Thank you for purchasing the Mitsubishi Motion Controller/A173UHCPU/A172SHCPUN/ A171SHCPUN.
This instruction manual describes the handing and precautions of this unit. Incorrect handing will lead to
unforeseen events, so we ask that you please read this manual thoroughly and use the unit correctly.
Please make sure that this manual is delivered to the final user of the unit and that it is stored for future
reference.
Precautions for Safety
Please read this instruction manual and enclosed doc uments before starting installation, operation, maintenance or inspections t o ensure correct usage. Thoroughly underst and the machine,
safety information and prec aut i ons before starting operation.
The safety precautions are ran ked as "Warning" and "Caution" in th is instruction manual.
WARNING
CAUTION
Note that some items described as cautions may lead to ma jor results depending on the
situation. In any case, import ant information that must be observed is described.
When a dangerous situation may occur if handling is mistaken
leading to fatal or m a j o r injuries.
When a dangerous situation may occur if handling is mistaken
leading to medium or minor injuries, or physical damage.
− I −
For Sate Operations
1. Prevention of electric shocks
Never open the front case or ter minal covers while the power is ON or the unit is running, as
this may lead to electric shocks.
Never run the unit with the front ca se or t erminal cover removed. The high voltage terminal
and charged sections will be exposed and may lead to electric shocks.
Never open the front case or terminal cover at times other than wiring work or per iodic
inspections even if the power is O FF. The insides of the control u nit and servo amplifier are
charged and may lead to electric shocks.
When performing wiring wor k or inspections, turn the power OFF, wait at least ten minutes,
and then check the voltage wit h a t est er, et c. Failing to do so may lead to electric shocks.
Always ground the control unit, servo amplifier and servomotor wit h C la ss 3 grounding. Do
not ground commonly with other devices.
The wiring work and inspections must be done by a qualified technician.
Wire the units after installing the control unit, servo ampli f ier and servomotor. Failing to do
so may lead to electric shocks or damage.
Never operate the switches w it h w et hands, as this may lead to electr ic shocks.
Do not damage, apply excessive stress, place heavy t hings on or sandwich the cables, as
this may lead to electric shocks.
Do not touch the control unit, servo amplifier or servomotor terminal blocks while the power
is ON, as this may lead to electric shocks.
Do not touch the interna l power supply, internal grounding or signal wires of the control unit
and servo amplifier, as this may lead to electric shocks.
WARNING
2. For fire prevention
Install the control unit, serv o amplifier, servomotor and regenerat ive resistor on inflammable
material. Direct installation on flammable material or near flammable mater ia l may lead to
fires.
If a fault occurs in the control unit or serv o amplifier, shut the power OFF at the serv o
amplifier’s power source. If a large current continues to flow, fires may occur.
When using a regenerative resist or, shut t he pow er OFF with an error signal. The regenerative resistor may abnormally ov erheat due to a fault in the regenerative t r ansist or, et c. , and
may lead to fires.
Always take heat measures suc h as f lame proofing for the inside of the control panel where
the servo amplifier or regenerative resistor is installed and for the w ires used. Failing to do
so may lead to fires.
CAUTION
− II −
3. For injury prevention
CAUTION
Do not apply a voltage other than that specified in the instruction manual on any t erminal.
Doing so may lead to destruct ion or damage.
Do not mistake the termina l connections, as this may lea d t o dest r uct i on or damage.
Do not mistake the polarity (+ / -), as this may lead to destruction or damage.
The servo amplifier's heat radiat i ng f ins, regenerative resistor and servo amplifier, etc., will
be hot while the power is ON and for a short time after the power is turned OFF. Do not
touch these parts as doing so may lead t o burns.
Always turn the power OFF before touching the servomotor shaft or coup led machines, as
these parts may lead to injuri es.
Do not go near the machine dur ing t est operations or during operat ions such as teaching.
Doing so may lead to injuries.
4. Various precautions
Strictly observe the following precautions.
Mistaken handling of the unit may lead to faults, injuries or electric shocks.
(1) System structure
CAUTION
Always install a lea ka ge breaker on the control unit and serv o amplifier power source.
If installation of a magnetic co nt act or for power shut off during an error, etc., is specified in
the instruction manual for t he servo amplifier, etc., always inst all the magnetic contactor.
Install an external emergen cy stop circuit so that the operation c an be st opped immediately
and the power shut off.
Use the control unit, servo a mpli fier, servomotor and regenerative resistor w ith t he combi-
nations listed in the instruct ion manual. Other combinat ions may lead to fires or faults.
If safety standards (ex., robot safety rules, etc.,) apply to the syst em using t he control unit,
servo amplifier and servomotor, make sure that the safety standards are sat is fie d.
If the operation during a control unit or servo amplifier error and the safety direction
operation of the control unit di ffer, const r uct a countermeasure circuit externally of the
control unit and servo amplifi er.
In systems where coasting of the serv omot or w ill be a pro bl em during emergency stop,
servo OFF or when the power is shut O FF, use dynamic brakes.
Make sure that the system considers the coasting amount even when using dynamic
brakes.
In systems where perpendicular shaft dropping may be a problem dur ing emergency stop,
servo OFF or when the power is shut O FF, use both dynamic brakes and magnetic brakes.
The dynamic brakes must be used only during emergency stop and errors where servo OFF
occurs. These brakes must not be us ed f or normal braking.
The brakes (magnetic brakes) assembled into the servomotor are for holding applications,
and must not be used for normal braki ng.
Construct the system so that t here is a mechanical allow ance allowing stopping ev en i f the
stroke end limit switch is pass ed t hrough at the max. speed.
Use wires and cables that have a w ire d ia m et er, heat resistance and bending resistance
compatible with the system.
− III −
Use wires and cables within the length of the range described in the instruction manual.
The ratings and characteristics o f the system parts (other than control unit, servo amplifier,
servomotor) must be compatible w ith t he control unit, servo amplifier and serv omot or.
Install a cover on the shaft so that t he rot ary parts of the servomotor are not touched during
operation.
There may be some cases where hol ding by the magnetic brakes is not possible due to the
life or mechanical structure (when the ball screw and servomotor are connected with a
timing belt, etc.). Install a stopping device to ensure safety on the machine side.
(2) Parameter settings and programming
Set the parameter values to those that are compatible with the control unit, servo amplifier,
servomotor and regenerative resistor model and the system applicati on. The protective
functions may not function if the settings are incorrect.
