Mitsubishi MSZ-A09RV- E1, MSZ-A12RV- E1, MUZ-A09RV- E1, MUZ-A12RV- E1 Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Wireless type Models
1999
No. OB230
MSZ-A09RV -
MSZ-A12RV -
(WH)
(WH)
MUZ-A09RV ­MUZ-A12RV -
CONTENTS
1. TECHINICAL CHANGES ··································2
2. PART NAMES AND FUNCTIONS······················4
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM··············12
8. PERFORMANCE CURVES······························13
9. MICROPROCESSOR CONTROL ····················23
10. SERVICE FUNCTIONS·····································38
11. TROUBLESHOOTING ······································40
12. DISASSEMBLY INSTRUCTIONS·····················57
13. PARTS LIST······················································61
14. OPTIONAL PARTS···········································65
E1E1
E1E1
1 TECHNICAL CHANGES
Lubricant
Refrigerant
New refrigerant
R-410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R-22
R-22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
New Specification Current Specification
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
The incompatible lubricant easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the lubricant of the upper layer to the compressor.
Since refrigerant and lubricant are compatible each, lubricant backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Lubricant
Refrigerant
Compressor
Suction muffler
Oil back hole
Lubricant /Refrigerant
Compressor
INFORMATION FOR THE AIR CONDITIONER WITH R-410A REFRIGERANT
• This room air conditioner adopts R-410A of HFC refrigerant which never destroys the ozone layer. Pay attention following points.
1 As R-410A working pressure is 1.6 times higher than that of R-22 of previous refrigerant, dedicated tools and piping are
required.
2 R-410A is more affected by water and contaminations than R-22. Keep R-410Aaway from water and contaminations during
storage and while installing.
3 Use clean dedicated piping materiales for R-410A only which are strong enough against R-410Apressure. Never use any
current pipes designed for R-22.
4 Composition change may occur in R-410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
2
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa.G)
R-410A R-22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(;)
NOTE : The unit of pressure has been changed to MPa on the
R-410A tools
Can R-22 tools be used?
Gas leak detector
R-410A pressures beyonds the measurement range of R-22 gauges. Port diameters have been changed to prevent other kinds of refrigerant from being charged into the units.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant. 1/4 and 3/8 wrenches can be used for both R-22 and R-410A units.
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R-22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps. It is difficult to measure R-410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes Yes
Newly required
Newly required
Newly required
Gauge manifold
Charge hose
Torque wrench Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R-410A Yes : Substitutable for R-410A
Wall thickness
Outside diameter
Pipe
mm inch For liquid For gas
6.35
9.52
1/4 3/8
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
1.Tools dedicated for the air conditioner with R-410A refrigerant
The following tools are required for R-410A refrigerant. Some R-22 tools can be substituted for R-410Atools. The diameter of the service port on the outdoor unit operation valve has been changed to prevent improper refrigerant charging. Cap size has also been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a coppor-alloy seamless pipe with a thickness of 0.7 mm or less, as the pressure resistance is in
2 Flaring work and flare nut
sufficient.
Flaring work for R-410A pipes differs from that for the existing refrigerant pipes. for details of flaring work, refer to Installation manual “6-1 FLARING WORK”.
3
2 Optional extension pipe for R-410A
3m 5m
7m 10m 12m
([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52) ([6.35/[9.52)
MAC-A00PI MAC-A01PI MAC-A02PI MAC-A03PI MAC-A04PI
3.Refrigerant oil
Apply the special refrigeration oil (accessories) to the flare and the union seat surfaces.
4.Air purge
Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition chang may occur in the refrigerant inside the cylinder and the outdoor unit. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Gas cylinder
2
PART NAMES AND FUNCTIONS
MSZ-A09RV­MSZ-A12RV-
INDOOR UNIT
Air cleaning filter(white bellows type)
Deodorizing filter (gray sponge type)
Air filter
Outdoor unit
Valve
Refrigerant gas cylinder for R-410A with siphon
Electronic scale for refrigerant charging
E1 E1
Grille
Air inlet
to Breaker
Power supply cord
Liquid
Front panel
Vertical vanes
Operation section
(When the grille is open)
Emergency operation switch
Remote control receiving section
Horizontal vane
Remote controller
Display section
Operation Indicator
Receiving section
4
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIME SET button)
TEMPERATURE buttons
VANE CONTROL button
OFF-TIMER button
RESET button
ON/OFF TOO
WARM
TOO
COOL
HR. MIN.
