MGE UPS Systems 66846, 66074, 66244 User Manual

Page 1
www.mgeups.com
Network Management Cards
User Manual
Minislot 66244
Transverse 66074
Environment Sensor 66846
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 2
www.mgeups.com
Network Management Cards
User Manual
Table of Contents
1 MGE NETWORK SOLUTION____________________________________________________________4
1.1 I
NTRODUCTION
_____________________________________________________________________4
1.1.1 Connecting the UPS to the Network________________________________________________4 The Network Management Card or Proxy: __________________________________________________4
1.1.2 Protecting the computers / servers_________________________________________________5
1.1.3 Monitoring the UPSs over the network______________________________________________5
1.1.4 Connection ___________________________________________________________________6
1.2 P
1.3 P
1.4 D
1.5 S
1.6 C
1.7 C
1.8 T
RESENTATION OF THE NETWORK MANAGEMENT CARDS RESENTATION OF THE ENVIRONMENT SENSOR SOLUTION IRECT SENDING OF E-MAIL ENDING TEXT MESSAGES OMPATIBILITY WITH THE NETWORK MANAGEMENT SYSTEMS OMPATIBILITY WITH THE LEGACY SOLUTION-PAC ECHNICAL DATA
___________________________________________________________________8
___________________________________________________________7
(SMS)_______________________________________________________7
(NMC) ________________________________6
_____________________________________6
WAN
OFFERING
(NMS) – T
RAP SENDING
________________7
______________________________7
1.8.1 Configuration _________________________________________________________________8
1.8.2 Administration_________________________________________________________________8
1.8.3 Network _____________________________________________________________________8
1.8.4 MIB (Management Information Base)_______________________________________________8
1.8.5 Environment sensor ____________________________________________________________8
2 INSTALLATION AND CONFIGURATION _________________________________________________10
2.1 I
NSTALLATION
____________________________________________________________________10
2.1.1 Installing the card in the UPS ____________________________________________________10
2.1.2 Connecting the card to the IT network _____________________________________________10
2.1.3 Understanding front panel signals ________________________________________________10
2.2 B
ASIC CONFIGURATION
_____________________________________________________________10
2.2.1 List of default parameters_______________________________________________________10
2.2.2 Adjusting the network parameters ________________________________________________10
2.2.3 Rebooting the card____________________________________________________________10
2.2.4 Restoring factory configuration___________________________________________________10
2.2.5 Lost password – restoring the default password _____________________________________10
2.2.6 Checking that the card is working_________________________________________________10
2.3 E
NVIRONMENT SENSOR
_____________________________________________________________10
3 SUPERVISION / ADMINISTRATION VIA A WEB BROWSER _________________________________11
3.1.1 Optimising the performance of your browser ________________________________________11
3.2 UPS ___________________________________________________________________________12
3.2.1 “UPS properties” page _________________________________________________________12
3.2.2 On-line help _________________________________________________________________14
3.2.3 3-Phase display ______________________________________________________________15
3.2.4 UPS Control _________________________________________________________________16
3.2.5 UPS weekly schedule programming_______________________________________________18
3.2.6 Shutdown parameters__________________________________________________________19
3.2.7 Viewing the alarms____________________________________________________________21
3.3 L
OGS
__________________________________________________________________________22
3.3.1 Measurements _______________________________________________________________22
3.3.2 Event log____________________________________________________________________24
3.3.3 System log __________________________________________________________________25
3.4 N
OTIFICATION
____________________________________________________________________26
3.4.1 Email Notification _____________________________________________________________26
3.4.2 Email Message Settings________________________________________________________28
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 3
www.mgeups.com
Network Management Cards
User Manual
3.5 C
ONFIGURATION
__________________________________________________________________30
3.5.1 Network Settings _____________________________________________________________31
3.5.2 System _____________________________________________________________________33
3.5.3 Notified Applications___________________________________________________________35
3.5.4 Central Shutdown Configuration__________________________________________________36
3.5.5 Access control _______________________________________________________________37
3.5.6 Time _______________________________________________________________________40
3.6 E
NVIRONMENT
____________________________________________________________________41
3.6.1 Characteristics _______________________________________________________________41
3.6.2 Environment status____________________________________________________________42
3.6.3 Environment Settings __________________________________________________________43
3.6.4 Log ________________________________________________________________________44
4 SERVERS PROTECTION _____________________________________________________________45
4.1 SET-
UP OF THE SHUTDOWN PARAMETERS
________________________________________________45
4.1.1 Shutdown criteria managed by the Management Card ________________________________45
4.1.2 Specific set-up for long autonomy installation (> 30 mn)_______________________________46
4.1.3 Controlled outlets _____________________________________________________________46
4.1.4 Connecting a server protected by UM-Client to a programmable outlet____________________46
4.2 T
HE DIFFERENT SERVER AND
UPS
SHUTDOWN SEQUENCES
___________________________________48
4.2.1 Extended power outage, shutdown initiated by the Shutdown Timer______________________48
4.2.2 Extended power outage, shutdown initiated by the “Low battery power” message ___________50
4.2.3 Extended power outage, shutdown initiated by the Shutdown Timer, but utility restoration before the end of the Shutdown Duration________________________________________________________52
4.2.4 Off/On command _____________________________________________________________54
5 CONFIGURING A SET OF CARDS WITH MUPGRADE______________________________________56 6 CONFIGURATION IN LOCAL MODE AND VIA TELNET OR SSH______________________________56
6.1 C
ONFIGURATION IN LOCAL MODE
______________________________________________________56
6.1.1 Choice 1: SNMP agent configuration menu _________________________________________57
6.1.2 Choice 2: UPS parameters______________________________________________________58
6.1.3 Choice 3: Access control _______________________________________________________58
6.1.4 Choice 4: Restore default configuration ____________________________________________59
6.1.5 Choice 5: Reset the card _______________________________________________________59
6.2 C
6.3 C
ONFIGURATION VIA TELNET ONFIGURATION VIA
SSH ___________________________________________________________60
_________________________________________________________60
6.3.1 PuTTY SSH Client Program_____________________________________________________60
7 MAINTENANCE _____________________________________________________________________62
7.1 S
OFTWARE UPGRADE
_______________________________________________________________62
7.1.1 Card firmware upgrade using Mupgrade (Windows) __________________________________62
7.1.2 Card software upgrade via TFTP (UNIX and Windows)________________________________62
7.1.3 Recovery tool software via the serial link ___________________________________________62
8 APPENDICES_______________________________________________________________________63
8.1 T
ABLES OF ALARMS AND EVENTS
______________________________________________________63
8.1.1 Alarm table __________________________________________________________________63
8.1.2 UPS event table ______________________________________________________________63
8.1.3 System alarm table____________________________________________________________66
8.2 G
LOSSARY
______________________________________________________________________67
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 4
www.mgeups.com
Network Management Cards
User Manual
1 MGE Network Solution
1.1 Introduction
Z provides information on events concerning the supply of power to the computers connected to your
computer network,
Z carries out automatic shutdown of computer systems, Z monitors and controls all the UPSs connected to the network.
As illustrated in the picture below, MGE Network Solution provides these 3 main functions:
Z connecting the UPS to the Network, Z protecting the computers, Z monitoring the UPSs over the Network
1.1.1 Connecting the UPS to the Network
This function can be performed either through network Cards inserted in the UPS (Network Management Card) or through a software “agent” running on a nearby PC that is called the Network Manag ement Proxy .
The Network Management Card or Proxy:
Z manages communication with the UPS (as well as local protection of the machine on which Proxy is
installed),
Z periodically accesses the information concerning the UPS,
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 5
www.mgeups.com
Network Management Cards
User Manual
Z makes this information available to the connected applications (Network Shutdown Modules, Web
Browser, Network Management Systems, Enterprise Power Manager)
Operation may be in standard secure mode (the default mode) or in SSL secure mode (Secure Socket Layer SSL).
1.1.2 Protecting the computers / servers
This function is performed by the Network Shutdown Module installed on each of the servers to be protected. Note that the Shutdown Module is available on several Operating Systems. The Network Shutdown module:
Z continuously waits for information from the Network Management Card / Proxy connected to the MGE
UPS.
Z warns administrators and users if AC power fails and proceeds with graceful system shutdown before the
end of battery backup power is reached.
1.1.3 Monitoring the UPSs over the network
Depending on your needs, you can either use:
Z your Internet browser to monitor each UPS, as Management Proxy and Management Card include a Web
server.
Z your company’s standard Network Management System (HP-Openvie w, CA Unicenter, HP Insight
Manager, IBM Tivoli Netview). To simplify integration of MGE UPSs with these NMS, you can use one of the Network Management System Kits for MGE devices. These kits are available on Management Pac 2 CD-Rom. (ref 66923)
Z the MGE supervisor " Enterprise Power Manager "
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 6
www.mgeups.com
Network Management Cards
User Manual
1.1.4 Connection
Before installing the MGE Network Solution, the UPS must be set up as indicated in the steps below.
Z Shut down the computers to be protected by the UPS.
Connect the UPS to a wall outlet. (For UPSs above 3kVA, please refer to the UPS installation manual)
Z Connect the power cord of each computer to an outlet on the UPS. (For UPSs above 3kVA, please refer to
the UPS installation manual)
1.1.4.1 How to connect UPS / agent / network :
Z Insert the optional card in the UPS and connect the UPS to the computer network. Z Start the MGE UPS, then the computers.
1.1.4.2 Setting up the protection
Z Set up the Network Management Card (see user manual). Z Install Network Shutdown Module on all machines that are to be protected by the UPS (supplied with UPS
battery backup power).
