•Refer to the Service Manual OB185 REVISED EDITION C when MSH-18NV-is connected with
MXZ-32NV-or MXZ-32NV-as multi system units.
•Refer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV-is connected with
MXZ-32RV-as multi system units.
E1
E2E1
E4
E4
Page 2
1
TECHNICAL CHANGES
MSH-18NV-became possible the connection to MXZ-32RV-as multi system units.
2
INDOOR UNIT
MSH-18NV -
PART NAMES AND FUNCTIONS
E4
E1E4
Front panel
(When the grille is open)
2
Page 3
OUTDOOR UNIT
MUH-18NV -
E4
Air inlet
(back and side)
Piping
Drainage hose
Air outlet
Drain outlet
REMOTE CONTROLLER
MSH-18NV -
E4
Signal transmitting section
Operation display section
OPERATE/STOP
(ON/OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
SLEEP button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIMER SET button)
TEMPERATURE buttons
VANE CONTROL button
SWING button
OFF-TIMER button
RESET button
3
Page 4
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity
Dehumidification
Air flow(Hi)
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding resistance(at20:)
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
Refrigerant filling capacity(R-22)
Refrigerating oil (Model)
Thermistor
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at25:)
RT12(at25:)
RT61(at0:)
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
"
mm
mm
mm
mm
mm
mm
kg
kg
dB
dB
rpm
rpm
kg
cc
k"
k"
k"
MSH-18NV -
E4
Single phase,220-240V,50Hz
INDOOR 756 OUTDOOR 2142-2244
15
52-58
INDOOR 0.25 OUTDOOR 0.39
PH-36VPET
1600
C-R1.03 C-S2.04
RA4V27-EA or EF
WHT-BLK183.8 BLK-RED250.5
RA6V50-OF or OG
WHT-BLK116.4 BLK-RED111.0
1,015
320
190
850
605
290
14
54
5
42
52
1,180
810-845
4
1
1.65
900 (MS32N1)
10
10
33.18
Cooling
5.1
2.5
9.4-9.2
2,030-2,120
—
98-96
8.76-8.56
2.51-2.41
Heating
5.4
—
9.2-9.0
1,980-2,070
—
98-96
8.56-8.36
2.73-2.61
WMSH-18NV- E4 (INDOOR UNIT)
Cooling Heating
Single phase,220-240V,50Hz
— —
—
756
10
0.28
60
—
97-89
—
—
0.25
—
—
—
—
RA4V27-EA or EF
WHT-BLK183.8 BLK-RED250.5
—
—
1,015
320
190
—
—
—
14
—
5
42
—
1,180
—
4
—
—
—
10
10
—
3
SPECIFICATION
E4
E4
wRefer to the Service Manual OB185 REVISED EDITION C when MSH-18NV-is connected with
MXZ-32NV-or MXZ-32NV-as multi system units.
E2E1
wRefer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV-is connected with
w Height difference should be within 5m
regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Model
MSH-18NV -
E4
Refrigerant piping length (one way)
Outdoor unit precharged
(up to 7m)
1650
15m
400
7m
0
10m
150
REFRIGERANT SYSTEM DIAGRAM
MSH-18NV -
INDOOR UNIT
Indoor
heat
exchanger
Room temperature
thermistor
RT11
E4
Indoor coil
thermistor
RT12
Distributor
Refrigerant pipe [15.88
(Option)
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe[ 6.35
(Option)
(with heat insulator)
Muffler
Stop valve
(with service port)
Accumulator
Strainer
Stop valve
Reversing valve
(4- way valve)
Capillary tube
[3.0o[2.0o500
Check
valve
Strainer
Compressor
Refrigerant flow in cooling
Refrigerant flow in heating
MUH-18NV -
OUTDOOR UNIT
Outdoor
Defrost
thermistor
RT61
heat
exchanger
Capillary tube
[3.0o[1.6o750
(2 pcs)
Reversing valve coil
(4-way valve coil)
Heating ON
Cooling OFF
E4
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R-22 : g)
7
Calculation : Xg=50g/m ✕ (A-7)m
Page 8
7
Wet-and dry-bulb
thermometers
Wet-and dry-bulb
thermometers
PERFORMANCE CURVES
MSH-18NV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor outlet air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°CDB
(6) Outdoor intake air wet-bulb temperature :°CWB
(7) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the
difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for
your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
E4
), 50Hz
Cooling
}
Heating
}
INDOOR UNIT
12.2
11.2
10.1
9.1
8.2
7.2
OUTDOOR UNIT
MSH-18NV - E4
8
Page 9
28.0
1520
50
25
60
30
70(%)
35(:)
0.3
0.4
0.5
0.6
0.7
1832
220V/240V
7
6
5
4
3
1520
50
25
60
30
70(%)
35(:)
6
7
8
9
10
11
1832
220V/240V
25.9
23.7
21.6
19.4
17.2
15.1
12.9
NOTE:The above curves are for the heating operation without any frost.
