MGE UPS Systems 3.5 to 21 kVA N+1 User Manual

3.5 to 21 kVA N+1
Inverter
Owner’s Manual
www.mgeups.com
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains important instructions for the S4 Inverter
Plant that must be followed during operation of the equipment.
WARNING: Opening enclosures expose hazardous voltages. Always refer
ATTENTION: L'ouverture des cabinets expose des tensions dangereuses.
Assurez-vous toujours que le service ne soit fait que par des personnes qualifiees.
WARNUNG! Das öffnen der Gehäuse legen gefährliche Spannungen bloss.
Service sollte immer nur von qualifizierten Personal durchge­führt werden.
WARNING: As standards, specifications, and designs are subject to
change, please ask for confirmation of the information given in this publication.
ATTENTION: Comme les normes, spécifications et produits peuvent chang-
er, veuillez demander confirmation des informations con­tenues dans cette publication.
WARNUNG! Normen, Spezifizierungen und Pläne unterliegen Anderungen.
Bitte verlangen Sie eine Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.
Important Safety information
3.5 to 21 kVA N+1 Inverter
page ii
..
NOTE: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica­tions. Operation of this equipment in a residential area is like­ly to cause harmful interference in which case the user will be required to correct the interference at user's own expense.
WARNING: To reduce the risk of fire or electric shock, install in a temper-
ature and humidity controlled indoor area free of conductive contaminant’s.
This equipment is intended only for installations in a RESTRICTED ACCESS LOCATION.
ATTENTION: Pour réduire le riske d'inccendie ou d'électrocution, installer
dans une enciente intérieure contrôlée en température et humidité et sans contaminant’s conducteurs.
Ce matériel est destiné seulement pour des installations dans un EMPLACEMENT RESTREINT d'cAccès.
WARNUNG! Um die Gefahr von Feuer und elektrischem Schock zu
reduzieren, muss das Gerät in einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfähigen Verunreinigungen, installiert werden. Dieses Gerät ist nur für die Installation an einem Ort mit eingeschränkter Zugangserlaubnis vorgesehen.
Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF STANDORT bestimmti.
WARNING: HIGH LEAKAGE CURRENT. Earth connection essential before
connecting supply.
ATTENTION: COURANT DE FUITE ELEVE. Raccordement a la terre indis-
pensable avant le raccordement au reseau.
WARNUNG! Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung
herstellen.
page iii
Owner’s Manual
3.5 to 21 kVA N+1 Inverter
page iv
This manual covers these models:
Product: Rating:
64074 7.0 kVA 120/240 Line to Neutral only 64144 14.0 kVA 120/240 Line to Neutral only 64214 21.0 kVA 120/240 Line to Neutral only
64074H 7.0 kVA 208/240 Line to Line only 64144H 14.0 kVA 208/240 Line to Line only 64214H 21.0 kVA 208/240 Line to Line only
3.5 kVA to 21 kVA Inverter Owner's Manual
For service call
1-800-523-0142 86-153460-01 C00 06/2003
Copyright © 2003 MGE UPS SYSTEMS, Inc. All rights reserved. Printed in U.S.A.
MGE UPS SYSTEMS, Inc. 1660 Scenic Avenue Costa Mesa, CA 92626
(714) 557-1636
Warranty Information
page v
Owner’s Manual
3.5 to 21 kVA N+1 Inverter Owner’s Manual
Warranty
The liability of MGE UPS SYSTEMS, Inc. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, Inc.’s factory or on the job site at MGE UPS SYSTEMS, Inc.’s option, any part or parts which are defective, including labor, for a period of 12 months from the date of purchase. The MGE UPS SYSTEMS, Inc. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS SYSTEMS, Inc. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, Inc.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, Inc. will not be liable for any damage done by unauthorized repair work, unautho­rized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God.
In no event shall the MGE UPS SYSTEMS, Inc. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS, Inc. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS SYSTEMS, Inc. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS SYSTEMS, Inc. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, Inc. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS SYSTEMS, Inc.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS SYSTEMS, Inc. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the MGE UPS SYSTEMS, Inc.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the MGE UPS SYSTEMS, Inc. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE UPS SYSTEMS, Inc., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS SYSTEMS, Inc. and which can be passed on to Purchaser.
MGE UPS SYSTEMS, Inc. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, Inc. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s speci­fications, or conforming to Purchaser’s specific design.
Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS SYSTEMS, Inc. and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, Inc. be responsible for consequential damages or for any damages except as expressly stated herein.
Service and Factory Repair - Call 1 - 800 - 523 - 0142
Direct questions about the operation, repair, or servicing of this equipment to MGE UPS SYSTEMS, Inc. Technical Support Services. Include the part number and serial number of the unit in any correspondence. Should you require factory service for your equipment, contact MGE UPS SYSTEMS, Inc. Technical Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE UPS SYSTEMS, Inc. without first obtaining an RMA.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS SYSTEMS, Inc., and represents a proprietary article in which MGE UPS SYSTEMS, Inc., retains any and all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, Inc.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, Inc. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.

Revision History

3.5 to 21 kVAN+1 Inverter Owner ’s Manual
86-153460-01
Copyright © 2003 MGE UPS SYSTEMS, Inc. All rights reserved Printed in U.S.A.
Revision: A00 ECN-002762 07/2002
B00 ECN#:002873 09/2002 C00 ECN#003170 06/2003
How To Use This Manual:
This manual is designed for ease of use and easy location of information. To quickly find the meaning of terms used within the text, look to the Glossary.
To quickly find a specific topic, look at the Table of Contents. This manual uses Note lines and icons to convey important information.
Note lines and icons come in four varieties.
WARNING: Indicates information provided to protect the User and service
personnel against safety hazards and possible equipment damage.
CAUTION: Indicates information provided to protect the User and serv-
ice personnel against possible equipment damage.
NOTE: Indicates information provided as an operating tip or an
equipment feature.
IMPORTANT: Indicates information provided as an operating instruction or
as a tip.
How To Use This Manual
3.5 to 21 kVA N+1 Inverter
page vi
CAUTION: Record All Serial Numbers
page vii
Owner’s Manual
CAUTION
RECORD ALL SERIAL NUMBERS FOR THE S4 INVERTER AND COMPONENTS. THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE. KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL NUMBERS IF SERVICE IS REQUIRED!
S4 INVERTER UNIT SERIAL NUMBER: _________________________________________
INVERTER MODULE SERIAL NUMBER: _________________________________________
RECEIVER CABINET SERIAL NUMBER: ________________________________________
ADDITIONAL MODULES SERIAL NUMBERS: __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________ __________________________ ______________________________
(This page left blank intentionally)
3.5 to 21 kVA N+1 Inverter
page viii
page c —i
Owner’s Manual
Contents
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
IMPORTANT SAFETY INSTRUCTIONS . . . . . .Inside Front Cover
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
How To Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vi
CAUTION: Record all Serial Numbers . . . . . . . . . . . . . . . . . . . .vii
Section 1 Introduction
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.1 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.2 Standard Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1.3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.3.1 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.3.2 AC Output (per module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.4 Mechanical Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.5 Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
1.5.1 Thermal Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
1.6 Safety Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
Section 2 Installation and Operation
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
2.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.1 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.1.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.1.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.2 Prerequisites to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.3 Mechanical Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
2.3.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
2.4 Wiring Connections Line To Neutral Units . . . . . . . . . . . . . . . .2-4
2.4.1 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
2.5 Input and Output Cable Connections . . . . . . . . . . . . . . . . . . . .2-4
2.5.1 AC Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Contents
Section 2 Installation and Operation (continued)
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
2.5.2 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
2.5.3 DC Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
2.5.4 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
2.5.5 AC Input/Output Voltage Selection . . . . . . . . . . . . . . . . . . . . .2-8
2.5.6 EMI Filter Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
2.6 Software Configuration Set-Up . . . . . . . . . . . . . . . . . . . . . . . . .2-9
2.6.1 Dual Processor Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
2.6.2 System Personalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.6.3 Rack kVARating ID Label . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
2.6.4 On-Line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
2.6.5 Off-Line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
2.7 Wiring Connections Line To Line Units . . . . . . . . . . . . . . . . . .2-11
2.7.1 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-11
2.8 Input and Output Cable Connections . . . . . . . . . . . . . . . . . . .2-11
2.8.1 AC Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-11
2.8.2 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-11
2.8.3 DC Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
2.8.4 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-14
2.8.5 AC Input/Output Voltage Selection . . . . . . . . . . . . . . . . . . . .2-14
2.9 Software Configuration Set-Up . . . . . . . . . . . . . . . . . . . . . . . .2-14
2.9.1 Dual Processor Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-14
2.9.2 System Personalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
2.9.3 Rack kVARating ID Label . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
2.9.4 On-Line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
2.9.5 Off-Line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
2.10 Redundant Controller Set-Up . . . . . . . . . . . . . . . . . . . . . . . . .2-16
2.10.1 Inverter Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . .2-16
2.11 Indicators and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
2.11.1 LCD Readout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
2.12 Remote Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
2.12.1 Alarm Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
2.13 Start-Up Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
2.13.1 Power-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
2.13.2 Powering Up the Inverters . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
2.13.3 De-Energizing the System . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
Contents
3.5 to 21 kVA N+1 Inverter
page c —ii
Contents
page c —iii
Owner’s Manual
Section 3 Maintenance Adjustment and Troubleshooting
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
3.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
3.1 Safety Instructions for Servicing . . . . . . . . . . . . . . . . . . . . . . . .3-2
3.2 Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
3.3 Equipment Adjustment and Calibration . . . . . . . . . . . . . . . . . . .3-3
3.4 Air Intake Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3.5 AC Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3.6 DC Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3.7 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3.8 Redundant Microprocessor
(72-153588-00) Installation/Configuration . . . . . . . . . . . . . . . .3-5
3.9 Troubleshooting and Servicing . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3.9.1 Installation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3.10 AC Output Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3.10.1 Cable Connection and Static Switch Module . . . . . . . . . . . . . .3-6
3.11 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Glossary g—1
Figures
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1 System Configurations. (N+1 = added redundancy) . . . . . . . . . . . 1-2
2-1 Installation Drawing, 7 kVA Inverter System . . . . . . . . . . . . . . . . .2-2
2-2 Front View, 7 kVA, System Component Description . . . . . . . . . . . .2-3
2-3 Line To Neutral Inverter Receiver Junction Box . . . . . . . . . . . . . . .2-5
2-3a Static Switch Section - Input and Output Wiring . . . . . . . . . . . . . . .2-6
2-4 EMI and Busbar VAC Configurations . . . . . . . . . . . . . . . . . . . . . . .2-7
2-5 Line To Neutral Setup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
2-6 Line To Line Inverter Receiver Junction Box . . . . . . . . . . . . . . . . .2-12
2-6a Static Switch Section - Input and Output Wiring . . . . . . . . . . . . . .2-13
2-7 Line To Line Setup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
2-8 Inverter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-16
2-9 S4 Inverter Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-18
3-1 Redundant Microprocessor Component Location . . . . . . . . . . . . . .3-5
Tables
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1 Inverter System Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
1-2 Inverter Module Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1-3 S4 AC Output Current Ratings (with resistive load) . . . . . . . . . . . .1-3
1-4 S4 Receiver Cabinet Mechanical Dimensions and Weights . . . . . .1-4
2-1 Line To Neutral Units Suggested Circuit Breaker Ratings . . . . . . . .2-4
2-2 Line To Neutral Units Suggested DC Circuit Breaker Ratings . . . . .2-5
2-3 Line To Line Units Suggested Circuit Breaker Ratings . . . . . . . . .2-11
2-4 Line To Line Units Suggested DC Circuit Breaker Ratings . . . . . .2-12
2-5 Alarm Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
3-1 Spare Parts and Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3-2 Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Contents
3.5 to 21 kVA N+1 Inverter
page c —iv
WARNING: An AC output will be present at the output terminals immedi-
ately when AC input is energized.
ATTENTION: La tension alternative de sortie appara ît dès la mise sous ten-
sion de l'entrée.
WARNUNG! Eine Ausgangsspannung liegt an den Ausgangsklemmen,
sobald der Netzeingang angeschlossen wird.
1.0 Scope
This manual provides technical information for installation, operation, and maintenance of MGE inverter systems series ranging from 3.5 kVAto 21 kVA. Please read this manual thoroughly before installing and operating the sys­tem. Please retain this manual for future reference.
The manual is divided into three sections:

