Mitsubishi CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-Y302-G2 Installation Manual

For use with R410A-compatible units
Table-2
Model
Condition
Model
200
Connectable indoor unit Connectable indoor unit Capacity Total indoor unit capacity
1~13
Model
20~250
100~260
Model
250
1~16
Model
20~250
125~325
Model
300
1~16
Model
20~250
150~390
Model
350
1~20
Model
20~250
175~455
Model
400
1~22
Model
20~250
200~520
Model
450
1~24
Model
20~250
225~585
Model
500
1~24
Model
20~250
250~650
Model
550
1~24
Model
20~250
275~715
Model
600
1~32
Model
20~250
300~780
Model
650
1~32
Model
20~250
325~845
Model
700
1~34
Model
20~250
350~910
Model
750
1~34
Model
20~250
375~910
Model
800
1~34
Model
20~250
400~1040
2-BRANCH JOINT PIPE
(CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-Y302-G2)
1The following parts are contained in this box. Please identify the quantity with types.
Part name
Shape
1. Instruction
2. 2-branch joint (small)
3. 2-branch joint (large)
For liquid line For gas line
4. Cover 1 5. Cover 2
For liquid line
For gas line
6. Pipe 1
INSTALLATION MANUAL
7. Pipe 2
8. Pipe 3
9. Pipe 4
OPTIONAL PARTS
10. Pipe 5
11. Pipe 6
12. Pipe 7
Caution
The incorrect selection of the type of branch pipe and the size of connecting pipe does not allow the air conditioner to provide the rated capacity. Please read this instruction manual carefully for correct mounting work.
13. Pipe 8
This sheet 1 sheet
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2 CMY-Y302-G2
Part name
1 1 1 1
14. Pipe 9
1 1 1 1
15. Pipe 10
1 1 1 1
16. Pipe 11
Shape
OD19.05-ID25.4
-
-
1
-
CMY-Y102S-G2 CMY-Y102L-G2 CMY-Y202-G2
CMY-Y302-G2
OD12.7-ID6.35
-
-
1
-
OD25.4-ID28.58
­2 3 1
2Please observe the items below for the mounting work.
1. Observe the restrictions on refrigerant
Limitation on Refrigerant Piping Length
piping length in Table-1.
2. Observe the restrictions regarding the connection of indoor units in Table-2.
3. Braze the pipes under nitrogen purge. The 2-branch joint is equipped with a stopper.
4.
Outdoor Unit
Push in the pipes into the branch joint until they stop.
5. Be careful that foreign materials like dust do not enter into the piping when connecting pipes.
6. Apply insulation material to all refrigerant pipings.
7. When attaching the branch joint to the gas side of the CMY-Y202-G2, CMY-Y302-G2 make sure that it is either horizontal or vertical as shown in the illustrations below. There are no restrictions on the installation of other joints.
When horizontal When vertical
±15°
(Should not face downward.)
±15°
H’ is 40 m or less (When outdoor unit is installed below)
H is 50 m or less (When outdoor unit is installed above)
Fig.1
1 1 1 1
17. Pipe 12
OD15.88-ID9.52
-
­1 1
A
1st Branch
(Branch Joint)
Branch Joint
OD15.88-ID12.7
OD25.4-ID19.05
1 1 1 1
18. Pipe 13
OD15.88-ID6.35
-
-
-
1
OD9.52-ID6.35
2 1
-
-
19. Pipe 14
OD31.75-ID28.58
-
-
-
1
(In the case of PUHY)
Table-1
Items
Total pipe length
Farthest pipe length (L)
Length
Farthest pipe length after the first branch (r) Between outdoor and indoor units
Height
Height difference
difference
between indoor units (h)
B
a
Indoor
Unit
C
Farthest pipe length after the first branch: R is 40 m or less
Farthest pipe length: L is 150 m or less
b
Indoor
Unit
D
e
Indoor
Unit
Note: No further branching allowed after the header branch
f
Indoor
Unit
OD19.05-ID12.7
1
­1 1
20. Pipe 17
1 1 1 1
21. Pipe 19
OD25.4-ID15.88
-
2
-
1
-
1
-
1
Pipe Section Allowable Length
A + B + C + D + a + b +
c + d + e + f + g
A + B + D + g
or A + B + d
C + D + g
or B + d Outdoor unit above (H) Outdoor unit below (H’)
Branch Header
d
c
Indoor
Unit
Indoor
Unit
g
Indoor
Unit
Height difference between
indoor units h must be 15 m or less.
