Mitsubishi MS-GA50/60VB, MSH-CA50VB Installation Manual

Page 1
1
SG79Y367H01
SPLIT-TYPE AIR CONDITIONERS Models
MS-GA50/60VB MSH-GA50VB Series MSH-CA50VB
English
INSTALLATION MANUAL
CAUTION
Earth the unit.
Do not connect the earth to a gas pipe, water pipe, lightning rod or telephone earth. Defective earthing could cause an electric shock.
Do not install the unit in a place where an inflammable gas leaks.
If gas leak and accumulate in the area surrounding the unit, it could cause an explosion.
Install an earth leakage breaker depending on the installation place (Where it is humid).
If an earth leakage breaker is not installed, it could cause an electric shock.
Perform the drainage/piping work securely according to the installation manual.
If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrigerant.
2. SELECTING THE INSTALLATION LOCATION
2-1 INDOOR UNIT
Where airflow is not blocked.
Where cool air spreads over the entire room.
Maximum refrigerant piping length between indoor unit and outdoor unit is 25 m and the difference of height of both units is 10 m.
Rigid wall without vibration.
Where it is not exposed to direct sunshine.
Where easily drained.
At a distance 1 m or more away from your TV and radio. Operation of the air conditioner interferes with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device.
In a place as far away as possible from fluorescent and incandescent lights (so the infrared remote control can operate the air conditioner normally).
Where the air filter can be removed and replaced easily.
2-2 OUTDOOR UNIT
Where it is not exposed to strong wind.
Where airflow is good and dustless.
Where it is not exposed to rain and direct sunshine.
Where neighbours are not annoyed by operation sound or hot air.
Where rigid wall or support is available to prevent the increase of operation sound or vibration.
Where there is no risk of combustible gas leakage.
When installing the unit at a high level, be sure to fix the unit legs.
Where it is at least 3 m away from the antenna of TV set or radio. Operation of the air conditioner interferes with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device.
Install the unit horizontally.
Please install it in an area not affected by snowfall or blowing snow. In areas with heavy snow, please install a canopy, a pedestal and/or some baffle boards.
Note:
It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there.
CAUTION
Avoid the following places for installation where air conditioner trouble is liable to occur.
Where flammable gas could leak.
Where there is much machine oil.
Salty places such as the seaside.
Where sulfide gas is generated such as a hot spring.
Where there is high-frequency or wireless equipment.
2-3 WIRELESS REMOTE CONTROLLER MOUNTING
Place of mounting
• Where it is easy to operate and easily visible.
• Where children can not touch.
Mounting Select a position about 1.2 m above the floor, check that signals from the remote controller are surely received by the indoor unit from that position (‘beep’ or ‘beep­beep’ receiving tone sounds). After that, attach remote controller holder 3 to a pillar or wall and set the wireless remote controller 6.
In rooms where inverter type fluorescent lamps are used, the signal from the wireless remote controller may not be received.
1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Please provide an exclusive circuit for the air conditioner and do not connect other electrical appliances to it. Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
The indications and meanings are as follows.
WARNING
Could lead to death, serious injury, etc.
CAUTION
Could lead to serious injury in particular environments when operated incorrectly.
After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS in a handy place on the customer’s site.
WARNING
Do not install the unit by yourself (customer).
Incomplete installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
Install the unit securely in a place which can bear the weight of the unit.
When installed in an insufficient strong place, the unit could fall causing injury.
Use the specified wires to connect the indoor and outdoor units securely
and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections.
Incomplete connecting and fixing could cause fire.
Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Check that the refrigerant gas do not leak after installation has com-
pleted.
If refrigerant gas leaks indoors, and comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
Perform the installation securely referring to the installation manual.
Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
Perform electrical work according to the installation manual and be sure
to use an exclusive circuit.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
Attach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.
If the electrical cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
Be sure to use the part provided or specified parts for the installation
work.
The use of defective parts could cause an injury or leakage of water due to a fire, an electric shock, the unit falling, etc.
Be sure to cut off the main power in case of setting up the indoor
electronic control P.C. board or wiring works.
It could cause an electric shock.
The appliance shall be installed in accordance with national wiring
regulations.
When installing or relocating the unit, make sure that no substance
other than the specified refrigerant (R410A) enters the refrigerant circuit.
Any presence of foreign substance such as air can cause abnormal pressure rise or an explosion.