Section 1 Introduction

This section introduces the 3.5 to 21 kVAstatic inverters, including a general description of the invert­er, its components, and specifications.
Section 2 Installation & Operation
This section describes installation of the inverters, including receiving, handling, and storage proce­dures; prerequisites to the installation; installation procedures; and start-up procedures.
Section 3 Maintenance
This section describes the maintenance and service of the S4 Inverter, including safety instructions, preventive maintenance, descriptions of replacement kits, and a troubleshooting table.
Owner’s Manual
Introduction
Introduction
page 1 — 1
1.1 General Description
This static, modular inverter system series provide stable, distortion-free AC power from a DC input source at a selectable output voltage and frequency prior to shipment, for sensitive equipment. With a built-in static transfer switch, the inverter also forms a reliable and economical part of uninterruptible power supply systems in either on­line or off-line mode. This series employed modular design to provide N+1 redundancy, and twin controller cards to double reliability. There are three distinctive parts in these tower inverter systems. The top part is a built-in mod­ule that houses the twin controller, alarm cards, LCD unit, and LED indicators. The center part is a built-in module that houses a static transfer switch, and where input and output connectors are located. It is easily recognized by a twin fan front panel. Above and below this static switch module are individual inverter modules rated 3.5 kVA/3kW each (those with single fan front panel).
S4 inverters are available in three receiver cabinet configurations housing 1 to 6 inverters, a static transfer switch console, and redundant microcontroller modules.
Figure 1-1: System Configurations. (N+1 = added redundancy).
7 kVA/3.5 kVA N+1 14 kVA/10.5 kVA N+1 21 kVA/17.5 kVA N+1
1.2 Standard Products
Consult table 1-1 below for the system(s) you are working on.
Table 1-1: Inverter System Characteristics.
Part Power Nominal Input Maximum Maximum Output Selectable
Number rating Input Voltage Input Current Amperes at selectable Output
(kVA) Voltage Range @ -40VDC output voltage of: Frequency
(VDC) (VDC) (Amperes) 120 208-240 Hz
64074/H 7 (-48) (-40 to -60) 176 58 29 50 or 60 64144/H 14 (-48) (-40 to -60) 353 116 58 50 or 60 64214/H 21 (-48) (-40 to -60) 529 174 87 50 or 60
Introduction
3.5 to 21 kVA N+1 Inverter
page 1 — 2
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
POWER MODULE
GREEN = NORMAL YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
Introduction
page 1 — 3
Owner’s Manual
Table 1-2: Inverter Module Dimensions.
Inverter Module HEIGHT (in/cm) DEPTH (in/cm) WIDTH (in/cm) WEIGHT (lb/kg)
64004-9MSK1 5.18 / 13.16 15.12 / 38.4 15.76 / 40.03 46 / 20.86
Note: Weight: Six-mod receiver = 135 lbs. (61.2 kg) 1 UPS Module = 46 lbs. (20.09 kg) Total System Weight, 21 kVAsystem = 411 lbs. (186.4 kg)
1.3 Electrical Specifications
Electrical Specifications are subject to revision without notice.
1.3.1 DC Input
Nominal: -48Vdc; Operating Range: -39.5Vdc to -57 Vdc
NOTE: An external DC circuit breaker or fuse should be used at the DC
source.
1.3.2 AC Output (per module)
Voltage: 120Vrms or 240Vrms Current: 25Arms or 12.5Arms Frequency: 60Hz or 50Hz
Table 1-3: S4 AC Output Current Ratings.
Attention: Watts rating = 85% of the VA rating at 120/240 VAC.
MAXIMUM OUTPUT RATINGS
7 KVAunit 14 KVAunit 21 KVA unit
Vout Iout Output Output Iout Output Output Iout Output Output (Vac) (A) Power VA (A) Power VA (A) Power VA
(W) (VA) (W) (VA) (W) (VA)
110 58.33 6000 6416 116.66 12000 12833 175 18000 19250 115 58.33 6000 6708 116.66 12000 13416 175 18000 20125 120 58.33 6000 7000 116.66 12000 14000 175 18000 21000 208 29.165 6000 6066 58.33 12000 12133 87.5 18000 18200 220 29.165 6000 6416 58.33 12000 12833 87.5 18000 19250 230 29.165 6000 6708 58.33 12000 13416 87.5 18000 20125 240 29.165 6000 7000 58.33 12000 14000 87.5 18000 21000 Units configured to other then 120/240VAC are derated due to current limit.
The % Load reading on the display panel is always with reference to the 120/240 Vac WATT and VA ratings.
Efficiency 85% minimum, 88% typical (on-line mode); 97% typical (off-line mode) at full kVA/Watt load. Power Factor Rated kVA is available over a power factor range of 0.6 lagging to 0.6 leading at nominal volt-
age. Watt rating should not be exceeded.
Total Harmonic Distortion Less than 1% for linear load conditions, 3% maximum for crest factor loads up to 3:1.
Line Regulation System output voltage variation, less than 1% over the DC voltage range. Load Regulation System output voltage variation, less than 1% from zero to full load at nominal DC input.
Output Frequency User-selectable, 50Hz or 60Hz. Free run frequency stability shall be within +/-0.02% of the
selected frequency.
Short Circuit Current (SCC)300% minimum of rated load current for four cycles. ASCC is defined as a current that
exceeds 150% of rated current.
Overload Capability Continuous overload up to 108% of rated VA/watts at 50°C maximum.
Transient Deviation and Recovery Within 20% of average value for any change in output current or step change in input
voltage within specified limits. Recovery within 1 millisecond from zero to full load.
EMI Emission Battery Bus less than 30dBrnc. FCC 47 CFR part 15 class A; EN 55022 class A;
CISPR 22 class A
1.4 Mechanical Specifications
Table 1-4: S4 Receiver Cabinet Mechanical Dimensions and Weights
MODEL
7 kVA 14 kVA 21 kVA
HEIGHT (in/cm) 21 / 54 31.5 / 81 42 / 107.9
DEPTH (in/cm) 18.5 / 47.5 18.5 / 47.5 18.5 / 47.5 WIDTH (in/cm) 17 / 43.7 17 / 43.7 17 / 43.7
RECEIVER WEIGHT (lb/kg) 88 / 39.9 111 / 50.3 136 / 61.7
RECEIVER + MODULES 182 / 82.6 299 / 135.6 418 / 189.6
WEIGHT (lb/kg)
RECEIVER SHIPPING 100 / 45.4 123 / 55.8 148 / 67.1
WEIGHT (lb/kg)
Introduction
3.5 to 21 kVA N+1 Inverter
page 1 — 4
Introduction
page 1 — 5
Owner’s Manual
1.5 Environmental Specifications
Operating Temperature All models operate to specifications from -5°C to +50°C (+23°F to +122°F) for alti-
tude up to 3,300 feet (1006 Meters), and -5°C to 35°C (+23°F to + 95°F) for up to 13,300 feet (4054 Meters).
Shipping Temperature -40°C to +75°C (-40°F to +192°F) for shipping; Not recommended for storage. Storage Temperature -40°C to +60°C (-40°F to +166°F). Operating Humidity 0 to 90% relative, without condensation. Operating Altitude 200 feet below to 13,300 feet (4054 Meters) above sea level. Audible Noise Less than 59 dBA per Type 2, IEC and ANSI SI.4, when measured in a 40 dBA
environment at a distance of 4 feet from any surface.
Cooling Cooling is by forced air. Air intake is through the front of the unit, exhaust out the
sides.
1.5.1 Thermal Dissipation
Heat rejection: 602.28 BTU/Hr for each rated KW of the inverter system. This is based on an inverter efficiency of 85% at full load and does not include load dissipation.
kVArating 71421 Watts 1059 2118 3177 BTU/Hr 3614 7227 10841 Est. A/C, TONS 0.301 0.602 0.903
1.6 Safety Approvals
Meets UL/CSA 60950 (listed) and European Standard EN60950.
(This page left blank intentionally.)
Introduction
3.5 to 21 kVA N+1 Inverter
page 1 — 6
IMPORTANT: Equipment is factory set to operate at 120VAC for Line to
Neutral and 240VAC for Line to Line units. Please read installation procedure to configure for Line to Neutral and 240VAC for Line to Line units other configurations.
2.0 Scope
This section describes installation of the inverters, including receiving, handling, and storage procedures, prerequi­sites to the installation, installation procedures, and start-up procedures.
2.1 Receiving
Before accepting the shipment from the freight carrier, inspect the exterior surfaces of all shipping containers or packaging used, and the equipment, for damage that may have occurred during transit. If the shipping containers or equipment shows evidence of damage, note the damage on the receiving document (bill of lading) prior to sign­ing for receipt of equipment.
ALL CLAIMS FOR SHIPPING DAMAGE MUST BE FILED DIRECTLY WITH THE CARRIER. Replacements for damaged components should be ordered through MGE UPS SYSTEMS.
2.1.1 Handling IMPORTANT: A spread bar must be used, to avoid bending the bolts or side
panels, if the S4 Inverter is to be lifted from the top using the eye-bolts.
The equipment can be lifted from the top, using the eye-bolts; however, a spreader bar must be used to avoid bend­ing the bolts or the side panels. The equipment may also be handled using a forklift or pallet mover.
2.1.2 Storage
If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location that is protected from rain, splashing water, chemical agents, etc. The equipment should be covered with a tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.
2.2 Prerequisites to Installation
An efficient installation depends on careful planning and site preparation. Installation of the equipment must be han­dled by skilled technicians and electricians familiar with the special requirements of high-voltage electrical equip­ment. The installation must comply with the requirements of the National Electrical Code (ANSI/NFPA 70, latest issue) and local codes as applicable.
We strongly recommend contracting MGE for system start-up. Do not allow unqualified personnel to handle, install, or operate MGE UPS SYSTEMS static inverter systems.
NOTE: The inverter can be mounted close to a rear wall, because there
is no rear access to the unit. All input DC, output AC, and input AC wiring to the inverter enters through the top or left side of the rack assembly. Service to the inverter rack is through the front. If a maintenance bypass unit or junction box is installed, rear access is required for this unit.
Owner’s Manual
Installation & Operation
Installation and Operation
page 2 — 1
2.3 Mechanical Mounting
The equipment can be floor mounted or rack mounted in a 19” (48.3 cm), 23” (58.4 cm), or 25” (63.5 cm) rack. Optional mounting bracket kits can be ordered for rack mounting in a 25” (63.5 cm) or 26” (66.0 cm) rack.
