MGE UPS Systems 4000 RT User Manual

Page 1
www.mgeups.com
Pulsar MX
4000 RT 5000 RT
Installation and user manual
R
E
D
I
V
O
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
E
N
I
N
U
E
H
T
34003641FR/AA - Page 1
Page 2
34008030EN/AA - Page 2
Page 3
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar MX range has been designed with the utmost care. We recommended that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System)
Warning: this is a class A UPS product. In a domestic environment, this product may cause radio interference, in wich case, the user may be required to take additional measures. Output cables should not be longer than 10 meters. If the device must be installed in overvoltage category III or IV envoronments, additional upstream overvoltage protection must be provided for.
Before installing Pulsar MX, please read the booklet on the required safety instructions. Then follow the indications in this manual.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar MX range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
Environmental protection
MGE UPS SYSTEMS has implemented an environmental-protection policy. Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Introduction
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use comprises over 50% of recycled cardboard. Sacks and bags are made of polyethylene. Packing materials are recyclable and bear the appropriate identification symbol .
Material Abbreviation Symbol
number
Polyethylene terephthalate PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
MGE UPS SYSTEMS will process products at the end of their service life in compliance with local regulations. MGE UPS SYSTEMS works with companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed to comply with regulations and in view of correct disposal.
"Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
The
(*) For more information or to contact the Product Environmental manager, use the www.mgeups.com -> About us -> Environment.
"Environmental Form" on the site:
34008030EN/AA - Page 3
Page 4
Introduction
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio signal.
In the illustrations on the following pages, the symbols below are used:
LED off
LED on
34008030EN/AA - Page 4
Page 5
Contents
1. Presentation
1.1 Standard positions ...................................................................................................................... 7
Tower position................................................................................................................................ 7
Rack position ................................................................................................................................. 7
1.2 Rear panels................................................................................................................................... 8
Pulsar MX 4000 RT / 5000 RT....................................................................................................... 8
Pulsar MX EXB RT (optional battery module)................................................................................ 8
1.3 Display and control panel ........................................................................................................... 9
1.4 Options ......................................................................................................................................... 9
Rack mounting kit .......................................................................................................................... 9
ModularEasy MX.......................................................................................................................... 10
Battery extensions for UPS backup times up to 80 minutes.........................................................11
Battery Integration System ...........................................................................................................11
Battery extension cable ................................................................................................................11
2. Installation
2.1 Unpacking and contents check ................................................................................................ 12
2.2 Internal batteries connection (Battery start-up)........................................................................ 12
2.3 Installation in tower position .................................................................................................... 13
2.4 Installation in rack position ...................................................................................................... 14
Adjustment of the orientation of the logo and control panel......................................................... 14
UPS module rack mounting ......................................................................................................... 14
UPS or battery module rack mounting......................................................................................... 15
2.5 Communication ports................................................................................................................ 16
Connection to the RS232 communication port ............................................................................ 16
Connection to the communication port by relays ......................................................................... 16
Remote Power Off communication port ....................................................................................... 17
Installation of communication cards.............................................................................................17
2.6 Required protective devices and cable cross-sections ......................................................... 18
Recommended upstream protection............................................................................................ 18
Recommended downstream protection ....................................................................................... 18
Required cable cross-sections..................................................................................................... 18
2.7 Connection of input/output power cables to UPS terminals ................................................. 19
2.8 Connection of IEC cables to output receptacles .................................................................... 20
3. Operation
3.1 Initial start-up ............................................................................................................................. 21
3.2 Final start-up sequence............................................................................................................. 21
3.3 Operating modes ....................................................................................................................... 22
3.4 Operation on battery power...................................................................................................... 23
