cause:indoor/outdoor unit
·
Mis-wiring
·
Serial signal error
Cause: in Indoor unit
·
Indoor coil thermistor abnormality
·
Room temperature thermistor abnormality
·
Auxiliary indoor coil thermistor abnormality
Cause: in outdoor unit
·
Outdoor power system abnormality
·
Outdoor unit temperature thermistor abnormality
·Outdoor converter power system
7 flashes
2.5 seconds OFF
Cause: in outdoor unit
·
Outdoor control system error
wIn case of serial signal
error, the mis-wiring indication will appear by turning the power off and then turning it back on.
5 flashes
2.5 seconds OFF 6 flashes
2.5 seconds OFF 12 flashes
2.5seconds OFF
Operation start
1 flash
2.5 seconds or
0.5 seconds OFF
Refer H ‘Check of indoor electronic P.C. board’ on page 50.
2 flashes
2.5 seconds OFF
Refer to ‘Checking serial signal error’ on page 44.
Check indoor/outdoor Mis-wiring on page 44.
Indoor coil thermistor Room temperature thermistor Auxiliary indoor coil thermistor
Refer to I ‘Check of outdoor thermistors’ on
Inverter/Compressor
Refer to A ~ E
‘Compressor’ on page 47 and 48.
Refer to A ~ E ‘Transistior module’ on page 47 and 48.
Refer to L 'Check of power supply' on page 52.
Outdoor electronic control P.C. board.
Refer to J ‘Check
of Reversing valve coil’ on page 51.
Refer to K ‘Check of outdoor fan motor’ on page 51.
Outdoor electronic control P.C. board.
3 flashes
2.5 seconds OFF
Refer to N ‘Check of electronic control P.C. board in the outdoor unit’ on page
Refer to P ‘Check of linear expansion valve (LEV)’ on page 53.
Page 42
42
1. Troubleshooting check table (Indoor unit troubleshooting check table) MSZ-A09RV ­MSZ-A12RV -
E1
E1
POWER
flash
· Flashing of the operation indicator lamp (on the left-hand side) indicates possible abnormalities.
· The operation indicator lamp (on the left-hand side) is lighting during normal operation.
No.
1
w2
w3
5
6
7
Symptom
Operation indicator lamp
Abnormal point Detection method Checkpoint
Outdoor unit does not operate
repeated flashes every 0.5 seconds
One flash
2.5 seconds OFF
2 flashes
2.5 seconds OFF
5 flashes
2.5 seconds OFF
Mis-Wiring
Serial signal
Outdoor power system
6 flashes
2.5 seconds OFF
Outdoor thermistors
7 flashes
2.5 seconds OFF
Outdoor control system
Indoor coil thermistor Auxiliary indoor coil thermistor Room temperature thermistor
When indoor electronic control p.c. board does not receive serial signals for 4 to 5 seconds with OPERATION/STOP button of remote controller ON and 52C relay ON for the first time, NOTE: In case of serial signal error, mis-wiring
indication will appear by turning power off and then turning it back on.
When indoor electronic control p.c. board does not receive serial signals from outdoor unit for 4 to 5 seconds,
Indoor electronic control p.c. board constantly detects resistance every 8 seconds. When thermistor shorts or opens.
When compressor has stopped due to over current protection or start-up failure protection 3 times in a row within 1 min. after start-up.
<Thermistor short> Thermistors are abnormal when they short after compressor start-up. <Thermistor open> Thermistors are abnormal when they open after compressor start-up. However, discharge temperature thermistor is abnormal when open circuit is detected more than 10 min. after compressor start-up.
When nonvolatile memory data cannot be read properly on outdoor control P.C. board, outdoor unit stops and restarts 3 minutes later,
· Shortage of refrigerant
· Outdoor electronic control p.c. board
Refer to I "Check
of outdoor thermistors" on page 50.
Refer to the characteristics of indoor coil thermistor, auxiliary indoor coil thermistor, and room temperature. thermistor on page
Refer to "How to check inverter/compressor" on page 47.
Replace outdoor electronic control P.C. board.
Refer to 'Checking serial signal error' on page 44.
w4
3 flashes
2.5 seconds OFF
Indoor fan motor.
When rotational frequency feedback signal is not emit during 12-second indoor fan operation.
Refer to F "Check of indoor fan motor" on page 49.
8
12 flashes
2.5 seconds OFF
Converter power system
When the converter protective suspension within 1 minute after start-up of the converter is operated 5 times successively. Also bus-bar voltage malfunction (140V or less or 400V or more) within 1 minute after start-up of the converter has happened 5 times successively.
Refer to I "Check of inverter P.C.board" on page 50.
wWhen the indoor unit has started operation and the above detection method has detected an abnormality (the first detection
after the power ON), the electronic control P.C. board turns OFF the 52C and the indoor fan motor with the operation indicator lamp lighting.
When the 52C and the indoor fan motor are turned ON again 3 minutes later and the same abnormality is detected (a
second detection of the above abnormality after the power ON), the control P.C. board turns OFF the 52C and the indoor fan motor with the operation indicator lamp flashing.
However, the first detection is cleared in case the power is turned OFF after the first detection.
Page 43
43
(Outdoor LED indication table)
MUZ-A09RV ­MUZ-A12RV -
NOTE 1. The location of LED is illustrated at the right figure.