HFC
utilized
R410A
When installing an MXZ series outdoor unit, refer to the MS and MSH type manual for indoor unit set up.
SG79Y367H13
Page 2
D
E
F
G
B
3
4
7
H
C
6
1
2
I
A
3. INSTALLATION DIAGRAM & ACCESSORIES
FLARED CONNECTIONS
This unit has flared connections on both indoor and outdoor sides.
Remove the outdoor units valve cover, then connect the pipe.
Refrigerant pipes are used to connect the indoor and outdoor units.
Be careful not to crush or bend the pipe in pipe bending.
Limits
Pipe length 25 m max.
Height difference 10 m max.
No. of bends 10 max.
Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R410A) charge is required. (The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Pipe length
Up to 7 m No additional charge is required.
Exceeding 7 m
Additional charge is required.
(Refer to the table below.)
Refrigerant to
20 g/m × (refrigerant piping length (m) -7)
be added
ACCESSORIES
Check the following parts before installation. <Indoor unit>
1 Installation plate 1
2 Installation plate fixing screw 4 × 25 mm 7
3 Remote controller holder 1
4 Fixing screw for 3 3.5 × 16 mm (Black) 2
5 Battery (AAA) for remote controller 2
6 Wireless remote controller 1
7 Felt tape (Used for left or left-rear piping) 1
<Outdoor unit: MUH type>
8 Drain socket 1
9 Drain cap ø33 2
PART TO BE PROVIDED AT YOUR SITE
Optional extension pipe
A
Indoor/outdoor unit connecting wire
1
(2-core 1.0 mm2-2.0 mm2)
B Extension pipe 1 C Wall hole sleeve 1 D Wall hole cover 1
E
Pipe fixing band (The quantity depends on the pipe length.)
2 to 5
F
Fixing screw for E 4 × 20 mm (The
2 to 5
quantity depends on the pipe length.)
G Piping tape 1 H Putty 1
I
Drain hose (or soft PVC. hose, 15 mm
1
inner dia. or hard PVC pipe VP16)
J Refrigeration oil 1
Power supply cord (See the table in 5
K
INDOOR/OUTDOOR WIRE CONNECTION
1
AND OUTDOOR POWER SUPPLY CORD CONNECTION for the cord size.)
Be careful the drain hose is not raised.
Separate the 2 connecting pipes and apply insulation individually.
8 mm thickness thermal insulation plastic
Decide the installation position using mark on the installation plate indicating the indoor unit size as reference.
When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Lock the catch.
Front
Piping can be directed towards rear, right, downward, left or left-rear directions.
Rear side Right
Rear
Downward
Left-rear
Left
7 mm or more
100 mm or more
100 mm or more
100 mm or more
500 mm
or more
350 mm
or more
Note: Do not
obstruct the air outlet.
72 mm or more
100 mm or more for left and left
back piping (using spacer
)
120 mm
or more
Heat resisting foam plastic 0.045 specific gravity
200 mm or more
5
PIPING PREPARATION
1 Specifications
Use the refrigerant pipes that meet the following specifications.
Pipe
Outside diameter Insulation thickness
Insulation material
mm mm
For liquid 6.35 8
MS(H)-GA50
12.7 8
For gas MSH-CA50
MS-GA60 15.88 8
Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (for ø6.35, 9.52, 12.7) or 1.0 mm (for ø15.88). Never use any pipe with a thickness less than 0.8 mm (for ø6.35, 9.52, 12.7) or 1.0 mm (for ø15.88), as the pressure resistance is insufficient.
2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation. 3 Refrigerant pipe bending radius must be 100 mm or more.
CAUTION
Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage.
850mm
290mm
310mm
500mm
18mm
18mm
10mm
Slot 4-10 mm × 21 mm
Units should be installed by licensed contractor according to local code requirement.
Air outlet
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.
Never install the outdoor unit in a place where its air inlet/ outlet side may be exposed directly to wind.
To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.
For MSH-CA50VB
For MS(H)-GA50VB
MS-GA60VB
Page 3
4. INDOOR UNIT INSTALLATION
4-1 FIXING OF INSTALLATION PLATE
Find a structural material (such as a stud) in the wall and fix installation plate horizontally.
When bolts recessed in the concrete wall are to be utilized, secure the installation plate 1 using 11 × 20 · 11 × 26 oval hole (450 mm pitch). If the recessed bolt is too long, change it for a shorter one available in the market.
