MGE UPS Systems 9 kVA, 4.5 kVA, 12 kVA, 6 kVA User Manual

www.mgeups.com
Comet EXtreme
Comet EXtreme
4.5/6/9/12 kVA
4,5/6/9/12 kVA
MGE UPS SYSTEMS
Comet EXtreme
Installation and user manual
R
E
D
I
V
O
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
E
T
N
I
N
U
E
H
T
51033212EN/AC - Page 1
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Comet EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Comet EXtreme a reference in environmental protection include:
Production in an ISO 14001 certified factory; Recycling of Comet EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Comet EXtreme range:
We invite you to visit our Web site at www.mgeups.com
(page: www.mgeups.com/products/pdt230/smallups/extreme/extrem10.htm),
Or contact your MGE UPS SYSTEMS representative.
Page 2 - 51033212EN/AC
Using this document
Information may be found primarily by consulting:
the contents, the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
Foreword
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
51033212EN/AC - Page 3
Contents
1. Presentation
1.1 Comet EXtreme range .................................................................................................................. 6
4.5 and 6 kVA tower models ........................................................................................................... 6
4.5 and 6 kVA rack models ............................................................................................................. 6
9 and 12 kVA tower models ............................................................................................................ 7
9 and 12 kVA rack models .............................................................................................................. 7
1.2 Back ............................................................................................................................................... 8
Comet EXtreme 4.5 and 6 kVA ...................................................................................................... 8
Comet EXtreme 9 and 12 kVA ....................................................................................................... 8
1.3 Options .......................................................................................................................................... 9
EPO (Emergency Power Off) .......................................................................................................... 9
Transformer for galvanic isolation or earthing arrangement change .............................................. 9
Battery extensions for UPS backup times of 80 minutes ................................................................ 9
CLA module (Long backup time charger) for backup times of 2 to 8 hours .................................. 10
1.4 Control panel ............................................................................................................................... 11
2. Installation
2.1 Unpacking and checks ............................................................................................................... 12
Comet EXtreme 4.5 and 6 kVA .................................................................................................... 12
Comet EXtreme 9 and 12 kVA ..................................................................................................... 13
2.2 Installation of the rack version .................................................................................................. 14
2.3 Battery-module connections ..................................................................................................... 15
Comet EXtreme 4.5 and 6 kVA .................................................................................................... 15
Comet EXtreme 9 and 12 kVA ..................................................................................................... 15
2.4 Connection to the RS 232 communications port (optional) ................................................... 16
2.5 Installation of the communications-card option ...................................................................... 16
2.6 Connection to the connection modules ................................................................................... 17
Page 4 - 51033212EN/AC
3. Operation
3.1 ON LINE operating mode ........................................................................................................... 18
3.2 Start-up ........................................................................................................................................ 19
3.3 Bargraph indications .................................................................................................................. 19
Contents
3.4 Failure of AC input power and operation on battery power.................................................... 20
Transfer to battery power .............................................................................................................. 20
Threshold for the low-battery shutdown warning .......................................................................... 20
End of backup time ....................................................................................................................... 20
Sleep mode ................................................................................................................................... 20
Return of AC input power.............................................................................................................. 20
3.5 Personalization ........................................................................................................................... 21
Function ........................................................................................................................................ 21
"ON / OFF conditions" tab............................................................................................................. 21
"Battery" tab .................................................................................................................................. 22
"Output" tab................................................................................................................................... 22
"By-pass" tab ................................................................................................................................ 22
3.6 Shutdown..................................................................................................................................... 23
Shutdown of connected equipment............................................................................................... 23
Complete shutdown of the UPS .................................................................................................... 23
4. Maintenance
4.1 Troubleshooting.......................................................................................................................... 24
4.2 Replacement of the electronic module ..................................................................................... 26
Disconnecting the connection module .......................................................................................... 26
Reconnecting the connection module ........................................................................................... 27
5. Environment .....................................................................................................................................28
6. Appendices
6.1 Glossary....................................................................................................................................... 29
6.2 Index............................................................................................................................................. 31
51033212EN/AC - Page 5
1. Presentation
1.1 Comet EXtreme range
4.5 and 6 kVA tower models
Electronic module
Battery module
Dimensions in mm
(H x W x D)
443 x 173 x 465 443 x 173 x 465
Weight in kg
4.5 and 6 kVA rack models
Electronic module
Battery module
Electronic module
Battery module
Electronic module
Battery module
14 48
Dimensions in mm
(H x W x D)
177 (4U) x 483 x 462 177 (4U) x 483 x 462
Weight in kg
18 51
Page 6 - 51033212EN/AC
9 and 12 kVA tower models
1. Presentation
Dimensions in mm
(H x W x D)
Electronic module
Battery module
443 x 216 x 465 443 x 173 x 465
Weight in kg
9 and 12 kVA rack models
Electronic module
Battery module
Electronic module
Battery module
Electronic module
Battery module
22 48
Dimensions in mm
(H x W x D)
221 (5U) x 483 x 462 177 (4U) x 483 x 462
Weight in kg
27 51
51033212EN/AC - Page 7
1. Presentation
1.2 Back
Comet EXtreme 4.5 and 6 kVA
1
RS232 communications port.