OD19.05-ID15.88
22. Pipe 20
OD31.75-ID34.93
300 m or less
150 m or less
40 m or less
50 m or less 40 m or less
15 m or less
2 1 1 1
OD31.75-ID41.28
-
-
-
2
Limitation on indoor unit connection
<Example: PUHY>
Fig.2
OD12.7-ID9.52
­2 1
-
23. Pipe 21
-
-
-
2
Example 1
Example 2
OD19.05-ID22.2
­1 1
-
Outdoor unit
Model 200
Indoor unit
Outdoor unit
Indoor unit
OD25.4-ID22.2
­2 1 1
OD25.4-ID12.7
-
-
-
1
Total indoor unit capacity 25 + 32 × 2 + 40 + 50 + 63 = 242
Total capacity of indoor units 25 × 2 + 32 + 40 + 50 + 63 + 80 = 315
3Selection of refrigerant piping size and use of 2-branch joint.
1. Prepare the pipe to be connected in the field.
2. Determine the piping sizes of each part from Table-3,4 and 5.
3. The 2-branch joint can be connected to all piping sizes selected in the item 2. to match a specified piping size.
(1) use the joint as standard. (no auxiliary pipe is necessary. Direct connection
available)
(2) use it by connecting the auxiliary pipe.
Please conduct actual work by referring Fig.3, and Table-6~12.
4. When pipe is cut with a pipe cutter or the like, remove burr, dust and foreign materials inside the pipe, and connect the pipe.
Table-3 Piping size between outdoor unit and 1st branching (Fig. 1-A)*
Outdoor unit model Liquid pipe Gas pipe
Model 200 Model 250 Model 300 Model 350 Model 400 Model 450 Model 500 Model 550 Model 600 Model 650 Model 700 Model 750 Model 800
Model 800 over
* As the values for some models differ from those in the above table, refer to
the Installation Manual for the outdoor unit. *1 ø12.7 for over 90m *2 ø12.7 for over 40m
ø9.52 ø9.52 *1 ø9.52 *2
ø12.7
ø12.7
ø15.88 ø15.88 ø15.88 ø15.88 ø15.88 ø19.05 ø19.05 ø19.05 ø19.05
ø19.05
ø22.2
ø22.2 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø28.58 ø34.93 ø34.93 ø34.93 ø41.28
Table-4 Piping size between branching (Fig. 1-B·C·D)
Total capacity of indoor units
~140 141~200 201~300 301~400 401~650 651~800
801~
Liquid pipe Gas pipe
ø9.52 ø9.52 ø9.52
ø12.7 ø15.88 ø19.05 ø19.05
ø15.88 ø19.05
ø22.2 ø28.58 ø28.58 ø34.93 ø41.28
Table-5 Piping size branching (Fig. 1-a~g)
Indoor unit model Liquid pipe Gas pipe
20, 25, 32, 40, 50
63, 71, 80, 100, 125, 140
200 250
ø6.35 ø9.52 ø9.52 ø9.52
ø12.7
ø15.88 ø19.05
ø22.2
Table-7 Between outdoor unit and 1st branching (Fig.1-A)
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
*1 If the pipe is over 90m for Model 250, it is not necessary to change the pipe. *1 If the pipe is over 40m for Model 300, it is not necessary to change the pipe.
Table-6 Between branching (Fig.1-C)
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
Outdoor unit
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
Down stream
capacity
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
Model
200 ø9.52/ø19.05 no need pipe no need pipe
-
-
-
-
-
-
~140
ø9.52/ø15.88
no need pipe
pipe 4
-
-
-
-
-
-
Model
250,300
ø9.52/ø22.2
-
-
pipe 5 *1
pipe 7
-
-
-
-
Table-12
Dimension
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
141~200
ø9.52/ø19.05
no need pipe no need pipe
Pipe Pipe
201~300
ø9.52/ø22.2
-
-
-
-
-
-
-
­pipe 5 pipe 7
-
-
-
-
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
301~400
ø12.7/ø28.58
-
-
no need pipe
pipe 10
-
-
-
-
2-Branch joint Pipe
A
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
401~650
ø15.88/ø28.58
-
-
-
-
no need pipe
pipe 10
-
-
Pipe
B
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
651~800
ø19.05/ø34.93
-
-
-
-
-
-
no need pipe
pipe 20
Fig.3
Model
350,400
ø12.7/ø28.58
no need pipe
pipe 10
-
-
-
-
-
-
Model
450~500
ø15.88/ø28.58
-
-
-
-
no need pipe
pipe 10
-
-
Model
550~650