MSH-18NV - E4
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
11
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20
25
Relative humidity(%)
50
60
3070
22
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa • G) =10.2(kgf/ff• G)
(kgf/F•G)(MPa•G)
MUH-18NV -
Outdoor low pressure
Ambient temperature(˚C)
Ambient humidity(%)
E4
MUH-18NV -
Outdoor unit current (A)
Ambient temperature(˚C)
Ambient humidity(%)
E4
HEAT operation
Condition indoor:Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
Outdoor:Dry bulb temperature 7,15,20°C
Wet bulb temperature 6,12,14.5°C
E4
220V/240V
10
11
MUH-18NV -
9
8
Outdoor unit current (A)
7
5 10152025
7
21
(:)
Ambient temperature(˚C)
9
Page 10
8
lighting
not lighting
Approx. 2 :
or more
Difference
betweeen set
temperature
and room
temperature
Approx. 2 :
or less
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait unit the
target temperature is
obtained.
This shows that the
room temperature is
approaching the
target temperature.
Operation state
Indication
Operation Indicator
Operation Indicator lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
INDOOR UNIT DISPLAY SECTION
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
25: or more
23:to 25:
less than 23:
MICROPROCESSOR CONTROL
WIRELESS REMOTE CONTROLLER
MSH-18NV -
Once the operation mode are set, the same operation mode
can be repeated by simply turning the OPERATE/STOP
(ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
E4
8-1. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote
controller. Operation Indicator lamp of the indoor unit
turns on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL
CONTROL”(). Then a beep tone is heard.
(3) The operation mode is determined by the room
temperature at start-up of the operation.
• Once the mode is fixed, the mode does not change by
room temperature afterwards.
• Under the ON-TIMER () operation, mode is
determined according to the room temperature as the
operation starts.
• When the system is stopped with the OPERATE/STOP
(ON/OFF) button on the remote controller, and restarted
within 2 hours in “I FEEL CONTROL” () mode, the
system operates in previous mode automatically
regardless of the room temperature.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the
operation mode is determined by the room temperature
at start-up of the operation.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
10
Restart
COOL mode of
“I FEEL CONTROL”
Restart
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that
determined by room
temperature at start-up
of the operation.
Page 11
(4) The initial set temperature is decided by the initial room temperature.
Difference between room
temperature and set temperature
during operation.
1deg. 1.7deg.
2deg. 4deg.
Model
COOL mode of
"I FEEL CONTROL"
Initial room temperatureInitial set temperature
26: or more
25: to 26:
Initial room temperature
24:
minus 2:
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
23: to 25:
less than 23:
Initial room temperature
minus 2:
26:
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature
regardless of room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” () mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Each time the TOO WARM or TOO COOL button is pressed,the indoor unit receives the signal and emits a beep tone.
• Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
❈1
▲ TOO
COOL… To raise the set temperature 1~2 degrees(°C)
▼ TOO
WARM … To lower the set temperature 1~2 degrees(°C)
— COOL mode of “I FEEL CONTROL” —
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In AUTO the fan speed is as follows.
Initial temperature difference Fan Speed
Room temperature minus set temperature : 2 degrees or more
Room temperature minus set temperature : Between 1 and 2 degrees
Room temperature minus set temperature : less than 1 degree
2. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads 3°C or below, the coil frost prevention mode starts immediately.
However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 3°C this mode prolonged until the RT12 reads over 3°C.
····························Hi
·················Me
····························
Lo
11
Page 12
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Lo or Me.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the
beginning.
Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds
26°C.However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
Operation chart
Example
Compressor
Outdoor fan
Indoor fan
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Lo.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
•When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
•When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
(continuously at set speed)
ON
ON
OFF
ON
Operation time chart
Example
Thermostat
Indoor fan
Outdoor fan
Compressor
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Lo.
OFF
ON
OFF
OFF
8 min.
ON
ON
OFF
OFF
ON
ON
3 min.
OFF
OFF
4 min.
OFF
ON
ON
1 min.
ON
12
Page 13
Difference between room
temperature and set temperature
during operation.
1deg. 1.7deg.
2deg. 4deg.
— HEAT mode of “I FEEL CONTROL” —
Released
Cold Air Prevention
18: 22:
Fan speed
Set speed
VLo or stop
High pressure protection
Released
56:60:
ON
Outdoor fan
OFF
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more················································· Hi
Set temperature minus room temperature: Between 1 and 2 degrees····································· Me
Set temperature minus room temperature: less than 1 degree················································· Lo
(2) Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at VLo
when the temperature of indoor coil thermistor RT12 is below 18°C. But the fan stops when the indoor fan operates at
VLo and the room temperature is 15°C or less.
NOTE : At initial in hysteresis this control works.
(3) Warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil
thermistor RT12 temperature to blow out warm air.
After releasing of cold air prevention, when the indoor coil temperature is 37°C or above, the fan speed shifts to the set
speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.
When the indoor coil temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed>
less than 2 minutes························Lo
2 minutes to 4 minutes···················Me
4 minutes or more··························Hi
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at VLo.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start at set speed until the indoor coil thermistor RT12 reads 22°C or more.