2
Battery circuit breaker.
3
Communications-card option.
4
EXB battery module connectors.
5
Connector for battery extension modules.
6
Rating plate.
7
Manual by-pass switch.
8
Connection module.
9
Output terminal block.
10
Input terminal block.
Comet EXtreme 9 and 12 kVA
Page 8 - 51033212EN/AC
EXB battery modules connectors.
4
1. Presentation
1.3 Options
EPO (Emergency Power Off)
Available for both tower and rack versions of UPSs with standard backup times and for the battery extensions, the EPO (Emergency Power Off) option lets you simultaneously switch off the UPS battery circuit breaker and the upstream circuit breaker of your installation by connecting both of them to a single emergency off button (not supplied). For more details, visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/epo.htm
Transformer for galvanic isolation or earthing arrangement change
Nominal power Nominal current Input voltage Voltage drop Frequency Isolation (EN 61558-1-2-4) Operating temperature Max. operating rel. humidity Derating / altitude Natural ventilation Dimensions HxWxD (tower) Dimensions HxWxD (rack 4U) Weight (tower) Weight (rack)
Important: to simplify installation, connect the Comet EXtreme Transformer downsteam of the UPSs. Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm
Battery extensions for UPS backup times of 80 minutes
Battery extensions for 4.5 or 6 kVA Comet EXtreme:
Comet EXtreme
4.5 / 6 kVA
Comet
EXtreme
EXB
+++
4.5 /
6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA
Comet EXtreme Transfo 4.5 - 6 kVA
6 kVA 32 A 230V (+15%, -20%)
2.2% 50/60 Hz (+/-10%)
3.75 kV / 5 M ohms From 0° to +40°C 95% Pn-10% > 1000 m IP20 ANAN 443 x 173 x 465 mm 177 x 483 x 462 mm 44 kg 48 kg
Comet EXtreme Transfo 9 - 12 kVA
12 kVA 63 A 230V (+15%, -20%)
1.7% 50/60 Hz (+/-10%)
3.75 kV / 5 M ohms From 0° to +40°C 95% Pn-10% > 1000 m IP20 ANAN 443 x 216 x 465 mm 177 x 483 x 462 mm 62 kg 67 kg
Comet EXtreme offers a standard backup time of 9/12 minutes. To increase backup time, it is possible to connect Comet EXtreme EXB modules to the UPSs. Visit our Web site: www.mgeups.com/
products/pdt230/smallups/extreme/ guide.htm.
4.5 kVA: 6 kVA:
12 min
9 min
30 min 23 min
54 min 40 min
80 min 75 min
51033212EN/AC - Page 9
1. Presentation
Battery extensions for 9 or 12 kVA Comet EXtreme:
Comet EXtreme
9 kVA: 12 kVA:
9 / 12 kVA
Comet
+++
12 min
9 min
EXtreme
EXB
9 / 12 kVA
30 min 23 min
Comet
EXtreme
EXB
9 / 12 kVA
45 min 40 min
Comet
EXtreme
EXB
9 / 12 kVA
The Comet EXtreme EXB modules are available in "tower" and in "rack" models. The Comet EXtreme EXB modules come with their connection cables.
