Mitsubishi CMY-R100XLVBK, CMY-R200XLVBK Installation Manual

When installing or relocating the unit, check that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
¡Any presence of foreign substance or air can cause abnormal
pressure rise or explosion.
¡For your safety, thoroughly read the following instructions prior to installation.
Safety Precautions
Mitsubishi Electric Air Conditioner CITY MULTI Twinning Kit Installation Manual
WARNING
CAUTION
WARNING
Incorrect handling can result in death or serious injury.
Incorrect handling can result in bodily injury and/or structure damage.
See the Installation Manual that came with the outdoor unit for installation instructions.
CAUTION
Only a dealer or qualified technician should perform installation.
¡Improper installation may result in refrigerant gas leakage
and equipment damage.
Do not make any modifications or alterations. Consult your dealer for repair.
¡Improper installation may result in water leakage, electric shock,
or fire.
In the event of a refrigerant leak, thoroughly ventilate the room.
¡If refrigerant leaks and comes in contact with an open flame,
toxic gases will be generated.
Properly install all parts according to the instructions in the Installation Manual.
¡If the wrong twinning pipe or wrong size connecting pipe is
used, air conditioning performance will suffer.
After installation, check for a refrigerant leak.
¡If leaked refrigerant comes in contact with a heat source,
such as a fan heater, stove, or electric grill, toxic gases will be generated.
Properly dispose of packing materials.
¡Plastic bags can pose suffocation and choking hazards: keep
them out of the reach of children. Tear the plastics bags before disposing of them.
Do not touch the refrigerant pipes and refrigerant circuit components with bare hands during and immediately after operation.
¡During or immediately after operation, certain parts of the unit
such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frostbites and burns, do not touch these parts with bare hands.
1
CMY-R100XLVBK CMY-R200XLVBK
WT05989X01
1. Confirming the Package Contents
The following items are included with the Twinning Kit (CMY-R100XLVBK, CMY-R200XLVBK). Verify that all items are present before starting installation. Always use the twinning pipes included in the kit when preparing the twinning kit.
If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.
(1) Package contents
Model
CMY-R100XLVBK 1 1 1 1 1 1 1 1
1
Low-pressure twinning kit
2
High-pressure twinning pipe
3
Fixing screw
5
Elbow pipe
Ø28.58 [1-1/8]
6
Elbow pipe
Ø31.75 [1-1/4]
7
High-pressure pipe
(for routing through
the bottom)
8
High-pressure pipe
(for routing through
the front)
9Pipe cover
Model
CMY-R100XLVBK 3 1 1 111
0
OD31.75 [1-1/4]
-ID28.58 [1-1/8]
A
OD22.2 [7/8]
-ID19.05 [3/4]
B
OD19.05 [3/4]
-ID22.2 [7/8]
C
OD22.2 [7/8]
-ID28.58 [1-1/8]
D
OD28.58 [1-1/8]
-ID22.2 [7/8]
E
OD31.75[1-1/4]
-ID34.93 [1-3/8]
H
OD34.93[1-3/8]
-ID41.28 [1-5/8]
11
CMY-R200XLVBK 3 - - 1-1
11
F
Installation Manual
(this booklet)
G
Insulation cover
-
1
2
CMY-R200XLVBK 1 1 1 1 1 1 1 1
2
4Cable tie
(2) List of field-supplied parts
· Refrigerant pipes other than the ones provided in the kit
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape
Package unit name
Outdoor Twinning Kit
Component unit name
Outdoor unit 1
Outdoor unit 2
BC controller ~ Twinning pipe
High-pressure
Low-pressureAB
A0
B0
C0
D0
E0
F0
PURY-**Y(S)JMU
PURY-**T(S)JMU
PURY-**Y(S)JM
A0
P216
P240
P264
P288
EP600
EP650
EP700
P800
P850
P900
B0
P120
P120
P144
P144
EP350
EP350
EP350
P450
P450
P450
C0
P96
P120
P120
P144
EP250
EP300
EP350
P350
P400
P450
D0
CMY-R100XLVBK
CMY-R100XLVBK
CMY-R200XLVBK
F0
Twinning pipe ~ Outdoor unit
Low-pressure
E or F
A3
B3
C3
PURY-**YJMU
PURY-**TJMU
PURY-**YJM
A1
A2
A3
P96
Ø19.05
Ø22.2
(*)
EP250
Ø19.05
Ø22.2
(*)
P350
Ø19.05
Ø28.58
B1
B2
B3
P120
Ø19.05
Ø28.58
EP300
Ø19.05
Ø22.2
(*)
P400
Ø22.2
(*)
Ø28.58
C1
C2
C3
P144
Ø22.2
(*)
Ø28.58
EP350
Ø19.05
Ø28.58
P450
Ø22.2
(*)
Ø28.58
Unit model
A1
B1
C1
High-pressure
C or D
A2
B2
C2
(
Unit : mm [in
] )(
Unit : mm [in
] )
Ø34.93(*
)
[1-3/8]
Ø34.93(*
)
[1-3/8]
Ø41.28
(*)
[1-5/8]
E0
Ø28.58
[1-1/8]
Ø28.58
(*)
[1-1/8]
Ø28.58
(*)
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
[1-1/8]
[3/4]
[7/8]
[3/4]
[7/8]
[3/4]
[1-1/8]
[3/4]
[1-1/8]
[3/4]
[7/8]
[7/8]
[1-1/8]
[7/8]
[1-1/8]
[3/4]
[1-1/8]
[7/8]
[1-1/8]
2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit
(1) Pipe size
1 Field-supply the pipes to be connected to the kit. 2 Choose the correct size pipe using the table
below. Connect the field- supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk (*).
3 If the pipe was cut with a pipe cutter, remove the
burrs and eliminate foreign materials before connecting.
On the low-pressure side, the twinning kit connects
to the field-supplied pipes inside the outdoor unit.
The distributor on the low-pressure side must be
placed in the outdoor unit that has a larger capacity index of the two, regardless of the relative positions of the outdoor units or their addresses.
If the distributor is placed in the outdoor unit that has
a smaller capacity, refrigerant will not be properly distributed and compressor failure may result.
( If outdoor units that have the same capacity are
used in combination, the distributor can be placed in either outdoor unit.)
D
Twinning pipe(High pressure)
A
To BC controller
C
F
E
Twinning kit (Low pressure)
To BC controller
B
Outdoor unit 1 Outdoor unit 2
2
See reverse.