Mitsubishi MA, PAR-21MAA Technical Manual

< for USA / Canada >
CONTENTS
I. Advantage of New MA Remote Con trol ler ........................................................................... 2
1. Weekly Timer ......................................................................................................................2
2. Easy Maintenance Function (Only for Mr. SLIM) .................................................................2
3. New Display ........................................................................................................................3
4. The Other Functions ...........................................................................................................3
4.2 Auto Off Timer ..................................................................................................................................................... 3
II. New Functions .......................................................................................................................4
III. Appearance ............................................................................................................................5
1. Display Section ...................................................................................................................5
2. Operation Section ...............................................................................................................5
IV. Easy Maintenance Function (For Mr. SLIM P series) .......................................................... 6
1. Maintenance Mode Operating Method ................................................................................6
2. Guide for Operation Condition ............................................................................................8
V. How to Select Functions of remote controller ....................................................................9
1. Function Items ....................................................................................................................9
2. Flowchart of Function Setting ...........................................................................................10
3. Screen Structure for Function Setting ...............................................................................11
4. Function Setting Mode ......................................................................................................12
4.2.1 Operation Lock (Operation Function Limit Setting) ............................................................................... 14
4.2.2 Auto Mode Setting .................................................................................................................................16
4.2.3 Temperature Range Limit Setting ..........................................................................................................18
4.3.1 Remote Controller Main/Sub Setting .....................................................................................................20
4.3.2 Timer function setting (Weekly timer/Auto off timer/Simple timer) ........................................................21
4.3.3 Contact Number Setting for Error Situation ...........................................................................................33
4.4.1 Temperature Display °F/°C Setting .......................................................................................................35
4.4.2 Inlet air Temperature Display Setting .................................................................................................... 36
4.4.3 Automatic Cooling/Heating Display Setting ...........................................................................................37
VI. Unit Function Setting by the Remote Controller (for Mr. SLIM P series) ........................38
VII. Test Run by the Remote Controller (for Mr. SLIM P series) .............................................42
1. Check Points Under Test Run ...........................................................................................42
2. Test Run using the Wired Remote Controller ....................................................................42
VIII. Self-Diagnosis by the Remote Controller (for Mr. SLIM P series) ...................................44
1. How to Proceed “Self-diagnosis” ........................................................................................44
2. Error Code List ..................................................................................................................46
IX. Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) ..........48
1. How to “Monitor the Operation Data” ................................................................................48
2. Request Code List ............................................................................................................49
X. System Control (for Mr. SLIM P series) ..............................................................................58
1. One-Remote Controller (Standard) Operation ..................................................................60
1.1 One Wired Remote Controller ........................................................................................................................... 60
2. Two-Remote Controller Operation .....................................................................................61
3. Group Control Operation (Collective Operation and Control of Multiple Refrigerant
Systems (2 to 16)) .............................................................................................................62
XI. External Dimensions ...........................................................................................................63
I. Advantage of New MA
Remote Controller
II. New Functions
III.
Appearance
IV.
Easy Maintenance Func­tion (For Mr. SLIM P series)
V. How to Select Functions
of remote controller
VI.
Unit Function Setting by the Remote Controller (for Mr. SLIM P series)
VII. Test Run by the Remote Control-
ler (for Mr. SLIM P series)
VIII.
Self-Diagnosis by the
Remote Controller (for Mr. SLIM P series)
Monitoring the Operation
IX.
Data by the remote Control­ler (for Mr. SLIM P series)
X. System Control (for Mr.
SLIM P series)
XI. External Dimensions
1
I. Advantage of New MA Remote Controller
1. Weekly Timer
The built-in weekly timer enables you not only to make on/off set tings but also temperature set tings. Up to eight pat terns can be set for each day of the week.
Saves you money
˚F
and space because
WEEKLY
ON/OFF
you need only one remote controller.
Conventional remote controller
Schedule remote controller
TIME SUN
˚F
TEMP.
Deluxe remote controller
Setting example (Restaurant in summer)
Economical operation ac cord ing to air conditioner use
80
78
76
74
72
Preset temperature (˚F)
0
*Joint research with Japan Facility Solutions, Inc.
temperature low.
hours
1
Start of daily business
10
3 5
Lunch time
Seven patterns can be set.
12 14 16 18 20 22 24 (H)
Dinner time
Set the
Busy
Quiet
hours
Set the temperature high.
6 7
End of daily business
2. Easy Maintenance Function
Enables you to check necessary data on site, drastically reducing the time required for maintenance work.
Information useful for maintenance can be dis played on the remote con trol ler.
Outdoor unit information can be checked even from inside a building. Furthermore, use of maintenance stable-operation control that fi xes the op er at ing frequency, allows smooth inspection, even for inverter models.
<Display information> Outputs data for nine items.
Compressor information Outdoor unit in for ma tion Indoor unit in for ma tion
• Accumulated operating time
• Number of ON/OFF times
• Operating current
The contact telephone number to be called when an
• Heat exchanger tem per a ture
• Discharge temperature
• Outside air temperature
• Heat exchanger tem per a ture
• Intake air temperature
• Filter operating time
Displays the contact number in case of abnormality.
error occurs is displayed au to mat i cal ly.
This helps smooth contact with appropriate personnel in when an error occurs.
The contact telephone number of the maintenance company to be called when an er­ror occurs can be registered in advance. When an error occurs, the contact telephone number will automatically appear, allowing you to call without diffi culty.
Telephone number registered in advance
Displayed alternately
2
3. New Display
Various information is displayed and conveyed clearly, enabling more ac cu rate op er a tion of the air conditioner.
3.1 Dot Liquid Crystal Display (LCD)
The dot liquid crystal display enables quick understanding of the op er a tion state.
3.2 Multi-language Display
In addition to English, contents can be displayed in seven other lan guag es.
This function makes the remote controller very useful in facilities where foreigners are present.
Display example [Operation mode] Dot liquid crystal display
Display example [Cool mode]
[Itarian]
[German]
[Chinese]
[Spanish]
[French]
TEMP.
TIME SUN
˚F
˚F
WEEKLY
ON/OFF
[Russian][English]
[Japanese]
4. The Other Functions
4.1 Temperature Range Limit Setting
Enables operation of air conditioner at comfortable temperatures at all times.
Upper and lower limits can be established for the temperature setting. This prevents overcooling or overheating, thereby contributing to energy saving.
I. Advantage of New MA Remote Con trol ler
4.2 Auto Off Timer
Shuts off wasteful air conditioner operations.
Operation is stopped automatically when the preset time elapses following the start of operation, thereby preventing wasteful op­erations. The time can be set from 30 minutes to 4 hours in 30-minute increments.
4.3 Simple Operation Lock
Prevents others from changing settings without permission.
This lets you disable all the buttons or all the buttons except for the [ON/OFF] button, preventing mischief and incorrect operations.
3
II. New Functions
Function Description Go to page
Easy maintenance function
II. New Functions
Operation data monitor function
Operation Hz fi xing
Error code monitor function
Contact number display
Multi language display
Temperature display (°C/°F) setting
Room temperature display setting
Auto heat/cool display setting
Weekly schedule timer
"Operation limit function setting (Operation lock)"
Temperature range limit function
Clock function setting
Auto off timer
Simple timer Remote controller main/sub setting
Displays information necessary for maintenance. Below information for easy maintenance of air-con di tion er can be dis­played.
• Compressor • Accumulated op er at ing time
• Number of ON/OFF times
• Operating current (A)
• Outdoor unit • Heat exchanger tem per a ture (°F)
• Discharge tem per a ture (°F)
• Outside air temperature (°F)
• Indoor unit • Intake air tem per a ture (°F)
• Heat ex chang er tem per a ture (°F)
• Filter op er at ing time (hours)
Information necessary for main te nance can be dis played on the remote controller.
The operation state of inverter mod els can be mon i tored using the main te nance stable-operation control (fi xed frequency).
Error code is displayed in the serv ice inspection mon i tor. Displays the contact telephone number to be called when an error oc-
curs. In addition to English, contents can be displayed in seven other lan-
guages.
• English, German, Spanish, Russian, Italian, Chinese, French, Japanese
Enables you to set the unit (°C/°F) in which tem per a tures are to be dis­played.
Enables you to set whether to show or hide the indoor (room) tempera­ture.
Enables you to set whether to display or hide “COOL”/“HEAT” in auto mode.
Provides a built-in weekly timer that allows you to make on/off and tem­ per a ture settings. Up to eight patterns can be set for each day of the week.
Lets you disable all the buttons or all the buttons except for the [ON/ OFF] button, preventing mischief and in cor rect operations.
Enables you to establish upper and lower limits for the temperature set­ ting. This prevents overcooling or over heat ing, thereby contributing to en er gy saving.
Enables you to set whether to use the clock function. Stops operation when the preset time elapses fol low ing the start of op-
er a tion. The time can be set from 30 minutes to 4 hours in 30-minute incre­ments. By default, the weekly timer is se lect ed. To switch to the auto off timer, select it using the remote controller’s function selection.
Enables you to set on/off settings in 1-hour increments within 72 hours.
Enables you to set the remote con trol ler as the main or sub.
6
48
6
44
33
12
35
36
37
23
14
18
21
26
29 20
4
III. Appearance
1. Display Section
For purposes of this ex pla na tion, all parts of the display are shown as lit. During actual op er a tion, only the rel e vant items will be lit.
Identifi es the current op er a tion
Shows the operating mode, etc. * Multilanguage display is sup-
port ed.
“Centrally Controlled” in di ca tor
Indicates that operation of the re­ mote controller has been pro hib it ed by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time re­maining.
TIME SUN MON TUE WED THU FRI SAT TIMER AFTER
ERROR CODE
˚F˚C
˚F˚C
ONLY1Hr.
Up/Down Air Direction in di ­ca tor
The indicator shows the di­ rec tion of the outcoming airfl ow.
“One Hour Only” indicator
Displayed if the airfl ow is set to low and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airfl ow di­ rec tion also changes.
Room Temperature dis play
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Hr AFTER
ON OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote con trol ler sensor is used.
“Locked” indicator
Indicates that remote controller but­ tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the fi lter.
Timer indicators
The indicator comes on if the cor­ re spond ing timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
III. Appearance
2. Operation Section
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set but ton)
Mode button (Return but­ ton)
Set Time but tons
Back
Ahead
Timer On/Off but ton (Set Day button)
Opening the door.
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
ON/OFF but ton
Fan Speed button
Filter button (<Enter> but ton)
Test Run button
Check button (Clear but ton)
Airfl ow Up/Down button
Louver button
Operation button)
(
To preceding op er a tion
number.
Ventilation button (
Op er a tion button) To next operation number.
Note:
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if the feature is not present
at every unit connected.
5
IV. Easy Maintenance Function (For Mr.SLIM P series)
Reduces maintenance work drastically.
Enables you to check operation data of the indoor and outdoor units by remote controller.
Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for inverter models.
Smooth Mainte­nance Function
Easy maintenance information (unit)
Compressor Outdoor unit Indoor unit
Accumulated operating time
( 10 hours) temperature ( ˚F) temperature (˚F) Number of ON/OFF Discharge Heat exchanger times ( 10 times) temperature (˚F) temperature (˚F) Operating Outside air Filter operating current (A) temperature (˚F) time* (Hours)
* The filter operating time is the time that has elapsed since the filter was reset.
Heat exchanger Intake air
1. Maintenance Mode Operating Method
* If you are going to use the "2.Guide for Operation Condition", set the airflow to "High" before activating maintenance mode.
Discharge temperature 147˚F
Remove the service panel.
Measure the discharge temperature.
Conventional inspection work
Outdoor unit
Indoor unit
Measure the intake air temperature.
Measure the outside air temperature
Switching to maintenance mode
Maintenance mode can be activated either when the air conditioner is operated or stopped. It cannot be activated during test run.
Maintenance information can be viewed even if the air conditioner is stopped.
Remote controller button information
Outdoor unit information
Confirm
Activate/cancel maintenance mode
Compressor information
(1) Press the
[Display ]
Operation mode
TEST
MAINTENANCE
button for three seconds to switch to maintenance mode.
Indoor unit information
If stable operation is unnecessary or if you want to check the data with the air conditioner stopped, skip to step (4).
Fixed Hz operation
The operating frequency can be fixed to stabilize operation of inverter model. If the air conditioner is currently stopped, start it by this operation.
(2) Press the
[Display ]
(3) Press the
MODE
FILTER
button to select the desired operation mode.
Stable cooling operation
COOL STABLE MODE
( ) button to confirm the setting.
[Display ] Waiting for stabilization
6
Stable heating operation
HEAT STABLE MODE
Stable operation cancellation
STABLE MODE CANCEL
Stabilized
After 10 to 20 minutes
Data measurement
When the operation is stabilized, measure operation data as explained below.
(4) Press the [TEMP] buttons (
and ) to select the desired refrigerant address.
[Screen ]
(5) Select the type of data to be displayed.
After selecting, go to step (6).
Compressor information
MENU
button
[Display ]
Outdoor unit information
ON/OFF
button
[Display ]
Indoor unit information
button
[Display ]
(6) Press the
FILTER
[Display example for accumulated operating time]
Display
Cumulative operation time
COMP ON x10 HOURS
Heat exchanger temperature
OUTDOOR UNIT H.EXC. TEMP
Indoor room temperature
INDOOR UNIT INLET TEMP
ON/OFF Number Operating current
COMP ON x100 TIMES
Comp discharge temperature
OUTDOOR UNIT OUTLET TEMP
Heat exchanger temperature
INDOOR UNIT
.
H
EXC. TEMP
( ) button to confirm the setting.