The regenerative resistor model and capacity parameters must be set to values that
conform to the operation mode, servo amplifier and servo power unit. Th e prot ect ive
functions may not function if the settings are incorrect.
Set the mechanical brake output and dynamic brake output validity parameters to values
that are compatible with the system application. The protective functions may not fu nct ion if
the settings are incorrect.
Set the stroke limit input v al idit y parameter to a value that is compatible with the system
application. The prote c t ive functions may not function if the setting is incorrect.
Set the servomotor encoder type (incre ment , absolute position type, etc.) parameter t o a
value that is compatible w ith the system application. The prot ective functions may not
function if the setting is incorrect.
Set the servomotor capacity and t ype (standard, low-inertia, flat, etc. ) paramet er t o values
that are compatible with the system application. The protective functions may not fu nct ion if
the settings are incorrect.
Set the servo amplifier capacity and type parameters to values that are compatible with the
system application. The protect ive functions may not function if the set t i ngs are incorrect.
Use the program commands for t he program with the conditions spec if ied in the instruction
manual.
Set the sequence function pro gram capacity setting, dev ice capacity, latch validity range, I/O
assignment setting, and v alidity of continuous operat i on during error detection to values t hat
are compatible with the syst em application. The protective functions may not function if the
settings are incorrect.
Some devices used in the program have fixed applicati ons, so use these with the conditions
specified in the instructi on manual.
The input devices and data registers assigned to the link will hold t he data previous to when
communication is terminat ed by an error, etc. Thus, an error correspondence int erlock
program specified in the instruction manual must be used.
Use the interlock program specified in the special func t io n unit's instruction manual for the
program corresponding to the special function unit.
CAUTION
CAUTION
− IV −
(3) Transportation and installation
Transport the product with the correct method according to the weight.
Use the servomotor suspension bolts only for the transportatio n of the servomotor. Do not
transport the servomotor with mac hine installed on it.
Do not stack products past the l i mit.
When transporting the control unit or servo amplifier, never hold the connected wires or
cables.
When transporting the servomotor, never hold the cables, shaft or detector.
When transporting the control unit or servo amplifier, never hold t he fr ont case as it may fall
off.
When transporting, installing or removing the control unit or servo amplifier, never hold the
edges.
Install the unit according to the instruction manual in a place where the weight can be withstood.
Do not get on or place heavy objects on the product.
Always observe the installation direction.
Keep the designated cleara nce between the control unit or serv o amplifier and control panel
inner surface or the control unit and s ervo amplifier, control unit or serv o amp l ifier and other
devices.
Do not install or operate cont rol units, servo amplifiers or servomotors that are damaged or
that have missing parts.
Do not block the intake/outt ake ports of the servomotor with cooling fan.
Do not allow conductive matter such a s screw or cut t in g chi ps or combustible matter such
as oil enter the control unit, serv o amp lifier or servomotor.
The control unit, servo amplifier and servomotor are precision machines, so do not drop or
apply strong impacts on the m.
Securely fix the control unit a nd servo amplifier to the machine according to the instruction
manual. If the fixing is insufficient, these may co me off duri ng operation.
Always install the servomotor with reduction gears in the designated direction. Fai ling t o do
so may lead to oil leaks.
Store and use the unit in the following environmental conditions.
CAUTION
Environment
Ambient
temperature
Ambient humidity
Storage
temperature
Atmosphere
Altitude1000m (3278.69ft.) or less above sea level
VibrationAccording to each instruction manual
Control unit/servo amplifierServomotor
0°C to +55°C
(With no freezing)
According to each instruction
manual.
According to each instruction
manual.
Indoors (where not subject to direct sunlight).
No corrosive gases, flammable gases, oil mist or dust must exist
− V −
Conditions
0°C to +40°C
(With no freezing)
RH or less
80
%
(With no dew condensation)
C to +65°C
−20°
When coupling with the synchronization encoder or servomotor shaft end, do not apply
impact such as by hitting with a hammer. Doing so may lead to detector damage.
Do not apply a load larger than the t olerable load onto the servo motor shaft. Doing so may
lead to shaft breakage.
When not using the unit for a long ti me, disconnect the power line from the control unit or
servo amplifier.
Place the control unit and servo amplifier in static electric it y preventing vinyl bags an d st ore.
When storing for a long time, please co nsult our sales representative.
(4) Wiring
Correctly and securely w ire the w ires. Reconfirm the connection s for mist akes and the
terminal screws for tightness after w iring. Failing to do so may lead to run away of the
servomotor.
After wiring, install the prote ct ive covers such as the terminal cov ers t o t he original positions.
Do not install a phase adv ancing capacitor, surge absorber or radio noise filter (option FR-
BIF) on the output side of the servo amplifier.
Correctly connect the output side (terminals U, V, W). Incorrect connections will lead the
servomotor to operate abnormally.
Do not connect a commercial power supply to the serv omotor, as t his may lead to trouble.
CAUTION
CAUTION
Do not mistake the direction o f the surge absorbing diode
installed on the DC relay for the c ont rol signal output of
brake signals, etc. Incorrect installation may lead to signals
not being output when trouble occurs or the protective
functions not functioning.
Do not connect or disconnect the connection cables
between each unit, the encoder cable or sequence expansion cable while the pow er is ON.
Securely tighten the cable co nnector fixing screws and fixing mechanisms. Insufficient fixing
may lead to the cables combing off during operation.
Do not bundle the power lin e or cables.
(5) Trial operation and adjustment
Confirm and adjust the progra m a nd each parameter before operation. U npredictable
movements may occur depend ing on the machine.
Extreme adjustments and changes may lead to unstable operation, so never make them.
When using the absolute posit ion system function, on starting up, and when the controller or
absolute value motor has been repla ced, always perform a home position return.
CAUTION
Servo amplifier
VIN
(24VDC)
Control output
signal
RA
− VI −
(6) Usage methods
Immediately turn OFF the pow er i f s m oke, abnormal sounds or odors are em it t ed from the
control unit, servo amplifier or servomotor.
Always execute a test operat ion before starting actual operatio ns after the program or
parameters have been changed or after maintenance and inspection.
The units must be disassembl ed and repaired by a qualified techn ici an.
Do not make any modifications t o t he unit.
Keep the effect or magnetic obstacles to a minimum by insta l ling a noise filter or by using
wire shields, etc. Magnetic obsta cl es may affect the electronic devic es used near the control
unit or servo amplifier.