2. LED lights up during normal operation.
E1
E1
Abnormal point
When the converter protective suspension within 1 minute after start-up of the converter is operated 5 times successively. Also bus-bat voltage malfunction (140V or less or 400V or more) within 1 minute after- start-up of the converter has happened 5 times successively.
When compressor has stopped by over current protection or start-up failure protection within 1 min. after compressor start­up 3 times in a row, compressor stops and then restarts 3 min. later.
When discharge temperature thermistor or fin temperature thermistor shorts or opens during compressor running, compressor stops and restarts 3 min. later.
When nonvolatile memory date cannot be read properly, compressor stops and restarts 3 min. later.
When 19A current flows into power transistor, compressor stops and restarts 3 min. later,
When discharge temperature thermistor exceeds 116:, compressor stops and restarts 3 min. later. (Compressor restarts when discharge temperature thermistor reads 100: or below.)
When temperature at heat sink exceeds 88: or outdoor electronic control P.C. board exceeds 67: , compressor stops and restarts 3 min. later.
When indoor coil thermistor exceeds 75:, compressor stops and restarts 3 min. later.
When current from power outlet exceeds 10. A, compressor frequency lowers.
When indoor coil thermistor exceeds 55: in HEAT mode, compressor frequency lowers.
When indoor coil thermistor reads 8: or below in COOL mode, compressor frequency lowers.
When discharge temperature thermistor exceeds 111:, compressor frequency lowers.
When defrost thermistor short or open. w In this case, compressor continues running.
When the converter suspends for protection
•Response abnormal suspension
•Bus-bar voltage abnormal suspension
•Converter over current/over voltage protective suspension
•Converter current detection abnormal suspension
•Converter zero cross abnormal suspension
When discharge temperature has been 50: or below for 20 min.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Symptom
LED indication
Detection method Checkpoint
Outdoor unit does not operate
'Outdoor unit stops and restarts 3 min. later' is repeated
Outdoor unit operates (at low frequency)
Outdoor unit operates
One flash every
2.5 seconds
NOTE: For abnormality location, refer to 'Indoor troubleshooting check table' on page 34.
2 flashes
2.5 seconds OFF 3 flashes
2.5 seconds OFF
4 flashes
2.5 seconds OFF
5 flashes
2.5 seconds OFF
one flash 2-5 seconds OFF
3 flash 2-5 seconds OFF
4 flashes 2-5 seconds OFF
5 flashes 2-5 seconds OFF
8 flashes 2-5 seconds OFF
7 flashes 2-5 seconds OFF
Converter power system
Outdoor power system
Outdoor thermistors
Outdoor control system
Over current protection
Discharge temperature overheat protection
Fin temperature thermistor overheat protection
High pressure protection
Frequency drop by current protection
Frequency drop by high pressure protection
Frequency drop by defrosting in COOL mode
Frequency drop by, discharge temperature protection.
Outdoor thermistors. Defrost thermistor.
Converter protection.
low discharge temperature protection
· Refer to N 'Check of electronic control P.C.board' on page 52.
· Refer to 'Checking inverter/ compressor on page 47.
· Refer to I 'Check of outdoor thermistors' on page 50.
Refer to A-E in 'How to check inverter/ compressor' on page 47~ 48.
Replace outdoor electronic control P.C. board.
· Check refrigerant circuit and refrigerant amount.
· Refer to I'Check of outdoor thermistor' on page 50.
· Check around outdoor unit.
· Check outdoor unit air passage.
· Check refrigerant circuit and refrigerant amount.
· Check stop valve.
The unit is normal, but check the following.
· Check if indoor filters are clogged
· Check if refrigerant is short.
· Check if indoor/outdoor unit air outlets are short cycled.
Refer to I 'Check of outdoor thermistors' on page 50.
· Refer to N 'Check of electronic
control P.C.board' on page 52.
· Refer to P 'Check of LEV' on page 53.
· Check refrigerant circuit and refrigerant amount.
<Outdoor electronic control P.C. board>
When switching from forced drive to normal drive (synchronised operation by a position detectable signal) failed 5 times successively at compressor start-up Restart-up after suspension when miss start-up or abnormal position detecting within 10 seconds after start-up.
7 flashes
2.5 seconds OFF
Mis-start up protection
When the position detectable signal is not input during normal starting up (synchronised operation by a position detectable signal) after 10 seconds of compressor operation
8 flashes
2.5 seconds OFF
Position detection protection
Check and replace as follows. 1 Check the compressor connecting lead wire between connector and transistor module. 2 Check inverter P.C.board (Position detecting circuit transistor module, Micro computer, etc) 3 Compressor replacement Refer to A~E Inverter Compressor simple check method (page 47~48)
When disconnecting the compressor connector, going to inverter check mode.
9 flashes 2-5 seconds OFF
Inverter check mode
· Refer to A~E Inverter Compressor simple check method (Page 47~48)
15
16
17
LED
IPM
PFC
flash
Refer to I 'Check of outdoor thermistors' on page 50.
Page 44
44
2. Checking mis-wiring and serial signal error. MSZ-A09RV ­MSZ-A12RV -
Outdoor unit does not operate. When the operation indicator lamp (on the left-hand side) flashes on and off continuously or only once.
E1
E1
1. Turn OFF power supply.
2. Turn ON power supply.
3. Press the EMERGENCY OPERATION switch.
Is the self-check function of indoor unit indicated when relay 52C turns ON 3min. later? wShort circuit of JPS (one-hour short circuit jumber cable) and JPG (GND
resistance) enables self-check function to be indicated within 3 min.