CLOCK
RESET
CLOCK
MODE
FAN
VANE
START
STOP
ECONO COOL button
ECONO COOL
I FEEL
COOL DRY HEAT
6 00
1 1 00
AM
PM
SWING
SWING button
MUZ-A09RV­MUZ-A12RV-
E1 E1
OUTDOOR UNIT
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
MSZ-A09RV­MSZ-A12RV-
E1 E1
REMOTE CONTROLLER
5
3
Indoor model
Function
Power supply
Capacity Air flow(Hi) Dehumidification Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (Hi) Fan speed (Hi) Fan speed regulator RT11(at25:) Thermistor RT12(at25:) RT13(at25:) Outdoor model Outdoor air flow Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity(R-410A) Refrigerating oil (Model)
RT61(at100:)
Thermistor RT62(at0:) RT64(at50:)
kW
K /h
R/h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k" k"
K /h
A A
W
"
  
"
mm
kg
dB
rpm
kg
cc k" k" k"
MSZ-A09RV -
E1
Single phase
220-240V,50Hz
10
99
4.55 - 4.17
0.17
RA4V19-BA
WHT-BLK 292.4
BLK-RED 324.6
850O278O191
10
5
3 10 10 10
MUZ-A09RV -
E1
0.27-0.25
SNB-092FBA
700
U-V 0.93 U-W 0.93
V-W 0.93
RA6V28-CA
WHT-BLK 197
BLK-RED 315 YLW-BLK 13
710(+69)o540o255
34
2
1.10
450 (NEO22)
13.4
32.6 17
Cooling
2.6 (0.9-3.3) 516
1.2
3.67-3.37
800 (250-1180)
36
920
1440
6.9
3.25
45
670
Heating
3.6 (0.9-4.8) 540
4.55-4.17
990 (250-1650)
35
950
1530
7.4
3.64
47
700
MSZ-A12RV -
E1
Single phase
220-240V,50Hz
10
— 99
7.25 - 6.65
0.19
RA4V19-BA WHT-BLK 292.4 BLK-RED 324.6
850O278O191
10
5
3 10 10 10
MUZ-A12RV -
E1
0.27-0.25
SNB-092FBA
900
U-V 0.93 U-W 0.93
V-W 0.93
RA6V28-CA
WHT-BLK 197
BLK-RED 315 YLW-BLK 13
710(+69)o540o255
34
2
1.10
450 (NEO22)
13.4
32.6 17
Cooling
3.4 (0.9-3.8) 588
1.6
5.60 - 5.13
1220 (250 - 1580)
39
1020
1440
7.4
2.79
46
670
Heating
`4.8 (0.9-6.1)
642
7.25 - 6.65
1580 (250 - 2050)
39
1100
1530
8.1
3.04
48
700
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical data
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
Capacity
SPECIFICATION
NOTE : Test conditions.
Cooling : Indoor DB27: WB19: Heating : Indoor DB 20: WB -:
Outdoor DB35: WB24: Ondoor DB 7: WB 6:
6
1.5+ 440V
MP24GA 12V 300"
ERZV10D471
S201DH1Y
4P
JM1aN-ZTMP-DC12V
93.5:5A 250V 136:i3: 2A
250V 3.15A
500+ 450V
1.8+ 440V RR-18
250V 2A
13A 1.0mH
EM43240 50m" 5W
100" 20W
4P
PS21101-AL / PS21204-A
G4U-1-E G4U-1-E
LB6 250V AC
PMA10001
G4A-1A-P-PS
INDOOR UNIT
OUTDOOR UNIT
Item
Model
Model
Item
Indoor fan capacitor Vane motor Varistor (NR11) Semiconductor relay Terminal block Relay (compressor) (52C) Terminal block thermal Fuse Indoor fan motor thermal fuse Fuse (F11)
Smoothing capacitor (C61,C62) Outdoor fan capacitor (C65) Current transformer (CT61) Fuse (F801, F901) Reactor (L64) Noise filter Current detecting resistor (R61, 62, 64) Current limiting resistor (R65) Terminal block Intelligent power module Relay (X61) Relay (X62) Reversing valve coil Power factor controll module Rush current limiting relay
MSZ-A09RV MSZ-A12RV
MUZ-A09RV MUZ-A12RV
Specifications and rating conditions of main electric parts
7
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19: Heating : DB20: WB -:
MSZ-A09RV- E1
HEATING
NOTCH
35
COOLING 36
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35
:
WB24
:
Heating :DB 7
:
WB 6
:
MUZ-A09RV- E1
HEATING
NOTCH
47
COOLING 45
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27
:
WB19
:
Heating : DB20
:
WB -
:
MSZ-A12RV- E1
HEATING COOLING
NOTCH
39
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB35
:
WB24
:
Heating :DB 7
:
WB 6
:
MUZ-A12RV- E1
HEATING
NOTCH
48
COOLING 46
SPL(dB(A)) LINE
4
NOISE CRITERIA CURVES
8
116.581.5
818
278
850
16562956
or more
100
41
2.5
42
271 4.5
231.5
82
169
326 326
5
189
56
160
17.5
Air in
Air out
Insulation [28
Drain hose [16 (Connected part O.D)
Installation plate
Wall hole [65
Indoor unit
Installation plate
Power supply cord Lead to right 1.0m Lead to left 0.3m
Wireless remote controller
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D
[21 I.D
78
67
7
{
OUTLINES AND DIMENSIONS5
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
Service port
Bolt pitch for installation
Handle
Air out
Air in
Drainage holes [28
4 holes 10o21
18
500 710
265
105
69
138
20
40
If both sides or back side is vacant. only to be free 50 cm in front of a unit
Air in
265
REQUIRED SPACE
If a front side or both sides is vacant. an upper side of a unit has only to be vacant 10cm.