The software components for each platform and the user manuals are supplied free-of-charge on the Solution­Pac 2 CD or are available for download on the www.mgeups.com Web site, in the “Download area” section”
1.2 Presentation of the Network Management Cards (NMC)
MGE provides 2 different form factors for its Network Management Cards :
Z NMC Minislot for UPS systems like the Evolution, EXtreme C, Pulsar EX RT, Pulsar/Comet DX series. Z NMC Transverse for UPS systems like the Galaxy 3000, Galaxy 5000, Galaxy PW, Pulsar and Comet
EXtreme series. Other MGE UPS systems (3-phase Comet, Galaxy, EPS 6000) can be remotely managed
using the Network Management Link . The Network Management Cards acquire information on the operation status of the UPS systems and provide
remote control of these systems by means of an ETHERNET network from any SNMP administration station or Web browser. They also supply alarms to the Network Shutdown Modules to trigger shutdown or other automatic actions for protected servers.
A simple html browser is used for supervision and configuration. Network Management Cards are compatible with all MGE UPS SYSTEMS supervision / protection systems:
Z Network Shutdown Modules Z Entreprise Power Manager Z Management-Pac 2
1.3 Presentation of the Environment Sensor solution
The Environment Sensor solution comprises a box to be connected to the Card Settings port of the Network Management Cards: Environment Sensor enables measurement of temperature and humidity around the UPS, consideration of external alarms via 2 dry contacts and notification of alarms according to pre-programmed thresho l ds.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 7
www.mgeups.com
Network Management Cards
User Manual
1.4 Direct sending of E-mail
When a UPS event occurs, the Network Management Card can directly notify up to 4 intranet or extranet addressees by e-mail (see Email Notification and Email Message Settings
).
1.5 Sending text messages (SMS)
SMS messages can be sent by specific configuration of the e-mail function via the internet access providers making the e-mail / SMS transfer.
1.6 Compatibility with the Network Management Systems (NMS) – Trap sending
The Network Management Cards are compatible with the major Network Management Syste ms (IBM Tivoli, CA Unicenter, HP Insight Manager ..),. The Management-Pac 2 offering includes the necessary SNMP plug-in to allows an easy integration in the NMS. Events are notified by SNMP trap
Z NMS can subscribe on page “Notified Application Z SNMP sequences are described in chapter “Server protection”
The trap list can be looked over in the document “Agent's MIB description” available on mgeups.com
1.7 Compatibility with the legacy Solution-Pac WAN offering
Network Management Card is compatible with the legacy protection module UM-Client and since the FA release also with the updated protection module Network Shutdown Module . It is possible to use the both modules on the same card, therefore, MGEUPS recommends to use the Network Shutdown Module on new installations.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 8
www.mgeups.com
Network Management Cards
User Manual
1.8 Technical data
1.8.1 Configuration
The user can configure the card with one of the following means:
Z Web browser Z Local serial link Z Telnet console Z BOOTP/DHCP Z Mupgrade
1.8.2 Administration
Z Up to 50 workstations protected Z Up to 15 browsers connected at the same time Z E-mail sending configurable according to UPS alarms and transmission of a periodical report
Z Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting
down the installation
Z Control of UPS on/off switching via the HTML interface Z Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation
and optimisation of backup time by shutting down non-priority systems
Z Adjustment of date and time via NTP server - Daylight Saving Time management Z Protection by encrypted password. Z Protection by secured connection SSL and SSH Z Saving of logs in the non-volatile memory Z Automatic language detection according to browser configuration. Z Languages available: English / French / Spanish / German / Italian Z On-line help available for each page Z Card firmware updated via the network Z Card configuration deployment on your installed base through network utility (Mupgrade)
1.8.3 Network
Z Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet Z SNMP trap port modifiable (by default = 162)
1.8.4 MIB (Management Information Base)
Z MIB IETF UPS (RFC1628) / MIB MGE V1.7
1.8.5 Environment sensor
Z Temperature measurement from 0 to 70 °C with +/- 1°C accuracy Z Measurement of humidity from 0 to 100 % with +/- 6 % accuracy Z Min / max time-stamped function for temperature and humidity Z Choice of temperature readings in Celsius or Fahrenheit Z High and low thresholds, hysteresis and offset adjustable via Web interface Z Possibility of notification of status changes by e-mail, SMS or SNMP traps Z Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m) Z Name and status of each configurable contact
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 9
www.mgeups.com
Network Management Cards
User Manual
Z Recording of events and measurements in the card log Z Possibility of shutting down the installation in the event of a threshold being exceeded or on opening /
closure of a dry contact
Z Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m)
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
Page 10
www.mgeups.com
Network Management Cards
User Manual
2 Installation and Configuration
For the following sections, read the installation manual supplied with the card or available for download on the
www.mgeups.com web site in the “Download area – embedded Software
2.1 Installation
2.1.1 Installing the card in the UPS
2.1.2 Connecting the card to the IT network
2.1.3 Understanding front panel signals
” section
2.2 Basic configuration
2.2.1 List of default parameters
2.2.2 Adjusting the network parameters
2.2.3 Rebooting the card
2.2.4 Restoring factory configuration
2.2.5 Lost password – restoring the default password
2.2.6 Checking that the card is working
2.3 Environment Sensor
Read the installation manual supplied with the box.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
10/69
Page 11
www.mgeups.com
Network Management Cards
User Manual
3 Supervision / Administration via a Web browser
A JVM (Java Virtual Machine) is required to ensure correct display of information in HTML pages.
Z On a computer equipped with a Web browser (Internet Explorer or Netscape recommended), enter the
address initialised previously in the Installation chapter (e.g.: http://213.30.17.30.)
Z The “UPS properties” home page is displayed.
3.1.1 Optimising the performance of your browser
Z To view status changes on the UPS in real time, the browser must be configured so that it automatically
refreshes all the objects on the current page. Example on IE 6: Tools / Internet Options / General / Parameters menu, tick Every time this page is visited and validate.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
11/69
Page 12
www.mgeups.com
Network Management Cards
User Manual
3.2 UPS
3.2.1 “UPS properties” page
Z This page gives instant access to the essential information about your UPS.
This page is automatically refreshed every 10 seconds (by default). To change this value, go to the “System” page.
3.2.1.1 UPS zone: general information on the UPS.
Indication of the picture and generic name of the UPS range Computer room: Customised name of your system corresponding to the “upsIdentName” object of the UPS
MIB (RFC 1628) You can change this name on the “System” page.
3.2.1.2 “UPS status” zone: essential information
Z The various icons showing the status of the UPS are:
Normal operation
Alarm present. This icon links directly to
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
the alarm page
– User Manual 34003676EN/GA
Page
12/69
Page 13
www.mgeups.com
Network Management Cards
User Manual
(green outlet)
(red outlet)
“Communication”: indicates the status of the communication between the card and the UPS
“Power source”: indicates whether the power comes from the utility or from the UPS battery “Batteries”: indicates whether the battery is being charged or discharged “Output load level”: indicates the power percentage used at UPS output “Master output”: indicates if the UPS output is protected “Controlled outlets”: indicates if the controlled outlets (if available) are powered.
Battery operation
Loss of communication with the UPS
Battery fault
Outlet powered – Flashing when an
on/off sequence is in progress
Outlet not powered or not protected
3.2.1.3 “Battery status” zone:
Z “Bargraph”: Graph showing the remaining battery charge (in percent). Z “Battery charge level”: Remaining battery charge (in percent). Z “Remaining backup time”: Estimation of the maximum backup time remaining before UPS shutdown.
This time can be modified by the adjustments on the “Shutdown parameters” page
Z “Last periodical test”: Result of the last automatic battery test carried out by the UPS
Possible values are:
- OK: the test was completed correctly – NOK: the battery needs to be checked – Deactivated: the automatic battery test is not validated on the UPS
The “About your UPS” zone provides information on the UPS and the Network Shutdown Card, in particular, the model range and software version.
Note: If the UPS is connected by dry contacts, neither picture or name are indicated, the “2 contacts” title is displayed and only the following parameters are specified in the UPS status zone:
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
13/69
Page 14
www.mgeups.com
Network Management Cards
User Manual
3.2.2 On-line help
On-line contextual help in English is available at the top of each page by clicking on the Help link, which is always located on the top right corner.
The Help page always opens a new window.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
14/69
Page 15
www.mgeups.com
A
App
Network Management Cards
User Manual
3.2.3 3-Phase display

Click 3-phase display to access to the detailed monitoring page

This item is added to the menu for all single UPSs having a three-phase output.
The link on the gauge symbols gives access to the measurement page related to the function.
Function symbols are outlined in red when an alarm is present.
The red triangle, linked to the alarm page, appears when an alarm is present, otherwise a green
symbol is displayed. This page is automatically refreshed every 10 seconds (by default).
To change this value, go to the “System” page.
Frequency and power factor
Static ByPass
Rectifi
Battery
Inverte
3.2.3.1 Normal input measurements
ctive power – Global and per phase
arente power – Global and per phase Output current Output voltagePhase / Phase Output voltage Phase / neutral
Maintenance position
Static switch operation
Normal operation
Battery
.
Input current Input voltagePhase / Phase
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
15/69
Page 16
www.mgeups.com
g
3.2.3.2 Battery measurements
3.2.3.3 By Pass measurements
Network Management Cards
User Manual
Remaining backup time estimted by the UPS Battery charge level Battery voltage Battery current – Negative when dischargin Battery temp. – Internal temperature probe
By Pass current By Pass voltagePhase / Phase
3.2.4 UPS Control
Click on the “UPS Control” section in the menu. If the UPS is not compatible with this function, a warning message is sent to the user.