CLA module (Long backup time charger) for backup times of 2 to 8 hours
Very long backup times, from 2 to 8 hours at full load, require a Comet EXtreme CLA module. Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/cla/cla2.htm.
Comet EXtreme
12V-65Ah
A
5
2
Comet
EXtreme
EXB
9 / 12 kVA
80 min 75 min
Page 10 - 51033212EN/AC
Comet EXtreme CLA
1
12V-65Ah
2
12V-65Ah
2 h
19
12V-65Ah
20
12V-65Ah
1
12V-65Ah
12V-65Ah
2
12V-65Ah
12V-65Ah
4 h
19
12V-65Ah
12V-65Ah
20
12V-65Ah
12V-65Ah
1
12V-65Ah
12V-65Ah
2
12V-65Ah
12V-65Ah
12V-65Ah
12V-65Ah
19
12V-65Ah
8 h
12V-65Ah
20
12V-65Ah
12V-65Ah
12V-65Ah
12V-65Ah
1.4 Control panel
1. Presentation
bypass
bypass
Alarms
% battery
remaining
11
UPS overload
12
Electronics fault
13
Battery fault
14
Ambient temp. > 40°C
15
Hold down to display percent load.
16
Lamp test or buzzer OFF.
17
Operation on manual bypass.
18
Operation on automatic bypass.
19
Operation in ON-LINE mode.
20
Operation on battery power.
21
ON/OFF.
100%
80%
50%
20%
% load
100%
80%
50%
20%
51033212EN/AC - Page 11
2. Installation
2.1 Unpacking and checks
Comet EXtreme 4.5 and 6 kVA
Electronic module
23 24 2522
Page 12 - 51033212EN/AC
battery module
RS 232 communications cable.
22
CD ROM with "Solution Pac" and
23
"UPS Driver" softwares.
24
Quick Start documentation.
22
26
24
25
25
26
Installation and user manual.
25
Telescopic rails for mounting in 19" bay with mounting hardware.
26
27
Cable for connection to battery module.
23
25
27
27
Comet EXtreme 9 and 12 kVA
Electronic module
2. Installation
Battery module
22
25
26
23
27
24
22
24
25
23
25
27
25
RS 232 communications cable.
22
CD ROM with "Solution Pac" and
23
"UPS Driver" softwares.
24
Quick Start documentation.
26
Installation and user manual.
25
Telescopic rails for mounting in 19" bay with mounting hardware.
26
Cable for connection to battery module.
27
27
51033212EN/AC - Page 13
27
2. Installation
2.2 Installation of the rack version
Rack mounting diagram with rails
1
3
3
3
3
2
The rails and the necessary mounting hardware are supplied with the UPS in the package.
4
Page 14 - 51033212EN/AC
2.3 Battery-module connections
Comet EXtreme 4.5 and 6 kVA
2. Installation
Check that the battery circuit breaker is OFF.
Comet EXtreme 9 and 12 kVA
Check that the battery circuit breaker is OFF.
2
Connect cable to the connectors of the electronic and
2
4
27
battery modules.
2
Connect cable to the connectors of the electronic and
2
battery modules.
4
27
4
427
27
4
51033212EN/AC - Page 15
2. Installation
2.4 Connection to the RS 232 communications port (optional)
1
1. Connect the RS 232 communications cable to the serial port on the computer.
22
OV
5 4 3 2 1
9 8 7 6
2. Connect the RS 232 communications cable to the RS 232 communications port on the UPS.
The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.
Pin-out diagram for the RS 232 communications port on the UPS.
RD TD
RTS
1
2.5 Installation of the communications-card option
22
22
1
Page 16 - 51033212EN/AC
3
Slots for communications card.