3.5 Return on Normal AC source.................................................................................................... 23
3.6 UPS shutdown............................................................................................................................ 24
4. Access to measurements and personalisation data
4.1 Display organisation.................................................................................................................. 25
4.2 Access to measurements.......................................................................................................... 25
4.3 Access to UPS set-up and maintenance using the control panel......................................... 25
4.4 UPS set-up.................................................................................................................................. 26
4.5 Maintenance............................................................................................................................... 27
4.6 Personalisation using external software ................................................................................. 27
34008030EN/AA - Page 5
Page 6
Contents
5. Troubleshooting
5.1 Troubleshooting LEDS (21) and (22).........................................................................................28
5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support.............................28
5.3 Troubleshooting requiring MGE UPS SYSTEMS after-sales support....................................29
6. Life Cycle Monitoring (LCM)
6.1 Description..................................................................................................................................30
Get free offers...............................................................................................................................30
Secure your installation power continuity .....................................................................................30
Reset or disable LCM...................................................................................................................31
7. Maintenance
7.1 Hot swapping the power sub-module.......................................................................................32
7.2 Hot swapping the battery sub-module .....................................................................................32
7.3 Maintenance on a UPS equipped with the ModularEasy MX module....................................33
7.4 Training centre............................................................................................................................33
8. Appendices
8.1 Technical specifications ............................................................................................................34
8.2 Glossary ......................................................................................................................................35
34008030EN/AA - Page 6
Page 7
1.1 Standard positions
Tower position
1. Presentation
Dimensions (H x W x D) in mm / Inches
Pulsar MX 4000 RT 444.5 x 131 x 700 /
17.5 x 5.16 x 27.56
Pulsar MX 5000 RT 444.5 x 131 x 700 /
17.5 x 5.16 x 27.56
Pulsar MX EXB RT 444.5 x 131 x 650 /
17.5 x 5.16 x 25.6
Weights in kg / lbs
Pulsar MX 4000 RT 57 / 125
Pulsar MX 5000 RT 57 / 125
Pulsar MX EXB RT 70 / 154
Rack position
Dimensions (H x W x D) in mm / Inches
Pulsar MX 4000 RT 131 x 444.5 x 700 /
5.16 x 17.5 x 27.56
Pulsar MX 5000 RT 131 x 444.5 x 700 /
5.16 x 17.5 x 27.56
Pulsar MX EXB RT 131 x 444.5 x 650 /
5.16 x 17.5 x 25.6
Weights in kg / lbs
Pulsar MX 4000 RT 57 / 125
Pulsar MX 5000 RT 57 / 125
Pulsar MX EXB RT 70 / 154
34008030EN/AA - Page 7
Page 8
1. Presentation
1.2 Rear panels
Pulsar MX 4000 RT / 5000 RT
7
8
9
11
12
13
SWITCHED GROUP 2
PARALLEL
RS232 CONTACTS
SWITCHED GROUP 1
BAT NO. RPO
(1) Two groups of 2 programmable (10A)
1
outlets for connection of equipment (2) Groups of 4 (10A) outlets for connection of equipment
2
(3) Groups of 2 (16A) outlets for connection of equipment
(4) 12A thermal switch (5) 20A thermal switch
3
(6) 12A thermal switch (7) Output terminal block (8) Normal AC source terminal block
4
5
6
10
14
15
16
(9) Connector for additional battery module (10) Slot for optional communication card (11) Connector for parallel operation (12) USB communication port (13) RS232 communication port (14) Communication port by relay (15) Connector for automatic detection of
battery module(s) (16) Connector for Remote Power Off control (RPO)
Pulsar MX EXB RT (optional battery module)
BATTERY
CONNECTOR
180Vdc
18
BATT. NO.
BATTERY BREAKER 50Adc
BATTERY
CONNECTOR
180Vdc
18
(17) Connectors for automatic detection of
battery module(s) (18) Connectors for battery modules (to the UPS or to the other battery modules) (19) Battery circuit breaker
17
19
34008030EN/AA - Page 8
Page 9
1.3 Display and control panel
25
24
30
31
32
33
ESC
20 21 22
IO
1. Presentation
(20) Load protected LED
(21) Downgraded operation LED (22) Load not protected LED (23) Alphanumeric display (24) Escape (cancel) button (25) (26) Function buttons
(scroll down / scroll up)
(27) Enter (confirm) button (28) UPS OFF button
23
(29) UPS ON button (30) Rectifier LED (31) Battery LED (32) Inverter LED
26
(33) Bypass LED
27
(34) Load powered LED
28
29
1.4 Options
Rack mounting kit
Telescopic rails for Pulsar MX RT mounting in 19’’ enclosure with mounting hardware (part number 68002)
34
(35) Ear hangup
35
36
37
(36) Rear bracket system for transportation (37) Telescopic rails, 639 mm to 1005 mm
length (27.36’’ to 39.96’’)
34008030EN/AA - Page 9
Page 10
1. Presentation
ModularEasy
Pulsar MX ModularEasy enables parallel
operation when combining two Pulsar MX UPSs. Consequently you can enhance the availbility level of your equipment (N+1 redundancy). You can also double your secured power capacity according to your needs (migration, network extension...). In the unlikely event a major fault would occur, the manual maintenance bypass of Pulsar MX ModularEasy would allow the UPS maintenance without interrupting your connected equipment.
In single unit mode, Pulsar MX ModularEasy combined with one Pulsar MX UPS adds a second level of availability to your installation.
The manual bypass mode allows the replacement of the UPS without any interruption to the connected equipment in case of a major fault that would not be related to the most critical components of the UPS (i-e front-accessible, hot-swappable Battery and Power Sub-Modules).
Example of Pulsar MX ModularEasy connected with two UPSs in parallel operation
SWITCHED GROUP 2
SWITCHED GROUP 1
SWITCHED GROUP 2
SWITCHED GROUP 1
UPS 1 (Pulsar MX RT)
Pulsar MX RT ModularEasy
UPS 2 (Pulsar MX RT)
PARALLEL
RS232 CONTACTS
BAT NO. RPO
PARALLEL
RS232 CONTACTS
BAT NO. RPO
UPS output to load
AC Normal input
34008030EN/AA - Page 10
Page 11
Battery extensions for UPS backup times up to 80 minutes (at full load)
Pulsar MX RT offers a standard backup time of 5/7 minutes at full load. To increase backup time, it is possible to connect Pulsar MX EXB RT modules to the UPSs.