Blinking
Waiting for response
After approx. 10 seconds
Outdoor ambient temperature
12,340 hours
COMP ON CURRENT (A)
OUTDOOR UNIT OUTDOOR TEMP
Filter operating time
INDOOR UNIT FILTER USE H
IV. Easy Maintenance Function (For Mr. SLIM P series)
(7) Data is displayed on the display (at ).
To check the data for each item, repeat steps (5) to (7).
(8) To cancel maintenance mode, press the
TEST
Refrigerant address Single refrigerant system
In the case of single refrigerant system, the refrigerant address is "00" and no operation is required. Simultaneous twin units belong to this category (single refrigerant system).
[1:1]
Refrigerant address=00
Outdoor
unit
Indoor unit
01
Remote
controller
[Twin]
Refrigerant address=00
Outdoor
unit
Indoor unit
01
Remote
controller
Indoor unit
02
button for three seconds or press the
Multi refrigerant system (group control)
Up to 16 refrigerant systems (16 outdoor units) can be con­nected as a group by one remote controller. To check or set the refrigerant addresses.
Refrigerant address 00
Outdoor
unit
Indoor unit
01
Remote
controller
Refrigerant address 01
Outdoor
unit
Indoor unit
01
Refrigerant address 02
Outdoor
Indoor unit
unit
01
ON/OFF
button.
Refrigerant address 15
Outdoor
unit
Indoor unit
01
7
2. Guide for Operation Condition
Inspection item Result
Breaker Good Retightened
Terminal block Outdoor Unit Good Retightened
Loose con-
nection
(Insulation resistance) M
Power supply
Com­pressor
(Voltage) V
Accumulated operating time Time Number of ON/OFF times Times Current A Refrigerant/heat exchanger temperature Refrigerant/discharge temperature Air/outside air temperature COOL ˚F HEAT ˚F
(Air/discharge temperature) COOL ˚F HEAT ˚F
Temperature
Appearance Good
Outdoor Unit
Heat exchanger Good Sound/vibration None Present
Cleanli-
ness
Air/intake air temperature COOL
(Air/discharge temperature) COOL ˚F HEAT ˚F
Refrigerant/heat exchanger temperature Filter operating time* Time
Temperature
Decorative panel Good Filter Good
Indoor Unit
Fan Good Heat exchanger Good
Cleanliness
Sound/vibration None Present
* The filter operating time is the time that has elapsed since the filter was reset.
Indoor Unit Good Retightened
COOL ˚F HEAT ˚F COOL ˚F HEAT ˚F
Cleaning required Cleaning required
˚F HEAT ˚F
COOL ˚F HEAT ˚F
Cleaning required Cleaning required Cleaning required Cleaning required
Check Points
Enter the temperature differences between , , and into the graph given below. Operation state is determined according to the plotted areas on the graph. For data measurements, set the fan speed to "Hi" before activat­ing maintenance mode.
Classification Item Result
Inspection
Temperature
Cool
difference
Inspection
Temperature
Heat
difference
* Fixed Hz operation may not be possible under the following tempera-
ture ranges. A)In cool mode, outdoor intake air temperature is 104 ˚F or higher or
indoor intake air temperature is 73 ˚F or lower
B)In heat mode, outdoor intake air temperature is 68 ˚F or higher or
indoor intake air temperature is 77 ˚F or lower
* If the air conditioner is operated at a temperature range other than the
ones above but operation is not stabilized after 30 minutes or more have elapsed, carry out inspection.
* In heat mode, the operation state may vary due to frost forming on the
outdoor heat exchanger.
Is "000" displayed stably in Display on the remote controller?
( Discharge temperature) - ( Outdoor heat exchanger temperature) ( Indoor intake air temperature) - ( Indoor heat exchanger temperature) Is "000" displayed stably in Display
D
on the remote controller?
( Discharge temperature) - ( Indoor heat exchanger temperature) ( Indoor heat exchanger temperature) ­( Indoor intake air temperature)
Stable Unstable
˚F
˚F
Stable Unstable
˚F
˚F
Area Check item
Normal Filter inspection Inspection A
Inspection B Inspection C
Normal operation state Filter may be clogged. *1 Performance has dropped. Detailed in­spection is necessary. Refrigerant amount is dropping. Filter or indoor heat exchanger may be clogged.
Judgment
Cool Heat
* The above judgement is just guide based on Japanese standard
conditions. It may be changed depending on the indoor and outdoor temperature.
Cool mode Heat mode
˚F
81
Indoor
72
Inspection C
63
54
45
Filter inspection
36
Normal
Result
( Indoor intake air temperature) - (
27
18
Inspection A
9
0 18 36 54 72 90 108 126 144
heat exchanger temperature)
[ Discharge temperature] - [ Outdoor heat exchanger temperature)
Inspection B
˚F
81
72
63
54
45
36
27
18
( Indoor heat exchanger temperature) -
( Indoor intake air temperature)
[ Discharge temperature] - [ Indoor heat exchanger temperature)
Inspection C
Filter inspection
Normal
Inspection B
Inspection A
9
18 36 54 72 90 108 126 144
˚F˚F
8
V. How to Select Functions of remote controller
Function Items
1.
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display / (2)
Room air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
Japanese (JP), English (GB), German (D), Spanish (E), Russian (RU), Italian (I), Chinese (CH), French (F)
[4] -2. Function limit (FUNCTION SELECTION) (1) Operation function limit setting (operation lock)(LOCKING FUNCTION)
no1 : Operation lock setting is made on all buttons other than
the [
ON/OFF] button. no2 : Operation lock setting is made on all buttons. OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
OFF : The automatic mode is not displayed
when the operation mode is selected.
(3) Temperature range limit setting (LIMIT TEMP FUNCTION) After this setting is made, the temperature can be changed within the set range.
LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.
OFF (initial setting) : The temperature range limit is not active.
*
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button. To switch the upper limit setting and the lower limit setting, press the button. The selected setting will blink and the temperature can be set. Settable range Cooling/Dry mode : Lower limit: 19 ~ 30 , 67
Upper limit: 30 ~ 19 , 87˚F~67˚F
Heating mode : Lower limit: 17 ~ 28 , 63˚F~83˚F
Upper limit: 28 ~ 17 , 83˚F~63˚F
Automatic mode : Lower limit: 19 ~ 28 , 67˚F~83˚F
Upper limit: 28 ~ 19 , 83˚F~67˚F
Item 2
˚F setting ("TEMP MODE /˚F")
[ ]
˚F~87˚F
Display in multiple languages is possible.
Setting the range of operation limit (operation lock) Setting the use or non-use of "automatic" operation mode Setting the temperature adjustable range (maximum, minimum) Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub. Setting the use or non-use of clock function Setting the timer type Contact number display in case of error Setting the telephone number Setting the temperature unit ( or Setting the use or non-use of the display of indoor (suction) air temperature Setting the use or non-use of the display of "Cooling" or "Heating" display during operation with automatic mode
Item 3 (Setting content)
˚F) to display
[4] -3. Mode selection setting (1) Remote controller main/sub setting(MODE SELECTION)
Main : The controller will be the main controller. Sub : The controller will be the sub controller.
(2) CLOCK setting
ON : The clock function can be used. OFF: The clock function cannot be used.
(3) Timer function setting
WEEKLY TIMER (initial setting):
The weekly timer can be used. AUTO OFF TIMER: The auto off timer can be used. SIMPLE TIMER : The simple timer can be used. TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
CALL OFF:
The set contact numbers are not displayed in case of error.
CALL **** *** **** : The set contact numbers are displayed in case
of error.
CALL_ : The contact number can be set when the display is as
shown on the left.
Setting the contact numbers To set the contact numbers, follow the following procedures. Move the blinking cursor to set numbers. Press the [ (
)] button to move the cursor to the right (left). Press the [ CLOCK (
) and ( )] button to set the numbers.
TEMP. ( ) and
[4] -4. Display change setting(DISP MODE SETTING) (1) Temperature display / ˚F setting
: The temperature unit is used.
˚F : The temperature unit ˚F is used.
(2) Room air temperature display setting(ROOM TEMP DISP SELECT)
ON :
The room air temperature is displayed.
OFF: The room air temperature is not displayed.
(3) Automatic cooling/heating display setting(AUTO MODE DISP C/H)
ON : One of "Automatic cooling" and "Automatic heating" is displayed
under the automatic mode is running.
OFF: Only "Automatic" is displayed under the automatic mode.
V. How to Select Functions of remote controller
9
2. Flowchart of Function Setting
Setting language (English)
Normal display (Display when the air condition is not running)
Hold down the button and press the button for 2 seconds.
Remote controller function selection mode
Item1 Item2
Change Language
EN
GE
Hold down the button and press the button for 2 seconds.
Press the operation mode button. Press the TIMER MENU button. Press the TIMER ON/OFF button.
Dot display
Function selection
Mode selection
ES
RU
IT
ZH
FR
JA
Item3
TEMP.
MENU
ON/OFF
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
OFF
no1
no2
ON
OFF
Operation lock setting is not used. (Initial setting value)
Operation lock setting for all buttons except ON/OFF is active.
Operation lock setting for all buttons is active.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
The automatic mode is not displayed when the operation mode
OPERATION
ON/OFF
CHECK
CLEAR
FILTER
TEST
is selected.
OFF
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
ON
OFF
The clock function can be used. (Initial setting value)
The clock function can not be used.
Display mode setting
10
One of the description marked * on the right will be displayed. (current setting)
OFF
CALL-
F
˚
C
˚
ON
OFF
ON
OFF
Weekly timer can be used. (Initial setting value)
*
*
Auto off timer can be used.
*
Simple timer can be used.
*
Timer mode can not be used.
The set contact numbers are not displayed in case of error. (Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit
˚F is used. (Initial setting value)
is used.The temperature unit
Room air temperature is displayed. (Initial setting value)
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
3. Screen Structure for Function Setting
Description of each screen
• Function selection of remote controller : Used to set the timer function and operation limit function, etc.
• Set day time : Used to set the current day of the week and time.
• Standard control screen : Used to set the air conditioner’s operating state.
• Timer monitor screen : Used to display the current settings of the timers (weekly, simple, auto off).
• Timer set up screen : Used to set the timers (weekly, simple, auto off).
Function Selection of Remote Controller
Standard Control Screens
Timer Monitor Timer Setup
Set Day Time
˚F
(ON)(OFF)
˚F
V. How to Select Functions of remote controller
˚F
How to change the screen display
: Press the [ON/OFF] button for two seconds while holding down the [MODE] button. : Press the [MENU] button. : Press the [MODE] (BACK) button. : Press the [CLOCK] buttons (
and ).
11
4. Function Setting Mode
4.1 Change Language
The language that appears on the dot display can be selected. The following languages can be selected. English (GB) German (D) Spanish (E) Russian (RU) Italian (I) Chinese (CH) French (F) Japanese (JP)
Changing the Display Language
Display ex am ple
(4)
(1)
(2) (3)
(1) While pressing the
selection mode.
(2) Press the
MODE
[Display ]
(3) Press the
MENU
[Display ]
(4) While pressing the
complete.
Display
English
ex am ple
(Cool mode)
Italian
MODE
button, press the
button until
CHANGE LANGUAGE
CHANGE LANGUAGE
appears on the screen (at ).
FUNCTION SELECTION
ON/OFF
button to select the desired display language.
[English] LANGUAGE ENGLISH(GB)
[Japanese] LANGUAGE (JP)
MODE
[German] LANGUAGE Deutsch(D)
[French] LANGUAGE FRENCH(F)
button, press the
[Spanish] LANGUAGE ESPAÑOL(E)
[Chinese] LANGUAGE (CH)
ON/OFF
German
Chinese
button for two seconds to activate the remote controller’s function
MODE SELECTION
[Russian] LANGUAGE pycck(RU)
[Italian] LANGUAGE ITALIANO(I)
DISP MODE SETTING
button for two seconds to return to normal mode. Setting is now
Spanish
French
Russian
Japanese
12
Multi Language Display
V. How to Select Functions of remote controller
13
4.2 Function Setting
4.2.1 Operation Lock (Operation Function Limit Setting)
The following settings can be made.
no1 :All buttons except for the [ON/OFF] button are locked. no2 :All buttons are locked.
OFF (default) :No buttons are locked.
* To activate this operation lock function on the normal screen, hold down the holding down the
FILTER
( ) button.
How to Lock the Buttons
Display ex am ple
(1)(5)
(2) (3) (4)
(1) While pressing the
function selection mode.
(2) Press the
[Display
MODE
]
MODE
button, press the
button to select
CHANGE LANGUAGE
FUNCTION SELECTION
FUNCTION SELECTION
on the screen (at ).
ON/OFF
MODE SELECTION
button for two seconds to activate the remote controller’s
ON/OFF
DISP MODE SETTING
button for two seconds while
(6)(7)
(3) Press the
[Display ]
MENU
button until “LOCKING FUNCTION” appears on the screen (at ).
LOCKING FUNCTION
SELECT AUTO MODE
* Displays the mode that is set in “Temperature Range Limit Setting”.
(4) Press the
[Display
ON/OFF
]
(5) While pressing the
button until the desired lock mode appears on the screen (at ).
No limitation Lock All Buttons
MODE
Lock All Except ON/OFF
button, press the
ON/OFF
now complete.
Completing steps (1) to (5) allows use of the operation lock function. To enable the lock function, carry out the following steps.
LIMIT TEMP FUNCTION
button for two seconds to return to normal mode. Setting is
14
Enabling the Lock Function
(6) While pressing the
function.
FUNCTION
* If a locked button is pressed while the operation lock function is in use,
appears on the screen (at ).