Is there indoor-outdoor mis-wiring, poor contact, or disconnection?
Is there approx. 220-240V AC between outdoor terminal block 2 and 1 ?
Is mis-wiring or serial signal error indicated when relay 52C turns ON 3 min. later?
Is there 370V DC between both ends of smoothing capacitor(C62) on the electronic control P.C. board?
Replace in-out connecting wire.
Does Power monitor lamp (on the right-hand side) flash on and off when OPERATE/STOP button on remote controller is pressed?
w1 If there is any error in
serial signal system, the mis-wiring indication will appear by turning the power off and then turning it back
w2 Mis-wiring may damage the electronic
control P.C. board during the operation in the left. Be sure to confirm the wiring is correct before the operation starts.
w3 Replace indoor
electronic control P.C. board.
w3 Be sure to release the
failure-mode recall function after checking.
w The serial signal indication on the Power
monitor lamp (right side) facilitates checking abnormality, based on the failure-mode
Mis-wiring indication
No
No
Yes
Correct wiring
Replace outdoor electronic control P.C. board.
· Main circuit
· Reactor
· Noise filter P.C. board
· Connection of connector
Yes
A
B
Turn off power supply and confirm that indoor-outdoor wiring is correct. Short-circuit indoor terminal block N and 3. While pressing OPERATE-STOP button on remote controller, press RESET button. (The above procedure allows Power monitor lamp to indicate the failure-mode) w2
Open-circuit indoor terminal block N and 3, Check if there is amplitude of 5 to 10VDC between outdoor terminal block N and 3 (for confirmation of serial signal) and if there is 220-240V AC between 2 and N
1. Unplug the power cord.
2. Disconnect the connector between compressor and transistor module.
3.Plug the power cord.
4. Press EMERGENCY OPERATION switch.
2.5 seconds OFFON ON
Serial signal error indication
defective
Yes
No
Yes
Yes
No
Yes
No
(light up or OFF)
· Turn off inverter­controlled lighting equipment.
· Plug the power cord.
· Press EMERGENCY OPERATION switch.
A
B
· Keep the unit away from fluorescent light.
· Attach a filter to light­intercepting part.
Green Sign
flash
21
22 24
30
29
28
27
26
25
23
Page 45
45
Checking method and criterionPart name
3. Trouble shooting procedure of main parts (Simple check method of main parts)
MSZ-A09RV - MUZ-A09RV ­MSZ-A12RV - MUZ-A12RV -
E1E1
E1E1
Room temperature
Indoor coil thermistor (main-auxiliary)
Defrost thermistor
Discharge temprature thermistor
Fin temperature thermistor
Compressor
Indoor fan motor
Disconnect the connector and measure the resistance with a tester. (Part temperature : 10:~30:)
normal abnormal
8k"~20K" Open or short circuit
Disconnect the connector and measure the resistance with a tester. (Part temperature : -10:~40:)
normal abnormal
5k"~55K" Open or short circuit
Disconnect the connector and measure the resistance with a tester. Before measurement, hold the termistor with your hands to warm it up. (Part temperature : 20:~40:)
normal abnormal
100k"~250K" Open or short circuit
Disconnect the connector and measure the resistance with a tester. (Part temperature : -10:~80:)
normal abnormal
5k"~30K" Open or short circuit
Disconnect the connector and measure the resistance between the terminals with a tester. (Winding temperature : -10:~40:)
Measure the resistance between the terminals with a tester. (Winding temperature : 10:~30:)
termina
(CN211)
normaL abnormal
WHT-BLK 280"~304"
BLK-RED 311"~338"
Open or short circuit
23
W
U
V
1
WHT
Compressor motor
RED BLK
2
3
1
WHT RED
BLK
normal abnormal
0.82"~1.01" Open or short circuit
Page 46
46
Checking method and criterionPart name
Outdoor fan motor
Vertical vane motor Horizontal vane motor
Reversing valve
Linear expansion valve (LEV)
Measure the resistance between the terminals with a tester. (Winding temperature : -10:~40:)
Measure the resistance between the RED terminal and the other ones. (Winding temperature : 20:~30:)
normal abnormal
Measure the resistance between the terminals with a tester. (Part temperature : -10:~40:)
Measure the resistance with a tester. (Part temperature : -10:~40:)
termina
(CN724)
normall abnormal
WHT-RED RED-ORN YLW-BRN
42~52' Open or short circuit
BRN-BLU
terminal normal abnormal
WHT-BLK 173.7'~212.6'
BLK-RED 277.8'~339.9' Open or short circuit YLW-BLK 11.4'~14.1'
approx. 300' in each phase
open or short circuit.
normal abnormal
882'~1079'
open or short circuit.
WHT
RED
BLK
P
YLW
ORN
LEV
WHT6
RED1
ORG4
YLW5
BRN2
BLU3
ORN
BLUYLW
RED
PNK
ROTOR
Page 47
47
(How to check inverter/compressor)
Start
Check voltage between terminals.
Are voltages
balanced?
Check compressor.
Disconnect the connector between compressor and IPM.
Check resistance of IPM.
See C 'Check of compressor.'
No
See A 'Check of open phase.'
See B 'Check of transistor module.'
Is resistance infinite?
Yes
Outdoor electronic control P.C. board is defective
IPM is defective.
Replace outdoor electronic control P.C. board and IPM.