Drainage holes [28
127
32.4
92
367
Drainage holes [28
33
32.5
255
285
320
155
90
43-
35-
540
270
10
35cm or more
50cm or more
10cm or more
10cm or more
10cm
or m
ore
MSZ-A09RV­MSZ-A12RV-
INDOOR UNIT
E1 E1
MUZ-A09RV­MUZ-A12RV-
OUTDOOR UNIT
E1 E1
9
6 WIRING DIAGRAM
MSZ-A09RV- MSZ-A12RV- MODELS WIRING DIAGRAM
E1E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
PE
CIRCUIT BREAKER
TB
L
BRN
BRN
3
2
WHT
N
BLU
BLU
GRN/YLW
RED
F12
GRN/YLW
GREEN SIGN MONITOR P.C.BOARD
11
BLU BLU
1 2
BLU
CN
CN
151
1J1
CN201
3 2 1
LD101T
10
MV1
MV2
3
4
ELECTRONIC CONTROL P.C. BOARD
5
POWER MONITOR, RECEIVER P.C.BOARD
52C
HIC1
TRANS
F11
NR11
SR141
REMOTE CONTROLLER
C11
4 3 2
1
CN112
CN
121
1 2 3
CN211
CN 111
RT13 RT12
BLK
3
GRY YLW BRN WHT RED
1 2 3
MF
4 5 6
RT11
SYMBOL C11 F11 F12 HIC1 MF MV1 MV2
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE (3.15A) THERMAL FUSE (93:) DC/DC CONVERTER INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL NR11
RT11
RT12
RT13
NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
SYMBOL SR141 TB 52C
NAME SOLID STATE RELAY TERMINAL BLOCK CONTACTOR
10
MUZ-A09RV- MUZ-A12RV- MODELS WIRING DIAGRAM
E1E1
OUTDOOR UNIT
220-240V ~
SYMBOL CT61 C61,C62 C65 DSA61 F801 F901 IC950 IPM LEV L61
NOISE FILTER P.C BOARD
R65
X64
LDNF2
CT61
LD-E
GRN
DSA61
NR61
TB1
3
12V
FROM INDOOR UNIT CONNECTING
RED
WHT
2
BLU
N
TAB61
L61
TAB62
BLU
GRN/YLW
NAME CURRENT TRANSFORMER SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (2A) FUSE (2A) DC/DC CONVERTER
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL CMC COIL
BLU
TAB72
SSR61
CN913
21S4
L63
LDNF1
WHT
RELAY
TAB71
P.C BOARD
F901
C65
12
ORG
SYMBOL L63 L64 MC MF61 NR61 PFC RT61 RT62 RT64 R61,62
TAB68
TAB69
CN912
CN
X61
X62
WHT BLU
CN914
3 2
911
1
654321
LD62 LD61
4
CN779CN778
4
3 2
CN726
1
CN771
ELECTRONIC
R61
R62
C61
C62
IC950
TRANS
CONTROL
BLK
RED
WHT
YLW
5
MF61
COIL REACTOR COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) VARISTOR POWER FACTOR CONTROL MODULE DISCHARGE TEMPERATURE THERMIST OR DEFROST THERMISTOR FIN TEMPERATURE THERMIST OR CURRENT-DETECTING RESISTOR
P.C BOARD
CN601
231
NAME
PFC
+ +
F801
R64
6 5 4 3 2
CN641
1
-
1 2
CN642
SYMBOL R64 R65 SSR61 TB1, TB2 X61, X62 X64
21S4
6
LEV
+
U
V W
RT64
CN724
TAB75
TAB76
LD65
LD66
LD67
V
GRY
TB2
BLK
1 2
BLK
WHT
RED
3
RED
~
~
P N
IPM
RT61
RT62
MC
NAME CURRENT-DETECTING RESISTOR CURRENT-LIMITING RESISTOR SOLID STATE RELAY TERMINAL BLOCK RELAY RELAY REVERSING VALVE COIL (COOLING TURN ON)
GRY
BLK
21
WHT
W
L64
BLK
U
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
11
7
Refrigerant Piping Max. length A
Height difference should be within 5m regardless of which unit, indoor or outdoor position is high.
w Max. Height
difference 8m
Indoor unit
Outdoor unit
Indoor heat exchanger
Outdoor heat exchanger
Distributor
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Defrost thermistor RT62
Discharge thermistor RT61
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
Capillary tube (2 pcs)
Refrigerant flow in cooling
Compressor
Accumulator
Maffler
Muffler
Reversing valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (Option)
Refrigerant pipe [6.35 (Option)
Indoor coil thermistor RT12(main)
Expansion valve
[3.0o[2.0o200
[3.0o[2.0o300
REFRIGERANT SYSTEM DIAGRAM
MSZ-A09RV ­MSZ-A12RV -
Unit : mm
E1 E1
MUZ-A09RV ­MUZ-A12RV -
E1 E1
INDOOR UNIT
MAX. REFRIGERANT PIPING LENGTH
Additional piping
Model
MSZ-A09RV­MSZ-A12RV-
E1
E1
Max. length :mm
A
12
OUTDOOR UNIT
Piping size O.D : mm
Gas Liquid Indoor unit Outdoor unit
9.52 6.35 0.43 0
Length of connecting pipe : m
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE (R-410A:g)
Model
MSZ-A09RV­MSZ-A12RV-
Outdoor unit precharged
E1
E1
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant inside the cylinder and the outdoor unit. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
1100
7m
0
Refrigerant piping length (one way)
30
12
9m8m
60
11m10m
12090
Calculation : Xg=30g /m(A-7)m
12m
150
PERFORMANCE CURVES8
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 242V ),50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature ::WB (2) Indoor discharge air wet-bulb temperature ::WB (3) Outdoor intake air dry-bulb temperature ::DB (4) Total input :W (5) Indoor intake air dry-bulb temperature ::DB (6) Outdoor intake air wet-bulb temperature ::WB (7) Total input :W
Indoor air wet-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet-bulb temperature and the indoor discharge air wet-bulb temperature for your reference at service.