It is not necessary to shut down the UPS to install the communications card:
1. Remove the slot cover .
2. Insert the card in the slot.
3. Secure the card with the two screws.
3
2.6 Connection to the connection modules
This type of connection must be carried out by qualified electrical personnel.
2. Installation
Before carrying out any connections, check that the battery circuit breaker is OFF
2
and that the upstream protection devices ( AC-power source) are open (OFF).
The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.
Comet EXtreme 4,5 to 6 kVA
Cable diameter
29
28
Cross-sectional area of each wire
Flexible wire Rigid wire
Recommended upstream circuit breaker
Nominal rating
(47 to 63Hz, 230V)
Maximum rating
(47 to 63Hz, 187V)
1. Remove the terminal-block cover .
15 to 25.5 mm 15 to 25.5 mm
4 to 10 mm
4 to 16 mm
C60N 32A 2P (maximum line current = 26A)
C60N 40A 2P (maximum line current = 32A)
2
2
28
2. Remove the cable entry knockouts from the cover.
3. Loosen the cable clamp .
9
4. Insert the cable supplying the equipment and the power cable through the terminal-block cover .
10
29
28
Comet EXtreme 9 to 12 kVA
2
10 mm 10 to 16 mm
C60N 63A 2P (maximum line current = 52A)
C60N 80A 2P (maximum line current = 64A)
2
Input terminal
10
block
9
Output terminal block
Earthing wires
28
5. Connect the three wires of the equipment cable to the output
29
terminal block .
Always connect the earthing wire first.
9
6. Connect the three wires of the power cable to the input terminal block .
7. Tighten the cable clamp .
8. Refit and secure the terminal-block cover .
10
29
28
51033212EN/AC - Page 17
3. Operation
3.1 ON-LINE operating mode
bypass
bypass
This is the normal operating mode for the UPS.
Two possible cases:
19
19
LED is ON: AC input power is available. Power is drawn from the AC-power source and supplied to the protected equipment via the UPS.
20
LED is ON: AC input power is not available. Power is drawn from the battery and supplied to the protected equipment.
20
Page 18 - 51033212EN/AC
3.2 Start-up
3. Operation
Prior to initial start-up, check the UPS voltage settings. The frequency of the output voltage (50 or 60 Hz) is automatically set to that of the input source.
1. Close the upstream device (ON position) controlling the supply of AC power to the UPS.
2. Set the battery circuit breaker(s) to ON.
2
The buzzer beeps three times. If the supply frequency is different than the default value set on the UPS, the new value is set and the buzzer beeps 4 times.
3. Press the ON / OFF button . All the equipment connected to the UPS is now energised, however it takes another 30 seconds before the UPS is fully operational.
19
20 21
19
If LED or do not go ON or if one of LED , , or flash, there is a fault (see section 4.1). In order to detect any wiring errors, it is essential that the AC-power source be present at the first switch-on.
20
After this time, the equipment connected to the UPS is protected.
14
11 12
13
Subsequently, the device may be switched-on without the presence of the AC-power source.
2
21
3.3 Bargraph indications
LEDs to provide three different indications.
11
14
bypass
1. Remaining backup time in percent (in ON-LINE mode).
11
12
13
14
15
2. Percent load drawn by the protected equipment, when button is pressed.
15
3. Operating faults (flashing LED and beeps):
Overload.
11
UPS fault.
12
Battery fault.
13
Excessive ambient temperature.
14
51033212EN/AC - Page 19
3. Operation
3.4 Failure of AC input power and operation on battery power
AC input power is not available, the battery steps in to supply the protected equipment.
Transfer to battery power
When AC-power source goes outside tolerances or fails
bypass
20
completely, LED goes ON and the buzzer beeps three times.
Threshold for the low-battery shutdown warning
The low-battery shutdown warning threshold can be set
bypass
20
by the user, with the "UPS Driver" software (default setting equal to 20% of full backup time). LED flashes when the setted level is reached.
20
The buzzer beeps every three seconds when less than 10% of backup time remains.
There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent.