All receivers and inverter power modules are shipped separately from the factory. Receivers will be shipped on a pallet. These receivers can be secured to a floor or to some other permanent base using one-half inch bolts through the four holes in the base supports. The inverter modules will be shipped based on customer’s discretion on power configuration or the size of the receiver they are using. Modules will be shipped separately from exterior chassis. Refer to Figure 2-2 on page 2—3.
Figure 2-1: Installation Drawing, 7 kVA Inverter System.
Installation & Operation
3.5 to 21 kVA N+1 Inverter
page 2 — 2
FOR 1" (2.54 cm),
1-1/2" (3.81cm)
CONDUITS
8.870
(22.53 cm )
2.825 (17.18 cm)
FOR 1" (2.54 cm),
2" (5.08 cm), 3" (7.62 cm)
FOR 1/2" (1.27 cm), 3/4" (1.90 cm)
CONDUITS (2 PLACES)
2" (5.08 cm), 3" (7.62 cm)
CONDUITS
1.650 (4.19 cm)
3.250
(8.26 cm)
FOR 1" (2.54 cm),
CONDUITS
16.060
(40.80)
TOP VIEW
12.210
(31.00 cm)
FOR 1" (2.54 cm),
1-1/2" (3.81cm)
CONDUITS
8.925
(22.67 cm)
11.675
(29.65 cm)
15.775
(40.07 cm)
LEFT SIDE VIEW
Installation & Operation
page 2 — 3
Owner’s Manual
Figure 2-2: Front View, 7 kVA, System Component Description.
2.3.1 Location
The equipment is designed for installation in a protected environment. Factors to be considered in selecting a loca­tion include ventilation, temperature, humidity, and accessibility. Install the unit in a clean, dry location with an unre­stricted air flow. The equipment is cooled by forced air. Allow at least 6 inches of air space to the sides of equip­ment for proper cooling. To comply with NEBS requirement, allow 12” (30.48 cm) to the sides when installed next to other heat generating equipment.
Alarm Panel
Cooling Fan
Assembly
3.5 kVA Inverter Module
WARNING:
DC INPUT
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
WARNING:
Disconnect AC (Mains) and DC supply before removing this cover.
Inverter on/Stand by
Disconnect AC (Mains) and DC supply before removing this cover.
!
Communications
Port
BYPASS
COM1
INVERTER
ON
!
STANDBY
Disconnect AC (Mains) and DC supply before removing this cover.
CAUTION:
Controller Status LEDs
CONTROLLERBCONTROLLER
A
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT/OPEN
STEADY = PRIMARY SOURCE
FLASHING = ALTERNATE SOURCE
STATUS
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
STATUS
STATUS
INVERTERBYPASSINVERTER
RED = FAULT
TEMPERATURE
AC RACEWAY
CAPACITOR FUSE
SCROLL
Redundant Microcontroller Panel
AC LONEUT
Primary Microcontroller
LCD Scroll Button
LCD Panel
Inverter Module Status LEDs
Static Transfer Switch Cabinet
Inverter DC
Input Switch
3.5 kVA Inverter Module
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
NOTE: Modules are shipped separately to receiver cabinet.
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
Thumb Screw
Receiver Cabinet Chasis
2.4 Wiring Connections Line to Neutral Units
Note: For Line to Line units please skip to section 2.7, page 2—10.
2.4.1 Grounding
For safety and proper operation of the unit, including maximum attenuation of electrical noise, suitable grounding is required. Aseparate grounding electrode conductor should be connected from the safety ground (GND) terminal to a nearby grounding electrode, and should be sized per National Electrical Code Article 250-94. The grounding elec­trode should be grounded structural metal, a metal water pipe, or a suitable ground rod (National Electrical Code 250-26). The grounding electrode should be as near as possible to the unit. The S4 will accommodate two 1/0 gauge wire. Customer provides grounding system.
Move the receiver cabinet to its intended location, using one of the suggested handling methods. After it is in its final position, remove the blank panels from the front of the receiver cabinet. Blank panels are supplied with the unit so as to prevent damage to the unit during shipment. Remove these blank panels, but do not discard them. Remove top cover panel on the receiver’s static switch (cover of the panel with two fans) for access to the wiring area. The connections to be made are the DC input connections, load connections, AC input connections, and optional remote alarm connections. The connection terminals and busbars are located at the static switch area, which is in the center of the receiver cabinet. For safety, the DC safety ground connection should be connected first, then DC positive (+) connection made next, then the DC negative (-) last.
2.5 Input and Output Cable Connections
2.5.1 AC Input Circuit Breaker
CAUTION: For Line to Neutral units 64074, 64144, and 64214 only.
WARNING: If utility line voltage is connected to the system, an appropri-
ately rated AC circuit breaker MUST be installed between the supplying AC source and the inverter plant. Installation must comply with local/national electrical installation requirements.
Table 2-1: Line To Neutral Units Suggested Circuit Breaker Ratings.
Inverter rating 7 kVA 14 kVA 21 kVA AC breaker rating 120VAC 80A 150A 225A
240VAC 40A 80A 125A
CAUTION: In applications with AC Input to the inverter, before connect-
ing the AC Input, remove the green bonding Jumper wire that is connected between the Neutral (TB4) to ground. The bond­ing wire is used for applications without AC Input, in Line to Neutral units only.
Installation & Operation - Line to Neutral
3.5 to 21 kVA N+1 Inverter
page 2 — 4
Installation & Operation - Line to Neutral
page 2 — 5
Owner’s Manual
2.5.2 DC Input
Normal: -48VDC Operating Range: -39.5 VDC to -57VDC
This system is designed for battery systems with the positive terminal Earth Ground. All DC breakers are in the negative DC lines. The system DC terminals are isolated from Earth Ground.
2.5.3 DC Input Circuit Breaker
Due to tremendous amounts of short circuit current available (in excess of 1000A for as long as several minutes!) from bank(s) of batteries, that supply electrical power to inverter systems, it is extremely important to connect a properly sized DC circuit breaker at the DC input cable that feeds the inverter system. The following table is pro­vided as a guide for selecting the proper circuit breaker.
Table 2-2: Line To Neutral Units Suggested DC Circuit Breaker Ratings.
Inverter rating 7 kVA 14 kVA 21 kVA CB rating 200A 400A 600A
Figure 2-3: Line To Neutral Inverter Receiver Junction Box.
GND
N-IN
N-OUT
TB1
L-OUT
L-IN
INVERTER RECEIVER
WITH JUNCTION BOX
BACK VIEW
JUNCTION
BOX
BATTERY
(-)
BATTERY
(+)
INVERTER RECEIVER
WITH JUNCTION BOX
SIDE VIEW
Figure 2-3a: Static Switch Section - Input and Output Wiring.
Installation & Operation - Line to Neutral
3.5 to 21 kVA N+1 Inverter
page 2 — 6
STATIC SWITCH SECTION
BATTERY (+)
BATTERY (-)
IND
GND
L-OUT
L-IN
N-OUT
N-IN
GND
AC & DC CONNECTIONS
Installation & Operation - Line to Neutral
page 2 — 7
Owner’s Manual
2.5.4 Connections
All DC input connections are made through the knock-outs, located in the top or left side panel. Refer to Figure 2-
1. Make sure that the upstream source DC circuit breaker and AC circuit breaker (if applicable) supplying the invert­er are in the off (or open) position. DC input power cables should be sized such that the maximum voltage drop between inverter busbar terminals and battery terminals is less than 1.0 volt at the breaker current rating. See Table 2-2 for CB breaker rating verses kVArating. The inverter can accommodate three positive wires and three nega­tive wires up to 4/0. Two 3/8” hole lugs, compression type with hole spacing of 1” should be used. All ground con­nections should be made first, then positive (+) DC input cable should be connected, then the negative (-) connec­tion last. The DC input landings are marked (+) and (–). Insert the input DC power cable through the selected top or side panel knock-out. Connect the positive (+) cable to the lower terminal connection and the negative (–) cable to the upper terminal connection landing. The 14 kVA and 21 kVA inverter require the super flexible (fine strand) wire, which is installed with an optional Maintenance Bypass unit, and with an optional Junction Box that is mount­ed to the back side of the Inverter receiver (14kVAand 21 kVAonly). See Figure 2-3.
Figure 2-4: EMI and Busbar VAC Configurations.
AC Line Output Stud
BUSBARS
Neutral Output
Neutral Wire
110-120VAC Configuration
EMI Filter
BUSBAR
EMI Filter
Neutral Wire
220-240VAC Configuration
The utility input and output cables are connected to a screw type terminal block. Connect the ground wires first, then the neutral wires, then connect the AC input wire (if applicable) and the AC output wire. A separate, optional Maintenance Bypass unit and a Power Distribution panel (200A Square D “QO” type of circuit breakers) are avail­able.
2.5.5 AC Input/Output Voltage Selection
The inverter is preset at the factory for 120VAC input, ON-LINE, 120VAC, 60 Hz output. If the input voltage for your installation is different (220VAC to 240VAC), the following procedure MUST be followed.
In the static switch area, there is a printed circuit board mounted to the right side panel. A multi-pin connector is located on the printed circuit board, close to the static switch front panel, identified as J23. This connector has 13 pins. Its mating plug has 12 positions, with interconnecting wires. This allows the jumper plug (P13) to be installed in one of two positions. When this jumper plug is in it most forward position (closest to the front panel), the unit is set for 110-120VAC operation. Removing the plug and installing it in its rear most position selects 220-240VAC operation. Verify that this plug is in the proper position before applying any voltage to the inverter system. See Figure 2-4.
2.5.6 EMI Filter Wiring
There are two separate inverter AC output EMI filters. Each filter provides one half of the output power to the sys­tem. These filters must be connected in parallel for 110-120VAC output or connected in series for 220-240VAC out­put. There are only two wires connected to these two filters. The neutral wire, with the white band, is connected to the lower EMI filter left-hand stud. The AC output wire is connected to the upper EMI filter right-hand stud. In the 110-120VAC configuration, the left-hand studs of the EMI filters are connected together by a copper busbar strap and the two right-hand studs of the EMI filters are connected together by a busbar strap. See Figure 2-4.
