MGE UPS Systems ESV 11+Rack, ESV 8+Rack, ESV 14+Rack, ESV 22+Rack User Manual

user manual
Pulsar
ESV 8+
Rack
/ 11+
Rack
14+
Rack
/ 22+
Rack
+
+
!
%
%
1
2
www.mgeups.com
MGE UPS SYSTEMS
Pulsar ESV 8+
Rack
/11+
Rack
/14+
Rack
/22+
Rack
: 86-153523-00
Dear Customer, Thank you for your purchase of the Pulsar
UPS. It has been designed for many years of trouble-free operation. Please review this manual which has been prepared to provide you with information concerning the proper installation and operation of your Pulsar ESV
8+
Rack
/
11+
Rack
/14+
Rack
/22+
Rack
.
Please feel free to call us at our toll-free number on the last page should you require assistance.
Yours truly,
MGE UPS SYSTEMS
Federal Communications Commission (FCC) Statement
Note: this equipment has been tested and found to comply with Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when equip­ment is operated in a residential environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits.
Revision A00 ECN - 000071
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
3
MGE UPS SYSTEMS
safety rules
this equipment can be operated by any individual, with
no previous training;
the UPS contains voltages which are potentially
hazardous. ALL REPAIRS SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL;
attention: risk of electric shock, even with unit discon-
nected from utility power.Hazardous voltages are present even when operating on battery.
do not attempt to power the UPS from any recepta-
cle other than a 2-pole 3-wire grounded receptacle;
do not place Pulsar near water or in environment of
excessive humidity;
do not allow liquids or any foreign objects to get inside
Pulsar;
do not block air vents in front, in the back or on the
sides of Pulsar;
do not plug household appliances such as hair dryers
into Pulsar receptacles;
do not place Pulsar in direct sunlight or close to heat-
emitting sources;
the utility power outlet shall be near the equipment and
easily accessible.To isolate Pulsar from AC input, turn unit off and remove the plug from the utility power outlet;
if Pulsar is to be stored for a long time, it is recom-
mended to recharge the batteries (by connecting the utili­ty power to Pulsar, switch "ON" or "OFF"), once a month for 24 hours to avoid a full battery discharge;
Pulsar contains batteries that should be disposed of or
recycled in accordance with applicable laws;
prior to installation, store Pulsar in a dry location;
storage temperatures must be between: –4°F and
+113°F (-20°C and +45°C);
when replacing the batteries, use the same number
and the following type of batteries: 6V/12Ah, 12V/7.2Ah;
do not incinerate batteries, they may explode;
do not open or mutilate the battery or batteries,
released electrolyte is harmful to the skin and eyes;
a battery can present a r isk of electric shock and high
short circuit current. The following precautions should be observed when working with batteries:
remove watches, rings or other metal objects,
use tools with insulated handles;
please dispose of the packaging in accordance with
applicable laws.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
4
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
5
general contents
discover Pulsar .......................................................................................................................................... 6
illustrations and features key diagram
introduction / getting started/ operation ............................................................................................................ 11
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
6
front view of ESV 8+
Rack
/11+
Rack
/14+
Rack
/22+
Rack
rear view of ESV11+
Rack
/14+
Rack
2
3 1g 1f
1e
%
+
%
2
1
+
!
1a 1b 1c
1d
12
7
7a
1
MGE UPS SYSTEMS, Inc.
2
Vac IN
10
17
15
6
9
5
7b
8
MGE UPS SYSTEM
1660 SCENIC AVENUE
COSTA MESA CA 92626
16
11
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
7
rear view of ESV8+
Rack
1
2
MGE UPS SYSTEMS, Inc.
T 10A/125V
I max 6.5A
Vac OUT
Vac IN
9
7
5
7a
7b
17
10
15
16
12
The indispensable companion sofware for your UPS
L'indispensable complément logiciel de votre onduleur
solution-pac
13
14
T 10A/125V
4
Ue/In/Eing
6a
6b
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
8
rear view of ESV22+
Rack
key to diagrams page 6 to 8
1a yellow indicator light flashing quickly only: bat-
tery fault,
1b yellow indicator light flashing quickly only:
device fault,
1c yellow indicator light flashing quickly only:
overload,
1d yellow indicator light flashing quickly only:
operating on "booster" or "fader" mode,
1e yellow indicator light flashing quickly only:
plug 2 not powered,
1f yellow indicator light flashing quickly only:
plug 1 not powered,
1g green indicator light on continuously: operating
on utility, green indicator light flashing: batter y back-up time,
2
1
MGE UPS SYSTEMS, Inc.