UPS configuration may also prevent the commands from being properly run. Read the UPS manual for more information.
This page enables triggering of startup and shutdown sequences for the UPS main output and Controlled outlets.
Z The status of each output is displayed by a symbol associated with the Off label (red symbol) or Powered
(green symbol).
Z The shutdown sequences take into account the time required for the registered servers to shut down
without losing data (see shutdown parameters ). Once the sequence has started, the commands are disabled until it ends.
Z After a startup sequence, the commands are disabled for 120 seconds to enable the servers to fully restart
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
16/69
Page 17
www.mgeups.com
Network Management Cards
User Manual
Z The main outlet has priority over the auxiliary outlets. Shutdown of the main outlet causes the auxiliary
outlets to shut down. Auxiliary outlets can only be started if the main outlet is powered
The Check column proposes six different commands, and a command is only actually started after clicking on
'Execute': “Safe power down”: a sequence to switch off output power is launched immediately. The symbol representing
the output flashes, indicating that the sequence is in progress. The systems supplied are shut down correctly while the shutdown sequence is running, then the output is cut.
“Safe power down & reboot”: A sequence to switch off then restore output power is launched immediately. The symbol representing the output flashes, indicating that the shutdown sequence is in progress. The powered systems are shut down correctly during the shutdown sequence, then the output is switched off. Finally, the restart sequence is launched at the end of the time delay specified in the “Toggle duration” parameter. The output status is updated.
Immediate On”: a sequence to switch on output power is launched immediately. The output is re-powered and the systems supplied start up again correctly.
Delayed, safe power down”: this is the same switch off sequence as for the “ Safe power down ” command, but postponed by the number of seconds programmed in the “Off Delay ” parameter.
Delayed, safe power down & reboot:” this is the same switch off then on sequence as for the Safe po wer down & reboot ” command, but postponed by the number of seconds programmed in the “ Off Delay ” parameter.
Delayed On ”: this is the same switch on sequence as for the “ Immediate On ” command, but postponed by the number of seconds programmed in the “ On Delay ” parameter.
The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card .
Security: The administrator must click on Save and enter his login / password to sav e modifications or run commands. The login and password by default are: MGEUPS.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
17/69
Page 18
www.mgeups.com
Network Management Cards
User Manual
3.2.5 UPS weekly schedule programming
Click on the “Weekly schedule” section of the menu. If the UPS is not compatible with this function, a warning message is sent to the user.
UPS configuration may also prevent the commands from being properly run. Read the UPS manual for more information.
The weekly schedule enables the administrator to optimise power consumption or program a reboot of the protected equipment at a set time.
In a shutdown sequence, the Network Shutdown Modules connected to the card are informed and ensure that each machine is shut down correctly before the UPS output is switched off. Up to 7 UPS shutdown sequences can be programmed in one week, with a minimum shutdown delay of 30 minutes.
Security: the administrator clicks on Save” and enters his/her login / password to save any edits. The login and password by default are: MGEUPS.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
18/69
Page 19
www.mgeups.com
Network Management Cards
User Manual
3.2.6 Shutdown parameters
Z Click on the “Shutdown parameters” section in the menu to see the list of parameters.
Important note:
For installations that do not use Network Shutdown Module (backup units, routers and other internetworki ng equipment, automated systems, etc.) or in the event of long backup periods, the card will send a command to the UPS to shut off end of the programmed Shutdown After time. To prevent this, the Shutdown After box must be not selected (default)
This page enables viewing and configuration of UPS operation parameters in battery mode and for powe r restoration.
When you tick the Show advanced parameters option, extra parameters are displayed. These parameters enable, in particular, adjustment of certain thresholds related to the percentage of remaining battery charge level.
The Output column enables each output to be named (maximum 30 characters).
Note
Priority is given to the main outlet, so the card does not accept configurations where the auxiliary outlets can be supplied while the main outlet is switched off
For the main outlet (Master)
Z Shutdown after is the operating time in minutes left for users after a switch to backup before starting
the shutdown sequences of the UPS and its equipment (from 0 to 1092).
Z If remaining time under (from 0 to 9999 seconds) and If Capacity under (from 0 to 100%) are two
extra conditions for remaining backup time and battery level that can trigger shutdown sequences before the “Shutdown after” period runs out
Z Shutdown duration is the time required for complete shutdown of systems when a switch to backup
time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of Shutdown duration of subscribed clients but can be modified in the Advanced mode
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
19/69
Page 20
www.mgeups.com
Network Management Cards
User Manual
Z Restart after is the minimum shutdown time before restarting the UPS after a shutdown sequence. It is
thus possible to limit repeated restarts that may be due to several successive utility failures.
Z If the Battery is charged for and If Capacity exceeds are two extra conditions for minimum battery
level and maximum recharge time to be reached before restarting the UPS after utility restoration For controlled outlets (group 1 or group 2 ), the page enables programming of operation time and level in backup mode to manage outlet load shedding in the event of electric power failure:
Z Switch Off after (from 0 to 65534).defines the time during which the outlet is supplied starting from
the moment of utility failure. Caution, this time includes the outlet shutdown duration.
Z Switch Off if capacity under is an extra condition for outlet shutdown that can trigger the shutdown
sequence before shutdown duration runs out.
Z Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet
when an outlet shutdown sequence is launched.
It is calculated automatically using the maximum shutdown durations of subscribed clients.
Z Switch On (from 0 to 65534). is the period between main output startup and startup of the relevant
programmable outlet, therefore outlet startup can be delayed in relation to the main output. Security: The administrator has to click on Save and enter his login/passwo rd to save any modifications. The
default login and password are: MGEUPS
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
20/69
Page 21
www.mgeups.com
Network Management Cards
User Manual
3.2.7 Viewing the alarms
Z Click on the “Alarm table” section in the menu to view the list of current alarms. The table of managed
alarms is included in the appendix.
Note: The alarm number is not related to the SNMP trap number
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
21/69
Page 22
www.mgeups.com
Network Management Cards
User Manual
3.3 Logs
3.3.1 Measurements
Click on the “Measurements” section in the menu.
The following measurements are saved and time-stamped:
Z “Input voltage”: Value of the utility voltage supplying your UPS (average of 3 phases for UPS' equipped
with a 3-phase input)
Z “Input frequency”: Value of the utility frequency feeding your UPS Z “Output voltage”: Value of the output voltage of your UPS (average of the 3 phases for UPS’ with a 3-
phase output)
Z “Output load”: Value of the percentage of load at UPS output (Value of the most loaded phase for 3-phase
UPS’)
Z “ Output current Ph x”: Value of the output current for each phase on three-phase UPSs Z “Battery capacity”: Percentage of charge available in the battery Z “Remaining time”: Estimation of the remaining backup time Z The save frequency of these values is defined in the “System” page (60 seconds by default).
Approximately 1000 time-stamps are stored permanently on the card. The oldest time-stamps are automatically deleted.
Z “Save” enables all saved values to be opened or saved in CSV format (compatible with Excel type
spreadsheets) “Clear” enables deletion of all records. The administrator must enter his login / password to validate this action if he has not already done so during the current session.
Select the time range to view
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
22/69
Page 23
www.mgeups.com
Network Management Cards
User Manual
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
23/69
Page 24
www.mgeups.com
Network Management Cards
User Manual
3.3.2 Event log
Click in the “Event log” section of the menu.
Z “Save Log” enables all values saved to be opened or saved in CSV format (compatible with Excel type
spreadsheets).
Z “Clear Log” enables deletion of all records. The administrator must enter hi s/her login / password to
validate this action.
Select the time range to view:
See the table of events generated in the UPS event table.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
24/69
Page 25
www.mgeups.com
Network Management Cards
User Manual
3.3.3 System log
Click in the “System log” section in the menu.
Z “Save” enables all values saved to be opened or saved in CSV format (compatible with Excel type
spreadsheets).
Z “Clear” enables deletion of all records. The administrator must enter his/her login / password to validate
this action.
Select the time range to view:
See the table of events generated in the System Alarm Table.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
25/69
Page 26
www.mgeups.com
Network Management Cards
User Manual
3.4 Notification
3.4.1 Email Notification
The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobile telephone transfer systems using text messages (SMS).
Z Notified events:
The left side of the page shows the events that can be notified. By default, only the main events of battery operation and a few UPS alarms are accessible. All the events appear if the Show advanced events option is ticked off. By default, two events are selected for notification. The user can modify this pre-selection by tickin g ot her events or can, on the contrary, restore the initial configuration by clicking on By default.
Z Environment alarms: (accessible when Show advanced events option is ticked off)
Environment alarms must be selected to activate e-mail notification of events concerning the Environment Sensor. The detail of notified events is accessed via the Configure Environment link.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
26/69
Page 27
www.mgeups.com
Network Management Cards
User Manual
Z Recipient List:
On the right side of this page, up to four recipients can be configured to receive e-mails from the card. Each addressee has its own trigger events, selected from the left side of the page, for which an e-mail is sent. The card’s log indicates e-mail transmission errors.
Each recipient is configured with the following parameters: Recipient: this is the e-mail address of the person or department to receive the e-mail.
The default value is recipientx@domain.com. Attached files: The files selected (UPS measurements, Event log, System log or Environment measurements)
are enclosed with each e-mail sent. The files are sent in CSV format. Periodic report: In addition to the e-mails sent when events occur, a periodical e-mail containing the 4 log files
can be sent to the recipient every x days at the time specified by the user. To configure the first transmission, specify the day, time and frequency of the next transmission in the Day of next report box. After this date, the page will show the date and time of the next transmission. Data are sent in CSV format.