To change to the 220-240VAC connection, remove the wires and busbars from the output terminals of the EMI fil­ter. Install the copper busbar between the lower EMI filter right-hand stud to the upper EMI filter left-hand stud. Re­connect the white neutral wire to the lower EMI filter left-hand stud and the AC output wire to the upper EMI filter right-hand stud. Replace the hardware (flat washer, lock washer, and nut) and tighten the 10MM nuts to the pre­scribed torque, 35.4 inch-lbs (4 Nm). Refer to the decal on the cover plate of the static switch for strap positions. Again, verify that P23 plug on the static switch printed circuit board (located on the right side panel, is in the 240VAC, rear most position before applying any voltage to the inverter system. The extra copper busbar may be discarded. Replace the top cover of the static switch and secure it with the three previously removed 6-32x1/4” Phillips head screws.
WARNING: Do not perform this procedure (under Section 2.5.6) unless
the configuration needs to be changed. The voltage selection jumper plug position must agree with the software selection. See Figure 2-4 EMI filter strapping.
Installation & Operation - Line To Neutral
3.5 to 21 kVA N+1 Inverter
page 2 — 8
Installation & Operation - Line To Neutral
page 2 — 9
Owner’s Manual
2.6 Software Configuration Set-Up
The factory default configurations of the inverter plant is: 120V, 60Hz, Utility voltage connected and Mode of oper­ation is Online. If the factory configuration is different, the inverter will ship with marking that will describe the invert­er plant configuration. Use the configuration setup program when a different configuration is required or when a new processor is installed.
A lap-top personal computer (PC) with the field service set-up software for the S4 inverter family needs to be avail­able and connected to the DB-9 connector of the display panel via the appropriate cable. In systems that do not have the redundant controller printed circuit board, there is no need to open the display panel or remove the redun­dant controller, skip the dual and redundant controller setup.
2.6.1 Dual Processor Set-Up
The following procedure should be followed for systems that contain a redundant (second) microprocessor. Using a #2 Phillips screw driver, remove the four screws securing the display panel to the receiver rack. Using the Phillips”screw driver, remove the two screws holding the microprocessor boards in place. The circuit board secur­ing bracket is also a circuit board extractor. Using this bracket, pull the top microprocessor circuit board out slight­ly so that it is disengaged from its 70 pin edge plated connector. Return the display panel back to its vertical posi­tion and install the two screws to hold the panel in position. Do not tighten the screws very much, since they will be removed again.
2.6.2 System Personalization
Before installing the power modules into the receiver rack, apply the 48 DC input voltage (44 to 56VDC). The con­troller (microprocessor) within the unit should become activated. The status indicators on the display panel should sequence through their self test mode, changing from red to yellow to green, then momentarily off in approximate­ly 4 seconds. After this, ignore all the LED displays. Using the laptop PC, call up the filed service set-up program. In the Windows menu, select the desired AC output voltage, frequency, and modes of operation. The Windows menu will appear similar to Figure 2-5.
Figure 2-5: Line To Neutral Setup Screen.
After the selections are complete, click on the Save button. The data will be sent to the appropriate address in the controllers “EEROM”. Remove the applied 48VDC to the system by turning off the main DC feed circuit breaker.
Line To Neutral Inverter Configuration
Rack kVA rating
7.0 14.0 21.0
Inverter voltage
110 115 120 220 230 240
Inverter frequency
50 hz 60 hz
Utility
Voltage connected AC Free
Mode
On-line Off-line
DC fail auto restart
x
?
Save
Cancel
2.6.3 Unit kVA Rating ID Label
For kVA rating see the inverter ID label. Use the label kVA rating, regardless of the number of inverter modules installed.
The processor will detect and display the number of modules installed and the number of modules that are “ON” and operating without fault. MGE is offering the 7, 14, and 21 kVA rating.
2.6.4 On-Line Mode
On-line mode is the mode in which the load is powered by the inverter system, not the utility. It will get clean, tran­sient free electrical power from the inverter system, which is producing the AC power from a DC power source. In the event of inverter failure, the static transfer switch will transfer the load to the utility power if available.
2.6.5 Off-Line Mode
Off-line mode is the mode in which the load is powered from the Utility power line (external AC input power). In the event of a power failure, a static transfer switch will connect the system output to the inverter and activate the invert­er so as to provide continuous power to the load with no interruptions of power to the load.
Installation & Operation - Line To Neutral
3.5 to 21 kVA N+1 Inverter
page 2 — 10
Installation & Operation - Line To Line
page 2 — 11
Owner’s Manual
2.7 Wiring Connections Line to Line Units
Note: For Line to Neutral units continue to section 2.11, page 2—17.
2.7.1 Grounding
For safety and proper operation of the unit, including maximum attenuation of electrical noise, suitable grounding is required. Aseparate grounding electrode conductor should be connected from the safety ground (GND) terminal to a nearby grounding electrode, and should be sized per National Electrical Code Article 250-94. The grounding elec­trode should be grounded structural metal, a metal water pipe, or a suitable ground rod (National Electrical Code 250-26). The grounding electrode should be as near as possible to the unit. The S4 will accommodate two 1/0 gauge wire. Customer provides grounding system.
Move the receiver cabinet to its intended location, using one of the suggested handling methods. After it is in its final position, remove the blank panels from the front of the receiver cabinet. Blank panels are supplied with the unit so as to prevent damage to the unit during shipment. Remove these blank panels, but do not discard them. Remove top cover panel on the receiver’s static switch (cover of the panel with two fans) for access to the wiring area. The connections to be made are the DC input connections, load connections, AC input connections, and optional remote alarm connections. The connection terminals and busbars are located at the static switch area, which is in the center of the receiver cabinet. For safety, the DC safety ground connection should be connected first, then DC positive (+) connection made next, then the DC negative (-) last.
2.8 Input and Output Cable Connections
2.8.1 AC Input Circuit Breaker
CAUTION: For Line to Line units 64074H, 64144H, and 64214H only.
WARNING: If utility line voltage is connected to the system, an appropri-
ately rated AC circuit breaker MUST be installed between the supplying AC source and the inverter plant. Installation must comply with local/national electrical installation requirements.
Table 2-3: Line To Line Units Suggested Circuit Breaker Ratings.
Inverter rating 7 kVA 14 kVA 21 kVA AC breaker rating 240VAC 40A 80A 125A
2.8.2 DC Input
Normal: -48VDC Operating Range: -39.5 VDC to -57VDC
This system is designed for battery systems with the positive terminal Earth Ground. All DC breakers are in the negative DC lines. The system DC terminals are isolated from Earth Ground.
2.8.3 DC Input Circuit Breaker
Due to tremendous amounts of short circuit current available (in excess of 1000A for as long as several minutes!) from bank(s) of batteries, that supply electrical power to inverter systems, it is extremely important to connect a properly sized DC circuit breaker at the DC input cable that feeds the inverter system. The following table is pro­vided as a guide for selecting the proper circuit breaker.
Table 2-4: Line To Line Units Suggested DC Circuit Breaker Ratings.
Inverter rating 7 kVA 14 kVA 21 kVA CB rating 200A 400A 600A
Figure 2-6: Inverter Receiver Junction Box, Input and Output Wiring.
Installation & Operation - Line To Line
3.5 to 21 kVA N+1 Inverter
page 2 — 12
GND
L2-IN
L2-OUT
TB1
L1-OUT
L1-IN
INVERTER RECEIVER
WITH JUNCTION BOX
BACK VIEW
JUNCTION
BOX
BATTERY
(-)
BATTERY
(+)
INVERTER RECEIVER
WITH JUNCTION BOX
SIDE VIEW
Installation & Operation - Line To Line
page 2 — 13
Owner’s Manual
Figure 2-6a: Static Switch Section - Input and Output Wiring.
STATIC SWITCH SECTION
BATTERY (+)
BATTERY (-)
GND
L1-OUT
L1-IN
L2-OUT
L2-IN
GND
AC & DC CONNECTIONS
2.8.4 Connections
All DC input connections are made through the knock-outs, located in the top or left side panel. Refer to Figure 2-
1. Make sure that the upstream source DC circuit breaker and AC circuit breaker (if applicable) supplying the invert­er are in the off (or open) position. DC input power cables should be sized such that the maximum voltage drop between inverter busbar terminals and battery terminals is less than 1.0 volt at the breaker current rating. See Table 2-4 for CB breaker rating verses kVArating. The inverter can accommodate three positive wires and three nega­tive wires up to 4/0. Two 3/8” hole lugs, compression type with hole spacing of 1” should be used. All ground con­nections should be made first, then positive (+) DC input cable should be connected, then the negative (-) connec­tion last. The DC input landings are marked (+) and (–). Insert the input DC power cable through the selected top or side panel knock-out. Connect the positive (+) cable to the lower terminal connection and the negative (–) cable to the upper terminal connection landing. The 14 kVA and 21 kVA inverter require the super flexible (fine strand) wire, which is installed with an optional Maintenance Bypass unit, and with an optional Junction Box that is mount­ed to the back side of the Inverter receiver (14kVAand 21 kVAonly). See Figure 2-6.