When using the CE Mark-compli ant equipment, refer to the "EMC Insta llation Guidelines"
(data number IB(NA)-67339) for the motion contro ll ers and refer to the corresponding EMC
guideline information for the servo amplifiers, inverters and ot her equipment.
Use the units with the fo llowing conditions.
Item
Input power
Input frequency50/60Hz5%
Tolerable momentary
power failure
CAUTION
Conditions
A1S61PNA1S62PN
100 to 240VAC
(85 to 264VAC)
Within 20ms
CPU module's built-
in power supply
+10%
-15%
(7) Remedies for errors
If an error occurs in the self diagnosis of the c ont rol unit or servo amplifier, confir m the
check details according to the instruct i on manual, and restore the operation.
If a dangerous state is predicted in case of a power failure or product failure, use a
servomotor with magnetic brakes or i nst al l a brake mechanism externally .
Use a double circuit construction so that the
magnetic brake operatio n circuit can be
operated by emergency stop signa ls set
externally.
If an error occurs, remove the cause, secure
the safety and then resume operat ion.
The unit may suddenly resume operation
after a power failure is restored, so do not go
near the machine. (Design the machine so
that personal safety can be ensure d even if
the machine restarts suddenly . )
CAUTION
Shut off with servo ON signal OFF,
alarm, magnetic brake signal.
Servo motor
Magnetic
brakes
RA1
Shut of f with th e
emergency stop
signal(EMG).
EMG
24VDC
− VII −
(8) Maintenance, inspection and part replacement
CAUTION
Perform the daily and pe riodic inspections according to the instruction manua l.
Perform maintenance and insp ect io n after backing up the program and para meters for the
control unit and servo amplifi er.
Do not place fingers or hands in the c learance when opening or closing any opening.
Periodically replace consumable parts such as batteries a ccording to the instruction manual.
Do not touch the lead sections such as ICs or the connector contacts.
Do not place the control unit or servo amplifier on metal that may cause a power leakage or
wood, plastic or vinyl that may cause static electricity buildup.
Do not perform a megger test (insulat i on resistance measurement) during inspection.
When replacing the control unit or servo amplifier, always set the new unit set t in gs correctly.
When the controller or absolute value mot or has been replaced, carry out a home positi on
return operation using one of the f ol lowing methods, otherwise p osition displacement cou ld
occur.
1) After writing the servo data to the P C using peripheral device softw are, switch on the
power again, then perform a ho me position return operation.
2) Using the backup function o f the peri pheral device software, load t he dat a backed up
before replacement.
After maintenance and inspections are complete d, confirm that the position detection of the
absolute position detector funct ion is correct.
Do not short circuit, charge, overheat, incinerate or disassemble the bat t eries.
The electrolytic capacitor will generate gas during a fault, so do not place your face near t he
control unit or servo amplifi er.
The electrolytic capacito r and fan will deteriorate. P eriodically change thes e t o prevent
secondary damage from faults. Replacements can be made by our sales representative.
(9) Disposal
Dispose of this unit as general industrial waste.
Do not disassemble the control unit , servo amplifier or servomotor parts.
Dispose of the battery accordi ng t o local laws and regulations.
(10) General cautions
All drawings provided in the instruction manual show t he st ate with the covers and safety
partitions removed to explain detai led s ect i ons. When operating the product, always return
the covers and partitions to the designated positions, and operat e according to the
instruction manual.
CAUTION
CAUTION
− VIII −
Revisions
*The manual number is given on the bottom left of the back cover.
Print Date*Manual NumberRevision
Apr.1998IB(NA)-67395-BFirst edition
Sep.2000IB(NA)-67395-C
Addition
Addition of information on the A173UHCPU
Correction
For Sate Operations (4. Various precautions (3), (6), (8)), CONTENTS, 1.1,
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial
property rights which may occur as a result of using the contents noted in this manual.
2. DESIGN......................................................................................................................................2- 1 to 2-22
2.1 System Designing Procedure ............................................................................................................ 2- 1
2.2 System Design...................................................................................................................................2- 4
Appendix 2.8 Serial Absolute Synchronous Encoder Specifications ............................................APP-26
− II −
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1. SPECIFICATIONS OF MO TION SYS TEM COM PONENTS
This chapter provides the system configuration of the motion system and the
specifications, functions, setting methods, external equipment connection
methods, part names and other information of the related modules for those who
are involved in the design, installation, wiring, trial run, adjustment and
maintenance of the motion system.
1.1 Overview of the Motion System
A173UHCPU/A172SHCPUN/A171SHCPUN are CPUs which incorporate the
positioning control CPU (hereinafter referred to as PCPU) and the sequence
control CPU (hereinafter referred to as SCPU) and perform the following functions:
•
PCPU..........Carries out the positioning control, home position return, servo
amplifier control status monitoring using a servo program or
motion program.
•
SCPU..........Carries out the sequence control, start-up of servo program or
motion program, enabling and disabling manual pulse generator
operation, and jog operation.
Positioning data setting and programming of A173UHCPU/A172SHCPUN/
A171SHCPUN is performed using the following peripheral devices and positioning
software package.
(1) Peripheral device
•
IBM PC/AT compatible running DOS/V5.0 or higher(hereinafter abbreviated
as "IBM PC")
(2) Positioning software package
•
For IBM PC ......... SW
SRX-GSV PE, SW RN-GSV PE
The following diagram outlines the peripheral devices and programs using a
positioning software package, data creation, and A173UHCPU/A172SHCPUN/
A171SHCPUN processing.
Servo program or
motion program
Positioning
parameter
SCPU
Positioning
device
PCPU
Sequence control
Servo program or motion
program execution
JOG operation
For communication
between SCPU and PCPU
Positioning control
Home position return
Servo monitoring
1 − 1
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
•
The sequence program written into the SCPU, the servo program or motion
program written into the PCPU, and the positioning parameters are created
after starting up corresponding positioning software package by the
peripheral device.
•
The peripheral device started up by the positioning software package can
monitor the positioning control conditions of A173UHCPU/A172SHCPUN/
A171SHCPUN, execute the servo program or motion program, and perform a
test such as JOG operation.
REMARKS
For information about a peripheral device and programming information for
producing a sequence program and a special function unit, refer to each
manual pertaining to the individual unit.
For information about creating motion programs, refer to the programming
manual of the operating system used. For information about the operation of
each peripheral software package, refer to each individual operating manuals.
In this manual, the following abbreviations are used.