Initial temperature differenceFan speed
2. High pressure protection
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess
rise protection of compressor discharge pressure.
Outdoor fan OFF: 60°C
Outdoor fan ON : 56°C
NOTE 1 During high pressure protection and for 4 minutes and 15 seconds after high pressure protection, defrosting of
NOTE 2 When connected to MXZ-32NV- or MXZ-32NV- or MXZ-32RV- outdoor unit, the indoor unit send the data
High pressure protection chart
Example
Indoor coil thermistor
RT12 temperature
60˚C
Outdoor fan motor
turn OFF
56˚C
Outdoor fan motor
turn ON
Outdoor fan motor
ON
OFF
ON
OFF
outdoor heat exchanger is not detected by the defrost thermistor RT61.
E1E2E1
for the temperature to the outdoor unit according to the indoor coil temperature.
For the further information, refer to the service manual No.OB185 REVISED EDITION C(Outdoor unit: MXZ-32NVor MXZ-32NV- ) or the service manual No.OB227 REVISED EDITION-B(Outdoor unit: MXZ-32RV- ).
13
E1E2
E1
Page 14
3. Defrosting
Defrosting of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.
(1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the defrosting
operation working.
b) The defrost thermistor RT61 reads - 3°C or less.
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 3°C or more.
e) The defrosting time exceeds 10 minutes.
(3) Defrosting time chart
Defrost thermistor RT61
3: or more
-3: or less
Outdoor 52C
contactor(Compressor)
ON
OFF
X62
(Reversing valve coil)
ON
OFF
SR61
Outdoor fan
Defrost
counter
Indoor fan
ON
OFF
ON
OFF
ON
VLo
OFF
Indoor vane
Horizontal
Set position
30 sec.
NOTE1
15 sec.
30 sec.
5~15 sec.
Max 10 min.
NOTE1 • When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.
• When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
NOTE2 • Refer to the Service Manual OB185 REVISED EDITION C when MSH-18NV-is connected with
MXZ-32NV-or MXZ-32NV- as multi system units.
E2E1
• Refer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV-is connected with
MXZ-32RV-as multi system units.
E1
E4
E4
14
Page 15
4. Reversing valve control
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE1 The Reversing valve reverses for 5 seconds right before start-up of the compressor.
NOTE2 • Refer to the Service Manual OB185 REVISED EDITION C when MSH-18NV-is connected with MXZ-32NV-
or MXZ-32NV- as multi system units.
E2
• Refer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV-is connected with MXZ-32RVas multi system units.
E1E4
E1E4
(COOL / DRY)
5 sec.
Compressor
ON
OFF
ON
Reversing valve
OFF
ON
Outdoor fan
OFF
8-2. COOL () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
Operation Indicator lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION
SELECT button.
(3) Press the TEMPERATURES button.
(TOO WARM or TOO COOL button) to select
the desired temperature.
The setting range is 16 ~ 31°C.
✻ Indoor fan continues to operate regardless of
thermostat’s OFF-ON at set speed.
✻ Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”.
8-3. DRY () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
Operation Indicator lamp of the indoor unit turns
on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room
temperature and determines the set
temperature. Set temperature is as shown on
the right chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY mode of
“I FEEL CONTROL”.
(4) DRY operation will not function when the room
temperature is 13°C or below.
(5) When DRY operation functions, the fan speed
is lower than cool operation.
(HEAT)
5 sec.
ON
OFF
ON
OFF
ON
OFF
8-4. HEAT () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
Operation Indicator lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with the OPERATION SELECT button.
(3) Press TEMPERATURES button (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
(4) Indoor fan speed control, high pressure protection, defrosting, reversing valve control are the same as HEAT mode of “I
15
Page 16
SLEEP
8-5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed
back the rotational frequency. Comparing the current rotational frequency with the target rotational frequency
(Hi,Me,Lo,SLEEP), the microprocessor controls IC141 and adjusts fan motor electric current to make the current
rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the
rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot
detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut
off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the Operation
Indicator lamp flashes on and off to show the fan motor abnormality. (See page 23.)
8-6. AUTO VANE OPERATION
(1) Vane motor drive
This model is equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the
motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL () button.
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP (ON/OFF) button is pressed.
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO () mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
① In COOL and DRY operation
Vane angle is fixed to Angle 1.
➁ In HEAT operation
Vane angle is fixed to Angle 4.
16
Page 17
(5) Dew prevention
Released
Cold Air Prevention
24:28:
Angle 1
Horizontal vane
Set position
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour,
the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE ()
By pressing the SWING button () the horizontal vane swings vertically. The remote controller displays “”. SWING
mode is cancelled when the SWING button or VANE CONTROLbutton () is pressed or the mode is changed to other
mode.
(7) Cold air prevention in HEAT operation
When any of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1
automatically to prevent cold air blowing on users.
① Compressor is not operating.
➁ Defrosting is performed.
➂ Indoor coil thermistor RT12 reads 24: or below.
➃ Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor RT12 temperature
NOTE:At initial in hysteresis this control works.