The utility input and output cables are connected to a screw type terminal block. Connect the ground wires first, then connect the AC input wires (if applicable) and the AC output wires. A separate, optional Maintenance Bypass unit and a Power Distribution panel (125/200A Square D “QO” type of circuit breakers) is available.
2.8.5 AC Input/Output Voltage Selection
The inverter is preset at the factory for 240VAC input, ON-LINE, 240VAC, 60 Hz output. If the input voltage for your installation is different (208VAC to 240VAC), the following procedure MUST be followed.
2.9 Software Configuration Set-Up
The factory default configurations of the inverter plant is: 240V, 60Hz, Utility voltage connected and Mode of oper­ation is Online. If the factory configuration is different the inverter plant will ship with marking that will describe the inverter plant configuration. Use the configuration setup program when a different configuration is required or when a new processor is installed.
A lap-top personal computer (PC) with the field service set-up software for the S4 inverter family needs to be avail­able and connected to the DB-9 connector of the display panel via the appropriate cable. In systems that do not have the redundant controller printed circuit board, there is no need to open the display panel or remove the redun­dant controller, skip the dual and redundant controller setup.
2.9.1 Dual Processor Set-Up
The following procedure should be followed for systems that contain a redundant (second) microprocessor. Using a #2 Phillips screw driver, remove the four screws securing the display panel to the receiver rack. Using the Phillips”screw driver, remove the two screws holding the microprocessor boards in place. The circuit board secur­ing bracket is also a circuit board extractor. Using this bracket, pull the top microprocessor circuit board out slight­ly so that it is disengaged from its 70 pin edge plated connector. Return the display panel back to its vertical posi­tion and install the two screws to hold the panel in position. Do not tighten the screws very much, since they will be removed again.
2.9.2 System Personalization
Before installing the power modules into the receiver rack, apply the 48 VDC input voltage (44 to 56VDC). The controller (microprocessor) within the unit should become activated. The status indicators on the display” panel should sequence through their self test mode, changing from red to yellow to green, then momentarily off in approx­imately 4 seconds. After this, ignore all the LED displays. Using the laptop PC, call up the filed service set-up pro­gram. In the Windows menu, select the desired inverter voltage, frequency, and modes of operation. The Windows menu will appear similar to Figure 2-7.
Installation & Operation - Line To Line
3.5 to 21 kVA N+1 Inverter
page 2 — 14
Installation & Operation - Line To Line
page 2 — 15
Owner’s Manual
Figure 2-7: Line To Line Setup Screen.
After the selections are complete, click on the Save button. The data will be sent to the appropriate address in the controllers “EEROM”. Remove the applied 48VDC to the system by turning off the main DC feed circuit breaker.
2.9.3 Unit kVA Rating ID Label
For kVA rating see the inverter ID label. Use the label kVA rating, regardless of the number of inverter modules installed.
The processor will detect and display the number of modules installed and the number of modules that are “ON” and operating without fault. MGE is offering the 7, 14, and 21 kVA rating.
2.9.4 On-Line Mode
On-line mode is the mode in which the load is powered by the inverter system, not the utility. It will get clean, tran­sient free electrical power from the inverter system, which is producing the AC power from a DC power source. In the event of inverter failure, the static transfer switch will transfer the load to the utility power if available.
2.9.5 Off-Line Mode
Off-line mode is the mode in which the load is powered from the Utility power line (external AC input power). In the event of a power failure, a static transfer switch will connect the system output to the inverter and activate the invert­er so as to provide continuous power to the load with no interruptions of power to the load.
Line To Line Inverter Configuration
x
?
Rack kVA rating
7.0 14.0 21.0
Inverter voltage
208 220 230 240
Inverter frequency
50 hz 60 hz
Save
Utility
Voltage connected
AC tree
Mode
On-line
Off-line
DC fail auto restart
Cancel
2.10 Redundant Controller Set-Up
After making sure the 48VDC power has been removed from the unit, remove the two Phillips head screws from the display panel as above. Re-install the top controller printed board that was previously partially removed. Using the circuit board retaining bracket, disengage the bottom controller board from its connector. Replace the display panel and secure it with the two Phillips head screws previously removed. Repeat steps for the second controller. When the set-up is complete, remove the 48VDC applied to the system. Again open the front display panel and reseat the bottom controller circuit board. Replace the circuit board retaining bracket and secure it in its final position using the two 6/32 Phillips head screws. Replace the display panel and secure it to the rack using the two 8/32 x 3/8” Phillips head screws. Set up is complete.
2.10.1 Inverter Module Installation
The power modules are designed to be hot swapped. However, for initial start up, all of the inverter modules should be installed. In a system where all of the module positions are not used, reinstall the previously removed blank panels in these locations. Install the inverter modules, and tighten the four thumbscrews on each module. Before turning on the main source DC circuit breaker and utility AC circuit breaker (if used), make sure that all of the inverter module cir­cuit breakers (upper left-hand corner) of each module is OFF. Also verify the ON/Stand-by switch on the display panel is in the Standby (down) position. The inverter plant usually supplies power to some type of distribution circuit break­er panel. Confirm that all of these circuit breakers (loads) are OFF before starting up the inverter. After the DC input cable, utility line cable, and output cable are properly connected and secured, the inverter system is ready to be turned ON.
Figure 2-8: Inverter Module.
ATTENTION!: Turn off the Input DC Breaker before removing the inverter
Module. After turning the inverter module off, to allow discharge of the Input capacitors, wait 3 minutes before turning the Inverter Module back “ON.
Installation & Operation
3.5 to 21 kVA N+1 Inverter
page 2 — 16
DC Breaker
3.5 kVA Inverter Module
DC INPUT
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
!
Thumbscrews (4 typical)
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
Inverter Module Status LEDs
Installation & Operation
page 2 — 17
Owner’s Manual
2.11 Indicators and Controls
There are six LED indicators divided into three groups – DS1 and DS2, DS3 and DS4, DS5 and DS6 - on the dis­play front panel. DS1 and DS2 are indicators of controller A; DS3 and DS4 are indicators for controller B; DS5 and DS6 are for output capacitors fuse indicators. Failure of output capacitors will trip output fuses, and will activate DS5 and/or DS6 indicators. See Figure 2-9.
At power-up, one of the two controller units will be up quicker than the other and will take control the system. The stand by controller LED’s will be green, toggling on/off. Consequently DS1 or DS3 will be on blinking green, sig­naling that AC Input is available and the system output is ready to be turned on, through the Power Distribution breakers.
The inverter output voltage is turned ON or to Stand-by via switch SW1 located on the left side of the LCD display panel. Pushing it up is to turn the inverter ON, and pushing it down is to turn the inverter OFF. WARNING: In the stand-by position, if AC power is applied to the AC input terminal block, AC power will be on the output of the unit. When the Inverter voltage is on, DS2 (or DS4) indicator will be on green steadily, signaling that every thing is nor­mal.
The system measurement information is displayed on the LCD display panel. Switch SW3 (scroll button, on the right side of the display panel), is pushed down (or up) to scroll the LCD’s screens for more information. Individual invert­er module has only one control, an ON/OFF circuit breaker, located at the upper left corner of the front panel. This breaker is used to energize (or de-energize) the inverter module.
Note: For initial start-up the module circuit breakers must be turned on prior to turning the system Inverter “ON”.
2.11.1 LCD Readout
The LCD unit displays two lines (out of a total of seven lines) of information at a time. Each line can be scrolled up (or down) independently by toggling the scroll switch SW3. Typical seven lines of information are shown below:
Line 1 INV: off normal Inverter off/on Line 2 BYP: static normal Static bypass on/normal operation Line 3 LOAD: 120V 100% AC Output/Load % of nominal Line 4 AC IN: 120V 60 Hz AC input voltage/frequency Line 5 DC IN: 48.0V 073.5A DC voltage/DC current Line 6 LOAD: 03000 W 025.0A Load Power (W)/Current (A) Line 7 INV: 6 of 6 60 Hz Number of good modules out of #
installed modules Operation/Frequency.
Installation & Operation
3.5 to 21 kVA N+1 Inverter
page 2 — 18
Figure 2-9: S4 Inverter Components.
Alarm Panel
Cooling Fan
Assembly
3.5 kVA Inverter Module
WARNING:
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
WARNING:
Disconnect AC (Mains) and DC supply before removing this cover.
Inverter on/Stand by
Disconnect AC (Mains) and DC supply before removing this cover.
DC INPUT
!
Communications
Port
BYPASS
COM1
INVERTER
ON
!
STANDBY
Disconnect AC (Mains) and DC supply before removing this cover.
CAUTION:
Controller Status LEDs
CONTROLLERBCONTROLLER
A
STATUS
STATUS
GREEN = NORMAL YELLOW = WARNING RED = FAULT/OPEN
STEADY = PRIMARY SOURCE
FLASHING = ALTERNATE SOURCE
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
STATUS
INVERTERBYPASSINVERTER
RED = FAULT
TEMPERATURE
AC RACEWAY
CAPACITOR FUSE
SCROLL