A172SENC manual pulse generator/synchronous encoder interface unit/moduleA172SENC
Fast serial communication betw een motion control ler and serv o ampl ifi erSSCNET
A173UHCPU/A172SHCPUN/
A171SHCPUN or CPU module
*1
*1 SSCNET: Servo System Controller NETwork
1 − 2
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1.2 Overall Configuration of Motion System
1.2.1 A172SHCPUN/A171SHCPUN System Overall Configuration
Serial absolute synchronous encoder cable
(MR-HSCBL M)
E
Serial absolute synchronous encoder 1
(MR-HENC)
External input signals
FLS upper stroke limit
RLS lower stroke limit
STOP signal
DOG/CHANGE near-zero point dog/
changeover between speed and position
TRA tracking
Electromagnetic brake command output
d1d2d3dn
Extension cable
(A1SC B for
A1S6 B
and A168B)
(A1S NB
for A6 B)
Main base unit(A178B-S1/A17 B)
GOT
module
Power supply
Sequence extension base
Up to one extension base unit for A1S6 B
Up to one extension base unit for A168B
(GOT compatible)
Up to one extension base unit for A6 B
A171SHCPUN A172SHCPUN
4
1
8
1
*2
Termination
resistance
*1:No. of motion slots
A17 B 1
A178B-S1 2
M
E
M
E
M
E
M
E
*2:n:No. of control axes (max.)
A171SHCPU N 4
A172SHCPU N 8
MR-H-BN/MR-J2S-B/MR-J2-B model
Servo amplifier
SSCNET:Servo System Controller NETwork
POINTS
(1) When using the sequence extension base and bus connection type GOT, select the A168B as the
sequence extension base. When not using the sequence extension base, you can connect the bus
connection type GOT directly to the extension connector of the main base unit.
(2) When using a teaching unit A31TU-E with a dead-man switch, a dedicated connecting cable
A31TUCBL03M is required between the CPU unit and A31TU-E connector. If the A31TU-E is
connected directly to the RS422 connector of the CPU without using a dedicated cable, the
A31TU-E will not operate at all. After disconnecting the A31TU-E, attach a short-circuit connector
A31SHORTCON for A31TUCBL.
(3) In a motion module, a sequence A1S I/O modules can also be installed.
(4) Though the external input signals of A172SENC are reserved for eight axes, for A171SHCPUN,
set those for the first half four axes (PX0 to PX0F).
1 − 3
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
CAUTION
Configure safety circuits external to the controller or servo amplifier if their abnormal operation
could cause axis motion in a direction other than the safe operating direction for the system.
Ensure that the characteristics of other components used in a system match those of the
controllers, servo amplifiers, and servo motors.
Set the parameters to values appropriate for the controllers, servo amplifiers, servo motors,
regenerative resistor types, and system application. The protective functions may not work if the
parameters are set incorrectly.
Main base unit
(A178B-S3/
A178B-S2/
A178B-S1/
A17 B)
A172
A172
SENC
A172
SENC
SENC
A1S input module or
special function module
P
Manual pulse generator 3
P
(MR-HDP01)
P
Serial absolute synchronous
E
encoder cable
E
(MR-HSCBLM)
E
Serial absolute synchronous encoder 4
E
(MR-HENC)
External input signals
FLS upper stroke limit
RLS lower stroke limit
STOP signal
DOG/CHANGE near-zero point dog/
speed-position change
TRA tracking
Electromagnetic brake command output
SSCNET2
d1
*3
SSCNET cable
SSCNET3
d8
d9
Extension cable
(A1SC B for
A1S6 B
and A168B)
(A1S NB
for A6 B)
d16
GOT
module
Power supply
Sequence extension base
Up to one extension base unit for A1S6 B
Up to one extension base unit for A168B
(GOT compatible)
Up to one extension base unit for A6 B
8
1
SSCNET4
d17
888
111
d24
d25
d32
SSCNET1
*1:No. of motion slots
A17 B 1
A178B-S1 2
A178B-S2 4
M
E
M
E
M
E
M
E
M
E
M
E
M
E
M
E
A178B-S3 8
MR-H-BN/MR-J2S-B/MR-J2-B model
Servo amplifier, max. 32 axes
SSCNET:Servo System Controller NETwork
POINTS
(1) When using the sequence extension base and bus connection type GOT, select the A168B as the
sequence extension base. When not using the sequence extension base, you can connect the bus
connection type GOT directly to the extension connector of the main base unit.
(2) When using a teaching unit A31TU-E with a dead-man switch, a dedicated connecting cable
A31TUCBL03M is required between the CPU unit and A31TU-E connector. If the A31TU-E is
connected directly to the RS422 connector of the CPU without using a dedicated cable, the
A31TU-E will not operate at all. After disconnecting the A31TU-E, attach a short-circuit connector
A31SHORTCON for A31TUCBL.
(3) In a motion module, a sequence A1S I/O modules can also be installed.
*2The A173UHCPU can use four channels of the SSCNET. When using the SSCNET card/board
(A30CD-PCF/A30BD-PCF), connect it to the SSCNET4 and the servo amplifiers to the SSCNET1
to 3.
In this case, up to 24 axes of servo amplifiers can be connected.
*3TRA tracking enable can use any one point.
1 − 5
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
CAUTION
Configure safety circuits external to the controller or servo amplifier if their abnormal operation
could cause axis motion in a direction other than the safe operating direction for the system.
Ensure that the characteristics of other components used in a system match those of the
controllers, servo amplifiers, and servo motors.
Set the parameters to values appropriate for the controllers, servo amplifiers, servo motors,
regenerative resistor types, and system application. The protective functions may not work if the
parameters are set incorrectly.