20
End of backup time
bypass
Sleep mode
This operating mode may be personalized using the "UPS Driver" software (see section 3.5). It saves battery power when no equipment is connected to the UPS. Shutdown occurs after 5 minutes. The UPS automatically restarts when the AC-power source returns to within tolerances.
Return of AC input power
If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.5).
Page 20 - 51033212EN/AC
The buzzer sounds continuously. Press button to turn the buzzer OFF.
16
16
The equipment is no longer supplied with power.
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
3. Operation
Check that the RS 232 cable is correctly connected and that the battery circuit breaker is closed.
"UPS Driver" installation:
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running Windows. 2 - Open the Windows File manager or Explorer and select the CD-ROM drive. 3 - Double-click "\Emb\Index.htm", then "UPS Driver".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.
"ON / OFF conditions" tab
Personalizable function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
22
2
Default setting
Enabled Enabled Enabled
Disabled
Enabled
51033212EN/AC - Page 21
3. Operation
"Battery" tab
"Low-battery shutdown warning" threshold
"Output" tab
Personalizable function
"Battery test" intervals
Charger
Default setting
Every day
20% remaining battery
backup time
Standard
Options
Once a week
Once a month
No test
40% remaining battery
backup time
CLA (2, 4 or 8 hours)
"By-pass" tab
Rated AC-power source voltage (see figure 1)
Rated AC-power source frequency
Tolerance for AC-power source frequency
Alarm threshold for overload
Restart inverter after short circuit
Authorized voltage range for transfer to bypass
if fault or overload
Authorized frequency range for transfer to bypass
230 V 50 Hz
± 5%
100%
Disabled
187 V to 265 V (for
230 V rated voltage)
± 10%
200 V-208 V-220 V-240 V
± 1% to ± 10% , in 1% steps
0 to 100%, in 10% steps
Enabled (click to add check)
187 V to 265 V,
in 1V steps
± 1% to ± 10%, in 1% steps
if fault or overload
Transfer to bypass if overload
Transfer to bypass following a fault, whatever
Enabled
Disabled
Disabled (click to remove check)
Enabled (click to add check)
the conditions on the AC-power source
The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).
Available power as a percentage of the rated power
100%
95% 90%
66%
50%
60 Hz
Page 22 - 51033212EN/AC
Fig. 1
84
Voltage in V
3.6 Shutdown
Shutdown of connected equipment
3. Operation
Complete shutdown of the UPS
1. Press button (return to the OFF position).
The connected equipment is no longer supplied with power, but the battery is maintened charged if AC-power source is
21
2
present.
1. Press button (return to the OFF position).
The connected equipment is no longer supplied with power.
2. Open the upstream device (OFF position) controlling the supply of AC power to the UPS.
3. Switch the battery circuit breaker(s) to OFF position.
Warning: if the upstream source is not switched off, the UPS remains in operation.
21
If the AC source fails, even though the connected equipment is no longer supplied, the UPS operates on battery power and therefore reduces the available backup time.
21
2
The UPS is now de-energised and the batteries are no longer recharged.
51033212EN/AC - Page 23
4. Maintenance
4.1 Troubleshooting
14
Signification
The UPS is not designed to operate more than eight hours under these conditions.
Correction
Shut down the UPS and check that the input power cable is properly connected to the input terminal block and the load to the output terminal block (see p. 17). After correcting any wiring errors, restart the UPS as indicated on page 19. If the problem persists, call MGE after-sales support.
Check the power drawn by the equipment and disconnect any non-priority devices.
Install the UPS in a room where the ambient temperature is not greater than 40° C.
See point 5 to 7 of in the "Reconnecting the connection module" part of section 4.2.
13
11 12 13
14
The UPS has detected a problem concerning the wiring of the connection module input.
UPS overload. Overload is too long or too high. The UPS cuts the supply of power to the connected equipment and the buzzer beeps continuously.
The ambient temperature is higher than 40° C.
The UPS is in maintenance mode (manual bypass)
If one or more LEDs , , or flash, there is a operating anomaly or an alarm.