Redundant Microcontroller Panel
AC LONEUT
Primary Microcontroller
LCD Scroll Button
LCD Panel
Inverter Module Status LEDs
Static Transfer Switch Cabinet
Inverter DC
Input Switch
3.5 kVA Inverter Module
DC INPUT
!
WARNING!
OPEN BREAKER BEFORE
REMOVING MODULE
NOTE: Modules are shipped separately to reveiver cabinet.
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
Thumb Screw
Receiver Cabinet Chasis
Installation & Operation
page 2 — 19
Owner’s Manual
2.12 Remote Alarm
The system provides three alarm signals, namely, Utility alarm, Minor alarm, and Major alarm.
Utility alarm – Utility alarm is ON when utility input voltage is lost/out of tolerance.Minor alarm – The system sends out this signal to indicate something is not functioning properly, but invert-
er can still maintain the load. Major alarm – Whenever load is lost power and the system is energized. For alarm connection, see Table 2-5.
2.12.1 Alarm Relays
There are three alarm relays. All relays are “form C” type, that is, the relay has a normally open and a normally closed contact set.
The Major Alarm relay will be energized when the system is operating properly, that is, power is being supplied to the load either from the Inverter or from the Utility. There are two sets of “form C” contact sets on the Major Alarm relay.
The Minor Alarm relay will be de-energized, and will be energized for the alarm condition. A minor alarm will be issued if the system is not operating properly. Such an alarm will be issued during overload, battery voltage not within specified limits, power modules over temperature and module fault.
The Utility Alarm relay will be de-energized during normal operation and will be energized for the alarm condition. This alarm will be issued if the utility voltage is not within specified limits or the input frequency is not within proper limits.
The table below shows the alarm and the non-alarm terminal block connections. This terminal block is located in the top, left side of the receiver cabinet. The small front panel must be removed to gain access to the terminal block.
Table 2-5: Alarm Connections.
J21 terminal block screw position --- 1 2 3 4 5 6 7 8 9 10 11 12
MAJOR ALARM --- X X MAJOR ALARM --- X X
No Major Alarm --- X X No Major Alarm --- X X
Minor Alarm --- X X
No Minor Alarm --- X X
Utility Alarm --- X X
No Utility Alarm --- X X
“X” indicates a short circuit between J21 terminal block points.
2.13 Start-Up Sequence
Confirm that all power modules’ ON/OFF circuit breakers are set to the OFF position. On the LCD “Display” panel, be sure inverter switch SW1 is set at STANDBY position.
2.13.1 Power-Up Procedure
Turn the main source DC input circuit breaker ON to apply 48VC to the system. The “controller” boards and LCD “Display” panels are now energized. The following message will be displayed. See Figure 2-9.
Line 1: INV: off module
Line 2: BYP: static AC LOW
If the system is equipped with two controllers, one controller will take control of the system, the other will be a back­up. Assuming “Controller A” takes control of the system, the BYPASS Status LED (DS1) will be red, Inverter Status LED (DS2) will be out, “Controller B” Bypass and Inverter LED's (DS3, DS4) will alternately blink On and Off, green for Bypass, green for Inverter. If “Controller B” takes control, its Status LED's will be as for “Controller A” above.
If an external AC power source is used, turn on the source AC circuit breaker. After about 20 seconds the LCD should display the following information:
Line 1: INV: off module Line 2: BYP: static normal
The “Status” LED's will be as above, except the “Bypass” will be green if the AC input voltage is within proper lim­its (voltage and frequency).
2.13.2 Powering Up the Inverters
DO NOT turn on the inverter switch SW1 yet! Turn the circuit breaker on each power module to the ON position. The LCD “Display” panel is still displaying the above two lines, but “module” will change to “normal”. Now, every­thing is ready and the inverter switch, SW1, can be turned ON (push-up). The “Status” LED's will be as above, except that the “Inverter” indicator that was out will now be green if the system is functioning properly. The invert­er is now supplying the power to the system. Using a voltmeter, verify that the proper voltage (110, 115, 120, 208, 220, 230, 240VAC) exist at the output terminals. Load circuit breaker may be turned ON.
2.13.3 De-Energizing the System
If the system is equipped with an AC input, turn off the main feed circuit breaker. Then turn switch SW1 to the stand­by position (push down). Next, turn all the power modules front panel circuit breakers OFF. Lastly, turn the DC input supply circuit breaker OFF.
Installation & Operation
3.5 to 21 kVA N+1 Inverter
page 2 — 20
Owner’s Manual
Maintenance Adjustment and Troubleshooting
Maintenance Adjustment and Troubleshooting
page 3 — 1
CAUTION: Troubleshooting the static inverter should be done only by
qualified electronic technicians. Connecting and disconnect­ing the input and output power conductors in the course of troubleshooting should be done in accordance with the installation instructions in Section 2 of this document. External circuit breakers are essential for the protection of the source and for safely connecting and disconnecting the input power connectors. The internal DC circuit breakers in the system are for protection of the systems internal circuits only. External circuit breakers between the AC or DC source and the system are essential for the protection of the source and for safely connecting and disconnecting the input power connectors.
ATTENTION
Le dépannage de l'inverseur statique devrait être fait seulement par les techniciens électroniques qualifiés. Relier et débrancher les conducteurs de puissance d'entrée et de sortie au cours du dépannage devraient être faits selon les instructions d'installation dans la section 2 de ce document. Les disjoncteurs externes sont essentiels pour la protection de la source et pour sans risque se relier et débrancher et les connecteurs de puissance d'entrée. Les disjoncteurs internes de C.C dans le système sont pour la protection des circuits internes de systèmes seulement. Les disjoncteurs externes entre la source à C.A. ou de C.C et le système sont essentiels pour la protection de la source et pour sans risque brancher et débrancher les connecteurs de puissance d'entrée.
VORSICHT
Fehlersuche am statischen Umformer sollte nur von qualifiziertem Elektronik-Technikern ausgeführt werden. Das Anschließen und das Trennen der Eingangs- und Ausgangsanschlußleitungen sollten in Übereinstim­mung mit den Montagevorschriften in Kapitel 2 dieses Dokumentes erfolgen. Externe Sicherungsautomaten sind für den Schutz der Quelle und für sicheres Anschließen und Trennen der Eingangsnetzes wesentlich. Die internen Gleichspannungssicerungsautomaten sind zum Schutz der internen Stromkreise der Systeme. Externe Sicherungsautomaten zwischen der Wechselspannungs­oder Gleichspannungsquelle und dem System sind für den Schutz der Quelle und für sicheres Anschließen und Trennen der Eingangsnetzstecker wesentlich.
NOTE 1: DC input power is normally from a battery system with a very high short circuit capacity. Accidental weld­ing and severe burns can be caused by errors while connecting or disconnecting these conductors.
NOTE 2: Many operation problems are due to incorrect installation or setup. Before turning the unit on, review the installation and setup instructions which are associated with your system configuration.
3.0 Scope
This section describes the maintenance and service of the S4 Inverter, including safety instructions, preventive maintenance, descriptions of replacement kits, and a troubleshooting table.
3.1 Safety Instructions for Servicing
IMPORTANT SAFETY INSTRUCTIONS FOR INVERTER SERVICING SHOULD BE PERFORMED OR SUPER­VISED BY QUALIFIED PERSONNEL ONLY.
WARNING: IMPORTANT SAFETY INSTRUCTIONS FOR INVERTER SERVICING
SHOULD BE PERFORMED OR SUPERVISED BY QUALIFIED PER­SONNEL ONLY.
WARNING: DC input power to the inverter is normally from a bank of bat-
teries with potentially high short circuit current capability. Accidental welding and severe burns are highly possible if mistake occurs during connecting or disconnecting these conductors.
WARNING: The green grounding wire at the TB1-4 to E1 ground lug needs
to be removed, If the inverter is to be attached to AC input power, instead of an AC free environment.
3.2 Preventative Maintenance
The following preventive maintenance routines should be considered as a minimum requirement. Your installation and site may require additional preventive maintenance to assure optimal performance from your installed inverter and associated equipment. These routines should be performed twice a year (more often if required). We strong­ly recommend a contract with MGE Customer Support Services for preventive and remedial maintenance.
The technician or electrician performing preventive maintenance on the equipment must read and understand thor-
oughly this manual and be familiar with the indicators, controls, and operation of the equipment. a. Isolate and de-energize the equipment for all maintenance operations. b. Ensure that the equipment is clean and free of loose dust, dirt, and debris. The exterior of the enclosures can
be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.
c. Inspect the air intake and exhaust areas in the inverter module. Verify that air flows freely through the equip-
ment. Clean the air intake and exhaust areas, and the enclosure interior, with a vacuum cleaner as required. d. Initiate the start-up procedure. e. Test the main operating sequences as applicable to your equipment configuration and installation.
3.5 to 21 kVA N+1 Inverter
page 3 — 2
Maintenance Adjustment and Troubleshooting
page 3 — 3
Owner’s Manual
3.3 Equipment Adjustment and Calibration
The equipment is factory adjusted and, normally, no further adjustments and calibration are required. However, in the course of repair, components may have to be changed that will require configuration of the equipment. These configurations should only be made by a qualified technician.