1 − 6
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1.3 Equipment in System
(1) Table of motion modules
Part NameModel NameDescription
A173UHCPU(-S1) Max. 32 axes control1.90
A172SHCPUNMax. 8 axes control1.63CPU module
A171SHCPUNMax. 4 axes control1.63
A172BOne motion module slot and one sequence module slot
A175BOne motion module slot and four sequence module slots
Limit output unit A 1SY4 2Transistor output 64 points, 12/24 VDC, 0.1A0.93
Manual pulse
generator
Serial absolute
synchronous
encoder
Serial absolute
synchronous
encoder cable
BatteryA6BAT
Teaching unit
SSC I/F boardA30BD-PCFISA bus loading type, 2 channels/board
SSC I/F cardA30CD-PCFPCMCIA TYPE II, 1 channel/card
SSC I/F board
cable
SSC I/F card
cable
A178B
A178B-S1Two motion module slots and six sequence module slots
A178B-S2Four motio n module slots and four sequence module slots
A178B-S3
A1S65B
A1S68B
A168B
A1SC01BFlat cable of 55 mm (2.17 in) in length
A1SC03BLength 330 mm (13 in)
A1SC07BLength 700 mm (27 in)
A1SC12BLength 1200 mm (47 in)
A1SC30BLength 3000 mm (118 in)
A1SC60BLength 6000 mm (236 in)
A1SC05NBLength 450 mm (17 in) AnN extension base cables
A1SC07NBLength 700 mm (27 in) AnN extension base cables
A1SC30NBLength 3000 mm (118 in) AnN extension base cables
A1SC50NBLength 5000 mm (197 in) AnN extension base cables
A172SENC
MR-HDP01
MR-HENC
MR-HSCBL
A30TU-EFor SV13, cable length 5 m (16.4 ft)0.22
A31TU-E
A31TU-RE
A31TUCBL03MCPU module to A31TU-E connector cable of 3 m (9.84 ft.)For control panel
A31SHORTCONShort-circuit connector for A31TUCBL
A270BDCBL
A270CDCBL
One motion module slot and seven sequence module
slots
Eight motion module slots and zero sequence module
slots
Extension power and five slots for system up to one
extension stage
Extension power and eight slots for system up to one
extension stage
Extension power and eight slots for system up to one
extension stage
32 points I/O signals
(FLS, RLS, STOP, DOG/CHANGE×8)
Tracking input 1 point
Electromagnetic brake control output 1 point
Manual pulse generator interface 1 point
Synchronous encoder interface 1 point
4.5 VDC to 13.2 VDC 25 PLS/rev, 100 PLS/rev at
magnification of 4
Synchronous encoder and A172SENC connector cables:
2 m (6.56 ft.), 5 m (16.4 ft.), 10 m (32.8 ft.), 20 m (65.6
ft.), 30 m (98.4 ft.)
M
(Same cables as encoder cables for HA-LH
SF/RF/UF(2000r/min)series motors.)
For CPU module memory back-up
(Sequence program/servo program)
For SV13 with deadman switch, cable length 5 m (16.4
ft)
For SV51 with deadman switch, cable length 5 m (16.4
ft)
(Need A31TUCBL03M and A31SHORTCON.)
3 m (9.84 ft.), 5 m (16.4 ft.), 10 m (32.8 ft.) for
M
A30BD-PCF
3 m (9.84 ft.), 5 m (16.4 ft.), 10 m (32.8 ft.) for
M
A30CD-PCF
K, HC-
Current
Consumption
5 VDC (A)
0.42
0.06
0.15
0.22
0.22
1 − 7
Remarks
Sequence extension
connector as
accessory
Extension connector
as accessory
For extension to the
right side
For A6 B
When A31TU-E is
not connected
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
y
(2) Table of servo amplifier modules
Part NameModel NameDescription
50 W to 22 kW
30 kW to 55 kW
External regenerative resistor 10 W to 500 W
Regenerative power 600 W
External regenerative resistor 1300, 3900 W
For connection of CPU module and MR-H-BN, for connection of MR-H-BN and
MR-H-BN
0.5 m(1.64 ft), 1 m (3.28ft), 5 m (16.4 ft)
For connection of HA-LH
BN
M-H
2 m (16.4 ft), 5 m (16.4 ft), 10 m (32.8 ft), 20 m (65.6 ft), 30 m (98.4 ft)
For
HA-LH
Amplifier side connector and encoder side connector set
50 W to 7 kW, three-phase 200 to 230 VAC or single-phase 230 VAC
50 W to 400 W, single-phase 100 to 120 VAC
For connection of CPU module and MR-J2S-B/MR-J2-B, for connection of MR-HBN and MR-J2S-B/MR-J2-B
M-A
0.5 m(1.64 ft), 1 m (3.28ft), 5 m (16.4 ft)
For connection of MR-J2S-B/MR-J2-B and MR-J2S-B/MR-J2-B
M
0.5 m(1.64 ft), 1 m (3.28ft), 5 m (16.4 ft)
Standard
M-L
cable
M-H
Long flexing
life cable
M-H
Standard
M-L
cable
Long flexing
M-H
life cable
For HC-SF/RF/UF (2000r/min), HC-SFS/RFS/UFS (2000r/min) series motors
Amplifier side connector and encoder side connector set
For HC-MF/UF (3000r/min), HA-FF, HC-MFS/KFS/UFS (3000r/min) series motors
Amplifier side connector and encoder side connector set
K, HC-SF/RF/UF (2000r/min) series motors
For connection of HC-SFS/RFS/UFS (2000r/min) series motor and
MR-J2S-B, and for connection of HC-SF/RF/UF (2000r/min) series
motor and MR-J2-B
2 m (6.56 ft), 5 m (16.4 ft), 10 m (32.8 ft), 20 m (65.6 ft),
30 m (98.4 ft)
For connection of HC-MFS/KFS/UFS (3000r/min) series motor and
MR-J2S-B, and for connection of HC-MF/UF (3000r/min), HA-FF
series motor and MR-J2-B
2 m (6.56 ft), 5 m (16.4 ft), 10 m (32.8 ft), 20 m (65.6 ft),
30 m (98.4 ft)
K, HC-SF/RF/UF (2000r/min) series motor and MR-H-
MR-H-BN
series
MR-J2S-B
series
MR-J2-B
series
Equipment
common to
MR-J2S-B
and
MR-J2-B
series
Servo amplifier
BatteryMR-BATBackup for absolute position detection
Termination
connector
Regenerative
resistor
SSCNET cable MR-HBUS
Encoder cable
*2
Encoder
connector set
Servo amplifier
Servo amplifier MR-J2BatteryMR-BATBackup for absolute position detection
Termination
connector
SSCNET cable
Encoder cable
*2
Encoder
connector set
MR-H BN
MR-H
KBN
MR-TMFitted to the last amplifier of SSCNET
MR-PB
MR-H
KB
Standard accessor
MR-PB -4
FR-BUBrake unit 15/30/55K
FR-RCPower return converter 15/30/55K
M
MR-HSCBL M
MR-EN1CBL
MR-JSCNS
MR-EN1CNS
MR-J2S- B
MR-J2S-
MR-A-TMFitted to the last amplifier of SSCNET
MR-J2HBUS
MR-J2HBUS
MR-JHSCBL
MR-JHSCBL
MR-ENCBL
MR-JCCBL
MR-JCCBL
MR-J2CNS
MR-ENCNS
MR-J2CNM
*1: 5kW and 7kW are scheduled for release.