15A / 125V
Vac OUT
Vac IN
30A / 250V
I max 18.3A
15
9
7
10
17
16
56
12
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
9
7 output receptacles for connection of comput-
er equipments to Pulsar ESV+
Rack
(2 for ESV 8+) with output switchable recep­tacles 7a and 7b by Solution-Pac,
8 power cords for connection of computer
equipment to Pulsar ESV+
Rack
(not includ-
ed),
9 SUB-D 9 pins connectors communication
port,
10 identification plate, 11 warranty card, 12 network protection, RJ45 connector, 13 Solution-Pac CD-ROM, 14 serial cable for communication with a PC, 15 cover for optional communication cards,
key to diagrams page 6 to 8
2 "function" button: switches off audio warning
device or measures load charge percentage (with utility power),
3 "ON/OFF" switch, 4 utility input receptacle, 5 utility power connection (use computer cord
only for ESV 8+
Rack
),
6 15A, circuit protector for Pulsar ESV 11+
Rack
20A, circuit protector for Pulsar ESV 14+
Rack
30A, circuit protector for Pulsar ESV 22+
Rack
6a 10A, delayed fuse for Pulsar ESV 8+
Rack
,
6b fuse holder,
16 Fan 17 Site wiring fault
NB:
Indicator lights 1c à 1f indicate the charge level of the battery (if utility power present) or the remaining battery backup time (without utility power). By pressing the button marked "function" 2 when utility power is present, they indicate the level of load charge.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
10
software supplied with Pulsar ESV+
Rack
To meet the different operating environments of your UPS, Pulsar ESV+
Rack
includes 2 MGE UPS SYS-
TEMS software programs:
ESV-Driver software for Windows;
Network based Solution-Pac™ power management
software.
ESV-Driver for Windows
ESV-Driver for Windows provides communication with the UPS from a simple Windows workstation.ESV-Driver is compatible with Windows 3.1x and Windows 95/98, for communication with the UPS via a serial connection for various needs:
personalization of the UPS operating mode: the
ESV-Tuner utility, can be used to change cer tain UPS operating parameters if the standard factory settings are not ideal for the operating conditions.
It is possible to modify the output voltage, battery-test fre­quency, startup and shutdown sequences, etc.;
Solution-PacTM for networks and multi-server systems
Protection by UPS is only complete and effective if com­bined with powerful software functions which warn users and the operator of any power supply problem, automate system shutdown, supervise and remotely control the UPSs. MGE UPS SYSTEMS created Solution-PacTM for this purpose. Solution-PacTM combines all these func­tions in a single CD-ROM, usable in local or remote mode (TCP/IP and SNMP), and covering the main net­work environments. Solution-PacTM is the ideal solution for protecting net­works and multiserver systems. Solution-PacTM on a single CD-ROM contains ever ything needed to safeguard one or more systems and to super­vise one or more UPSs from a local or remote station. Solution-PacTM includes SNMP proxy agents, system shutdown software, and supervision software.
Solution-PacTM is a powerful and upgradable software tool which provides all the supervision, control and safety functions associated with a UPS:
graphic display of the UPS,
remote control of the UPS and output receptacles,
user alarm of problems,
recording of events in log files,
automatic system shutdown and restart,
local or remote supervision of UPSs and ancillar y
devices,
transmission of UPS information and alarms to any
SNMP supervisor.
paging / e-mail capabilities
multiple server shutdown in heterogeneous environ-
ment.
Platforms supported:
Windows 3.1, 95, 98, NT, Novelle Netware, OS/2, Linux, Mac/OS, Sun Solaris, HP/UX, IBM Aix, Dec Unix and Open VMS, Silicon Graphics, IRIX.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
11
introduction ......................................................................................................................12
benefits ......................................................................................................................................12
options........................................................................................................................................12
getting started ..................................................................................................................13
installation..................................................................................................................................13
preliminary checks ....................................................................................................................13
connections................................................................................................................................13
power connections ................................................................................................................13
serial connections ..................................................................................................................13
computer network protection..................................................................................................13
communication ..........................................................................................................................14
operation ............................................................................................................................15
starting up with utility power ......................................................................................................15
starting up without utility power..................................................................................................16
normal operation........................................................................................................................17
operation with battery backup time............................................................................................18
overload......................................................................................................................................19
operating anomalies ..................................................................................................................19
battery replacement ..................................................................................................................20
technical data ............................................................................................................................21
contents
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
12
introduction of Pulsar UPS
benefits
Network servers and data are very sensitive to electrical disturbances of all types including out­ages, brownout, voltage sags, interference, etc. The origins of disturbances also vary, ranging from atmospheric phenomena such as lightning or frost, to near-by devices generating interference such as elevators, copiers and machine-tools, not to men­tion human errors such as the accidental pulling out of power cords or tripping of circuit breakers. The consequences of disturbances on computer systems range from damage to hardware (power supplies, hard disks) to the loss of data.