3.4 Air Intake Cleaning

Inspect the air intake and exhaust openings for blockage. Verify that air flows freely through the equipment. Clean the air intake and exhaust openings with a vacuum and a soft brush.

3.5 AC Fan Replacement

Every five years, replace the Static Switch front panel, including fans (MGE part number 64004-0SSK1). This is accomplish by removing all the DC and AC power to the unit by turning the Maintenance Bypass Switch to the MBP position.
Perform the following steps:
1. Remove the front panel from the “static switch panel (with two fans), using a #2 Phillips screw driver take out the four screws securing the panel to the receiver rack.
2. Unplug the two fan wires at the static switch printed circuit board.
3. Install the fan assembly onto the static switch, making sure to plug fan’s back into the static switch printed cir­cuit board connectors.
4. Secure the front panel in place by using the four Phillips”head screws previously removed.
5. Power up the system by switching the Maintenance Bypass Switch to SBP and to Normal.
6. Close DC Breaker and verify that the inverter is in normal mode - display panel inverter indicator should be green.
7. Verify that the Inverter output indicator on the Maintenance Bypass Switch display is “ON”.

3.6 DC Fan Replacement

Every five years, replace the DC fan in each power modules (MGE fan part number 64004-0FSK1). This is accom­plished by removing the power module from the receiver.
Perform the following steps:
1. Remove the front panel from the power module by removing the six Phillips head screws securing the front panel to the chassis, the two screws securing the top cover to the front panel (6-32” Phillips head screws), and the two screws hold the DC circuit breaker to the front panel. It should not be necessary to remove the top cover.
2. Remove the front panel, being careful to unplug the fan from the printed circuit board.
3. Observe the orientation of the fan wires and the fan guard so that it will appear like all other power module front panels. Remove the fan from the front panel by removing the four screws holding the fan, panel, and fan guard together.
4. Install the new fan in the reverse order of disassembly. When installing the front panel onto the chassis, care must be taken to ensure the three LED’s project through the front panel. Install all ten flat head screws.
5. Make sure the circuit breaker on the front panel is in its OFF position.
6. Install the inverter module back into the receiver rack.
Maintenance Adjustment and Troubleshooting