FILTER
( ) button, press the
Display example when operation lock function is in use
ON/OFF
How to Unlock the Buttons
(7) While pressing the
FUNCTION
disappears from the screen (at ).
FILTER
( ) button, press the
Display example when the operation lock function is not in use
ON/OFF
button for two seconds to enable the operation lock
FUNCTION
button for two seconds.
will blink on the screen (at ).
V. How to Select Functions of remote controller
15
4.2.2 Auto Mode Setting
The following settings can be made.
ON (default) : Auto mode is displayed when selecting an operation mode only if the unit to be connected supports the auto
mode. However, this does not apply if the unit to be connected does not support the auto mode. Operation mode can be switched:
COOL DRY FAN HEATAUTO
OFF : Even if the unit supports the auto mode, auto mode is not displayed when selecting an operation mode.
Operation mode can be switched :
COOL DRY FAN HEAT
How to Set Auto Mode
Display ex am ple
(1) While pressing the
MODE
function selection mode.
(2) Press the
[Display ]
(3) Press the
MODE
button to select
CHANGE LANGUAGE
MENU
button so that
* The current setting is displayed.
(4) Press the
[Display ]
(5) While pressing the
ON/OFF
SELECT AUTO MODE
MODE
now complete.
* If you press the
ON/OFF
button, press the
FUNCTION SELECTION
SELECT AUTO MODE
on the screen (at ).
FUNCTION SELECTION
ON/OFF
appears on the screen (at ).
button for two seconds to activate the remote controller’s
MODE SELECTION
DISP MODE SETTING
button to select whether auto mode is to be used (on) or not (off).
SELECT AUTO MODE
button, press the
button before the
ON/OFF
MODE
button for two seconds to return to normal mode. Setting is
button, the settings you have made will be cancelled.
16
Screen display when auto mode is set to ON
(1) Press the The ON lamp lights up and operating contents are displayed on the LCD.
(2) Press the Each time the
ON/OFF
MODE
MODE
COOL DRY FAN HEAT
*1: If the remote controller is connected with the unit for cool operation only, “AUTO” and “HEAT” will not be displayed, nor will
it be possible to select them.
button.
button.
button is pressed, the operation mode switches from one to another. “AUTO” is also displayed.
AUTO
*1
Display example when auto mode is set to ON
If AUTO MODE DISP C/H is ON (see 4.4.3), it takes about 10 seconds before the display is switched from one mode to another.
*1
Screen display when auto mode is set to OFF
(1) Press the The ON lamp lights up and operating contents are displayed on the LCD.
(2) Press the Each time the
ON/OFF
MODE
MODE
button.
button.
button is pressed, the operation mode switches from one to another, but “AUTO” is not displayed.
COOL DRY FAN HEAT
*1
*1: If the remote controller is connected with the unit for cool operation only, “HEAT” will not be displayed.
V. How to Select Functions of remote controller
17
4.2.3 Temperature Range Limit Setting
The temperature setting range can be limited. It can be limited for each mode.
Cool mode : The temperature setting range for cool/dry mode can be changed. Heat mode : The temperature setting range for heat mode can be changed. Auto mode : The temperature setting range for auto mode can be changed. OFF (default) : The temperature setting range is not limited.
* When a mode other than OFF mode is set, temperature setting range limit setting for cool, heat and auto modes will be made
simultaneously.
However, limit setting will not be made unless the range has been changed.
Setting range Standard setting COOL·DRY Mode Lower limit 67 °F – 87 °F Upper limit 87 °F – 67 °F HEAT Mode Lower limit 63 °F – 83 °F Upper limit 83 °F – 63 °F AUTO Mode Lower limit 67 °F – 83 °F Upper limit 83 °F – 67 °F
* Temperatures can be set within the range of “upper limit ” “lower limit”.
Limiting the Temperature Range
Display ex am ple
67 °F – 87 °F
63 °F – 83 °F
67 °F – 83 °F
(1) While pressing the
MODE
button, press the
ON/OFF
button for two seconds to activate the remote controller’s
function selection mode.
(2) Press the
[Display ]
(3) Press the
MODE
MENU
button to select
CHANGE LANGUAGE
button to select
FUNCTION SELECTION
FUNCTION SELECTION
LIMIT TEMP FUNCTION
on the screen (at ).
MODE SELECTION
on the screen (at ).
DISP MODE SETTING
* If a setting change was made previously, the mode that was set (one of the modes shown in step (4)) will be displayed.
(4) Press the
[Display ]
ON/OFF
button to select the mode for which temperature range limit setting is to be made.
DRY mode COOL mode
LIMIT TEMP COOL MODE
HEAT mode AUTO mode* No limitation
LIMIT TEMP HEAT MODE
LIMIT TEMP AUTO MODE
LIMIT TEMP FUNCTION
Display
* No operation modes will be displayed if auto mode has been set to OFF.
18
(5) Press the button to select lower limit or upper limit. Lower limit blinks. Upper limit blinks.
[Display ]
(6) Press the [TEMP] buttons ( [Setting example for lower limit]
and ) to set the desired temperature setting range.
Display
(7) While pressing the
now complete. * If you press the
* If an attempt is made to set a temperature outside the range when the temperature range limit function is in use, “LIMIT
TEMP FUNCTION” will blink.
Display example when the temperature range limit function is in use
If employees tend to lower the temperature excessively in the offi ce without permission, set the temperature setting range for cool/dry mode to 77 °F-87 °F.
Setting
MODE
ON/OFF
button, press the
button before the
ON/OFF
MODE
button for two seconds to return to normal mode. Setting is
button, the settings you have made will be cancelled.
Even if someone who feels hot tries to press remote the con trol ler’s buttons to lower the temperature below 76 °F, or lower…
LIMIT TEMP FUNCTION
V. How to Select Functions of remote controller
blinks and the command is not accepted.
19
4.3 Basic Functions Setting
4.3.1 Remote Controller Main/Sub Setting
When using two remote controllers, they must be designated as the main and sub remote controllers. The following settings can be made. MAIN (default) : The remote controller is set as the main controller. SUB : The remote controller is set as the sub controller.
To Change the Main/Sub Setting
Display ex am ple
(1)(5)
(2) (3)
(4)
(1) While pressing the
function selection mode.
(2) Press the
[Display
(3) Press the (4) Press the
[Display
MODE
]
MENU
ON/OFF
]
(5) While pressing the
MODE
button until
CHANGE LANGUAGE
button, press the
MODE SELECTION
appears on the screen (at
FUNCTION SELECTION
ON/OFF
button to select “CONTROLLER” on the screen (at
button for two seconds to activate the remote controller’s
).
MODE SELECTION
DISP MODE SETTING
).
button to select “CONTROLLER MAIN” or “CONTROLLER SUB” on the screen (at
CONTROLLER
MAIN
MODE
button, press the
CONTROLLER
SUB
ON/OFF
button for two seconds to return to normal mode.
).
20
4.3.2 Timer function setting (Weekly timer/Auto off timer/Simple timer)
The following settings can be made.
Weekly Timer (default) : The weekly timer can be used. Auto Off Timer : The auto off timer can be used. Simple Timer : The simple timer can be used. Timer Mode Off : Timer mode cannot be used. * If the clock function is disabled (OFF), “Weekly Timer” cannot be selected.
Clock function setting
The following settings can be made.
ON (default) : The clock function can be used. OFF : The clock function cannot be used. * If “OFF” is selected to disable the clock function, the weekly timer cannot be used to make day of the week/time settings. To use the weekly timer to set the day of the week and time, the clock function must be set to “ON” (default).
To Use the Clock
Display ex am ple
(1) While pressing the
function selection mode.
(2) Press the
[Display
(3) Press the (4) Press the
[Display
(5) While pressing the
* If you press the
MODE
]
MENU
ON/OFF
]
(1)
(5)
(2) (3) (4)
MODE
button until
MODE
ON/OFF
button, press the
MODE
CHANGE LANGUAGE
button to select “CLOCK” on the screen (at ).
SELECTION
button so that “ON” appears on the screen (at
button, press the
button before the
appears on the screen (at ).
FUNCTION SELECTION
ON/OFF
ON/OFF
MODE
MODE SELECTION
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
button for two seconds to activate the remote controller’s
DISP MODE SETTING
).
V. How to Select Functions of remote controller
Day of the week and time setting
The day of the week and time can be set and changed.
[The time can be set in 1-minute increments.]
Notes
• This setting is not possible if the clock function is disabled by the function setting.
• The day of the week and time are not displayed if the clock function is disabled by function selection.
• This setting is not possible if the simple timer or auto off timer has been selected.
21
(1)
(3)
Setting the Day of the Week and Time
Display ex am ple
(2)
(4)
(5)
(1) Press the [CLOCK] buttons ( and ) to display (2) Press the
[Display
(3) Press the [CLOCK] buttons ( Press the [CLOCK] buttons ( and ) longer will switch the time in 10-minute and 1-hour increments.
[Display
(4) Press the
Note
The time you have set can be cancelled by pressing the
(5) Press the
* The day of the week and time you have set are displayed on the normal screen.
ON/OFF
]
]
FILTER
MODE
button until the desired day of the week appears.
Sun Mon Tue Wed Thu SatFri
and ) to set the desired time.
One-minute Ten-minute One hour
( ) button to confi rm the time.
(BACK) button to return to the normal screen and complete the day of the week/time setting.
TIME SET
:ENTER
MODE
on the screen (at ).
(BACK) button without confi rming it.
22
(4)
Weekly Timer
The weekly timer allows you to set up to eight operations per day of the week.
• For each operation, you can set the ON (start) or OFF (stop) timer and temperature. The start timer, stop timer and temperature can also be set individually.
• The air conditioner is operated at the times you have set and according to the settings you have made.
The time for the weekly timer can be set in 1-minute increments.
* If “OFF” is selected to disable the clock function, the weekly timer cannot be used to make day of the week/time settings. To use the weekly timer to set the day of the week and time, the clock function must be set to “ON” (default). (Refer to page 21.)
Note With the weekly timer, it is not possible to designate an operation mode. The air conditioner will be operated in the currently selected operation mode. (Cool, Dry, Heat or Auto)
How to set the Weekly Timer
Display example (for
)
(7)
(11)(3)
(6)
(8)
(10)
(2)
(5)
(1) Make sure that “WEEKLY” is displayed on the screen (at ).
(2) Press the
[Display ]
(3) Press the
[Display
MENU
ON/OFF
]
button to select
TIMER MONITOR
button until the desired day of the week appears.
Sun-Sat Sun Mon Fri Sat
(4) Press the and buttons to set the desired operation No. (Up to 8 patterns can be set.)
[Display
]
* A cell from the following setup matrix is selected according to the settings you have made in steps (2) and (3).
Set up Matrix
Op No. Sunday Monday Saturday no1 • 8:30
ON
73 °F no2 • 10:00 • 10:00 • 10:00 • 10:00
• OFF • OFF • OFF • OFF
TIMER SET :ENTER
TIMER SET :ENTER
on the screen (at ).
- Setting contents ­Starts the air conditioner at 8:30 with the tem­ per a ture set to 73 °F.
- Setting contents ­Stops the air conditioner at 10:00.
V. How to Select Functions of remote controller
no8
Note If “Sun – Sat” is set in step (3), the same pattern can be set for each day of the week at a time. The same pattern is set in the shaded areas in the above setup matrix. (Example: Selecting “Sun – Sat” and setting operation No. “no2”)
23
(5) Press the [CLOCK] buttons ( and ) to set the desired time. (0:00 to 23:59)
[Display
(6) Press the
[Display
(7) Press the [TEMP] buttons (
[Display
Temperature setting range : The temperature can be set within a range of 53 °F to 87 °F. However, the setting range varies
(8) After completing the settings in steps (4) to (7), press the To cancel the settings you have made, press the
* The time setting will change to “- -:- -”, and the ON/OFF and temperature settings will all disappear.
(To clear all the weekly timer settings you have made, hold down the
more until the settings blink. All of the settings will be cleared.)
Note The settings you have made can be cancelled by pressing the
button. When two or more different operations for the same time are set, only the operation with the larger operation No. will be effective.
]
ON/OFF
]
]
button to select whether to start or stop the air conditioner at the time you have set in step (5).
ON OFF
(Space)
and ) to set the desired room temperature. (53 °F to 87 °F)
(Space)
with the type of the air conditioner. (Refer to 4-2-3.)
FILTER
CHECK
( ) button to confi rm them.
(CLEAR) button once.
CHECK
MODE
(BACK) button befor pressing
(CLEAR) button for two seconds or
FILTER
( )
(9) Repeat step (3) to (8) to set the contents in the setup matrix.
(10) Press the
(11) If you press the Make sure that “
MODE
(BACK) button to return to the normal screen and complete weekly timer setting.
ON/OFF
” disappears.
button, the weekly timer will start and “ ” will disappear from the screen.
How to Review the Weekly Timer Settings
(1) Make sure that “WEEKLY” is displayed on the screen (at ).
(2) Press the
(3) Press the
(4) Press the
* The settings are displayed in order of time setting.
(5) To close the
MENU
ON/OFF
TIMER MONITOR
button to display
button to select the day of the week you want to check.
and buttons to switch the settings from one to another, one at a time.
and return to the normal screen, press the
TIMER
on the screen (at ).
MONITOR
MODE
button.
To Turn Off the Weekly Timer
(1) Press the
ON/OFF
24
button to display on the screen (at ).
To Turn On the Weekly Timer
(1) Press the
Weekly timer setting procedure
ON/OFF
button so that disappears from the screen (at ).