8-7. SLEEP MODE ()
• When the SLEEP button () is pressed, the indoor fan speed drops and the air flow sound from the indoor
unit is decreased.
• The indications of the remote controller are “” and “”.
• When the FAN SPEED CONTROL button ( ) or the SLEEP button () or mode change button is pressed during
the SLEEP mode, the SLEEP mode is released.
8-8. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
“” button... AUTO START operation (ON timer)
“” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” mark is flashing.
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• Apower failure occurs.
•The circuit breaker functions.
2. Cancel
TIME setting can be cancelled with the TIMER CONTROL buttons. (“” or “”)
To cancel the ON timer, press the “” button.
To cancel the OFF timer, press the “” button.
TIME is cancelled and the display of set time disappears.
17
Page 18
PROGRAM TIMER
EMERGENCY OPERATION switch
Press once <Cool>
Press again<Heat>
Press once again <Stop>
Operation Indicator lamp
• The OFF timer and ON timer can be used in combination.
• “” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
8-9. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION switch
on the front of the indoor unit. The unit will start and the Operation Indicator lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan runs at high notch
and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation the system shifts to
The fan shifts to Me notch.
This operation continues until the EMERGENCY OPERATION switch is pressed again or the unit receives any signal from
the remote controller. In case of latter normal operation will start.
The coil frost prevention works even in this operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO mode.
EMERGENCY COOL/HEAT MODE
with a set temperature of 24°C.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
18
Page 19
9
Jumper wire
JPC
JPE
Change point
Defrost interval time changes from 40 minutes to 15 minutes
Deforst start temperature changes from -3: to 0:
Deforst finish temperature changes from 3: to 10:.
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Cut J1
–
–
3 units operation
Same as at left
Same as at left
Cut J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Cut both J1 and J2
SERVICE FUNCTIONS
MSH-18NV -
E4
9-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished
regardless of the defrost interval restriction. See page 29.
Defrost thermistor RT61 must read below -3°C.
9-2. CHANGE IN DEFROST SETTING
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (See page 29.)
<JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed. (See page 29.)
9-3. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows.
3-minutes delay : 3-minutes ➔ 3-seconds.
AUTO START : 1 hour ➔ 1-minute
AUTO STOP : 1 hour ➔ 1-minute
Short the connector during the timer mode.
}
9-4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodelling, take out
the batteries at first.
After finish remodelling, put
back the batteries then
push the RESET button.
The P.C.board has the print “J1” and “J2”.Jumper wires are mounted to each “J1” and “J2”.Cut J1 and J2 according to the
number of indoor unit as shown in Table. 1.
After modification, push the reset button.
Table.1
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When
the power supply is turned on and indoor unit receives the first signals from the remote controller, the
remote controller number is designated as the indoor unit number. Therefore at and after the second
time indoor unit accepts the remote controller of the initial setting number.
At setting - error, turn the power supply off to cancel the individual operation and then turn the power
supply on to restart the setting.
19
Page 20
JR06
CN102
CN151
CN112 CN111CN121
CN101
BZ
SW
52C
IC101RA102
IC141
CN211
C11CN201
9-5. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power
has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL
CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is
decided by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Remove the electronic control P.C. board and the display P.C.board. (See page 30.)
3Cut the RESISTOR JR06 on the indoor electronic control P.C.board.
Operation
1If the main power (220/240V AC) has been cut, the operation settings remain.
2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE
•The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
•If main power is turned off or a power failure occurs while AUTO START/STOP timer is active ,the timer setting is
cancelled.
•If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
•To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
•When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
20
Page 21
10TROUBLESHOOTING
Lead wiring
Housing point
RESET button
MSH-18NV -
E4
10-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
(2) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
(3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the Operation Indicator lamp on the indoor unit is flashing on and off to indicate an abnormality. To
make sure, check how many times the abnormality indication is flashing on and off before starting service work.
(2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration.
(3) When troubleshooting, refer to the flow chart on page 22 and the check table on page 23.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote controller
normally, discharge the remote controller in the following order.
This remote controller has the RESET button. After refilling new batteries, press the RESET button with tip end of ball
point pen or the like, and then use the remote controller.
NOTE: INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
(OUTDOOR UNIT : MXZ-32NV-, MXZ-32NV-
Multi system air conditioner (Outdoor unit: MXZ-32NV-, MXZ-32NV-, MXZ-32RV-) can connect two or more
indoor units with one outdoor unit.
According to the capacity, two or more units can operate simultaneously.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the
other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units that
will start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the
indoor units to the same operation mode.
•When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes
(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing
may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
, MXZ-32RV-)
E1E2E1
Operation Indicator
21
E1E2E1
lighting
flashing
Page 22
10-2. Instruction of troubleshooting
Start
Indoor unit
operates. Outdoor
unit doesn’t
Outdoor unit
operates in
only Test
Run
operation.
Check room
temperature
thermistor.
Outdoor unit
doesn’t
operate even
in Test Run
operation.
Refer to
“Check of
outdoor unit”
on page 26.
