For use with R410A-compatible units
Table-1 Accesorry pipes
Pipe 1
Pipe 2
Pipe 3
Pipe 4
Pipe 5
Pipe 6
Pipe 7
Pipe 8
Pipe 9
Pipe 10
Pipe 11
Pipe 12
F (Connecting
Pipe Size)
ø9.52
ø15.88
ø12.7
ø6.35
ø12.7
ø19.05
ø22.2
ø28.58
ø15.88
ø9.52
ø19.05
ø22.2
Pipe Connection Specification
Quantity
G (Outer
Diameter)
ø12.7
ø19.05
ø19.05
ø9.52
ø15.88
ø25.4
ø25.4
ø25.4
ø12.7
ø6.35
ø15.88
ø19.05
CMY-Y104-G
1
1
–
3
3
–
–
–
–
–
–
–
CMY-Y108-G
1
1
1
6
5
1
1
1
–
–
2
1
CMY-Y1010-G
1
2
2
5
6
1
1
1
3
5
1
1
Table-2 Accesorry plugs
Plug 1
Plug 2
Plug 3
Plug 4
Plug 5
H (Connecting Pipe Size)
ø6.35
ø9.52
ø12.7
ø15.88
ø19.05
Pipe Connection Specification
Quantity
CMY-Y104-G
1
1
1
1
–
CMY-Y108-G
2
2
2
2
1
CMY-Y1010-G
2
2
2
2
1
Table-4
Model
Condition
Model
200
Connectable
indoor unit
Connectable
indoor unit
capacity
Total indoor
unit capacity
1~13
Model
20~250
100~260
Model
250
1~16
Model
20~250
125~325
Model
300
1~16
Model
20~250
150~390
Model
350
1~20
Model
20~250
175~455
Model
400
1~22
Model
20~250
200~520
Model
450
1~24
Model
20~250
225~585
Model
500
1~24
Model
20~250
250~650
Model
550
1~24
Model
20~250
275~715
Model
600
1~32
Model
20~250
300~780
Model
650
1~32
Model
20~250
325~845
Model
700
1~34
Model
20~250
350~910
Model
750
1~34
Model
20~250
375~910
Model
800
1~34
Model
20~250
400~1040
HEADER FOR 4 BRANCHING (CMY-Y104-G)
HEADER FOR 8 BRANCHING (CMY-Y108-G)
HEADER FOR 10 BRANCHING (CMY-Y1010-G)
1 The following parts are contained in this box. Please identify the quantity with types.
Header for 4 branching (CMY-Y104-G)
1 Instruction 2 Header 3 Header
For liquid line
This sheet 1 sheet
For gas line
1 pc.
Header for 8 branching (CMY-Y108-G)
1 Instruction 2 Header 3 Header
For liquid line
For gas line
4 Pipe cover - 1
1pc.
4 Pipe cover - 1
5 Pipe cover - 2 6 Band
2 pcs. 2 pcs. 4 pcs.
5 Pipe cover - 2 6 Band
INSTALLATION MANUAL
Usable for 3/4 branching
(* For 2 branching, use the optional header
for 2 branching.)
7
Sealing material
Usable for 5/6/7/8 branching
OPTIONAL PARTS
ODøG
IDøF
ODøG
IDøF
Pipe 1 – 7 Pipe 8 – 12
Caution
The incorrect selection of the type
of branch pipe and the size of
connecting pipe does not allow the
air conditioner to provide the rated
capacity.
Please read this instruction manual
carefully for correct mounting work.
This sheet 1 sheet
1 pc.
1pc.
Each 2 pcs. 4 pcs. 6 pcs.
Each 1 pc.
Plug 1 – 3 Plug 4·5
Header for 10 branching (CMY-Y1010-G)
1 Instruction 2 Header 3 Header
For liquid line
This sheet 1 sheet
For gas line
1 pc.
4 Pipe cover - 1
1pc. Each 2 pcs.
5 Pipe cover - 2 6 Band
4 pcs. 6 pcs.
7
Sealing material
Each 1 pc.
Usable for 9/10 branching
Note 1) Please prepare the following materials in addition to the items above. (1) Tape for sealing of insulation material (2) Extension pipe for refrigerant circuit.