4-2 WALL HOLE DRILLING
1 Determine the wall hole position. 2 Drill a 75 mm hole so that outside can be lower than inside. 3 Insert the wall hole sleeve C.
Positioning of the holes on the wall
Be sure to use wall hole sleeve C to prevent the outdoor connecting wires from contacting with metal part in the wall and to prevent damage by rat in case the wall is hollow.
Wall hole sealing and fixing pipe to wall
72 mm or more 100 mm or more for left and left back piping (using spacer)
200 mm or more
(off the wall)
Plumb
Installation plate fixing screw 2 4 × 25 mm
120 mm or more
(off the w
all)
Insert the scale.
Align the scale with the line.
Installation plate 1
Hole of dia. 75 mm
Repeat the same procedure for the left hole.
Wall hole
75 mm dia.
(Indoor side)
(Wall hole cross section)
Wall thickness
One scale
Wall hole sleeve C
Cut with 1 extra scale length.
Installation plate 1
To prevent the installation plate from vibrating, be sure to fix the holes as indicated by the arrows c.
Wall hole sleeve C
Indoor unit
Wall hole cover D
Seal the wall hole gap with putty H.
Fix the pipe to wall with pipe fixing band E.
Cut off the extra length. Pipe fixing
band E
Fixing screw F
Align the plumb line with the mark .
Bind the line to the center hole.
100 mm
4-3 CONNECTING WIRE SPECIFICATIONS
Use special room air conditioning circuit.
Power supply cord length
1 m/2 m
(Lead to left/Lead to right)
Indoor/outdoor unit connecting Cable 2-core 1.0 mm2, in conformity wire Specification with Design 245 IEC 57.
Take out power supply cord from the left or right bottom corner of the indoor unit.
Connect to the power switch which has a gap of 3 mm or more when open to interrupt the source power phase. (When the power switch is shut off, it must interrupt all phases.) (Rated Voltage/Frequency : 230 V/50 Hz) (Input capacity Main switch/Fuse : 10 A) (This plug has to be the one meets the Standards.) Power supply cord
WARNING
Never cut the indoor and outdoor unit connecting wire and connect it to other wires. It may cause a fire.
Do not bundle the spare wire, but put it as shown below.
4-4 INDOOR AND OUTDOOR CONNECTING WIRE CON-
NECTION
You can connect indoor/outdoor lead wire without removing the front panel.
1 Open the front panel. 2 Remove one screw holding the electrical cover, then remove the cover. 3 Remove the VA clamp and the cord clamp. 4 Pass the indoor/outdoor unit connecting wire from the back of the indoor unit and
process the end of the wire, then connect it to the terminal block.
5 Replace the fixture and electrical cover securely.
WARNING
Use the indoor/outdoor unit connecting wire that meets the Standards to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block. Incomplete connection or fixing of the wire could result in a fire.
Attach the electrical cover securely. If it is attached incorrectly, it could result in a fire or an electric shock due to dust, water, etc.
Indoor terminal block
ELECTRICAL COVER
Fixing screws
Securely push the wire into the terminal block until no part of its core is appeared.
Indoor/outdoor unit connecting wire A
VA clamp
Never fail to hook the left claw on the wire fixture to secure indoor/ outdoor unit connecting wire A.
Green/Yellow : Ground Blue : N Brown : L
MSH type
15 mm
35 mm
Indoor terminal block
Indoor/outdoor unit connecting wire A 2-core 1.0 mm
2
Outdoor terminal block
<Connection details>
Loosen terminal screw.
Lead wire
Terminal block
3 N
3
N
Page 4
15 mm
35 mm
Drain hose
Drain cap
FOR LEFT OR LEFT-REAR PIPING
Pipe arrangement Put the refrigerant piping and the drain hose together, then apply felt tape 7 to them.
REATTACHING DRAIN HOSE
Be sure to reattach the drain hose and the drain cap in case of left or left-rear piping. Otherwise, it could cause drops of water to drip down from the drain hose.
1
Pull out the drain cap at the rear right of the indoor unit.
Hold the convex section at the end and pull the drain cap.
2
Pull out the drain hose at the rear left of the indoor unit.
Hold the claw marked by the arrow and pull out the drain hose forward.
Cut off in case of left piping.
