Mission Javelin I, Javelin II Operator's Manual

Javelin I & II Power Supply Operator’s Manual
I & II Power Supply
Power Factor Corrected AC-DC Switcher
Operator’s Manual
and
“Quick Install” Instructions
www.mpwrs.com
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 1
Javelin I & II Power Supply Operator’s Manual
Javelin I & II Power Supply
Power Factor Corrected AC-DC Switcher
Javelin I & II Power Supply “Quick Install” Instructions
Mounting the Javelin Power Supply
 The Javelin can be mounted at either of two sides (top or bottom).  Use #8-32 mounting screws. Maximum penetration should not exceed 0.21″ (5,33mm).Maintain 2″ (50,8mm) clearance at either end for airflow.
Input Connections
Input Connector (J1)
Input AC or DC power is applied to connector J1 using a 3W3 Power
Connector (Table 1).
To connect, use ITT/Cannon mating receptacle P/N DAM3W3SA197
with pins, P/N DM53744-6.
A fault-clearing device, such as a fuse or circuit breaker, with
maximum 15A rating at the power supply input is required for safety agency compliance.
A1 A2 A3
Single Phase DC
A1 L1 A1 + A2 L2/N A2 – A3 Earth Gnd A3 Earth Gnd
Table 1. AC and DC Input Connections
Status/Control Connector (J2)
J2-1 and J2-9 are spare pins and are not used. J2-2 and J2-4 are Signal Return pins. J2-3 is +12V fan power. J2-5 is VCC +5V @ 300mA. J2-6 is AC Power OK (+5V = true). J2-7 and J2-8 are used in conjunction according to the following table:
J2-8
INHIBIT′
1 X ON 0 0 ON 0 1 OFF
Table 2. Inhibit/Enable Logic Table
J2-7
ENABLE′
POWER SUPPLY
STATE
Use ITT/Cannon mating connector P/N DE9PK87 with Amp cover
shell P/N 205729-1.
Use 20-24 AWG stranded wire.
5
J2 Interface Pin Out
J2-1 Spare J2-2 Signal Return J2-3 Fan Power J2-4 Signal Return J2-5 VCC +5V @ 300mA J2-6 AC Power OK J2-7 PS Enable J2-8 PS Inhibit J2-9 Spare
1
6 9
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 2
Javelin I & II Power Supply Operator’s Manual
Output Connections
Installing ring lugs on output studs:
When viewed from the rear, the left stud is Positive and the
right stud is Return.
Remove the nut and place .312” ID ring lug over output stud. Replace and tighten the nut to a torque of 130 in/lbs. Do Not
Over-Tighten Nuts.
DC OK/Sense Connector (J3)
The Javelin is equipped with Auto-Sense (load sensed at output studs if
remote sense is not connected).
Connector pin J3-1 is the +Remote Sense and J3-6 is the –Remote
Sense.
If Remote Sense is desired, connect pin J3-1 to the positive load con-
nection and pin J3-6 to the negative load connection. Attach load end of sense lines at the point where regulation is desired.
J3-2 and J3-8 provide DC OK′ and DC OK signals. J3-3 and J3-7 provide +5V VCC and +5V Return. J3-4 and J3-9 provide paralleling signals PR1 and PR2. J3-5 is Chassis Ground. Use ITT/Cannon mating receptacle P/N DE9FK87 with Amp cover
shell P/N 205729-1.
Attach terminals to 20-24 AWG stranded wire. Use 20-24 AWG stranded, twisted pair wire for sense connections. Verify that sense lines are not cross-connected.