Pulsar ESV+
Rack
has been specially designed to protect network servers and all other connected devices that are sensitive to electrical distur­bances. Pulsar ESV+
Rack
adds fault-tolerance to
the power source supplying your server.
Pulsar ESV+
Rack
is designed as a compact unit that silently protects your electrical devices. Because of its backup battery, Pulsar ESV+
Rack
protects your system for several minutes (see the "characteristics" section) in the event of a power failure.A built-in filtering system protects connect­ed devices from line interference.Finally, to counter voltage sags or spikes, Pulsar ESV+
Rack
uses voltage compensation circuits ("booster" and "fader" modes) to guarantee a stable supply of clean power. As standard, Pulsar ESV+
Rack
offers the PowerShare function that was previously available only on large UPSs. Power outputs may be remotely controlled, thus making possible sequen­tial start-ups of various devices, selective load shedding in the event of an overload and priority management near the end of battery power to pro­tect the most sensitive load.
options
UM Sensor environment measurement unit:
compatible with SNMP or Solution PacTM, this unit measures the temperature and the relative humidity in the room where the Pulsar is installed. Eight relay contacts are provided to transmit sig­nals to an administration platform, in the form of voltage free contacts to enable monitoring of (fire alarm, climate control fault, intrusion, etc.);
additional communications options:
SNMP administration: MGE has the most com-
plete offering for the administration of a group of UPSs using the SNMP protocol with different net­work-connection modules (SNMP card or proxy software), supervision modules (application for NMS platforms such as HP OpenView or C.A. UNICENTER TNG) and a file-closing module (UM Client).
SNMP card: this card, inser ted into your UPS,
can establish a direct Ethernet network connection for your UPS. It can then be temporarily managed using SNMP or the various software modules of Solution-Pac. The MGE UPS SYSTEMS offering complies with RFC 1628 specifications (IETF) and was certified by the InterWorking Labs during the Test Summit in June 1994;
status information card: this option provides
you with 3 data elements on voltage-free contacts: operating on battery, low battery warning, operat­ing on utility power. This card can be used with the UPS driver of IBM AS/400.
Contact your reseller for further information on these options.
(*) CD-ROM :EMB/ESVPLUS/CONFIG
Pulsar ESV+
Rack
offers a number of functions and characteristics intended to simplify power management:
automatic batter y test carr ied out per iodically. In
the event of a fault, a LED provides enough advance warning for battery replacement;
LEDs on the front signalling all types of faults
and alarms;
bar graph continuously indicating the battery
charge level or the computer-application load level;
environment friendly: all components are recy-
clable and an electronic power-saver device reduces consumption if the UPS is not active for a period exceeding five minutes;
Pulsar ESV+
Rack
incluses user-replaceable batteries, no need to power off connected equip­ments to replace them;
ESV Dr iver software is part of our CD-ROM
(*).
It lets you edit the default parameters of Pulsar to ideally match your requirements;
Pusar ESV+
Rack
is Plug and Play: its installa-
tion on Windows 95/98 is fully automatic;
advanced operation and monitoring of Pulsar
are achieved by means of the Solution-Pac CD-ROM included in your package. To learn more about all the advanced features offered (system shutdown, remote monitoring, SNMP administra­tion,…) please view the navigator tool of the CD­ROM;
networ k protection is built-in to ensure safe data
transmission.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
13
Vac IN
mains outlet
5
Network Protection
IN
OUT
1
2
MGE UPS SYSTEMS, Inc.
7b
7a
7
8
getting started
installation
observe the safety rules indicated at the beginning of this document.
preliminary checks
check that button 3 ""on the front is not pushed in;
check that rating shown on identification plate 10 corresponds to the input volt­age specification and power requirement of the load.
connections
power connections:
use the UPS input cord to supply input
power to Pulsar as shown.
serial connections:
If you wish to use the functions of the CD-ROM supplied with your Pulsar, con­nect one end of the supplied serial cable
14 to the communication por t 9 . Connect the other end to a serial port of a computer system.
computer network protection:
If you wish to use the network line filtering functions (Ethernet for example), use a cable of the RJ45 type.Connect the "IN" output to the network and use another cable to connect the "OUT" output to the protect­ed computer system.