Felt tape 7
Firmly apply felt tape 7 from the end. (Felt tape 7 overlap width should be 1/3 the tape width.)
Be careful drain hose is not heaved.
Use a bandage stopper at the end of felt tape 7.
Drain cap
Be careful drain hose is not heaved.
Firmly apply piping tape G from the end.
Cut off in case of right piping. Cut off in case of downward piping.
FOR REAR, RIGHT OR DOWNWARD PIPING
Pipe arrangement Put the refrigerant piping and the drain hose together, then apply piping tape G to them.
Insert the piping and the drain hose into the wall hole sleeve C, and hook the upper part of the indoor unit on the installation plate 1.
Check if the indoor unit is hooked securely on the installation plate 1 by moving the unit to left and right.
Thrust the lower part of the indoor unit into the installation plate 1.
Drain hose
Liquid pipe
Gas pipe
Felt tape 7
Indoor/outdoor unit connecting wire A
CAUTION
Be careful not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit does not operate normally.
If an earth is incorrect, it may cause an electric shock.
Make earth wire a little longer than the others. (more than 35 mm)
4-5 AUTO RESTART FUNCTION
These models are equipped with an auto restart function. If you do not want to use this function, please consult the service representative because the setting of the unit needs to be changed.
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically. If the unit is operated in “I FEEL...” or “AUTO” mode before power failure, the operation mode (COOL, DRY or HEAT) is not stored in the memory. When the main power is turned on, the unit decides the operation mode by the initial room temperature at restart and starts operation again.
Operation
1 If the main power has been cut, the operation settings remain. 2 When three minutes have passed after power was restored, the unit will restart
automatically according to the memory.
Notes:
The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with timer cancelled at the same time that power is restored.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same time.
4-6 PIPE FORMING
Place the drain hose below the refrigerant piping.
Make sure that the drain hose is not heaved or snaked.
Do not pull the hose to apply the tape.
When the drain hose passes the room, be sure to wrap insulation material (obtain­able at a store) around it.
Wrap the felt tape 7 around the pipe and the drain hose, then put the pipe in the back space of the indoor unit.
MS type
Indoor terminal block
Indoor/outdoor unit connecting wire A 2-core 1.0 mm
2
Outdoor terminal block
<Connection details>
Loosen terminal screw.
Lead wire
Terminal block
Page 5
10 m or less
15 m or less
25 m or less
Power supply cord Specification
Indoor and Outdoor connecting wire Specification
3-core 1.5 mm2 or more, in conformity with Design 245 IEC 57. 3-core 2.5 mm
2
or more, in conformity with Design 245 IEC 57. 3-core 4.0 mm
2
or more, in conformity with Design 245 IEC 57.
Cable 2-core 1.0 mm
2
,
in conformity with Design 245 IEC 57.
Drain hose
Downward slope
Water leakage
Do not raise.
Water leakage
Accumulated drain water
Waving
Water leakage
Tip of drain hose dipped in water.
Ditch
Air
4
Insert the drain hose into the section to which the drain hose is to be attached at the rear right of the indoor unit.
Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to the projection of its inserting part at the drain pan.
INDOOR UNIT INSTALLATION
Insert the drain hose into the wall hole sleeve C, and hook the upper part of indoor unit on the installation plate 1. Then, move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit. After that, cut the part of packing material (spacer assembly) to hook it on the back rib and lift the indoor unit as shown in the figure below.
Connect the refrigerant piping with the extension pipe B.
Thrust the lower part of the indoor unit into the installation plate 1.
4-7 DRAIN PIPING
The drain hose should point downward for easy drain flow. (Fig. 1) Do not make drain piping as shown in Fig. 2 to 5.
(Fig. 1) (Fig. 2) (Fig. 3)
(Fig. 4) (Fig. 5)
If the drain hose provided with the indoor unit is too short, connect it with drain hose I that should be provided at your site.
If the extension drain hose has to pass through a room, be sure to wrap it with commercially sold insulation.
Soft hose I.D. 15 mm or hard vinyl chloride
Spacer assembly
Securely attach the spacer assembly in the concave part of the rib, taking care its direction is correct as shown in the right.
Spacer
Cut part of packing material (spacer assembly) to hook it on the back rib.
Drain hose
Less than 50 mm gap
WARNING
A means for disconnection of the supply with an isolation switch, or similar device, in all active conductors shall be incorporated in the fixed wiring.