E1
Cooling
}
Heating
}
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
13
7.4
6.9
6.3
5.8
5.3
4.8
MSZ-A09RV- E1
8.5
7.9
7.3
6.7
6.1
5.5
MSZ-A12RV- E1
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Cooling capacity
MUZ-A09RV -
MUZ-A12RV -
E1
MUZ-A09RV -
E1
Correction of total input
2.0
1.5
1.0
0.5
Capacity correction factors
0 50 100 150(Hz)
The operational frequency of compressor
E1
MUZ-A12RV -
E1
Correction of total input
2.0
1.5
1.0
0.5
Capacity correction factors
0 50 100 150(Hz)
The operational frequency of compressor
14
27.1
25.1
23.0
20.9
18.8
16.7
14.6
12.5
30.4
28.1
25.8
23.4
21.1
18.7
16.4
14.1
MSZ-A12RV- E1
MSZ-A09RV- E1
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Heating capacity
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
Correction of total input
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.5
1.0
1.5
NOTE:The above curves are for the heating operation without any frost.
MUZ-A09RV -
MUZ-A12RV -
E1
E1
MUZ-A09RV -
MUZ-A12RV -
E1
E1
15
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
(MPa • G)
(kgf/F • G)
(reference)
18 32
62Hz
15 20
50
25 60
30 70(%)
35(:)
0.6
0.7
0.8
0.9
1.0
1.1
62Hz
6
7
8
9
10
11
12
1.2
220V
240V
15 20
50
25 60
30
70(%)
35(:)
3
4
5
6
7
83Hz
32
18
15 20
50
25 6030 70(%)
35(:)
1
2
3
4
5
32
18
220V
240V
53Hz
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit , and select either the COOLmode or the HEAT mode before starting to operate the air conditioner.
2. The compressor starts up. The operational frequency of the compressor is 83Hz in the COOL mode and 58Hz in the HEAT mode.
3. The fan speed of the indoor unit is Hi.
4. This operation continues for 30minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch again, press any button on the remote
controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
COOL operation
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25 30
2 Air flow should be set at Hi.
Relative humidity(%)
50 60 70
3 Operational frequency : 83Hz
(reference) (kgf/F • G)
13
12
11
10
9
8
Outdoor low pressure
7
Outdoor low pressure
MUZ-A09RV -
(MPa • G)
1.3
1.2
1.1
1.0
0.9
0.8
0.7 18 32
15 20
50
25 60
Ambient temperature(:) Ambient humidity(%)
MUZ-A12RV -
Ambient temperature(:) Ambient humidity(%)
E1
62Hz
62Hz
MUZ-A09RV -
E1
Outdoor unit current (A)
30
70(%)
35(:)
Ambient temperature(:) Ambient humidity(%)
E1
MUZ-A12RV -
E1
Outdoor unit current (A)
Ambient temperature(:) Ambient humidity(%)
16
6.0
5.5
5.0
4.5
4.0
3.5
3.0 2
5 10152025
240V
220V
58Hz
HEAT operation
58Hz
220V
240V
6.0
5.5
5.0
4.5
4.0
3.5
3.0 2
510152025
Condition Indoor : Dry bulb temperature 20.0:
Wet bulb temperature 14.5:
Outdoor : Dry bulb temperature 2 7 15 20.0:
Wet bulb temperature 1 6 12 14.5:
MUZ-A09RV -
Outdoor unit current (A)
Ambient temperature(:)
E1
MUZ-A12RV -
E1
Outdoor unit current (A)
Ambient temperature(:)
17
PERFORMANCE DATA COOL operation
MUZ-A09RV -
CAPACITY : 2.6 kW INPUT : 800 W SHF : 0.74
INDOOR INDOOR
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