To facilitate weekly timer setting, it is recommended that the settings (day of the week, time, operation (on/off)) you are going to make be entered in the setup table shown below. Weekly timer setup table (up to 8 patterns can be set for each day of the week, 56 patterns in total for a week)
Operation No. Sunday Monday Tuesday Wednesday Thursday Friday Saturday
Time setting 1 no 1 On/off setting Temperature Time setting 2 no 2 On/off setting Temperature Time setting 3 no 3 On/off setting Temperature Time setting 4 no 4 On/off setting Temperature Time setting 5 no 5 On/off setting Temperature Time setting 6 no 6 On/off setting Temperature Time setting 7 no 7 On/off setting Temperature Time setting 8 no 8 On/off setting
Temperature
Operation No. : Use the
Day of the week : Use the
and buttons to select the desired operation No.
ON/OFF
button to select the desired day. (“Sun to Sat”, “Sun”, “Mon”, “Tue”, “Wed”, “Thu”, “Fri”
or “Sat” can be selected.)
V. How to Select Functions of remote controller
Time : Use the [
to 23:59 in 1-minute increments.)
Operation (ON/OFF) : Use the
Temperature : Press the [
CLOCK] buttons ( and ) to set the desired time. (The time can be set from 0:00
ON/OFF
button to select the desired operation (ON,OFF,
(space)
).
TEMP] buttons ( and ) to set the desired temperature.
25
2 Auto Off Timer
The auto off timer begins counting down when the air conditioner starts, and stops the air conditioner when the set time
passed.
The time on the auto off timer can be set in a range of 30 minutes to 4 hours, in 30-minute increments.
* By default, the weekly timer is selected as the remoter controller’s timer function. To use the auto off timer, switch the timer function to the auto off timer using the remote controller’s function selection. Note 1 : If the auto off timer is selected, it is not possible to use the weekly and simple timers. Note 2 : Timer operation is not possible when: A timer is operating, an error has occurred, the air conditioner is operating, the remote controller is diagnosing a
problem, function selection is in progress, timer setting is in progress, or the system is centrally controlled.
(ON/OFF operation is prohibited under the above conditions.)
Selecting the Auto Off Timer
Display ex am ple
(1)
(5)
(2) (3) (4)
Steps (1) to (5) are necessary when switching the timer function from simple timer, weekly timer and no timer.
(1) While pressing the
function selection mode.
(2) Press the
[Display
(3) Press the
(4) Press the
[Display
MODE
]
MENU
ON/OFF
]
(5) While pressing the
* If you press the
MODE
button until
CHANGE LANGUAGE
TIMER MODE OFF
MODE
ON/OFF
button, press the
MODE SELECTION
appears on the screen (at
FUNCTION SELECTION
ON/OFF
button for two seconds to activate the remote controller’s
).
MODE SELECTION
button so that “Timer” appears on the screen (at ).
button until
button, press the
AUTO OFF TIMER
appears on the screen (at ).
AUTO OFF TIMER
button before the
SIMPLE TIMER
ON/OFF
MODE
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
DISP MODE SETTING
WEEKLY TIMER
26
How to Set the Auto Off Timer
Display ex am ple
(5)
(4) (1)
(2)
(1)Press the
[Display
MENU
]
(2) Press the [CLOCK] buttons (
button for 3 seconds so that
TIMER MONITOR
TIMER SET :ENTER
and ) to set the desired time.
(The time can be set up to 4 hours in 30-minute increments.)
[Display
(3) Press the
(4) Press the
]
FILTER
MODE
( ) button to confi rm the setting.
button to complete the setting procedure.
[Set display example]
TIMER SET :ENTER
[Display ] [Display ]
AFTER
Two hours
OFF
(3)
appears on the screen (at ).
V. How to Select Functions of remote controller
AUTO OFF
Checking the Current Auto Off Timer Setting
(1) Make sure that
(2) Press the
• The time you have set is displayed.
(3) To close the
AUTO OFF
MENU
TIMER
and return to the normal screen, press the
MONITOR
is displayed on the screen (at ).
button for 3 seconds to display
Display ex am ple
TIMER
on the screen (at ).
MONITOR
MODE
button.
27
To Turn Off the Auto Off Timer…
(1) Press the
• If the air conditioner is operated with the auto off timer turned OFF, * The auto off timer will be effective the next time that the air conditioner is operated.
ON/OFF
button for 3 seconds so that the timer execution time disappears from the screen (at ).
will appear on the screen (at ).
Display example (auto off timer is off)
To Turn On the Auto Off Timer…
(1) Press the
the timer execution time appears on the screen (at
* The timer execution time that was set previously will be displayed.
ON/OFF
button for 3 seconds while the timer is OFF, so that
).
Display example (auto off timer is on)
disappears from the screen (at
) and
28
Simple Timer
You can set the simple timer in any of three ways.
Start time only : The air conditioner starts when the set time has passed.
Stop time only : The air conditioner stops when the set time has passed.
Start & Stop times : The air conditioner starts and stops at the respective passed times.
The simple timer (Start and stop) can be set only once within a 72-hour period.
The time setting is made in hour increments.
Note 1: Timer operation is not possible when:
A timer is operating, an error has occurred, the air conditioner is operating, the remote controller is diagnosing a prob­lem, function selection is in progress, timer setting is in progress, or the system is centrally controlled. (ON/OFF operation is prohibited under the above conditions.)
If the simple timer is not currently selected, select it and make the necessary changes to the current settings as explained
below.
Switching to the simple timer
Display ex am ple
(1)
(5)
(2) (3) (4)
Steps (1) to (5) are necessary when switching the timer function from auto off timer, weekly timer and no timer.
(1) While pressing the
function selection mode.
(2) Press the
[Display
(3) Press the
(4) Press the
MODE
]
MENU
ON/OFF
[Display ]
MODE
button until
button, press the
MODE
CHANGE LANGUAGE
SELECTION
ON/OFF
appears on the screen (at ).
FUNCTION SELECTION
button for two seconds to activate the remote controller’s
MODE SELECTION
button so that “TIMER” appears on the screen (at ).
button until “SIMPLE TIMER” appears on the screen (at ).
TIMER MODE OFF
AUTO OFF TIMER
SIMPLE TIMER
DISP MODE SETTING
WEEKLY TIMER
V. How to Select Functions of remote controller
(5) While pressing the
* If you press the
MODE
ON/OFF
button, press the
button before the
ON/OFF
MODE
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
29
How to Set the Simple Timer
Display ex am ple
(2)
(7)
(6) (1)
(3)
Make sure that “SIMPLE TIMER” is displayed on the screen (at ).
(1) Press the
[Display
(2) Press the
MENU
]
ON/OFF
button to select
TIMER MONITOR
button to select “Start time only” or “Stop time only”.
Hr
ON Hr
AFTER
• Start time only (Displays the time at which the air conditioner starts) : “Hr AFTER ON”
• Stop time only (Displays the time at which the air conditioner stops) : “Hr AFTER OFF”
(3) Press the [
CLOCK] buttons ( and ) to set the desired time. (The time can be set up to 72 hours in 1-hour
increments.)
1 2 71 72
[Display
]
TIMER SET :ENTER
TIMER SET :ENTER
AFTER OFF
on the screen (at ).
(4)
* To cancel the time you have set, press the
(4) Press the
FILTER
( ) button to confi rm the setting.
CHECK
(CLEAR) button.
*1. When using only the start timer or stop timer, make sure that “– –” is displayed for the timer you are not going to use.
*2. To cancel the time you have set, press the
CHECK
(CLEAR) button to display “– –”, and then press the
button to confi rm it.
(5) When using both the start and stop timers, carry out steps (2) to (4) to set both the start and stop times.
* It is not possible to set the same time for both the start and stop times.
(6) Press the [Set display example]
MODE
[Display ] [Display ]
(7)Press the
button to complete the setting procedure.
Hr
ON
AFTER
Ten hours
ON/OFF
button. The simple timer will start to operate and the timer execution time you have set will be
SIMPLE
displayed.
If both start and stop timers are set, whichever time will come fi rst will be displayed.
FILTER
( )
30
Review the Current Simple Timer Settings
(1) Be sure that the “SIMPLE” indicator is displayed on the screen (at ).
(2) Press the
MENU
button, so that the
TIMER
appears on the screen (at ).
MONITOR
• The time you have set to start or stop the timer appears on the screen (at
(3) Press the
MODE
button to close the
TIMER
display and return to the standard control screen.
MONITOR
To Turn Off the Simple Timer…
).
(1) Press the
ON/OFF
button so that the timer setting no longer appears on the screen (at ).
Examples
1 Start timer operation : Operation starts
after 2 hours.
4 When both the start and stop timers are set
Example 1 : To activate the on timer fi rst Time set for the on tim er: ON after 3 hours Time set for the off tim er: OFF after 7 hours
2 Stop timer operation : Operation stops
after 10 hours.
3 Timer cancelled
Timer setting no longer ap pears
V. How to Select Functions of remote controller
Once seven hours have elapsed, the air conditioner will remain stopped until an operation is per formed.
Timer start Displays the time set for the start timer.
Displays “stop time” – “start time”.
After 3 hours
Example 2 : To activate the off timer fi rst Time set for the off timer: OFF after 2 hours Time set for the on timer: ON after 5 hours
Timer start Displays the time set for the off timer.
Displays on timer (5hr)·off timer (2hr)
After 2 hours
After 7 hours
Once fi ve hours have elapsed, the air con di tion er will continue operating un til an op er a tion is performed.
After 5 hours
31
Timer Mode Off
Timer mode cannot be used.
(1)
(5)
(2) (3) (4)
How to set the Timer mode Off
(1) While pressing the
function selection mode.
(2) Press the
MODE
MODE
button until appears on the screen (at ).
Display ex am ple
button, press the
ON/OFF
button for two seconds to activate the remote controller’s
[Display
(3) Press the
(4) Press the
[Display
]
MENU
ON/OFF
]
(5) While pressing the
* If you press the
CHANGE LANGUAGE
FUNCTION SELECTION
MODE SELECTION
button so that “TIMER” appears on the screen (at ).
button until “TIMER MODE OFF” appears on the screen (at ).
TIMER MODE OFF
MODE
ON/OFF
button, press the
AUTO OFF TIMER
button before the
SIMPLE TIMER
ON/OFF
MODE
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
DISP MODE SETTING
WEEKLY TIMER
32
4.3.3 Contact Number Setting for Error Situation
The following settings can be made. CALL • OFF (default) : The preset contact number is not displayed even when an error occurs. CALL • ************ : The preset contact number is displayed when an error occurs. (The contact number can consist of up
to 12 digits.)
CALL • – : The contact number is not set in default setting.It is displayed as shown on the left.
Setting the Contact Numbers
Display ex am ple
(5)
(6)
(1)
(2) (3) (4) (5)
(7)
(1) While pressing the
MODE
button, press the
function selection mode.
(2) Press the
[Display
MODE
]
(3) Press the
[Display
]
(4) Press the
Do not show Show
[Display ]
[Display
]
(5) Press the [ CLOCK] buttons (
button until appears on the screen (at ).
CHANGE LANGUAGE
MENU
ON/OFF
button until “CALL” appears on the screen (at ).
.
TIMER CONTROLLER CLOCK
CALL
button to select whether or not to show the contact number.
.
CALL
and ) to set the desired contact number, one digit at a time. To move the input digit
position left or right, press the [ TEMP] buttons (
[Display
]
01 9
FUNCTION SELECTION
.
CALL
ON/OFF
MODE SELECTION
and ).
Space
button for two seconds to activate the remote controller’s
DISP MODE SETTING
V. How to Select Functions of remote controller
The contact number can contain up to 12 digits.
[When entering “012”]
[Display
“0” Press the [ CLOCK] button (
] CALL • 012_
) once.
Each time a value is entered, press the [TEMP] button ( ) to move the cursor to the next digit to the right.
“1” Press the [ CLOCK] button (
“2” Press the [ CLOCK] button (
) twice.
) three times.
33
(6) While pressing the
* If you press the
MODE
ON/OFF
button, press the
button before the
ON/OFF
MODE
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
(7) If you press the
Once the contact number has been set, the error code and contact number will be displayed alternately when an error
occurs.
CHECK
Error Code
(CLEAR) button, the contact number will be displayed for fi ve seconds.
Indoor unit No.
(Alternating Display)
Indoor unit No.
Error Code
34
4.4 Display Change Setting
4.4.1 Temperature Display °F/°C Setting
The following settings can be made.
°F(default) : Temperatures are displayed in Fahrenheit.
(Degrees F = 1.8 × degrees C + 32)
°C : Temperatures are displayed in Celsius.
(Degrees C = (Degrees F - 32) / 1.8)
Switching the Temperature Display Unit between °F and °C
Display ex am ple
(1)
(5)
(2) (3) (4)
(1) While pressing the
function selection mode.
(2) Press the
[Display ]
(3) Press the
(4) Press the
[Display
(5) While pressing the
* If you press the
■Temperature display example when “°F” is selected
MODE
]
MODE
button until
MENU
ON/OFF
MODE
ON/OFF
button, press the
DISP MODE SETTING
CHANGE LANGUAGE
button to select “TEMP MODE °C/°F” on the screen (at ).
button to select “°F” or “°C”on the screen (at ).
appears on the screen (at ).
FUNCTION SELECTION
CF
button, press the
button before the
ON/OFF
ON/OFF
MODE
button for two seconds to activate the remote controller’s
MODE SELECTION
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
Temperature display example when “°C” is selected
DISP MODE SETTING
V. How to Select Functions of remote controller
35
4.4.2 Room air Temperature Display Setting
The following settings can be made.