Battery extensions for Pulsar MX RT
1. Presentation
Pulsar MX 4000 RT:
Pulsar MX 5000 RT:
Battery Integration System
Pulsar MX 4000 RT / 5000 RT
7 min
5 min
Pulsar MX
+++
EXB RT
29 min
22 min
Pulsar MX EXB RT
53 min
41 min
The Battery Integration System is intended for extended backup time configurations to conveniently stack and secure up to 9 modules on the same cart (swivel wheels with brakes, leveling feet, seismic side panels, plates to lock modules and screws included).
Pulsar MX EXB RT
80 min
62 min
Battery extension cable (1,8 m / 6 ft)
This extended battery cable will be used instead of the standard battery cable when battery modules are distant from each other (located in two different enclosures, for instance).
34008030EN/AA - Page 11
Page 12
2. Installation
2.1 Unpacking and contents check
40
41
43
42
44
45
47
46
48
IP= MAC=00E0D8FF855E
Card Settings
100 10
UPS data
Reset
1 2 ON
RS232 Download
RS232
ETHERNET
49
66074
(40) Pulsar MX 4000 or 5000 UPS.
(41) Two sets of tower stands.
(42) RS232 communications cable
(43) Product documentation.
(44) 4 cable lockers.
(46) Screw driver.
(47) Solution-Pac power management suite CD-ROM.
(48) Network Management card (optional, or standard in NetPack version).
(49) 4 IEC 10A output cables.
(45) Telescopic rails for rack enclosure with mounting
hardware (optional, or standard with NetPack version).
Packaging must be destroyed according to waste management standards. Recycling icons are displayed for easy selection.
A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out on these modules must be done so by qualified staff.
2.2 Internal battery connection (Battery start-up)
1 - Remove the two fixing screws (59) to free
60
59
the battery connector. 2 - Push the battery connector so that you can read
"Connected".
3 - Secure the two fixing screws (59).
34008030EN/AA - Page 12
Page 13
2.3 Installation in tower position
Follow steps 1 to 3 to adjust the tower stands for the upright position.
2. Installation
1
1
ESC
150 mm
2
3
3
2
3
3
450 mm
Always keep 150 mm free space behind the UPS rear panel. The distance between the tower stands should be 450 mm.
34008030EN/AA - Page 13
Page 14
2. Installation
2.4 Installation in rack position
Adjustment of the orientation of the logo and control panel
1
2
3
UPS module rack mounting (optional rails required)
Pulsar MX RT is very heavy. To ease its rack integration, we strongly recommend to remove the battery tray as shown below:
2
4
3
3
1
1
34008030EN/AA - Page 14
x 6
1
1 - Remove the 6 fixing screws to free the main front panel bezel. 2 - Place the front panel above the UPS. 3 - Remove the 4 fixing screws on the right side to free the battery sub-module. 4 - Pull the battery sub-module slightly, then lift it to extract it.
Page 15
UPS or battery module rack mounting (optional rails required)
It is not allowed to install the UPS or battery module in a hermetically closed environment without any exchange of air.
Follow steps 1 to 4 for rack mounting the UPS onto the rails.
3
3
3
2
2. Installation
3
1
4
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.
Note for step 1: it is possible to adjust the position of both front mounting ears.
Rear bracket system (included with rail kits)
To be used if you need to move the rack enclosure with UPS already rack-mounted inside.
1
4
34008030EN/AA - Page 15
Page 16
2. Installation
2.5 Communication ports
Pulsar MX RT provides 3 communication methods that can be used simultaneously:
2 COM ports provide RS232 or USB communications using MGE UPS SYSTEMS SHUT protocol. Compatible with most
power management software applications available into the enclosed Solution Pac CD-Rom. Please, note that both ports cannot be used at the same time.
The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.The slot is compatible with any MGE UPS SYSTEMS communication card (check www.mgeups.com web site for the
complete list of compatible cards).
Connection to the RS 232 communication port
1 - Connect the RS232 (42) communications
SWITCHED
SWITCHED
GROUP 2
GROUP 1
The UPS can now communicate with various
PARALLEL
42
cable to the serial port on the computer equipment.
2 - Connect the other end of the communication cable (42) to the RS232 (13) communications port on the UPS.
MGE UPS SYSTEMS power management application software. Please note that the configuration software is included with Personal Solution Pac for Windows.
RS232 CONTACTS
BAT NO. RPO
13
Connection to the communication port by relays (14)
(see page 8)
Pin 1, 2: not used,
5432
9876
n.o.n.c. n.o. n.o. n.o.
common
1
14
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.
Pin 3: remote Power Off signal (5 to 27 V DC, 10 mA max),
Pin 4: operation on mains (not on battery),
Pin 5: user common,
Pin 6: operation on automatic by-pass,
Pin 7: low battery,
Pin 8: load protected,
Pin 9: operation on battery.
n.o.: contact normally open. n.c.: contact normally closed.
34008030EN/AA - Page 16
Output relays specifications
Voltage: 48 V DC max, Current: 2 A max, Power: 62,5 VA, 30 W.