Save: Saves any modifications. Test: enables an e-mail to be sent to the recipient immediately. This is one way of checking e-mail
transmission, particularly access to the SMTP server configured in “Network settings”. A transmission report is added to the system log. In the event of failure, the card will repeat the transmission 3 times, at one minute intervals, before producing a transmission report. The event label in the subject and text of the message is replaced with a test label. If the user makes any modifications to the page, they must be saved before using the “Test” function.
E-mail message configuration: see next page Network settings: enables the name of the SMTP server to be entered. See “Network settings” Security: The administrator has to click on Save and enter his login/passwo rd to save any modifications. The
default login and password are: MGEUPS
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
27/69
Page 28
www.mgeups.com
Network Management Cards
User Manual
3.4.2 Email Message Settings
This page enables customisation of the content of the messages received by recipients of e-mails sent by the card. Customisation is common to the four recipients that can be notified (see E-mail notification).
Z Sender
(32 characters maximum) identifies the source of the message. The default value is ups@domain.com. This field is free. However, depending on the type of SMTP server configuration, it is possible that the server checks that the domain name contained in the From address exists, and even that the user in the From address belongs to this domain.
Z Subject
enables the user to specify the subject of the e-mail to be sent. By entering some free text and selecting from several optional fields, if desired, the message subject is built:
- UPS name recalls the name of the UPS, can be selected or not. – UPS location recalls the geographic location of the UPS (see System Settings), can be selected or not. – Event message identifies the event generating the e-mail, can be selected or not.
- Message text is a free zone. The body of the e-mail sent is composed of:
- Message text, which is free text.
- the date and time of the event, as saved in the log.
- URL of the card, enabling a direct link with the card to be established. – Attachments, as configured for the e-mail recipients .- duplication of the subject, as configured.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
28/69
Page 29
www.mgeups.com
-
Network Management Cards
User Manual
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
29/69
Page 30
www.mgeups.com
Network Management Cards
User Manual
3.5 Configuration
The parameters of this menu can only be modified after entering the “User Name” and “Password”. The following screen is proposed automatically:
User Name and password by default are: MGEUPS
Each field accepts up to 10 characters max. After entering the login and password, these identifiers remain active as long as the browser is open, so you only have to enter them once. If the browser is closed, they will have to be re-entered.
Tick the “Save this password in your password list” box if you want to avoid systematic re-entry.
An error in either field results in systematic rejection of the requested action (save, page access, card reboot, etc.). After three unsuccessful attempts, the browser must be rebooted. These two fields do not travel “decoded” on the IT network, they are encrypted with an MD5 type algorithm, ensuring total confidentiality.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
30/69
Page 31
www.mgeups.com
Network Management Cards
User Manual
3.5.1 Network Settings
Click on the Networksection in the menu. This menu enables the administrator to configure the network parameters of the card and authorisation of the
remote upgrade of the embedded system.
Z IP address: The IP address of the card (e.g.: 172.17.23.205). Z Subnet Mask: The mask of the sub-network of your network (e.g.: 255.255.255.0). Z Gateway Address: Indicate the IP address of the gateway to access the stations located outside the
card’s sub-network (e.g.: 172.17.1.24).
Z Hostname must be suited to the card. This is the first part of the full qualified domain name, used by the
DNS (name must be compatible with DNS rules)
Z Domain name is the domain to which the card belongs. This is the part of the full qualified domain name
that follows the host name and is used by the DNS. The default value of the two parameters comprising the full qualified domain name: ups.domain.com
Z TELNET connection: Authorises (choose enable) remote connection with a terminal to access the
maintenance menu. See “Configuration in local mode and via Telnet “ for more information
Z BootP/DHCP: Authorises (choose enable) configuration of network parameters with your BootP/DHCP
server when the card is booted
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
31/69
Page 32
www.mgeups.com
Network Management Cards
User Manual
Mode of card operation with server: after any reboot, if this option is enabled, the card tries to recover the network parameters from the server for 10 sec. If no response is received from the server, the card boots with the last saved parameters from the previous start. These parameters are those shown on the page The default value for this parameter is “Enable”
. Note: The IP address supplied by the DHCP server must be fixed to maintain connection with the clients installed on the stations to be protected.
Z Network Upgrade: Authorises (choose enable) remote upgrading of the embedded system on the card
using the Mupgrade tool. Read the “Maintenance” section for more details.
Z Primary DNS server: contains the IP address of the main DNS server ensuring conversion of the domain
name to IP address.
Z Secondary DNS server: contains the IP address of the secondary DNS server ensuring conversion of the
domain name to IP address if the primary DNS server is not available.
Z SMTP server: contains the name or IP address of the local server with which the card connects to send e-
mails. It may be filled in either as host + domain name (DNS resolution), or directly with the IP address The default value is stmpserver.domain.com . The card uses port 25 to send e-mails.
Z The Authentication option must be selected if the SMPT server requires this parameter for query
submission (see the RFC 2554 for SMTP authentication) for commercial reasons, acce ss control, etc. When authentication is selected, the User and Password parameters must be specified for identification with the local SMTP server. Default values are MGEUPS/MGEUPS.
Note: The card must be rebooted after any changes to these parameters. See “System” Security: the administrator must click on Save and enter his login/password to save any modifications.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
32/69
Page 33
www.mgeups.com
Network Management Cards
User Manual
3.5.2 System
Click the “System” section in the menu. This menu enables the customisation of the information on the UPS properties and Environment pages.
Z UPS contact: This text field is limited to 32 characters. Enter the name of the person responsible for UPS
administration at IT network level and/or electrical maintenance. This field does not appear on any other Web page. By default, its value is “Computer Room Manager”.
Z UPS location: Enter a description (limited to 32 characters) of the location of the UPS in your installation
(e.g. Computer room E1-C066). This text is displayed on the home page at the top right, above the name of the UPS. Its value by default is “Computer room”.
Z History Log interval: [5 to 99999 seconds]. Measurement save period. Default value = 60 se c. Z Refresh rate: [5 to 99999 seconds]. Home page and alarms table refresh period. Default value = 10 sec. Z Default language: Enables initialisation of the browser language at card connection.
Auto: Automatically displays the Web page texts in the same language as your browser. If the Network Management Card is not able to display the recognised language, the pages will be displayed in English.
Choice of one of the available languages: English, French, Italian, German, Spanish changes the language of the html interface pages
Z Note:
Alarm notification remains in English / French (reboot the browser after modification). SNMP message remain in English.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
33/69
Page 34
www.mgeups.com
Network Management Cards
User Manual
Z Environment log interval: [from 5 to 99999 sec ]. Temperature and humidity measurement save period.
Default value = 300 sec. (only visible if the sensor is present).
Z Environment refresh rate: [from 5 to 99999 sec]. “Environment status” page refresh rate. Default value
= 60 sec. (only visible if the sensor is present).
Z Environment input grace period : [from 0 to 9 sec ]. Period during which a status change by one of the
inputs is not considered. Default value = 1 sec. (only visible if the sensor is present).
Z “Reset communication” button: performs a remote reboot of the card without modifying the configuration.
This action is compulsory for consideration of any changes made on the “Network settingspage. Security of this operation is ensured by requesting Login and Password.
Z “Fatory Reset” button: enables restoration of the default configuration of all the card’s parameters. The
TCP/IP parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the “Keep TCP/IP parameters” option is selected. Security of this operation is ensured by requesting Login and Password. Default login and Password are: MGEUPS Note: If any of these parameters are changed, the card must be rebooted.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
34/69
Page 35
www.mgeups.com
Network Management Cards
User Manual
3.5.3 Notified Applications
Click the “Notified Application” section in the menu. Security: the administrator has to enter his login/password to view this information. This menu enables:
Z The addition of the supervision stations receiving traps and configuration of the trap type. Z To list all the Notified Applications and the main parameters. Z Simulate events to test notification and shutdown of the Notified Applications.
Up to 50 destinations can be managed by the card. The card is compatible with the Network Shutdown Module and with the legacy SNMP UM-Client Note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list as it is done automatically.
Select an entry in the list to modify the values in the edit zone at the bottom of the page. Note that the Network Shutdown Module and the UM-Client must not be manually modified. The applications in the table appears in the order they have subscribed to the card. Following informations are displayed :
Z Nr : is the index where the application is stored into the table. Z Hostname or IP Address : By priority the hostname of the computer is displayed when the IP address can
be converted into a hostname with a DNS server or if the application has been entered as a hostname (see page Network Management System settings). Otherwise the IP address is displayed.
Z Application Name : sent by the application at subscribe time or manually entered. Z Output : is the number of the output from which the client is powered. Z Configuration : shows where the parameters of Network Shutdown Module comes from : Local(coming
from the application) or Central(coming from the card).
Z The Central Shutdown Configuration is available by clicking on Configuration link. Z Shutdown duration : is the shutdown duration necessary to properly shutdown the computer. Z Shutdown after : is the time available to the user from the Power failure until the launch of the shutoff
sequence of the UPS. This parameter is optionnal.
Many actions are available on this page :
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
35/69
Page 36
www.mgeups.com
Network Management Cards
User Manual
Z Remove : Depending on the kind of application, the selected ones will definitively disappear from the table
as SNMP applications, or they will disappear and automatically re-subscribe as the Network Shutdown Module application.