ON (default) : The room air temperature is displayed.
OFF : The room air temperature is not displayed.
Setting the Room Air Temperature
Display ex am ple
(1)
(5)
(2) (3) (4)
(1) While pressing the
function selection mode.
(2) Press the
[Display ]
(3) Press the
(4) Press the
[Display
(5) While pressing the
* If you press the
Room air temperature display example
when “ON” is selected when “OFF” is selected
MODE
]
MODE
button until
CHANGE LANGUAGE
MENU
ON/OFF
MODE
ON/OFF
button, press the
DISP MODE SETTING
button so that “ROOM TEMP DISP SELECT” appears on the screen (at ).
button to select “on” or “oFF” on the screen (at ).
button, press the
button before the
appears on the screen (at ).
FUNCTION SELECTION
ON/OFF
ON/OFF
MODE
button for two seconds to activate the remote controller’s
MODE SELECTION
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
Room air temperature display example
DISP MODE SETTING
36
4.4.3 Automatic Cooling/Heating Display Setting
• This section explains how to set whether to display “COOL”/“HEAT” in auto mode. It will not be displayed if auto mode is set to OFF.
ON (default) : One of “Automatic cooling” and “Automatic heating” is displayed under the automatic mode is displayed.
OFF : Only “Automatic” is displayed under the automatic mode.
Selecting Whether to Display “COOL”/“HEAT” in Auto Mode
Display ex am ple
(1)
(5)
(2) (3) (4)
(1) While pressing the
function selection mode.
(2) Press the
[Display
(3) Press the
(4) Press the
[Display
(5) While pressing the
* If you press the
Display example when “AUTO MODE DISP C/H” is set to “ON”
[During auto (cool) mode] [During auto (heat) mode]
MODE
]
]
MODE
button until
MENU
ON/OFF
MODE
ON/OFF
button, press the
DISP MODE SETTING
CHANGE LANGUAGE
button so that “AUTO MODE DISP C/H” appears on the screen (at ).
button to select “on” or “oFF” on the screen (at ).
button, press the
button before the
appears on the screen (at ).
FUNCTION SELECTION
ON/OFF
ON/OFF
MODE
button for two seconds to activate the remote controller’s
MODE SELECTION
button for two seconds to return to normal mode.
button, the settings you have made will be cancelled.
DISP MODE SETTING
V. How to Select Functions of remote controller
Display example when “AUTO MODE DISP C/H” is set to “OFF”
37
VI.
Unit Function Setting by the Remote Controller (for Mr. SLIM P Series)
Perform the following settings only to change the functions for Mr. Slim series.
(This setting is not possible with the City-Multi series.)
Each unit’s functions can be set by a remote controller. Setting of each unit’s functions is possible by remote controller only. Table Functions Available (For details regarding initial settings and operation modes of each unit, refer to the unit installation manual.)
(1) Itemised functions of the entire refrigerant system (select unit number 00)
Function Settings Mode No. Setting No. Check Remarks
Power failure automatic recovery
Indoor temperature detecting *1
LOSSNAY connectivity
Power voltage
Auto operating mode *2
Frost prevention temperature
Defrosting control
*1. Can be set only when a wired remote controller is used. This function cannot be set for fl oor type models. When using two remote controllers (two-remote controller operation), the remote controller with a built-in sensor must be set as the main re-
mote controller.
Not available Available
(Approx. 4-minute wait-period after power is restored.)
Average data from each indoor unit Data from the indoor unit with remote controllers Data from main remote controller Not supported Supported Supported
(Indoor unit does not intake outdoor air through LOSSNAY.) (Indoor unit intakes outdoor air through LOSSNAY.)
230V 208V Auto energy-saving operation ON Auto energy-saving operation OFF 2 C [36 F](Normal) 3 C [37 F
]
Standard For high humidity
1
2
3
4
5
15
17
Meaning of "Function setting" ModeNo.02 : indoor temperature detecting
No
Indoor temperature : ta
OUTDOOR
OUTDOOR
OUTDOOR
1
2
1 2 3 1 2 3 1 2 1 2 1 2 1 2
OUTDOOR
INDOOR
REMOTE (SUB)
No1.
Average data of the sensor on all the
INDOOR
REMOTE (MAIN)
factory
ta=(A+B)/2 ta=(A+B)/2 ta=A ta=A
setting
indoor units
No2.
the data of the sensor
ta=A ta=B ta=A ta=A on the indoor unit that connected with remote controller
No3
the data of the sensor
ta=C ta=C ta=C ta=C on main remote controller.
*2. Can be set only when the outdoor unit is an inverter type.
INDOOR
REMOTE (MAIN)
INDOOR
REMOTE (SUB)
INDOOR
REMOTE (MAIN)
REMOTE (SUB)
INDOOR
REMOTE (MAIN)
38
(2) Itemised functions of the in door unit (select unit numbers 01 to 03 or AL [Wired remote controller] / 07 Wireless re mote controller])
Function
Filter sign
Air flow (Fan speed )
No. of air outlets of PLA-A·AA
Installed options (highperformance filter)
Vane setting
Energy saving air flow (Heating mode)
Swing
Set temperature in heating mode 4deg-up
Fan speed when the heating thermostat is OFF
Fan speed when the cooling thermostat is OFF
Detection of abnormality (P8) of the pipe temperature
100Hr 2500Hr "Clean the filter" indicator is not displayed. Quiet Standard 1 Standard High ceiling 4 directions 3 directions 2 directions Not supported Supported No vanes(Vane No.3 setting : PLA-A·AA only) Vane No. 1 setting Vane No. 2 setting OFF ON Not available Available ON OFF Extra low Stop Keeping fan speed set by remote controller Keeping fan speed set by remote controller Stop Detect Neglect
Settings
High ceiling PLA-A·AA type High ceiling
Mode No. Setting No. Check Remarks
1
07
2 3
08
2 3 1
09
2 3
10
1 2 1
11
2 3
12
23
24
1 2 1 2 1 2 1
25
2 3
27
28
1 2 1 2
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a “ ” mark, etc., is given in the “Check” column of Table to indicate the change
Unit Function Setting by the Remote Controller (for Mr. SLIM P series) VI.
39
[Flow of function selection]
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps to .
Setting number
Mode number
Selecting functions using the wired remote controller
Refrigerant address Unit number
Modes 01 to 14 can be activated by pressing buttons simultaneously, and modes 15 to 28 by pressing buttons
and
and .
Check the function selection setting.
Switch to function setting mode. (Press with the remote controller stopped.)
Specify refrigerant address 00 (outdoor unit) Specify unit No. 00. (indoor unit)
(Use and .)
Select mode No. 02 (room temperature detection position). Select setting No. 03 (remote controller fixed). (Use and .)
and at the same time
Enter the setting.
(Press .)
Enter the setting.
(Press .)
(Specified indoor unit:
FAN operation)
Example: Selecting room temperature detection position
For modes 15 and higher, press and at the same time.
NO
YES
Change refrigerant address unit No.
40
Finished
NO
YES
Ending function display (Press and at the same time.)
The above procedure must be carried out only if changes are necessary.
[Operating Procedure]
Check the setting items provided by function selection. If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps to , fill in the "Check" column in Table, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
Switch off the remote controller.
Hold down the ( ( mode is 15 to 28)and
buttons simultaneously for atleast two seconds. will start to blink,
and then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path.
Note If you have made operational mistakes during this procedure, exit function selection (see step
Set the indoor unit number.
Press the area.
FILTER
Refrigerant address display section
FUNCTION SELECTION
ON/OFF
button so that "- -" blinks in the unit number display
Unit number display section
blinked for two seconds or "88" blinks in the room temperature display area for two seconds, a transmission error may have occurred.
FUNCTION SELECTION
TEST
Set the outdoor unit's refrigerant address.
Press the [ CLOCK] buttons ( and ) to select the desired refrigerant address. The refrigerant address changes from "00" to "15".
(This operation is not possible for single refrigerant systems.)
), and then restart from step .
Press the [ of the indoor unit for which you want to perform function selection. The unit
number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
To set each indoor unit individually, select "01" to "04". To set all the indoor units collectively, select "AL".
Confirm the refrigerant address and unit number.
Press the number. After a while, "- - " will start to blink in the mode number display area.
Mode number display section
* "88" will blink in the room temperature display area if the selected refrigerant
address does not exist in the system. Furthermore, if refrigerant address display area also blinks, there are no units that corre­spond to the selected unit number. In this case, the refrigerant address and unit number may be incorrect, so repeat steps
Select the mode number.
Press the [ TEMP] buttons ( and ) to set the desired mode number.
(Only the selectable mode numbers can be selected.)
Select the setting content for the selected mode.
Press the blink, so check the currently set content.
Register the settings you have made in steps to .
Press the to blink and registration starts.
MODE
button to confirm the refrigerant address and unit
MODE
"F"
appears and blinks in the unit number display area and the
and to set the correct ones.
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
Setting number 1 = Indoor unit operating average
When the refrigerant address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified refrigerant address will start fan operation.
Example) When the refrigerant address is set to 00 and the unit number is 02.
00 refrigerant address
Outdoor unit
Indoor unit
Designate operation
* When grouping different refrigerant systems, if an indoor unit other than the
one to which the refrigerant address has been set performs fan operation, there may be another refrigerant address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a refrigerant address exists.
Mode number display section
Press the [ TEMP] buttons ( and ) to select the desired setting number.
The mode number and setting number will stop blinking and remain lit, indicating the end of registration.
Unit number 01 Unit number 02
Remote controller
Mode number 02 = Indoor tempreture detection
Setting number 3 = Remote controller built-in sensor
Fan draft
Unit Function Setting by the Remote Controller (for Mr. SLIM P series) VI.
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path.
If you wish to continue to select other functions, repeat steps to .
Complete function selection.
Hold down the ( mode is 15 to 28) and buttons
simultaneously for at least two seconds. After a while, the function selection screen will disappear and the air condi-
tioner OFF screen will reappear.
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table to indicate the change.
FILTER
TEST
" blinks in the room temperature display area, a transmission error may have occurred.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
41
VII. Test Run by the Remote Controller (for Mr. SLIM P Series)
1. Check Points Under Test Run
Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leakage, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L1, L2) on the outdoor unit by 500V Merger and check that it is 1.0M
Don't use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block (1, 2).
This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply twelve hours before test run in order to protect compressor.
• For specifi c models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes of settings referring to the description of Selection of Functions through Remote Controller.
Make sure to read operation manual before test run. (Especially items to secure safety.)
2.Test Run using the Wired Remote Controller
or over.
"TEST RUN" and the currently selected operation mode are displayed altemately.
Displays the remaining test run time.
[TEST] button
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION MODE button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit's fan is rotating.
6. Press the ON/OFF button to reset the test run in progress.
While the room temperature display on the remote controller is “PLEASE WAIT”, the remote controller is disabled. Wait until “PLEASE WAIT” disappears before using remote controller. “PLEASE WAIT” appears for about 2 minutes after power supply is turned on. 1
The TEST RUN appears on the screen.
Cooling mode: Heating mode: Check if warm air blows. (It takes a little while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to provide optimum fan speeds. Therefore, the fan keeps running at a low speed to meet the current outside air condition unless it exceeds its available maximum power. Then, in actuality, the fan may stop or run in the reverse direction depending on the outside air, but this does not mean malfunction.
Check if cool air blows and water is drained.
7. Register the contact number.(Refer to V.4.3.3.)
Pipe (liquid) temperature
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not be displayed regardless of incorrect wiring.
1 After turning on the power supply, the system will go into startup mode, "PLEASE WAIT" will blink on the display section of
the room temperature, and lamp(green) of the remote controller will blink.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the
address is not 0. LED3 will blink. As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system fi nishes, LED2(red) will be turned off.) In case OUTDOOR BOARD LED is digital display, [- ] and [ -] will be displayed alternately every second.
• If one of the above operations doesn't function correctly, the causes written below should be considered. Find causes from the
symptoms. The below symptoms are under test run mode. startup in the table means the display status of
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE WAIT”, and
After power is turned on, “PLEASE WAIT” is displayed for 3 minutes, then error code is displayed.
No display appears even when remote controller operation switch is turned on. (Operation lamp does not light up.)
Display appears but soon disappears even when remote controller is operated.
cannot be operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only green lights up. <00> After “startup” is displayed,
green(once) and red(once) blink alternately. <F1>
After “startup” is displayed, green(once) and red(twice) blink alternately. <F3, F5, F9>
After “startup” is displayed, green(twice) and red(once) blink alternately. <EA. Eb>
After “startup” is displayed, only green lights up. <00>
After “startup” is displayed, only green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2 minutes during
• Incorrect connection of outdoor terminal block (L1, L2, and S1, S2, S3.)
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity is wrong for S1, S2, S3.)
• Remote controller transmission wire is short circuit.
• There is no outdoor unit of address 0. (Address is other than 0.)
• Remote controller transmission wire is open-circuit.
• After canceling function selection, operation is not possible for about 30 seconds. (Normal)
system startup. (Normal)
1 written above.
Cause
42
Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD display.For details,please refer to "VIII.2. Error code list".
LCD
Malfunction indoor unit
P1~9
Malfunction indoor unit
Fb
Malfunction outdoor unit
U1~UP
Malfunction
F3~F9
E0~E5
Remote controller transmitting error Indoor/outdoor unit communication error
E6~EF
No error history
---­No applied unit
FFFF
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Contents of inferior phenomena
outdoor unit
Lits when power is supplied. Lits when power is supplied for wired remote controller. The indoor unit should be connected to the outdoor unit with address “0” setting.
Blink when indoor and outdoor unit are communicating.