Connect the UPS input cord 5 to a near­by power outlet. For the ESV8+
Rack
, the input cord is not attached to the UPS. Connect the input cord to the UPS input recepticle 4 , as shown on page 7, and to a nearby power outlet.
use included IEC cords 8 to connect
the computer loads to output sockets 7 , 7a and 7b .
Note 1:
Following connection, the battery automatical­ly charges, regardless of the position of the ON/OFF button 3 "" .
Note 2:
The batteries will provide full back-up time after approximately 8 hours of recharge time.
Note 3:
The rating of the input power cord must not be less than the nominal input rating of Pulsar.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
14
option 1
status information card: after the card is installed in the rear of the Pulsar, communi­cation port 15 transmits status information on a SUB-D 9-pin female connector using the following pinouts:
1- ground, 4- nor mal operation, 5- common, 7- low batter y warning, 9- operation on batter y.
communication
The communication port 9 , at the rear of Pulsar, delivers information in the form of
an RS232 serial link supported by the com­munication protocol exclusive to MGE UPS SYSTEMS.The Solution-Pac programs use the data made available by this protocol.
1 - ground 2 - TD 3 - RD 5 - common
With the ESV Driver software program you can set up Pulsar ESV+
Rack
to suit your user conditions (ESV Tuner). To install ESV Driver, connect the serial cable supplied to COM1 to COM4 (set up by ESV Tuner) seri­al port of your computer equipped with Windows 3.1 or 95/98 on the one end, and to the serial Pulsar ESV+
Rack
connector
on the other end. ESV Driver software (included in the
CD-ROM: EMB/ESVPLUS/CONFIG) lets you edit the default parameter of Pulsar:
battery test frequency (default: ever y week);
nominal output voltage (default: 120 Volts);
high/low voltage thresholds (default: 138/92 Volts);
Relay breaking capacity:
Vmax = 25V DC, Imax = 10mA
n.o. : normally open, n.c. : normally closed.
option 2
SNMP card: after the card is installed in the rear of the Pulsar, communication port 15 transmits information supported by the TCP/IP and SNMP protocols on an RJ45 connector to any ethernet network. Contact your sales agent for further details.
Fader/Booster activation thresholds (default : 102/128 Volts);
on/off conditions:
automatic restart,
forced reboot,
energy saving,
cold start.
0V
I
V
RD TD
5432
9876
1
9
0V
54321
9876
n.c.
n.o.
0V 0V
15
n.o.
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
15
operation
starting up with utility power present
12s6s4s0 s
several beeps
all your devices are powered by utility power
1 s beep
Your protected devices are not powered
your protected devices are not powered
normal operation
indicator lights and audio warning device test
press button "on/off" :
press button 3 (>1 sec.)
automatic sequence:
your main devices are supported by the battery. Output receptacles 1 and 2 are not powered
battery test
indicating the recharge percentage of the battery (100, 75, 50, 25%): here > at 50%
silence
1 beep every second
9s
your main devices are supported by the battery. Output receptacle 2 is not powered
battery test
1 beep every second
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
16
starting up without utility power
press button 3 (>1 sec.)
automatic sequence:
1 s beep
Your protected devices are not powered
indicator lights and audio warning device test
several beeps
your protected devices are not powered
battery test
3s beep
your main devices are supported by the battery. Output receptacles 1 and 2 are not powered
battery test
9s
1 beep every second
your main devices and output receptacle 1 are supported by the battery. Output receptacle 2 is not powered
normal operation with battery autonomy
12s6s4s0 s
indicating the remaining autonomy percentage (<100, 75, 50, 25%): here < 50%
1 beep every 10 s
all your devices are powered by the battery
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
17
(*)
(*)
128V
102V
92 Volts
138 Volts
max
rated
min
rated
mini (**)
input voltage variation range
output voltage variation range
"booster" mode in operation
"fader" mode in operation
maxi
(*) outside the min.-max. range indicated, Pulsar runs in battery backup (**) standard setting
normal operation
without utility power
with utility power
the "fader" and "booster" functions are used to keep the output voltage range (Umax-Umin) compatible with the supply operating range of your application;
this operating range can be configured via the "ESV Driver" software (included in your CD-ROM);
on operation in the "fader" or "booster" range, the indicator light
1d
begins
flashing.