Z Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the
applications selected, making sure that the applications can be reached over the network.
Z Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected
applications. It enables an easy check to see if the server protection works correctly.- No intervention on the UPS is required.
- Simulated alarms will be processed by the applications selected only.
- Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown Module is running.
Add NMS allows to add a SNMP trap receiver as a Network Management System. Modify NMS allows to modify a SNMP trap receiver.
Both buttons makes appear a new window where it is possible to enter the Application name, the Hostname or IP Address, the Trap community and the severity.
Z Trap community indicates the name of the SNMP community
For more details, read the MIB description document: 34003627zjaa.pdf , available in the Embedded zone of the www.mgeups.com site.
3.5.4 Central Shutdown Configuration
Click the “Notified Application” section in the menu then in “Configuration”.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
36/69
Page 37
www.mgeups.com
Network Management Cards
User Manual
This page is used to define either the shutdown or the notification settings used by the Network Shutdown Modules that connect to Network Management Card. These settings are used by the Network Shutdown Modules if they are in centralized-configuration mode or if their configuration is not valid.
Z Shutdown After (time before shutdown) This is the time in seconds that the system waits following
failure of AC power before initiating the system-shutdown procedure. This value must be selected to provide users with enough time to close their applications and disconnect, but within the battery backup time provided by the UPS. If another criterion occurs before the end of the shutdown timer, the shutdown procedure is immediately run. This parameter is optional, uncheck it to invalidate
Z Shutdown Duration : This is the time in seconds required by the system to go through its shutdown
procedure.
Z Broadcast : Send network notifications to the Administrators and Users groups on events
If you wish to set up a new configuration for the Network Shutdown Modules already set to centralized­configuration mode, proceed as indicated below.
Z Change the Network Shutdown Module parameters in the page “Central Shutdown Configuration”. Z Click the Save button. Open the List of notified applications.
Select the Network Shutdown Modules to receive the new configuration. Press the button “Remove” They reconnect and use the new configuration
3.5.5 Access control
Click the “Access control” section in the menu. To access this page, the login and password are systematically requested if they have not already been
entered. This menu enables configuration of the different parameters enabling secure access to the card via a browser
or SNMP.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
37/69
Page 38
www.mgeups.com
Network Management Cards
User Manual
Z Enter New Manager Login: Text field limited to 10 characters. Enables secure access and modification of
pages. Default value “MGEUPS”.
Z Enter New Password: Text field limited to 10 characters. Enables secure access to the sections of the
Configuration menu. Default value “MGEUPS”.
Z Confirm New Password: Text field limited to 10 characters. Must be strictly identical (including
upper/lower case) to the field above .
Z SNMP Access Control: permits to limit or disable SNMP access.
- Read / Write: All SNMP operations are allowed
- Read only: only read operations can be done. . When selecting this mode,
- Disable: Card doesn't manage SNMP
Z Current Community Read-only is: Enables read-only SNMP access control (GET). Default value “public”. Z Change Community Read-only: Text field limited to 31 characters. This field is only validated after
clicking on “Save” . Default value “public”.
Z Current Community Read/Write is: Enables read and write SNMP access control (GET and SET).
Default value “public”.
Z Change Community Read/Write: Text field limited to 31 characters. This field is only validated after
clicking on “Save” . Default value “public”.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
38/69
Page 39
www.mgeups.com
Network Management Cards
User Manual
Z Change Trap Port Number: Numeric field limited to 65534. Enables forwarding of traps sent by the card to
a port other than the port usually used for SNMP. Default value 162.
Z SSL Activation: When selected, access to Web interface is made in secure mode (https). Telnet
access is disabled and the card is accessible in SSH. Connections with Network Shutdown Modules stay in standard mode (secure TCP) SSL Security Implementation
SSL Îversion 3.0 Method Î TLS_RSA_WITH_RC4_128_MD5 Auth Î RSA Key Exchange Î RSA Encryption Î RC4_128 Digest Î MD5
SSH Security Implementation
SSH v1 Method ==> SSH_CIPHER_3DES Encryption ==> Triple_DES in CBC mode This change takes effect after a card reboot.
Z Authentication for all html pages : Login/password Authentication is required for all pages.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
39/69
Page 40
www.mgeups.com
Network Management Cards
User Manual
3.5.6 Time
Click the “Time” section in the menu.
This menu enables initialisation of the date and time of the card in three different ways.
Z Synchronise manually: Enables initialisation of the date and time of the card, with the values entered in
the Date and Time fields. Values are updated after clicking the “Save” button.
Z Synchronise with computer time: Enables the date and time of your PC to be transferred to the card. This
transfer is made after clicking on the “Save” button. Time is not adjusted regularly, it is set one time after clicking the “Save” button.
Z Synchronise with an NTP server: Enables connection with a time server, either available on the
company’s internal network or on the Web. This server communicates GMT time. The IP address of the time server must be entered, and the time zone of your geographic area must then be selected from the list. Connection is made with the server and the date and time are set after clicking on the “Save” button. Time is updated every hour.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
40/69
Page 41
www.mgeups.com
Network Management Cards
User Manual
The card uses the NTP protocol (UDP 123 port) and the firewall must be set accordingly, no error message is generated if the time server contact fails
Z Daylight Saving Time: Enables corrections due to summer / winter time changes, this option must b e
supported by the NTP server.
Note 1:
Time drift is related to card electronics. It may be up to a maximum of +/- 2min/month.
3.6 Environment
The environment sensor is an option that enables temperature and humidity to be measured, and indication of the position of two external contacts. It is connected with a standard network cable to the Card Settings port of the Network Management Card. On startup, the card automatically detects sensor presence. The main menu then displays an additional section “Environment” with the following elements:
Z Status Z Configuration Z Log
Note 1 This function is only accessible with the DA version software (or superior) for the card. This software can be downloaded on the www.mgeups.com site, from the download Note 2: To switch the serial port to the configuration mode, just disconnect the sensor cable and reinitialise the card by pressing “Reset”. The reverse operation must be performed to manage the environment sensor once again.
section.
3.6.1 Characteristics
Z Temperature measurement from 0 to 70 °C with +/- 1°C accuracy Z Humidity measurement from 0 to 100 % with +/- 6 % accuracy Z Min. / max. time-stamped function for temperature and humidity Z Choice of displaying temperature in Celsius or Fahrenheit Z High and low thresholds, hysteresis and offset adjustment via Web interface Z Possibility of notification of status changes by e-mail, SMS or SNMP trap Z Position detection of 2 dry contacts (maximum sensor/contact distance: 20m) Z Name and status of each contact can be configured Z Recording of events and measurements in the card log Z Possibility of shutting down the installation safely if one of the thresholds is exceeded or if a dry contact
closes
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
41/69
Page 42
www.mgeups.com
Network Management Cards
User Manual
Z Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum
card/sensor distance: 20m)
3.6.2 Environment status
For both measurements, a graduated gauge proposes the following functions: The cursor indicates the current value. Two red zones to the left and right represent the high and low thresholds that can be set on the Environment
Settings page.
When the measured value enters one of these zones, a alarm can be notified (see Notification parameter in the Environment Settings page). Time-stamped minimum and maximum temperatures show the extreme values recorded since the last Reset Min/Max, a thin dotted line shows their positions on the gauge. Min and Max can be forced at any time to the current value by clicking on the Reset Min/Max button.
Calibrate: the sensor is calibrated in the factory, but the user can apply an offset to adjust the measurement. Input # 1 and Input # 2 show the position of the two contacts acquired by the sensor.
The position is displayed with the parameters entered in the Environment Settings page. The last status change of each contact is time-stamped.
The Internet browser updates this page regularly according to the Environment refresh rate parameter on the
System settings page.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
42/69
Page 43
www.mgeups.com
3.6.3 Environment Settings
Network Management Cards
User Manual
The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door, alarms or generator unit). The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the protected system. The Sensor name is the function name given to the sensor, usually it enables location of the sensor.
Temperature: choose the temperature unit (°C or °F) from the selection box. High threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 40 °C / 104
°F.
Low threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 5 °C / 41 °F. Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold.
Default value is 2 °C / 3.6 °F. (Advanced parameters) The high alarm cannot be reactivated while temperature remains above the High threshold – Hyster esis value. The low alarm cannot be reactivated while temperature remains below Low threshold + hysteresis value.
Humidity High threshold: if this value is exceeded, a notification is sent if enabled. Default value is 90%. Low threshold: if this value is exceeded, a notification is sent if enabled. Default value is 5%.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
43/69
Page 44
www.mgeups.com
Network Management Cards
User Manual
Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. Default value is 5%. (Advanced parameters)
The high alarm cannot be reactivated while humidity remains above the High threshold – Hysteresi s value. The low alarm cannot be reactivated while humidity remains below Low threshold + hysteresis value.
Input No 1 and Input No 2: enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning, generator unit, etc.). Max. length is 28 characters. If contact closed and if contact open: are the names associated to the two contact positions. (e.g.: "open" and "closed" for a door, "On" and "Off" for a generator). Each status change triggers a notification if enabled.
Notification includes: Log, Notification by e-mail and generation of SNMP Trap. The list of messages is given in the appendix.
System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the Shutdown option cannot be used. (Advanced parameters)
Security: the administrator has to click on Save and enter his login/password to save any modifications.