43
Test Run by the Remote Controller (for Mr. SLIM P series)
VII.
VIII. Self-Diagnosis by the Remote Controller (for Mr.SLIM)
1. How To Proceed "Self-Diagnosis"
1-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below.
(If the outdoor unit is malfunctioning, the unit number will be "00".) In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the unit that first experienced trouble (i.e., the unit that transmitted the error code) will be displayed.
To clear the error code, press the
ON/OFF
button.
(Alternating Display)
Error code (2 or 4 digits)
When using remote operation of remote/local combined control,clear the error code by pressing the button on
Address (3 digits) or unit number (2 digits)
ON/OFF
remote controller after changing operation from remote to local.During central control by MELANS control , clear the erorr
code by pressing button on MELANS remote controller.
ON/OFF
1-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote controller or power is shut off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the will change as shown below.
Display self-diagnosis results. <When there is error code history> (For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
CHECK
button twice within three seconds. The display content
Unit number or refrigerant address to be diagnosed
(Alternating Display)
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number or address. The number (address) changes between [01] and [50] o r [00]
an d
[15].
The refrigerant address will begin to blink approximately three seconds after being selected and the self-diagnosis process will begin.
Error code (2 or 4 digits)
<When there is no error code history> <When there is no corresponding unit>
Reset the error history. Display the error history in the diagnosis result display screen (see step
44
Address (3 digits) or unit number (2 digits)
).
Press the
address or refrigerant address will blink.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following two methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within three seconds. The self-diagnosis
button twice within three seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the start
button. Self-diagnosis will be cancelled and the indoor unit will stop.
of self-diagnosis.
When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again.
1-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the
indicator will not light.
If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
change as shown below.
CHECK
button for five seconds or more. The display content will
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote
controller.
[Where the remote controller is not defective, but cannot be operated.]
(Error display 2) [E3], [6833] or [6832]blinks.
There might be noise or interference on the transmission path, or the indoor unit
or other remote controllers are defective. Check the transmission path and other
controllers.
Transmission is not possible.
[When the remote controller malfunctions] (Error display 1) "NG" blinks. The remote controller's transmitting-receiv-
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmis­sion path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
ing circuit is defective.
"ERC" and the number of data errors are displayed. Data error has occurred.
When the number of data errors is "02":
Transmission data from remote controller Transmission data on transmission path
Self-Diagnosis by the Remote Controller (for Mr. SLIM P series)
VIII.
To cancel remote controller diagnosis
Press the approximately 30 seconds, the state in effect before the diagnosis will be restored.
CHECK
button for five seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
45
2.Error Code List(for Mr.SLIM P series)
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1(green) and LED2(red) indicate the types of abnormality when it occurs. Types of abnormality can be indicated in details by connecting an optional part A-Control Service Tool (PAC-SK52ST) to connector CNM on outdoor controller board.
[Display] (1)Normal condition
Unit condition
When the power is turned on When unit stops When compressor is warming up When unit operates
(2)Abnormal condition
Indication Error
Outdoor controller board
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
Connector(63L) is open.
Connector(63H) is open.
2 connectors are open.
2 blinking 1 blinking
Mis-wiring of indoor/outdoor unit conne­cting wire, excessive number of indoor units (4 units or more)
Mis-wiring of indoor/outdoor unit co­nnecting wire (converse wiring or di­sconnection)
Startup time over
2 blinking
3 blinking
4 blinking
5 blinking
Indoor/outdoor unit communication error (signal receiving error) is detected by in­door unit.
Indoor/outdoor unit communication error (transmitting error) is detected by indoor unit.
Indoor/outdoor unit communication error (signal receiving error) is detected by outdoor unit.
Indoor/outdoor unit communication error (transmitting error) is detected by outdoor unit.
Remote controller signal receiving error is detected by remote controller.
Remote controller transmitting error is detected by remote controller.
Remote controller signal receiving error is detected by indoor unit.
Remote controller transmitting error is detected by indoor unit.
Error code is not defined.
Serial communication error <Communication between outdoor controller board and outdoor power board> <Communication between outdoor controller board and M-NET p.c. board>
Communication error of high prior signal(M-NET)
1.Error code displayed on remote controller.Error codes
Outdoor controller board A-Control Service Tool
LED1 (Green) LED2 (Red) Error code
Lighted Lighted Lighted Lighted
Lighted
Contents Inspection method
Not lighted Not lighted
Lighted
Error code
00, etc. 08, etc.
C5, H7 etc.
1
F3
Check if connector (63L or 63H) on the outdoor controller board is not disconnected.
F5
Check continuity of pressure switch (63L or 63H) by tester.
F9
Check if indoor/outdoor connecting wire is connected correctly.
(EA)
Check if 4 or more indoor units are connected to outdoor unit.
Check if noise entered into indoor/outdoor connecting wire or
(Eb)
power supply. Re-check error by turning off power, and on again.
(EC)
Check if indoor/outdoor connecting wire is connected correctly.
E6
Check if noise entered into indoor/outdoor connecting wire or power supply.
E7
Check if noise entered into indoor/outdoor controller board. Re-check error by turning off power, and on again.
(E8)
(E9)
Check if connecting wire of indoor unit or remote controller is
E0
connected correctly. Check if noise entered into transmission wire of remote vcontroller.
E3
Re-check error by turning off power, and on again.
E4
E5
Check if remote controller is MA remote controller(PAR-21MAA).
EF
Check if noise entered into transmission wire of remote controller. Check if noise entered into indoor/outdoor connecting wire. Re-check error by turning off power, and on again.
Check if connector (CN4) on outdoor controller board and outdoor
Ed
power board is not disconnected.
Check if there is poor connection of connector on outdoor controller
board(CNMNT and CNVMNT).
Check M-NET communication signal.
A0~A8
given in ( ) are not displayed on remote controller.
Indication of the display
Alternately blinking display
Operation mode
46
Indication Error
Outdoor controller board
LED1 (Green)
3 blinking 1 blinking
LED2 (Red)
Abnormality of shell thermostat and discharging temperature (TH4)
Contents Inspection method
Error code
1
Check if stop valves are open.
U2
Check if connectors (TH4, LEV-A) on outdoor controller board are not disconnected. Check if unit fills with specified amount of refrigerant. Measure resistance values among terminals on indoor valve and outdoor linear expansion valve using a tester.
4 blinking
2 blinking
3 blinking
4 blinking
5 blinking
6 blinking
7 blinking
1 blinking
2 blinking
3 blinking
4 blinking
Abnormal high pressure (High pressure switch 63H worked.)
Abnormality of outdoor fan
Check if indoor/outdoor units have a short cycle on their air ducts.
U1
Check if connector (63H) on outdoor controller board is not disconnected. Check if heat exchanger and filter is not dirty. Measure resistance values among terminals on linear expansion valve using a tester.
Check the outdoor fan motor.
U8
motor rotational speed
Compressor over current breaking (Start-up locked) Compressor over current breaking Abnormality of current sensor (P.B.) Abnormality of power module Open/short of discharge thermistor (TH4)
Open/short of outdoor thermistors
Check if stop valves are open.
UF
Check looseness, disconnection, and converse connection of compressor wiring.
UP
Measure resistance values among terminals on compressor using a tester. Check if outdoor unit has a short cycle on its air duct.
UH
U6
Check if connectors (TH3, TH4, TH6 and TH7) on outdoor controller board and conn-
U3
ector (CN3) on outdoor power board are not disconnected.
U4
Measure resistance value of outdoor thermistors.
(TH3, TH6, TH7 and TH8) Abnormality of radiator panel
temperature Abnormality of voltage Check looseness, disconnection, and converse connection of compressor wiring.
Abnormality of room temperature thermistor (TH1) Abnormality of pipe temperature thermistor /Liquid (TH2) Abnormality of pipe temperature
Check if indoor/outdoor units have a short cycle on their air ducts.
U5
Measure resistance value of outdoor thermistor(TH8).
U9
Measure resistance value among terminals on compressor using a tester. Check the continuity of contactor (52C). Check if power supply voltage decreases. Check the wiring of CN52C. Check the wiring of CNAF.
Check if connectors (CN20, CN21 and CN29) on indoor controller board are not
P1
disconnected.
P2
Measure resistance value of indoor thermistors.
P9
thermistor/Condenser-Evaporator Abnormality of drain sensor (DS) Indoor drain overflow protection
Freezing (cooling)/overheating (heating) protection
Abnormality of pipe temperature
Check if connector (CN31) on indoor controller board is not disconnected.
P4
Measure resistance value of indoor thermistors.
P5
Measure resistance value among terminals on drain-up machine using a tester. Check if drain-up machine works. Check drain function.
Check if indoor unit has a short cycle on its air duct.
P6
Check if heat exchanger and filter is not dirty. Measure resistance value on indoor and outdoor fan motors. Check if the inside of refrigerant piping is not clogged.
Check if indoor thermistors (TH2 and TH5) are not disconnected from holder.
P8
Check if stop valve is open. Check converse connection of extension pipe. (on plural units connection) Check if indoor/outdoor connecting wire is connected correctly. (on plural units connection)
5 blinking
Abnormality of indoor
Fb
controller board
--
Abnormality of remote controller board
E1,E2
1.Error code displayed on remote controller.Error codes
Replace indoor controller board.
Replace the remote controller.
given in ( ) are not displayed on remote controller.
Self-Diagnosis by the Remote Controller (for Mr. SLIM P series)
VIII.
47
IX.
Monitoring the Operation Data by the Remote Controller(for Mr. SLIM)
1.How to "Monitor the Operation Data"
Turn on the [Monitoring the operation data]
Example) Request code "004"
Discharge temperature 156˚F Refrigerant address "00"
(3)
(7)
(5)
(1)
(2)
(4)
(1) Press the
(2) Press the
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode (i.e., while "- - - -" is blinking),
Operating the service inspection monitor
- - - ] appears on the screen (at
[
(The display (at (3) Press the [TEMP] buttons (
[Screen
(4) Press the [CLOCK] buttons ( and ) to set the desired request code No.
(5) Press the
(The requested data will be displayed at
TEST
CHECK
since no buttons are operative.
]
FILTER
button for three seconds so that [Maintenance mode] appears on the screen (at ).
button for three seconds to switch to [Maintenance monitor].
) when [Maintenance monitor] is activated.
) now allows you to set a request code No.)
and ) to select the desired refrigerant address.
button to perform data request.
in the same way as in maintenance mode.)
(6)
B: Refrigerant address C: Data display area D: Request code display area
Data collected during operation of the remote controller will be displayed. The collected data such as temperature data will not be updated automatically even if the data changes. To display the updated data, carry out step (4) again.
Canceling the Monitoring the operation data
(6) While [Maintenance monitor] is displayed, press the
(7) To return to normal mode, press the
ON/OFF
CHECK
button.
button for three seconds to return to maintenance mode.
48
2. Request Code List
* Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.
Request content
Request code
Operation state
0
Compressor-Operating current (rms)
1
Compressor-Accumulated operating time
2
Compressor-Number of operation times
3
Discharge temperature (TH4)
4
Outdoor unit - Liquid pipe 1 temperature (TH3)
5
Outdoor unit - Liquid pipe 2 temperature
6
Outdoor unit-2-phase pipe temperature (TH6)
7
8
Outdoor unit-Outside air temperature (TH7)
9
Outdoor unit-Heat sink temperature (TH8)
10
11
Discharge super heat (SHd)
12
Sub-cool (SC)
13
14
15
Compressor-Operating frequency
16
Compressor-Target operating frequency
17
Outdoor unit-Fan output step
18
Outdoor unit-Fan 1 speed
19
(Only for air conditioners with DC fan motor)
Outdoor unit-Fan 2 speed
20
(Only for air conditioners with DC fan motor)
21
LEV (A) opening
22
LEV (B) opening
23
24
Primary current
25
DC bus voltage
26
27
28
Number of connected indoor units
29
Indoor unit-Setting temperature
30
Indoor unit-Intake air temperature <Measured by thermostat>
31
Indoor unit-Intake air temperature (Unit No. 1)
32
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 2)
33
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 3)
34
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 4)
35
<Heat mode-4-deg correction>
36
Indoor unit - Liquid pipe temperature (Unit No. 1)
37
Indoor unit - Liquid pipe temperature (Unit No. 2)
38
Indoor unit - Liquid pipe temperature (Unit No. 3)
39
Indoor unit - Liquid pipe temperature (Unit No. 4)
40
41
Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)
42
Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)
43
Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)
44
Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)
45
46
47
Thermostat ON operating time
48
Test run elapsed time
49
Description
(Display range)
Refer to 2-1. Detail Contents in Request Code.
0 – 50
0 – 9999
0 – 9999
37 ~ 327
-40 ~ 194
-40 ~ 194
-38 ~ 190
-38 ~ 190
-40 ~ 327
0 – 327
0 – 234
0 – 255
0 – 255
0 – 10
0 – 9999
0 – 9999
0 – 500
0 – 500
0 – 50
180 – 370
0 – 4
62 ~ 86
46 ~ 102
46 ~ 102
46 ~ 102
46 ~ 102
46 ~ 102
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
0 – 999
0 – 120
10 hours
100 times
Unit Remarks
A
(3 ~ 164˚C)
˚F
(-40 ~ 90˚C)
˚F
(-40 ~ 90˚C)
˚F
˚F
(-39 ~ 88˚C)
(-39 ~ 88˚C)
˚F
(-40 ~ 164˚C)
˚F
deg F
deg F
Step
rpm
rpm
Pulses
Pulses
Units
Minutes
Minutes
(0 ~ 182 deg C)
(0 ~ 130 deg C)
Hz
Hz
"0" is displayed if the air conditioner is a single-fan type.