No (0~several
")
Check of open phase
A
Be sure to use the analog voltmeter for measurement
With the connector between compressor and transistor module
disconnected, activate the inverter and measure the balance of voltage between terminals.
Output voltage : 120V
<< Operation method>> Start heating opration by pressing the Emergency operation switch on the indoor unit. (test-run mode) <<Measurement point>>
at 3 points BLK-WHT BLK-RED WHT-RED
NOTE Measure AC voltage, at 3 points more than one minute ofter
the outdoor fan motor starts running.
Check of IPM
B
Disconnect the connector between compressor and IPM, and measure resistance between terminals on the IPM.
<<Measurement point>> at 6 points BLK-WHT, WHT-BLK BLK-RED, RED-BLK WHT-RED, RED-WHT at 6 points <<Judgment>> Infinite ["]···········normal 0~dozens of ······abnormal (short)
w Measure resistance between the lead wires at 3 points
ohmmeter indication
normal (infinite)
abnormal (0~dozens of ")
X1
"
X1
"
2.5 seconds OFF
9 flashes
<Outdoor electronic control P.C. board>
LED
IPM
PFC
Note1.Output voltage changes depending power supply
voltage. (Max. i10%)
2. Measure by analogue tester.
3. During the measurement, LED in the outdoor electronic control P.C. board flashes 9 times.
flash
Yes
Page 48
48
Check of compressor winding
D
Check of compressor
C
Disconnect the connector between compressor and IPM, and measure resistance between the compressor terminals.
<<Measurement point>>
at 3 points BLK-WHT BLK-RED WHT-RED
<<Judgment>>
0.82 to 1.01" at -10: to 40: of part temperature. 0["] ···············abnormal [short] Infinite["] ·······abnormal [open] NOTE 1.Be sure to zero the ohmmeter before measurement.
2.Winding resistance for each phase is 0.45" at 20:.
Check of compressor operation time
E
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent.
<<Operation method>>
Start heating or cooling operation by pressing the Emergency operation switch on the indoor unit. (Test-run mode)
<<Measurement>> Measure the time from the start of outdoor fan running till the
stop of the inverter due to overcurrent.
<<Judgment>>
For reference 0~10 seconds·····················abnormal (short) 10~60 seconds···················abnormal (compressor lock-out) 60 seconds~5 minutes·······abnormal (refrigerant circuit defect) more than 5 minutes···········normal
w Measure resistace between the lead wires at 3 points.
Outdoor fan starts Abnormal (Compressor short circuit or layer short)
Abnormal (Compressor lock-out)
Abnormal (refrigerant circuit defect, etc.)
Normal
0 sec.
10 sec.
60 sec.
5 min.
normal (1~several ")
abnormal (0" ····· short)
abnormal (infinite····· open)
Ohmmeter indication
Check resistance of compressor.
Check compressor operation time
Normal
Compressor short or open Replace compressor
See D 'Check of compressor winding'
Is resistance
1~several " at -10:
~ 40: of winding
temperature?
Does compressor run
continuously?
See E ' Check of compressor operation time,'
No
Compressor layer short , lock-out or refrigerant circuit defective.
Replace compressor. Check refrigerant circuit.
No
Yes
X1
"
X1
"
X1
"
23
W
U
V
1
WHT
Compressor motor
RED BLK
Yes
Page 49
49
Re-install the unit away from the lights.
Attach a filter to light­intercepting part.
Check of remote controller and indoor electronic control P.C. board.
G
Check of indoor fan motor.
F
Turn off power supply and check connector CN 211 visually.
Are lead wires dis connected?
No
No
Yes
Yes
No
No
Yes
Yes
Normal
Disconnect lead wires from CN 211 on indoor electronic control P.C. board. Measure resistance between lead wire 1 and 3 and then 2 and 3.
Yes
Yes
No
No
(not clear)
No
Yes
(How to check main parts)
Indoor fan does not operate.
Indoor unit operates by pressing the Emergency operation switch, but does not operate with the remote controller.
Is soldered point abnormal?
Lead wires are not properly connectes
Is LCD display on remote controller visible?
Does the unit operate with remote controller?
Is noise heard from the radio?
Is voltage approx. +4V DC?
Are there any fluorescent lights of inverter or radio start type within 1 meter?
Is resistance 0" (short) or " (open) ?
Connector is not properly soldered.
Replace batteries and then press RESET button. See page 32.
Receiver defect
Indoor electronic control P.C. board defect.
Indoor fan motor defect
Indoor electronic control P.C. board defect.
CN211
3 2 1
fan
motor
indoor electronic control P.C. board
Check the model name of remote controller.
Remove batteries and set them back. Check again if indoor unit operates with remote controller.
Tune a radio in to AM and press OPERATE/STOP button on remote controller.
Remote controller defect
Turn on power to indoor unit, and measure voltage between connector LD 101 2 (+) and JPG(-1) on indoor control P.C. board when OPERATE/STOP button on remote controller is pressed.
Yes
No (+5V DC)
Model name and part No. are witten here
back side of remote controller
()
LD101 1 2 3 4 5
1 2 3 4 5
remote controller
Indoor electronic control P.C. board
light-interception ihdication board
Page 50
50
Check of outdoor thermistors
I
Check of indoor electronic P.C. board
H
Measure resistance between. CN 6411 and 2
Measure resistance between. CN 6421 and 2
No
No
Yes
Yes
The unit does not operate with the remote controller. The operation indicator lamp does not light up either, with the Emergency operation switch ON.