*2: Long distance cable or cable without connector (cable only) is also available.
Avoid using a short cable as it will cause a position shift or the like.
*1
B1
B50 W to 3.5 kW
1 − 8
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
(3) Table of software package
(a) Motion function
Peripheral Software PackageMain OS Software Package Model Name
Use
For conveyor
assembly
(SV13)
For motion
SFCcompatible
conveyor
assembly
(SV13)
For automatic
machinery
(SV22)
For motion
SFCcompatible
automatic
machinery
(SV22)
For machine
tool peripheral
(SV43)
For dedicated
robot (SV51)
Peripheral
Devices
Japanese SW2SRX-GSV13PFrom 0AC on 00T or later
DOS
EnglishSW2SRX-GSV13PE From 00J on 00F or later
IBM PC/AT
IBM PC/AT
IBM PC/AT
IBM PC/AT
IBM PC/AT DOS Japanese SW2SRX-GSV43PFrom 00T on 00J or later
IBM PC/AT DOS Japanese SW2SRX-GSV51P
Japanese SW3RNC-GSVFrom 00F on 00E or later
NT/
98
EnglishSW3RNC-GSVE
Japanese SW3RNC-GSVFrom 00F on
NT/
98
EnglishSW3RNC-GSVE
Japanese
DOS
English
Japanese SW3RNC-GSVFrom 00F on 00E or later
NT/
98
EnglishSW3RNC-GSVE
Japanese SW3RNC-GSVFrom 00F on
NT/
98
EnglishSW3RNC-GSVE
Model Name
SW2SRX-GSV22PFrom 0AC on 00T or later
SW0SRX-CAMPFrom 00B on 00B or later
SW2SRX-GSV22PE From 00J on 00F or later
SW0IX-CAMPE
Applicable version
For
A173UH
Without
restriction
Without
restriction
Without
restriction
Without
restriction
Without
restriction
For
A172SH/
A171SH
Without
restriction
Without
restriction
Without
restriction
Without
restriction
Without
restriction
Without
restriction
Without
restriction
00E or later
For
A173UH
SW2SRXSV13B
SW2SRXSV13B
SW3RNSV13B
SW2SRXSV22A
SW3RNSV22A
SW2SRXSV43A
A172SH
SW0SRXSV13D
SW2SRXSV13D
SW3RNSV13D
SW0SRXSV22C
SW3RNSV22C
SW0SRXSV43C
SW0SRXSV51D
For
For
A171SH
SW0SRXSV13G
SW0SRXSV13G
SW0SRXSV22F
SW0SRXSV43F
SW0SRXSV51G
Teaching
function
Yes
No
No
Yes
1 − 9
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1.4 General Specifications
Table 1.1 Generation Specifications
ItemSpecification
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
FrequencyAccelerationAmplitude
Vibration resistance
Shock resistanceConforms to JIS C 0912 (98m/s2 (10g), 3 directions, 3 times)*
Noise resistance
Withstand voltage2830V A C rms / 3 cycles across all i nputs/ LG and all out puts/F G (alt itude 2000m (6557. 38f t. ))
Insulation resistance5M
GroundClass 3 grounding. Connect to enclosure when grounding is impossible.
Operating environment No corrosive gas, low dust
Cooling methodNatural cooling.
or more by 500VDC insulation resistance tester across all inputs/LG and all outputs/FG
10 to 55Hz
55 to 150Hz9.8m/s
10% to 90%RH, no condensation
10% to 90%RH, no condensation
0 to 55°C
-20 to 75°C
Number of Sweeps
0.075mm
(0.003 in)
2
2
µ
s, noise frequency: 25 to 60 Hz, with a noise simulator
(1 octave/minute)*
10
1
REMARKS
*1 An “octave” refers to an increase or decrease in frequency by a factor of
two. For example, the following are all octaves: 10 Hz to 20 Hz, 20 Hz to
40 Hz, 40 Hz to 20 Hz, and 20 Hz to 10 Hz.
Refer to “CHAPTER 2 DESIGN” for the installation environment and
mounting instructio ns.
*2 JIS: Japan Industrial Standards
WARNING
Class 3 grounding should be used. The motion controller should not share a common ground with
any other equipment. The ground terminal is located on the motion controller module terminal
block. (See Section 1.5.2.)
CAUTION
The motion controller must be stored and operated under the conditions listed in the table of
specifications above.
Disconnect the power cables from the motion controller if it is to remain unused for a long period
of time.
Insert a controller or servo amplifier into the static-proof vinyl bag for storage.
Consult the system service or service station before storing equipment for a long period of time.
1 − 10
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
1.5 Specifications and Settings of Components
1.5.1 A173UHCPU/A172SHCPUN/A171SHCPUN
(1) Basic specifications of A173UHCPU, A172SHCPUN and A171SHCPUN
ItemA173UHCPU(-S1)A172SHCPUNA171SHCPUN
No. of control axes32-axes8-axes4-axes
SV13
Motion
PC
System
configuration
Compatibility
Outside dimensions130 113.3 93.6 (5.12 4.46 3.69) unit = mm (inch)
Weight (kg (lb))0.85 (1.87)
Computing
frequency
Sequencer CPUEquivalent to A3UCPU
Processing speed
(
s) (Sequence
instruction)
No. of I/O points8192 points2048 points
No. of real I/O points *
Memory capacity (built-in RAM)
Program capacity
(Main sequence)
No. of file register (R)Max. 8192 registers
2
block *
No. of sequencer extension
base units
Pulser synchronous encoder
interface unit
No. of SSCNET I/F4CH.
Teaching unit (OS
with teaching
function)
Sequence program, parameter
Servo program
Mechanism program (SV22)
Parameter
System settingMust be set anew.
SV22
Direct
method
Refresh
method
1
Standard
-S1
StandardMax. 10 blocksNo. of extension file register
-S1Max. 46 block s
(Corresponding to external signal input
A30TU-E
A31TU-E
After starting A173UHCPU and reading
a file, those created by A273UHCPU
(32-axes) can be used as it is.
