Mitsubishi CMY-R100VBK, CMY-R200VBK Installation Manual

When installing or relocating the unit, check that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
¡Any presence of foreign substance or air can cause abnormal
pressure rise or explosion.
¡For your safety, thoroughly read the following instructions prior to installation.
Safety Precautions
Mitsubishi Electric Air Conditioner CITY MULTI Twinning Kit Installation Manual
WARNING
CAUTION
WARNING
Incorrect handling can result in death or serious injury. Incorrect handling can result in bodily injury and/or structure damage.
See the Installation Manual that came with the outdoor unit for installation instructions.
CAUTION
Only a dealer or qualified technician should perform installation.
¡Improper installation may result in refrigerant gas leakage
and equipment damage.
Do not make any modifications or alterations. Consult your dealer for repair.
¡Improper installation may result in water leakage, electric shock,
or fire.
In the event of a refrigerant leak, thoroughly ventilate the room.
¡If refrigerant leaks and comes in contact with an open flame,
toxic gases will be generated.
Properly install all parts according to the instructions in the Installation Manual.
¡If the wrong twinning pipe or wrong size connecting pipe is
used, air conditioning performance will suffer.
After installation, check for a refrigerant leak.
¡If leaked refrigerant comes in contact with a heat source,
such as a fan heater, stove, or electric grill, toxic gases will be generated.
Properly dispose of packing materials.
¡Plastic bags can pose suffocation and choking hazards: keep
them out of the reach of children. Tear the plastics bags before disposing of them.
Do not touch the refrigerant pipes and refrigerant circuit components with bare hands during and immediately after operation.
¡During or immediately after operation, certain parts of the unit
such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frostbites and burns, do not touch these parts with bare hands.
1
CMY-R100VBK, CMY-R200VBK
WT05221X02
1. Confirming the Package Contents
The following items are included with the Twinning Kit (CMY-R100VBK, CMY-R200VBK). Verify that all items are present before starting installation. Always use the twinning pipes included in the kit when preparing the twinning kit.
If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.
(1) Package contents
Model
CMY-R100VBK CMY-R200VBK
1 1
1 1
2 1
1
-
1 1
-
1
3 1
3 1
1 1
1
Low-pressure
twinning kit
2
High-pressure
twinning pipe
3
Fixing screw
4
Elbow pipe
Ø22.2 [7/8]
5
Elbow pipe
Ø28.58 [1-1/8]
6
Elbow pipe
Ø31.75 [1-1/4]
7
High-pressure pipe
(for routing through
the bottom)
8
High-pressure pipe
(for routing through
the front)
9
Pipe cover
Model
CMY-R100VBK CMY-R200VBK
­2
1
-
-
1
-
1
1
-
1
-
1
-
1
-
1
-
BCD E
FU-PIPE
ID25.4 [1]
G
U-PIPE
ID19.05 [3/4]
-ID25.4 [1]
HSaddle
2
-
0
1 1
IPacking
1
-
A
1 1
J
Fixing plate
2 2
K
Installation Manual
(this booklet)
L
Insulation cover
MCable tie
OD19.05 [3/4]
-ID15.88 [5/8]
OD22.2 [7/8]
-ID19.05 [3/4]
OD19.05 [3/4]
-ID22.2 [7/8]
OD22.2 [7/8]
-ID28.58 [1-1/8]
OD28.58 [1-1/8]
-ID22.2 [7/8]
OD31.75[1-1/4]
-ID34.93 [1-3/8]
(2) List of field-supplied parts
· Refrigerant pipes other than the ones provided in the kit
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape
Package unit name
Outdoor Twinning Kit
Component unit name
Outdoor unit 1 Outdoor unit 2
BC controller ~ Twinning pipe
High-pressure
Low-pressureAB
A0 B0 C0 D0 E0 F0
PURY-**Y(S)HM
PURY-**Y(S)HMU
PURY-**T(S)HMU
A0 P450 P500 P550 P600 P650 P700 P750 P800
EP400 EP450 EP500 EP550 EP600
P144 P168 P192 P216 P240 P144 P168 P192 P216 P240
B0 P250 P250 P300 P300 P350 P400 P400 P400
EP200
P250
EP300 EP300 EP300
P72 P96
P96 P120 P120
P72
P96
P96 P120 P120
C0 P200 P250 P250 P300 P300 P300 P350 P400
EP200 EP200 EP200
P250
EP300
P72 P72 P96 P96
P120
P72 P72 P96 P96
P120
D0
CMY-R100VBK
CMY-R200VBK
CMY-R100VBK
CMY-R100VBK
CMY-R100VBK
F0
Twinning pipe ~ Outdoor unit
Low-pressure
E or F
A3 B3 C3 D3 E3
PURY-**YHM
PURY-**YHMU
PURY-**THMU
A1 A2 A3
P200
Ø15.88
(*)
Ø19.05(*
)
EP200
Ø15.88
(*)
Ø19.05(*
)
P72
Ø15.88
(*)
Ø19.05(*
)
P72
Ø15.88
(*)
Ø19.05(*
)
B1 B2 B3
P250
Ø19.05
Ø22.2
EP300
Ø19.05
Ø22.2
P96
Ø19.05
Ø22.2
P96
Ø19.05
Ø22.2
C1 C2 C3
P300
Ø19.05
Ø22.2
(
*
A)
-
-
-
P120
Ø19.05
Ø28.58
P120
Ø19.05
Ø28.58
D1 D2 D3
P350
Ø19.05
Ø28.58
-
-
-
-
-
-
-
-
-
E1 E2 E3
P400
Ø22.2
(*)
Ø28.58
-
-
-
-
-
-
-
-
-
-
Unit model
A1 B1 C1 D1 E1
High-pressure
C or D
A2 B2 C2 D2 E2
(
Unit : mm [in
] )
(
Unit : mm [in
] )
*
A : In case of CMY-R200VBK
Ø34.93
(*)
[1-3/8]
E0
Ø22.2
[7/8]
Ø22.2
[7/8]
Ø22.2
[7/8]
Ø22.2
[7/8]
Ø28.58
(*)
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
[1-1/8]
Ø28.58
(*)
[1-1/8]
Ø28.58
(*)
[1-1/8]
Ø28.58
(*)
[1-1/8]
[5/8]
[3/4]
[5/8]
[3/4]
[5/8]
[3/4]
[5/8]
[3/4]
[3/4]
[7/8]
[3/4]
[7/8]
[3/4]
[7/8]
[3/4]
[7/8]
[3/4]
[7/8]
[3/4]
[1-1/8]
[3/4]
[1-1/8]
[3/4]
[1-1/8]
[7/8]
[1-1/8]
2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit
(1) Pipe size
1 Field-supply the pipes to be connected to the kit. 2 Choose the correct size pipe using the table below. Connect the field-
supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk (*).
3 If the pipe was cut with a pipe cutter, remove the burrs and eliminate
foreign materials before connecting.
On the low-pressure side, the twinning kit connects to the field-supplied
pipes inside the outdoor unit.
The distributor on the low-pressure side must be placed in the outdoor unit
that has a larger capacity index of the two, regardless of the relative positions of the outdoor units or their addresses.
If the distributor is placed in the outdoor unit that has a smaller capacity,
refrigerant will not be properly distributed and compressor failure may result.
( If outdoor units that have the same capacity are used in combination, the
distributor can be placed in either outdoor unit.)
Twinning pipe (high pressure)
Twinning Kit (low pressure)
C
E
D
A
B
To BC controller
To BC controller
Outdoor unit 2
Outdoor unit 1
F
2
See reverse.