E1
OUTDOOR DB(:)
21 25 27 30
18
3.06 1.71 0.56 640 2.93 1.64 0.56 672 2.81 1.57 0.56 704 2.70 1.51 0.56 736
20
3.19 1.40 0.44 672 3.06 1.34 0.44 712 2.96 1.30 0.44 728 2.86 1.26 0.44 760
18
3.06 1.83 0.60 640 2.93 1.76 0.60 672 2.81 1.68 0.60 704 2.70 1.62 0.60 736
20
3.19 1.53 0.48 672 3.06 1.47 0.48 712 2.96 1.42 0.48 728 2.86 1.37 0.48 760
22
3.32 1.19 0.36 696 3.20 1.15 0.36 740 3.12 1.12 0.36 760 2.99 1.08 0.36 792
18
3.06 1.96 0.64 640 2.93 1.87 0.64 672 2.81 1.80 0.64 704 2.70 1.73 0.64 736
20
3.19 1.66 0.52 672 3.06 1.59 0.52 712 2.96 1.54 0.52 728 2.86 1.49 0.52 760
22
3.32 1.33 0.40 696 3.20 1.28 0.40 740 3.12 1.25 0.40 760 2.99 1.20 0.40 792
18
3.06 2.08 0.68 640 2.93 1.99 0.68 672 2.81 1.91 0.68 704 2.70 1.84 0.68 736
20
3.19 1.78 0.56 672 3.06 1.71 0.56 712 2.96 1.66 0.56 728 2.86 1.60 0.56 760
22
3.32 1.46 0.44 696 3.20 1.41 0.44 740 3.12 1.37 0.44 760 2.99 1.32 0.44 792
24
3.48 1.11 0.32 728 3.35 1.07 0.32 768 3.28 1.05 0.32 792 3.17 1.02 0.32 832
18
3.06 2.20 0.72 640 2.93 2.11 0.72 672 2.81 2.02 0.72 704 2.70 1.95 0.72 736
20
3.19 1.91 0.60 672 3.06 1.83 0.60 712 2.96 1.78 0.60 728 2.86 1.72 0.60 760
22
3.32 1.59 0.48 696 3.20 1.54 0.48 740 3.12 1.50 0.48 760 2.99 1.44 0.48 792
24
3.48 1.25 0.36 728 3.35 1.21 0.36 768 3.28 1.18 0.36 792 3.17 1.14 0.36 832
18
3.06 2.32 0.76 640 2.93 2.22 0.76 672 2.81 2.13 0.76 704 2.70 2.06 0.76 736
20
3.19 2.04 0.64 672 3.06 1.96 0.64 712 2.96 1.90 0.64 728 2.86 1.83 0.64 760
22
3.32 1.72 0.52 696 3.20 1.66 0.52 740 3.12 1.62 0.52 760 2.99 1.55 0.52 792
24
3.48 1.39 0.40 728 3.35 1.34 0.40 768 3.28 1.31 0.40 792 3.17 1.27 0.40 832
26
3.59 1.00 0.28 768 3.48 0.98 0.28 808 3.43 0.96 0.28 832 3.33 0.93 0.28 856
18
3.06 2.44 0.80 640 2.93 2.34 0.80 672 2.81 2.25 0.80 704 2.70 2.16 0.80 736
20
3.19 2.17 0.68 672 3.06 2.08 0.68 712 2.96 2.02 0.68 728 2.86 1.94 0.68 760
22
3.32 1.86 0.56 696 3.20 1.79 0.56 740 3.12 1.75 0.56 760 2.99 1.67 0.56 792
24
3.48 1.53 0.44 728 3.35 1.48 0.44 768 3.28 1.44 0.44 792 3.17 1.40 0.44 832
26
3.59 1.15 0.32 768 3.48 1.11 0.32 808 3.43 1.10 0.32 832 3.33 1.06 0.32 856
18
3.06 2.57 0.84 640 2.93 2.46 0.84 672 2.81 2.36 0.84 704 2.70 2.27 0.84 736
20
3.19 2.29 0.72 672 3.06 2.20 0.72 712 2.96 2.13 0.72 728 2.86 2.06 0.72 760
22
3.32 1.99 0.60 696 3.20 1.92 0.60 740 3.12 1.87 0.60 760 2.99 1.79 0.60 792
24
3.48 1.67 0.48 728 3.35 1.61 0.48 768 3.28 1.57 0.48 792 3.17 1.52 0.48 832
26
3.59 1.29 0.36 768 3.48 1.25 0.36 808 3.43 1.24 0.36 832 3.33 1.20 0.36 856
18
3.06 2.69 0.88 640 2.93 2.57 0.88 672 2.81 2.47 0.88 704 2.70 2.38 0.88 736
20
3.19 2.42 0.76 672 3.06 2.32 0.76 712 2.96 2.25 0.76 728 2.86 2.17 0.76 760
22
3.32 2.12 0.64 696 3.20 2.05 0.64 740 3.12 2.00 0.64 760 2.99 1.91 0.64 792
24
3.48 1.81 0.52 728 3.35 1.74 0.52 768 3.28 1.70 0.52 792 3.17 1.65 0.52 832
26
3.59 1.44 0.40 768 3.48 1.39 0.40 808 3.43 1.37 0.40 832 3.33 1.33 0.40 856
18
3.06 2.81 0.92 640 2.93 2.69 0.92 672 2.81 2.58 0.92 704 2.70 2.49 0.92 736
20
3.19 2.55 0.80 672 3.06 2.44 0.80 712 2.96 2.37 0.80 728 2.86 2.29 0.80 760