Never cut the power cord and connect it to other wires. It may cause a fire.
Power supply cord K
Drain cap
3
Put the drain cap into the section to which the drain hose is to be attached at the rear of the indoor unit.
Insert the screwdriver, etc. (not sharp-edged tool) into the hole at the end of the cap and insert the cap fully into the drain pan.
Indoor terminal block
Outdoor terminal block
3 N
3
N
Indoor/outdoor unit connecting wire A 2-core 1.0 mm
2
MSH type
Indoor terminal block
Outdoor terminal block
Indoor/outdoor unit connecting wire A 2-core 1.0 mm
2
MS type
10 m or less
15 m or less
25 m or less
Power supply cord Specification
Indoor and Outdoor connecting wire Specification
3-core 2.5 mm2 or more, in conformity with Design 245 IEC 57. 3-core 4.0 mm
2
or more, in conformity with Design 245 IEC 57. 3-core 6.0 mm
2
or more, in conformity with Design 245 IEC 57.
Cable 2-core 1.0 mm
2
,
in conformity with Design 245 IEC 57.
MS-GA60
5. OUTDOOR UNIT INSTALLATION
INDOOR/OUTDOOR UNIT CONNECTING WIRE CON­NECTION AND OUTDOOR POWER SUPPLY CORD CONNECTION
Connect the indoor/outdoor unit connecting wire A from the indoor unit correctly on the terminal block.
For future servicing, give extra length to connecting wire.
Model
Rated Breaker
Voltage capacity
MS(H)-GA50
15 A
MSH-CA50
230 V
MS-GA60
25 A
Peel off both ends of connecting wire (extension wire). When too long, or connected by cutting off the middle, peel off power supply wire to the size as shown in the right.
Be careful not to contact connecting wire with piping.
Make earth wire a little longer than the others. (more than 35 mm)
For the power supply cord and the indoor/outdoor unit connecting wires, be sure to use the ones in compliance with the standards.
Be sure to push the core until it is hidden and pull each cable to make sure that it is not pulled up incomplete insertion may cause a risk of burning the terminal blocks.
Connect to the supply terminals and leave a contact separation of at least 3 mm at each pole to discon­nect the source power pole. (When the power switch is shut off, it must disconnect all poles.)
N~L
~
35 mm
15 mm
CAUTION
Use care not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit does not operate normally.
MS(H)
-GA50
MSH
-CA50
Page 6
6. INDOOR/OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN
INSTALLATION INFORMATION FOR THE AIR CONDI­TIONER WITH R410A REFRIGERANT
This room air conditioner adopts an HFC refrigerant (R410A) which will never destroy the ozone layer.
Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air conditioners.
1 As R410A has a working pressure approx. 1.6 times as high as that of R22, some
special tools and piping parts / materials are required. (Refer to the table below.)
2 Take sufficient care not to allow water and other contaminations to enter the
R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts / materials specifically
designed for R410A. (Refer to 2. Refrigerant piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When
charging, charge liquid refrigerant to prevent composition change.
6-1 Tools dedicated for the air conditioner with R410A
refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. (Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.)
R410A tools Can R22 tools be used? Description
R410A has high pressures beyond the meas­urement range of existing gauges.
Gauge manifold No Port diameters have been changed to prevent
any other refrigerant from being charged into the unit.
Charge hose No
Hose material and cap size have been changed to improve the pressure resistance.
Gas leak detector No Dedicated for HFC refrigerant.
Torque wrench
Yes 1/4
No 1/2 and 5/8
Flare tool Yes
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Flare gauge New
Provided for flaring work (to be used with R22 flare tool).
New
Provided to prevent the back flow of oil. This adapter enables you to use existing vacuum pumps.
New
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization.
No: Not substitutable for R410A Yes: Substitutable for R410A
Electronic scale for refrigerant charging
Vacuum pump adaptor
A
Remove two fixing screws to open the service panel.
Service panel
Fixing screws
Be sure to put the left portion into the square hole of the service panel.
Be sure to fix the indoor/outdoor unit connecting wire A using this cord clamp.
WARNING
Be sure to attach the service panel of the outdoor unit securely. If it is not attached correctly, it could result in a fire or an electric shock due to dust, water, etc.
