Mitsubishi CMY-Q100VBK Installation Manual

When installing or relocating the unit, check that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
¡Any presence of foreign substance or air can cause abnormal
pressure rise or explosion.
¡For your safety, thoroughly read the following instructions prior to installation.
Safety Precautions
Mitsubishi Electric Air Conditioner CITY MULTI Twinning Kit Installation Manual
WARNING
CAUTION
WARNING
Incorrect handling can result in death or serious injury.
Incorrect handling can result in bodily injury and/or structure damage.
See the Installation Manual that came with the outdoor unit for installation instructions.
CAUTION
Only a dealer or qualified technician should perform installation.
¡Improper installation may result in refrigerant gas leakage
and equipment damage.
Do not make any modifications or alterations. Consult your dealer for repair.
¡Improper installation may result in water leakage, electric shock,
or fire.
In the event of a refrigerant leak, thoroughly ventilate the room.
¡If refrigerant leaks and comes in contact with an open flame,
toxic gases will be generated.
Properly install all parts according to the instructions in the Installation Manual.
¡If the wrong twinning pipe or wrong size connecting pipe is
used, air conditioning performance will suffer.
After installation, check for a refrigerant leak.
¡If leaked refrigerant comes in contact with a heat source,
such as a fan heater, stove, or electric grill, toxic gases will be generated.
Properly dispose of packing materials.
¡Plastic bags can pose suffocation and choking hazards: keep
them out of the reach of children. Tear the plastics bags before disposing of them.
Do not touch the refrigerant pipes and refrigerant circuit components with bare hands during and immediately after operation.
¡During or immediately after operation, certain parts of the unit
such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frostbites and burns, do not touch these parts with bare hands.
1
CMY-Q100VBK
WT05688X01
Twinning pipe(high pressure)
c
e
d
a
b
To BC controller
To BC controller
Twinning kit(low pressure)
Heat source unit 1 Heat source unit 2
1780
20
880 880
1. Confirming the Package Contents
The following items are included with the Twinning Kit (CMY-Q100VBK). Verify that all items are present before starting installation. Always use the twinning pipes included in the kit when preparing the twinning kit.
If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.
(1) Package contents
Model
CMY-Q100VBK
Model
CMY-Q100VBK
1
1
1
1
1
1
1
1
1
1
1
2
1
1
Low-pressure
twinning kit
2
High-pressure
twinning pipe
3Fixing screw
4Elbow pipe
Ø22.2 [7/8]
5Elbow pipe
Ø28.58 [1-1/8]
6
High-pressure
pipe
7Pipe cover
1
D
ID22.2 [7/8]
-ID25.4 [1]
B
Insulation cover
A
Installation Manual
(this booklet)
0
OD22.2 [7/8]
-ID25.4 [1]
9
OD22.2 [7/8]
-ID19.05 [3/4]
8
OD19.05 [3/4]
-ID15.88 [5/8]
CCable tie
(2) List of field-supplied parts
· Refrigerant pipes other than the ones provided in the kit
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape
CMY-Q100VBK
PQRY-P600YSHM-A PQRY-P300YHM-A PQRY-P300YHM-APQRY-P250YHM-A
PQRY-P250YHM-A
PQRY-P500YSHM-A
Low pressure
Twinning pipe connection size
Heat Source unit 1
Component unit name
Package unit name
BC controller~Twinning pipe
a b
PQRY-P400YSHM-A PQRY-P200YHM-A PQRY-P200YHM-A
High pressure
Low pressure
c d
High pressure
e
High pressure
Twinning pipe Kit(optional parts)
Twinning pipe~Heat Source unit 1 Twinning pipe~Heat Source unit 2 Twinning pipe~Heat Source unit 2
Heat Source unit 2
PQRY-P450YSHM-A PQRY-P250YHM-A PQRY-P200YHM-A
PQRY-P550YSHM-A PQRY-P300YHM-A PQRY-P250YHM-A
Ø28.58
(*)
Ø22.2
Ø28.58 Ø19.05
Ø22.2
Ø19.05
2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit
(1) Pipe size
1 Field-supply the pipes to be connected to the kit. 2 If the pipe was cut with a pipe cutter, remove the
burrs and eliminate foreign materials before connecting.
On the low-pressure side, the twinning kit connects to
the field-supplied pipes inside the heat source unit.
The distributor on the low-pressure side must be
placed in the heat source unit that has a larger capacity index of the two, regardless of the relative positions of the heat source units or their addresses.
If the distributor is placed in the heat source unit that
has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result.
( If heat source units that have the same capacity are
used in combination, the distributor can be placed in either heat source unit.)
Choose the correct size pipe using the above table. Connect the field- supplied pipe to the twinning kit for the sizes in the
table that are marked with an asterisk (*).