22
3.32 2.25 0.68 696 3.20 2.17 0.68 740 3.12 2.12 0.68 760 2.99 2.03 0.68 792
24
3.48 1.95 0.56 728 3.35 1.88 0.56 768 3.28 1.83 0.56 792 3.17 1.78 0.56 832
26
3.59 1.58 0.44 768 3.48 1.53 0.44 808 3.43 1.51 0.44 832 3.33 1.46 0.44 856
18
3.06 2.93 0.96 640 2.93 2.81 0.96 672 2.81 2.70 0.96 704 2.70 2.60 0.96 736
20
3.19 2.68 0.84 672 3.06 2.57 0.84 712 2.96 2.49 0.84 728 2.86 2.40 0.84 760
22
3.32 2.39 0.72 696 3.20 2.30 0.72 740 3.12 2.25 0.72 760 2.99 2.15 0.72 792
24
3.48 2.09 0.60 728 3.35 2.01 0.60 768 3.28 1.97 0.60 792 3.17 1.90 0.60 832
26
3.59 1.72 0.48 768 3.48 1.67 0.48 808 3.43 1.65 0.48 832 3.33 1.60 0.48 856
18
3.06 3.06 1.00 640 2.93 2.93 1.00 672 2.81 2.81 1.00 704 2.70 2.70 1.00 736
20
3.19 2.80 0.88 672 3.06 2.69 0.88 712 2.96 2.61 0.88 728 2.86 2.52 0.88 760
22
3.32 2.52 0.76 696 3.20 2.43 0.76 740 3.12 2.37 0.76 760 2.99 2.27 0.76 792
24
3.48 2.23 0.64 728 3.35 2.15 0.64 768 3.28 2.10 0.64 792 3.17 2.03 0.64 832
26
3.59 1.87 0.52 768 3.48 1.81 0.52 808 3.43 1.78 0.52 832 3.33 1.73 0.52 856
18
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.55 1.43 0.56 784 2.34 1.31 0.56 832 2.25 1.26 0.56 848 21 20 2.68 1.18 0.44 816 2.50 1.10 0.44 856 2.41 1.06 0.44 880 22 18 2.55 1.53 0.60 784 2.34 1.40 0.60 832 2.25 1.35 0.60 848 22 20 2.68 1.29 0.48 816 2.50 1.20 0.48 856 2.41 1.15 0.48 880 22 22 2.83 1.02 0.36 848 2.65 0.95 0.36 896 2.56 0.92 0.36 912 23 18 2.55 1.63 0.64 784 2.34 1.50 0.64 832 2.25 1.44 0.64 848 23 20 2.68 1.39 0.52 816 2.50 1.30 0.52 856 2.41 1.25 0.52 880 23 22 2.83 1.13 0.40 848 2.65 1.06 0.40 896 2.56 1.02 0.40 912 24 18 2.55 1.73 0.68 784 2.34 1.59 0.68 832 2.25 1.53 0.68 848 24 20 2.68 1.50 0.56 816 2.50 1.40 0.56 856 2.41 1.35 0.56 880 24 22 2.83 1.25 0.44 848 2.65 1.17 0.44 896 2.56 1.13 0.44 912 24 24 2.99 0.96 0.32 880 2.81 0.90 0.32 920 2.73 0.87 0.32 940 25 18 2.55 1.83 0.72 784 2.34 1.68 0.72 832 2.25 1.62 0.72 848 25 20 2.68 1.61 0.60 816 2.50 1.50 0.60 856 2.41 1.44 0.60 880 25 22 2.83 1.36 0.48 848 2.65 1.27 0.48 896 2.56 1.23 0.48 912 25 24 2.99 1.08 0.36 880 2.81 1.01 0.36 920 2.73 0.98 0.36 940 26 18 2.55 1.94 0.76 784 2.34 1.78 0.76 832 2.25 1.71 0.76 848 26 20 2.68 1.71 0.64 816 2.50 1.60 0.64 856 2.41 1.54 0.64 880 26 22 2.83 1.47 0.52 848 2.65 1.38 0.52 896 2.56 1.33 0.52 912 26 24 2.99 1.20 0.40 880 2.81 1.12 0.40 920 2.73 1.09 0.40 940 26 26 3.15 0.88 0.28 912 2.96 0.83 0.28 952 2.87 0.80 0.28 972 27 18 2.55 2.04 0.80 784 2.34 1.87 0.80 832 2.25 1.80 0.80 848 27 20 2.68 1.82 0.68 816 2.50 1.70 0.68 856 2.41 1.64 0.68 880 27 22 2.83 1.59 0.56 848 2.65 1.49 0.56 896 2.56 1.43 0.56 912 27 24 2.99 1.32 0.44 880 2.81 1.24 0.44 920 2.73 1.20 0.44 940 27 26 3.15 1.01 0.32 912 2.96 0.95 0.32 952 2.87 0.92 0.32 972 28 18 2.55 2.14 0.84 784 2.34 1.97 0.84 832 2.25 1.89 0.84 848 28 20 2.68 1.93 0.72 816 2.50 1.80 0.72 856 2.41 1.73 0.72 880 28 22 2.83 1.70 0.60 848 2.65 1.59 0.60 896 2.56 1.54 0.60 912 28 24 2.99 1.44 0.48 880 2.81 1.35 0.48 920 2.73 1.31 