1
6 9
J3 Interface Pin Out
J3-1 +Remote Sense J3-2 DC OK′ J3-3 +5V VCC J3-4 PR2 J3-5 Chassis Ground J3-6 ─Remote Sense J3-7 +5V Return J3-8 DC OK J3-9 PR1
5
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 3
Javelin I & II Power Supply Operator’s Manual
I & II Power Supply
Power Factor Corrected AC-DC Switcher
Overview
The Javelin is a ruggedized, switching power supply that combines the advantages of power factor correction and power density with user-selectable output voltage and power. Accepting input voltages of 85 to 254 VAC and 85 to 380 VDC, the Javelin can provide up to 1800 watts in a 4.9 H x 7.0 W x 10.75 L (9.5 L for Javelin II) package. Its inherent flexibility comes from its use of Vicor 2nd Generation DC-DC converters. Javelin I has a 100 CFM fan installed, while Javelin II utilizes customer-provided forced-air cooling.
Standard Features
Power Factor Correction: .99 at 115 VAC; .95 at 230 VAC. Universal Input: 85-254 VAC, 47-500 Hz, or 85-380 VDC. Power Output: 1800W at 230 VAC for selected outputs; 800W at 115 VAC (See Graph 1, Pg 13, for
breakdown of input voltage vs. output power).
Full power to 55C; half power at 70C . (See Graph 2, Pg 14 for breakdown of output power vs. ambient
temperature.)
Soft start for limiting inrush current. EMI Compliance: FCC Class A; EN 55022 Class A & B; MIL-STD-461E. Transient Protection: MIL-STD-704E. Environmental: MIL-STD-810E. MIL-STD-1399 (300A); 115VAC, 60Hz, single phase; 1KVA5KVA. Harmonic Distortion to EN61000-3-2. AC Power OK status signal. Fan cooled (Javelin I only, Javelin II requires 100 CFM to be provided by customer). Equipped with Auto-Sense. Output overcurrent, overvoltage and overtemperature protection. Ride-through (holdup) time: 20 ms at 1200W load. Size: 4.9 H x 7.0 W x 10.75 L (9.5 L for Javelin II). Heavy-duty “ruggedized” enclosure designed for a high shock and vibration environment. Extra cooling provided for higher output with increased altitude capability. “D” shell connectors for input and interface connections.
Technical Description
The Javelin consists of a DC or off-line single phase power-factor-corrected front end, with an EMI filter, cool­ing fan (Javelin I), customer interface, associated housekeeping circuits, and a selection of Vicor’s DC -DC con­verters.
Input DC or AC mains voltage is applied to a 3-pin power connector. The input current is passed through an EMI filter designed to meet conducted noise limit specification EN55022, level A and B.
At start-up, inrush current is limited by a PTC thermistor. The PTC is shunted out shortly after initial power-up by a DC bus voltage sense circuit driving a thyristor. After rectification, the input voltage is put through a boost converter that keeps the AC input current sinusoidal and synchronized with the input AC voltage (in compliance with EN61000-3-2). The boost converter delivers a regulated input to the hold-up capacitors and a high voltage backplane. The backplane supplies power to the DC-DC converters that provide the desired low voltage, regulated output.
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 4
Javelin I & II Power Supply Operator’s Manual
Power
Output
Line Filter
Rectifier
Soft Start
Circuit Boost Converter
Output
PFC Control
Customer
Interface
I/E Control
Fan Housekeeping
Power
Input
Current
Sample
Waveform
Sample Inhibit/Enable Control
Inhibit/Enable
Voltage conversion is achieved by Vicor’s family of Zero-Current-Switching (ZCS) DC-DC converters. These are forward converters in which the main switching element switches at zero current. This patented topology has a number of unique attributes: low switching losses, high frequency operation (resulting in reduced size for magnetics and capacitors), excellent line and load regulation, wide output adjustment range, low EMI/RFI emission, and high efficiency.
At initial power-up, the Javelin output is disabled to limit the inrush current and to allow the DC bus potential to settle out to the correct operating level. A low-power flyback converter operating with PWM current-mode control converts the high voltage DC bus into regulated low voltage to power the internal housekeeping circuits and DC cooling fans.