your devices are powered by the utility power
indicating the recharge percentage of the battery (< 100, 75, 50, 25%): shown > 50%
indicating the remaining autonomy percentage (< 100, 75, 50, 25%): shown < 50%
your devices are powered by the battery
(**)
1 beep every 10 s
silence
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
18
operation with battery back up time
no utility power
return of utility power
indicating the battery recharge per­centage: shown, between 0 and 25%
load charge percentage
your load is supplied by the utility power
indicating the load charge percentage: shown, between 25 and 50%
If utility power present, press button 2 :
At whatever point the utility power returns, Pulsar switches to normal operation:
Note:
Button 2 is to disable or activate the audible alarm device when operating on battery.
silence
silence
power failure
indicating the remaining autonomy time: here, between 75 and 50%
1 beep every 10 s
your load is powered by the battery
low battery warning
x min 5 min0 min
discontinue use of load, battery is near exhaustion
Pulsar switches off automatically
x + ε min
1 beep every 3 s
your load is no longer powered
silence silence
if Pulsar is operating off load: device switches off (*)
your load is no longer powered
(*)
configuration via ESV Driver
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
19
overload
utility power present
operating anomalies
device fault
battery fault
Pulsar switches off automatically after operating in overload for approximately 5 min.
no utility power present
Pulsar switches off automatically after a length of time which depends on the level of overload.
NOTE:
Overload occurs if the electricity consumption of the load connected is greater than the rated power of Pulsar. To acknowledge the fault, push button 3 , temporarily disconnected Pulsar from the wall socket 5 , disconnect non-priority loads and re-start Pulsar.
switch off Pulsar (push button 3 ), dis-
connect from the wall socket (flex 5 ), and check that Pulsar has not short-circuited (dis­connect all applications),
check the input fuse
6b
and replace it with a fuse of the same rating or reset ther­mal breaker 6 ,
re-start Pulsar.
A battery test is carried out while Pulsar, is in start-up phase, then automatically every 7 days (overhaul times adjustable using ESV Driver). If a battery fault is detected, the following occurs:
recharge your battery for 8 hours. If battery fault persists, see next page.
utility power outside limits
continuous beep
after the start-up sequence, if the audio warning device sounds continuously, check
the voltage and frequency of your utility power (see the § entitled "characteristics") and/or recharge your battery for 8 hours.
Start/Stop control on output receptacles 1 and 2 (PowerShare)
You can use the applications included on the CD-ROM to remote control the Start/Stop sequences on output receptacles
7a
(or 7b). If 7a(or 7b) is disabled
through software, front panel led
1f
(or 1e) flashes, with 1 beep every second. Beep can be deactivated by "function" button 2 .
NOTE:
If the previous symptoms persist, contact our after sales department.
1 beep every second
1 beep every second
1 beep every second
1 beep every second
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
20
battery replacement ESV8+
Rack
/ 11+
Rack
/
14+
Rack
/22+
Rack
see important battery safety rules (see page i);
batteries can be replaced without risk, but don't hesitate to contact our after sales department to confirm batter y failure, and to give you further information;
battery replacement can be performed with UPS on utility power, but we recommend you to switch off the unit in order to avoid any data loss;
use a screwdriver to remove the cover on the right side of the UPS ESV+
Rack
;
use a screwdriver to remove horizontal metal plate holding the batteries.
For ESV22+
Rack
remove terminal before
removing the battery.
pull out battery block using tapes on the sides;
disconnect battery wires red (+) and black (-) from the UPS on battery terminals;
replace all batteries with new batteries, same voltage and same rating (Volts, Ah), then connect battery wires again (sparks may occur during connection);
push battery block back in, screw metal front panel on, then click plastic front panel into place and secure the plastic plate with screws.
+
+
!
%
%
1
2
+
+
!
%
%
1
2
+
+
!