3.7 Replacement Parts

MGE offers a complete spare parts kit for each model number. Spare parts kits include the inverter modules. Parts (those included in the spare parts kit) can be ordered individually or as a complete parts kit. To order on individual part, give the full description along with the complete model number and serial number of the inverter.
Table 3-1: Spare Parts and Kits.
MGE Parts # Description
64004-L1SK1 Level 1 Spares Kit
64004-OFSK1 6 x 038-003002-0000-15A Fuse for PCB-72-153594-OX
64004-L2SK1 Level 2 Spares Kit
Level 1 + 64004-9MSK1
64004-L3SK1 Level 3 Spares Kit
Level 2+ Static Switch PCB-72-153595-00 + 64004-03SK1
64004-L3SK2 Level 3 Spares Kit for L-L receiver
Level 2+ Static Switch PCB-72-153842-00 + 64004-03SK1 64004-03SK1 LCD Display 64004-0SSK1 Static Switch Fan Assembly 64004-0FSK1 Inverter Module Fan 64004-01SK1 System Controller 64004-9MSK1 Inverter Module
3.5 to 21 kVA N+1 Inverter
page 3 — 4
Maintenance Adjustment and Troubleshooting
page 3 — 5
Owner’s Manual
3.8 Redundant Microprocessor (72-153588-00) Installation/Configuration
Follow this procedure to replace or add a microprocessor board to the S4 Inverter. Only one microprocessor can be configured at a time. To configure a microprocessor, install only that microprocessor board in the inverter receiver.
The redundant microprocessor board is factory calibrated and pre-configured. Please see the configuration on the label. If this is the desired configuration, skip steps 6 to 10.
Before installing the microprocessor, disconnect all power sources that feed the inverter. If a Maintenance Bypass Switch is installed – transfer the unit to MBP position. If no Maintenance Bypass switch is installed – Turn the inverter off (Attention: No power to the load in this case),
open the DC and AC breakers that feed the inverter.
1. Using a Phillips screwdriver, remove the four screws securing the display panel to the inverter receiver.
2. Remove the two screws securing the bracket in front of the Microprocessor board.
3. Use this bracket to pull out the old microprocessor.
4. Install the new microprocessor. Mount the Display Panel.
5. Verify that the unit is in Standby mode and the inverter modules are OFF.
6. Apply AC only to the inverter. Attention: The inverter output is powered. (Unit with Maintenance Bypass – move switch to SBP) The display should be ON.
7. Connect a PC through a RS232 cable to the communication port on the Display Panel.
8. Run the configuration setup program on the PC.
9. On the configuration screen, select the correct configuration for your unit: KVA rating, inverter voltage, inverter
frequency, Utility, Mode and Auto restart. Click on SAVE to send the configuration to the Microprocessor mem­ory. Disconnect the AC power. (Unit with Maintenance Bypass – move switch to MBP)
10. To configure a second Microprocessor, repeat steps 1, and 3 to 9. Repeat step 1. Reinstall the first
Microprocessor board.
11. Mount the bracket and the Display panel.
12. Restart the unit; follow start up instruction in the unit installation and user manual.
Figure 3-1: Redundant Microprocessor Component Location.
Maintenance Adjustment and Troubleshooting
OPEN BREAKER BEFORE
REMOVING MODULE
WARNING:
Disconnect AC (Mains) and DC supply before removing this cover.
OPEN BREAKER BEFORE
REMOVING MODULE
Disconnect AC (Mains) and DC supply before removing this cover.WARNING:
DC INPUT
!
WARNING!
DC INPUT
!
WARNING!
INVERTER
ON
STANDBY
COM1
!
CAUTION:
CONTROLLERBCONTROLLER
BYPASS
Disconnect AC (Mains) and DC supply before removing this cover.
A
STATUS
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT/OPEN
STEADY = PRIMARY SOURCE
FLASHING = ALTERNATE SOURCE
STATUS
INVERTERBYPASSINVERTER
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
POWER MODULE
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT
STATUS
TEMPERATURE
TEMPERATURE
AC RACEWAY
CAPACITOR FUSE
AC LONEUT
SCROLL
Redundant Controller Card (inserted into Slot #1)
PCB Slot #2
FUSE
AC RACEWAY
CAPACITOR
R
CONTROLLE
B
INVERTER
STANDBY
COM1
ON
!
Disconnect AC (Mains) and DC supply before removi
CAUTION:
CONTROLLE
STATUS
BYPASS
STEADY = PRIMARY SOURCE
FLASHING = ALTERNATE
R
A
INVERTER
GREEN = NORMAL
YELLOW = WARNING
RED = FAULT/OPEN
STATUS
BYPASS
SOURCE
ng this cover.
INVERTER
SCROLL
AC LO
NEUT
Primary Microcontroller Display
3.9 Troubleshooting and Servicing
Should you encounter a problem in the operation of the inverter and need MGE Systems to service your equipment, it is recommended to leave the unit in its current state. Record message (if any) and color signals on the LCD dis­play and LED indicators on the display panel, then call MGE Customer Support Services at 1-800-523-0142 for assistance. Leaving the unit in its current state will facilitate the field engineers to troubleshoot and bring your equip­ment back on line more easily. If you cannot wait, you may want to consider the following troubleshooting tips.
3.9.1 Installation Check
Often, operation problems are caused by incorrect installation or setup. Before turning the system on, review Chapter 2 for instructions pertaining to your particular system. Use the checklist below. If the system fails to oper­ate properly after being turned on, all items in this list need to be rechecked and verified to make sure things are connected correctly.
Installation Checklist: (Installed item to be verified)
Inverter System included static transfer switch DC input terminals have correct voltage polarity Utility input terminals have correct voltage connections AC output terminals voltage connections Input conductor size correct ampacity Output conductor size correct ampacity Correct output voltage selected in personalization Correct frequency selected On/Off Line Inverter is on-line Automatic or manual start is selected
3.10 AC Output Circuit Breaker
A Power Distribution Panel is available from MGE UPS SYSTEMS at a nominal cost. Order part number 6421P-9 for 14 or 21 kVAunits,
or 6210-0AD for the 7 kVA, which will accommodate up to 20/24 single-pole circuit breakers,
“Square-D” QO type.
3.10.1 Cable Connection and Static Switch Module
All input and output connection terminals are mounted inside the built-in Static Switch. It is very easy to identify this module by looking at a front panel that has twin cooling fans. The top panel can be opened with a #2 Phillips screw driver. When making connection, always double check to make sure that DC cable goes to DC busbars,
identified as (+) and (-). The utility cables go to a terminal block, for Line to Neutral units 120/240VAC line connects to TB1-2, NEUTRAL to TB1-4.
AC output is from TB1-1 (120/240VAC), NEUTRAL to TB1-3. For Line to Line units (208-240): Line 1 connects to TB1-2 and L2 to TB1-4, AC outputs: L1 connects to TB1-1 and L2 to TB1-3. One of the best ways to verify continuity is to use a DMM.
3.5 to 21 kVA N+1 Inverter
page 3 — 6
Maintenance Adjustment and Troubleshooting
page 3 — 7
Owner’s Manual
3.11 Troubleshooting Guide
After having thoroughly reexamined the installation and setup of the system, and still found it un-operational, user can follow Table 3-2 to identify a problem, its cause, and recommendations for fixing it.
Table 3-2: Troubleshooting table.
Problem Possible Cause Possible Solution
Display panel not illuminated No power to system Check AC & DC power sources. No output voltage SW1 not ON Turn SW1 ON System starts, then shuts Overload, or shorted Remove some of the load and
down almost immediately output. restart the inverter. Power module LED turn red Module faulted Reset by recycling circuit breaker Module temp. indicator on Module fan failure Replace module or cooling fan
Maintenance Adjustment and Troubleshooting
3.5 to 21 kVA N+1 Inverter
page 3 — 8
(This page left blank intentionally)
Maintenance Adjustment and T roubleshooting
Symbols Definition/Meaning @ At. / And/or. +/- Plus or Minus. Equal to or less than.
# Number. °C Degree Celsius. °F Degree Fahrenheit. Ø Phase angle. Ohm; unit of resistance. ®Trade Mark. 2nd Second. ABC Normal sequence of phase (clockwise) in three-phase power. AC or ac Alternating current, also implies root-mean-square (rms). Ambient Temp. Temperature of surrounding air. Ambient noise Acoustical noise of surrounding environment. ANSI American National Standard Institute. AWG American Wire Gauge.
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment directly to the AC-power source.
Automatic start When AC input power returns following shutdown at the end of the following return of battery backup time, UPS automatic start can be enabled or disabled. AC input power
Backup time Time that the connected equipment can operate on battery power.
Bar graph Device on the front panel indicating the percent remaining backup time or the percent load.
Battery circuit DC-power circuit breaker that protects the battery circuit. breaker
Battery test Internal UPS test on battery status.
Breaker Electrical circuit interrupter. BTU or Btu British thermal unit. Defined as the amount of heat required to raise the tempera-
ture of one pound of water by 1°F.
Owner’s Manual

Glossary

Glossary
page g — 1
BYPASS See “Static Transfer switch”. Bypass Maintenance bypass; wrap-around manual maintenance bypass using the optional bypass cir-
cuit breaker Q3BP in conjunction with circuit breaker Q4S and isolation circuit breaker Q5N. Bypass AC Input Mains 2. BYPASS mode See “off-line mode”. Carrier The company or individual responsible for delivering goods from one location to another. C Common. CB Circuit breaker. cm Centimeter.
Comm. Communication. Conduit A flexible or rigid tube enclosing electrical conductors.
Cold start See "Start on battery power".
Connection module Unit grouping the receptacles for connection to the AC-power source and the equipment.
C.S.S. Customer Support Service. Current rating The maximum current that a conductor or equipment can carry reliably without damage. dB Decibels.
DC Direct current. dBA Decibel Adjusted.
dBrnC Decibel above reference noise. DC or dc Direct current, or voltage. Digital Meter The LCD display on the front panel of inverter system.
Double conversion The power supplied to the connected equipment is completely regenerated by continuous
double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC),
then converted back (DC - AC) to AC power.
Earth ground A ground circuit that has contact with the earth. Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in
accordance with local codes and regulations. Not necessarily qualified to maintain or repair
electrical or electronic equipment. FET Field effect transistor.
Freq. Frequency. Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
Glossary
3.5 to 21 kVA N+1 Inverter
page g — 2
GND Ground (safety). Hz Hertz, frequency measurement unit, 1Hz is one cycle per second. Inverter mode See “on-line” mode. I Current. IEC International Electrotechnical Commission. IEEE Institute of Electrical and Electronic Engineers. Input branch circuit The input circuit from the building power panel to the equipment. Inverter An electrical circuit that generates an AC voltage source from a DC voltage source. IGBT Insulated gate bipolar transistors
kVA KiloVolt-Ampere; is equal to 1000 Volt-Ampere. kVAR KiloVolt-Amperes reactive. kW KiloWatt; a measure of real power, equal to 1000 watts. L Line. LCD Liquid-Crystal Display unit. LED Light Emitting Diode. Load Connected to the UPS output, such as computer systems or critical devices. Low battery shutdown The battery has reached the lowest permitted operating voltage, and the inverter has
shutdown (disconnecting the load) to protect the battery from damage due to further
discharge. Mains or Mains 1 Main AC input source. Mains 2 Bypass AC input source. mA Milliampere. MAX. Maximum. MCM Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0
AWG in diameter. M is from Roman numerical system indicating 1000. M-M Multi-Module. Module Refers to individual power inverter module. NNeutral. NC Normally close. NEC National Electrical Code. NFPA National Fire Protection Association.
Glossary
page g — 3
Owner’s Manual
NO. or No. Part number. NO Normally open. Online mode Inverter output power is the primary energy source to load. Offline mode Inverter output is off, and the load connected at the inverter output receives power from utility
line via a static transfer switch or maintenance bypass relay. OSHA Occupational Safety and Health Agency. PCA Printed circuit assembly.
PCB Printed circuit board. P.F. Power Factor.
PWM Pulse Width Modulation. Rectifier/Charger Converts the AC input voltage from the utility source into DC voltage, supplying the inverter and
regulating the charge of the battery system. SCR Silicon controlled rectifier. Shipping damage Any damage done to an article while it is in transit. S-M Single-Module. SPDT Single Pole Double Throw. SSC Static Switch Cabinet (in shared systems). Static Transfer Switch A solid state switching mechanism electronically controlled to pass AC power directly from the
utility to an output load. Sync or synch Synchronization. Technician Refers to an electronic technician qualified to maintain and repair electronic equipment. Not
necessarily qualified to install electrical wiring. Test connector DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer Support
Service technician to access programmable and diagnostic features of the system. Test/Maintenance Mode Maintenance bypass circuit breaker is closed and system output circuit breaker is open. UPS Uninterruptible power system.
VVolts. VA Vo lt amperes. VA Volt-amps, unit for apparent power measurement, equal V x I.
VAC or Vac Voltage of AC type. VDC or Vdc Voltage of DC type.
Glossary
3.5 to 21 kVA N+1 Inverter
page g — 4
Reorder form
1660 Scenic Avenue
Costa Mesa, CA 92626
to order additional copies of this document, or to report any errors, omissions, or other problems you have experienced.
NAME
COMPANY __________________________________________________________________
STREET ADDRESS ___________________________________________________________
CITY ___________________________________ STATE ___________ ZIP ______________
I would like to order ________ (quantity @ $50.00 each) additional copies of the:
3.5 to 21 kVA N+1 Inverter
Owners Manual
86-153460-01 C00
I would like to report the following problems with this document:
Use this form
www.mgeups.com
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636
Loading...