The internal housekeeping Vcc comes up within 1 second after the application of input power. Once the high
voltage bus is within operating limits, the AC Power OK signal changes its output to a TTL “1,” indicating the
input power is OK, and allows the power output to come up 15-30 ms later. An auxiliary Vcc output of 5 VDC capable of sourcing up to 300mA is provided for peripheral use.
An output Inhibit/Enable function is provided by using an optocoupler to control Vicor’s DC -DC converters. If the Inhibit control pin is pulled low and the Enable pin is high or open, the optocoupler will turn on and disable the output. The delay for an output to come up when measured from release of the Enable pin is 5-10 ms.
Interface Connections
Input Power Terminal (J1)
Input AC (and DC) Power is applied to connector J1 using a 3W3 power connector. J1-A1 is Line (L1), J1-A2 is Line 2/Neutral (L2/N), and J1-A3 is Earth Ground (G) for safety.
A fault-clearing device, such as a fuse or circuit breaker, with a maximum 15A rating at the power supply input is required for safety agency compli­ance. It should be sized to handle the start-up inrush current of 30A at 115 VAC and 60A at 230 VAC.
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 5
Figure 1. Javelin Architecture
A1 A2 A3
J1 Pin Out
A1 Line 1 A2 Line 2/Neutral A3 Ground
Javelin I & II Power Supply Operator’s Manual
Output Power Connections
The output power terminals available on the Javelin are 5/16–18 studs with flanged nuts. The positive polarity of the output is the left stud when viewed from the output end. In order to minimize parasitic cable inductance and reduce EMI, the output power cables should be routed in close proximity to one another, and large current loops should be avoided. To avoid excessive voltage drop, do not undersize power cables, especially for high current outputs. Exces­sive cable inductance, coupled with large capacitive loading, can introduce instability in switching power supplies. This problem can be avoided with proper system design. Consult Mission Power So-
lutions’ Engineering Department for assistance with applications
Positive Return
that use long cable lengths and excessive load capacitance.
Signal Return (J2-4)
Signal Return on J2-4 is an isolated secondary ground reference for all J2 interfacing signals. This is not the same as Earth Ground on input power connector J1.
Inhibit/Enable (J2-7 to J2-8)
The Inhibit/Enable control pins allow the output to be controlled with either “inhibit” or “enable” logic. Con-
necting Inhibit (J2-8) and Enable (J2-7) to ground causes the Javelin to operate. With Inhibit (J2-8) open the Javelin will operate, and the Enable pin has no effect. Connecting Inhibit to ground and leaving Enable open will disable the output of the Javelin. Refer to Table 2 (Pg. 2).
AC OK (J2-6)
AC OK is an active high TTL-compatible signal and provides a status indication of the AC input power. It is on pin J2-6 and is capable of sinking 16 mA maximum. This signal switches to a TTL “1” when the high volt- age bus exceeds low-line condition during turn-on. Upon loss of input power, the bus voltage will drop, caus­ing the AC OK signal to go low. A minimum of 3 ms holdup time is provided for a 1200W load following the loss of the AC OK signal.
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 6
+5V
AC OK
2.5K
PN2222
J2-6 AC Power OK
J2-4 Signal Return
Figure 2. AC OK Output Circuit
Javelin I & II Power Supply Operator’s Manual
Auxiliary Vcc +5V/0.3A (J2-5)
The Vcc on J2-5 is an auxiliary 5V regulated power source. It is +5VDC 5% with respect to Signal Ground (J2-4 and J2-2) and can supply 300mA maximum. It is short-circuit proof, but if shorted, all outputs will be shut down through the Inhibit/Enable circuitry.
+5V/300mA J2-5 Auxiliary Vcc
78M05
0.1uF
J2-4 Signal Ground
J2-2 Signal Ground
Figure 3. Auxiliary Vcc Circuit
Remote Sense Connections
The Javelin is shipped from the factory with Auto-Sense installed. If Remote Sense is desired, sense leads must be connected from J3-1 (+Remote Sense) and J3-6 (−Remote Sense) to the load point where regulation is required.