2 Please observe the items below for the mounting work.
Table-3
Length
Height
difference
Item Pipe section
Total piping length
Farthest piping length (L)
Farthest piping length
after 1st branching (R)
Height difference between
indoor and outdoor units (H)
Height difference
between indoor units (h)
A + B + C + D + a +
b + c + d + e + f + g
A + C + D + g
or A + B + d
C + D + g
or B + d
Allowable value
300 m or less
150 m or less
40 m or less
—
—
50 m or less
15 m or less
1. Observe the limit on refrigerant piping length in
Table-3.
2. Observe the limit on the connection of indoor units
in Table-4.
3. Connect the header to piping or plug/pipe by
brazing. Non-oxidized brazing should be applied.
4. The header is equipped with stopper. Push in the
Limitation on refrigerant piping length
Outdoor unit
stopper until the pipe to be connected stops.
5. No limitation is applied to the mounting posture.
6. Be careful that foreign materials like dust will not
enter into the piping at the connection work.
1st branch
(Branch joint)
Indoor unit
Indoor unit
Branch header
Indoor unit
Indoor unit
7. Apply insulation material to all refrigerant pipings.
8. The piping after the header branching can not be
branched again.
Farthest piping length after 1st branching R= 30m or less
Farthest piping length L = 100m or less
Be sure to connect it to the indoor unit.
Branch joint
H is 50 m or less (When outdoor unit is installed above)
H’ is 40 m or less (When outdoor unit is installed below)
Indoor unit
Indoor unit
Indoor unit
difference h = 15m or less
Indoor - outdoor units height
Fig. 1 Note : Branch piping can not be applied after header branching.
Note: When the number of connecting pipes is less
than the number of header branches, insert a
plug of the appropriate size into each branch
that does not have piping connected to it.
Limitation on indoor unit connection
Outdoor unit
Indoor unit
ODøH
Model 200
ODøH
Example 1
Total indoor unit capacity
25 × 3 + 32 × 2 + 50 + 63 = 252
Fig. 2
Outdoor unit
Indoor unit
Model 250
Example 2
Total capacity of indoor units
25 × 2 + 32 + 40 + 50 + 63 + 80 = 315
3 Selection of refrigerant piping size and use of header
1. Prepare the pipe to be connected in the field.
2. Determine the piping sizes of each part from Table-5, 6 and 7.
3. The header can be connected to all piping sizes selected in the item
2. To match a specified piping size.
(1) use the joint as it is.
(2) use it by connecting the auxiliary pipe.
Please conduct actual work by referring Fig 3 and Table-5 ~ 12.
4. Cover the branch pipe end of the header, which are not in use, with the
plugs 1 ~ 5 provided.
Table-5 Piping size between outdoor unit and 1st branching (Fig.1-A)
Outdoor unit model Liquid pipe Gas pipe
Model 200
Model 250
Model 300
Model 350
Model 400
Model 450
Model 500
Model 550
Model 600
Model 650
Model 700
Model 750
Model 800
Model 800 over
*1 ø12.7 for over 90m
*2 ø12.7 for over 40m
ø9.52
ø9.52 *1
ø9.52 *2
ø12.7
ø12.7
ø15.88
ø15.88
ø15.88
ø15.88
ø15.88
ø19.05
ø19.05
ø19.05
ø19.05
Table-6 Piping size between branching (Fig.1-B·C·D)
Total capacity
of indoor units
~140
141~200
201~300
301~400
401~650
651~800
801~
Note: If Indoor unit capacity is 651 or more, it can’t connect to
Fig.1-B directly. Then use the 2-branch joints. (Fig.1-C·D)
Liquid pipe Gas pipe
ø9.52
ø9.52
ø9.52
ø12.7
ø15.88
ø19.05
ø19.05
ø15.88
ø19.05
ø22.2
ø28.58
ø28.58
ø34.93
ø41.28
Table-7 Piping size branching (Fig.1-a~g)
Indoor unit model Liquid pipe Gas pipe
20, 25, 32, 40, 50
63, 71, 80, 100, 125, 140
Note: If indoor unit model is 200 and 250, it can’t use the CMY-
200
250
Y104, Y108 and Y1010-G.
Then use the 2-branch joints.