3.6.4 Log
The environment sensor’s two measurements, Temperature and Humidity, are recorded at an interval defined by the Environment log interval parameter on the System settings page. By default, this period is 300 seconds. Each measurement is dated and stored in the log of the UPS’ communication card. The size of log files is limited by a time indexing system. The user can Save the log on his workstation at any time, in a CSV format file. He can also Clear the files contained in the card to reset the log.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
44/69
Page 45
www.mgeups.com
Network Management Cards
User Manual
4 Servers protection
4.1 Set-up of the shutdown parameters
The Network Shutdown Module, on protected server boot, subscribes itself automatically to Notified Applications list and sends its essential data:
Z IP address or name of the server on which it is installed, to be notified by the card of any power events Z Time required to shutdown the server (Shutdown Duration, configurable in the Shutdown Module “set-up”
menu): The card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed to manage UPS shutdown without affecting any of the servers protected.
In case of a major power event, the Shutdown Module receives messages from the card and regularly checks its accessibility. The most important messages can generate actions and are sent back to the administrator and users via the network. When the server shuts down, the Shutdown Module unsubscribes itself from the Notified Applications.
4.1.1 Shutdown criteria managed by the Management Card
During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, the first criterion encountered will launch the shutdown procedure. At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid unnecessary discharge of its batteries, depending on its configuration.
4.1.1.1 Backup time before initiating the shutdown procedure (Shutdown After)
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown. This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time. By default, this value is set to 30 minutes. Since GA release, this criterion is not selected in the default configuration
Note 1:
The Network Shutdown Module can also manages its own Shutdown Timer (configurable in the Shutdown Module “set-up” menu) Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down). By default, this parameter is not selected.
4.1.1.2 Initiating the shutdown procedure when the battery level is lower than: (if capacity under)
When the card detects that the remaining backup time percentage is less than the configured level, the shutdown sequence is started. By default, the card uses the value set in the UPS.
Note:
Certain types of UPS only accept pre-defined minimum battery level values (e.g. : 20% or 40% for COMET and PULSAR EXtreme). Check the UPS documentation.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
45/69
Page 46
www.mgeups.com
Network Management Cards
User Manual
4.1.1.3 Shutdown when backup time is less than
When the Network Management Card detects that the percentage of backup time remaining is less than the value set, the shutdown sequence is started.
4.1.1.4 Shutdown duration
Duration required for the systems protected by the Shutdown Modules to shut down (in seconds).
4.1.2 Specific set-up for long autonomy installation (> 30 mn)
On installation where the backup period is longer than 30 minutes, the Network Management Card will initiate automatically a shutdown at the end of the shutdown timer if this parameter is selected on the “Shutdown parameters” page.
4.1.3 Controlled outlets
Some UPS models are equipped with outlets (typically 2), that can be controlled individually (while still remaining dependent on the main UPS control). Shutdown of the main outlet systematically causes shutdown of the programmable outlets.
Depending on the UPS range, the following notation is used to mark these outlets:
Z Main outlet: Main or 1 Z Programmable outlet 1 1 or 2 Z Programmable outlet 2 2 or 3
4.1.4 Connecting a server protected by UM-Client to a programmable outlet
Only UM-Client is compatible with the programmable outlets, the Network Shutdown Module will be compatible with release 3.0. After connecting the server electrically to one of the controlled outlets, UM-Client must be informed of the outlet number to which it is connected. Start UM-Editor (installed with Solution-Pac / WAN), select the “Switchable plug” box and specify the outlet number (1=main, 2 or 3) in the “Receptacle Number” field.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
46/69
Page 47
www.mgeups.com
Network Management Cards
User Manual
4.1.4.1 Load shedding or sequential shutdown
It is possible to optimise backup time by shutting down non-priority equipment or sequencing the shutdown of several devices. Two shutdown criteria are possible: Shutdown of outlets after a set battery back-up time (ShutOff Delay) Shutdown of outlets at a given battery discharge level (ShutOff Level) It is possible to specify values for both criteria. The first criterion reached will initiate server shutdown.
4.1.4.2 Sequential startup
It is possible to delay outlet power-on to reduce inrush currents on startup or to sequence the startup of several devices. Outlet startup after a given time is based on startup of the main outlet (Restart delay)
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
47/69
Page 48
www.mgeups.com
y
Network Management Cards
User Manual
4.2 The different server and UPS shutdown sequences
4.2.1 Extended power outage, shutdown initiated by the Shutdown Timer
During battery backup time, the Shutdown Timer of the Network Management Card is reached: after a user­defined backup time period, the shutdown of all servers is initiated, followed by the UPS shutdown (depending on its configuration). The UPS restarts when utility power is restored (depending on its configuration).
Z Shutdown Duration: Maximum value of shutdown times of the Network Shutdown Modules and UM-
Clients subscribed to the card and depending on the main UPS outlet. This value is updated each time a client subscribes/ unsubscribes.
Z Shutdown Duration 1 (2): Maximum value of shutdown times of the UM-Client subscribed to the card and
dependent on outlet 1 (2). This value is updated each time a UM-Client dependent on outlet 1 (2) subscribes /unsubscribes.
Note: During battery operation, these values are not updated.
4.2.1.1 Main UPS outlet
Shuts down after the ShutDown Timer + Shutdown Duration after having stopped the servers Restarts when utility power is restored (possibility of programming a restart delay)
Utility
Trap,11, Trap 29 ShutdownTim
NSM / UMC Shutdown Reboot
Main outlet OFF
ON
Trap 17
Trap 31 Shutdown
OFF ON
Trap 18
Duration
Trap 32
4.2.1.2 Programmable outlet 1
Shuts down after Shutoff Delay 1 after having stopped the servers dependent on outlet 1 Restarts when utility power is restored by applying Restart Delay 1
Trap 29 ShutoffDelay 1 Restart
Dela
Trap 31
Trap 32
1
UM-Client
Outlet 1 OFF
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
48/69
Page 49
www.mgeups.com
4.2.1.3 Programmable outlet 2
Shuts down after Shutoff Delay 2 after having stopped the servers Restarts when utility power is restored by applying Restart Delay 2
Trap 29 ShutoffDelay 2 Restart
Trap 31 Shutdown
Duration.2
Trap 32
UM-Client Shutdown
Outlet 2 OFF
Network Management Cards
User Manual
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
49/69
Page 50
www.mgeups.com
y
y
Network Management Cards
User Manual
4.2.2 Extended power outage, shutdown initiated by the “Low battery power”
message
When the ”Low battery power” message is displayed, the UPS is shut off after taking into account the shutdown duration of the servers.
“Low battery power”: The message appears if either of the two following criteria is checked:
- Low Battery Level
- Minimum remaining backup time (Low Battery Delay)
4.2.2.1 Main UPS outlet
Utility OFF
Trap 17 Trap 11
NSM / UMC Shutdown
Main outlet OFF
4.2.2.2 Programmable outlet 1
Trap 29 ShutoffTimer.1 Restart
UM-Client
Outlet 1 OFF
Low
battery
Trap 31 Shutdown
Duration
Trap 32
Trap 31 Sh`down
Duration.
Trap 32
Shutdown
Trap 18 Trap 10
Dela
.1
4.2.2.3 Programmable outlet 2
Trap 29 ShutoffTimer.2 Restart
Dela
Trap 31 Sh`down
Duration.
Trap 32
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
.2
Page
50/69
Page 51
www.mgeups.com
UM-Client
Outlet 2 OFF
Network Management Cards
User Manual
Shutdow Rebo
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
51/69
Page 52
www.mgeups.com
Network Management Cards
User Manual
4.2.3 Extended power outage, shutdown initiated by the Shutdown Timer, but utility
restoration before the end of the Shutdown Duration
If utility power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for a period equal to the forced reboot time delay
4.2.3.1 Main UPS outlet
Utility OFF
Trap 17 Trap 11
NSM / UMC
Main outlet OFF
4.2.3.2 Programmable outlet 1
Trap 29 ShutoffTimer.1
UM-Client
ShutdownTimer Trap
18
Trap 31
ShutDurati
Trap 32 10s
Reb
Resta
Trap 31
Shutdow
Trap 32
Outlet 1 OFF
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
52/69
Page 53
www.mgeups.com
y
4.2.3.3 Programmable outlet 2
Trap 29 ShutoffTimer.2 Restart
UM-Client
Outlet 2 OFF
Trap 31
Shutdow
Trap 32
Network Management Cards
User Manual
Dela
.2
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
53/69
Page 54
www.mgeups.com
Network Management Cards
User Manual
4.2.4 Off/On command
Off/On command is sent from the “UPS control” page After a power on, controls are disabled during 120 secondes to allow the server to reboot.
4.2.4.1 Main outlet
Utility
Off command with a
shutdown delay = 2
minutes Trap 29 Trap 31
NSM / UMC
Main outlet OFF
4.2.4.2 Programmable outlet 1
Trap 29 ShutoffTimer.1
UM-Client
Outlet 1 OFF
2
minutes
Trap 31
On command with a
restart delay = 0
minutes
Shutdow
Trap 32
Resta
Shutdow
Trap 32
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
54/69
Page 55
www.mgeups.com
y
4.2.4.3 Programmable outlet 2
Trap 29 ShutoffTimer.2 Restart
UM-Client
Outlet 2 OFF
Trap 31
Shutdow
Trap 32
Network Management Cards
User Manual
Dela
.2
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
55/69
Page 56
www.mgeups.com
Network Management Cards
User Manual
5 Configuring a set of cards with Mupgrade
This feature is particularly useful to configure large UPSs installed base. The Remote configuration features of Mupgrade allows you to import, modify and export configuration files from
and to Network Management Cards. Configure all your Network Management Cards in four step :
1. Configure a Network Management Card located on the network through the html interface to create a master configuration..