When Auto-Sense is used, the power supply will regulate the output at the output terminals. The voltage ap­pearing at the load may drop slightly due to voltage drop in the power cables. If it is necessary to compensate for voltage drop along the output power cables, the output can be trimmed up or configured for Remote Sense. Use stranded, twisted pair 20-24 AWG wire for the Remote Sense lines. Remote Sense can compensate for a voltage drop of up to 0.5V, or 0.25V on each leg.
DC OK/DC OK′ (J3-8 and J3-2)
DC OK and DC OK′ are logic signals provided to indicate with either TTL logic “1” or “0” that the correct output voltage is available. DC OK (J3-8) is a logic “1” when output voltage is within specification and a logic “0” when output is out of tolerance. A logic “0” is capable of sinking 16 mA in either circuit. The inverse signal, DC OK′, is available at J3-2. The circuit is operated with a +5Vcc provided by either the customer or
taken from connector J2-5 (+5V Vcc) and J2-2 (+5V Return).
J3-3 +5V Vcc
4.99K J3-8 DC OK
J3-2 DC OK’
2N7002
J3-7 +5V Return
DC OK
4.99K
49.9K
2N7002
MOC217
Figure 4. DC OK Circuit
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 7
Javelin I & II Power Supply Operator’s Manual
Connecting Javelin I & II Power Supplies in Parallel
To connect up to three Javelin Power Supplies in parallel, connect PR1 (J3-9) to corresponding PR1(s) (J3-9) and PR2 (J3-4) to corresponding PR2(s) (J3-4). Use 20-24 AWG twisted pair, shielded hook-up cable with the shield connected to each unit’s chassis ground (J3-9). All units must use equivalent power sources, and all outputs must be connected to a common bus with equal impedance connections. Output voltage can be ad­justed on one power supply provided the other unit(s) is/are adjusted completely counterclockwise. If Remote Sense is used, all units must have a connection to the point of regulation using 20-24 AWG twisted pair wires.
Output Cables
Output Bus
Output Return Bus
Twisted Pair Remote Sense Wires
Shielded, Twisted Pair Paralleling Cable
AC/DC
Input
Power Supply 1
Power Supply 2
Power Supply 3
+
J3
+
J3
+
J3
Figure 5. Paralleling Javelin I and II Power Supplies
Mechanical Considerations
The Javelin can be mounted on either of two surfaces (top or bottom) using standard 8-32 size screws. Maxi­mum allowable torque is 20 in/lbs., and the maximum penetration is 0.21 (5,33mm).
When selecting a mounting location and orientation, the unit should be positioned so that airflow is not re­stricted. Maintain a 2 (50,8mm) minimum clearance at both ends of the Javelin, and route all cables so airflow is not obstructed. The power supply draws air in at the front side and exhausts air out the load/input side. If airflow ducting is used, avoid sharp turns that could create backpressure. The fan moves approximately 100 CFM of air.
Avoid excessive bending of output power cables after they are connected to the output terminals. For high­current outputs, use cable ties to support heavy cables and minimize mechanical stress on connectors. Be care­ful to not short out to neighboring outputs. The maximum torque recommended on output nuts is 130 in/lbs.
Javelin Do’s and Don’ts
Run the output (+/) power cables next to each other to minimize inductance. Insert proper fault protection at power supply input terminals (i.e., a fuse). Use proper size wires to avoid overheating and excessive voltage drop. Do not attempt to repair or modify the power supply in any manner. Do not restrict airflow to the unit. The cooling fan draws air into the front of the unit and forces it out at
the input/output terminal (rear) side. It is necessary to provide at least 100 CFM of cooling airflow for the Javelin II.