Copper pipe
Good
No good
Tilted
Uneven
Burred
Burr
Copper pipe
Spare reamer
Pipe cutter
90°
6-2 FLARING WORK
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1
Pipe cutting
• Cut the copper pipe correctly with pipe cutter.
2
Burrs removal
• Completely remove all burrs from the cut cross section of pipe.
• Put the end of the copper pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the piping.
A
Flare nut
Copper pipe
Die
Copper pipe
Flare nut
Die
Copper pipe
York
Smooth all around
Even length all around
Inside is shining without any scratches.
Flaring tool
Wing nut type
Clutch type
3
Putting nut on
• Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (not possible to put them on after flaring work)
• Flare nut for R410A pipe differs from R22 pipe. Refer to the following table for detail.
4
Flaring work
• Carry out flaring work using flaring tool as shown below.
• Firmly hold copper pipe in a die in the dimension shown in the table above.
5
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and do flaring work again.
mm inch R410A R22
ø6.35 1/4 17 17
ø12.7 1/2 26 24
ø15.88 5/8 29 27
A (mm)
Outside diameter Conventional flare tool
Clutch type Wing nut type
ø6.35 mm 0 to 0.5 1.0 to 1.5 1.5 to 2.0
ø12.7 mm 0 to 0.5 1.0 to 1.5 2.0 to 2.5
ø15.88 mm 0 to 0.5 1.0 to 1.5 2.0 to 2.5
Flare tool for R410A
clutch type
Page 7
6-3 PIPE CONNECTION
Note:
Fasten a flare nut with a torque wrench as specified in the table below. When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrigerant. 1 Indoor unit connection Connect both liquid and gas pipings to indoor unit.
Apply a thin coat of refrigeration oil J on the seat surface of pipe.
For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
Use tightening torque table below as a guideline for indoor unit side union joint section, and tighten using two wrenches. Excessive tightening damages the flare section.
Pipe diameter Tightening torque
mm N·m kgf·cm
6.35 13.7 to 17.7 140 to 180
12.7 49.0 to 56.4 500 to 575
15.88 73.5 to 78.4 750 to 800
2 Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for indoor unit.
For tightening, use a torque wrench or spanner and use the same tightening torque applied for indoor unit.
WARNING
When installing the unit, securely connect the refrigerant pipes before starting the compressor.
PURGING PROCEDURES
Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor and the outdoor unit.
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will not work in it initial state fresh out of the factory (totally closed with cap on).)
Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit.
Run the vacuum pump. (Vacuumize for more than 15 minutes.)
Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum pump.
Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same position. Confirm that the pressure gauge shows–0.101 Mpa [Gauge] (–760 mmHg).
*Close
*Open
Hexagonal wrench
Stop valve
*4 to 5 turns
Stop valve
(or the vacuum pump with the function to prevent the back flow)
Gauge manifold valve (for R410A)
Pressure gauge (for R410A)
Compound pressure gauge (for R410A)
-0.101MPa (-760 mmHg)
Handle Low
Handle High
Window
Charge hose (for R410A)
Vacuum pump
Adapter for preventing the back flow
Charge hose (for R410A)
Service port
Stop valve
6-4 PURGING PROCEDURES·LEAK TEST
INSULATION AND TAPING
1 Cover piping joints with pipe cover. 2 For outdoor unit side, surely insulate every piping including valves. 3 Using piping tape G, apply taping starting from the entry of outdoor unit.
Stop the end of piping tape G with tape (with adhesive agent attached).
When piping have to be arranged through above ceiling, closet or where the temperature and humidity are high, wind additional commercially sold insulation for prevention of condensation.
Pipe length up to 7 m No gas charge is needed.
Pipe length exceeding 7 m Charge the prescribed amount of gas. (refer to 3)
Remove the gauge manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without fully opening lowers the performance and this causes trouble.
Tighten the cap to the service port to obtain the initial status.
Retighten the cap.
Leak test
6-5 TEST RUN
MS type
Before performing the test run, recheck for any wrong wiring. Wrong wiring prevents normal operation or results in blown fuse disabling operation.
The test run can be started by pressing EMERGENCY OPERATION switch. When the EMERGENCY OPERATION switch is once pressed, the unit will start the test run (continuous operation) for 30 minutes. A thermostat does not work during this time. After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 24°C in COOL MODE.
Perform test run in the following procedure.
PROCEDURE
Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts. 2 Press it once more, and the operation stops.
(The operation mode alternates between 1 and 2 every time the EMERGENCY OPERATION switch is pressed.)
