Mitsubishi CMY-Y104-G, CMY-Y108-G, CMY-Y1010-G Installation Manual

For use with R410A-compatible units
Table-1 Accesorry pipes
Pipe 1 Pipe 2 Pipe 3 Pipe 4 Pipe 5 Pipe 6 Pipe 7 Pipe 8 Pipe 9 Pipe 10 Pipe 11 Pipe 12
F (Connecting
Pipe Size)
ø9.52
ø15.88
ø12.7 ø6.35 ø12.7
ø19.05
ø22.2 ø28.58 ø15.88
ø9.52 ø19.05
ø22.2
Pipe Connection Specification
Quantity
G (Outer
Diameter)
ø12.7 ø19.05 ø19.05
ø9.52 ø15.88
ø25.4
ø25.4
ø25.4
ø12.7
ø6.35 ø15.88 ø19.05
CMY-Y104-G
1 1
3 3
– – – – – – –
CMY-Y108-G
1 1 1 6 5 1 1 1
– –
2 1
CMY-Y1010-G
1 2 2 5 6 1 1 1 3 5 1 1
Table-2 Accesorry plugs
Plug 1 Plug 2 Plug 3 Plug 4 Plug 5
H (Connecting Pipe Size)
ø6.35 ø9.52
ø12.7 ø15.88 ø19.05
Pipe Connection Specification
Quantity
CMY-Y104-G
1 1 1 1
CMY-Y108-G
2 2 2 2 1
CMY-Y1010-G
2 2 2 2 1
Table-4
Model
Condition
Model
200
Connectable indoor unit Connectable indoor unit capacity Total indoor unit capacity
1~13
Model
20~250
100~260
Model
250
1~16
Model
20~250
125~325
Model
300
1~16
Model
20~250
150~390
Model
350
1~20
Model
20~250
175~455
Model
400
1~22
Model
20~250
200~520
Model
450
1~24
Model
20~250
225~585
Model
500
1~24
Model
20~250
250~650
Model
550
1~24
Model
20~250
275~715
Model
600
1~32
Model
20~250
300~780
Model
650
1~32
Model
20~250
325~845
Model
700
1~34
Model
20~250
350~910
Model
750
1~34
Model
20~250
375~910
Model
800
1~34
Model
20~250
400~1040
HEADER FOR 4 BRANCHING (CMY-Y104-G) HEADER FOR 8 BRANCHING (CMY-Y108-G) HEADER FOR 10 BRANCHING (CMY-Y1010-G)
1 The following parts are contained in this box. Please identify the quantity with types.
Header for 4 branching (CMY-Y104-G)
1 Instruction 2 Header 3 Header
For liquid line
This sheet 1 sheet
For gas line
1 pc.
Header for 8 branching (CMY-Y108-G)
1 Instruction 2 Header 3 Header
For liquid line
For gas line
4 Pipe cover - 1
1pc.
4 Pipe cover - 1
5 Pipe cover - 2 6 Band
2 pcs. 2 pcs. 4 pcs.
5 Pipe cover - 2 6 Band
INSTALLATION MANUAL
Usable for 3/4 branching (* For 2 branching, use the optional header
for 2 branching.)
7
Sealing material
Usable for 5/6/7/8 branching
OPTIONAL PARTS
ODøG
IDøF
ODøG
IDøF
Pipe 1 – 7 Pipe 8 – 12
Caution
The incorrect selection of the type of branch pipe and the size of connecting pipe does not allow the air conditioner to provide the rated capacity. Please read this instruction manual carefully for correct mounting work.
This sheet 1 sheet
1 pc.
1pc.
Each 2 pcs. 4 pcs. 6 pcs.
Each 1 pc.
Plug 1 – 3 Plug 4·5
Header for 10 branching (CMY-Y1010-G)
1 Instruction 2 Header 3 Header
For liquid line
This sheet 1 sheet
For gas line
1 pc.
4 Pipe cover - 1
1pc. Each 2 pcs.
5 Pipe cover - 2 6 Band
4 pcs. 6 pcs.
7
Sealing material
Each 1 pc.
Usable for 9/10 branching
Note 1) Please prepare the following materials in addition to the items above. (1) Tape for sealing of insulation material (2) Extension pipe for refrigerant circuit. 2 Please observe the items below for the mounting work.