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 8
Javelin I & II Power Supply Operator’s Manual
Mechanical Drawing - Javelin I
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.co m Pg. 9
Javelin I & II Power Supply Operator’s Manual
Mechanical Drawing - Javelin II (page 1)
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.co m Pg. 10
Javelin I & II Power Supply Operator’s Manual
Mechanical Drawing - Javelin II (page 2)
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.co m Pg. 11
Javelin I & II Power Supply Operator’s Manual
Specifications
(Typical at 25C, nominal line and 75% load, unless otherwise specified)
General
Number of Outputs 1 Efficiency 75% Safety Approvals N/A MIL-STD’s 461E; 704E; 810E; 1399 Maximum Output Power 800W, >104 VAC
1200W, >160 VAC 1800W, >212 VAC (Selected Output Voltages)
Input
Input 85-254 VAC, 47-500Hz
85-380 VDC
Line Regulation 0.2% from 10% load to full load Inrush Current 30A rms. max. @ 115 VAC
60A rms. max. @ 230 VAC
Ride-Through Time 20 ms at 1200W load Conducted EMI FCC Class A, EN 55022 Class B
MIL-STD-461E Power Factor .99 (115 VAC 800W load) .95 (230 VAC 1200W load)
Transient Surge IEC 801-5 level 3 (Common Mode & Normal Mode) Dielectric Withstand Primary to Chassis GND = 2121 VDC
Primary to Secondary = 4242 VDC Secondary to Chassis GND = 500 VDC
Output
Parameter MIN. TYP. MAX. UNITS NOTES
Setpoint Accuracy
Load/Line Regulation
Temperature Regulation
Long Term Drift
Output Ripple – pp:
2V, 3.3V
5V
12-95V
Trim
Total Remote Sense Compensation
OVP Set Point
Current Limit
Over-Temperature Protection
90
0.5
112
102
85>TA<95
0.5 1
0.02 0.2
0.002 0.005
0.02
100
2
1
110 % of V
135 % of V
135 % of I max Automatic restart
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 12
% of V
NOM
% of V
NOM
%C 20 to 100C
%1K hours
mV 20 MHz bandwidth
% 20 MHz bandwidth
% 20 MHz bandwidth
NOM
Volts 0.25V max. each leg
NOM
0% to 100%
Recycle power
Varies according to power level
Environmental
Maximum Output Pow er vs. Input Voltage AC or DC
0
200
400
600
800
1000
1200
1400
1600
1800
2000
50 100 150 200 250
Minimum Input Voltage AC or DC
Maximum Output Pow er
Output Voltages > 10Vdc Output Voltages < 10 Vdc
Maximum Output Power vs. Temperature
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 20 40 60 80 100
TA max
Pout m ax
400W
600W
800W
1200W
1600W
1800W
Javelin I & II Power Supply Operator’s Manual
MIL-STD
Storage Temperature
C Grade
T Grade
H Grade
M Grade
Operating Temperature
C Grade, Full Power
C Grade, Half Power
T Grade, Full Power
T Grade, Half Power
H Grade, Full Power
H Grade, Half Power
M Grade, Full Power
M Grade, Half Power
Product Weight Dimensions 4.9 H (124,46mm) x 7.0 W (177,8mm) x 10.75 L (273,1mm)
Warranty
810E
40C to 125C
40C to 125C
55C to 125C
65C to +125C
20C to +55C
20C to +70C
40C to 55C
40C to 70C
40C to 55C
40C to 70C
55C to 55C
55C to 70C
11.50 lbs. (11.0 lbs. Javelin II)
[9.5 L (241,3mm) for Javelin II]
1 Year Limited
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 13
Graph 1. Maximum Output Power vs. Input Voltage
Javelin I & II Power Supply Operator’s Manual
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 20 40 60 80 100
Pout max
Temperature, Ambient (C)
Maximum Output Power vs. Temperature
400W
600W
800W
1200W
1600W
1800W
Graph 2. Maximum Output Power vs. Temperature
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 sales@mpwrs.com Pg. 14
Notes
Javelin I & II Power Supply Operator’s Manual