A
V
(17 ~ 30˚C)
˚F
(8 ~ 39˚C)
˚F
"0" is displayed if the target unit is not present.
˚F
(8 ~ 39˚C)
˚F
˚F
˚F
˚F
˚F
˚F
˚F
˚F
˚F
˚F
˚F
is displayed if the target unit is not present.
"0"
(-39 ~ 88˚C)
is displayed if the target unit is not present.
"0" (-39 ~ 88˚C)
Not possible to activate maintenance mode during the test run.
Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) IX.
49
Request content
Request code
Indoor unit-Control state
50
Outdoor unit-Control state
51
Compressor-Frequency control state
52
Outdoor unit-Fan control state
53
Actuator output state
54
Error content (U9)
55
56
57
58
59
Signal transmission demand capacity
60
Contact demand capacity
61
External input state (silent mode, etc.)
62
63
64
65
66
67
68
69
Outdoor unit-Capacity setting display
70
Outdoor unit-Setting information
71
72
Outdoor unit-SW1 setting information
73
Outdoor unit-SW2 setting information
74
75
Outdoor unit-SW4 setting information
76
Outdoor unit-SW5 setting information
77
Outdoor unit-SW6 setting information
78
Outdoor unit-SW7 setting information
79
Outdoor unit-SW8 setting information
80
Outdoor unit-SW9 setting information
81
Outdoor unit-SW10 setting information
82
83
M-NET adapter connection (presence/absence)
84
85
86
87
88
89
Display of execution of replace/wash operation
Outdoor unit-Microcomputer version information
90
Outdoor unit-Microcomputer version information (sub No.)
91
92
93
94
95
96
97
98
99
Outdoor unit - Error postponement history 1 (latest)
100
Outdoor unit - Error postponement history 2 (previous)
101
Outdoor unit - Error postponement history 3 (last but one)
102
Description
(Display range)
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
0 – 255
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
Refer to 2-1.Detail Contents in Request Code.
"0000": Not connected "0001": Connected
"0000": Not washed "0001": Washed
Examples) Ver 5.01
"0501"
Auxiliary information (displayed after
version information)
Examples) Ver 5.01 A000
Displays postponement code. (" - - " is
displayed if no postponement code is present)
Displays postponement code. (" - - " is
displayed if no postponement code is present)
Displays postponement code. (" - - " is
displayed if no postponement code is present)
"A000"
Code
Code
Code
Unit Remarks
%
Ver
50
Request content
Request code
Error history 1 (latest)
103
Error history 2 (second to last)
104
Error history 3 (third to last)
105
Abnormal thermistor display
106
(TH3/TH6/TH7/TH8)
Operation mode at time of error
107
Compressor-Operating current at time of error
108
Compressor-Accumulated operating time at time of error
109
Compressor-Number of operation times at time of error
110
Discharge temperature at time of error
111
Outdoor unit - Liquid pipe 1 temperature (TH3) at time of error
112
Outdoor unit - Liquid pipe 2 temperature at time of error
113
Outdoor unit-2-phase pipe temperature (TH6) at time of error
114
115
Outdoor unit-Outside air temperature (TH7) at time of error
116
Outdoor unit-Heat sink temperature (TH8) at time of error
117
Discharge super heat (SHd) at time of error
118
Sub-cool (SC) at time of error
119
Compressor-Operating frequency at time of error
120
Outdoor unit at time of error
121
• Fan output step
Outdoor unit at time of error
122
• Fan 1 speed (Only for air conditioners with DC fan)
Outdoor unit at time of error
123
• Fan 2 speed (Only for air conditioners with DC fan)
124
LEV (A) opening at time of error
125
LEV (B) opening at time of error
126
127
128
129
Thermostat ON time until operation stops due to error
130
131
Indoor - Liquid pipe temperature at time of error
132
Indoor-2-phase pipe temperature at time of error
133
Indoor at time of error
134
• Intake air temperature <Thermostat judge temperature>
135
136
137
138
139
140
~
146
147
148
149
Indoor-Actual intake air temperature
150
Indoor - Liquid pipe temperature
151
Indoor-2-phase pipe temperature
152
Description
(Display range)
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
3
: F TH3
6 : F TH6
7 : F TH7
8 : F TH8
0 : F No thermistor error
Displayed in the same way as request code "0".
0 – 50
0 – 9999
0 – 9999
37 ~ 327
-40 ~ 194
-40 ~ 194
-38 ~ 190
-38 ~ 190
-40 ~ 327
0 – 327
0 – 234
0 – 255
0 – 10
0 – 9999
0 – 9999
0 – 500
0 – 500
0 – 999
-38 ~ 190(-39~88˚C)
-38 ~ 190(-39~88˚C)
-38 ~ 190
-38 ~ 190
-38 ~ 190
-38 ~ 190
Unit Remarks
Code
Code
Code
Sensor
number
A
10 hours
100 times
˚F
˚F
˚F
˚F
˚F
˚F
deg F
deg F
Hz
Step
rpm
rpm
Pulses
Pulses
Minutes
˚F
˚F
˚F
˚F
˚F
˚F
(3 ~ 164˚C)
(-40 ~ 90˚C)
(-40 ~ 90˚C)
(-39 ~ 88˚C)
(-39 ~ 88˚C)
(-39 ~ 88˚C)
(-40 ~ 164˚C)
(0 ~ 182 deg C)
(0 ~ 130deg C)
"0" is displayed if the air conditioner is a single-
fan type.
Average value of all indoor units is displayed if the air condi-
tioner consists of two or more indoor units.
Average value of all indoor units is displayed if the air condi-
tioner consists of two or more indoor units.
(-39~88˚C)
(-39~88˚C)
(-39~88˚C)
(-39~88˚C)
Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) IX.
51
Request content
Request code
153
Indoor-Fan operating time
154
(After filter is reset)
Indoor-Total operating time
155
(Fan motor ON time)
156
Indoor fan output value (Sj value)
157
Indoor fan output value
158
(Pulsation ON/OFF)
Indoor fan output value (duty value)
159
160
161
Indoor unit-Model setting information
162
Indoor unit-Capacity setting information
163
Indoor unit-SW3 information
164
Wireless pair No. (indoor control board side) setting
165
Indoor unit-SW5 information
166
167
~
189
Indoor unit-Microcomputer version information
190
Indoor unit-Microcomputer version information (sub No.)
191
192
~
764
Stable operation (Heat mode)
765
Stable operation (Cool mode)
766
Stable operation cancellation
767
Description
(Display range)
0 – 9999
0 – 9999
0 –
255
Fan control data
"
00 **" "**" indicates fan control data.
"00 **" "**" indicates fan control data.
Refer to 12-2-1 Detail Contents in Request Code.
Refer to 12-2-1 Detail Contents in Request Code.
Undefined
Refer to
12-2-1 Detail Contents in Request Code.
Undefined
Examples) Ver 5.01 "0501"
Auxiliary information (displayed after version information)
Examples) Ver 5.01 A000 "A000"
This request code is not provided to collect data. It is used to fix the operation state.
This request code is not provided to collect data. It is used to fix the operation state.
This request code is not provided to collect data. It is used to cancel the operation state that has been
fixed by request codes "765" and "766".
Unit Remarks
1 hour
10 hours
For indoor fan phase control
For indoor fan pulsation control
For indoor DC brushless motor control
Ver
52
2-1. Detail Contents in Request Code
[Operation state] (Request code ":0")
Data display
C4
Relay output state
Operation mode
Operation mode
Display Operation mode
0 STOP • FAN C COOL • DRY H HEAT
d Defrost
[Indoor unit – Control state] (Request code :" 50")
Data display
Unit No. 4 state
Unit No. 3 state
Unit No. 2 state
Unit No. 1 state
Example) Request code "004"
B: Refrigerant address C: Data display area D: Request code display area
Relay output state
Display
0 1
2 3
4 5 6 7
8
A
Display State
0 Normal 1 Preparing for heat operation. 2– 3– 4 Heater is ON. 5 Anti-freeze protection is ON. 6 Overheat protection is ON. 7 Requesting compressor to turn OFF. F There are no corresponding units.
Power currently
supplied to compressor
ON ON
Compressor Four-way valve Solenoid valve
ON ON ON ON
Discharge temperature 156˚F Refrigerant address "00"
ON ON
ON ON
ON
ON
ON
ON
ON
[Outdoor unit – Control state] (Request code ":51")
Data display State 0 0 0 0 Normal 0 0 0 1 Preparing for heat operation. 0 0 0 2 Defrost
[Compressor – Frequency control state] (Request code ":52")
Data display
00
Frequency control state
Frequency control state
Frequency control state
Display Current limit control
0 No current limit 1 Primary current limit control is ON. 2 Secondary current limit control is ON.
Frequency control state
Display
Discharge temperature
0 1 Controlled 2 Controlled 3 Controlled Controlled 4 Controlled 5 Controlled Controlled 6 Controlled Controlled 7 Controlled Controlled Controlled 8 Controlled 9 Controlled Controlled A Controlled Controlled b Controlled Controlled Controlled C Controlled Controlled d Controlled Controlled Controlled E Controlled Controlled Controlled F Controlled Controlled Controlled Controlled
Condensation temperature
overheat prevention
overheat prevention
protection control
Anti-freeze
Heat sink temperature
overheat prevention
Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) IX.
53
[Fan control state] (Request code :" 53")
Data display
00
Fan step correction value by heat sink temperature overheat prevention control
Fan step correction value by cool condensation temperature overheat prevention control
Display Correction value
- (minus) – 1 00
1
2
+1
+2
[Actuator output state] (Request code :"54")
Data display
00
Actuator output state
Actuator output state
Actuator output state
Display SV1 Four-way valve Compressor
0 1
2 3
4 5
6 7
8 9
A
b
C
d
E F
ON
ON
ON
ON
ON
ON
ON
ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
Compressor is
warming up
ON ON
ON ON
ON ON
ON ON
Actuator output state
Display 52C SV2 SS
0 1
2 3 4 5 6 7
ON
ON
ON
ON
ON ON
ON ON
ON ON ON ON
[Error content (U9)] (Request code :"55")
Data display
00
Error content
Error content
Error content : Detected
Display
0 1 2 3 4 5 6 7 8 9 A b C d E F
Overvoltage Undervoltage L1-phase
error error open error
Power synchronizing
signal error
Error content : Detected
0 1 2 3
Converter Fo
error
PAM error
Display
54
[Contact demand capacity] (Request code "61")
Data display
000
Setting content
[External input state] (Request code "62")
Data display
000
Input state
Setting content
ON
ON
Setting
ON
Display Setting value
0 1 50% 2 75% ON 3 100%
Input state : Input present
Display
0 1 2 3 4 5 6 7 8 9 A b
C
d E F
0%
Contact demand Silent mode Spare 1 Spare 2
input input input input
SW7-1 SW7-2
[Outdoor unit -– Capacity setting display] (Request code : "70")
Data display
935 10 50 11 60 14 71 20 100 25 125 28 140 40 200 50 250
Capacity
[Outdoor unit – Setting information] (Request code "71")
Data display
00
Setting information
Setting information
Setting information
Display Defrost mode
0 Standard 1 For high humidity
Setting information
Display
0 1 2 3
Single-/ Heat pump/
three-phase
Single-phase
Three-phase
cooling only
Heat pump
Cooling only
Heat pump
Cooling only
Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) IX.
55
[Outdoor unit switch setting display (SW1 to SW10, except SW3)] Request codes: 73 to 82
0: Swich OFF 1: Swich ON
SW1, SW2, SW6, SW7
123456
000000 0000 100000 0001 010000 0002 110000 0003 001000 0004 101000 0005 011000 0006 111000 0007 000100 0008 100100 0009 010100 000A 110100 000b 001100 000C 101100 000d 011100 000E 111100 000F 000010 0010 100010 010010 110010 001010 101010 011010 111010 000110 100110 010110 110110 001110 101110 011110 111110 000001 100001 010001 110001 001001 101001 011001 111001 000101 100101 010101 110101 001101 101101 011101 111101 000011 100011 010011 110011 001011 101011 011011 111011 000111 100111 010111 110111 001111 101111 011111 111111
Data display
00 11 00 12 00 13 00 14 00 15 00 16 00 17 00 18 00 19 00 1A 00 1B 00 1C 00 1D 00 1E 00 1F 00 20 00 21 00 22 00 23 00 24 00 25 00 26 00 27 00 28 00 29 00 2A 00 2B 00 2C 00 2D 00 2E 00 2F 00 30 00 31 00 32 00 33 00 34 00 35 00 36 00 37 00 38 00 39 00 3A 00 3B 00 3C 00 3D 00 3E 00 3F
0: Swich OFF 1: Swich ON
SW5
1234
0000 0000 1000 0001 0100 0002 1100 0003 0010 0004 1010 0005 0110 0006 1110 0007 0001 0008 1001 0009 0101 000A 1101 000b 0011 000C 1011 000d 0111 000E 1111 000F
0: Swich OFF 1: Swich ON
SW8
123
000 0000 100 0001 010 0002 110 0003 001 0004 101 0005 011 0006 111 0007
0: Swich OFF 1: Swich ON
SW4, SW9, SW10
12
0 0 00 00 1 0 00 01 0 1 00 02 1 1 00 03
Data display
Data display
Data display
56
[Indoor unit – Model setting information] (Request code : 162)
Data display
00
See the table on the right.