2. Import this configuration from the master card in Mupgrade.
3. Edit and change some parameters , select the fields which must be overwritten in the destination cards and save the new configuration in a file.
4. Export the new configuration to other cards which have same firmware release as the master card
Read the relevant documentation available for download on the www.mgeups.com web site, in the “Download
area – embedded Software” section.
6 Configuration in local mode and via Telnet or SSH
6.1 Configuration in local mode
Z Use the cable supplied with the card. Z Connect the card to a computer equipped with a hyper-terminal type emulator. The serial link should be set
at 9600 bauds, 8 bits, no parity, 1 stop bit and no flow control.
Z Check that UPS power is on. Z A few seconds after terminal opening, press the "Enter” button. The menu asks you to enter your password
(MGEUPS by default), and then press Enter”.
Z The card will disconnect itself after 3 minutes of inactivity. Z The menu is in English only.
+=========================================================================== + | [ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] | +=========================================================================== + Enter Password: ******
+=========================================================================== + | [ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] | +=========================================================================== +
1. Agent Configuration
2. UPS Parameters
3. Access Control Table
4. Reset Configuration To Default
5. Reset Agent
0. Exit
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
56/69
Page 57
www.mgeups.com
Network Management Cards
User Manual
Please Enter Your Choice =>
6.1.1 Choice 1: SNMP agent configuration menu
The blue lines are those displayed on screen.
+============================================================================+ | [ Agent Configuration Menu ] | +============================================================================+ SNMP/Web Agent Version : GA (SN 49DC40116)
Indicates the version level of the software and the serial number of the card.
Ethernet address : 00 E0 D8 09 85 78
MAC address of the card.
Agent BIOS Version : AB
Version number of the BIOS.
1. IP Address : 172.17.133.120
To change the IP address of the card, press “1” then “Enter”. Specify an IP address, then press “Enter’.
2. Gateway Address : 172.17.1.1
Enter the name of the gateway to be used to communicate with other sub-networks.
3. Network Mask : 255.255.0.0
Enter the mask of the sub-network defining the user group to which the card is connected.
4. sysContact : Computer Room Manager
Enter the name of the person responsible for the UPS.
5. sysName : MGEUPS
Enter a string of characters to identify the UPS. 32 characters maximum
6. sysLocation : Computer Room
Enter a string of characters to identify the installation location of the UPS. 32 characters maximum
7. Community Read-Only : public
Enter the name of the read-only community (by default = public) 31 characters maximum
8. Community Read/Write : public
Enter the name of the read/write community. This name is used by the UM-Clients to subscribe to the table of notified Clients. It is recommended to personalise this name. Value by default “public”.
31 characters maximum
9. HTTP Login Username : MGEUPS
Text field limited to 10 characters. Enables secure access to the sections of the Configuration menu. Default value “MGEUPS”.
a. Manager Password : *
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
57/69
Page 58
www.mgeups.com
Network Management Cards
User Manual
Text field limited to 10 characters. Enables secure access to the sections of the Configuration menu. Default value “MGEUPS”.
b. BOOTP/DHCP Enabled : Enabled
Authorises the configuration of network parameters with your BootP/DHCP as a startup mode (choose enable). Card operating mode with the server: after all reboots, the card (if this option is enabled), attempts to recover the network parameters from the server for 10 seconds. If no response is obtained from the server, the card boots with the last parameters saved from the previous start.
0. Return to previous menu
Goes back to the previous menu.
6.1.2 Choice 2: UPS parameters
The blue lines are those displayed on screen.
+============================================================================+ | [ UPS Parameters Menu ] | +============================================================================+ SNMP/Web Agent Version : CAb8 (SN 49DC40116) Ethernet address : 00 E0 D8 09 85 78 Agent BIOS Version : AB
1. Log Periodicity : 60
Value between 20 and 99999. Enables initialisation of the save frequency of Measurements, Events and System in the Log menu. Default value = 60 sec.
2. Trap Port Number : 162
Numeric field limited to 65534. Enables forwarding of the traps sent by the card to a port other than the one usually used for SNMP. Default value 162
3. System Date (yyyy/mm/dd) : 2003/06/10
Enables adjustment of the date
4. System Time (hh:mm:ss) : 14:47:53
Enables adjustment of the time
0. Return to previous menu
6.1.3 Choice 3: Access control
+============================================================================+ | IP Address Community String Access | +============================================================================+ [1] 0.0.0.0 public NotAccess [2] 0.0.0.0 public NotAccess [3] 0.0.0.0 public NotAccess [4] 0.0.0.0 public NotAccess
COMMANDS -
1. Modify - Modify an entry of table
2. Reset - Reset an entry to default from table
0. Return to previous menu
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
58/69
Page 59
www.mgeups.com
Network Management Cards
User Manual
Please Enter Your Choice =>
This menu enables configuration of access to the four supervision stations (identified by the IP address) with read/write community names different to those already defined in the card “1” menu. First enter the figure corresponding to the command to be carried out, then the number of the target input. The example below shows how to configure the read/write rights for a station (172.17.1.1) with a community name MyCom:
Please Enter Your Choice => 1 Entry Number : 1 Enter IP address : [0.0.0.0] 172.172.1.1 Enter Community String : [public] MyCom Select Access Type ­ [NotAccess]
1. Read
2. Read/Write
3. NotAccess
Please Enter Your Choice => 2 +============================================================================+ | IP Address Community String Access | +============================================================================+ [1] 172.172.1.1 MyCom Read/Write
6.1.4 Choice 4: Restore default configuration
Use this function to restore the card’s factory configuration. Reboot the card so that the network parameter changes are taken into account.
6.1.5 Choice 5: Reset the card
Use this function to reboot the card
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
59/69
Page 60
www.mgeups.com
Network Management Cards
User Manual
6.2 Configuration via Telnet
You can access the configuration menu (see “configuration in local mode” section) from a station equipped with the Telnet protocol. As soon as the card is accessible on the network, enter the command:
telnet < card IP address > to access the menu. The password defined by default is MGEUPS.
The card will disconnect automatically after 3 minutes of inactivity.
6.3 Configuration via SSH
You can access the configuration menu (see “configuration in local mode” section) from a station equipped with the SSH protocol when https option is selected. The NMC implements SSH V1 and 3DES encryption cipher only, connection use port 22.
when user connect to NMC by SSH, the screen will hold about 10 seconds for process encryption cipher.
6.3.1 PuTTY SSH Client Program
PuTTY is a free implementation of Telnet and SSH for Win32 and Unix platforms, along with an xterm terminal emulator. You can get the PuTTY by
http://www.chiark.greenend.org.uk/~sgtatham/putty/
Here after, we will show you how to set up PuTTY programme for connecting to NMC card by SSH V1 protocol.
Execute PuTTY and select the following options:.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
60/69
Page 61
www.mgeups.com
Select SSH :
Network Management Cards
User Manual
and Clic on « Open » to start connection
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
61/69
Page 62
www.mgeups.com
Network Management Cards
User Manual
7 Maintenance
7.1 Software upgrade
7.1.1 Card firmware upgrade using Mupgrade (Windows)
This feature is particularly useful to upgrade a large UPS installed base in one operation. Read the relevant documentation available for download on the www.mgeups.com web site, in the “Download
area – embedded Software” section.
7.1.2 Card software upgrade via TFTP (UNIX and Windows)
Upgrading is also possible with TFTP command. Generic command is:
tftp -i @IP put nmc_fb.bin upgrade@password@username Where:
-i indicates binary mode
@IP is the address of the NMC card nmc_fb.bin is the firmware name @password value defined in the acces control page @username value defined in the acces control page
Check syntax depending of your operating system
7.1.3 Recovery tool software via the serial link
Read the relevant documentation available for download on the www.mgeups.com web site, in the “Download
area – embedded Software” section.