Example: for 48 V DC, Imax=625 mA
Page 17
Remote Power Off communication port (16)
(see page 8)
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations. In order to fully de-energize devices and Pulsar MX RT with the RPO port, it is necessary:
to use a two-position switch (Normally Open or Closed contact should be held more than 1 second to be taken into account). to connect to this RPO switch a device that allows to trip all breaker(s) located upstream
RT. This can be achieved by means of a shunt trip.
(1) : If not, the output devices could be powered again through static switch when the two-position switch is released. (2) : If not, the output devices will remain powered several seconds after the RPO activation.
Please, notice that the internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Remote power off contact normally open Remote power off contact normally closed
2. Installation
(1)
and downstream
(2)
Pulsar MX
5432
6
RJ12 (6p6c)
1
6
5432
RJ12 (6p6c)
1
5 V DC to 27 V DC
5 V DC to 27 V DC
Signal:
- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.
Installation of communication cards (optional, standard with the NetPack version)
SWITCHED
1 - Remove the slot cover secured by two
GROUP 2
SWITCHED GROUP 1
It is not necessary to shutdown the UPS before installing a communications card.
screws. 2 - Insert the communications card in the slot. 3 - Secure the card with both screws.
IP= MAC=00E0D8FF855E
PARALLEL
1 2 ON
RS232 Download
RS232 CONTACTS
Reset
100 10
ETHERNET
Card Settings UPS data
BAT NO. RPO
RS232
Communication card (restricted access)
66074
34008030EN/AA - Page 17
Page 18
2. Installation
2.6 Required protective devices and cable cross-sections
Recommended upstream protection
UPS power rating Upstream circuit breaker The indicated protection ensures
4000 RT D curve - 32A
5000 RT D curve - 32A
2 poles circuit breaker
L
To UPS Normal AC source
N
G N L
discrimination for each output circuit downstream of the UPS. If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.
Recommended downstream protection
UPS power rating Downstream circuit breaker The indicated protection ensures
4000 RT Z curve - 10A
5000 RT Z curve - 10A
Required cable cross-sections
Terminal-block cable capacity: 6 mmCapacity for earthing conductor: 6 mm
discrimination for each output circuit downstream of the UPS.
C curve - 4A
C curve - 6A
2
, solid or stranded wire (maximum 8 mm2 or AWG 8).
2
, solid or stranded wire (maximum 8 mm2 or AWG 8).
If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.
34008030EN/AA - Page 18
Page 19
2.7 Connection of input/output power cables on UPS terminals
This type of connection must be carried out by qualified electrical personnel. Before carrying out any connection, check that the battery circuit breaker (19) (see page 8) and that the upstream protection
device (Normal AC source) is open ("0").
Use included insulated ferrules with stranded wires.
1 - Remove the terminal block cover (2
screws) with the included screwdriver. 2 - Insert the Normal AC cable through the cable gland (8). 3 - Connect the 3 wires to the Normal AC terminal block.
4 - Insert the output cable through the cable
8
7
1
gland (7). 5 - Connect the 3 wires to the output terminal block. 6 - Refit the terminal block cover and tighten the cable glands. 7 - Secure the terminal block cover by means of 2 screws.
2. Installation
Always connect first the earthing wire.
3
2
5
8
7
4
6
7
34008030EN/AA - Page 19
Page 20
2. Installation
2.8 Connection of IEC cables to output receptacles
1 - Connect the equipments to the UPS using
1
44
49
the cables (49). It is preferable to connect the priority
2
equipments to the four outlets (2) and the non priority equipments to the four outlets (1) that can be programmed in pairs (1 and 2). Connect any high-power devices to the 16 A outlet (3) To program shutdown of outlets (2) during operation on battery power and thus optimise the available backup time, the MGE UPS SYSTEMS communication software is required.
2 - Fit the connection securing system (44) that prevents the plugs from being pulled out accidentally.
3
34008030EN/AA - Page 20
Page 21
3.1 Initial start-up
3. Operation
1 - Check that the battery switch (60) (see
LEDs (22) is ON, LEDs (33) and (34) are
It is essential to contact our Customer Service to ensure that your system is commissionned in complete safety and to benefit from the manufacturer’s guarantee.
22
ESC
section 2.2, page 12) on top cover is connected. 2 - Set the upstream circuit breaker (not included) to the
The equipments are powered via the Normal AC source, but not protected by the UPS.
Batteries are recharging, an 8 hour recharge period is necessary to get full backup time.
green.
"I" position (ON).
IO
3433
UPS personalisation
If UPS personalisation is desired, it is advised to enter the personalisation mode at this time (see the 4.4 section).
3.2 Final start-up sequence
ESC
"Personalisation"
21 2220
3- Press the
The buzzer beeps once, and after UPS internal test sequence, the LED (20) is ON.
LEDs (30), (32), (34) are green.
The equipments are protected by the UPS.
If LED (21) or (22) is ON, an alarm has occurred (see the
"I" button (29) more than 3s.
"troubleshooting" section).