Refer to
“How to check
mis-wiring and
signal error
(when outdoor unit
doesn’t work)”
on page 27.❈1
D
E
Indoor unit
doesn’t receive
the signal from
remote
controller.
Refer to “Check
of remote controller
and receiver P.C.
board” on page 25.
1-time flash
Cause:indoor/outdoor unit
connecting
Trouble of mis-wiring
(
Trouble of the serial signal
B
Check indoor coil
thermistor. Refer
to“Test point
diagram and
voltage” on page
28.
Operation Indicator lamp
on the indoor unit is
flashing on and off.
2-time flash
2.5-second OFF
3-time flash
2.5-second OFF
Cause:Indoor unit
2-time-Room
temperature/Indoo
r coil thermistor
trouble
3-time-Indoor fan motor
trouble
Refer to
“Check of indoor
fan motor” on
page 25.
Indoor unit doesn’t
receive the signal from
remote controller.
Also, Operation Indicator
lamp doesn’t flash, when
the EMERGENCY
OPERATION switch is
pressed.
Refer to “Check of
indoor electronic control
P.C. board” on page 26.
6-time flash
Cause:outdoor unit
6-time-check the defrost
A
Check room temperature
thermistor. Refer to“Test
point diagram and
voltage” on page 28.
C
2.5-second OFF
thermistor
❈1<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the
indication shows “the trouble of mis-wiring.”
22
Page 23
1. troubleshooting check table
Operation Indicator
Operation Indicator
❈ Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
NO.
Abnormal
point
Indication
Symptom
Detect method
Check point
Mis-wiring
1
Serial
signal
Indoor coil
thermistor
2
Room
temperatur
e
thermistor
Indoor fan
3
motor
Defrost
4
thermistor
❈
Outdoor
power
5
system
❈
Outdoor
control
6
P.C. board
❈
Outdoor
control
7
P.C. board
❈
Outdoor
control
8
P.C. board
❈
The indication is shown only when the indoor unit connects with the outdoor unit MXZ-32NV-or MXZ-32NV-or
MXZ-32RV-.
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
2-time flash
2.5-second OFF
3-time flash
2.5-second OFF
6-time flash
2.5-second OFF
5-time flash
2.5-second OFF
7-time flash
10-time flash
lighting 2.5-second OFF
flashing
E1
2.5-second OFF
2.5-second OFF
Outdoor unit
does not run.
Outdoor unit
does not run.
Indoor fan motor
repeats 12
seconds ON and
3 minutes OFF.
When the indoor
fan breaks, the
fan motor keeps
stopping.
Outdoor unit
does not run
Outdoor unit
does not run
Outdoor unit
does not run
Outdoor unit
does not run
Outdoor unit
runs but the
indoor unit does
not run.
23
When serial signal stops for 4
to 5 seconds after 1st on of
52C relay by POWER turning
on.
When serial signal from
outdoor unit stops for 4 to 5
seconds.
Detect Indoor coil/room
temperature thermistor short
or open circuit every 8
seconds during operation.
When rotational frequency
feedback signal is not emit
during 12-second indoor fan
operation.
When the defrost thermistor
shorts or opens after the
compressor start-up.
When the compressor
operation is continuously three
times interrupted by over
current protection within 1
minute after start-up , it stops
operation.
The outdoor unit stops
operation when it cannot
properly read data in the
nonvolatile memory of the
outdoor control P.C.board.
When the indoor unit detects
drain abnormality and the
indoor coil temperature is too
low.
When the operation mode of
each rooms is set
COOL(includes DRY) and
HEAT at same time, it take
precedence the operation
mode runs first.
● Check wiring (visual check and
conductivity check).
● Check indoor electronic control
P.C.board.
● Check outdoor DEICER P.C. board.
● Check electrical parts.
● Check resistance of thermistor.
● Reconnect connector.
● Check indoor electronic control P.C.board.
● Disconnect connector CN211 and then
check connector CN121 - to make
sure rotational frequency feedback signal
of 1.5V or over exists.
● Check indoor electronic control P.C.
board.
● Check indoor fan motor.
● Reconnect connector.
● Check outdoor DEICER P.C. board.
● Check resistance of thermistor.
● Reconnect connector.
● Check the inverter output.
● Check the compressor.
● Check the outdoor control P.C.board.
● Check the drain pump.
● Check the drain sensor.
● Check LEV.
● Adjust the operation mode.
2
3
E2E1
Page 24
2. Trouble criterion of main parts
P
~
BLK
R
MAIN
AUX
RED
S
C
WHT
MAIN
AUX
BLK
RED
WHTORN
P
MSH-18NV -
E4
Part name
Room
temperature
thermistor
Indoor coil
thermistor
Defrost
thermistor
Compressor
Indoor fan
motor
Check method and criterion
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Normal
8k½ ~ 20k½
Opened or short-circuited
Abnormal
Measure the resistance with a tester.