The thermistors in the outdoor unit are abnormal.
Thermistor is defective.
Disconnecting connector or inferior connecting
indoor electronic control P.C. board
varistor (NR11)
Indoor electronic control P.C. board
fuse (F11)
1 3
N 2 3
thermal fuse connector
Disconnect the connectors CN 641 and CN 642 from the outdoor electronic control P.C. board. (Check the characteristics of each thermistor.)
1 Connect CN 641 and
CN 642.
2 Disconnect the
connector between compressor and IPM.
(Defrost thermistor)
Measure resistance between. CN 6413 and 4
Turn on power to indoor unit and press Emergency operation switch
Discharge temperature thermistor
()
Fin temperature thermistor
()
As per the characteristics on page 55?
As per the characteristics on page 55?
Does the unit operate 10 minutes or more?
No
Yes
Thermal
block
Is LED in the electronic control P.C. board flashing 5 minutes?
Inferior
electronic control
P.C. board
No
Yes
Check both “parts side” and “pattern side” of indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse(F11) blown?
Be sure to check both fuse and varistor in any case.
Replace the fan motor .
Trouble of the indoor electronic control P.C. board.
Is winding resistance of fan motor 0 "?
Is winding resistance of vane motor 0 "?
No
Yes
Replace the vane motor. .
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the ELECTRONIC CONTROL P.C. board and turn on the power supply.
No
No
The unit doesn’t operate with the remote controller. Also, the Power monitor lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
No
Yes
Be sure to check both resistance.
Page 51
51
Check of outdoor fan motor
K
Check of reversing valve coil
J
Disconnect connector between compressor and IPM.
Turn on power to indoor unit, and press Emergency operation switch (Heat).
Heating operation works when cooling is expected.
0utdoor fan motor does not work
· Press Emergency operation switch again to check if Relay 52C works.
· Mis-wiring of in-out connection.
· Indoor electronic control P.C. board defect.
· Outdoor fan motor lead wires defect
· Poor contact of connector CN 771
· Outdoor fan motor defect
Reversing valve coil defect
Relay P.C. board defect
• If the connector CN 913 is not connected or the reversing valve coil is open, the voltage occurs between the terminals even when the control is OFF.
Is there voltage of 220-240V AC between CN 913 1 and 2 on relay P.C. board 3 min. after power?
3 minutes after power­on, is there voltage of 220-240V AC between outdoor terminal block 2 and N?
Is there voltage of approx. 220-240V AC either between 2 and 3 or between 2 and 4 or between 2 and 5 at CN 771?
In-out Connecting Wire
outdoor terminal block TB1
N 2 3
Disconnect connector CN 771 on relay P.C. board. Disconnect connector between compressor and IPM.
Turn power on to indoor unit and press Emergency operation switch.
3 minites after power-on, measure voltage between terminals of CN 771.
1
CN913
Relay P.C. P.C. board
2
Reversing valve
AC 220-240V
Yes
Yes
Yes
No
No
No
CN771
Relay P.C. board
1
23
4
56
fan
motor
In-out Connecting Wire
outdoor terminal block TB1
N 2 3
Cooling operation works when heating is expected.
•First, measure resistance of the reversing valve coil to check if it is defective or not.
• If the connector CN 913 is not connected or the reversing valve coil is open, the voltage occurs between the terminals even when the control is OFF.
Relay P.C. board defect
Is there voltage of 0V between CN 912 1 (+)and 2 (-) on relay P.C. board.
Approx. 1V DC voltage occurs
Yes
Electrinic control P.C.board defect
Disconnect connector between compressor and IPM.
Turn on power to indoor unit, and press Emergency operation switch (Cool).
Is there voltage of 220-240V AC between CN 913 1 and 2 on relay P.C. board 3 min. after power?
Yes
No
Relay P.C. board defect
Is there voltage of 1V DC between CN 912 1 (+)and 2 (-) on relay P.C. board.
No The voltage is 0V
Yes
Electrinic control P.C.board defect
· Reversing valve coil lead wires defect
· Poor contact of connector
· Reversing valve defect
Page 52
52
Check of thermal fuse
M
Check of power supply.
L
Disconnect connector between compressor and IPM. Turn power on to indoor unit and press Emergency operation switch. 3 minutes after power-on, is there voltage of approx. 220-240V AC between outdoor terminal block 2and N?
Unplug the power cord. Replace thermal fuse.
Inverter does not work.
· Press Emergency operation switch again to check if Relay 52C works.
· Mis-wiring of in-out connection or disconnection.
· Indoor electronic control P.C. board defect.
Repair according to the LED indication.
Outdoor electronic control P.C. board defect.
Normal
Normal
Is there approx. 370V DC between both ends of smoothing capacitor (C62) on electronic control P.C. board?
Dose LED light up or flash on outdoor electronic control P.C. board.?
Is resistance ° between connector CN 201 1 on indoor electronic control P.C. board and terminal block N?
Yes
No
No
No
Flash
(How to check power supply and others)
Yes
No
CN201
Indoor electronic control P.C. board.
Check the applicable parts by LED indication
Check of electronic control P.C. board
N
Not become cooling/heating. (Not increase speed of compressor rotation)
Replace electronic control P.C. board
Does the outdoor unit fan operate nomally?
Check the connecting CN911 in the relay P.C. board and CN726 in the electronic control P.C. board.