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE after-sales support
Indication
11 12
LEDs , , , flash and the buzzer beeps.
11
LED flashes and the buzzer beeps.
14
LED flashes.
17
LED is ON.
Page 24 - 51033212EN/AC
To allow you to use MGE UPS SYSTEMS products effectively and carry out basic maintenance, we offer a complete range of technical training courses in English and French.
FRENCH Training Center on Montbonnot site:
MGE UPS SYSTEMS 140, Avenue Jean Kuntzmann Zirst - Montbonnot St Martin 38334 - ST ISMIER CEDEX - FRANCE
Tel: (33) (0)4 76 18 34 15 Fax: (33) (0)4 76 18 45 21 Email: delphine.malossane@mgeups.com
Internet: www.mgeups.com (On-line catalogue and registration).
USA Training Center on Costa Mesa site:
MGE UPS SYSTEMS 1660, Scenic Avenue Costa Mesa, CA 92626, USA
Tel: (1) 714 557 1636 Fax: (1) 714 557 7230 Email: david.muro@mgeups.com
Troubleshooting requiring MGE after-sales support
4. Maintenance
Indication
12
LED flashes and the buzzer beeps.
LED flashes.
13
Signification
UPS electronics have detected a UPS
fault. Depending on the UPS personalization parameters (see section 3.5), there are two possibilities:
the equipment connected to the UPS
continues to be supplied, but directly from the AC-power source via the automatic bypass for a maximum of 8 hours (LED ON);
the connected equipment is no longer
18
supplied.
The equipment connected to the UPS is no longer protected.
A battery fault was detected during the battery test.
Correction
Follow the UPS replacement procedure (see section 4.2).
Call the after-sales support department.
Call the after-sales support department because the batteries need replacing.
51033212EN/AC - Page 25
4. Maintenance
4.2 Replacement of the electronic module
Disconnecting the connection module
Before turning the switch,
see the manual
NORMAL
bypass
Before turning the switch,
see the manual
NORMAL
BY-PASS
BY-PASS
1. Turn the manual bypass switch , located behind the UPS
7
(see section 1.2), from the NORMAL to the intermediate position.
2. Check that LED is ON before continuing to the BYPASS
7
position.
If LED is not ON, do not switch to the BYPASS
18
18
position and call the after-sales support department.
18
3. Turn the manual bypass switch from the intermediate position to the BYPASS position.
7
The connected equipment is supplied by the AC­power source, via the manual bypass.
21
4. Shut down the UPS by pressing button (return to the OFF
21
position).
5. Switch the battery circuit breaker(s) to the OFF position.
6. Remove the two fixing screws to free the connection module (see next page).
8
2
30
7. Remove the connection cable(s) from the battery module(s).
The UPS can be replaced. The connected equipment is supplied by the AC-power source.
Page 26 - 51033212EN/AC
Reconnecting the connection module
4. Maintenance
1. Secure the connection module using the two screws .
17
18 19 21
2. Reconnect the connection cable(s) to the battery module(s).
3. Switch the battery circuit breaker(s) to the ON position and check that LED is ON.
17
Check that UPS personalization settings still
8
2
30
correspond to the equipment to be supplied (see section 3.5).
4. Press button and wait 20 seconds.
5. Check that LED is ON.
2
21
18
18
If LED is not ON, do not switch the manual bypass to the intermediate position and call the after-sales support department.
6. Turn the manual bypass switch from the BYPASS position to the intermediate position and check that LED is OFF.
7. Turn the manual bypass switch from the intermediate position to the NORMAL position.
goes ON.
30
8
The connected equipment is again protected by the UPS.
7
17
7
17
LED goes OFF and LED
19
51033212EN/AC - Page 27
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs. It was manufactured in a factory certified ISO 14001.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not correctly recycled by specialized companies.
Page 28 - 51033212EN/AC
Web site : www.mgeups.com
6.1 Glossary
Authorized voltage Upper and lower voltage thresholds within which the UPS can operate range for transfer to on the automatic bypass in the event of a UPS fault or overload.
bypass if fault or overload
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment
Automatic start following When AC input power returns following shutdown at the end of the battery return of AC input power backup time, UPS automatic start can be enabled or disabled.