Table-3
Length
Height
difference
Item Pipe section
Total piping length
Farthest piping length (L)
Farthest piping length after 1st branching (R) Height difference between indoor and outdoor units (H) Height difference between indoor units (h)
A + B + C + D + a + b + c + d + e + f + g
A + C + D + g
or A + B + d
C + D + g
or B + d
Allowable value
300 m or less
150 m or less
40 m or less
50 m or less
15 m or less
1. Observe the limit on refrigerant piping length in Table-3.
2. Observe the limit on the connection of indoor units in Table-4.
3. Connect the header to piping or plug/pipe by brazing. Non-oxidized brazing should be applied.
4. The header is equipped with stopper. Push in the
Limitation on refrigerant piping length
Outdoor unit
stopper until the pipe to be connected stops.
5. No limitation is applied to the mounting posture.
6. Be careful that foreign materials like dust will not enter into the piping at the connection work.
1st branch (Branch joint)
Indoor unit
Indoor unit
Branch header
Indoor unit
Indoor unit
7. Apply insulation material to all refrigerant pipings.
8. The piping after the header branching can not be branched again.
Farthest piping length after 1st branching R= 30m or less
Farthest piping length L = 100m or less
Be sure to connect it to the indoor unit.
Branch joint
H is 50 m or less (When outdoor unit is installed above)
H is 40 m or less (When outdoor unit is installed below)
Indoor unit
Indoor unit
Indoor unit
difference h = 15m or less
Indoor - outdoor units height
Fig. 1 Note : Branch piping can not be applied after header branching.
Note: When the number of connecting pipes is less
than the number of header branches, insert a plug of the appropriate size into each branch that does not have piping connected to it.
Limitation on indoor unit connection
Outdoor unit
Indoor unit
ODøH
Model 200
ODøH
Example 1
Total indoor unit capacity 25 × 3 + 32 × 2 + 50 + 63 = 252
Fig. 2
Outdoor unit
Indoor unit
Model 250
Example 2
Total capacity of indoor units 25 × 2 + 32 + 40 + 50 + 63 + 80 = 315
3 Selection of refrigerant piping size and use of header
1. Prepare the pipe to be connected in the field.
2. Determine the piping sizes of each part from Table-5, 6 and 7.
3. The header can be connected to all piping sizes selected in the item
2. To match a specified piping size. (1) use the joint as it is. (2) use it by connecting the auxiliary pipe. Please conduct actual work by referring Fig 3 and Table-5 ~ 12.
4. Cover the branch pipe end of the header, which are not in use, with the plugs 1 ~ 5 provided.
Outdoor unit model Liquid pipe Gas pipe
Model 200 Model 250 Model 300 Model 350 Model 400 Model 450 Model 500 Model 550 Model 600 Model 650 Model 700 Model 750 Model 800
Model 800 over
*1 ø12.7 for over 90m *2 ø12.7 for over 40m
ø9.52 ø9.52 *1 ø9.52 *2
ø12.7
ø12.7
ø15.88 ø15.88 ø15.88 ø15.88 ø15.88 ø19.05 ø19.05 ø19.05 ø19.05
Table-6 Piping size between branching (Fig.1-B·C·D)
Total capacity of indoor units
~140 141~200 201~300 301~400 401~650 651~800
801~
Note: If Indoor unit capacity is 651 or more, it can’t connect to
Fig.1-B directly. Then use the 2-branch joints. (Fig.1-C·D)
Liquid pipe Gas pipe
ø9.52 ø9.52 ø9.52
ø12.7 ø15.88 ø19.05 ø19.05
ø15.88 ø19.05
ø22.2 ø28.58 ø28.58 ø34.93 ø41.28
Table-7 Piping size branching (Fig.1-a~g)
Indoor unit model Liquid pipe Gas pipe
20, 25, 32, 40, 50
63, 71, 80, 100, 125, 140
Note: If indoor unit model is 200 and 250, it can’t use the CMY-
200 250
Y104, Y108 and Y1010-G. Then use the 2-branch joints.