(Part temperature –10°C ~ 40°C)
Normal
5k½ ~ 60k½
Opened or short-circuited
Abnormal
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
Normal
C-R
C-S
0.90½ ~ 1.11½
1.79½ ~ 2.20½
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Normal
Motor part
WHT-BLK
BLK-RED
176 ~ 192½
240 ~ 261½
Measure the voltage Power ON.
Normal
Sensor part
BRN-YLW
YLW-GRY
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V
(Approx.)
Abnormal
Opened or
short-circuited
Abnormal
Opened or
short-circuited
Abnormal
Remain 0V or 5V
FUSE
Figure
MAIN
AUX
BLK
YLW
BRN
GRY
RED
WHT
Outdoor fan
motor
Vane motor
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
Normal
WHT-BLK
BLK-RED
102 ~ 126½
97.9 ~ 120½
Measure the resistance between the terminals with a tester.
(Part temperature10°C ~ 30°C)
Normal
358 ~ 388½
Opened or short-circuited
Abnormal
Abnormal
Opened or
short-circuited
PNK
ORN
RED
YLW
P
INNER PROTECTOR
ROTOR
BLU
24
Page 25
A
Check of indoor fan motor
Indoor fan does not operate.
No
Reconnect the lead wires.
Check of remote controller and receiver P.C. board
B
Are lead wires connected?
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.1 and No.2.
Turn OFF the power supply.
Check connector CN211 visually.
Yes
Is resistance 0 (short circuit) or ° (open circuit)?
Yes ( 0 or ° )
Repair the indoor fan motor.
Is soldered point normal?
No
Yes
Insert screwdriver into air outlet to rotate indoor fan
motor slowly for 1 revolution or over, and measure
voltage No.2(+) and No.3(-) on CN121.
No
(others)
No
Does voltage repeat 0V DC and 5V DC?
Yes
Replace the indoor electronic control P.C. board.
Resolder it.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote
controller.
w Check if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the the remote
controller visible?
Yes
Remove the batteries and then set them
back. Check if the unit operates with the
remote controller.
Does the unit operate with the
remote controller?
Yes
OK
No
(not clear)
No
Measure the voltage between receiver P.C. board connector No.2
pressed.
Replace the batteries.(See page 21.)
Turn on a radio to AM and press switch on
the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
No
No
Yes
Replace the remote controller.
● Re-install the unit away from lights.
● Attach a filter on receiving part.
(+)
and No.1 when the remote controller button is
Is the voltage approx. 4V DC?
No(5V or 0V DC)
Replace the receiver P.C. board.
25
Yes
Replace the indoor electronic control P.C.
board.
Page 26
Check of indoor electronic control P.C. board
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Replace the fuse.
Is fuse(F11) blown?
Be sure to check both fuse
and varistor in any case.
Replace the fan
motor.
Replace the indoor
electronic control
P.C. board.
Is winding
resistance of
fan motor 0 "?
Is winding
resistance of
vane motor 0 "?
No
Yes
Replace the vane
motor.
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
No
No
The unit doesn’t operate with the remote controller.
Also, the Operation Indicator lamp doesn’t light up
by pressing the EMERGENCY OPERATION switch.
No
Yes
Measure the
resistance between
CN201
1on the
indoor electronic
control P.C. board
and
N on the terminal
block with the tester.
Is resistance approx. 0"?
Replace the fuse (F12).
CN201
1
2
L
N
F12
1
3
Terminal
block
Be sure to check both resistance.
No(°)
Yes
Turn OFF the
power supply.
Turn OFF the
power supply.
C
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by
pressing the EMERGENCY OPERATION switch.
D
Check of outdoor unit
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
Start
Press the EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Check the voltage to the terminal block of outdoor
unit. Is there 220-240V AC to the terminal block
between - ?
Check the voltage to the terminal block of indoor unit.
Is there 220-240V AC to the terminal block between
N
2
- ?
2
N
Replace the indoor
electronic control P.C.
No
No
Yes
Yes
Check the outdoor DEICER P.C.board at first, then check
the outdoor fan motor and the compressor.
Check the continuity of indoor and outdoor unit connection.
26
Page 27
How to check mis-wiring and serial signal error (when outdoor unit does not work)
E
Start
3 min. later, when 52C contactor turns ON, what self-check result
is displayed on Operation Indicator lamp on the indoor unit? ❈1
Repair wiring.
Yes
1. Turn OFF the power supply and disconnect in-out connecting wire on the indoor side.
2. Short-circuit between indoor terminal block and .
3. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Is there 20V DC between both ends of R132 when
52C contactor turns ON?
( By tester, the stylus is between 0 ~ 20V. )
Yes
1. Turn OFF the power supply.
2. Reconnect in-out connecting wire.
3. Turn ON the power supply.
1. Turn OFF the power supply.
2. Turn ON the power supply.
3. Press the
EMERGENCY OPERATION
switch.
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)
Is there mis-wiring, poor contact, or wire disconnection?
No
3
N
No
❈1 Short circuit of JPG and JPS on the
indoor electronic control P.C. board
enables self-check to be displayed in 3
seconds.
Serial signal error is indicated.
(0.5-sec.ON, 2.5-sec.OFF)
Replace the indoor electronic control
P.C. board.