EMERGENCY OPERATION switch
Mode
Operation Indicator lamp
1
COOL
(Light) (Off)
2
STOP
(Off) (Off)
EMERGENCY OPERATION switch
Mode
Operation Indicator lamp
1
COOL
(Light) (Off)
2
HEAT
(Off) (Light)
3
STOP
(Off) (Off)
MSH type
Before performing the test run, recheck any wrong wiring. Wrong wiring prevents normal operation or results in blown fuse disabling operation.
The test run can be started by pressing EMERGENCY OPERATION switch. When the EMERGENCY OPERATION switch is once pressed, the unit will start the test run (con­tinuous operation) for 30 minutes. A thermostat does not work during this time. After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 24°C in COOL MODE or HEAT MODE.
Perform test run in the following procedure.
PROCEDURE
Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.
If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect the indoor/outdoor unit connecting wire A for mis-wiring.
2 Press it once more, and the EMERGENCY HEAT MODE starts. 3 Press it once more, and the operation stops.
(The operation mode changes in order of 1 ~ 3 every time the EMERGENCY OPERATION switch is pressed.)
In starting the heating operation, indoor unit fan may not operate to prevent blowing cool air. Please wait for a few minutes until the temperature of heat exchanger rises and warm air blows out.
Tightening torque
N·m kgf·cm
Cap for service port 13.7 to 17.7 140 to 180
Cap for stop valve 19.6 to 29.4 200 to 300
Page 8
7-3 GAS CHARGE
1 Connect gas cylinder to the service port of stop valve (3-way). 2 Execute air purge of the pipe (or hose) coming from refrigerant gas cylinder. 3 Replenish specified amount of the refrigerant, while operating the air conditioner
for cooling.
Note:
In case of adding refrigerant, comply with the quantity specified for the refrigerating cycle.
CAUTION
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 40°C) during cold season. But never use naked fire or steam.
Union
Indoor unit
Liquid pipe
Gas pipe
Stop valve
Service port
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN AUTHORIZED REPRESENTATIVE IN EU: MITSUBISHI ELECTRIC EUROPE B.V. HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.
This product is designed and intended for use in the residential, commercial and light-industrial environment.
The product at hand is based on • Low Voltage Directive 2006/95/EC the following EU regulations: • Electromagnetic Compatibility Directive 2004/108/
EC
7-4 PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/cm2).
4) Start the emergency COOL operation.
To start the emergency operation in COOL mode, disconnect the power
supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/ cm
2
).
6) Stop the emergency COOL operation.
Press the E.O. SW twice to stop the operation.
WARNING
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it.
MS type and MSH type
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and check that an electronic sound is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
If the indoor unit is operated with the remote controller, both the test run and the emergency operation are released by commands from the remote controller.
Once the compressor stops, the restart preventive device operates so the compressor will not operate for three minutes to protect the air conditioner.
6-6 EXPLANATION TO THE CUSTOMER
Using the OPERATING INSTRUCTIONS, explain the following to the customer, how to control temperature, how to remove the air filters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.
Recommend the customer to read the OPERATING INSTRUCTIONS carefully.
1 Remove the screw caps. 2 Remove three screws.
3 Pull the bottom.
Hold this concave section and pull the bottom forward to remove the front panel.
4 Release the hooks.
Push
Go down
Square hole
5 Push
Horizontal vane
3
2 4
1 Point the
horizontal vane slightly downward.
7. FOR MOVEMENT AND MAINTENANCE
7-1 REMOVING AND REINSTALLING THE FRONT PANEL
FRONT PANEL REMOVAL
FRONT PANEL REINSTALLATION
Note:
Do not open the front panel up beyond the level position. The panel may come off in order to prevent it from being damaged. 1 Set the horizontal vane to the position as below before reinstalling the front
panel.
2 Attach the bottom of the front panel under the horizontal vane. 3 Fit in the top of the front panel. 4 Fit in the bottom of the front panel and tighten it using screws. 5 Push the section of the front panel marked by the arrow and fit the panel into the
air conditioner.
7-2 REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
1 Remove the front panel. (See FRONT PANEL REMOVAL shown above.) 2 Insert flat screwdrivers into the square holes at the left and right bottom of the
indoor unit and push them up; the bottom of the indoor unit goes down and the hooks are released.
Loading...