343230 29
IO
34008030EN/AA - Page 21
Page 22
3. Operation
3.3 Operating modes
Normal mode
This is the standard operating mode, set by
ESC
20
default in the factory.
Under normal condition (Normal AC source available): LED (20) is ON. LEDs (30), (32), (34) are green.
The equipments are protected by the UPS.
IO
343230
Eco mode
The main advantage of the Eco mode (see
ESC
20
glossary) is that it reduces the consumption of electrical power.
Under normal condition (Normal AC source available): LED (20) is ON. LEDs (32), (34) are green.
IO
3432
If normal AC source is out of tolerance:
ESC
20 21
The equipments are supplied in ECO mode.
LEDs (20), (21) are ON. LEDs (30), (32), (34) are green.
The equipments are protected by the UPS.
IO
343230
34008030EN/AA - Page 22
Page 23
3.4 Operation on battery power
When the Normal AC source is not available, the load continues to be protected by the UPS. Power is supplied by the battery.
Transfer to battery power
3. Operation
ESC
20 21
IO
343231
LEDs (20), (21) are ON.
LEDs (31), (32), (34) are green.
The audio alarm beeps every 10 seconds.
The equipments are protected by the UPS and supplied by the battery.
The display indicates the battery remaining backup time.
Low battery warning
ESC
20 21
IO
LEDs (20), (21) are ON.
LEDs (31), (32), (34) are green.
The audio alarm beeps every 3 seconds.
The remaining battery power is low.
Shut down all applications on the connected equipment because automatic UPS shutdown is imminent.
343231
End of backup time
ESC
34
3.5 Return on Normal AC source
After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalisation) and the load is supplied again.
22
IO
LED (22) is ON.
LED (34) is red.
The audio alarm beeps continuously.
The equipments are not powered.
The UPS displays Battery low
".
"End of backup time
34008030EN/AA - Page 23
Page 24
3. Operation
3.6 UPS shutdown
22
1 - Press the
"0" button (28) more than 3s.
ESC
The buzzer beeps once, and the load is no longer protected by the UPS. It is powered via the Normal AC source. If the UPS is set in frequency converter mode, the equipments will not be powered.
If the Normal AC source is out of tolerance, the UPS will generate a 10ms output calibrated break.
2 - For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the
"0" position.
IO
34
2833
34008030EN/AA - Page 24
Page 25
4. Access to measurements and personalisation data
4.1 Display organisation
Status and Alarms
Measurements
UPS input measurements
UPS output measurements
Battery measurements
UPS Set-up
Local settings
Output settings
ON/OFF settings
Battery settings
Maintenance
Model
Alarm History
Manual batt test
Led & Buzzer test
LCM
Statistics
Operation limits
4.2 Access to measurements
Press the scroll button (24) (see section 1.3, page 9) to access measurements for voltage, current, frequency, power output and battery capacity.
4.3 Access to UPS set-up and maintenance using the control panel (23)
Press the scroll button (25) a number of
times to point the UPS set-up or Maintenance menu
Press the Enter button (27) to get access.
UPS SET-UP MAINTENANCE
ESC
23
25
27
IO
34008030EN/AA - Page 25
Page 26
4. Access to measurements and personalisation data
4.4 UPS set-up
Local settings
Function Factory setting Options
Language English French, German, Italian, Portuguese, Spanish
Date / Time Format International
(DD-MM-YYYY/HH :MM)
Date / Time Change GMT + 1
(Continental Europe)
Audible Alarm Yes No
US (MM-DD-YYYY/HH:MM AM/PM)
MM-DD-YYYY/HH :MM adjustable
Output settings
Function Factory setting Options Comments
Output Voltage 230 V 200 V / 208 V / 220 V /
240 V / 250 V
Freq Converter Disable Enable
Output Frequency 50 Hz 60 Hz User selectable under frequency-
converter mode
Eco Mode DisablE Enable See glossary
Slew Rate 1 Hz / sec. 0.5 Hz / sec.
Bypass Transfer If bypass Ac nok?
Interrupt Time 10 ms 20 ms, ...... , 200 ms Break time calibration during load
Yes No Transfer to bypass if Normal AC
source is out of tolerance
transfer on Normal AC source out of tolerance
Overload Prealarm 105 % 40 %, 50 %, 70 % Alarm if threshold is overrun
Redundancy Mode No Yes On parallel sequence : Alarm if
redundancy loss
ON/OFF settings
Function Factory setting Options Comments
Cold Start Disable Enable Start on battery
Forced Reboot Enable Disable Enables automatic restart of the
system even if Normal AC source is restored before the end of the shutdown sequence
Auto Restart Enable Disable UPS restarts automatically when
Normal AC source is restored
Energy Saving Disable Enable Automatic shutdown on battery if
output load level < 10 %
Sleep Mode Enable Disable
Remote Command Enable Disable Enables consideration of shutdown
or restart orders from software to be authorised
34008030EN/AA - Page 26
Page 27
4. Access to measurements and personalisation data
Battery settings
Function Factory setting Options Comments
Auto Battery Test Everyweek No test / everyday /
everyweek /everymonth
Low Batt Warning 20% 0 to 100% 1% increment
User Batt Settings UPS reads number of
Deep Disch Protect Yes No Protection against deep discharge.