3 minutes later, when the EMERGENCY OPERATION switch is
pressed and 52C contactor turns ON, is there 220-240V AC between
N
the outdoor terminal block -? ❈2
2
Yes
Is there 5V DC between
+
–
J8 -J9 on the outdoor DEICER P.C. board? ❈2
No
Yes
Is there 10V DC between both ends of R601? ❈2
No
(By tester, the stylus is between 5 ~10V)
Yes
Replace the outdoor DEICER P.C. board.
No
Rectify in-out connecting wire.
Check and rectify the fuse and the varistor
on the outdoor DEICER P.C. board.
Rectify in-out connecting wire.
❈2 While the serial signal error is indicated,
52C contactor alternates ON for about 10
seconds and OFF for 3 minutes.
Measure the voltage when 52C contactor
is ON.
27
Page 28
TEST POINT DIAGRAM AND VOLTAGE
MSH-18NV -
E4
Fan motor power supply
Fuse 250V AC 3.15A
Power supply input
220-240V AC
}
R132
0~20V DC
C144
+
5V DC
}
C144
Room temperature
thermistor(RT11)
Indoor coil thermistor(RT12)
JPS
Time short mode point
JPG
Emergency operation switch
JPG
12V DC
}
+
JP41
P.C.board
28
Page 29
MUH-18NV Outdoor deicer P.C. board
E4
Outdoor fan motor
220-240V AC
}
Reversing valve
coil
220-240V AC
}
R601
5~10V DC
}
+
INPUT
220-240V AC
}
Defrost thermistor(RT61)
}
Fuse 2A/250V
Defrost interval
time short pin
+
J9
}
J8
5V DC
}
12V DC
+
+
}
52C
12V DC
29
Jumper wire for change in
defrost setting (JPC, JPE)
(See page 19.)
Page 30
11
(1)
(2)
1Slide the sleeve.
2Pull the terminal while
pushing the locking
lever.
1Hold the sleeve, and
pull out the terminal
slowly.
In the case of terminal with lock mechanism, detach the terminal as shown below.
<"Terminal with lock mechanism" Detaching points>
NOTE:
DISASSEMBLY INSTRUCTIONS
11-1. MSH-18NV -
E4
INDOOR UNIT
OPERATING PROCEDURE
1. Removing the front panel
(1) Remove the screw caps at the down of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
PHOTOS
Photo 1
Front panel
Screws
2. Removing the electronic control P.C. board
(1) Remove the front panel. (Refer to 1)
(2) Remove the electrical cover.
(3) Remove the screw, remove the terminal cover.
(4) Remove the screw of terminal block.
(5) Unhook the catch of the lamp holder.
(6) Remove the receiver holder.
(7) Disconnect the connectors and the lead wire from 52C
contactor on the electronic control P.C. board and remove
the ground and the indoor coil thermistor.
(8) Remove the electronic control P.C. board.
Photo 2
30
Ground
Indoor coil thermistor
Screw
Terminal
block
screw
Indoor
electronic
control
P.C. board
Page 31
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1)
(2) Remove the electrical cover.
(3) Disconnect the connector of the indoor coil thermistor.
(4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic
control P.C. board.
(5) Remove the screw of the electrical box, remove the
electrical box.
4. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel.
(2) Remove the electrical box.
(3) Unhook the catch on the both sides of the nozzle
assembly.
(4) Remove the nozzle assembly.
(5) Remove the screws of the bearing support.
(6) Remove the screw of the heat exchanger unhook the
catch.
(7) Lifting the heat exchanger, remove the bearing support.
(8) Remove the motor support.
(9) Loose the screw fixing the line flow fan, remove the line
flow fan.
)
(
Remove the screws of the motor band, remove the fan
10
motor.
Photo 3
Photo 4
Catch
Heat exchanger
screw
Bearing support
screws
screw
screw
Heat exchanger
31
Photo 5
Indoor fan motor
Fan
motor
screws
Line flow fanMotor band
Page 32
11-2. MUH-18NV -
E4
OUTDOOR UNIT
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet.
(2) Hold the down of the cabinet on the both side to remove
the cabinet.
Photo 1
Photo 2
Screws
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Service
panel
Photo 3
Screws
Screws
Deicer
P.C. board
32
Compressor
capacitor
Red lead wire
White lead wire
Black lead wire
Terminal
block
Page 33
OPERATING PROCEDUREPHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1)
(2) Disconnect the connector remove the clamp of fan motor
lead wire.
(3) Remove the propeller nut and remove the propeller fan.
(4) Remove screws securing the fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the soundproof felt.
(3) Remove the terminal cover on the compressor.
(4) Remove the electrical assembly.
(Refer to 2)
(5) Release gas from the refrigerant circuit.
(6) Disconnect the welded part of the discharge pipe.
(7) Disconnect the welded part of the suction pipe.
(8) Remove nuts fixing the compressor.
(9) Remove the compressor.