3.5 ms/1 to 20 axes
7.1 ms/21 to 32 axes
3.5 ms/1 to 12 axes
7.1 ms/13 to 24 axes
14.2 ms/25 to 32 axes
0.15
s/step0.25 s/step
2048 points1024 points512 points
192k bytes (Equivalent to
A3NMCA-24)
768k bytes (Equivalent to
A3AMCA-96)
Max. 30k stepsMax. 30k stepsMax. 14k steps
A172SENC
32-axes)
4
(With dead-man switch)
3.5 ms/1 to 8 axes3.5 ms/1 to 4 axes
Equivalent to
reinforced I/O
memory of
A2SHCPU
0.25 to 1.9 s/step
192k bytes
(Equivalent to
A3NMCA-24)
Max. 10 blocksMa x. 2 blocks
Max. one
A172SENC 1
(Corresponding to external signal input
8-axes)
2CH.
SSCNET1..... For connection of servo
SSCNET2..... For personal computer link
After starting A172SH/A171SH and
reading a file, those created by
A171SCPU can be used as it is.
By making sure of system setting screen
after being started up by A172SH/A171SH
and reading a file, changeover below is
carried out:
A171SCPU
A171SENC
now the system is ready for operation.
amplifier
dedicated
A172SH/A171SHCPUN
A172SENC
Equivalent to
A2SHCPU
64k bytes
(Equivalent to
A3NMCA-8)
*1 The real I/O points can be used within the range of one extension base.
*2 No. of extension file register blocks varies depending on the setting of program capacity, No. of file
registers, and No. of comments.
1 − 11
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
(2) Functions and performance specifications of PCPU
The performance specifications and functions of the PCPU depend on the
motion function OS model installed in the CPU module.
Refer to the programming manual of the motion functions installed in the CPU
module.
1 − 12
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
(3) SCPU performance specifications and functions
(a) SCPU performance specifications
As the SCPU performance specifications differ according to the operating
system used, refer to the appropriate OS Programming Manual for details.
Table 1.2 Table of SCPU Performance Specifications
ItemA173UHCPU(-S1)A172SHCPUNA171SHCPUN
Control methodStored programs repe at ed op era ti on
I/O control methodRefresh methodRefresh method/direct method (selectable)
Programming language
Sequence instructions2226
Number of instructions
Processing speed ( s)
(sequence instructions)
No. of I/O points8192 points (X/Y0 to 1FF)2048 points (X/Y0 to X/Y7FF)
No. of real I/O points *
Watchdog timer (WDT)200 ms fixed10 to 2000 ms
Memory capacity (internal RAM)
No. of internal relays (M) *
No. of latch relays (L)1048 points (L1000 to L2047)
No. of step relays (S)0 point (none at initial status)
No. of link relays (B)8192 points (B0 to B1FFF)1024 points (B0 to B3FF)
Timers (T)
Device
Counters (C)
No. of data registers (D) *
No. of link registers (W)8192 points (W0 to W1FFF)1024 points (W0 to W3FF)
No. of annunciators (F)2048 points (F0 to F2047)256 points (F0 to F255)
No. of file registers (R)Max. 8192 points (R0 to R8191) (set with parameters)
No. of accumulators (A)2 points (A0, A1)
No. of index registers (V, Z)
No. of pointers (P)256 points (P0 to P255)
No. of interrupt pointers (I)32 points (I0 to I31)
No. of special-function rela ys( M)256 points (M9000 to M9255)
No. of special-function registers (D)
Basic instructions252131
Special instructions204106
Motion dedicated instruc ti on s44
Direct method0.25 to 1.9 s/step
Refresh method0.15
5
Standard
-S1
Main sequence programMax. 30 k stepsMax. 14k steps
Sub-sequence programMax. 30k stepsNoneNoneProgram capacity
Micro computer programNoneMax. 58k bytesMax. 26k bytes
1
Points256 points
Specifications
Points256 points
Specifications
1
8192 points (D0 to D8191)1024 points (D0 to D1024)
(Relay symbol language, logic symbol language, MELSAP-II (SFC))
s/step0.25 s/step
2048 points (X/Y0 to 7FF)
192k bytes
(Equivalent to
A3NMCA-24)
768k bytes
(Equivalent to
A3AMCA-96)
7144 points (M0 to M999,
M2048 to M8191)
100 ms timer0.1 to 3276.7sT0 to T199
10 ms timer0.01 to 327.67sT200 to T255
100ms retentive timer0.1 to 3276.7sNo initial value
Normal counter1 to 32767C0 to C255
Interrupt program counter1 to 32767
14 points
(V, V
to V6, Z, Z1 to Z6)
1
Sequence control dedicated language
1024 points (X/Y0 to
X/Y3FF)
192k bytes64k bytes
1000 points (M0 to M999)
Time settingDevice
Set with parameters
Setting rangeDevice
Set with parameters
2 points (V, Z)
256 points (D9000 to D9255)
512 points (X/Y0 to X/Y1FF)
C224 to C255
(No initial value)
3
*
4
*
1 − 13
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
Table 4.1 Table of SCPU Performance Specifications (Continued)
ItemA173UHCPU (-S1)A172SHCPUNA171SHCPUN
Standard
No. of extension file register block
-S1
No. of commentsMax. 4032 points (64k by tes), 1 point = 16 bytes (set in 64-point unit)
No. of extension comments *
Self-diagnosis functionWatchdog error monitoring, memory/CPU/input output/battery, etc. error detection
Operating mode on errorSelect stop/continue
Output mode selection when switching from STOP to RUN
Clock functionYear, month, day, hour, minute, day of the week (leap year automatic distinction)
*1 Range of positioning dedicated devices differs depending on the OS. Refer to the Programming Manual of each OS.
When shared between M, L and S, the total number of devices points is 8192 for the A173UHCPU or 2048 for the A172SHCPUN/A171SHCPUN.
*2 Extension comments are not stored into the internal memory of the CPU.
*3 For the A173UHCPU, set the times of the extension timers (T256 to T2047) using the word devices (D, W, R).
*4 For the A173UHCPU, set the count values of the extension counters (C256 to C1023) using the word devices (D, W, R).
*5 The real I/O points can be used within the range of one extension base.
*6 SW0GHP-UTLP-FN1 is necessary for using A6GPP and A6PHP.
2
Max. 10 blocks
(set by memory
capacity)
Max. 46 blocks
(set by memory
capacity)
Max. 3968 points (63k bytes), 1 point = 16 bytes (set in 64-point unit)
Select re-output operation status before STOP (default) or output after operation
Max. 10 blocks
(set by memory capacity)
execution.