Backup time Time that the connected equipment can operate on battery power.
Bargraph Device on the front panel indicating the percent remaining backup time
Battery test Internal UPS test on battery status.
Cold start See "Start on battery power".
Connection module Unit grouping the receptacles for connection to the AC-power source
Dialog box A window in a computer program displayed for selection by the user of various
6. Appendices
directly to the AC-power source.
or the percent load.
and the equipment.
options and parameter settings.
Double conversion The power supplied to the connected equipment is completely regenerated
by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.
Equipment Devices or systems connected to the UPS output.
Forced shutdown Allows a "clean" of computer operating systems depending on the low battery
threshold setting. If the input source is restored during the time period between the shutdown order and actual system shutdown, it causes a voluntary interruption of the supply of power to the connected equipment (lasting 10 seconds) after system shutdown.
Manual bypass Rotary switch controlled by the user, used to connect the equipment directly
to the AC-power source. Transfer of the load to the manual bypass enables UPS maintenance or replacement, without interrupting the supply of power to the connected equipment.
ON-LINE mode The normal UPS operating mode, by which the AC-power source supplies
the UPS, which in turn, following double conversion of the AC power, supplies the connected equipment.
51033212EN/AC - Page 29
6. Appendices
Out of tolerance The AC input source is either absent or its voltage or frequency is outside the
Percent load Ratio between the power drawn by the connected equipment and the total
Personalization A number of UPS functions can be modified using the "UPS Driver" software
Sleep mode This function shuts down the UPS after 5 minutes when it operates on
Start on battery power This function makes it possible to energize the connected equipment even
Tolerance for AC-power The range of frequency supplied by the AC-power source within which source frequency the UPS can operate in ON-LINE mode (double conversion).
UPS Uninterruptible Power Supply.
UPS ON / OFF It is possible to enable or disable use of UPS ON / OFF controls via software by the computer-system protection software.
set limits.
power that the UPS can supply.
to better meet the user's needs.
battery power and no load is detected on the UPS output. The UPS restarts automatically as soon as the AC input source is restored.
when AC input power is not available (operation exclusively on battery power).
Page 30 - 51033212EN/AC
6.2 Index
6. Appendices
A
AC power
Failure ........................................................... 20
Frequency tolerance ..................................... 22
Rated frequency ............................................22
Rated voltage ................................................ 22
Return............................................................ 20
B
Bargraph .............................................................. 19
Battery
Battery test .................................................... 22
End of backup time ....................................... 20
Fault ........................................................ 11, 19
Low-battery shutdown warning ..................... 20
Recycling ....................................................... 28
Transfer to battery power .............................. 20
Buzzer ...................................................3, 11, 19-20
By-pass
Automatic bypass ....................................18, 25
Manual bypass ............................... 8, 11, 26-27
C
Communication .................................................... 16
Connection
Communications card ................................... 16
Connection modules ..................................... 17
RS 232 communications port ........................ 16
F
Fault (UPS)
Load .............................................................. 11
Transfer to automatic bypass ........................25
L
LEDs
Lamp test....................................................... 11
O
Overload................................................... 11, 22, 24
P
Personalization ............................................. 21, 23
Battery .......................................................... 22
ON / OFF conditions..................................... 21
Output........................................................... 22
R
Rack ........................................................ 6-7, 12-14
S
Shutdown
Forced shutdown ........................................... 21
UPS ON / OFF via software .......................... 21
UPS shutdown ........................................ 11, 23
Sleep mode ................................................... 20-21
Software
UPS Driver.............................12-13, 19, 21, 23
Start-up
Automatic start .............................................. 21
T
Temperature
Excessive ambient temp ................... 11, 19, 24
U
UPS Driver .................................. 12-13, 19, 21, 23
M
Mode
ON-LINE mode ........................................ 11, 18
51033212EN/AC - Page 31
Page 32 - 51033212EN/AC
Loading...