0.48 940 28 26 3.15 1.13 0.36 912 2.96 1.07 0.36 952 2.87 1.03 0.36 972 29 18 2.55 2.24 0.88 784 2.34 2.06 0.88 832 2.25 1.98 0.88 848 29 20 2.68 2.04 0.76 816 2.50 1.90 0.76 856 2.41 1.83 0.76 880 29 22 2.83 1.81 0.64 848 2.65 1.70 0.64 896 2.56 1.64 0.64 912 29 24 2.99 1.55 0.52 880 2.81 1.46 0.52 920 2.73 1.42 0.52 940 29 26 3.15 1.26 0.40 912 2.96 1.19 0.40 952 2.87 1.15 0.40 972 30 18 2.55 2.34 0.92 784 2.34 2.15 0.92 832 2.25 2.07 0.92 848 30 20 2.68 2.14 0.80 816 2.50 2.00 0.80 856 2.41 1.92 0.80 880 30 22 2.83 1.93 0.68 848 2.65 1.80 0.68 896 2.56 1.74 0.68 912 30 24 2.99 1.67 0.56 880 2.81 1.57 0.56 920 2.73 1.53 0.56 940 30 26 3.15 1.38 0.44 912 2.96 1.30 0.44 952 2.87 1.26 0.44 972 31 18 2.55 2.45 0.96 784 2.34 2.25 0.96 832 2.25 2.16 0.96 848 31 20 2.68 2.25 0.84 816 2.50 2.10 0.84 856 2.41 2.02 0.84 880 31 22 2.83 2.04 0.72 848 2.65 1.91 0.72 896 2.56 1.84 0.72 912 31 24 2.99 1.79 0.60 880 2.81 1.68 0.60 920 2.73 1.64 0.60 940 31 26 3.15 1.51 0.48 912 2.96 1.42 0.48 952 2.87 1.38 0.48 972 32 18 2.55 2.55 1.00 784 2.34 2.34 1.00 832 2.25 2.25 1.00 848 32 20 2.68 2.36 0.88 816 2.50 2.20 0.88 856 2.41 2.12 0.88 880 32 22 2.83 2.15 0.76 848 2.65 2.02 0.76 896 2.56 1.95 0.76 912 32 24 2.99 1.91 0.64 880 2.81 1.80 0.64 920 2.73 1.75 0.64 940 32 26 3.15 1.64 0.52 912 2.96 1.54 0.52 952 2.87 1.49 0.52 972
CAPACITY : 2.6 kW INPUT : 800 W SHF : 0.74
PERFORMANCE DATA COOL operation
MUZ-A09RV -
E1
19
PERFORMANCE DATA COOL operation
MUZ-A12RV -
CAPACITY : 3.4 kW INPUT : 1220 W SHF : 0.69
INDOOR INDOOR
DB(:) WB(:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.00 2.04 0.51 976 3.83 1.95 0.51 1025 3.67 1.87 0.51 1074 3.54 1.80 0.51 1122 21 20 4.17 1.62 0.39 1025 4.00 1.56 0.39 1086 3.88 1.51 0.39 1110 3.74 1.46 0.39 1159 22 18 4.00 2.20 0.55 976 3.83 2.10 0.55 1025 3.67 2.02 0.55 1074 3.54 1.94 0.55 1122 22 20 4.17 1.79 0.43 1025 4.00 1.72 0.43 1086 3.88 1.67 0.43 1110 3.74 1.61 0.43 1159 22 22 4.34 1.34 0.31 1061 4.18 1.30 0.31 1129 4.08 1.26 0.31 1159 3.91 1.21 0.31 1208 23 18 4.00 2.36 0.59 976 3.83 2.26 0.59 1025 3.67 2.17 0.59 1074 3.54 2.09 0.59 1122 23 20 4.17 1.96 0.47 1025 4.00 1.88 0.47 1086 3.88 1.82 0.47 1110 3.74 1.76 0.47 1159 23 22 4.34 1.52 0.35 1061 4.18 1.46 0.35 1129 4.08 1.43 0.35 1159 3.91 1.37 0.35 1208 24 18 4.00 2.52 0.63 976 3.83 2.41 0.63 1025 3.67 2.31 0.63 1074 3.54 2.23 0.63 1122 24 20 4.17 2.12 0.51 1025 4.00 2.04 0.51 1086 3.88 1.98 0.51 1110 3.74 1.91 0.51 1159 24 22 4.34 1.69 0.39 1061 4.18 1.63 0.39 1129 4.08 1.59 0.39 1159 3.91 1.52 0.39 1208 24 24 4.56 1.23 0.27 1110 4.39 1.18 0.27 1171 4.28 1.16 0.27 1208 4.15 1.12 0.27 1269 25 18 4.00 2.68 0.67 976 3.83 2.56 0.67 1025 3.67 2.46 0.67 1074 3.54 2.37 0.67 1122 25 20 4.17 2.29 0.55 1025 4.00 2.20 0.55 1086 3.88 2.13 0.55 1110 3.74 2.06 0.55 1159 25 22 4.34 1.86 0.43 1061 4.18 1.80 0.43 1129 4.08 1.75 0.43 1159 3.91 1.68 0.43 1208 25 24 4.56 1.41 0.31 1110 4.39 1.36 0.31 1171 4.28 1.33 0.31 1208 4.15 1.29 0.31 1269 26 18 4.00 2.84 0.71 976 3.83 2.72 0.71 