4.5 Maintenance
Function Sub-Function Option / Display Comments
Model Power Module SN: xxxxxxxxx
Alarm History Read Description
Manual Batt Test Manual Battery Test No / Yes
Led & Buzzer Test Led & Buzzer Test No / Yes
Life Cycle Monitoring LCM Enable / Disable Life cycling monitoring alarms
From 0 to 40 Ah 5 Ah increment battery modules connected
Frame
Erase No / Yes
SOFT: xxx
NT: xxx
Date Hour
Alarm xxx
If disable, MGE UPS SYSTEMS warranty will be void
Serial number Soft version Technical level
10 alarms can be stored automatically
Statistics Auto Statistics Statistics You need to register at
Custom Statistics Reset Date ?
Operation Limits Operation Limits Automatic alarms displayed when
4.6 Personalisation using external software
Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
Solution-Pac software.
◗ Then select "Settings", "Advanced settings" and "UPS settings".
Note that only the Windows versions of the Personal Solution-Pac software offer this possibility.
Are you sure ?
www.mgeups.com/Icm to get the code and get access to free statistics
UPS is operating near the limits
34008030EN/AA - Page 27
Page 28
5. Troubleshooting
5.1 Troubleshooting LEDS (21) and (22)
If LED (21) is ON:
If LED (22) is ON:
Press the escape button (24) to stop the
LOAD PROTECTED x.xkVA / xxx% LOADED
ENVIRONMENT FAULT
SINGLE UPS
2120
22
24
the equipments are protected by the UPS but the operation is downgraded.
the equipments are no longer protected by the UPS.
audible alarm.
Note :
In case of
"MULTIPLE FAULT", press the
"Enter" button (27) and the scroll button (25)
ESC
25
27
to get access to further details. In case of section (see section 6).
"LCM WARNING", refer to LCM
5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support
LOAD PROTECTED x.xkVA / xxx% LOADED
x x x x x x x x FAULT
SINGLE UPS
ESC
Press the
Displayed details Signification Correction
NO BATTERY The battery is incorrectly connected Check battery connections
I/O BAD CONNECTION AC source is not connected to the correct
NO POWER MODULE The power sub-module is not inserted Check power sub-module connections (see
"Enter" button (27) to display the details below :
Check AC wiring
terminals
section 7.1)
34008030EN/AA - Page 28
NO BATTERY MODULE The battery sub-module is incorrectly
connected
INV THERM OVERLOAD The UPS shuts down automatically because
of a major overload.
INVERT LIMITATION Short circuit conditions on output devices Check the installation at the UPS output
Check battery connections (see section 7.2)
Check the power drawn by the connected devices and disconnect any non-priority devices.
(wiring, fault equipment)
Page 29
5. Troubleshooting
5.3 Troubleshooting requiring MGE UPS SYSTEMS after-sales support
LOAD PROTECTED x.xkVA / xxx% LOADED
x x x x x x x x FAULT
SINGLE UPS
ESC
Display Signification Correction
POWER MODULE
FAULT
BATT MODULE FAULT Battery fault detected during the battery test.
FRAME FAULT Internal chassis fault detected.
Note: In case of multiple fault, press the
Internal power sub-module fault detected. Use
Use
Use
Troubleshooting one UPS (or two UPS in parallel) with ModularEasy module:
Indication Diagnostic Correction
The equipments are no longer supplied when the manual bypass on the ModularEasy module is set on the Bypass position.
25
27
"Enter" button (27) to display details.
"Enter" button (27) to display details.
"Enter" button (27) to display details.
Call the after-sales support department. Follow the power sub-module replacement procedure (see section 7.1)
Call the after-sales support department. Follow the battery sub-module and battery module replacement procedure (see section
7.2)
Call the after-sales support department. Follow the frame replacement procedure (see section 7.1, 7.2)
"Enter" button (27) and the scroll button (25) to get access to further details.
The equipments are connected to the UPS output instead of the ModularEasy module output.
Check the wiring(s) between the UPS and the ModularEasy module (see ModularEasy install manual).
The equipments are no longer supplied when the manual bypass on the ModularEasy module is set on the Normal position.
The equipments are no longer supplied if Normal AC source fails
The wiring(s) between the UPS and the ModularEasy module is not correct.
The manual bypass on the ModularEasy module is set on the Bypass position. The wiring(s) between the UPS and the ModularEasy module is not correct.
Check the wiring(s) between the UPS and the ModularEasy module (see ModularEasy install manual).
Set the manual bypass on the ModularEasy module to the Normal position. Check the wiring(s) between the UPS and the ModularEasy module (see ModularEasy install manual).
34008030EN/AA - Page 29
Page 30
6. Life Cycle Monitoring (LCM)
6.1 Description
This function, embedded in the UPS, displays messages, on screen and communication channels, at every important stage of the UPS’s life, allowing you to:
Press the
LOAD PROTECTED x.xkVA / xxx% LOADED
LCM WARNING
SINGLE UPS
ESC
Get free offers
LCM warning details Signification
"Enter" button (27) to display LCM
warning details.