ø15.88/ø28.58
-
-
-
-
no need pipe
pipe 10
-
-
Model
700~800
ø19.05/ø34.93
-
-
-
-
-
-
no need pipe
pipe 20
Model
800 over
ø19.05/ø41.28
-
-
-
-
-
-
no need pipe
pipe 21
C
ø9.52
ø15.88
ø9.52
ø19.05
ø12.7 ø19.05 ø15.88
ø25.4
801~
ø19.05/ø41.28
-
-
-
-
-
-
no need pipe
pipe 21
Table-8 Between branching (Fig.1-C)
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Down stream
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
capacity
ø9.52
ø15.88
ø9.52
ø19.05
ø12.7 ø19.05 ø15.88
ø25.4
~140
ø9.52/ø15.88
no need pipe no need pipe no need pipe
pipe 4 pipe 5 pipe 4
pipe 12
pipe19
141~200
ø9.52/ø19.05
-
­no need pipe no need pipe
pipe 5
no need pipe
pipe 12 pipe 17
201~300
ø9.52/ø22.2
-
-
no need pipe
pipe 6 pipe 5 pipe 6
pipe 12
pipe 7
301~400
ø12.7/ø28.58
no need pipe pipe 11, 10
pipe 10
Table-9 Between branching and indoor unit (Fig.1-e·f)
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
Indoor unit
ø9.52
ø15.88
ø9.52
ø19.05
ø 12.7 ø19.05 ø15.88
ø25.4
Model 20~50
ø6.35/ø12.7
pipe 1 pipe 2 pipe 1 pipe 3 pipe 9 pipe 3
pipe 13
pipe 8
Model
63~140
ø9.52/ø15.88
no need pipe no need pipe no need pipe
pipe 4 pipe 5
pipe 4 pipe 12 pipe 19
Model
200
ø9.52/ø19.05
-
­no need pipe no need pipe
pipe 5
no need pipe
pipe 12 pipe 17
ø9.52/ø22.2
no need pipe
pipe 12
Table-10 Between branching (Fig.1-D)
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Down stream
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
capacity
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
~140 ø9.52/ø15.88 no need pipe
pipe 4 pipe 5
pipe 19
-
-
-
-
141~200 ø9.52/ø19.05 no need pipe no need pipe
pipe 5
pipe 17
-
-
-
-
201~300
ø9.52/ø22.2
-
­pipe 5 pipe 7
pipe 12
pipe 7
-
-
301~400
ø12.7/ø28.58
no need pipe
pipe 10
pipe 10
pipe 14
Table-11 Between branching and indoor unit (Fig.1-g)
Indoor unit
Pipe types
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Note 1: The diameter of the pipes after the first branch does not need to be greater
than that of the main pipe.
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
ø9.52
ø19.05
ø12.7 ø25.4
ø15.88
ø25.4 ø19.05 ø31.75
Model 20~50
ø6.35/ø12.7
pipe 1 pipe 3
-
-
-
-
-
-
Model
63~140 ø9.52/ø15.88 no need pipe
pipe 4 pipe 5
pipe 19
-
-
-
-
Model
200
ø9.52/ø19.05
no need pipe no need pipe
pipe 5
pipe 17
-
-
-
-
ø9.52/ø22.2
pipe 12
-
-
-
-
pipe 2
Model
250
-
-
pipe 6 pipe 5 pipe 6
pipe 7
-
-
pipe 2
pipe 3
Model
250
-
­pipe 5 pipe 7
pipe 7
-
-
401~650
ø15.88/ø28.58
-
-
-
-
-
-
no need pipe
pipe 10
401~650
ø15.88/ø28.58
-
-
-
-
no need pipe
pipe 10
pipe 4
pipe 14
651~800
ø19.05/ø34.93
-
-
-
-
-
-
-
-
651~800
ø19.05/ø34.93
-
-
-
-
-
-
no need pipe
pipe 20
801~
ø19.05/ø41.28
-
-
-
-
-
-
-
-
801~
ø19.05/ø41.28
-
-
-
-
-
-
no need pipe
pipe 21
4Installing the cover (insulation material)
Fig.4 (Example for liquid line)
• Install the pipe cover 4 along the liquid pipe 2.
• Apply the same procedures to the gas pipe 3 also.
Seal the joint section of pipe cover 4 with insulated sealing tape (field supply). (Refer to Fig.4.)
Liquid pipe 2
Pipe cover 4
Tape (field supply)
Insulation material (field supply)
Fig.5
Pipe cover 4
Lapped space of taping
Insulation material (field supply)
Note 1. Apply insulation to all refrigerant piping (field
supply). When using a commercially avail­able insulation material, make sure to use the heat-resistant insulation material (heat resistant 120 °C minimum).
Note 2. The insulation cover shrinks slightly, so wrap
the pipe cover 4 and the field-installed insulation material securely with tape by overlapping the tape as shown in Fig. 5.
Tape (field supply)
WT05132X01
Loading...