Photo 4
propeller fan
Outdoor
fan motor
Propeller
fan nut
Photo 5
Set screws for
outdoor fan motor
Discharge
pipe
Lead clamps
Set screws for
outdoor fan motor
Terminal cover
Suction
pipe
33
Compressor
Compressor nuts
Page 34
12PARTS LIST
Symbol
in Wiring
Diagram
Q'ty/unit
3PCS/SET
RemarksPart No.
NO.
Part Name
MSH-18NV-
1
2
3
4
5
6
7
FRONT PANEL(WH)
GRILLE(WH)
BOX(WH)
AIR FILTER
INSTALLATION PLATE
SCREW CAP(WH)
LAMP PANEL(WH)
Part number that is circled is not shown in the illustration.
12-2. INDOOR UNIT HEAT EXCHANGER
34
Page 35
MSH-18NV -(WH)
E02 139 426
E02 141 083
21
22
REMOTE CONTROLLER
REMOTE CONTROLLER HOLDER
1
1
E4
12-3. INDOOR UNIT
FUNCTIONAL PARTS
AND ELECTRICAL PARTS
SLEEVE
BEARING
11
810
15
12-4. ACCESSORY PARTS
AND REMOTE CONTROLLER
2122
7
5
3
4
1
16
14
2
INDOOR COIL
THERMISTOR
9
12
6
17
ROOM TEMPERATURE
THERMISTOR
12-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part number that are circled are not shown in the illustration.
Q'ty/unit
MSH-18NV-
(WH)
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
NO.
Part No.
1
E02 143 235
2
E02 143 040
3
E02 141 702
4
E02 141 300
5
E02 001 505
6
E02 138 395
7
E02 444 452
8
E02 141 302
9
E02 141 303
10
E02 138 329
11
E02 141 509
12
E02 198 375
13
E02 336 385
14
E02 141 468
15
E02 001 504
16
E02 138 307
17
E02 138 308
18
E02 127 382
19
E02 205 381
20
E02 138 383
Part Name
NOZZLE(WH)
VANE(WH)
DRAIN HOSE
INDOOR FAN MOTOR
FAN MOTOR RUBBER MOUNT
POWER SUPPLY CORD
ELECTRONIC CONTROL P.C. BOARD
LINE FLOW FAN
VANE MOTOR
DISPLAY P.C. BOARD
BEARING MOUNT
TERMINAL BLOCK
VARISTOR
RECEIVER P. C. BOARD
SLEEVE BEARING
INDOOR COIL THERMISTOR
ROOM TEMPERATURE THERMISTOR
FUSE
THERMAL FUSE
SURGE ABSORBER
CABINET
GRILLE
SERVICE PANEL
OUTDOOR HEAT EXCHANGER
MOTOR SUPPORT
COMPRESSOR
BASE
OUTDOOR FAN MOTOR
PROPELLER FAN
COMPRESSOR CAPACITOR
CONTACTOR
TERMINAL BLOCK
CAPILLARY TUBE
CAPILLARY TUBE
COMPRESSOR RUBBER SET
STOP VALVE(LIQUID)
STOP VALVE(GAS)
BACK PANEL
FUSE
DEICER P.C. BOARD
DEFROST THERMISTOR
REVERSING VALVE COIL
REVERSING VALVE
SURGE ABSORBER
CHECK VALVE
1
1
1
1
1
1
1
1
1
1
1
1
2
1
4
1
1
1
1
1
1
1
1
1
1
MC
MF
C1
52C
TB
F61
RT61
21S4
DSAR
PH-36VPET
RA6V50 -
55+/420V
{3.0✕{1.6✕750
{3.0✕{2.0✕500
4RUBBERS/SET
{ 6.35
{15.88
250V / 2A
NO.
MUH-18NV -
E4
12-5. OUTDOOR UNIT
STRUCTURAL PARTS
17
DEFROST
THERMISTOR
20
8
19
12
1
4
Part number that are circled are not shown in the illustration.
592
36
14
10
22
3
15
16
6
7
Page 37
Deodorizing filter (Gray sponge type)
,
Air cleanig filter (White bellows type)
Model
Part No.
MAC-1100FT
MSH-18NV-
E4
Model
Part No.
MAC-1600DF
MSH-18NV-
E4
MUH-18NV -
E4
12-6. ACCESSORY PARTS
1
2
Q'ty/unit
MUH-18NV-
1
2
1
E4
[33
[16.2
NO.
Part No.
1
E02 444 704
2
E02 444 705
3
E02 444 706
Part Name
DRAIN SOCKET
DRAIN CAP
DRAIN CAP
Symbol
in Wiring
Diagram
13OPTIONAL PARTS
13-1. AIR CLEANING FILTER
● AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
● Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.
● Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
● DO NOT reuse AIR CLEANING FILTER even if it is washed.
● DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Remarks
13-2. DEODORIZING FILTER
● DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odor of pets.
● Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
● For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
● When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
● DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
37
Page 38
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
CC
Copyright 1999 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Issued in Apr. 1999. No.OB229 REVISED EDITION-A 294
Issued in Jan. 1999. No.OB229 305
Printed in Japan
New publication, effective Apr. 1999
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.