*6
Max. 3 blocks
(set by memory capacity)
*6
1 − 14
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
(b) SCPU functions
Refer to the A2SHCPU user's manual for details of the SCPU functions of
A171SHCPUN/A172SHCPUN and A3UCPU user’s manual for details of
the SCPU functions of A173UHCPU.
Table 1.3 Table of SCPU Functions
FunctionDescription
!
Sets a constant time for one scan of a sequence program which is independent of the sequence
Constant scan
Latch (hold on
power interruption)
Remote
RUN/STOP
PAUSE
Status latch
Sampling trace
Off-line switch
Error indicator
order or priority
Clock
program scan.
!
Set the constant scan time between 10 ms and 2000 ms.
!
The contents of devices set as latch devices are retained when a reset or a power interruption
over 20 ms occurs if the power is turned off.
!
Devices L, B, T, C, D, W can be set as latch devices.
!
Conducts remote RUN/STOP sequence control from external inputs or peripheral devices when
the RUN/STOP switch is set to RUN.
!
Stops the operation and holds the output (Y) ON/OFF status.
!
The PAUSE status can be set by two method:
!
With the remote PAUSE contacts
!
From a peripheral device
!
The contents of all devices are written to the CPU module status latch area when the status
latch conditions are met.
!
The contents of the devices stored in the status latch area can be monitored from a peripheral
device.
!
The operating status of the designated device is sampled at the set interval, and the results are
stored in the CPU module sampling trace area.
!
Data stored in the sampling trace area can be monitored from a peripheral device.
!
Separates the devices (Y, M, L, S, F, B) used by the OUT instruction from the sequence
program operations.
!
Sets order in which the indicators light and go out when an error occurs.
!
Executes the CPU module internal clock operations .
!
Clock data is: year, month, day, hour, minute, second, day of week.
!
The clock data can be read to D9025 to D9028.
1 − 15
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
(4) Names of A173UHCPU/A172SHCPUN/A171SHCPUN Parts
A173UHCPU/A172SHCPUN
3)
1)2)
13)
6)
7)
8)
9)
A171SHCPUN
5)
6)
7)
8)
9)
N
100 240VAC
105VA
NC
NC
[A173UHCPU]
FRONT
SSCNET
41
32
1:SSCNET1 2:SSCNET2
3:SSCNET3 4:SSCNET4
N
100 240VAC
3
105VA
24VDC 0.6A
+24V
24G
15)
17)
1)2)3)
15)
17)
4)
100 240VAC
10)
18), 19)
4)
100 240VAC
10)
16)
N
105VA
12)
14)
11)19)
18)
13)
12)
N
3
105VA
24VDC 0.6A
16)
14)
18), 19)
11)19)
No.NameApplication
!
RUN/STOP: Starts or stops operation of a sequence program.
!
RESET: Resets the hardware.
1) RUN/STOP key switch
!
LATCH CLEAR (L. CLR): Clears the latch area data set with the parameters
Applies a reset after an operation error occurs and initializes the operations.
(to OFF or 0).
(LATCH CLEAR also clears data outside the latch area.)
2) POWER indicator
!
Display indicator for 5 VDC power supply.
1 − 16
18)
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
No.NameApplications
!
Lit: Sequence program operating with RUN/STOP key switch set to RUN.
The indicator remains lit if an operation error occurs in the sequence
program (Refer to section 5.4.1 (10)).
!
Not lit: The RUN indicator is not lit in the following cases:
!
No 100/200 VAC power supplied to the CPU module.
!
RUN/STOP key switch is set to STOP.
!
3) RUN i ndicator
4) ERROR indicator
24 VDC, 24 GDC
5)
terminals
6) FG terminal
7) LG terminal
Power supply input
8)
terminals
9) Terminal screws
10) Terminal cover
11) RS-422 connector
12) Covers
13) Module fixing screws
14) Battery
15) DIP switch 1
16) DIP switch 402
17) Battery connector
Motion network connector
SSCNET1 to 2
(A172SHCPUN/
18)
A171SHCPUN)
SSCNET1 to 4
(A173UHCPU)
!
Flashing: The RUN indicator flashes in the following cases:
!
Lit: Self-diagnosis function detected an error.
!
Not lit: Normal, or error detected by
!
Flashing: Sequence program annunciator (F) is on.
!
Internally supplies output modules which require 24 VDC (supplied through external
wiring). (A171SHCPUN only)
!
A grounding terminal connected with the shielding pattern on the printed circuit
board.
!
Ground for power supply filter, with 1/2 the electrical potential of the input voltage.
!
Connect the 100 VAC or 200 VAC power supply to the power supply input
terminals.
!
M3.5 7
!
A cover to protect the terminal block.
!
Connector to read, write, monitor, or test main programs with a peripheral device.
!
Covered by a cover when not connected to a peripheral device.
!
Open the protective cover for the printed circuit board, RS-422 connector, or
battery to carry out the following operations:
!
!
!
!
Screws to fix the module to the base unit.
!
Back-up battery for programs, devices in the latch range, and file registers.
(See Section 1.5.7 for the battery mounting procedure.)
!
Installation switch
This switch is used to change the installed CPU modu le opera t ing syst em w ith a
peripheral device.
(See Section 1.5.1 (5) for details about the switch settings.)
ON: Turn ON to install an operating system.
OFF : Turn OFF to enable CPU operation when OS installation is complete.
!
This switch selects the I/O control method and enables or disables memory
protection.
(See Section 1.5.1 (5) for details about the switch settings.)
!
A connector for connecting the battery unit
!
Connectors to HR-H-BN/MR-J2S-B/MR-J2-B.
A remote STOP is applied.
!
A remote PAUSE is applied.
!
Self-diagnosis function detected an error which stops sequence
program
operation.
!
A latch clear operation is conducted.
However, the indicator does not light if it is set not to light for the error
detected in the order of priority settings.
CHK
instruction.
Set DIP switches.
Connect the battery connectors.
Replace the battery.
1 − 17
1. SPECIFICATIONS OF MOTION SYSTEM COMPONENTS
No.NameApplications
Personal computer link
SSC connector
SSCNET2
(A172SHCPUN/
19)
A171SHCPUN)
SSCNET4
(A173UHCPU)
!
A connector for linking a personal computer and personal computer link SSC.
When using the A172SHCPUN/A171SHCPUN, connect the servo amplifier or
personal computer to SSCNET2, or when using the A173UHCPU, connect it to
SSCNET4.
1 − 18
Loading...
+ 131 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.