Turn on power supply to indoor unit, and press Emergency operation switch.
Check LED indication in the electronic control P.C. board.
No
Check the outdoor fan motor (refer to page 46)
Yes
Except for 8 times flashing
8 times flashing
Converter protect suspension
· Main circuit
· Reactor
· Noise filter P.C. board
· Connection of connector
defective
Yes
Dose LED flash on outdoor electronic control P.C. board.?
Yes
Light up
LED
Electronic control P.C. board
C62
(+)
(-)
370V DC
Page 53
53
Replace LEV (coil defect)
Replace LEV
Check of linear expansion valve (LEV)
P
• Press RESET button, while pressing OPERATION SELECT button on remote controller. (All displays on operational display section are ON.) (Refer to right diagram.)
• With remote controller set toward the indoor unit, press OPERATE/STOP button and confirm one beep tone.
• With remote controller set toward the indoor unit, OPERATE/STOP button and confirm two beep tones.
Confirm again that LEV is operating
Replace outdoor electronic control P.C. board.
LEV operates in full-opening direction.
· Is LEV connector connected?
· Is LEV coil properly fixed to the body?
Heating/Cooling do not operate.
Normal
Do you hear LEV "click, click·······"? Do you touch LEV and feel it vibrate?
Is LEV coil resistance as per characterictics below?
Do you hear LEV "click, click·········"?
No
Yes
Yes
Yes
LEV is normal
Yes
Yes
No
No
LEV (CN 724) WHT(6)–RED(1) RED(1)–ORE(4) YLW(5)–BRN(2) BRN(2)–BLU(3)
resistance
39"~56"
Characteristics of LEV coil
After you have followed the entire flow chart of "Check of linear expansion valve (LEV)", be sure to follow the procedure below.
Replace current limiting resistor.
Check of rush current limiting circuit
O
Outdoor unit does not operate at all or stops immediately due to overcurrent.
NOTE : When the current limiting resistor is open, the rush current limiting relay may not be working properly. There fore confirm the limiting resistor works properly after replacing it.
Normal
Does current limiting resistor detect 10"?
No °
Yes
Heating/Cooling do not operate.
1Press EMERGENCY OPERATION switch. 2Unplug the power cord and then plug it again. 3Press RESET button on remote controller.
Page 54
54
TEST POINT DIAGRAM AND VOLTAGE MSZ-A09RV ­MSZ-A12RV ­Indoor electronic control P.C. board
E1
E1
Varistor (NR11)
Fuse 250V AC 3.15A
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12)
Timer short mode point
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12, 13)
0
0
10 20 30 40 50 60
Emergency operation switch
}
Power supply input 220­240V AC
}
Fan motor power supply
How to set “Auto restart function” Cut the Resistor JR07.(Refer page 39.)
}
5V DC
--
+
{
12V DC
-­+
Temperature (;;)
Resistance (k
''
)
Indoor coil thermistor (RT13)
Page 55
55
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Defrost thermistor(RT62)
Temperature(:)
Discharge temperature thermistor(RT61)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor(RT64)
Resistance(k")
Resistance(k")
Resistance(k")
MUZ-A09RV ­MUZ-A12RV -
E1
E1
Fin temperature thermistor(RT64) CN642
Outdoor electronic control P.C.board
370V DC (C62)
Defrost termination temperature change. Jumper wire (JP7).
Defrost thermistor (RT62) CN641
Discharge temperature thermistor(RT61)
LED monitor lamp
Power supply zero crossing signal 220­240V AC (CN726)
Connector for indoor/outdoo r communicatio
LEV connector (CN724)
15V DC
12V DC
5V DC
220-240V AC
FRONT
BACK
Page 56
56
MUZ-A09RV ­MUZ-A12RV -
Noise filter P.C board
E1
E1
Outdoor fan motor 220-240V AC
R.V. coil 220-240V AC
Relay P.C board
220-240V AC
FRONT
BACK
FRONT BACK
Power supply zero crossing signal 220-240V AC (CN911)
220-240V AC
Page 57
57
DISASSEMBLY INSTRUCTIONS12
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws caps of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
Photo 1
Photo 2
Screws
Front panel
12-1. MSZ-A09RV - MSZ-A12RV -
INDOOR UNIT
E1E1
(1)
(2)
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of a terminal with lock mechanism, detach the terminal as shown below.
<"Terminal with lock mechanism" Detaching points>
2. Removing the electronic control P.C. board and the display P.C. board.
(1) Remove the front panel. (Refer to 1) (2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the terminal cover.
Remove the screw of the terminal block. (4) Remove the cord clamp. (5) Remove the screw of the ground wire. (6) Disconnect all the connectors and all the lead wires on the
electronic control P.C. board.
(7) Remove the electronic control P.C. board and the display
P.C. board.
Terminal block cover
Terminal block cover screw
Room temperature thermistor connector
Cord clamp
Indoor electronic control P.C.board
Ground
Vane motor connector
Fan motor connector
Page 58
58
OPERATING PROCEDURE PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211) and the vane
motor connector (CN151) on the electronic control P.C. board.
(5) Remove the screw fixing the electrical box, remove the
electrical box.
4. Removing the vane motor
(1) Remove the front panel. (2) Remove the screws (both upper and lower) of the vane
motor, disconnect the connector.
(3) Remove the vane motor.