Display Model setting state Display Model setting state
00 20 01 21 02 22 03 23 04 24 05 25 06 26 07 27 08 28 09 29 0A 2A 0b 2b 0C 2C 0d 2d 0E 2E 0F 2F 10 30 11 31 12 32 13 33 14 34 15 35 16 36 17 37 18 38 19 39 1A 3A 1b 3b 1C 3C 1d 3d 1E 3E 1F 3F
PKA-A•GA(L) PKA-A•FA(L) PCA-A•GA PLA-A•AA
[Indoor unit – Capacity setting information] (Request code 163 )
Data display
00
See the table on the right.
Display Capacity setting state Display Capacity setting state
00 10 42 01 11 02 12 03 13 04 14 05 15 06 12 16 07 17 08 18 09 18 19 0A 1A 0b 24 1b 0C 1C 0d 30 1d 0E 1E 0F 36 1F
[Wireless pair No. (indoor control board side) setting] (Request code 165 )
Data display
00
See the table on the right.
Display Pair No. setting state
00 No. 0 01 No. 1 J41 disconnected 02 No. 2 J42 disconnected 03 No. 3 J41, J42 disconnected
Monitoring the Operation Data by the remote Controller (for Mr. SLIM P series) IX.
57
X. System Control (for Mr. SLIM)
VARIETY OF SYSTEM FUNCTION
System Name System Diagram Features
There are two types of remote controllers: wired type and wireless type. Simultaneous twin units are counted as one unit, and the indoor units are started or stopped
simultaneously.
Up to two remote controllers can be connected to one group. Simultaneous twin units are counted as one unit.
Operation control by the latest command (last en­tered priority) Wired and wireless remote controllers can be com­bined as a pair.
One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each outdoor unit. Simultaneous twin units are counted as one unit. All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each outdoor unit. Up to two remote controllers can be connected.
All the air conditioners can be turned ON/OFF collectively from a distance. Operation can be switched between the remote operat­ing panel and local controller. Operations (e.g., temperature adjustment, airflow, air­flow direction) except for start/stop operations can be performed even if the operations from the local remote controllers are prohibits. In the case of simultaneous twin units, connect the controller to one indoor unit only. If connected to two or more indoor units, an error (operation stop) may occur. Control by an external timer is possible by connecting it.
A.Remote control-
ler operation (Standard)
B.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
C.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
* Outdoor unit`s re-
frigerant address needs to be set.
Remote/local
D.
combined control operation
Allows start/stop of the air condi­tioner from a dis­tance, and prohib­its/permits start/ stop from remote controllers.
Indoor unit
Outdoor unit
Remote Controller
Indoor unit
Remote Controller
* One of the wired remote con-
trollers must be set as a sub remote controller.
Indoor unit
Outdoor unit
Remote Controller
Relay box
Indoor unit
Remote Controller
Remote operating panel
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
Wired remote controller (addi­tional) (PAR-21MAA)
Remote ON/OFF adapter (PAC-SE55RA-E) Relay box (Part to be provided at your site) Remote operating panel (Part to be provided at your site)
E.Operation by
external signal
F.Control by external signal
and remote display
Enables you to display the op­eration state and control start/stop from a distance.
58
Adapter
Indoor unit
Remote Controller
Remote display panel (operation, error)
Use of optional "remote ON/OFF adapter" enables remote control via relay. (Level signal)
Extraction of non-voltage contact output
Use of optional "remote operation adapter" and "remote display panel" (Part to be provided at your site) provides non-voltage contact outputs of signals (operation, error) and operation/stop input
function.
Extraction of DC12 V contact output
Use of optional "Multiple remote controller adapter" and "remote display panel" your site) (operation, error)
provides DC12 V contact outputs of signals
and operation/stop input function.
(Part to be provided at
Remote ON/OFF adapter (PAC-SE55RA-E)
Remote operation adapter (PAC-SF40RM-E) Remote display panel (Part to be provided at your site)
Multiple remote controller adapter (PAC-SA88HA) Remote display panel (Part to be provided at your site)
System Name System Diagram Features
Weekly timer:In addition to ON/OFF, up to eight
temperature patterns can be set for each day of the week.
G. Timer operation
Enables control of start and stop.
* For control by
external timer, refer to Remote/ local combined control operation".
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined. Simple timer: Start and stop operations can each be
performed once within 72 hours (can be set in 1-hour increments).
Auto off timer: Operation is stopped when the preset
time elapses following the start of operation. The time can be set from 30 minutes to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
MA Remote controller (PAR-21MAA)
H.Interlock opera-
tion with periph-
eral equipment
Enables control of Mitsubishi Lossnay ventilator by remote controller.
I.Centralized
control
J.Demand control
Lossnay ventilator
<Connection with M-NET system>
Power supply unit
Central controller, etc.
Adaptor to input external demand signal
Relay box
Remote Operating panel
Indoor unit
Remote Controller
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Remote Controller
Connecting a Lossnay ventilator and an indoor unit enables control of interlock/solo ventilation opera­tion and airflow. (Only the microcomputer type Lossnay ventilator can be used.)
Connecting the M-NET connection adapter to outdoor unit enables connection of MELANS system control­ler (for M-NET). When using A-control operation, the number of indoor units in a MELANS system is limited to the number of outdoor units. (Simultaneous twin units are counted as one unit.) Number of controlled outdoor units Central controller: 50 units Group remote controller (PAC-SC30GR): 16 units
• Demand control is available by external input. In this mode, power consumption iis decreased within the range of usual 0-100%.
M-NET adapter (Option PARTS) Central controller (G-50A) Group remote controller (PAC-SC30GR), etc.
Adapter to input external demand signals. (PAC-SC36NA)
Relay box (Part to be provided at your site )
Remote operating panel (Part to be provided at your site)
59
X. System Control (for Mr. SLIM P series)
1. One Remote Controller (Standard) Operation
1-1 One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
Slim Air Conditioners System
System diagram (Wired remote controller)
Outdoor unit OC
Indoor unit IC
Wired remote
Indoor/Outdoor connection cable
Remote controller cable
controller R
(Reference)
If simultaneous twin, connect the remote controller to any one of the indoor units. All functions of the indoor unit can
be controlled even if different models (different types) are mixed. Do not use crossover wiring among indoor units with simultaneous twin units. (Prohibited item.) Electrical wiring diagram
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
Outdoor unit Indoor unit Remote controller
Standard 1:1 Simultaneous Twin
OC
3(2)
IC-1
2
R
OC
IC-1
R
3(2)
2
3(2)
IC-2
Power source wiring
L L2
GR
OC
1
S1 S2 S3
(Polarity)
S1 S2 S3
IC
1 2
(No polarity)
R
1 2
1-2 Wireless remote controller
Slim Air Conditioners System
System diagram
Outdoor unit OC
(Wireless remote controller receiver)
(Reference)
If simultaneous twin, connect the remote controller to any one of the indoor units. All functions of the indoor unit can be controlled even if
different models (different types) are mixed. Do not use crossover wiring among indoor units with simultaneous twin units. (Prohibited item.) Electrical wiring diagram
Indoor unit IC
Wireless remote controller receiver section R'
Indoor/Outdoor connection cable
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
Standard 1:1 Simultaneous Twin
OC
IC-1
R'
3(2)
9
OC
IC-1
R'
3(2)
9
3(2)
IC-2
60
Indoor unit IC
Controller board
S1 S2 S3
Indoor/outdoor connection cable terminal block
CN90
9
12
Remote controller cable terminal block
Wireless remote controller receiver R’
CNB
2. Two-remote Controller Operation
2-1 Two Wired Remote Controllers
Slim Air Conditioner System
Standard 1:1 Simultaneous Twin
(R: Wired remote controller)'
System diagram (Wired remote controller)
[Reference]
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
Indoor/outdoor connection cable
Remote controller cable
OC
IC
2
R-1
3(2)
OC
IC
R-1
2
3(2)
2
R-2
2
R-2
OC
3(2)
3(2)
IC-1
R-1 R-2
OC
IC-1
R-1 R-2
2
2
3(2)
IC-2
2
3(2)
IC-2
2
In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should not be connected by crossover wiring. (Prohibited) Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote
controller's function
selection.
2-2 Two Wireless Remote Controllers
Slim Air Conditioner System
Standard 1:1 Simultaneous Twin
(R': Wireless remote controller receiver)
Outdoor unit OC
System diagram (Wireless remote controller receiver)
Indoor unit IC
Wireless remote controller receiver section R'
Indoor/outdoor
connection cable
Receiver connection
cable
OC
3(2)
IC-1
9 9
R'-1
3(2)
IC-2
R'-2
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
[Reference]
In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers (one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should not be connected by crossover wiring. (Prohibited) In the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with systems consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the pair numbers will be "0"(factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously. When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the operation made last by any of the remote controllers will be effective.
2-3 One Wired and One Wireless Remote Controller
Slim Air Conditioner System
System diagram (Wired remote controller and wireless remote controller receiver)
Outdoor unit OC
Indoor unit IC
Wired remote controller
Indoor/outdoor connection cable
Standard 1:1 Simultaneous Twin
OC
3(2)
R
2
Receiver connection
9
cable
R'
Remote controller cable
IC
(R: Wired remote controller, R': Wireless remote controller receiver)
OC
3(2)
3(2)
IC-1
R
IC-2
9
2
R'
Receiver R·R'
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
[Reference]
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should not be connected by crossover wiring. (Prohibited) When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the operation made last by any of the wireless remote controllers will be effective.
X. System Control (for Mr. SLIM P series)
61
3. Group Control Operation
(Collective Operation and Control of Multiple Refrigerant Systems (2 to 16))
Multiple Mr.Slim air conditioners can be operated with the same settings (e.g., operation mode, preset temperature, etc.) by using one remote controller. Each outdoor unit can be turned ON/OFF individually by the intake sensor. Up to 16 refrigerant systems can be controlled as a group by one remote controller. A refrigerant address must be set for each outdoor unit. Addresses "0" to "15" can be set with no duplicates. Address "0" must be set for one of the outdoor units.
* In the case of simultaneous twin, triple and quad units, only one refrigerant system is used.
Slim Air Conditioner System
Outdoor unit
System diagram (Wired remote controller or wireless remote controller receiver)
OC
Indoor unit IC
Wired remote controller R
Outdoor unit OC
Indoor/outdoor connection cable
Remote controller cable
Indoor/outdoor connection cable
Indoor unit IC
Wireless remote controller re­ceiver section R'
[Reference]
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.
For two-remote controller control, refer to "2. Two-Remote Controller Operation". However, when using both wired and wireless remote controllers, receivers must be connected to indoor units that are connected by crossover wiring. Connect an indoor unit having the highest functions among the group to the outdoor unit assigned to refrigerant address "0". <Refer to the example given below> If indoor units with vanes are used with those without vanes, connect the outdoor unit to a unit with vanes.
Function specifications <Example>
Item
Fan Number of fan speeds Up/down Presence / absence vane Swing function
Function
Left / right swing louver
Presence / absence
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should not be connected by crossover wiring. (Prohibited)
Standard 1:1 2 Standard 1:1 + Simultaneous Twin
OC-A
IC-A
OC-A
IC-A
Receiver connection cable
4-way ceiling cassette Wall mounted
PLA-A.AA PCA-A.GA
OC-B
3(2)
3(2)
IC-B
2
R
3(2)
9
R'
2
OC-B
3(2)
IC-B
controller crossover wiring
Remote controller crossover wiring
OC-A
IC-A
Remote
2
Ceiling
suspended
PKA-A.GA(L) PKA-A.FA(L)
44
OC-A
R'
3(2)
IC-A
2
R
3(2)
9
2
OC
IC-B1 IC-B2
2
OC
3(2)
3(2)
IC-B1 IC-B2
3(2)
3(2)
24
Outdoor unit address setting
For group control, an address must be set for each outdoor unit. To set addresses to outdoor units, use the DIP switch SW1 (3–6) provided on each outdoor control board (factory setting: all are set to "OFF"). Address setting by SW1 is as follows.
Function
Forced defrosting
1
Error history clear
SW1
Function selection
2
Refrigerant address setting
3 4 5 6
Operation by switch
ON OFF
Start Normal
Clear Normal
Used to set outdoor unit addresses ("0" to "15").
<SW1>
OFF
1 2 3 4 5 6
ON
OFF
1 2 3
0
4 5 6
OFF
1 2 3
8
4 5 6
Factory setting: All switches are set to OFF (i.e., refrigerant address
Refrigerant address No.
OFF
OFF
ON
ON
ON
1
1
2
2
3
3
2
1
4
4
5
5
6
6
OFF
OFF
ON
1
1
2
2
3
3
10
9
4
4
5
5
6
6
ON
1 2 3
3
4 5 6
OFF
ON
ON
1 2 3
11
4 5 6
1
1
2
2
3
3
5
4
4
4
5
5
6
6
OFF
ON
OFF
ON
1
1
2
2
3
3
13
12
4
4
5
5
6
6
1
1
2
2
3
3
7
6
4
4
5
5
6
6
OFF
ON
OFF
ON
1
1
2
2
3
3
15
14
4
4
5
5
6
6
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
"0").
* Checking the outdoor unit refrigerant addresses
To find the location of an outdoor unit with a specific refrigerant address, specify the address in self-diagnosis mode. The outdoor unit will operate intermittently. (For details on using self-diagnosis mode.)
Group operation by multiple remote controllers
Up to two remote controllers can be connected to each group. For details, refer to "2. TWO-REMOTE CONTROLLER OPERATION".
62
XI. External Dimensions
130<5-1/8>
unit : mm <inch>
120<4-3/4>
19
<3/4>
External colors : Cover Pure white (Munsell 6.9Y 8.9 /0.4)
LCD peripheral area Medium gray
63
XI. External Dimensions
Loading...