%
%
1
2
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
21
technical data
output power:
Pulsar ESV 8+
Rack
: 780VA/490W Pulsar ESV 14+
Rack
: 1400VA/980W
Pulsar ESV 11+
Rack
1080VA/700W Pulsar ESV 22+
Rack
: 2200VA/1540W
utility power source:
voltage (V): 92V to 138V single phase (*)
frequency (F): 47Hz to 53Hz or 57Hz to 63Hz
battery: Pulsar ESV 8+
Rack
: 2 x 12V - 7.2Ah
type: Pulsar ESV 11+
Rack
: 3 x 12V - 7.2Ah
Pulsar ESV 14+
Rack
: 4 x 12V - 7.2Ah
Pulsar ESV 22+
Rack
: 8 x 6V - 12Ah
maintenance free sealed lead-acid
caution: battery life (4 or 5 years) is halved every 10°C above 25°C
output specifications with load on battery:
voltage (V): single phase 120V ±5% (**)
frequency (F): 50Hz/60Hz ± .1Hz auto selection
output specifications with load on utility power:
voltage (V): see "normal operation with utility power present"
frequency (F): 47Hz to 53Hz or 57Hz to 63Hz
environment:
noise level: 40dBA for operation on utility power
45dBA for battery backup time
operating temperature: 0 to 35°C
relative humidity: 0 to 90%
non condensing
dimensions and weights: Pulsar ESV 8+
Rack
/ 11+
Rack
/ 14+
Rack
Pulsar ESV 22+
Rack
height H (mm/inch): 133.35/5.25 177.8/7
width W (mm/inch): 482.6/19 482.6/19
depth D (mm/inch): 457.2/18 457.2/18
weight (kg/lb) : 25/29/31 (kg) 55/64/68 (lbs) 44/97
(*): adjustable high and low thresholds using ESV Driver (CD-ROM: EMB/ESVPLUS/CONFIG) (**): can be adjusted from 100 to 127V using ESV Dr iver (CD-ROM: EMB/ESVPLUS/CONFIG)
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
22
technical data (continued)
Pulsar ESV 8+
Rack
battery back-up time
Pulsar ESV 11+
Rack
/14+
Rack
battery
back-up time
Pulsar ESV 22+
Rack
battery back-up time
t (mn)
0
2 tower servers
desktop server
tower server + external mass storage
tower server + 12 port Hub
tower server
10 15 20 25 30 35 45405
ESV11+
Rack
ESV14+
Rack
2 desktop servers
tower server + 12 port Hub
4 stack Hub
tower server
desktop server
025
2015105
t (mn)
20 40 60 80 100 120 140
0
2 tower servers + external mass storage
tower server + external mass storage system
tower server + Hub
high end modular Hub
t (mn)
MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack : 86-153523-00
23
North American warranty
MGE UPS Systems warrants that products furnished hereunder shall be free of defects in material and workmanship for a period of two (2) years from date of purchase. Upon notice of any such defect, MGE UPS Systems shall, at its option, repair or replace the defective product at no cost to the buyer.
Proven defective units will be replaced with new or re-certified units, at MGE’s sole option. Replacement units will be reshipped within five working days of receipt of defective units at MGE’s Costa Mesa facility. Replacement units will carry the balance of
original two (2) year warranty, or 90 days, whichever is greater.
Customer must first obtain a Return Material Authorization number (RMA#) from MGE’s Sales Administration department.The RMA# must be clearly printed on the outside of each box when returned.The RMA# and serial number(s) of the returned units must appear on the return shipping documents. Call MGE for shipping boxes if necessar y.
Freight:All products retur ned shall be shipped to MGE UPS Systems, Costa Mesa facility, freight and shipping charges prepaid.
This warranty constitutes the sole and exclusive remedy of any buyer of MGE UPS Systems equipment and the sole and exclu­sive liability of MGE in connection with the products and is in lieu of all other warranties, expressed, implied or statutory, including but not limited to, any implied warranty of mer­chantability of fitness.
Norway :800 11 221 United Kingdom : 0800 96 8558 South-East Asia (Singapore) : (65) 288 43 23 Spain : 900 99 3384 Sweden : 020 795 475 Switzerland : 155 1107 Other countries : (33) (0)4 76 33 91 36
As standard, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Product names mentioned herein may be trademarks and registered trademarks of their respective companies.
Published by MGE UPS SYSTEMS 02/99
Austria : 0660 6215 Belgium : 0800 7 2189 China/Hong Kong : (852) 2 811 2399 Denmark : 8001 0137 France :0800 33 68 58 Germany : 0130 81 9431 Italy : 1678 700 98 Netherlands : 06022 3057 North America : 1 800 438 7373
Version Info.: 86-153523-00 02/99
MGE UPS SYSTEMS INC
1660 Scenic Avenue Costa Mesa, CA 92626 800-523-0142
MGE UPS SYSTEMS INC
1660 Scenic Avenue Costa Mesa, CA 92626 800-523-0142
Loading...