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
62/69
Page 63
www.mgeups.com
8 Appendices
8.1 Tables of alarms and events
8.1.1 Alarm table
English French
Battery Fault Défaut batterie Output On Battery Sortie alimentée par batterie Low Battery Fin d’autonomie UPS Over Temperature Défaut température Output not protected Sortie non protégée UPS Overload Surcharge onduleur Output On Bypass Sortie sur Bypass Charger Fault, Not Charging Battery Utility failure Perte secteur No Battery Pas de batterie Replace Battery Batterie à remplacer Unavailable Battery Batterie indisponible Boost Activated on UPS Onduleur en mode Boost Buck Activated on UPS Onduleur en mode Buck <Sensor name>: Temperature is above high threshold xx °C "<Sensor name>: Humidity is above high threshold xx %", <Sensor name>: Temperature is below low threshold xx °C <Sensor name>: Humidity is below low threshold xx % <Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when open label>
Défaut chargeur
<Sensor name>: La température est au dessus du seuil haut xx °C <Sensor name>: L'humidité est au dessus du seuil haut xx %", <Sensor name>: La température est en dessous du seuil bas xx °C <Sensor name>: L'humidité est en dessous du seuil bas xx % <Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when open label>
Network Management Cards
User Manual
8.1.2 UPS event table
English French
Battery fault Défaut batterie Battery OK Fin défaut batterie Replace battery Batterie à remplacer Battery replaced Batterie remplacée Low battery Fin d’autonomie UPS return from low battery Fin préalarme d'autonomie UPS battery charger is not active Chargeur batterie arrêté UPS battery charger is active Chargeur batterie en marche UPS battery entering minimum condition
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Batterie en charge minimum
Page
63/69
Page 64
www.mgeups.com
Network Management Cards
User Manual
UPS battery exiting from minimum condition Output on battery Sortie alimentée par batterie Return on UPS Sortie sur onduleur Output on Bypass Sortie sur Bypass Bypass : Return on UPS Sortie sur onduleur UPS bypass unavailable Bypass indisponible UPS bypass available Bypass disponible Utility failure Perte secteur Utility restored Retour secteur Boost activated on UPS Onduleur e n mode Boost Boost de-activated on UPS Mode Boost désactivé UPS overload Surcharge onduleur UPS return to normal load Fin de surcharge onduleur UPS over temperature Défaut température UPS return to normal temperature Fin de défaut température %s on sequence started Début séquence de démarrage %s %s on sequence cancelled Arrêt séquence de démarrage %s %s on sequence in progress Séquence de démarrage %s en cours %s on sequence completed Fin séquence de démarrage %s %s off sequence started Début séquence d’arrêt %s %s off sequence cancelled Arrêt séquence d’arrêt %s %s off sequence in progress Séquence d’arrêt %s en cours %s off sequence completed Fin séquence d’arrêt %s %s toggle (off/on) sequence started Début séquence d’arrêt/marche %s %s toggle (off/on) sequence cancelled %s toggle (off/on) sequence in progress %s toggle (off/on) sequence completed UPS Outlet 1 Outlet 2 UPS communication failed Perte de communication avec l’onduleur UPS communication restored Retour de communication avec l’onduleur Unavailable battery Batterie indisponible Battery available Batterie disponible UPS waiting for battery charging condition UPS reached battery charging condition UPS fault défaut interne UPS OK Fin défaut interne UPS passed battery test Test batterie terminé UPS failed battery test Test batterie en défaut UPS enter environment external alarm UPS exit environment external alarm Buck activated on UPS Onduleur en mode Buck Buck de-activated on UPS Mode Buck désactivé Normal input switch (Q1) closed Interrupteur d'entrée (Q1) fermé Normal input switch (Q1) open Interrupteur d'entrée (Q1) ouvert
Fin batterie en charge minimum
Arrêt séquence d’arrêt/marche %s Séquence d’arrêt/marche %s en cours Fin séquence d’arrêt/marche %s onduleur
prise 1 prise 2
UPS waiting for battery charging condition UPS reached battery charging condition
UPS enter environment external alarm UPS exit environment external alarm
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
64/69
Page 65
www.mgeups.com
Network Management Cards
User Manual
Bypass switch (Q4S) closed Interrupteur bypass (Q4S) fermé Battery switch (QF1) closed Disjoncteur batterie QF1 fermé Battery switch (QF1) open Disjoncteur batterie QF1 ouvert Manual bypass switch (Q3BP) closed Manual bypass switch (Q3BP) open Interrupteur bypass manual (Q3BP) ouvert Output switch (Q5N) closed Interrupteur de sortie (Q5N) fermé Output switch (Q5N) open Interrupteur de sortie (Q5N) ouvert <Sensor name>: Temperature is below low threshold %d °C <Sensor name>: Temperature is above high threshold %d °C <Sensor name>: Temperature is in normal range <Sensor name>: Humidity is below low threshold %d % <Sensor name>: Humidity is above high threshold %d % <Sensor name>: Humidity is in normal range <Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when open label> Output not protected Sortie non protégée
Output On
Interrupteur bypass manual (Q3BP) fermé
<Sensor name>: La température est en dessous du seuil bas %d °C <Sensor name>: La température est au dessus du seuil haut %d °C <Sensor name>: La température est revenue à un niveau normal <Sensor name>: L'humidité est en dessous du seuil bas %d % <Sensor name>: L'humidité est au dessus du seuil haut %d % <Sensor name>: L'humidité est revenue à un niveau normal <Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when open label>
Sortie alimentée
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
65/69
Page 66
www.mgeups.com
Network Management Cards
User Manual
8.1.3 System alarm table
English French
Cold boot Démarrage de la carte Warm boot Réinitialisation de la carte Network link up Carte connectée au réseau Network link down Carte déconnectée du réseau Agent Card Restart Redémarrage de la carte Parameters reset to default Paramètres par défaut reprogrammés Firmware upgrade with version xx Carte reprogrammée avec version xx History log cleared Historique des mesures effacé UPS event log cleared Historique des événements effacé Agent event log cleared Historique système effacé History log interval changed Période des historiques modifiée Communication failure Perte de communication Communication restored Retour de communication Time changed by user Date et heure réglées manuellement Time changed by server Date et heure synchronisées par serveur Time changed by RTC Date et heure réglées par RTC Access to SMTP server failed to mail to recipient Access to SMTP server succeed to test mail to recipient Environment log cleared Historique des mesures environnement effacé <Sensor name> communication failed
L'accès au serveur SMTP a échoué pendant l'envoi au destinataire de mail L'accès au serveur SMTP a réussi pour le test d'envoi au destinataire de mail
<Sensor name> communication restored
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
66/69
Page 67
www.mgeups.com
Network Management Cards
User Manual
8.2 Glossary
Bootp:
Protocol based on UDP used to allocate an IP address corresponding to an Ethernet card during the startup phase. Defined by the RCF 951
Community name:
Access key to access SNMP agent information DHCP Dynamic Host Configuration Protocol
This IETF protocol enables remote, automatic, self-configuration of the IP addresses of a workstation. DNS Domain Name Sevicel
The DNS protocol ensure correspondence between the name of a machine and its IP address DST Daylight Saving Time
Extension of the NTP protocol to manage time changes in summer and winter
E-mail
Electronic means of transmitting messages and/or files.
Gateway
Interconnection equipment between networks with different conventions, to enable communication between them
HTML
(HyperText Markup Language) Language used to describe hypertext pages on the web. HTTPS : is the secure version of HTTP, the communication protocol of the World Wide Web. It was invented by
Netscape Communications Corporation to provide authentication and encrypted communi cation a nd is used in electronic commerce.
IP
Internet Protocol. Network layer protocol in the TCP/IP stack offering a no-connection inter-network service . The IP protocol offers functions for addressing, service type specification, fragmentation and re-assembli ng and security. Defined in RFC 791.
MD5
Message Digest 5. Algorithm producing an output message from an input message of arbitrary length, in the form of a replica or s mary 128 bit message. Intended for digital signature applications requiring large files to be compressed in total security before being coded with a private key, using a public key algorithm, like RSA.
MIB MANAGEMENT INFORMATION BASE
- Group of software commands to control and administrate a device through the network. Each type of device
(server, hub, PC, UPS, etc.) has its own MIB – The IETF has proposed a standard MIB for each group of devices (hubs, for example) to simplify administration if they come from different suppliers
MultiSlot
Expander module for MGEUPS communication card. NETWORK MANAGEMENT CARD
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
67/69
Page 68
www.mgeups.com
Network Management Cards
User Manual
Communication cards to supervise UPS and communicate with Network Shutdown Module to insure power protection on servers
NETWORK MANAGEMENT PROXY Communication software installed on a PC connected to the UPS to supervise it and communicate with Network Shutdown Module to insure power protection on servers
NMS NETWORK MANAGEMENT STATION (SNMP) The dedicated PC or workstation is used on the company’s networks to administrate all devices connected to the network. Data are transmitted using the SNMP protocol. Popular NMS systems include HP OpenView, IBM Tivoli, CA Unicenter, etc.
NETWORK SHUTDOWN MODULE Protection software installed on a PC or server to protect it
NTP Network Time Protocol Protocol to position a set of machines on a network at the same time.
Programmable outlet (controlled outlet): Outlet that can be remote-switched on or off. UM-Client components enable management of such outlets.
REBOOT – To restart a system after an interruption. – To perform an obstacle-free “reboot”, it is essential that the system is correctly and carefully shut down beforehand. – The reboot is usually automatic if the computer is re-supplied with electricity (from the utility or from the UPS).
RFC
Request for Comments. All documents defining internal Internet operation. SNMP (SIMPLE NETWORK MANAGEMENT PROTOCOL)
Protocol used to remote-supervise, administrate and control devices connected to a company network. SMTP (SIMPLE MAIL TRANSFER PROTOCOL)
Enables message transfer between e-mail servers or between the client and its server. It is based on the server’s port 25. It is described in RFC 821
SSL (Secure Sockets Layers) is a protocol developed by Netscape Communications Corporation for securing data transmission in commercial transactions on the Internet. Using public-key cryptography, SSL provides server authentication, data encryption, and data integrity for client/server communications
Subnet mask:
Mask of bits used to identify and differentiate the network address and the equipment address in an IP address. Normally, the mask is automatically determined by the class of address, which defines in a unique manner the network part/equipment part division of the IP address.
- Class A: internet address: 255.0.0.0.
- Class B: internet address: 255.255.0.0.
- Class C: internet address: 255.255.255.0.
TCP/IP
Transmission Control Protocol/Internet Protocol. Common name of a series of protocols developed by the DOD in the US to help build Internet networks throughout the world.
Telnet
THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card
– User Manual 34003676EN/GA
Page
68/69
Page 69
www.mgeups.com
Network Management Cards
User Manual
Internet protocol used for terminal emulation, i.e. enabling a computer to connect with a server as if it was a simple terminal locally connected to this server.
Trap (SNMP) This term describes an event that affects an MIB variable. Traps are sent to the manager, which is programmed to perform specific tasks upon reception of the traps.
UM-Client
UM-Client is a legacy software package (SNMP manager) that uses the information sent by the agent dedicated to the MGE UPS in order to inform users of the computer of the power quality status. In case of a power failure, UM-Client triggers a graceful shutdown procedure at the end of a preset battery runtime.