ø6.35
ø9.52
ø9.52
ø9.52
ø12.7
ø15.88
ø19.05
ø22.2
ø19.05
ø22.2
ø22.2
ø28.58
ø28.58
ø28.58
ø28.58
ø28.58
ø28.58
ø28.58
ø34.93
ø34.93
ø34.93
ø41.28
Table-9 Between branching (Fig.1-B)
Pipe types
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Down stream
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Table-10 4-branch header (CMY-Y104-G) (Fig.1-a~d)
Section
Liquid pipe
1
Gas pipe
Liquid pipe
2
Gas pipe
Liquid pipe
3
Gas pipe
Liquid pipe
4
Gas pipe
Between branchings
capacity
Indoor unit
Outdoor unit
Joint
2-branch joints are
sold separately.
Connecting
Pipe Size (X)
ø12.7
ø19.05
ø12.7
ø 25.4
ø15.88
ø25.4
Connecting
Pipe Size
ø9.52
ø15.88
ø6.35
ø12.7
ø9.52
ø15.88
ø9.52
ø15.88
Model
140
Connect with
pipe 1
Connect with
pipe 2
Connect with
pipe 1
Connect with
pipe 2, 6
Not
connectable
Not
connectable
Model 20, 25,
32, 40, 50
Connect with
pipe 4
Connect with
pipe 5
No need pipe
No need pipe
Connect with
pipe 4
Connect with
pipe 5
Connect with
pipe 4
Connect with
pipe 5
Between First branching and outdoor unit
X
Model
141~200
Connect with
pipe 1
No need pipe
Connect with
pipe 1
Connect with
pipe 6
Connect with
pipe 1, 5
Connect with
pipe 6
Model 71, 80,
100, 125, 400
No need pipe
No need pipe
Not
connectable
Not
connectable
No need pipe
No need pipe
No need pipe
No need pipe
Model
201~300
Not
connectable
Not
connectable
Connect with
pipe 1
Connect with
pipe 7
Connect with
pipe 1, 5
Connect with
pipe 7
Model
200
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Model
301~400
Not
connectable
Not
connectable
No need pipe
No need pipe
Connect with
pipe 5
Connect with
pipe 8
Model
250
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Table-8 Between First branching and outdoor unit (Fig.1-A)
Pipe types
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Note: Pipes on 450-type unit and up cannot be branched using a header (4~10-branch header); use an optional 2-branch
Outdoor unit
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
joint.
Header
2
1
3
Connecting
Pipe Size (X)
ø12.7
ø19.05
ø12.7
ø 25.4
ø15.88
ø25.4
4
Model 200
Connect with pipe 1
No need pipe
Connect with pipe 1
Connect with pipe 6
Connect with pipe 1, 5
Connect with pipe 6
5
Model 250, 300
Not connectable
Not connectable
Connect with pipe 1
Connect with pipe 7
Connect with pipe 1, 5
Connect with pipe 7
6
7
Model 350
Not connectable
Not connectable
No need pipe
Connect with pipe 8
Connect with pipe 5
Connect with pipe 8
8
Table-11 8-branch header (CMY-Y108-G) (Fig.1-a~d)
Fig. 3
Model
401~650
Not
connectable
Not
connectable
Not
connectable
Not
connectable
No need pipe
Connect with
pipe 8
Model
651~800
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Model
801 or more
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Section
Indoor unit
Liquid pipe
1
Gas pipe
Liquid pipe
2
Gas pipe
Liquid pipe
3
Gas pipe
Liquid pipe
4
Gas pipe
Liquid pipe
5
Gas pipe
Liquid pipe
6
Gas pipe
Liquid pipe
7
Gas pipe
Liquid pipe
8
Gas pipe
Connecting
Pipe Size
ø9.52
ø19.05
ø9.52
ø15.88
ø9.52
ø15.88
ø9.52
ø15.88
ø9.52
ø15.88
ø6.35
ø12.7
ø9.52
ø15.88
ø6.35
ø12.7
Table-12 10-branch header (CMY-Y1010-G) (Fig.1-a~d)
Section
Indoor unit
Liquid pipe
1
Gas pipe
Liquid pipe
2
Gas pipe
Liquid pipe
3
Gas pipe
Liquid pipe
4
Gas pipe
Liquid pipe
5
Gas pipe
Liquid pipe
6
Gas pipe
Liquid pipe
7
Gas pipe
Liquid pipe
8
Gas pipe
Liquid pipe
9
Gas pipe
10
Liquid pipe
Gas pipe
Connecting
Pipe Size
ø9.52
ø19.05
ø6.35
ø15.88
ø9.52
ø19.05
ø6.35
ø15.88
ø9.52
ø15.88
ø6.35
ø12.7
ø9.52
ø15.88
ø6.35
ø12.7
ø9.52
ø15.88
ø6.35
ø12.7