Photo 4
Photo 5
Drain hose
Vane motor
Fan motor screws
Indoor coil thermistor
5. Removing the line flow fan and the indoor fan motor
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical box. (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly. (4) Remove the screws fixing the fan motor. (5) Remove the screws fixing the left side of the heat
exchanger. (6) Lifting the left side of the heat exchanger. (7) Remove the hexagon socket set screws. (8) Remove the fan motor, and remove the line flow fan.
Electrical box screw
Photo 3
The screws fixing the left side of the heat exchanger
Vane motor screws
Page 59
59
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws fixing the service panel. (2) Pull down the service panel and remove it from the cabinet. (3) Remove the screws fixing the cabinet.
2. Removing the inverter assembly
(1) Remove the service panel and the cabinet. (2) Disconnect the connectors (CN641),(CN642),(CN601) and
(CN724) on the control P.C. board.
(3) Remove the connectors (CN771) and (CN913) on the relay
P.C. board. (4) Remove the lead wires from the reactor(L641) on the TB2. (5) Remove the screws fixing the relay panel.
5. Removing the noise filter p.c. board
(1) Remove the service panel and the cabinet.(refer to 1) (2) Remove the control P.C. board and relay P.C. board. (3) Remove all the connectors and the terminals on noise filter
P.C. board. (4) Remove the ground wire screwed down on the relay panel. (5) Remove the noise filter P.C. board.
4. Removing the relay p.c. board
(1) Remove the service panel and the cabinet.(refer to 1) (2) Remove all the connectors and the terminals on relay P.C.
board.
(3)Remove the relay P.C. board.
3. Removing the control p.c. board
(1) Remove the service panel and the cabinet.(refer to 1) (2) Remove the cover. (3) Remove all the connectors and the terminals on the control
P.C. board. (4) Remove the connector from the compressor. (5) Remove the screws fixing the PFC and IPM. (6) Remove the control P.C. board from the heat sink.
Screw
Hook
Screw
Screw
Screw
Screw
Connector
12-2 MUZ-A09RV - MUZ-A12RV -
OUTDOOR UNIT
E1E1
Photo 1
Photo 2
Photo 3
Photo 4
Noise filter P.C. board
Cover screw
Control P.C. board
Relay P.C. board
Screw
Screw
Heat sink
Page 60
60
OPERATING PROCEDURE
PHOTOS
7. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor (4) Remove the electrical assembly. (Refer to 2) (5) Release gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
6. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Unconnect the connector remove the clamp of fan motor
lead wire.
(3) Remove the propeller nut and remove the propeller. (4) Remove screws fixing the fan motor.
Propeller fan
Propeller nut
Set screws for outdoor fan motor
Lead clamps
Welded section
Photo 5
Compressor nut
Page 61
61
PARTS LIST13
MSZ-A09RV - (WH) MSZ-A12RV - (WH) 13-1. INDOOR UNIT STRUCTURAL PARTS
E1
E1
E02 409 000 E02 409 010 E02 410 100 E02 411 234 E02 408 970 E02 409 067 E02 408 142 E02 448 020 E02 409 975 E02 409 976
-
-
FRONT PANEL (WH) GRILLE (WH) AIR FILTER BOX (WH) INSTALLATION PLATE SCREW CAP (WH) CATCH DECORATION COVER (WH) CORNER BOX RIGHT (WH) CORNER BOX LEFT (WH) AIR CLEANING FILTER DEODORIZING FILTER
Symbol
in Wiring
Diagram
Q'ty/unit
2PCS/SET 3PCS/SET
See page 65. (MAC-1300FT) See page 65. (MAC-1800DF)
RemarksPart No.
NO.
Part Name
1 1 2 1 1 2 3 1 1 1 1 1
MSZ-A09RV-
E1
(WH)
1 2 3 4 5 6 7 8 9
10
11
12
(WH)
1 1 2 1 1 2 3 1 1 1 1 1
MSZ-A12RV-
E1
13-2. INDOOR UNIT HEAT EXCHANGER
4
7
6
3
2
10
5
11
9
13
12
8
1
CATCH
SCREW CAP
E02 448 620 E02 151 667 E02 151 666
INDOOR HEAT EXCHANGER UNION (LIQUID) UNION (GAS)
{6.35 {9.52
1 1 1
1 1 1
11 12 13
13-2. INDOOR UNIT HEAT EXCHANGER
13-1. INDOOR UNIT STRUCTURAL PARTS
11 12
Page 62
62
E02 448 235 E02 409 040 E02 409 041 E02 408 702 E02 001 504 E02 408 303 E02 448 303 E02 151 300 E02 151 505 E02 408 302 E02 408 509 E02 408 308 E02 448 307 E02 448 375 E02 448 452 E02 449 452 E02 408 329 E02 151 468 E02 408 034 E02 448 034 E02 408 381 E02 127 382 E02 336 385 E02 424 395
1 2 3 4 5 6 7 8
9 10 11 12 13 14
15
16 17 18 19 20 21 22 23
NOZZLE (WH) VANE UPPER (WH) VANE LOWER (WH) DRAIN HOSE SLEEVE BEARING VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL) INDOOR FAN MOTOR FAN MOTOR RUBBER MOUNT LINE FLOW FAN BEARING MOUNT ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL BLOCK ELECTRIC CONTROL P.C.BOARD ELECTRIC CONTROL P.C.BOARD GREEN SIGN P.C.BOARD RECEIVER P.C.BOARD VANE CLANK SET VANE MOTOR SUPPROT SET THERMAL FUSE FUSE VARISTOR POWER SUPPLY CORD
Symbol
in Wiring
Diagram
Q'ty/unit
UP & DOWN RIGHT & LEFT RC4V19 ­2PES/SET
3P AUTO RESTART AUTO RESTART
UP & DOWN RIGHT & LEFT 93;
3.15A
RemarksPart No.