ø6.35 ø9.52 ø9.52 ø9.52
ø12.7 ø15.88 ø19.05
ø22.2
ø19.05
ø22.2
ø22.2 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø34.93 ø34.93 ø34.93 ø41.28
Table-9 Between branching (Fig.1-B)
Pipe types
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Down stream
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
Table-10 4-branch header (CMY-Y104-G) (Fig.1-a~d)
Section
Liquid pipe
1
Gas pipe
Liquid pipe
2
Gas pipe
Liquid pipe
3
Gas pipe
Liquid pipe
4
Gas pipe
Between branchings
capacity
Indoor unit
Outdoor unit
Joint
2-branch joints are
sold separately.
Connecting
Pipe Size (X)
ø12.7
ø19.05
ø12.7
ø 25.4
ø15.88
ø25.4
Connecting
Pipe Size
ø9.52
ø15.88
ø6.35
ø12.7
ø9.52
ø15.88
ø9.52
ø15.88
Model
140
Connect with
pipe 1
Connect with
pipe 2
Connect with
pipe 1
Connect with
pipe 2, 6
Not
connectable
Not
connectable
Model 20, 25,
32, 40, 50
Connect with
pipe 4
Connect with
pipe 5
No need pipe
No need pipe
Connect with
pipe 4
Connect with
pipe 5
Connect with
pipe 4
Connect with
pipe 5
Between First branching and outdoor unit
X
Model
141~200
Connect with
pipe 1
No need pipe
Connect with
pipe 1
Connect with
pipe 6
Connect with
pipe 1, 5
Connect with
pipe 6
Model 71, 80, 100, 125, 400
No need pipe
No need pipe
Not
connectable
Not
connectable
No need pipe
No need pipe
No need pipe
No need pipe
Model
201~300
Not
connectable
Not
connectable
Connect with
pipe 1
Connect with
pipe 7
Connect with
pipe 1, 5
Connect with
pipe 7
Model
200 Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Model
301~400
Not
connectable
Not
connectable
No need pipe
No need pipe
Connect with
pipe 5
Connect with
pipe 8
Model
250 Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Table-8 Between First branching and outdoor unit (Fig.1-A)
Pipe types
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Note: Pipes on 450-type unit and up cannot be branched using a header (4~10-branch header); use an optional 2-branch
Outdoor unit
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
joint.
Header
2
1
3
Connecting
Pipe Size (X)
ø12.7
ø19.05
ø12.7
ø 25.4
ø15.88
ø25.4
4
Model 200
Connect with pipe 1
No need pipe Connect with pipe 1 Connect with pipe 6
Connect with pipe 1, 5
Connect with pipe 6
5
Model 250, 300
Not connectable
Not connectable Connect with pipe 1 Connect with pipe 7
Connect with pipe 1, 5
Connect with pipe 7
6
7
Model 350
Not connectable Not connectable
No need pipe Connect with pipe 8 Connect with pipe 5 Connect with pipe 8
8
Table-11 8-branch header (CMY-Y108-G) (Fig.1-a~d)
Fig. 3
Model
401~650
Not
connectable
Not
connectable
Not
connectable
Not
connectable
No need pipe
Connect with
pipe 8
Model
651~800
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Model
801 or more
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Not
connectable
Section
Indoor unit
Liquid pipe
1
Gas pipe Liquid pipe
2
Gas pipe Liquid pipe
3
Gas pipe Liquid pipe
4
Gas pipe Liquid pipe
5
Gas pipe Liquid pipe
6
Gas pipe Liquid pipe
7
Gas pipe Liquid pipe
8
Gas pipe
Connecting
Pipe Size
ø9.52
ø19.05
ø9.52
ø15.88
ø9.52
ø15.88
ø9.52
ø15.88
ø9.52
ø15.88
ø6.35 ø12.7 ø9.52
ø15.88
ø6.35 ø12.7
Table-12 10-branch header (CMY-Y1010-G) (Fig.1-a~d)
Section
Indoor unit
Liquid pipe
1
Gas pipe Liquid pipe
2
Gas pipe Liquid pipe
3
Gas pipe Liquid pipe
4
Gas pipe Liquid pipe
5
Gas pipe Liquid pipe
6
Gas pipe Liquid pipe
7
Gas pipe Liquid pipe
8
Gas pipe Liquid pipe
9
Gas pipe
10
Liquid pipe Gas pipe
Connecting
Pipe Size
ø9.52
ø19.05
ø6.35
ø15.88
ø9.52
ø19.05
ø6.35
ø15.88
ø9.52
ø15.88
ø6.35 ø12.7 ø9.52
ø15.88
ø6.35 ø12.7 ø9.52
ø15.88
ø6.35 ø12.7