Model 20, 25, 32,
40, 50
Connect with pipe 4
Connect with pipe 3
Connect with pipe 4
Connect with pipe 5
Connect with pipe 4
Connect with pipe 5
Connect with pipe 4
Connect with pipe 5
Connect with pipe 4
Connect with pipe 5
No need pipe
No need pipe
Connect with pipe 4
Connect with pipe 5
No need pipe
No need pipe
Model 20, 25, 32,
40, 50
Connect with pipe 4
Connect with pipe 3
No need pipe
Connect with pipe 5
Connect with pipe 4
Connect with pipe 3
No need pipe
Connect with pipe 5
Connect with pipe 4
Connect with pipe 5
No need pipe
No need pipe
Connect with pipe 4
Connect with pipe 5
No need pipe
No need pipe
Connect with pipe 4
Connect with pipe 5
No need pipe
No need pipe
Model 400
Not connectable
Not connectable
No need pipe
Connect with pipe 8
Connect with pipe 5
Connect with pipe 8
9
Model 71, 80, 100,
125, 140
No need pipe
Connect with pipe 2
No need pipe
No need pipe
No need pipe
No need pipe
No need pipe
No need pipe
No need pipe
No need pipe
Not connectable
Not connectable
No need pipe
No need pipe
Not connectable
Not connectable
Model 71, 80, 100,
125, 140
No need pipe
Connect with pipe 2
Connect with pipe 10
No need pipe
No need pipe
Connect with pipe 2
Connect with pipe 10
No need pipe
No need pipe
No need pipe
Connect with pipe 10
Connect with pipe 9
No need pipe
No need pipe
Connect with pipe 10
Connect with pipe 9
No need pipe
No need pipe
Connect with pipe 10
Connect with pipe 9
Model 450, 500,
550, 600, 650
Not connectable
Not connectable
Not connectable
Not connectable
No need pipe
Connect with pipe 8
10
Model
200
No need pipe
No need pipe
No need pipe
Connect with pipe 11
No need pipe
Connect with pipe 11
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Model
200
No need pipe
No need pipe
Connect with pipe 10
Connect with pipe 11
No need pipe
No need pipe
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Model
700, 750, 800
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Model
250
No need pipe
Connect with pipe 12
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Model
250
No need pipe
Connect with pipe 12
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
Not connectable
4 Mounting of cover (insulation material)
(i) CMY-Y104-G
Field pipings
4 Pipe cover 1
(1) Insert the 23 headers into the pipe cover 1 (2
pcs.) respectively, peel off the paper pasted on
the inner surface of the 4 pipe cover, and catch
the 23 headers with the 4 pipe cover 1.
23 Headers
Peel off
Plug (stopping)
(ii)CMY-Y108-G
CMY-Y1010-G
Field pipings
(1) Wind sealing material onto A-section of 23 headers, [thin
Note) For a part where sealing material is overlapped, wind sealing
Sealing material
23 Headers
Peel off
4 Pipe cover
Contact here
Sealing material
Cross section A/A
piping-small sealing material, thick piping-large sealing material], insert each header into 4 pipe cover 1, and put 23
headers between 4 pipe cover 1.
material onto the header so that the overlapped part locates
at the upper side when the 10 branch header is installed.
Upper side
4 Pipe cover 1
6 Band
6 Band
(2) Fasten both ends of the indoor side
branching of the 4 pipe cover 1 with the
6 band as shown in the figure above.
Cut off the surplus of the band.
In case of the 10 branch header
4 Pipe cover 1
Tape
(field supply)
Tape (field supply)
4 Pipe cover 1
5 Pipe cover 2
(3) Mount the 5 pipe cover 2 onto the positions stopped with the
plugs 1 ~ 5 provided.
Fully seal the butting section of the pipe cover with a tape (field
supply). (Insufficient sealing causes condensation dripping.)
WT04325X01