1025 3.67 2.61 0.71 1074 3.54 2.51 0.71 1122 26 20 4.17 2.46 0.59 1025 4.00 2.36 0.59 1086 3.88 2.29 0.59 1110 3.74 2.21 0.59 1159 26 22 4.34 2.04 0.47 1061 4.18 1.97 0.47 1129 4.08 1.92 0.47 1159 3.91 1.84 0.47 1208 26 24 4.56 1.59 0.35 1110 4.39 1.54 0.35 1171 4.28 1.50 0.35 1208 4.15 1.45 0.35 1269 26 26 4.69 1.08 0.23 1171 4.56 1.05 0.23 1232 4.49 1.03 0.23 1269 4.35 1.00 0.23 1305 27 18 4.00 3.00 0.75 976 3.83 2.87 0.75 1025 3.67 2.75 0.75 1074 3.54 2.65 0.75 1122 27 20 4.17 2.62 0.63 1025 4.00 2.52 0.63 1086 3.88 2.44 0.63 1110 3.74 2.36 0.63 1159 27 22 4.34 2.21 0.51 1061 4.18 2.13 0.51 1129 4.08 2.08 0.51 1159 3.91 1.99 0.51 1208 27 24 4.56 1.78 0.39 1110 4.39 1.71 0.39 1171 4.28 1.67 0.39 1208 4.15 1.62 0.39 1269 27 26 4.69 1.27 0.27 1171 4.56 1.23 0.27 1232 4.49 1.21 0.27 1269 4.35 1.18 0.27 1305 28 18 4.00 3.16 0.79 976 3.83 3.02 0.79 1025 3.67 2.90 0.79 1074 3.54 2.79 0.79 1122 28 20 4.17 2.79 0.67 1025 4.00 2.68 0.67 1086 3.88 2.60 0.67 1110 3.74 2.51 0.67 1159 28 22 4.34 2.38 0.55 1061 4.18 2.30 0.55 1129 4.08 2.24 0.55 1159 3.91 2.15 0.55 1208 28 24 4.56 1.96 0.43 1110 4.39 1.89 0.43 1171 4.28 1.84 0.43 1208 4.15 1.78 0.43 1269 28 26 4.69 1.45 0.31 1171 4.56 1.41 0.31 1232 4.49 1.39 0.31 1269 4.35 1.35 0.31 1305 29 18 4.00 3.32 0.83 976 3.83 3.17 0.83 1025 3.67 3.05 0.83 1074 3.54 2.93 0.83 1122 29 20 4.17 2.96 0.71 1025 4.00 2.84 0.71 1086 3.88 2.75 0.71 1110 3.74 2.66 0.71 1159 29 22 4.34 2.56 0.59 1061 4.18 2.47 0.59 1129 4.08 2.41 0.59 1159 3.91 2.31 0.59 1208 29 24 4.56 2.14 0.47 1110 4.39 2.06 0.47 1171 4.28 2.01 0.47 1208 4.15 1.95 0.47 1269 29 26 4.69 1.64 0.35 1171 4.56 1.59 0.35 1232 4.49 1.57 0.35 1269 4.35 1.52 0.35 1305 30 18 4.00 3.48 0.87 976 3.83 3.33 0.87 1025 3.67 3.19 0.87 1074 3.54 3.08 0.87 1122 30 20 4.17 3.12 0.75 1025 4.00 3.00 0.75 1086 3.88 2.91 0.75 1110 3.74 2.81 0.75 1159 30 22 4.34 2.73 0.63 1061 4.18 2.63 0.63 1129 4.08 2.57 0.63 1159 3.91 2.46 0.63 1208 30 24 4.56 2.32 0.51 1110 4.39 2.24 0.51 1171 4.28 2.18 0.51 1208 4.15 2.12 0.51 1269 30 26 4.69 1.83 0.39 1171 4.56 1.78 0.39 1232 4.49 1.75 0.39 1269 4.35 1.70 0.39 1305 31 18 4.00 3.64 0.91 976 3.83 3.48 0.91 1025 3.67 3.34 0.91 1074 3.54 3.22 0.91 1122 31 20 4.17 3.29 0.79 1025 4.00 3.16 0.79 1086 3.88 3.06 0.79 1110 3.74 2.95 0.79 1159 31 22 4.34 2.90 0.67 1061 4.18 2.80 0.67 1129 4.08 2.73 0.67 1159 3.91 2.62 0.67 1208 31 24 4.56 2.51 0.55 1110 4.39 2.41 0.55 1171 4.28 2.36 0.55 1208 4.15 2.28 0.55 1269 31 26 4.69 2.02 0.43 1171 4.56 1.96 0.43 1232 4.49 1.93 0.43 1269 4.35 1.87 0.43 1305 32 18 4.00 3.80 0.95 976 3.83 3.63 0.95 1025 3.67 3.49 0.95 1074 3.54 3.36 0.95 1122 32 20 4.17 3.46 0.83 1025 4.00 3.32 0.83 1086 3.88 3.22 0.83 1110 3.74 3.10 0.83 1159 32 22 4.34 3.08 0.71 1061 4.18 2.97 0.71 1129 4.08 2.90 0.71 1159 3.91 2.78 0.71 1208 32 24 4.56 2.69 0.59 1110 4.39 2.59 0.59 1171 4.28 2.53 0.59 1208 4.15 2.45 0.59 1269 32 26 4.69 2.21 0.47 1171 4.56 2.14 0.47 1232 4.49 2.11 0.47 1269 4.35 2.05 0.47 1305
E1
OUTDOOR DB(:)
21 25 27 30
20