27
3 MONTHS FREE WARRANTY EXTENSION FOR PRODUCT REGISTRATION CONTACT MGE AT www.mgeups.com/lcm
FREE STATISTIC FEATURE FOR PRODUCT WEB REGISTRATION CONTACT MGE AT www.mgeups.com/lcm
Secure your installation power continuity
Anticipate maintenance actions thanks to automatically displayed warnings while displaying automatic warnings when maintenance actions need to be planned :
LCM warning details Signification
FOR A SECURED START-UP CALL MGE CONTACT MGE AT www.mgeups.com/lcm
END OF WARRANTY SOON CONTACT MGE AT www.mgeups.com/lcm
Get free offer after registration at: www.mgeups.com/lcm
Get free offer after registration at: www.mgeups.com/lcm
These statistics will allow you to have an accurate follow-up (on the display) of the major environmental parameters of your installation:
Autonomy, time with mains 2 out of tolerance, overloads number, load level
in %, Battery ambient temperature, time on inverter, time on mains 2
Entrust your product commissioning to MGE UPS SYSTEMS: MGE UPS SYSTEMS will check the installation according to local regulations, in respect of the state of the art.
Get your product warranty extension, contacting MGE UPS SYSTEMS at: www.mgeups.com/lcm
34008030EN/AA - Page 30
BATTERY CHECK RECOMMENDED CONTACT MGE AT www.mgeups.com/lcm
TECHNICAL CHECK RECOMMENDED CONTACT MGE AT www.mgeups.com/lcm
ALARM OPERATION LIMITS XXX CONTACT MGE AT www.mgeups.com/lcm
Battery is approaching its reliability end of life. Risk to reduce dramatically backup time
Wearing parts of your product must be checked
One of the following parameters is close to the limit of your product: Autonomy, time with mains 2 out of tolerance, overloads load level in %, battery environment temperature
Page 31
Reset or disable LCM
In case of any LCM messages displayed:
For temporary reset: press the escape button (24) more than 3 seconds, into Status and Alarm screen, to cancel temporary
the alarm status. The alert will be repeated twice each 30 days.
For permanent reset: press the enter button (27) more than 3 seconds, into LCM warning screen, to cancel permanently this
LCM event.
At any time: To Disable all LCM messages select Be careful: you will not be aware of any LCM events that can happen on the UPS if you disable all LCM messages.
6. Life Cycle Monitoring (LCM)
"disable all" ,into LCM menu with LCD navigation.
34008030EN/AA - Page 31
Page 32
7. Maintenance
7.1 Hot swapping the power sub-module
This operation must be carried out by qualified electrical personnel only.
This operation can be performed without interrupting the equipments.
Disconnecting the power sub-module :
1 - Remove the 6 fixing screws to free the
2
3
4
3
main front panel bezel. 2 - Place the front panel above the UPS. 3 - Remove the 4 fixing screws on the left side to free the power sub-module. 4 - Withdraw the power sub-module.
1
1
x 6
1
Reconnecting the power sub-module :
Carry out the above instructions in reverse order.
◗ Replace the faulty power sub-module by another one with same power rating (Pulsar MX 4000 or Pulsar MX 5000).
7.2 Hot swapping the battery sub-module
1 - Remove the 6 fixing screws to free the
Caution: a battery can cause electrocution and high short circuit currents.
Servicing of batteries should be performed or supervised by personel knowledgeable of batteries and the required
precautions. Keep unauthorized personel away from batteries.
Remove watches, rings, bracelets and all other metal objects from the hands and arms, Use tools with an insulated handle. When replacing batteries, replace with the same number of the BB/HR5.5-12 batteries.
This operation can be performed without interrupting the equipments.
Disconnecting the battery sub-module :
2
4
main front panel bezel. 2 - Place the front panel above the UPS. 3 - Remove the 4 fixing screws on the right side to free the battery sub-module. 4 - Pull the battery sub-module slightly, then lift it to extract it.
34008030EN/AA - Page 32
3
3
1
1
x 6
1
Page 33
7. Maintenance
Reconnecting the battery sub-module :
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS.
7.3 Maintenance on a UPS equipped with the ModularEasy MX module
Before any action on the manual bypass (61) located on the ModularEasy module front panel, always check that the
inverter is stopped (press the "0" button more than 3 seconds). The equipments should be powered via the Normal AC source, and not protected by the UPS.
The ModularEasy module makes possible to
service or even replace the UPS without
ESC
3230 29
34
TEST
6
NORMAL
TEST
1
BYPASS
NORMAL
TEST
BYPASS
3
NORMAL
BYPASS
IO
7
affecting the connected equipments (HotSwap function).
Maintenance: 1 - Set the manual bypass (61) to the Bypass
61
position. The equipments are supplied directly with Normal AC source. 2 - Check the UPS main bezel and wait the LCD stops (30 seconds). 3 - Padlock the manual bypass (61) on bypass position. 4 - The UPS can now be disconnected and replaced.