Model 20, 25, 32,
40, 50 Connect with pipe 4 Connect with pipe 3 Connect with pipe 4 Connect with pipe 5 Connect with pipe 4 Connect with pipe 5 Connect with pipe 4 Connect with pipe 5 Connect with pipe 4 Connect with pipe 5
No need pipe
No need pipe Connect with pipe 4 Connect with pipe 5
No need pipe
No need pipe
Model 20, 25, 32,
40, 50 Connect with pipe 4 Connect with pipe 3
No need pipe Connect with pipe 5 Connect with pipe 4 Connect with pipe 3
No need pipe Connect with pipe 5 Connect with pipe 4 Connect with pipe 5
No need pipe
No need pipe Connect with pipe 4 Connect with pipe 5
No need pipe
No need pipe Connect with pipe 4 Connect with pipe 5
No need pipe
No need pipe
Model 400
Not connectable Not connectable
No need pipe Connect with pipe 8 Connect with pipe 5 Connect with pipe 8
9
Model 71, 80, 100,
125, 140
No need pipe
Connect with pipe 2
No need pipe No need pipe No need pipe No need pipe No need pipe No need pipe No need pipe
No need pipe Not connectable Not connectable
No need pipe
No need pipe Not connectable Not connectable
Model 71, 80, 100,
125, 140
No need pipe
Connect with pipe 2 Connect with pipe 10
No need pipe
No need pipe
Connect with pipe 2 Connect with pipe 10
No need pipe
No need pipe
No need pipe
Connect with pipe 10 Connect with pipe 9
No need pipe
No need pipe
Connect with pipe 10 Connect with pipe 9
No need pipe
No need pipe
Connect with pipe 10 Connect with pipe 9
Model 450, 500,
550, 600, 650 Not connectable Not connectable Not connectable Not connectable
No need pipe
Connect with pipe 8
10
Model
200 No need pipe No need pipe No need pipe
Connect with pipe 11
No need pipe
Connect with pipe 11
Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable
Model
200 No need pipe No need pipe
Connect with pipe 10 Connect with pipe 11
No need pipe No need pipe
Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable
Model
700, 750, 800 Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable
Model
250
No need pipe
Connect with pipe 12
Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable
Model
250
No need pipe
Connect with pipe 12
Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable Not connectable
4 Mounting of cover (insulation material)
(i) CMY-Y104-G
Field pipings
4 Pipe cover 1
(1) Insert the 23 headers into the pipe cover 1 (2
pcs.) respectively, peel off the paper pasted on the inner surface of the 4 pipe cover, and catch the 23 headers with the 4 pipe cover 1.
23 Headers
Peel off
Plug (stopping)
(ii)CMY-Y108-G
CMY-Y1010-G
Field pipings
(1) Wind sealing material onto A-section of 23 headers, [thin
Note) For a part where sealing material is overlapped, wind sealing
Sealing material
23 Headers
Peel off
4 Pipe cover
Contact here
Sealing material
Cross section A/A
piping-small sealing material, thick piping-large sealing mate­rial], insert each header into 4 pipe cover 1, and put 23 headers between 4 pipe cover 1.
material onto the header so that the overlapped part locates at the upper side when the 10 branch header is installed.
Upper side
4 Pipe cover 1
6 Band
6 Band
(2) Fasten both ends of the indoor side
branching of the 4 pipe cover 1 with the 6 band as shown in the figure above. Cut off the surplus of the band.
In case of the 10 branch header
4 Pipe cover 1
Tape
(field supply)
Tape (field supply)
4 Pipe cover 1
5 Pipe cover 2
(3) Mount the 5 pipe cover 2 onto the positions stopped with the
plugs 1 ~ 5 provided. Fully seal the butting section of the pipe cover with a tape (field supply). (Insufficient sealing causes condensation dripping.)
WT04325X01