NO.
Part Name
MV1 MV2
MF
RT11
RT12, 13
TB
F12 F11
NR11
1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
1 1 1 1 1 1 1 1
MSZ-A09RV-
E1
(WH)
1 1 1 1 1 1 1 1 2 1 1 1 1 1
1 1 1 1 1 1 1 1 1
MSZ-A12RV-
E1
(WH)
Part number that is circled is not shown in the illustration.
MSZ-A09RV - (WH) MSZ-A12RV - (WH)
E1
E1
13-4. ACCESSORY AND
REMOTE CONTROLLER PARTS
13-3. INDOOR UNIT ELECTRICAL PARTS
24 25
13-3. INDOOR UNIT ELECTRICAL PARTS
14
11
2
4
3
6
8
1
5
9
7
10
12
13
17
18
15
16
22
SLEEVE BEARING
ROOM TEMPERATURE THERMISTOR
VARISTOR
FUSE
24 25
E02 448 426 E02 141 083
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
1 1
1 1
13-4. ACCESSORY AND REMOTE CONTROLLER PARTS
21
23
Page 63
63
T2W E56 521 T2W E45 232 T2W E56 531 M21 40L 245 M21 75K 297 M21 21J 501 T2W E56 301 T2W E56 515 T2W E56 293 T2W E57 630 M21 68V 961 T2W E56 645 M21 40J 662 M21 41A 661 T92 510 280 M21 54A 290 M21 20A 523 M21 K89 936 T2W E56 943 T2W E57 943
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
GRILLE FRONT PANEL BACK PANEL SERVICE PANEL TOP PANEL PROPELLER OUTDOOR FAN MOTOR MOTOR SUPPORT SEPARATOR OUTDOOR HEAT EXCHANGER REVERSING VALVE PIPE ASSEMBL Y STOP VALVE (LIQUID) STOP VALVE (GAS) COMPRESSOR BASE CONDENSER NET CAPILLARY TUBE MUFFLER MUFFLER SPECIAL
Symbol
in Wiring
Diagram
Q'ty/unit
RA6V28-
EXP. VALVE, CAPILLARY
SNB-092FBA
2PC/SET{3.0{2.0300
RemarksPart No.
NO.
Part Name
MF
MC
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1
MUZ-A09RV-
E1
MUZ-A12RV-
E1
5
9
17
4
15
16
6
2
1
8
10
13
14
3
7
11 12
MUZ-A09RV - (WH) MUZ-A12RV - (WH)
E1
E1
13-5. OUTDOOR UNIT STRUCTURAL PARTS
When servicing , cut the tube to the propper length as shown in the REFRIGERANT SYSTEM DIAGRAM. See page 12.
Page 64
64
T2W E56 451 T2W E57 451 T2W E56 424 T2W E45 376 T2W E56 376 T2W E56 389 M21 90A 308 T2W E56 331 T2W E56 309 T2W E56 441
1
2 3 4 5 6 7 8 9
ELECTRIC CONTROL P.C BOARD ELECTRIC CONTROL P.C BOARD NOISE FILTER P.C BOARD TERMINAL BLOCK TERMINAL BLOCK REVERSING VALVE COIL FIN TEMPERATURE THERMISTOR REACTOR THERMISTOR SET RELAY P.C BOARD
Symbol
in Wiring
Diagram
Q'ty/unit
RemarksPart No.
NO.
Part Name
TB1 TB2
21S4
RT64
L64
RT61,62
1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1
MUZ-A09RV-
E1
MUZ-A12RV-
E1
1
9
6
7
2
8
3
5
MUZ-A09RV - (WH) MUZ-A12RV - (WH)
E1
E1
13-6. OUTDOOR UNIT
ELECTRICAL PARTS
Part number that is circled is not shown in the illustration.
Page 65
65
65
3m 5m
7m 10m 12m
9.52(3/8) 6.35(1/4) 31
21
MAC-A00PI MAC-A01PI MAC-A02PI MAC-A03PI MAC-A04PI
MSZ-A09RV­MSZ-A12RV-
0
90
150
Pipe length
Cross-section
Part No.Model
A-Gas B-Liquid
Pipe size O.D mm (in.)
Insulation
DC
Additional refrigerant
charge
R-410a(g)
E1 E1
14 OPTIONAL PARTS
13-7. AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
13-8. DEODORIZING FILTER
DEODORIZING FILTER removes ammonia and hydrogen sulfide emitted from tobacco, and odors of pets.
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
Model Part No.
MSZ-A09RV ­MSZ-A12RV -
E1
E1
MAC-1300FT
1. REFRIGERANT PIPES
The air conditioner has flared connections its indoor and outdoor sides. Please use the optional extension pipe as follows.
Model Part No.
MSZ-A09RV ­MSZ-A12RV -
E1
E1
MAC-1800DF
Page 66
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
CC
Copyright 1999 MITSUBISHI ELECTRIC ENGINIEERING CO.,LTD Issued in. Mar. 1999 MEE No. OB230 244 Printed in Japan
New publication, effective Mar. 1999 Specifications subject to change without notice.
Loading...