Return to normal operation:
5 - Properly wire the UPS (see section 2), and connect internal batteries. 6 - Set the manual bypass (61) to the Test position then to Normal position : the equipments are powered via the Normal AC source, but not protected by the UPS.. 7 - Push the
"I" button (29) till the buzzer
beeps. LED (20) is ON, and LEDs (30), (32) and (34) (see page 9) are green: the equipments are protected by the UPS.
Test position:
It is also possible to fully test the UPS before the manual bypass (61) is set on Normal position. To check the UPS, after step 5, follow this operating method: 6bis - Set the manual bypass (61) to the test position. 7bis - Push the
"I" button (29) till the buzzer
beeps. After UPS Internal test, LED’s (30), (32) and (22) should be ON: no failure has
been detected. To return to normal operation:
Push the "0" button (28) more than 3
seconds.
Then follow the operating method from step
6.
34008030EN/AA - Page 33
Page 34
7. Maintenance
7.4 Training centre
To fully master operation of your MGE UPS SYSTEMS product and carry out level 1 servicing, see our complete range of technical training courses, available in both French and English.
50 Hz training centre
60 Hz training centre
MGE UPS SYSTEMS 140 avenue Jean-Kuntzmann Zirst - Montbonnot St-Martin 38334 St-Ismier Cedex FRANCE
Tel. +33 (0)4 76 18 34 14 Fax +33 (0)4 76 18 45 21 training@mgeups.com www.mgepowerlearning.com (Catalogue and registration available on line)
MGE UPS SYSTEMS 1660 Scenic Avenue Costa Mesa CA 92626 USA
Tel. +1 714 557 1637 Fax +1 714 437 9072 technical.training@mgeups.com www.mgepowerlearning.com (Catalogue and registration available on line)
34008030EN/AA - Page 34
Page 35
8.1 Technical specifications
Output power 4000 VA /
Electrical supply network
Rated input voltageInput voltage rangeFrequencyPower factorLeakage current
8. Appendices
Pulsar MX 4000 Pulsar MX 5000 Pulsar MX EXB
4500 W
(3)
(1)
/
(2)
5000 VA
3600 W
Single phase 230 V
120 / 156 V to 280 V
50/60 Hz (autoselection)
> 0.99
7 mA max.
Load output
VoltageFrequencyHarmonic distortionOverload capacity
Single phase 230 V ±3%
50/60 Hz ±0,5%
< 3%
105% continuous, 110% 2min,
(4)
(5)
125% 1min, > 150% 0.5s
Battery 15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
Environment
Operating temperature rangeRelative humidityStorage temperature rangeAltitude
Noise level
20% to 90% (non-condensing)
< 45 dBA
0°C to 40°C
-25°C to 40°C
0 to 1000 m without derating
(1) If the output voltage is 200V - 250V, the output power is 4500VA / 4000W. (2) With one EXB module or more, the standard output power is 5000VA / 4000W. (3) Values for 70% / 100% of UPS output. (4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the UPS Config software. (5) Frequency-converter mode is programmable using the UPS Config software.
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
34008030EN/AA - Page 35
Page 36
8.2 Glossary
8. Appendices
Backup time Time that the connected equipments can operate on battery power.
Bypass AC source Source supplying the bypass line. The equipments can be transferred to the bypass line if an
overload occurs on the UPS output, for maintenance or in the event of a malfunction.
ECO mode Operating mode by which the equipments are supplied directly by the AC source if it is within the
tolerances defined by the user. This mode reduces the consumption of electrical power.
Equipments Devices or systems connected to the UPS output.
Frequency converter Operating mode used to convert the AC-power frequency between the UPS input and output
(50 Hz -> 60 Hz or 60 Hz -> 50 Hz).
Low-battery warning This is a battery-voltage level indicating that battery power is low and that the user must take
action in light of the imminent break in the supply of power to the load.
Manual bypass Rotary switch controlled by the user, used to connect the equipments directly to the AC source.
Transfer of the equipments to the manual bypass enables UPS maintenance without interrupting the supply of power to the connected equipments.
Normal AC source Normal source of power for the UPS.
Normal (double conversion) mode
Personalisation It is possible to modify certain UPS parameters set in the factory. Certain UPS functions can also
Programmable outlets
Relay contacts Contacts supplying information to the user in forme of signals.
UPS Uninterruptible Power System.
The normal UPS operating mode in which the AC source supplies the UPS which in turn supplies the connected equipments (after electronic double conversion).
be modified by the MGE UPS SYSTEMS power management products to better suit user needs.
These outlets can be automatically shut down during operation on battery power (shutdown time delays can be programmed with the MGE UPS SYSTEMS power management products). The UPS has two sets of two programmable outlets.
34008030EN/AA - Page 36
Page 37
34008030EN/AA - Page 37
Page 38
MGE UPS SYSTEMS T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
140, Avenue Jean Kuntzmann ZIRST - Montbonnot St Martin 38334 - Saint Ismier Cedex - France www.mgeups.com
34008030EN/AA
Loading...